CAS SEC (Serial) Protocol for Mitsubishi UPS. Gateway
|
|
- Bonnie Jacobs
- 6 years ago
- Views:
Transcription
1 CAS SEC (Serial) Protocol for Mitsubishi UPS Modbus (RTU and TCP) and BACnet and HTML Gateway Description The SEC protocol can be used to connect to suitably enabled UPS s manufactured by Mitsubshi. This is a serial protocol using RS232. The protocol is nodeless, so only one UPS can be connected to each port of the gateway. The Gateway serves data from the Mitsubishi UPS as Modbus (RTU or TCP), BACnet, or Web (REST XML, JSON, CSV). The Gateway supports all of these options simultaneously. Use the data you want and ignore the others. The Gateway connects to the UPS, reads data and stores it internally. When a remote system requests data, this data is served in a form that is appropriate to the requesting protocol. In the event that the connection to the UPS controller is lost, or data cannot be read, the gateway can signal this to the remote data client. The gateway requires minimal configuration and can be considered a plug and play component of a system, in that it is ready to operate out of the box with the default configuration. Specifications UL and ULc approved 10/100BaseT with RJ-45 connector 1x RS232 Port 1x RS485 Port (Different Models have additional ports) 2MBytes flash memory, 8MBytes of SDRAM Power: 5-24VDC Operating Temperature: 0 to 70 C Dimensions: 4.2" x 3.25" x 1" LEDs: Link, Speed/Data, Power Page 1 of 7
2 Max Nodes Supported Gateway Mode Nodes Comments Client 1 Only 1 UPS per connection Server 0 Not supported or documented. Connection Information - Port 1: UPS Ports (Port 1 can only be used for the UPS if it is not being used for ModbusRTU) Connection type: EIA232 (RS232) Baud Rates: Driver Supports : 1200,2400,4800, 9600; 19200Baud Data Bits: Driver Supports : 7,8 Stop Bits: Driver Supports : 1,2 Parity: Hardware interface: Multidrop Capability Driver Supports : Odd, Even, None N/A No Connection Information - Port 0: Modbus RTU Server Port (May be used for Modbus if this port is not used to connect to a UPS) Connection type: RS485 (Jumper change to RS232) Baud Rates: 9600; 19200Baud Data Bits: 8 Stop Bits: 1 Parity: None Hardware interface: N/A Multidrop Capability Yes Page 2 of 7
3 Devices Supported The CAS supports configuration for connecting to the following Mitsubishi UPS systems: A C D AE A B C AB Devices Tested Device UPS Model DP-A12-1-OK 9900B Tested (FACTORY, SITE) Tested Factory Tested Site Page 3 of 7
4 Connection configurations Page 4 of 7
5 Driver Operation The driver can be configured to execute any of the commands in the supported function list. The data sent is stored internally in the Gateway and is made available to other protocols (Modbus RTU, Modbus TCP, BACnet IP and HTML). The frequency with each data set (see supported function list) is read is configurable. The driver retries on errors or timeouts. If the data cannot be read then after some configurable time it is marked as out of service. Configuration Via Web Page. Configure IP settings, Node ID s, Baud Rate and other parameters. Users can specify following: Client Mitsubishi UPS: Device Type, Data Points, Baud, Parity, Data bits, Stop bits Server ModbusTCP: ModbusRTU: BACnet: Node_ID, Port Node_ID, Baud, Parity, Data bits, Stop bits Device instance number, Device name, Port. Exception Handling If communications to the UPS are lost, then after some (configurable) time, the data values can all be set to zero, -1 or some other configurable value. This method allows the consumers of the data to know, if the values are valid. Communications functions Supported functions Not all SEC communication functions are supported. Most that report status info