Table of Contents. General Safety Information

Size: px
Start display at page:

Download "Table of Contents. General Safety Information"

Transcription

1 Document Vektor Laboratory Exhaust with Variable Geometry zzle (VGN) Technology Electrical Controls Information Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Table of Contents VFD Controller General Safety Information Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward. 1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada. 2. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces, or chemicals. Replace cord immediately if damaged. 3. Verify the power source is compatible with the equipment. DANGER zzle Controller Always disconnect power before working on or near a unit. Lock and tag the disconnect switch or breaker to prevent accidental power up. CAUTION When servicing the unit, variable frequency drives (VFD) may be hot enough to cause pain or injury. Allow motor to cool before servicing. General Safety Information....1 Receiving, Handling and Storage Component Checklist - Electrical System Components....3 Wiring Installation....3 Fan Operation - Single Fan Set Point and Minimum Variables....4 Defined Modes....4 VGN Technology Control Flow Chart....5 Fan Operation - Multiple Fans, Staging Set Point and Minimum Variables....6 Defined Modes VGN Technology Control Flow Chart....8 Fan Operation - Multiple Fans, With Staging Set Point and Minimum Variables....9 Defined Modes VGN Technology Control Flow Chart Factory-Supplied Variable Frequency Drive System Diagram Wiring Diagram Communication BACnet and LonWorks Protocol. 14 Start-Up Procedure - Electrical Controls System Test and Balance for VGN zzle Velocity Adjustment Customer-Supplied Variable Frequency Drive System Diagram Wiring Diagram VGN zzle Controller Intro. and Tutorial Communication Start-Up Procedure - Electrical Controls System Test and Balance for VGN zzle Velocity Adjustment Troubleshooting Maintenance Electrical Replacement Parts Our Commitment VGN Technology 1

2 General Electrical Controls Information Receiving Upon receiving the product, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Greenheck Representative. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation. Component Checklist - Electrical Check off the following system components to verify all components are received. ABB Eclipse Variable Frequency Drive (VFD) with bypass mode and internal wiring kit. (VGN with factory-supplied VFD) VGN nozzle controller (VGN customer-supplied VFD) Transducer/terminal enclosure with Sure Aire pressure transducer and system terminals in NEMA 3R enclosure 24 volt VGN nozzle with modulating actuator 0/2-10 VDC with feedback Unpacking Verify that all required parts and the correct quantity of each item have been received. If any items are missing; report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading. Handling Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion. Storage Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user. INDOOR - The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30 F (-1 C) and 110 F (43 C) (wide temperature swings may cause condensation and sweating of metal parts). All accessories must be stored indoors in a clean, dry atmosphere. Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid sweating of metal parts, allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to eliminate any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection. The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection. Inspection and Maintenance during Storage While in storage, inspect equipment once per month. Keep a record of inspection and maintenance performed. If moisture or dirt accumulations are found on parts, the source should be located and eliminated. Removed From Storage As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order. 1. Check all fasteners, and accessories for tightness. 2 VGN Technology

3 General Electrical Controls Information System Components System Components (supplied by Greenheck) Quantity Description 1 transducer with adjustable pressure range and VDC signal 1 VFD with bypass mode and integrated controller (VGN with factory-supplied VFD) 1 VGN nozzle controller. (VGN, customer-supplied VFD) 1 to 4 Actuator motor(s) (nozzle) 24 volts, modulating VDC signal with feedback Varies Actuator motor (bypass damper), if provided by manufacturer Varies Actuator motor (isolation damper) 24 volts, open/close. Quantity will be zero if isolation damper actuator is supplied by others or if gravity style isolation damper is used. System Components (customer-supplied) Quantity Description Varies Wiring, conduit, miscellaneous fittings 1 Building control system with required communication wiring and shielding Varies transducer for duct pressure Varies Actuator motor (bypass damper) if provided by others 1 Actuator motor (isolation damper), if provided by others. Quantity will be zero if gravity style isolation damper is used. Varies 1/4 inch tubing. Connection from Sure-Aire termination plate mounted on fan to mounting location of transducer/terminal enclosure. 1 Fan motor VFD. (VGN, customer-supplied VFD) Wiring Installation NOTE All field installation and wiring of electrical equipment must be done to meet NEC and local codes. NOTE Be sure to use appropriately sized wire for the full load amp draw. The following items are a list of requirements necessary to install the controls for the VGN Technology system. 1. Mount variable frequency drive in the desired location; indoors or outdoors. Maximum distance from fan is 100 feet (30.5 meters). 2. Mount transducer/terminal enclosure at fan or bypass air plenum (BAP). 3. Run main power wiring from building breaker panel to variable frequency drive. By others. 4. Run motor power wiring from service disconnect switch to variable frequency drive. Wire length to be less than 100 feet. By others. 5. Connect control wiring pigtail (by factory) from VGN nozzle actuator(s) to transducer/terminal enclosure. (See wiring diagram). Optional: Connect wiring from isolation damper actuator(s) to transducer/terminal enclosure. By others. 6. Run control wiring from transducer/terminal enclosure to variable frequency drive or nozzle controller terminal strip. Wire length to be less than 100 feet (See wiring diagram). 7a. Run communication cable from variable frequency drive to Building Management System (BMS). See VFD manual for type and maximum length. By others. (VGN with factory-supplied VFD). 7b. Run VGN nozzle controller system wiring from main control panel to Building Management System (BMS). By others. (Customer-supplied VFD). 8. Run nozzle actuator feedback control wire from transducer/terminal enclosure at the fan to BMS controls. 9. Install 1/4 inch pressure tubing (by others) from transducer/terminal enclosure to Sure-Aire connection plate on fan. By others. 10. Install BMS with duct pressure control system. By others. 11. For specific device installation reference the appropriate component cut sheet or IOM. Also reference the following system and wiring diagrams on pages 4 and 7 for more detail. VGN Technology 3

4 General Electrical Controls Information Fan Operation - Single Fan Set point and minimum variables 1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of the fan, based on the airflow monitoring station. Building Management System (BMS) to monitor nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity. 2. Fan to run at BMS defined operation for speed and bypass mode. Mode reference will be determined by minimum fan speed and by minimum nozzle actuator feedback. a. If the BMS speed is equal to the minimum specific fan speed and nozzle feedback is minimum for a set time period (user-defined) the BMS will begin to modulate the bypass damper open to assist with pressure control. b. If the bypass damper is at full closed for a set time period, the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control. c. The PID sequence to be programmed at the BMS for bypass damper operation. The BMS to provide fan enable and VFD speed reference. Definition of typical operation modes: Mode #1: Unoccupied. Defined as no one inside the lab(s), all lab hoods are closed. 1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. BMS to monitor nozzle actuator feedback and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period. 4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system. Mode #2: Occupied; no lab hoods being used. Defined as people entering the lab(s), no work being done at the hoods. 1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. BMS to monitor nozzle actuator feedback and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period (user-defined). 4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system. Mode #3: Occupied; some or all lab hoods being used. Defined as people in the lab(s), lab hood sashes being used. A. Sashes opening in the lab 1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. Typical system response should be to increase fan speed and increase nozzle open area. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system. B. Sashes closing in the lab 1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. Typical system response should be to decrease fan speed and decrease nozzle open area. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period (userdefined). 4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system. Mode #4: Fault mode. Defined as safety mode; the system has an issue and needs to default to VFD bypass. 1. VFD failure detected, automatically or manually put into VFD bypass if available, by operator or BMS. 2. zzle area to increase proportional to fan airflow which will increase as fan speed is at maximum. 3. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 4. Duct pressure control will modulate bypass damper as required if system is in alarm mode. Duct pressure control is provided and programmed by the BMS system. 5. System manually to be reset and placed back in VFD auto mode. 4 VGN Technology

