Metasys Integrator Powerware Application (previously the Exide Application)

Size: px
Start display at page:

Download "Metasys Integrator Powerware Application (previously the Exide Application)"

Transcription

1 Application Note Issue Date 11/01/01 APPLICATION NOTE Metasys Integrator Powerware Application (previously the Exide Application) lntroduction Page Application Details Component Requirements 4 Vendor Contact Information 5 Design Considerations 5 Cable Connections 6 Cable Pinouts 6 Connecting the Cable 6 Metasys Integrator Setup 7 Point Mapping Table 8 Powerware UPS Points for a Generic Binary Computer Mode Application 8 Example of a Plus UPS or Plus 750 UPS Application 14 Metasys Network Setup 17 Mapping to a CS Object 17 Custom Integration Johnson Controls, Inc. 1 Code No. LIT

2 lntroduction This document explains the Metasys Integrator Powerware applications. This Powerware application note was previously known as the Metasys Integrator Exide Application Note. For information on Powerware equipment, see Powerware documentation (obtainable from a Powerware representative). Note: If you use a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator Series 00 in a two-high enclosure (EN-EWC5-0) rather than a one-high enclosure (EN-EWC1-0) as shown in the figures in this application note. Application Details The Metasys Integrator unit allows Powerware Uninterruptible Power Supply (UPS) equipment to become an integral part of the Metasys and Metasys Companion Networks. Once the Powerware equipment is connected to the Metasys N Bus via the Metasys Integrator unit, data from Powerware UPSs that support the Revision AD (or later) Binary Computer Mode (BCM) protocol is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. Each Metasys Integrator vendor port can connect to one Powerware UPS. Figure 1 shows a Powerware UPS integrated into the Metasys Network, and Figure shows a Powerware UPS integrated into the Metasys Companion Network. Metasys Integrator Powerware Application Application Note

3 um p N1 LAN Standard Network Control Unit (NCU) Metasys Integrator RS- Powerware UPS N Bus Note: Pwrware1 If you use a UPM enclosure, you must install the Metasys Integrator Series 00 in a two-high enclosure (EN-EWC5-0) rather than a one-high enclosure (EN-EWC1-0) as shown in the figures in this application note. Figure 1: Powerware and Metasys Network Integration Panel Unit Workstation Metasys Integrator RS- Powerware UPS UNT N Bus Pwrware Note: If you use a UPM enclosure, you must install the Metasys Integrator Series 00 in a two-high enclosure (EN-EWC5-0) rather than a one-high enclosure (EN-EWC1-0) as shown in the figures in this application note. Figure : Powerware and Metasys Companion Integration Metasys Integrator Powerware Application Application Note

4 Component Requirements Metasys Network Release Requirements Metasys Companion Release Requirements Vendor Component Requirements To integrate Powerware equipment, you will need the following: properly installed Powerware UPS that supports Revision AD of the Binary Computer Mode (BCM) protocol RS- cable (for connecting the UPS to the Metasys Integrator unit) Metasys Integrator unit N Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Network) portable Personal Computer (PC) for running diagnostics and downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit. cable for connecting portable PC to the Metasys Integrator unit the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on CD-ROM) This document describes the RS- cable and the vendor communication tables. Powerware documentation describes the vendor s equipment. The remaining components are described in the Metasys Network Integrator Technical Bulletin (LIT ). To integrate Powerware equipment into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release 6.0 or later Metasys Integrator software/firmware Release 7.0 or later To integrate Powerware equipment into the Metasys Companion Network, you need: Metasys Companion Release 5.0 or later Metasys Integrator software/firmware Release 7.0 or later Integration between the Metasys Integrator unit and Powerware UPS has been tested with Powerware UPSs that support Revision AD of the Binary Computer Mode (BCM) protocol. If you are unsure whether your UPS complies with the above protocol revision, call Powerware technical support for further information. Changes to this equipment or integration of Powerware products not discussed in this document require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this document. 4 Metasys Integrator Powerware Application Application Note

5 Vendor Contact Information Design Considerations Powerware Corporation 401 Spring Forest Road Raleigh, NC 7616 Phone: (800) When integrating Powerware UPS equipment, keep the following considerations in mind: Make sure all Powerware equipment is set up and running properly before attempting to integrate with Metasys or Companion Network. (The Powerware representative is responsible for proper operation of UPS equipment.) Port on the UPS should be set to the following: Mode = computer; Baud rate = 9600; Data = 8, Stop = 1; Handshaking = disabled. (The Powerware representative is responsible for setting the UPS port.) RS- cable distance between the Metasys Integrator unit and the UPS can be a maximum of 50 feet. Only the points that apply to the configuration of this particular Powerware UPS are reliable. Obtain a BCM/XCP Compliance specification from your Powerware representative, which lists the points available for your application. (Consult your Powerware representative for a list of applicable points for your particular UPS.) Metasys Integrator Powerware Application Application Note 5

6 Cable Connections Cable Pinouts Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the Powerware UPS: Vendor Port A or B on Integrator DB-9 Female RS- Connector on Powerware UPS DB-5 Male Note: Signal RD TD GND Pin 5 RS- (50 ft maximum) Pin 7 Signal TD RD GND Pwrware Some UPS connectors may be configured as Data Terminal Equipment (DTE) instead of Data Communication Equipment (DCE). In theses cases, swap pins and at the Powerware UPS. Figure : Cable Pinouts Connecting the Cable Connect the female end of the RS- cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the male end to the RS- connector on the UPS. Metasys Integrator Powerware UPS Vendor Port A or B RS- Cable RS- Port Pwrware4 Figure 4: Port-to-Port Connection 6 Metasys Integrator Powerware Application Application Note