are provided. Those used to configure the unit are not included. Please review this list in determining whether this driver is fit for your purpose. Not all data points are available on all UPS s. Mitsubishi publish a document that details which variables are available per model. COMMAND NOM UPS Nominal Values DATA Nominal Input Voltage, Nominal Input Frequency, Nominal Output Voltage, Nominal Output Frequency, Nominal VA Rating, Nominal Output Power, Low Battery Time, Audible Alarm, Low Voltage Transfer Point, High Voltage Transfer Point, Battery Installed Date, Nominal Battery Life ST1 Status group 1 (Battery) Page 5 of 7
6 Battery Condition, Battery Status, Battery Charge, Seconds on Battery, Estimated Minutes, Estimated Charge, Battery Voltage, Battery Current, Battery Temperature ST2 Status group 2 (Input) Input Line Bads, Input Num Lines, Input Frequency 1, Input Voltage 1, Input Current 1, Input Power 1, Input Frequency 2, Input Voltage 2, Input Current 2, Input Power 2, Input Frequency 3, Input Voltage 3, Input Current 3, Input Power 3 ST3 Status group 3 (Output) Output Source, Output Frequency, Output Num Lines, Output Voltage 1, Output Current 1, Output Power 1, Output Load 1, Output Voltage 2, Output Current 2, Output Power 2, Output Load 2, Output Voltage 3, Output Current 3, Output Power 3, Output Load 3 ST4 Status group 4 (Bypass) Bypass Frequency, Bypass Num Lines, Bypass Voltage 1, Bypass Current 1, Bypass Power 1, Bypass Voltage 2, Bypass Current 2, Bypass Power 2, Bypass Voltage 3, Bypass Current 3, Bypass Power 3 ST5 Status group 5 (Alarm) Alarm Temperature, Alarm Input Bad, Alarm Output Bad, Alarm Overload, Alarm Bypass Bad, Alarm Output Off, Alarm UPS Shutdown, Alarm Charger Failure, Alarm System Off, Alarm Fan Failure, Alarm Fuse Failure, Alarm General Fault, Alarm Awaiting Power, Alarm Shutdown Pending, Alarm Shutdown Imminent The driver will not send the next message until a response has been received from the previous or until a timeout has expired. Support This driver was developed by Chipkin Automation Systems (CAS). CAS are proud to provide support for the driver. For support please call CAS at (866) Page 6 of 7
7 Revision History For Driver Doc. Date Resp Comment mat Ver. Rev. 18 Dec 2014 ACF Created Page 7 of 7
CAS Veeder TCP - TLS 300, 350, 450. Gateway
CAS-2700-03 Veeder TCP - TLS 300, 350, 450 Modbus (RTU and TCP) and BACnet and HTML Gateway Description The Veeder TCP Driver allows the Gateway to poll Veeder TLS Panel s for status, real time and configuration
More informationCAS OPW Fuel Management Systems Gateway Modbus (RTU and TCP) and BACnet IP and Web (HTML, REST, JSON, XML, CSV, COSM)
CAS-2700-40 OPW Fuel Management Systems Gateway Modbus (RTU and TCP) and BACnet IP and Web (HTML, REST, JSON, XML, CSV, COSM) Description The OPW Fuel Management Systems Gateway uses the Veeder Root TLS
More informationCAS Veeder TLS 300, 350, 450. Gateway
CAS-2700-02 Veeder TLS 300, 350, 450 (RTU and TCP) and BACnet and HTML Gateway Description The Veeder Serial Driver allows the Gateway to poll Veeder TLS Panel s for status, real time and configuration
More informationCAS Danfoss AK-SC-255 XML Interface Modbus (RTU and TCP) and BACnet and HTML Gateway
CAS-2700-15 Danfoss AK-SC-255 XML Interface Modbus (RTU and TCP) and BACnet and HTML Gateway Description The Danfoss XML Rest Driver allows the Gateway connect to a Danfoss systems and poll for real time
More informationFS Multistack Compu25 Protocol, Modbus TCP and BACnet and HTML Gateway
FS8705-18 Multistack Compu25 Protocol, Modbus TCP and BACnet and HTML Gateway Description The Compu25 protocol can be used to connect to suitably enabled legacy Multistack Inc, Chiller and Heat Pumps.