5 General Electrical Controls Information VGN Technology Control Flow Chart - Single Fan Positive Fault Negative Fault BMS Control Drive Fault Alarm Drive Fault Bypass Mode Max. VFD Monitor Time Static Valve Static = Setpoint Fan at Full Speed Above Setpoint (more positive) Static Value Below Setpoint (more negative) zzle Feedback at Minimum Min. VFD Monitor Time Required zzle Area VFD at Full Speed VFD at Minimum Speed Increase Fan Speed Send to BMS Controller Met? Positive Alarm Reset at Fault CLR Met? BMS Control Bypass Damper PID Reset by BMS Decrease Fan Speed Static Value Above Setpoint (more positive) Static = Setpoint Static Value Below Setpoint (more negative) Close Bypass Damper Bypass Feedback = Mimimum VDC Open Bypass Damper Bypass Feedback = Maximum VDC Damper Position Monitor Time Met? Met? Reset at Fault CLR Reset by BMS Negative Alarm Send to BMS Controller VGN Technology 5

6 General Electrical Controls Information Fan Operation - Multiple Fans, Staging Set point and minimum variables 1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of each fan, based on the airflow monitoring station. Building Management System (BMS) to monitor each fan nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity. 2. Each fan to run at BMS defined operation for fan on or off, and event timing, as required per system airflow requirements. BMS is also required to control fan speed for all fans. Bypass damper mode reference will be determined by the following scenario listed: A. All fans in system running at minimum. Minimum flow condition. a. BMS will control fan speed and monitor nozzle feedback as required to maintain system set point. b. Decreased flow condition from minimum speed. When the speed is equal to the minimum specific fan speed and nozzle feedback is at minimum for a set time period (user-defined), the BMS will begin to modulate the bypass damper(s) open to assist with pressure control. Increased flow condition from minimum speed. If the bypass damper(s) are at full closed for a set time period (user-defined), the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control. c. The PID sequence to be programmed at the BMS for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference. B. rmal operation. Fan operation normal system flow. a. Flow requirement for system within reach of fan operation. Fans operating will float together from minimum speed to maximum speed to keep set point. b. If any of the fans run in the surge area for a set time period, the BMS will need to add the bypass damper(s). c. The PID sequence to be programmed at the BMS for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference. Definition of typical operation modes: Mode #1: Unoccupied. Defined as no one inside the lab(s), all lab hoods are closed. 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #2: Occupied; no lab hoods being used. Defined as people entering the lab(s), no work being done at the hoods. 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #3: Occupied; some or all lab hoods being used. Defined as people in the lab(s), lab hood sashes being used. A. Sashes opening in the lab 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to increase fan(s) speed and increase nozzle open area. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. 6 VGN Technology

7 General Electrical Controls Information B. Sashes closing in the lab 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to decrease fan(s) speed and decrease nozzle open area. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #4: Fault Mode. Defined as safety mode; the system has an issue and needs to default to VFD bypass. 1. VFD failure detected, automatically or manually put into VFD bypass if available by operator or BMS. 2. zzle area to increase proportional to fan airflow which will increase as fan speed is at maximum. 3. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 4. Duct pressure control will modulate bypass damper(s) as required if system is in alarm mode. Duct pressure control is provided and programmed by the BMS system. 5. System manually to be reset and placed back in VFD auto mode. VGN Technology 7

8 General Electrical Controls Information VGN Technology Control Flow Chart - Multiple Fans, Staging Positive Fault Negative Fault BMS Control Drive Fault Alarm Drive Fault Bypass Mode Fan Stall Monitor Time Max. VFD Monitor Time Fan(s) in Stall Mode Time Period Reset by BMS Static Value Above Setpoint (more positive) Static = Setpoint Static Value Below Setpoint (more negative) Increase Fan(s) Speed VFD(S) at Full Speed Met? All zzle Feedback at Minimum VFD(S) Minimum Speed Min. VFD Monitor Time Fan Full Speed Required zzle Area Send to BMS Controller Positive Alarm Reset at Fault Clr Decrease Fan(s) Speed Time Period Met? BMS Control Bypass Damper PID Reset by BMS Static Value Above Setpoint (more positive) Static = Setpoint Static Value Below Setpoint (more negative) Close Bypass Damper Bypass Feedback = Min. VDC Open Bypass Damper Bypass Feedback = Max. VDC Damper Position Monitor Time Met? Met? Reset at Fault Clr Reset by BMS Negative Alarm Send to BMS Controller 8 VGN Technology

9 General Electrical Controls Information Fan Operation - Multiple Fans, With Staging Set point and minimum variables 1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of each fan, based on the airflow monitoring station. Building Management System (BMS) to monitor each fan nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity. 2. Each fan to run at BMS defined operation for fan staging, on or off, and event timing, as required per system airflow requirements. BMS is also required to control fan speed for all fans. Bypass damper mode reference will be determined by the following scenario listed: A. One fan in system running, all other fans off. Minimum flow condition. a. One fan in operation, BMS will control fan speed and monitor nozzle feedback as required to maintain system set point. b. Decreased flow condition from minimum speed. When the speed is equal to the minimum specific fan speed and nozzle feedback is at minimum for a set time period (user-defined), the BMS will begin to modulate the bypass damper(s) open to assist with pressure control. Increased flow condition from minimum speed. If the bypass damper(s) are at full closed for a set time period (user-defined), the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control. c. If one fan is at maximum speed for a set time period, another fan may be required to keep system set point. te section B for multiple fan operation. d. The PID sequence to be programmed at the BMS for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference. B. Two or more fans running, normal operation. Fan operation normal system flow. a. Flow requirement for system within reach of fan operation. Fans operating will float together from minimum speed to maximum speed to keep set point. b. If all fans in operation are at maximum speed for a set time period (user-defined) and other fans are available, another fan can be added by the BMS as required. c. With additional fan added to the system, all fans in operation will decrease and match speed of new fan until set point is reached, then fans can float together between minimum to maximum speed. te section C if a dead band zone is created. d. When more than one fan is operating and all are at the minimum speed for a set time period and the pressure is still too negative, the BMS will need to subtract a fan. e. When more than one fan is in operation and any of the fans run in the surge area for a set time period, the BMS will need to subtract a fan or bypass damper(s) may need to be used. f. With the subtraction of a fan from the system, the BMS will need to increase speed of all remaining fans and they will float together until set point is reached. te section C if a dead band zone is created. g. The PID sequence to be programmed at the BMS for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference. C. Dead band in system. Flow between fans cycle on/off. Flow requirement for system out of reach causing undesirable fan cycling on and off. If the fans in the system running at full speed is not enough air and adding an additional fan and running all fans at minimum is too much air, then the bypass damper mode may be necessary to settle these dead band zones. a. The BMS notices and counts cycling of fans to determine dead band zone. If a dead band is determined, the BMS will begin to modulate the bypass damper(s) open to assist with pressure control. b. If the bypass damper(s) are at full closed for a set time period, the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control. c. The PID sequence to be programmed at the BMS for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference. VGN Technology 9