7 Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the port setting up the network addressing The following table provides information specific to the Powerware application. For detailed procedures, see the Metasys Integrator technical bulletins. Table 1: Metasys Integrator Setup for Powerware UPS Vendor Communication Table (.VCT File) Powerware UPS EX_UPS.VCT Port Setup Baud Rate 9600 Word Length 8 Stop Bit 1 Parity None Interface RS- Network Setup Vendor Address sb 1 Timeout Value 5000 ms Poll Delay 1500 ms Performance Guide Approximate Scan Time (for a single device) Powerware UPS 8 seconds 1 The vendor address format depends on the UPS system configuration. The sb is the submodule number, and is required for all configurations. For a single-module system, enter 1 for the sb. For a multi-module system, enter the corresponding submodule number for the UPS being integrated (1 to 55). For example: Configuration Vendor Address Single-module system 1 Multi-module system 4 Metasys Integrator Powerware Application Application Note 7

8 Point Mapping Table Powerware UPS Points for a Generic Binary Computer Mode Application To get the hardware for mapping points to a Control System (CS) object (via the software model), combine the Network Point Address (NPT). For example, the hardware reference for the Bypass Frequency point is A18. Binary Data (BD) points (internal parameters) cannot be mapped to standard objects. To monitor the BDs, map them to Control System (CS) object BD attributes (which can then be mapped to standard BD The following tables show points available for mapping in the Powerware UPS. Only the points that apply to the Powerware UPS configuration are reliable. Table : Powerware UPS for a Generic Binary Computer Mode Application NPT 1 NPA Unit Description kw kva Hz Hz Hz Hz % Secs Mins DegF Inverter Average Current Phase A (Rectified) Output kilowatts Output kilovolt-ampere (kva) Output Power Factor Output Frequency Input Frequency Inverter Frequency Bypass Frequency DC Link s Battery age Percentage of Battery Left Battery Time Remaining Battery Charge Time Input s Phase A Inverter s Phase A Ambient Temperature Load Current Phase A Positive DC Link Rail age Negative DC Link Rail age Inverter AC Over age Inverter AC Under age Inverter Under or Over Frequency Bypass AC Over age Bypass AC Under age Bypass Under or Over Frequency Input AC Over age Input AC Under age Input Under or Over Frequency 1. Network Point Type. Network Point Address. Analog Input 4. Binary Input Continued on next page... 8 Metasys Integrator Powerware Application Application Note

9 NPT 1 NPA Unit Description (Cont.) Output AC Over age Output AC Under age Output Under or Over Frequency Remote Emergency Power Off Remote Go To Bypass Building Alarm 6 Building Alarm 5 Building Alarm 4 Building Alarm Building Alarm Building Alarm 1 Static Switch Over Temperature Charger Over Temperature Charger Logic Power Fail 4 Charger Over age or Current 5 Inverter Over Temperature 6 Output Overload 7 Rectifier Input Over Current 8 Inverter Input Over Current 9 DC Link Over age 0 DC Link Under age 1 Rectifier Failed Inverter Failed Battery Connector Fail 4 Bypass Breaker Fail 5 Charger Failure 6 Ramp Up Failed 7 Static Switch Failure 8 Analog Board A/D Reference Fail 9 Bypass Uncalibrated Rectifier Uncalibrated Output Uncalibrated Inverter Uncalibrated DC age Uncalibrated Output Current Uncalibrated Rectifier Current Uncalibrated Battery Current Uncalibrated 1. Network Point Type. Network Point Address. Binary Input Continued on next page... Metasys Integrator Powerware Application Application Note 9

10 NPT 1 NPA Unit Description (Cont.) Inverter On/Off Stat Failure Battery Current Limit Inverter Failure Attempts Analog Board A/D Stat Failure Output Current Over 100% Battery Ground Fault Waiting for Charger Sync Non-Volatile RAM Failure Analog Board A/D Timeout Shutdown Imminent Battery Low Utility Fail Output Short Circuit Utility Not Present 61 Full Time Charging 6 Fast Bypass Command 6 A/D Error 64 SPI Communications Error 65 Rectifier Failed Self-Test 66 Rectifier EEPROM Failure 67 Rectifier EPROM Failure 68 Input Line age Loss 69 Battery DC Over age 70 Power Supply Over Temperature 71 Power Supply Failure 7 Power Supply 5 Fault 7 Power Supply +/-1 Fault 74 Heatsink Over Temperature 75 Heatsink Temperature Sensor Failed 76 Rectifier Current Over 15% Rectifier Fault Interrupt Failed Rectifier Power Capacitor Fault Inverter Program Stack Error Inverter Control Board Failed Self-Test Inverter A/D Converter Self-Test Fail Inverter RAM Self-Test Failure Inverter EEPROM Checksum Fail Inverter EPROM Checksum Fail 1. Network Point Type. Network Point Address. Binary Input Continued on next page Metasys Integrator Powerware Application Application Note