More informationChipkin Automation Systems A member of BACnet International
Chipkin Automation Systems A member of BACnet International CAS-2700-32 CAS Gateway: Inovonics DMP XR500 to BACnet- IP and Modbus-TCP Description The CAS-2700-32 Gateway connects to a daisy chained pair
More informationCAS Barrington LanSTAR to BACnet-IP
CAS-2700-54 Barrington LanSTAR to BACnet-IP Description The CAS-2700-54 Gateway translates data between a Barrington LanSTAR and BACnet-IP. The gateway connects to a Barrington LanSTAR through RS232. It
More informationCAS Modbus TCP Data Client
Toll Free: 1 866 383-1657 3381 Cambie St., #211 Vancouver, BC Canada V5Z 4R3 March 16, 2018 CAS-2500-02 CAS Modbus TCP Data Client PRODUCT DESCRIPTION Chipkin Modbus TCP Data Client is a device that connects
More informationVeederRoot to BACnet IP and Modbus (RTU and TCP) and HTML Gateway
Toll Free: 1 866 383-1657 3381 Cambie St., #211 Vancouver, BC Canada V5Z 4R3 February 09, 2018 CAS-2700-02 VeederRoot to BACnet IP and Modbus (RTU and TCP) and HTML Gateway PRODUCT DESCRIPTION Chipkin
More informationCAS Gateway 1-Wire to Modbus RTU/TCP, BACnet and HTTP
Toll Free: 1 866 383-1657 3381 Cambie St., #211 Vancouver, BC Canada V5Z 4R3 July 26, 2017 CAS-2700-26 CAS Gateway 1-Wire to Modbus RTU/TCP, BACnet and HTTP PRODUCT DESCRIPTION Chipkin 1-Wire Modbus RTU/TCP,
More informationCAS IKS Gateway (Modbus RTU/TCP and HTML) Manual
CAS-2700-42 IKS to Modbus RTU Gateway CAS 2700-42 IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS 2700-42 IKS Gateway Manual Page 1 of 34 BLANK PAGE CAS 2700-42 IKS Gateway Manual Page 2 of 34 Contents
More informationCAS & CAS UL. Modbus RTU Data Client. (Hardware and Software Solutions) Manual
CAS-2500-01 & CAS-2500-01-UL ModbusRTU Data Client (Hard and Soft Solutions) CAS 2500-01 & CAS 2500-01-UL Modbus RTU Data Client (Hardware and Software Solutions) Manual Email: dfs@chipkin.com Website:
More informationCAS Driver FS GE-TLC ( GE Total Lighting Control)
CAS Driver FS8700-108 GE-TLC ( GE Total Lighting Control) Description This serial driver allows connectivity to a GE-TLC network by providing data transfer to the RLINK device. The RLINK device is provided
More informationFieldServer Driver FS Serial Driver for Multistack Comput25 Master Controller
FieldServer Driver FS8705-18 - Serial Driver for Multistack Comput25 Master Controller Description The Compu25 protocol can be used to connect to suitably enabled legacy Multistack Inc, Chiller and Heat
More informationDoc October ProtoNode Reference Manual
Doc. 66932-001 October 2015 ProtoNode Reference Manual ii ProtoNode Reference Manual 66932-001 Table of Contents 1.0 INTRODUCTION... 1 2.0 PACKAGE COMPONENTS (CHECK-LIST)... 1 3.0 PRODUCT DESCRIPTION...