10 General Electrical Controls Information Fan Operation - Multiple Fans, With Staging - continued Definition of typical operation modes: Mode #1: Unoccupied. Defined as no one inside the lab(s), all lab hoods are closed. 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #2: Occupied; no lab hoods being used. Defined as people entering the lab(s), no work being done at the hoods. 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #3: Occupied; some or all lab hoods being used. Defined as people in the lab(s), lab hood sashes being used. A. Sashes opening in the lab 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to increase fan speed and increase nozzle open area. Additional fans may be added as necessary. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. B. Sashes closing in the lab 1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to decrease fan speed and decrease nozzle open area. Removal of fans may be required as necessary. 2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required. te: Follow bypass damper(s) operation depending on number of fans running. 4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system. Mode #4: Fault Mode. Defined as safety mode; the system has an issue and needs to default to VFD bypass. 1. VFD failure detected, automatically or manually put into VFD bypass if available by operator or BMS. 2. zzle area to increase proportional to fan airflow which will increase as fan speed is at maximum. 3. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS. 4. Duct pressure control will modulate bypass damper(s) as required if system is in alarm mode. Duct pressure control is provided and programmed by the BMS system. 5. System manually to be reset and placed back in VFD auto mode. 10 VGN Technology

11 General Electrical Controls Information VGN Technology Control Flow Chart - Multiple Fans, With Staging Positive Fault Negative Fault BMS Control Drive Fault Alarm Deadband Range Fan On/Off Cycling Drive Fault Bypass Mode Fan Stall Monitor Time Max. VFD Monitor Time Fan(s) in Stall Mode Met? Reset by BMS Static Value Remove a fan Static = Setpoint Met Reset by BMS Above Setpoint (more positive) Static Value Below Setpoint (more negative) Fan Full Speed VFD(S) Full Speed Fan(s) available to add Met? Reset by BMS All zzle Feedback at Minimum Required zzle Area Increase Fan(s) Speed Send to BMS Controller Met? Positive Alarm Reset at Fault Clr Add a Fan Decrease Fan(s) Speed VFD(S) Minimum Speed Fan(s) Running = 1 Met? BMS Control Bypass Damper PID Met? Reset by BMS Reset by BMS Static Value Above Setpoint (more positive) Static = Setpoint Static Value Below Setpoint (more negative) Close Bypass Damper Open Bypass Damper Damper Position Monitor Time Bypass Feedback = Min. VDC Bypass Feedback = Max. VDC Met? Met? Reset at Fault Clr Reset by BMS Negative Alarm Send to BMS Controller VGN Technology 11

12 Electrical Controls Information for Factory-Supplied Variable Frequency Drive System Diagram ALL GFC PROVIDED CONTROL DEVICES ARE 24V POWER VEKTOR ROOF EXHAUST FAN STATIC PRESSURE TRANSDUCER AND TERMINAL BOX SHIPPED LOOSE (INSTALLED BY OTHERS) 1/4 INCH PRESSURE TUBING ISOLATION DAMPER WITH OPEN/CLOSE ACTUATOR BYPASS DAMPER ACTUATOR (MODULATING) (CONTROLLED BY BMS) EXHAUST DUCT VGN NOZZLE WITH MODULATING ACTUATOR(S) VFD IN A NEMA 3R UL LISTED ENCLOSURE WITH BYPASS AND INTEGRATED CONTROLLER (SHIPPED LOOSE; FIELD MOUNTED) COMMUNICATION WIRING SERVICE DISCONNECT SWITCH DRIVE BMS COMMUNICATIONS - BACNET (STANDARD) - ANALOG SIGNAL(S) (STANDARD) - LONWORKS (OPTIONAL) TO BMS CONTROL SYSTEM POWER WIRING MOTOR WIRING CONTROL WIRING ROOF LINE NOZZLE FEEDBACK DUCT PRESSURE CONTROL STATIC PRESSURE TRANSDUCER BOX EQUIPMENT BY GFC WIRING BY GFC EQUIPMENT BY OTHERS WIRING BY OTHERS 1/4 INCH PRESSURE TUBING STATIC PRESSURE PROBE NOTES: - All wiring in rigid metal conduit or flexible metal conduit and liquid tight. - All tubing and conduit to be UV resistant for outdoor use. 12 VGN Technology

13 Electrical Controls Information for Factory-Supplied Variable Frequency Drive Wiring Diagram ABB ECLIPSE DRIVE WITH VGN TECHNOLOGY ABB BYPASS MODULE CBL#3 (ORANGE) 1 DRIVE DISCONNECT LOAD SIDE GND CBL#3 (ORANGE) 5 CBL#3 (BLACK) CBL#3 (RED) 14 DIGITAL RELAY OUT CLOSE WHEN FAN ON 16 SET DIP SWITCHES SHIELD ABB DRIVE MODULE U I 1 ANALOG INPUT 2 SIGNAL SWITCH SGND T1 OUTGOING POWER - TO FAN MOTOR CBL#1 (BLACK) CBL#1 (WHITE) CBL#2 (WHITE) CBL#2 (BLACK) AI1 SURE AIRE AGND AO1 VARIABLE N. T2 T3 GND VGN PCB TB1 zzle VDC Sure-Aire VCD Isolation Power Manual Switch 1 Manual Switch Volts +24 Volts +24 Volts Common Common Common FUSE COMM BMS SYSTEM SUPPLIED BY OTHERS R1 BMS COMMUNICATIONS (STD) - BACNET (STANDARD) - LONWORKS (OPTIONAL) TB2 Power Supply + Common AI1 AGND AO1 POWER SUPPLY REQUIRED WIRING: -DIGITAL ON/OFF (THRU COMM) -SPEED REFERENCE (THRU COMM) -NOZZLE FEEDBACK (HARDWIRE) -ALARM (THRU COMM) -FAN FLOW (THRU COMM) TRANSDUCER ACTUATOR DUCT PRESSURE SIGNAL COMPONENT BY OTHERS 5 BYPASS DAMPER COMPONENT BY OTHERS TRANSDUCER/TERMINAL ENCLOSURE - AT THE FAN NOZZLE POSITION FEEDBACK TO BMS TRANSDUCER 2 + SURE-AIRE SIGNAL DC +24DC +24DC COM COM COM SURAIR ISOPWR NOZVDC NOZFB1 NOZFB2 GND GND NOZZLE ACTUATOR FEEDBACK RECOMMEND 1 PER SHAFT MAY BE MULTIPLE ACTUATORS PER NOZZLE BLADE SHAFT FAN PRESSURE (LOW&HIGH) TO SURE-AIRE CONNECTION PLATE ON FAN - + ACTUATOR 1 ISOLATION DAMPER FACTORY WIRING FIELD WIRING ACTUATOR 2 NOZZLE ACTUATOR 1 ACTUATOR 3,4,5 ADDITIONAL NOZZLE ACTUATORS QTY. DEPENDENT ON UNIT SIZE VGN Technology 13