11 NPT 1 (Cont.) NPA Unit Description 85 Inverter CPU Self-Test Failed 86 Network Not Responding 87 Front Panel Self-Test Failure 88 Node EEPROM Verification Error 89 Output AC Over age Test Failed 90 Output DC Over age 91 Input Phase Rotation Error 9 Inverter Ramp Up Test Failed 9 Inverter Off Command 94 To Bypass Command 95 Emergency Shutdown Command 96 Setup Switch Open 97 Inverter AC Over age Int 98 Inverter AC Under age Int 99 Absolute DCOV/ACOV Int 100 Phase A Current Limit 101 Phase B Current Limit 10 Phase C Current Limit 10 Bypass Not Available 104 Rectifier Breaker Open 105 Battery Contactor Open 106 Inverter Contactor Open 107 Inverter Board ACOV Int Test Fail 108 Inverter Over Temperature Trip 109 Inverter Board ACUV Int Test Fail 110 Inverter age Feedback Error 111 DC Under age Timeout 11 AC Under age Timeout 11 DC Under While Charger is Full On 114 Inverter age Bias Error 115 Rectifier Phase Rotation 116 System Interface Board Failure 117 Parallel Board Failure 118 Parallel Board Failure 119 Loss Of Load Sharing Phase A 10 Loss Of Load Sharing Phase B 11 Loss Of Load Sharing Phase C 1. Network Point Type. Network Point Address. Binary Input Continued on next page... Metasys Integrator Powerware Application Application Note 11

12 NPT 1 (Cont.) NPA Unit Description 1 DC Over age Timeout 1 Battery Totally Discharged 14 Inverter Phase Bias Error 15 Inverter age Bias Error 16 Large Charger Input Current 17 Inverter Too Low For Ramp Level 18 Loss of Redundancy 19 Loss of Sync Bus 10 Rectifier Breaker Shunt Tripped 11 Loss of Charger Sync 1 Inverter Low Level Test Timeout 1 Output Breaker Open 14 Bypass Power Loss 15 CPU ISR Error 16 System ISR Restart 17 Check Battery Flag 18 Battery Not Charged 19 >106% Overload on Phase A 140 >106% Overload on Phase B 141 >106% Overload on Phase C 14 >15% Overload on Phase A 14 >15% Overload on Phase B 144 >15% Overload on Phase C 145 >150% Overload on Phase A 146 >150% Overload on Phase B 147 >150% Overload on Phase C 148 UPS On Battery 149 UPS On Bypass 150 Load Dumped Load Power Off 151 Low Battery Shutdown 15 Software Incompatibility Detected 15 Inverter Temperature Sensor Failed 154 Waiting for Utility Input 155 Bypass Failure 156 Auto Off Command Executed 157 Battery Test Failed 158 Fuse Failure 159 Fan Failure 1. Network Point Type. Network Point Address. Binary Input Continued on next page... 1 Metasys Integrator Powerware Application Application Note

13 NPT 1 (Cont.) NPA Unit Description ADI 4 ADI ADI 1 Degree 1. Network Point Type. Network Point Address. Analog Data Float 4. Analog Data Integer Control Panel Revision Number Inverter Revision Number Rectifier Revision Number NIC Revision Number kva Rating Output s Phase-to-Phase A-B Output s Phase-to-Phase B-C Output s Phase-to-Phase C-A Input s Phase-to-Phase A-B Input s Phase-to-Phase B-C Input s Phase-to-Phase C-A Inverter s Phase-to-Phase A-B Inverter s Phase-to-Phase B-C Inverter s Phase-to-Phase C-A Bypass s Phase-to-Phase A-B Bypass s Phase-to-Phase B-C Bypass s Phase-to-Phase C-A Inverter Average Current Phase B (Rectified) Inverter Average Current Phase C (Rectified) Input Current Phase A Input Current Phase B Input Current Phase C Input Power Factor Input s Phase B Input s Phase C Inverter s Phase B Inverter s Phase C Load Current Phase B Load Current Phase C Number of CPUs Number of Output Phases Output Phase Angle Metasys Integrator Powerware Application Application Note 1

14 Powerware Ups Points for a Plus UPS or Plus 750 UPS Binary Computer Mode Application To get the hardware for mapping points to a Control System (CS) object (via the software model), combine the Network Point Address (NPT). For example, the hardware reference for the Bypass Frequency point is A18. Binary Data (BD) points (internal parameters) cannot be mapped to standard objects. To monitor the BDs, map them to Control System (CS) object BD attributes (which can then be mapped to standard BD objects). Table : Example of a Plus UPS or Plus 750 UPS Application Example (Includes only those points implemented for a Powerware Plus UPS or Plus 750 UPS) NPT 1 NPA Unit Description kw kva Hz Hz Hz Hz % Secs Output Kilowatts Output kva Output Power Factor Output Frequency Input Frequency Inverter Frequency Bypass Frequency Battery age Percentage of Battery Left Battery Time Remaining Inverter s Phase A Load Current Phase A Inverter AC Over age Inverter AC Under age Inverter Under or Over Frequency Bypass AC Over age Bypass AC Under age Bypass Under or Over Frequency Input AC Over age Input AC Under age Input Under or Over Frequency 10 Output AC Over age 11 Output AC Under age 1 Output Under or Over Frequency 15 Building Alarm 6 16 Building Alarm 5 17 Building Alarm 4 18 Building Alarm 19 Building Alarm 0 Building Alarm 1 6 Output Overload 9 DC Link Over age 0 DC Link Under age 1 Rectifier Failed Battery Connector Fail 4 Bypass Breaker Fail 1. Network Point Type. Network Point Address. Analog Input 4. Binary Input Continued on next page Metasys Integrator Powerware Application Application Note