More informationisma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw
isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4
More informationModbus MS Card User manual
www.eaton.com Modbus MS Card User manual Modbus MS Card User Manual 34009048XT_EN/AB Page 1/46 Contents 1 INTRODUCTION 4 2 PRESENTATION 5 2.1 OVERVIEW 5 2.1.1 Functions 5 2.2 TECHNICAL CHARACTERISTICS
More informationMETERING/DISPLAY MANUAL
METERING/DISPLAY MANUAL 175W - 750W SINGLE PHASE Series LV EMERGENCY LIGHTING CENTRAL INVERTER Myers Power Products, Inc. 44 South Commerce Way, Bethlehem, PA 18017 1-800-526-5088 (610) 868-3500 Fax: (610)
More informationSetup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630
La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) or Fiber SCADA Interface for A12B Chargers Option 21P Option 57T Option 57U Setup Instructions This
More informationFieldServer Driver - Serial FS Fire Control Instruments - FCI 7100 Series
Driver Version: 1.01 Document Revision: 1 Description FieldServer Driver - Serial FS-8700-112 Fire Control Instruments - FCI 7100 Series The FCI 7100 Series System Control Units are manufactured by Fire
More informationModbus Register Map: Galaxy 300
Modbus Map: Galaxy 300 Notes: 1. 16-bit are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word in in n+1 n+1 (i.e. (i.e.
More informationPowerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)
Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL
More informationFS Multistack Comput25 Master Controller Serial Driver
Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8705-18 Multistack Comput25 Master Controller Serial Driver APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after
More informationMODBUS-IN. Modbus Card. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.
MODBUS-IN User & Installation Manual www.xpcc.com 2014. All rights reserved. (Rev 12/17/14) Thank you for purchasing. This manual contains instructions and warnings that should be followed during the installation,
More informationInstallation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA
DUCM DF1 Manual DUCM DF1 Installation and Programming Manual This manual describes the DUCM application for interfacing DF1 slaves to a Modbus or RNIM serial network. Effective: February 16, 2017 Niobrara
More informationCAS CAS Hobart Ground Power Modbus / BACnet / HTML Gateway
CAS-2700-01 Hobart Ground Power Modbus / BACnet / HTML Gateway CAS 2700 01 Hobart Ground Power Modbus / BACnet / HTML Gateway Chipkin Automation Systems, 3495 Cambie St- Box 211, Vancouver, BC, Canada,
More informationMXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.
MXM-50 Modbus Interface for Mitsubishi Air-Conditioning Installation and User Guide www.innon.co.uk 1. Product Overview The Black Pear MXM-50 unit allows a Modbus building management system (BMS) to monitor
More informationSENTRY HPS / HTS COMMUNICATION PROTOCOL
SENTRY HPS / HTS COMMUNICATION PROTOCOL Rev. 1.00 - October 1996-1 - The communication with Sentry.RPS uses RS232 serial line connection with: - only 3 wires TX, RX and GND; - 8 bits; - no parity; - 1
More informationPG AB Notifier NFS 3030 to Modbus RTU Protocol Converter
PG-141-100-AB Notifier NFS 3030 to Modbus RTU Protocol Converter PG-141-100-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators
More informationModbus Register Map: Galaxy 5000 & Galaxy 5500
Modbus Map: Galaxy 5000 & Galaxy 5500 Notes: 1. 16-bit registers are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word
More informationThe accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
User Manual INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
More informationThis is the procedure to use the Clone module as a serial converter: To enable communication you must set the following parameters in the drive.
AC10 Clone module 1002-00-00 There are a number of different ways in which the Clone Module can be used with AC10 drive. It can be used to Clone a drive or it can be used as a USB to serial converter to
More informationPM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features
PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging
More informationTrident and Trident X2 Digital Process and Temperature Panel Meter
Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products
More informationDNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS
DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS - OPTION 21PQ - FOR 205T BASED SYSTEMS DNP 3.0 & Modbus SCADA INTERFACE OPTION 21PQ INSTRUCTIONS FOR 205T BASED SYSTEMS CPN114830 ECN/DATE ISSUE DATE: ECN
More informationFor more information Contact with details of the application.