14 Electrical Controls Information for Factory-Supplied Variable Frequency Drive Communication The VGN Technology variable frequency drive (VFD) has an embedded fieldbus as standard and optional fieldbus adapter(s) that can be purchased. Greenheck offers and supports BACnet MS/TP as our standard communication protocol and also LonWorks as an optional communication. The VFD does have other languages available, but are not supported by Greenheck, however, it may be supported by the VFD manufacturer. Please contact the VFD factory support if you have alternate communication requirements. The following information is a guide to summarize the set up of the VFD to a BMS system. The guide is a general overview and it is suggested the controls contractor and BMS group reference the VFD manual for detailed installation and setup of the VFD communications. It is also suggested to follow the manufacturers recommendations for communication cable type and maximum lead length. The recommended cable is different for each protocol. The following is only a general checklist and does not specify exact parameters. NOTE All parameters are to be modified at the bypass keypad, which is the lower keypad on the enclosure. BACnet MS/TP Protocol (standard) Connect the communication wiring from the appropriate VFD terminations to the BMS control system. Reference the VFD manual for terminal location and approved wiring type. Apply power to the VFD. Enable BACnet MS/TP as the desired Protocol. Place the BACnet MS/TP channel in the reset mode, this is required to set up all the remaining parameters. Define the system baud rate being used. Define the Device object instance. Define a unique object ID. Confirm the communication. Configure the device name. Take the VFD out of reset mode. Cycle power to the VFD to save all changes. For a list of BMS points available for BACnet MS/TP communication, see the manufacturer s point listing chart(s) in the manual. LonWorks Protocol (optional) The LonWorks communication requires an optional plug-in module that is added to the bypass module of the VFD. The module needs to be specified at time of ordering of the fan and control system. It is also suggested to follow the manufacturers recommendations for communication cable type and maximum lead length for LonWorks. The recommended cable is different for each protocol. Verify mounting of plug-in module that nothing was loosened in shipping. Connect the communication wiring from the appropriate VFD terminations to the BMS control system. Reference the VFD manual for terminal location and approved wiring type. Apply power to the VFD. Activate the field buss adaptor port. Verify the HOST LED is lit to a solid green color. Program the system enable control. Program the bypass fault reset if required to reset VFD from BMS. Program the system VFD speed control. Program the VFD fault reset if required to reset VFD from BMS. Cycle power to the VFD to save all changes. For a list of BMS points available for LonWorks communication, see the manufacturer s point listing chart(s) in the manual. 14 VGN Technology

15 Electrical Controls Information for Factory-Supplied Variable Frequency Drive Start-Up Procedure - Electrical Controls The following start-up procedure is to be completed in order to verify that the fan is in working order. It does not cover the details for test and balance, VFD programming, commissioning, or system troubleshooting which is covered in other parts of the Installation, Operation and Maintenance Manual. Mechanical Component System Verification For detailed descriptions to complete these operations, see equipment Installation, Operation and Maintenance Manual (IOM). Fan assembly and installation completed. Check all fasteners for tightness, as they may loosen during shipping. All pressure tubing lines installed as required. All control enclosures and devices mounted in the appropriate locations. Verify fan wheel alignment. Electrical Control Components System Verification For detailed descriptions to complete these operations, see equipment Installation, Operation and Maintenance Manual, National Electrical Code and local electrical code. Service feeder(s) to all controls completed. Control wiring to all devices completed. All field electrical connections tested and torqued. Communication wiring to Building Management System completed. Electrical System Start-Up for VGN Use appropriate electrical safety gear as required. Make sure disconnect switch at the VFD is in the OFF position. Verify each power phase at the VFD disconnect is not shorted to ground using a voltmeter. Turn on the breaker that feeds the fan VFD. Verify the voltage is correct from phase to phase using a voltmeter at the VFD disconnect. Apply power to the VFD by turning on the disconnect switch that is interlocked to the door. Verify that the VFD is in the OFF mode at the VFD keypad. Check control voltage at drive terminals to verify the control voltage is correct. Turn on the service disconnect switch at the fan. Open all lab hoods inside the building and verify duct control is operational. te the fan speed at the VFD keypad; it should be at full speed. Increase fan speed if required using the VFD keypad up and down arrows. Press the HAND button at the VFD keypad. The isolation damper will start to open. The fan speed will start to accelerate to full speed. As the fan speed increases the nozzle will open to maintain constant velocity. Verify fan wheel rotation. Verify it matches labeled direction and IOM. If the fan wheel is rotating in the wrong direction, turn off fan, disconnect power, and lockout main feeder. Reverse two of the motor wiring leads to change wheel direction. Reapply power and press HAND mode once again at the VFD keypad. Verify fan wheel rotation, verify it matches labeled direction and fan Installation, Operation and Maintenance Manual. Use the up and down arrows at VFD keypad, change the speed to verify nozzle reaction. - As speed increases the nozzle will open. - As speed decreases the nozzle will close. VGN Technology 15

16 Electrical Controls Information for Factory-Supplied Variable Frequency Drive System Test and Balance for VGN The VGN Technology control system needs to be set up at a desired fixed fan speed and nozzle area. If the following is not done, it will be difficult to do the test and balance of the building as the fan will continually be adjusting during changes in the building lab airflow. The following steps listed are necessary to create a stable fan system for the test and balance setup of a building. The fan speed can be set at a fixed speed by two different options: Option #1 is by selecting the bypass mode; this will put the fan at full speed. Option #2 is put the VFD in HAND mode; this will give you speed adjustment from minimum speed to full speed. The nozzle area can by set to a fixed position by doing the following. 1. Minimum zzle Actuator Signal is adjusted by the VFD parameter #1504 at the VFD keypad. te the factory default setting from Greenheck prior to adjusting. Use the following table to record for your reference. 2. Maximum zzle Actuator Signal is adjusted by the VFD parameter #1505 at the VFD keypad. te the factory default setting from Greenheck prior to adjusting. Use the following table to record for your reference. 3. To create a fixed nozzle location, the Test and Balance personnel can set the parameter #1504 and #1505 to the same value within Greenheck range and it will keep the nozzle fixed to a specific location. For example, if the maximum value is 15 ma, do not go over that maximum value. By setting the value to the same number, the outlet velocity and airflow of the fan can be set to a desired reading for balancing the building. Parameter & Description Minimum zzle Actuator Signal Parameter 1504 Maximum zzle Actuator Signal Parameter 1505 Value (Set at Factory) New User Set Point After testing is completed, VFD parameters need to be set back to Greenheck factory default numbers for the nozzle to modulate. The fan can be put back into the desired mode (off, hand, or auto). For more information on the keypad details and how to access the following parameters, see the VFD manufacturer user s guide. zzle Velocity Adjustment The VGN control system is shipped from the factory to output an average minimum 3000 fpm nozzle velocity. The VFD for the system will have a given cfm range that is programmed into the parameter set. The following parameters can be set as required if the desired velocity is required to be higher than the factory default setting. The following steps can be done to adjust the nozzle velocity range of the fan. Setting the minimum range parameter of the system: 1. Minimum air volume range is adjusted by the VFD parameter #1502 at the VFD keypad. The factory default setting from Greenheck is specific to every fan; note the parameter setting prior to changing the value and record below for future reference. 2. To change the minimum value, follow the following guidelines. Example: 3,500 fpm (desired) New VFD Reading = Current VFD Reading x (3,500/3000) Setting the minimum speed parameter of the system: 1. Minimum fan speed is adjusted by the VFD parameter #2007 at the VFD keypad. te the parameter setting prior to changing the value and record below for future reference. 2. The minimum fan speed may be increase from the factory value if a higher nozzle velocity is required. It is not required to increase the minimum fan speed but once the nozzle is at the minimum area the velocity may potentially go lower than the desired velocity. It is suggested by Greenheck however that the value not be lower then the factory preset minimum value set at time of shipment. Adjust Fan RPM for velocity increase: 1. The fan may also need the pulley changed to adjust the fan RPM. It is suggested to consult the factory to size accordingly. After completing the velocity changes, the fan can be put into the desired mode (off, hand, or auto). Parameter & Description Minimum Range Value Parameter 1502 Minimum Speed Value Parameter 2007 Value (Set at Factory) New User Set Point For more information on the keypad details and how to access the following parameters, see the VFD manufacture user s guide. 16 VGN Technology