15 NPT 1 (Cont.) NPA Unit Description Battery Current Limit Inverter Failure Attempts Output Current Over 100% Shutdown Imminent Battery Low Battery DC Over age Power Supply Failure Heatsink Over Temperature Heatsink Temperature Sensor Failed Network Not Responding Input Phase Rotation Error Emergency Shutdown Command Bypass Not Available Battery Contactor Open Inverter Contactor Open 1 Battery Totally Discharged 18 Battery Not Charged 148 UPS On Battery 149 UPS On Bypass 150 Load Dumped (Load Power Off) 159 Fan Failure 1. Network Point Type. Network Point Address. Binary Input for Inverter Fault Status Continued on next page... 0-Alarm, 1-OK Metasys Integrator Powerware Application Application Note 15

16 NPT 1 (Cont.) NPA Unit Description ADI 4 ADI ADI 1 Degree 1. Network Point Type. Network Point Address. Analog Data Float 4. Analog Data Input Control Panel Revision Number Inverter Revision Number Rectifier Revision Number NIC Revision Number kva Rating Output s Phase-to-Phase A-B Output s Phase-to-Phase B-C Output s Phase-to-Phase C-A Input s Phase-to-Phase A-B Input s Phase-to-Phase B-C Input s Phase-to-Phase C-A Bypass s Phase-to-Phase A-B Bypass s Phase-to-Phase B-C Bypass s Phase-to-Phase C-A Input Current Phase A Input Current Phase B Input Current Phase C Input Power Factor Inverter s Phase B Inverter s Phase C Load Current Phase B Load Current Phase C Number of CPUs Number of Output Phases Output Phase Angle 16 Metasys Integrator Powerware Application Application Note

17 Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator technical bulletins. This section contains details specific to the Powerware UPS application. Mapping to a CS Object Table 4: Software Model and CS Object Definition Application Software Model (on Tables and Models CD-ROM) Display Attribute (recommended) NT Command Attribute (recommended) Powerware UPS EX_UPS.DDL Output kva * Output kva * For the Network Terminal (NT) Command attribute, use the same attribute as the Display attribute. However, since the points are not commandable, you cannot command the attribute. (This must be defined because the NT Command attribute cannot be null.) Metasys Integrator Powerware Application Application Note 17

18 Custom Integration For information on integrating products which are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. Access this database from the Johnson Controls Corporate website ( by clicking Controls>Metasys Building Automation System>Products. Search the Metasys Compatible Database by application, vendor, or connect type. If you need further assistance, contact the Johnson Controls Field Support Center. Controls Group 507 E. Michigan Street P.O. Box 4 Metasys Integrator Release 1.00 Milwaukee, WI 501 Printed in U.S.A. 18 Metasys Integrator Powerware Application Application Note

Metasys Integrator Multistack Application

Metasys Integrator Multistack Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details

More information

Metasys Integrator Northern Application

Metasys Integrator Northern Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details

More information

Metasys Integrator GE Lighting Application

Metasys Integrator GE Lighting Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details

More information

Metasys Integrator Allen-Bradley Custom Application

Metasys Integrator Allen-Bradley Custom Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Allen-Bradley Custom Application Introduction Page 3 Application

More information

Metasys Integrator United Power Application

Metasys Integrator United Power Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator United Power Application lntroduction Page 3 Application Details

More information

Metasys Integrator Graham Application

Metasys Integrator Graham Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

Metasys Integrator Cutler-Hammer Application

Metasys Integrator Cutler-Hammer Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Cutler-Hammer Application Introduction Application Details Component Requirements 9 Vendor Contact Information Design Considerations

More information

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL

More information

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 02 June 2009 David Walker Initial release.

More information

Downloading Metasys Integrator 300 Series Code

Downloading Metasys Integrator 300 Series Code M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key

More information

Extended Digital Controller

Extended Digital Controller The Metasys Extended Digital Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1093 Extended Digital Controller (DX-9100) is the

More information

SENTRY HPS / HTS COMMUNICATION PROTOCOL

SENTRY HPS / HTS COMMUNICATION PROTOCOL SENTRY HPS / HTS COMMUNICATION PROTOCOL Rev. 1.00 - October 1996-1 - The communication with Sentry.RPS uses RS232 serial line connection with: - only 3 wires TX, RX and GND; - 8 bits; - no parity; - 1

More information

N2 Dialer Module. Features and Benefits

N2 Dialer Module. Features and Benefits Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1194 N2 Dialer Module The N2 Dialer Module (NDM) provides a low-cost method of connecting

More information

Lab and Central Plant Controller

Lab and Central Plant Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is

More information

XT-9100 Technical Bulletin

XT-9100 Technical Bulletin System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX

More information

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B Metasys N2 Instruction Manual VLT 6000 Adjustable Frequency Drive 12/99-6110-00 Revision B 2 Table of Contents Overview Page Introduction... 5 About this Manual... 5 References... 5 Instructions Abbreviations

More information

Metasys Integrator 300 Series Commissioning

Metasys Integrator 300 Series Commissioning Metasys Connectivity Technical Manual 629.5 Section Technical Bulletin Issue Date 0900 TECHNICAL BULLETIN 300 Series Commissioning 300 Series Commissioning...3 Introduction...3 Key Concepts...5 Related

More information

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 3 May 2010 David Walker Initial release.