Eaton Corporation Telecommunications Power Solutions Email: dc.info@eaton.com www.eaton.com/telecompower Application Note AN0107 SC200 Modbus Server Last updated 20 January 2017 Applicable products SC200
More informationModbus RTU Interface For GEDE UPS
Modbus RTU Interface For GEDE UPS Version 1.2 Reference Guide g SA 6595 Riazzino (Locarno) Switzerland Telephone: +41 (0) 91/850 51 51 Fax: +41 (0) 91/850 51 44 Connectivity Technology for the digital
More informationPremium Online Series
Premium Online Series UPS backup power systems backup protection with double conversion that isolates and conditions output power for clean, consistent, reliable power features: Permanent connection to
More informationSmart Energy & Power Quality Solutions. ProData datalogger. Datalogger and Gateway
Smart Energy & Power Quality Solutions ProData datalogger Datalogger and Gateway Smart and compact: Our most universal datalogger ever saves power costs Ethernet connection Modbus-Ethernet-Gateway 32 MB
More information12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)
4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type
More informationManual# Installation Manual SDU 410. Safety Shutdown Unit
Manual# 1100641 Installation Manual SDU 410 Safety Shutdown Unit Installation Manual for SDU 410 ~~~ Safety Shutdown Unit Revision 1.0 Revised August 31, 2017 Revision history: Rev. Date Description 1.0
More informationMODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE
INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.
More informationExtra Communication Card Quick Start Guide
Extra Communication Card Quick Start Guide www.xpcc.com 2018. All rights reserved. (Rev 2/23/18) 1. Product Outlook... 3 2. Product Introduction... 3 2.2. RS232 port... 4 2.3. COMM. Slot... 4 2.4. Dry
More informationSerial Connection of HC900 Hybrid Controller to 900CS Control Station
Note: Ethernet connections will provide faster performance than RS-485 HC900 1. Remove HC900 CPU and set S2 Dip Switches for RS-485 unterminated Replace CPU & follow instructions per Installation and User
More informationA12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE
A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE OPTION 21P INSTRUCTIONS This manual is only valid for A12B units equipped with a S2A-225C control module and a S2A-383S-3X20 communications card.
More informationINSTALLATION GUIDE Maxiflex P3e CPU M1262F
INSTALLATION GUIDE Maxiflex P3e CPU M1262F Introduction This Installation Guide is intended to aid the fitment of the M1262B CPU in the field. For operating details of this product, refer to the Users
More informationMotortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision
Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803
More informationINTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx
INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box
More informationMillennium Simplicity Elite Parameter Points and Quirks
Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The
More informationPostfach 2327, Offenburg * Helmholtzstr. 13, Offenburg. Technical Data. Model protecto ER
On-line UPS-system according to DIN EN 62040-3 (VFI-SS-111) with sinus soidal output voltage in each operation mode, RS232 interface and Shutdown-Software for Windows NT/2000/XP/2003/Vista, Novell and
More informationUPS Series. features: uninterruptible power supply. what great systems are built on.
uninterruptible power supply uninterruptible power supply with energy saver design that is optimized to address the needs of A/V systems features: Pure Sine Wave technology with Automatic Voltage Regulation
More informationPG AB Omron FINS to Modbus RTU Protocol Converter
PG- 135-100-AB Omron FINS to Modbus RTU Protocol Converter PG-135-100-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to
More informationEtherSeries Modbus Gateway EMB-2 User s Guide
EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC
More informationUser Manual Revision English
Document code: MN45001_ENG Revision 2.000 Page 1 of 7 User Manual Revision 2.000 English SWD-MRTU Driver Software for ModbusRTU DLL & ActiveX version INDEX: Page INDEX 2 UPDATED DOCUMENTATION 2 REVISION
More informationAny device, including routers and hosts, is running an implementation of IP address Host
INSTRUCTION MANUAL IM471-U v0.1 EMI-10L Introduction EMI-10L converter lets you convert a serial RS485 communications port on a bus Ethernet with TCP / IP. The concepts and terms commonly used in the TCP
More informationHubbell Building Automation #LXBASM. ProtoNode LER Startup Guide
Hubbell Building Automation #LXBASM ProtoNode LER Startup Guide For Interfacing Customer Product: Hubbell Automation LX Lighting Control Panels To Building Automation Systems: BACnet MS/TP, BACnet/IP,
More informationQuick Guide. Extra Communication Card
Quick Guide Extra Communication Card Uninterruptible Power Supply System Version: 1.0 Table of Contents 1. Product Outlook... 3 2. Product Introduction... 3 2.2. RS232 port... 4 2.3. COMM. Slot... 4 2.4.