17 This page is intentionally blank. VGN Technology 17

18 Electrical Controls Information for Customer-Supplied Variable Frequency Drive System Diagram ALL GFC PROVIDED CONTROL DEVICES ARE 24V POWER VEKTOR ROOF EXHAUST FAN STATIC PRESSURE TRANSDUCER AND TERMINAL BOX SHIPPED LOOSE (INSTALLED BY OTHERS) 1/4 INCH PRESSURE TUBING ISOLATION DAMPER WITH OPEN/CLOSE ACTUATOR BYPASS DAMPER ACTUATOR (MODULATING) (CONTROLLER BY BMS) EXHAUST DUCT VGN NOZZLE WITH MODULATING ACTUATOR(S) NOZZLE CONTROLLER ANALOG SIGNAL(S) VFD COMMUNICATION TO BMS CONTROL SERVICE DISCONNECT SWITCH VFD PROVIDED AND PROGRAMMED BY OTHERS CONTROLLER POWER WIRING VFD POWER WIRING FAN RUNNING STATUS CONTACT MOTOR WIRING ISOLATION DAMPER WIRING TO VFD BY OTHERS ROOF LINE NOZZLE FEEDBACK DUCT PRESSURE CONTROL STATIC PRESSURE TRANSDUCER BOX EQUIPMENT BY GFC WIRING BY GFC EQUIPMENT BY OTHERS WIRING BY OTHERS 1/4 INCH PRESSURE TUBING STATIC PRESSURE PROBE NOTES: - All wiring in rigid metal conduit or flexible metal conduit and liquid tight. - All tubing and conduit to be UV resistant for outdoor use. 18 VGN Technology

19 Electrical Controls Information for Customer-Supplied Variable Frequency Drive Wiring Diagram NOZZLE CONTROLLER ID2 GND Y2 Y4 GND TRANSFORMERS NOZZLE CONTROLLER G GO B1 GND C1 NO1 L1 L1 N NGND GND FAN RUN CONTACT(S) FROM VFD BY OTHERS BMS SYSTEM SUPPLIED BY OTHERS BMS COMMUNICATIONS (STD) - ANALOG SIGNAL(S) - ON/OFF CONTACT(S) +24V +24V +24V +24V +24V COM COM COM COM COM SURAIR FNRUN NOZVDC CFM1 ALM GND GND GND GND FNRUN ALM CFM1 COM MEASURE 0-10VDC +24V NOZFB1 NOZFB2 ISOPWR REQUIRED WIRING: -DIGITAL ON/OFF (HARDWIRE) -NOZZLE FEEDBACK (HARDWIRE) -ALARM (HARDWIRE) -FAN FLOW (HARDWIRE) -ISOLATION DAMPER CONTACT (HARDWIRE) MEASURE 2-10VDC TRANSDUCER TERMINAL ENCLOSURE - AT THE FAN INCOMING POWER 120/1PH. 20 AMP CIRCUIT TRANSDUCER DUCT PRESSURE SIGNAL COMPONENT BY OTHERS - ACTUATOR BYPASS DAMPER COMPONENT BY OTHERS ISOLATION DAMPER TRANSDUCER V +24V +24V COM COM COM SURAIR ISOPWR NOZVDC NOZFB1 NOZFB2 GND GND NOZZLE POSITION FEEDBACK TO BMS FAN FLOW (LOW&HIGH) TO FAN CONNECTION PLATE - + ACTUATOR 1 ISOLATION DAMPER ACTUATOR 2 NOZZLE (REQUIRED) FACTORY WIRING FIELD WIRING ACTUATOR 3,4,5 ADDITIONAL NOZZLE ACTUATORS QTY. DEPENDENT ON UNIT SIZE VGN Technology 19

20 Electrical Controls Information for Customer-Supplied Variable Frequency Drive VGN zzle Controller Controller Introduction and Tutorial The VGN zzle Controller is located in the main control panel. The controller has factory set points that can be modified to configure the system for job specific functions. The controller introduction and directions for the setup screens are shown in this section. The face of the controller has six buttons, allowing the user to view unit conditions and alter parameters. The controller is pre-programmed with easy to use menus. Keypad Navigation Escape Up Down Allows the user to exit the current menu, jumping to the Main Menu. The arrow buttons allow the user to scroll through different screens and adjust parameters.! Alarm Button will blink red, indicating an alarm condition. Press to review current alarms. To review previous alarms, access the DATA LOGGER through the main menu. Enter A. In screens with adjustable parameters, pressing the Enter button moves the cursor from the upper left corner of the screen to the parameter. The arrow buttons can then be used to adjust the parameter. B. To move to the next parameter on the same screen, press the Enter button. C. To save the change, press the Enter button until the cursor moves back to the upper left corner of the screen. Program Pressing the Program button allows the user to enter the Main Program Menu. Example of Parameter Adjustment GREENHECK VGN SYSTEM SETTINGS H FAN SIZE 36 FLOW MEASURE INLET UNITS ENGLISH ELEVATION OUTLET VELOCITY 3000 The cursor always begins in the upper left corner of the display and will be blinking. Press the button to move the cursor down for parameter adjustment. GREENHECK VGN SYSTEM SETTINGS H FAN SIZE 36 FLOW MEASURE INLET UNITS ENGLISH ELEVATION OUTLET VELOCITY 3000 Once the cursor has reached the desired parameter, press the adjust the value. buttons to GREENHECK VGN SYSTEM SETTINGS H FAN SIZE 36 FLOW MEASURE INLET UNITS ENGLISH ELEVATION OUTLET VELOCITY 3000 When satisfied with the adjustment, press the button to save the parameter. When finished, make certain the cursor is in the upper left corner. If the cursor is not in the upper left corner, the changes will not be saved. The cursor must be in the upper left corner to enable screen advancement. 20 VGN Technology