More information

Modbus Register Map: Galaxy 5000 & Galaxy 5500

Modbus Register Map: Galaxy 5000 & Galaxy 5500 Modbus Map: Galaxy 5000 & Galaxy 5500 Notes: 1. 16-bit registers are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word

More information

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance

More information

Doc October ProtoNode Reference Manual

Doc October ProtoNode Reference Manual Doc. 66932-001 October 2015 ProtoNode Reference Manual ii ProtoNode Reference Manual 66932-001 Table of Contents 1.0 INTRODUCTION... 1 2.0 PACKAGE COMPONENTS (CHECK-LIST)... 1 3.0 PRODUCT DESCRIPTION...

More information

N30 Supervisory Controller Installation

N30 Supervisory Controller Installation Technical Bulletin Issue Date July 25, 2002 N30 Supervisory Controller Installation N30 Supervisory Controller Installation...2 Introduction... 2 Key Concepts... 3 Installation Site Considerations... 3

More information

Q9 ASD LOW VOLTAGE DRIVE

Q9 ASD LOW VOLTAGE DRIVE ASD LOW VOLTAGE DRIVE HVAC-MINDED, SYSTEM FRIENDLY RELIABLE Toshiba has manufactured pulse-width modulated drives since 1981 and is one of the few companies that manufactures both motors and drives in

More information

TC-9102 Terminal Controller

TC-9102 Terminal Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1095 TC-9102 Terminal Controller The TC-9102 Terminal Controller, the latest addition to the

More information

Modbus MS Card User manual

Modbus MS Card User manual www.eaton.com Modbus MS Card User manual Modbus MS Card User Manual 34009048XT_EN/AB Page 1/46 Contents 1 INTRODUCTION 4 2 PRESENTATION 5 2.1 OVERVIEW 5 2.1.1 Functions 5 2.2 TECHNICAL CHARACTERISTICS

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

For more information Contact with details of the application.

For more information Contact with details of the application. Eaton Corporation Telecommunications Power Solutions Email: dc.info@eaton.com www.eaton.com/telecompower Application Note AN0107 SC200 Modbus Server Last updated 20 January 2017 Applicable products SC200

More information

Modbus Register Map: Galaxy 300

Modbus Register Map: Galaxy 300 Modbus Map: Galaxy 300 Notes: 1. 16-bit are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word in in n+1 n+1 (i.e. (i.e.

More information

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) A55-00017 SEC PLUS 8-10 KVA MAREKTING SPECS REV. A 9/10 8kVA, 10kVA POWERVAR Isolated On-Line UPS Specifications Index 1.0 General

More information

LBC Series 3-phase PSU / Battery Charger

LBC Series 3-phase PSU / Battery Charger 3-phase PSU / Battery Charger The shelf consists of a ruggedized Battery Charger, PSU with a 3-phase input for 400 / 480 VAC (line to line) and with an output suitable for 110V battery charging. DC-DC

More information

Output Relay Latched Function Module

Output Relay Latched Function Module Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0793 Output Relay Latched Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory

More information

A66N2 Installation and Programming Manual

A66N2 Installation and Programming Manual A66N2 Manual A66N2 Installation and Programming Manual This Manual describes the A66N2 Communications Adapter for the Altivar 66 Variable Frequency Drive, its uses and set up. Effective: 14 February 2001

More information

Cardkey S300 Enclosures

Cardkey S300 Enclosures Cardkey S300 Enclosures Product Bulletin Code No. LIT-12011184 Issued March 13, 2007 Supersedes April 10, 2006 Introduction Johnson Controls S300 enclosures provide a secure tamper-resistant housing for

More information

Metasys and Companion

Metasys and Companion Metasys Network Technical Manual 636 App. Notes: Operator Devices Section Technical Bulletin Issue Date 0191 Metasys and Companion Application Page 3 Purpose of Application 3 Setting Up the Windows Terminal

More information

Comet 5-30 kva J-BUS. Installation and user manual. MGE UPS SYSTEMS D E V I P R O W E R P O L E I B U P T E R R N T N I E U T H

Comet 5-30 kva J-BUS. Installation and user manual.   MGE UPS SYSTEMS D E V I P R O W E R P O L E I B U P T E R R N T N I E U T H fault www.mgeups.com Comet 5-30 kva J-BUS XM1 XM2 Installation and user manual!! C o m e t P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H Dear User, This manual has been designed to provide

More information

Output Relay Electrical Function Module

Output Relay Electrical Function Module Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0294 Output Relay Electrical Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory

More information

For additional PowerFlex 4M data and general drive information, refer to the following publications:

For additional PowerFlex 4M data and general drive information, refer to the following publications: Product Overview Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley PowerFlex 4M AC drive is the smallest and most cost effective member of the PowerFlex

More information

Metasys N2 Communications Protocol Operating Instructions

Metasys N2 Communications Protocol Operating Instructions Metasys N2 Communications Protocol Operating Instructions TR200 BAS-SVX26A-EN November 2009 BAS-SVX26B-EN Table of Contents Safety 1-1 High voltage warning 1-1 Before commencing repair work 1-4 Special

More information

Contents. Index 35. VLT HVAC Drive Metasys N2

Contents. Index 35. VLT HVAC Drive Metasys N2 VLT HVAC Drive Metasys N Contents Contents Introduction 3 About this Manual 3 References 3 Abbreviations and Definitions 5 Network Connection 5 Hardware Set-up 5 VLT Parameters 7 Analog s (AI) 3 Binary