More informationSENS Setup Utility CONFIGURE CHARGERS/SYSTEMS WITH CUSTOM SETTINGS. Operation Manual
SENS Setup Utility For SENS MicroGenius and MicroCab TM Products CONFIGURE CHARGERS/SYSTEMS WITH CUSTOM SETTINGS Operation Manual SENS Part Number: 101325 Document Revision: F DCN Number: 107593 Date:
More informationATK3 I/O Module (Modbus Slave)
ATK3 I/O Module (Modbus Slave) 2011-01-13 The ATK3 I/O Module by ElectroCom Table of contents 2011-01-13...1 The ATK3 I/O Module by ElectroCom...1 1 Hardware...2 1.1 Inputs...3 1.2 Outputs...3 1.2.1 Relay...3
More informationHRM-0800 Instruction Manual
HRM-0800 Instruction Manual Table of Contents 1 Highway Addressable Remote Transducer (HART ) 4 2 General Specifications 5 3 Dimensions: 6 4 General Description 7 4.1 Introduction 7 4.2 Purpose 8 4.3 Functions
More informationHow-To. Modbus-TCP communication between CelciuX and NJ. History
History Date Version Author Description 03.10.12 1.0 pk 1 st release 04.10.12 1.1 pk Added very important notes (tips and tricks) 22.11.12 1.2 pk Minor corrections according Thomas Grootenboers HowTo_ModbusTCP_CelciuX_NJ.docx
More information900-4RL Option Board. Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914. Note
*44487080* 44487080 DANGER To avoid risk of electric shock, turn off AC power to power supply before installing or wiring option board. 900- Option Board Installation Instructions 900- Specifications Inputs
More informationtsh-700 Series User Manual
tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery
More informationSTS Web card for Upsilon/Epsilon STS (66073) STS Web card User Manual
STS Web card User Manual STS Web card for Upsilon/Epsilon STS (66073) STS Web card User Manual 34003765EN/BB Contents 1 PRESENTATION...3 1.1 OVERVIEW...3 1.2 USE IN A UPS...3 1.3 FUNCTIONS...4 1.4 TECHNICAL
More informationSC168MBM 16x8 Characters MODBUS MASTER LCD
Product Description SC168MBM is a programmable LCD that serve as MASTER RTU MODBUS device. It reads and display registers values from MODBUS Slave devices through its RS485 port. The LCD can be configured
More information3-7 Tiny Serial-to-Ethernet Device Server & Modbus Gateway
Tiny Serial-to- Device Server & Modbus Gateway - Tiny Serial-to- Device Server & Modbus Gateway tds-00 Series NEW tds-12 tds-00 series Tiny Serial-to- Device Server Features Incorporates any /422/485 serial
More informationProtoConvert Modbus RTU / Modbus TCP/IP / BACnet MSTP / BACnet IP / SNMP - Telnet (Lighting Controller) PG
ProtoConvert Modbus RTU / Modbus TCP/IP / BACnet MSTP / BACnet IP / SNMP - Telnet (Lighting Controller) PG-100-101-102-103-104-110-120 PG-100-101-102-103-104-110-120 is an embedded remote monitoring solution
More informationPC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM
PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM Modbus is a trademark of Modicon, Inc. Manual content copyright 2015 Extreme Telematics Corporation. All Rights Reserved. Ver 3.2 10/07/15
More informationModel 2000 Programmer EnSonic Display & Control Unit. Document code: M2KCNF.001
Model 2000 Programmer EnSonic Display & Control Unit Document code: 10735.M2KCNF.001 Document Model 2000 Programmer: EnSonic Display & Control Unit Document code 10735.M2KCNF.001 Date January 25, 2004
More informationWireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:
Wireless Transducer INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 2 Revision
More informationDNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions
La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U Setup Instructions This
More informationThe accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual
More informationInstruction Manual Modbus Converter Unigate-CL-RS
BA_MODBUS-Gateway_e_2011-12-16.doc, Stand: 16.12.2011 (Subject to technical changes) 1 Introduction The Unigate-CL-RS Module serves as gateway between the ExTox RS232 Interface and the bus system of the
More informationASTAT XB/XBm Remote Operator
ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery
More informationPG AA Modbus RTU to SNMP Protocol Converter
PG-100-104-AA Modbus RTU to SNMP Protocol Converter PG-100-104-AA is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to effortlessly
More informationA36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE
SCADA INTERFACE INSTRUCTIONS - OPTION 21P / 21Q - FOR A36D/TPSD SYSTEMS A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE OPTION 21P / 21Q INSTRUCTIONS This manual is only valid for A36D/TPSD Chargers equipped
More informationFS Barrington Lanstar Serial Driver
Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8705-26 Barrington Lanstar Serial Driver APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after Aug 20, 2012 2014 Chipkin
More informationProcess & Temperature Digital Panel Meter
Process & Temperature Digital Panel Meter TRIDENT PD765 4-20 ma, ± 10 V, TC & RTD Inputs NEMA 4X, IP65 Front Shallow Depth Case 3.6" Behind Panel Universal Power Supply 85-265 VAC Two Relays Option with
More informationBluetooth/RS-232 Enhanced Data Communication
Bluetooth/RS-232 Enhanced Data Communication 9650-0307-01 Rev. E The issue date or revision level for this operation guide is shown on the front cover. ZOLL, and M Series are registered trademarks, and
More informationGateway MODBUS-to-Opentherm MB-OTG Technical manual. Revision 1 SETECNA. Rel. Date 1 14/09/2016. Page: 1 di 10. Rev /09/2016
Page: 1 di 10 Gateway MODBUS-to-Opentherm MB-OTG Revision 1 Rel. Date 1 Page: 2 di 10 Table of Contents 1 Introduction... 3 2 Installation... 4 3 Integration... 5 3.1 Communication to the MODBUS, Parameter
More informationINTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL
INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:
More informationZLAN5443A. User Manual
ZLAN5443A Serial Device Server User Manual 4 ports RS232/485/422 To TCP/IP converter CopyRight 2008 Shanghai ZLAN Information Technology Co., Ltd. All right reserved Document DI: ZL DUI 20150413.1.0 1
More informationGW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway
GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway User s Manual www.icpdas.com 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one
More informationNGC-40-BRIDGE. Control and Monitoring Modules for use with the nvent Raychem NGC-40 System Installation Instructions
NGC-40-BRIDGE Control and Moniting s f use with the nvent Raychem NGC-40 System Installation Instructions B C D A DESCRIPTION The nvent RAYCHEM NGC-40-BRIDGE module provides the interface between a panel's
More informationMetasys Integrator Powerware Application (previously the Exide Application)
Application Note Issue Date 11/01/01 APPLICATION NOTE Metasys Integrator Powerware Application (previously the Exide Application) lntroduction Page Application Details Component Requirements 4 Vendor Contact
More informationMODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION
ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 02 June 2009 David Walker Initial release.