21 Electrical Controls Information for Customer-Supplied Variable Frequency Drive Controller Menu Screens The nozzle controller consists of five menu screens to operate the VGN system. The following information describes the menu screens in detail. GREENHECK VGN AIR FLOW FLOW xxxxx FLOW VDC X.X VDC LOW SCALE 0 TO XXXXX NOZZLE OPEN XXX % The following value ranges are specific to the Air Flow menu screen. Flow Active reading calculated by the Sure-Aire system. English = CFM; Metric = m 3 /hr Flow VDC Scaled voltage output specific to the flow scale. 0 VDC = no flow; 10 VDC = maximum flow Flow Scale Flow range specific to VGN fan. English = CFM; Metric = m 3 /hr. zzle Open Active reading stating the % open of the VGN nozzle. 0% = nozzle closed; 100% = nozzle open The values in this menu are not user-editable and are locked by the controller program. GREENHECK VGN SYSTEM STATUS FAN STATUS XXX VELOCITY XXX FAN FLOW XXX ALARM CONTACT XXX GREENHECK VGN SYSTEM SETTINGS H FAN SIZE XX FLOW MEASURE XXXXX UNITS XXXXXX ELEVATION XXXXX OUTLET VELOCITY XXXX The following value ranges are specific to the System Status menu screen. Fan Status Shows the status of the fan. On or Off Velocity Determines if outlet velocity is acceptable per system setting. OK or Low Fan Flow Determines if fan flow is acceptable per required nozzle area and velocity. OK or Low Alarm Contact Alarm and contact closure for the following. Alarm list: a. Velocity is below the required preset system value. b. Fan is shown as running but no flow is being created. The values in this menu are not user-editable and are locked by the controller program. The following value ranges are specific to the System Settings menu screen. H / M / C Fan Size Factory set for system fan size. Selects the correct fan variables for the control. Flow Measure Sets the location of the airflow monitor location. Inlet or outlet condition Units Sets up the control screen variables for the system. English or Metric Elevation Location above sea level the system is located to set air density. 0 to 10,000 feet Outlet Velocity Required velocity at the VGN zzle outlet. 3,000 to 4,000 FPM; 912 to 1216 MPM. All the values in this menu can be changed by the user. te factory settings prior to making adjustments. GREENHECK VGN TEST AND BALANCE T&B BALANCING NOZZLE % OPEN FLOW CORRECT XXX XXX XXXX The following value ranges are specific to the Test and Balance menu screen. T&B Balancing Used to start the balancing process of the system. or. zzle % Open Gives Test and Balance personnel complete control of nozzle regardless of fan flow. 0% = closed; 100% = open Flow Correct K factor for Test and Balance personnel to measure and adjust airflow. te that K value is not CFM, but subtracts or adds to the flow calculation within the program to All the values in this menu can be changed by the user. te factory settings prior to making adjustments. VGN Technology 21

Table of Contents. General Safety Information

Table of Contents. General Safety Information Document 481885 Vektor Laboratory Exhaust with Variable Geometry Nozzle (VGN) Technology Electrical Controls Information Installation, Operation and Maintenance Manual Please read and save these instructions

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 479653 Generation 2 Constant /Air Flow Control Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

DVFP Series Variable Frequency Drive - Product Manual. pg. 1

DVFP Series Variable Frequency Drive - Product Manual. pg. 1 pg. 1 Set Up Instructions for DVFP Inspect the packaging of the equipment to confirm that nothing was damaged during shipping. Remove the system from the packaging. Make sure everything is included and

More information

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M INSTALLATION INSTRUCTIONS PECCSUN672 Series Power Exhaust for York - 6 Ton Units Before Starting Installation Warning Severe injury can result from incorrect servicing. Only qualified HVAC service personnel

More information

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1 200 HP)

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -H Performance High Plume April 07 Laboratory Exhaust Systems Model Vektor -H Table of Contents Vektor-H Specification Chart.... Plume Height Calculation... Quick Select

More information

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION Document 476092 User and Service Manual Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Table of Contents 1. Overview Installation...6

Table of Contents 1. Overview Installation...6 (2003-01-31) Table of Contents 1. Overview...1 1.1. Introduction... 1 1.2. Product Description... 1 1.2.1. Mechanical Actuator Assembly with M2CP Electrical Enclosure... 1 1.2.2. Variable Frequency Controller

More information

SEZ7656R1045B / SEZ7656H1045B

SEZ7656R1045B / SEZ7656H1045B SEZ7656R1045B / SEZ7656H1045B Installation Guide f BACnet MS-TP RTU / HP Room Controllers F Commercial Zoning Systems CONTENTS Installation 2 Location 2 Installation 2 BACnet System Overview 3 Terminal,

More information

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

SED2 VFD NEMA Type 3R Bypass/Air Conditioner SED2 VFD NEMA Type 3R Bypass/Air Conditioner Description The NEMA Type 3R Bypass with Air Conditioner allows SED2 to be employed in a harsh environment. The SED2 is designed specifically for HVAC applications

More information

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS SEZ7656E1045B Installation Guide f BACnet MS/TP RTU Terminal with IAQ Control CONTENTS Installation 2 Location 2 Installation 2 BACnet System Overview 3 Terminal, Identification and Function 4 Wiring 4

More information

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS FORM 31003-C INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS PRESSURE CONTROL OPTION WITH ECM MOTORS CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax:

More information

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST MODEL WGSEIFM-5 For Use with Bard 3 through 5 Ton Step Capacity Wall Mount Air Conditioners with Gas Heat Bard Manufacturing Company, Inc. Bryan, Ohio

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

Zenith DS9000 Dispensing System

Zenith DS9000 Dispensing System Page Date: 04/2009 Zenith DS9000 Dispensing System Installation & Operation Manual Page 2 Table of Content Introduction... 3 Control Specification... 4 Wiring Diagram... 5 Wiring Instructions... 6 Field

More information

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller SEZ7260X5x45B Installation Guide f BACnet MS/TP Zone Controller CONTENTS Installation 2 Location 2 Installation 2 Typical Applications 4 Main outputs wiring 5 Wiring examples 8 CO2 Sens wiring 8 Configuring

More information

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 Instruction Manual D2-3342-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

Service Instructions. Conductor 420

Service Instructions. Conductor 420 Service Instructions Conductor 420 Listed, File No. E195547 Input: 480 VAC, 50/60 HZ. (Operating range 380-480 VAC) 20 AMP MAX OUTPUT W/25 AMP FUSE Output: 0-90% of Input Voltage Table of Contents General

More information

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions Controls Guide for XeteX Units Beyond meeting the typical specification and performance requirements, controlling the equipment is usually the most important success factor for HVAC projects. XeteX provides

More information

AD-7830 Servo Amplifier

AD-7830 Servo Amplifier Instruction Manual IM-0606 AD-7830 Servo Amplifier Table of Contents General Information... 2 Introduction... 2 Receiving/Inspection... 2 Storage... 2 Equipment Return... 2 Abbreviations Used in This Manual...

More information

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

SED2 Variable Frequency Drives with Electronic (E) Bypass Options SED2 Variable Frequency Drives with Electronic (E) Options Description The E- Options are companion packages for the family of SED2 Variable Frequency Drives (s). For information on the family of SED2

More information

SED2 Variable Frequency Drives

SED2 Variable Frequency Drives SED2 Variable Frequency Drives Startup Procedure and Checklist Document No. 155-718 Table of Contents Prerequisites...1 Preparing for SED2 VFD Startup...1 HVAC Startup Procedure for SED2 with Bypass Option...4

More information

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION LOCATION The I/CO 2 transmitter is designed to mount over a standard single

More information

4/8/ nd Annual OTCO WW Workshop W/WW Product Overview ACQ550. ABB Slide 1

4/8/ nd Annual OTCO WW Workshop W/WW Product Overview ACQ550. ABB Slide 1 4/8/2015 52 nd Annual OTCO WW Workshop W/WW Product Overview ACQ550 Slide 1 Drive Basics Why Use Adjustable Speed Drives? Reduced Energy Consumption Improved Process Control / Efficiency Increased Product

More information

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC.   RATING IS 1 AMP COND. B ENABLE COOL B ENABLE. Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER

More information

GOLANDER PUMP. Operation Manual. For Microflow Variable-Speed Peristaltic Pump BT50S/BT102S.