More information

Setup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630

Setup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630 La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) or Fiber SCADA Interface for A12B Chargers Option 21P Option 57T Option 57U Setup Instructions This

More information

48V 2KW 1U AC-DC Power Supply PS Electrical Specification for: Telkoor Model:

48V 2KW 1U AC-DC Power Supply PS Electrical Specification for: Telkoor Model: Electrical Specification for: Telkoor Model: 48V 2KW 1U AC-DC Power Supply PS-2048 SCALE RELEASE DATE 26/06/11 SHEET 1 OF 11 REVISION HISTORY Rev Level Rev Date Change Made Reason for Change Effective

More information

Liebert GXT MT kva

Liebert GXT MT kva Liebert GXT MT+ 10-20 kva Liebert GXT MT+ UPS, 10 kva - 20 kva Intelligent, Reliable UPS Protection Liebert GXT MT+ is a true on-line UPS that delivers continuous, high-quality AC power to connected equipment

More information

the Centric 300 An advanced modular UPS up to 1800kVA/kW

the Centric 300 An advanced modular UPS up to 1800kVA/kW the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has

More information

APPLICATION NOTE JC/85

APPLICATION NOTE JC/85 Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software

More information

Powerware Software Connectivity Service. > Powerware Software Suite ensures data integrity; free updates on

Powerware Software Connectivity Service. > Powerware Software Suite ensures data integrity; free updates on Powerware 9120 Features True double conversion online technology give you protection from all nine power problems Simple installation and operation Intuitive LCD screen provides realtime updates of UPS

More information

Intelligent Devices IDI 1100 Series Technical Manual

Intelligent Devices IDI 1100 Series Technical Manual Intelligent Devices IDI 1100 Series 4411 Suwanee Dam Road, Suite 510 Suwanee, GA 30024 T: (770) 831-3370 support@intelligentdevicesinc.com Copyright 2011, Intelligent Devices, Inc. All Rights Reserved

More information

Product Snapshot. The Powerware Uninterruptible Power System. Product Focus

Product Snapshot. The Powerware Uninterruptible Power System. Product Focus Powerware 9120 Uninterruptible Power System Product Focus Product Snapshot Power Rating: 700-3000VA Voltage: 120 and 230 Vac Frequency: 50/60 Hz (auto-sensing) Configuration: tower Features True double-conversion

More information

Powerware 9120 UPS. Product Snapshot. Features

Powerware 9120 UPS. Product Snapshot. Features Powerware 9120 UPS Features True double conversion online technology give you protection from all nine power problems Simple installation and operation Intuitive LCD screen provides realtime updates of

More information

R E C T I F I E R I N V E R T E R C O N V E R T E R MP7

R E C T I F I E R I N V E R T E R C O N V E R T E R MP7 Uninterruptible Power Supply Product Specifications Description The industrial UPS provides your critical equipment with uninterruptible 3 phase AC power. Using high frequency dual conversion technology,

More information

AC-DC Converter RECE K21

AC-DC Converter RECE K21 Thanks to the variety of modules available, the RECE3200-230-48-K21 system offers the perfect solution for all areas of applications requiring a power output of up to 3,2kW. Modular Battery Charger / Inverter

More information

XRS 3000 Controller Reference Guide V-2

XRS 3000 Controller Reference Guide V-2 XRS 3000 Controller Reference Guide V-2 XRS-3000 1 WHITE MAIN POWER COLLIGHTLIGHT THREE POSITION KEY SWITCH 1. OFF 2. STANDBY 3. ON XRS-3000 SAFETY CIRCUIT ENGAGED X- RAY PREWARNING X- RAY BEING PRODUCED

More information

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches S&C M Series Switch Operator Sophisticated Microprocessor Control of Overhead Distribution Switches S&C s M Series Switch Operator is a fully integrated, microprocessor-based operator that lets you automate

More information

Milpower Source M359-1 is a ruggedized, high performance On-Line UPS designed for Naval Shipboard and tough industrial applications.

Milpower Source M359-1 is a ruggedized, high performance On-Line UPS designed for Naval Shipboard and tough industrial applications. Milpower Source Milpower Source: 7 Field Lane, Belmont, NH 03220 Phone : (603) 267-7355 www.milpower.com West Cost Sales Office: Dave Hall Tel 626-304-9620 E-mail: dmhall@pacbell.net M359-1 2.0KW/2.5KVA

More information

FieldServer FS Toshiba UPS

FieldServer FS Toshiba UPS FieldServer FS-8700-124 Toshiba UPS Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after August 2017. Driver Version:

More information

1.1.1 Software Version Introduction About this Manual References 2

1.1.1 Software Version Introduction About this Manual References 2 Contents Contents 1 Overview 2 1.1.1 Software Version 2 1.1.2 Introduction 2 1.1.3 About this Manual 2 1.1.4 References 2 2 Instructions 3 2.1.1 Abbreviations and Definitions 3 2.1.2 Network Connection

More information

MasterFlux 48V Cascade BLDC Motor Controller Product Specification 030F0137

MasterFlux 48V Cascade BLDC Motor Controller Product Specification 030F0137 MasterFlux 48V Cascade BLDC Motor Controller Product Specification 030F0137 Revision History Page 1 of 11 Date ECN Rev Description By 09/01/10 EC34869 A Initial Release D. Stahl 07/14/11 EC39745 B Updated