More informationInterface Module XC Modbus Protocol Converter / User Manual
Page 1 from 10 Bär Industrie-Elektronik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950 General The Interface Module XC Modbus is designed for use with the EMH LZQJ-XC and DMTZ-XC
More informationModbus Communications Board
- Modbus Communications Board (RS-485) User Manual Document No. 360-0183-01 (Revision D) Sensidyne, LP. 1000 112 th Circle N, Suite 100 St. Petersburg, Florida 33716 USA 800-451-9444 +1 727-530-3602 +1
More informationPG AB Fike Cheetah to Modbus TCP Protocol Converter
PG-139-101-AB Fike Cheetah to Modbus TCP Protocol Converter PG-139-101-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to
More informationAdvant OCS. The Compact and Cost Effective Advant Controller. Advant Controller 210. Open Control System
Advant OCS Open Control System Advant Controller 210 The Compact and Cost Effective Advant Controller Advant Controller 210 is a small, cost-effective system belonging to the Advant Controller family.
More informationGPRS/SerialGateway. GPRS/Serial Gateway. User Manual
GPRS/Serial Gateway User Manual 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...5 1.1 General Information... 5 1.2 Proper Use and Safety Conditions... 6 1.3 Connections and Micro SIM Card Placement...
More informationIntesisBox Modbus Server - Honeywell XLS 80
IntesisBox Server - Honeywell XLS 80 Gateway for integration of Honeywell XLS 80 fire panels into (RTU and TCP) enabled control systems. Integrate your Honeywell fire panels into your master device or
More informationDTSX3000 Communications(Modbus) Guide
User s Manual DTSX3000 Communications(Modbus) Guide First Edition Blank Page < Introduction > i Introduction About this Manual Thank you for purchasing the DTSX3000 Distributed Temperature Sensor. This
More informationPD765 TRIDENT. Trident Series Process & Temperature Meters.
PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) Type 4X, NEMA 4X, IP65 Front 1/8 DIN Shallow
More informationAPPLICATION NOTE. OJ-DRHX Modbus protocol OJ DRHX A DRIVES PROGRAMME DEDICATED TO ROTARY HEAT EXCHANGERS /17 (OSH) 2017 OJ Electronics A/S
APPLICATION NOTE OJ-DRHX Modbus protocol 67730 10/17 (OSH) 2017 OJ Electronics A/S OJ DRHX A DRIVES PROGRAMME DEDICATED TO ROTARY HEAT EXCHANGERS Introduction This protocol contains the Modbus addresses
More informationPOWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)
POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) A55-00017 SEC PLUS 8-10 KVA MAREKTING SPECS REV. A 9/10 8kVA, 10kVA POWERVAR Isolated On-Line UPS Specifications Index 1.0 General
More informationDPS INC. TL1 4-Port MUX. Operation Guide TABLE OF CONTENTS. Overview
DPS INC "Your Partners in Telemetry Monitoring Systems" TABLE OF CONTENTS Overview.... Functional Schematic... Typical MUX Applications... Shipping List... Installation... and SWT Buttons... LED Display
More informationFieldServer FS Toshiba UPS
FieldServer FS-8700-124 Toshiba UPS Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after August 2017. Driver Version:
More informationNETAFIM WILL NOT ACCEPT RESPONSIBILITY FOR DAMAGE RESULTING FROM THE USE OF NETAFIM'S PRODUCTS OR THE USE OF THIS MANUAL.
[Type text] COPYRIGHT 2011, NETAFIM NO PARTS OF THIS PUBLICATION MAY BE REPRODUCED, STORED IN AN AUTOMATED DATA FILE OR MADE PUBLIC IN ANY FORM OR BY ANY MEANS, WHETHER ELECTRONIC, MECHANICAL, BY PHOTOCOPYING,
More informationThe benefits are ease of set-up, more data available for the user from the drive, fast control, and state of the art technology.
APPLICATION NOTE THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT These documents are provided by our technical support department to assist others. We do not guarantee that the data
More information