GOLANDER PUMP. Operation Manual. For Microflow Variable-Speed Peristaltic Pump BT50S/BT102S. GOLANDER PUMP Operation Manual For Microflow Variable-Speed Peristaltic Pump BT50S/BT102S info@golanderpump.com http://golanderpump.com 1-678-587-8806 Contents Safety Cautions... 1 1 Description... 1 2

More information

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions. Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel. LX Breaker Control Panels Installation and Setup Procedure Hubbell Building Automation, Inc. 9601 Dessau Road Building One Suite 100 Austin, Texas 78754 512-450-1100 512-450-1215 Fax www.hubbell-automation.com

More information

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options BT300 HVAC Drives Electronic Bypass (E-Bypass) Options Description The BT300 Electronic Bypass (E-Bypass) Options are companion packages for the family of BT300 Variable Frequency Drives (VFDs). For information

More information

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC5000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare epi Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5 Pa) Electronic

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

BACnet Flow Controller for Fan Filter Units

BACnet Flow Controller for Fan Filter Units MANUAL SERVICE + INSTALLATION BACnet Flow Controller for Fan Filter Units BFC Series v300 Issue Date: 08/23/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General

More information

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL PHASETRONICS Specialists EP1 Series Power Control Single Phase SCR 10-50 Amps OPERATION & SERVICE MANUAL Phasetronics, Inc. P.O. Box 5988 1600 Sunshine Drive Clearwater, FL 33765 (727)573-1900 FAX(727)573-1803

More information

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D Specification Number: 23 09 33 Product Name: FRENIC-Eco AC Drives for Variable Torque Fan & Pump Applications (1-125Hp at 208/230V and 1-900Hp at 460V) PART 1: GENERAL 1.01 SUMMARY A. This specification

More information

System Controls Suggested Specification

System Controls Suggested Specification 1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall

More information

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

C. New or replacement products installed in existing facilities shall be consistent with existing equipment. September 2012, rev 00 26 2923 Variable Frequency Controllers PART 1. GENERAL 1.01 Description A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 September 24, 2014 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides

More information

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP. DIVERSIFIED HEAT TRANSFER SERIES 700 STEAM GENERATOR CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE AT SIGMACONTROLS.COM SERIES 700 DHT STEAM GENERATOR MANUAL 042514 2 TABLE OF CONTENTS INTRODUCTION.

More information

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING Installation and Operation Manual ETV Platinum Plus Electronic Tempering Valve with Safeguard WARNING This Heat-Timer control is strictly an operating control; it should never be used as a primary limit

More information

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter Standard Options Model 4100 Position Indicating Meter A percent-of-full-travel meter is supplied with a trim potentiometer resistor, terminal block and connectors. A potentiometer is required in the actuator

More information

TOXALERT MODEL AIR 2000

TOXALERT MODEL AIR 2000 TOXALERT MODEL AIR 2000 NOTE: Toxalert s Model GVU-CO 2 Sensor is the same as the Air2000R. Microprocessor-based, Infrared Environmental CO 2 Sensor OPERATOR S MANUAL TOXALERT TM INTERNATIONAL INC. P.O.

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

Electric Actuators and Control Systems. Established Leaders in Valve Actuation AD Instruction Manual. Publication P972E Issue 08/09

Electric Actuators and Control Systems. Established Leaders in Valve Actuation AD Instruction Manual. Publication P972E Issue 08/09 Electric Actuators and Control Systems Established Leaders in Valve Actuation AD-9120 Instruction Manual Publication P972E Issue 08/09 Instruction Manual IM-0626 AD-9120 Digital Servo Amplifier Table of

More information

Custom Controller Installation Instructions

Custom Controller Installation Instructions MODEL CUSTOM CONTROLLER HARDWARE CODE MAX ALLOWABLE AMBIENT TEMP: 70 C (158 F) THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: 1) THIS DEVICE MAY

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

1395 Node Adapter Board Troubleshooting

1395 Node Adapter Board Troubleshooting 1395 Node Adapter Board Troubleshooting Specifications Electrical: Board power provided by Drive (+5V) Discrete Input 24V DC or 115V AC, jumper selectable Environmental: Ambient Operating Temperature Storage

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Operation Manual WARNING. Be sure to read this Operation Manual before use. Universal Space Amusement Equipment Ltd.

Operation Manual WARNING. Be sure to read this Operation Manual before use. Universal Space Amusement Equipment Ltd. WARNING Be sure to read this Operation Manual before use. Universal Space Amusement Equipment Ltd. CONTENTS 1. The company..2 2. Specifications.. 3 3. Package Contents..5 4. Installation, Fix and Transport..6

More information

INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps

INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST Model EIFM-5C For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since

More information

FUME HOOD CONTROLLER (FHC)

FUME HOOD CONTROLLER (FHC) CRITICAL CONTROLS - PRODUCT OVERVIEW FUME HOOD CONTROLLER (FHC) The FHC is designed to control face velocity on variable volume fume hoods with audible and visual indicating alarms. The Fume Hood Controller

More information

Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q

Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q AQUASNAP 30RB060-390 Air-Cooled Liquid Chillers with COMFORTLINK Controls 60 Hz Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q INDEX* POWER SCHEMATICS 30RB Unit Size Voltage Figure Number Label

More information

Type VR Electrically Operated Ground and Test Device

Type VR Electrically Operated Ground and Test Device Type VR Electrically Operated Ground and Test Device For Use with Masterclad Switchgear 4.76 kv 15 kv, 1200, 2000, 3000, 4000 A Up to 63 ka Short Circuit Rating Class 6055 Instruction Bulletin 6055-37

More information

Installation Manual Updated May 2017

Installation Manual Updated May 2017 Code No. LIT-12012114 Installation Manual Updated May 2017 JC-VSD Factory Packaged (FP) Series II drive frames 4 8, Type 1 and 3R Johnson Controls variable speed drives Disclaimer of warranties and limitation

More information

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95 Part 1 - GENERAL ASEA BROWN BOVERI ABB Industrial Systems Inc. Standard Drives ACH500-06E Effective 6/1/95 Sample Specification for Adjustable Frequency Drives (2 to 400 HP) for Variable Torque Applications

More information

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

ETM-2050/ETM-2051 Service Manual

ETM-2050/ETM-2051 Service Manual Introduction Novar s Electronic Thermostat Modules (ETMs) are intelligent control modules that provide local, direct digital control of unitary, packaged, staged HVAC systems. This document: Describes

More information

Nevco Message Center Installation Manual Retain this manual in your permanent file. 08/27/ Rev. C