More information

1. Safety Danger Warnings Earthing and earth fault protection... 4

1. Safety Danger Warnings Earthing and earth fault protection... 4 vacon 1 INDEX Document: DPD00386A Version release date: 24.9.10 1. Safety... 2 1.1 Danger... 2 1.2 Warnings... 3 1.3 Earthing and earth fault protection... 4 2. Metasys N2 - general info... 5 3. N2 technical

More information

Uninterruptible Power Supplies

Uninterruptible Power Supplies Xi Series 1-6kVA True On-Line UPS Features Rack-Mount/Standalone Format Universal Battery Design (Optional 10 year batteries) Dual Mains Input Dual Position Backlit LCD LCD Load Segment Control 2.5kVA

More information

A0750 AC-DC POWER MODULE

A0750 AC-DC POWER MODULE FEATURES High power density, 7.7W / in³ Net Weight:< 2.2 KG Low profile : 40.8mm (fit 1U 19 shelf R2250 series) Efficiency: 77% ~ 86 % typical Power factor correction (meet IEC1000-3-2 requirements) Overvoltage

More information

Metasys N1 Network Integration

Metasys N1 Network Integration Product Bulletin Issue Date March 31, 2003 Metasys N1 Network Integration The Metasys N1 Network Integration solution connects existing Metasys N1 based building automation systems into the new generation

More information

AC-DC Converter REC /60-K20

AC-DC Converter REC /60-K20 Thanks to the variety of modules available, the REC3200-230-48-K20 system offers the perfect solution for all areas of applications requiring a power output of up to 3,2kW. Modular Battery Charger / Inverter

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

MP7. Uninterruptible Power Supply

MP7. Uninterruptible Power Supply Uninterruptible Power Supply PRODUCT SPECIFICATIONS Description The industrial UPS provides your critical equipment with uninterruptible 3 phase AC power. Using high frequency dual conversion technology,

More information

7011A Series Single-Phase

7011A Series Single-Phase 7011A Series Single-Phase UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (1/2/3/5.4/6/8/10/12kVA) Tower Type (1.5/ 3kVA) Rackmount Type ISO 9001 CERTIFIED The Power Protection Solution Provider For Critical Operations

More information

Introduction to DX LCD Display

Introduction to DX LCD Display DX LCD Display User s Guide 2-1 Chapter 2 Introduction to DX LCD Display Introduction The DX LCD Display unit is a person/controller interface used with the DX-9100 series of controllers. The display can

More information

VLT 2800 DRIVE SPECIFICATIONS

VLT 2800 DRIVE SPECIFICATIONS VLT 2800 DRIVE SPECIFICATIONS Drive Input Power Input voltage 3 phase... 200 through 240, or 380 through 460; 3-phase all ratings 200 through 240, 1-phase through 2 HP Input voltage range for full output...

More information

A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE

A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE OPTION 21P INSTRUCTIONS This manual is only valid for A12B units equipped with a S2A-225C control module and a S2A-383S-3X20 communications card.

More information

Type Version Ordering Code Package PEB 2025-N V 1.5 Q67100-H6300 P-LCC-28-R (SMD) PEB 2025-P V 1.5 Q67100-H6241 P-DIP-22

Type Version Ordering Code Package PEB 2025-N V 1.5 Q67100-H6300 P-LCC-28-R (SMD) PEB 2025-P V 1.5 Q67100-H6241 P-DIP-22 ISDN Exchange Power Controller (IEPC) PEB 2025 CMOS IC Features Supplies power to up to four transmission lines CCITT recommendations compatible for power feed at the S interface Each line is individually

More information

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions GE Consumer & Industrial Electrical Distribution AF-600 FP TM Metasys Operating Instructions Contents 1 Overview 3 Introduction 3 About this Manual 3 References 3 Instructions 5 Abbreviations and Definitions

More information

T SERIES UPS kva PF Vac with Internal Battery 7.0 Touch Screen. User Guide

T SERIES UPS kva PF Vac with Internal Battery 7.0 Touch Screen. User Guide T SERIES UPS 10-15 - 20 kva PF 1.0 208 Vac with Internal Battery 7.0 Touch Screen User Guide UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY

More information

P.T.C. Production & Trading Company AG

P.T.C. Production & Trading Company AG P.T.C. Production & Trading Company AG UNINTERRUPTIBLE POWER SOURCE SINGLE PHASE 2kVA PTC-0130BA-1 MADE IN THE U.S.A USER S MANUAL P.T.C. Production & Trading Co. AG P.O. Box CH-6330 Cham Switzerland Phone:

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

METERING/DISPLAY MANUAL

METERING/DISPLAY MANUAL METERING/DISPLAY MANUAL 175W - 750W SINGLE PHASE Series LV EMERGENCY LIGHTING CENTRAL INVERTER Myers Power Products, Inc. 44 South Commerce Way, Bethlehem, PA 18017 1-800-526-5088 (610) 868-3500 Fax: (610)

More information

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module. Installation INSTALLATION INSTRUCTIONS: MCD PROFIBUS MODULE Order Code: 175G9001 1. Installation 1. Remove control power and mains supply from the soft starter. 2. Attach the module to the soft starter

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

GE Energy. ACE184 Series Power Shelf Main Output: 600A; Standby output: 8A. Preliminary Data Sheet. Features. Applications.

GE Energy. ACE184 Series Power Shelf Main Output: 600A; Standby output: 8A. Preliminary Data Sheet. Features. Applications. Applications 12Vdc distributed power architectures Mid-End Servers Blade Servers Network Equipment Network Attached Storage Storage Area Networks Routers/Switches Enterprise Networks Advanced workstations

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual

More information

Installing the DX LCD Display

Installing the DX LCD Display DX LCD Display User s Guide 3-1 Chapter 3 Installing the DX LCD Display Introduction Use the DX LCD Display as either a portable device, or permanently mount it in a panel or on the wall. For panel and

More information

Product Specifications

Product Specifications Product Specifications Models: USC-10001, USC-10002 USC-20001, USC-20002 USC-30001, USC-30002 Guide Specification for UniStar C Series Rack/Universal 1, 2, 3Kva Single-Phase, On-Line Double Conversoin

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

RT4F-110V/25A RECTIFIER

RT4F-110V/25A RECTIFIER The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V

More information

Multi-IQ. Firmware: RS232-Data Manager for UPS 4 x RS232 / 1 x LAN-Contacts flash upgradeable. User manual. (Serial Number / Seriennummer)

Multi-IQ. Firmware: RS232-Data Manager for UPS 4 x RS232 / 1 x LAN-Contacts flash upgradeable. User manual. (Serial Number / Seriennummer) Version: 2016-08-18 Multi-IQ Firmware: (Serial Number / Seriennummer) RS232-Data Manager for UPS 4 x RS232 / 1 x LAN-Contacts flash upgradeable User manual MANUAL ENGLISH... 2 GENERAL PROPERTIES:... 2

More information

RT9-48V/1.4kW Rectifier Specification

RT9-48V/1.4kW Rectifier Specification The RT9-48V/1.4kW is a switched mode rectifier (SMR) module that delivers up to 1.4kW of output power (and up to 30A output current) into a 48V nominal DC system. The RT9 suits AC supply voltages between

More information

g GE Power Quality Digital Energy GT Series On-Line, Double Conversion Uninterruptible Power Supply 1000, 1500, 2200, 3000 VA UL-version

g GE Power Quality Digital Energy GT Series On-Line, Double Conversion Uninterruptible Power Supply 1000, 1500, 2200, 3000 VA UL-version GE Power Quality Product Description On-Line, Double Conversion Uninterruptible Power Supply 1000, 1500, 2200, 3000 VA UL-version Manufactured by: GE Digital Energy General Electric Company Telephone 800-637-1738

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

BACnet. b3810 Series Local Controllers

BACnet. b3810 Series Local Controllers BACnet b380 Series Local Controllers The Andover Continuum TM b380 series controllers are designed for control of Air Handling Units, Roof Top Units, and other mechanical plant equipment. 0 Features Choose

More information

Manual and Protocol Description

Manual and Protocol Description Communication Module MSR240 1 Manual and Protocol Description Overview The MSR240 Communication Module serves as an interface between a MSR210 or MSR211 Basic Module and a standard serial data communication

More information

Considerations for Use. of the SITOP DC UPS Module

Considerations for Use. of the SITOP DC UPS Module Considerations for Use of the SITOP DC UPS Module 6A without interface 6A with serial interface 6A with USB interface 15A without interface 15A with serial interface 15A with USB interface 40A without

More information

RT12-240V/2.4kW Rectifier Specification

RT12-240V/2.4kW Rectifier Specification The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between

More information

CAS SEC (Serial) Protocol for Mitsubishi UPS. Gateway

CAS SEC (Serial) Protocol for Mitsubishi UPS. Gateway CAS-2700-44 SEC (Serial) Protocol for Mitsubishi UPS Modbus (RTU and TCP) and BACnet and HTML Gateway Description The SEC protocol can be used to connect to suitably enabled UPS s manufactured by Mitsubshi.

More information

1. Introduction External description Front and Rear Panel The LCD screen Alarm Conditions...6

1. Introduction External description Front and Rear Panel The LCD screen Alarm Conditions...6 Product Description LanPro 31 Contents: 1. Introduction...2 2. Functional explanation...2 2.1 Principles of Operation...2 2.2 Normal Conditions...3 2.3 Mains Failure...3 2.4 Bypass operation...4 3. External

More information

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SVT30KX Highlights On-line double-conversion topology, VFI operation

More information

48V 1.5KW 1U AC-DC Power Supply Electrical Specification for: Telkoor Model: 0/ 7 SHEET 1 OF 1

48V 1.5KW 1U AC-DC Power Supply Electrical Specification for: Telkoor Model: 0/ 7 SHEET 1 OF 1 Electrical Specification for: 48V 1.5KW 1U AC-DC Power Supply Telkoor Model: 900-1548-0000 0/ 7 SHEET 1 OF 1 REVISION HISTORY Rev Level A B Rev Date Change Made Reason for Change Effective Approved 22/06

More information

Andover ContinuumTM Infinet II

Andover ContinuumTM Infinet II Andover ContinuumTM Infinet II The i80 Series controllers are designed for control of Air Handling Units, Roof Top Units, and other mechanical plant equipment. Features 0 Choose the i80 model with the

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

CPU 224. The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design

CPU 224. The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design CPU 224 The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design The CPU 224 is equipped with the following: Integral 24 V encoder/load current

More information

Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS kva

Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS kva GE Critical Power Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS 3 5 6 8 10 kva GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91

More information