Nevco Message Center Installation Manual Retain this manual in your permanent file. 08/27/ Rev. C Nevco Message Center Installation Manual Retain this manual in your permanent file. 08/27/2014 135-0144 Rev. C Table of Contents INSTALLATION INSTRUCTIONS... 1 UNPACKING THE EQUIPMENT... 1 MESSAGE CENTER

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

ST-PTZ High-Speed Intelligent Dome PTZ Color Camera

ST-PTZ High-Speed Intelligent Dome PTZ Color Camera INSTALLATION MANUAL ST-PTZ550-27 High-Speed Intelligent Dome PTZ Color Camera Copyright North American Cable Equipment, Inc. 1 PACKAGE CONTENTS This package contains: One ST-PTZ550-27 high-speed intelligent

More information

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018 Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018 Tags: P-8 1800RPM Premium Efficient Motor 460/3/60 Pump and Motor Weight: 183lbs

More information

MAKING MODERN LIVING POSSIBLE. Installation Guide. Twin Kit 086L

MAKING MODERN LIVING POSSIBLE. Installation Guide. Twin Kit 086L MAKING MODERN LIVING POSSIBLE Installation Guide 086L70 www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The

More information

SAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS OUTDOOR HARDWIRE INSTALLATION INSTRUCTIONS Please read and save these instructions. Read carefully before using product. Protect yourself and others by observing all safety information, warnings and cautions.

More information

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Constant Volume Technical Specification Sheet Document No. 149-852 September 24, 2014 Siemens BACnet Programmable TEC Constant Volume Returns from power failure without operator intervention. No calibration required,

More information

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ONE ARTIS ZEEGO / ZEEGO.ZEN ARTIS ZEE MULTIPURPOSE SINGLE PLANE IECAX480V125A Main Disconnect Panel Bevco Engineering

More information

Instruction Manual CTC-1

Instruction Manual CTC-1 Troubleshooting & Specs CTC-1 Amps / Volts requirements Min / Max operating temperature Min / Max operating Humidity Temperature Measurement range Temperature Accuracy CO2 sensor type CO2 Measurement range

More information

Installation, Start-up and Operating Instructions

Installation, Start-up and Operating Instructions Installation, Start-up and Operating Instructions EVOLUTION SMART SENSOR FOR ZONING Cancels: NEW II ZONESMS-0-1 7-04 NOTE: Read the entire instruction manual before starting the installation. This symbol

More information

99 Washington Street Melrose, MA Phone Toll Free Visit us at

99 Washington Street Melrose, MA Phone Toll Free Visit us at 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Table of Contents 1. General Safety Requirements... 1 2. Safety Terms and Symbols...

More information

Differential Liquid/Gas Pressure Transmitter

Differential Liquid/Gas Pressure Transmitter Installation Instruction Differential Liquid/Gas Pressure Transmitter Catalog Number(s) 1414-CPZ10FWFAA, 1414-IPZ10FWFAA Explosion Hazard WARNING Do not use in an explosive or hazardous environment, with

More information

BA/BS4S Temperature Sensor Installation & Operating Instructions

BA/BS4S Temperature Sensor Installation & Operating Instructions Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.

More information

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers DATA CENTER COOLING EXPERTISE Data Center managers have unique needs. Nortek Air Solutions listens

More information

Manual Simatek Control Unit GFC 32

Manual Simatek Control Unit GFC 32 Manual Simatek Control Unit GFC 32 Original instructions 1400004_GB Ver. 2014.01.09 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 August 12, 2011 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides high

More information

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions DIFFERENTIAL PRESSURE Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL

More information

SUPPLEMENTAL MANUAL FACTORY-INSTALLED LENZE AC TECH VARIABLE FREQUENCY DRIVES (VFD) IN RENEWAIRE (ERV) VENTILATORS TABLE OF CONTENTS

SUPPLEMENTAL MANUAL FACTORY-INSTALLED LENZE AC TECH VARIABLE FREQUENCY DRIVES (VFD) IN RENEWAIRE (ERV) VENTILATORS TABLE OF CONTENTS SUPPLEMENTAL MANUAL FACTORYINSTALLED LENZE AC TECH VARIABLE FREQUENCY DRIVES (VFD) IN RENEWAIRE (ERV) VENTILATORS LENZE AC TECH VFD TABLE OF CONTENTS VFD KEYPADS IN EBOX Product info... 2 Installation...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Adaptor Model No. CZ-CFUNC1U For your safety Read the following instructions carefully, and carry out secure installation and electrical work. The precautions given in this manual

More information

GOLANDER PUMP BQ80S Microflow Variable-Speed Peristaltic Pump Operation Manual

GOLANDER PUMP BQ80S Microflow Variable-Speed Peristaltic Pump Operation Manual GOLANDER PUMP BQ80S Microflow Variable-Speed Peristaltic Pump Operation Manual info@golanderpump.com http://golanderpump.com 1-678-587-8806 Contents 1 Safety Cautions... 1 2 Introduction... 1 3 Functions

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING Litho U.S.A. 2014 ECONOMIZERS 3/2014 Supersedes: New Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH 092-150 UNITS Application The Z1ECON30B-1 economizer

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016 SCC Inc. TS-MS Master Lead/Lag Panels for Boiler Management, and Building Management System Interface Technical Instructions March 15, 2016 Description A TS-MS Series Master Lead/Lag Panel sequences and

More information

Master Panel. Specifications. Document No. TS-2010 February 15, Product Description. Sample Specification

Master Panel. Specifications. Document No. TS-2010 February 15, Product Description. Sample Specification SCC Inc. Master Panel Product Description February 15, 2017 The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with

More information

Manual. ZIG-NANO Wireless Transmitter. Installation Maintenance Repair Manual CONNECTED ON:01

Manual. ZIG-NANO Wireless Transmitter. Installation Maintenance Repair Manual CONNECTED ON:01 Manual ZIG-NANO Wireless Transmitter Installation Maintenance Repair Manual CONNECTED ON:01 Advantage Controls P.O. Box 1472 Muskogee, OK 74402 Phone: 800-743-7431 Fax: 888-686-6212 www.advantagecontrols.com

More information

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W Differential Pressure Sensor (Air) Differential pressure transmitter with 8 selectable ranges 0 to 5/10 V, 4 to 20 ma outputs and Modbus functionality. NEMA 4X / IP65 rated enclosure. For monitoring the

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options Submittal Sheet SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options Description The Bypass Options are companion packages for the family of SED2 Variable Frequency Drives. For information

More information

ORB TM 4-20 ma Input Box Installation & Operation Manual

ORB TM 4-20 ma Input Box Installation & Operation Manual IOM ORB TM 4-20 ma Input Box Installation & Operation Manual ORB TM 4-20 ma Input Box Installation & Operation Manual CONTENTS I. HANDLING & STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

Installation Instructions

Installation Instructions Infinityt Series WiFi (Wireless) Broadband Remote Access Module Installation Instructions NOTE: Read the entire instruction manual before starting the installation. pointsett U.S. Pat No. 7,415,102 SAFETY

More information

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions

More information

TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE...

TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE... TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE... 2 1.0 General Information... 3 1.1 System Components... 3 1.2 Specifications... 3 1.2.1 Torque Ranges... 3 1.2.2 Electrical Specifications...

More information

ACH550 Product Overview

ACH550 Product Overview ACH550 Product Overview Description The ACH550 series is a microprocessor based Pulse Width Modulated (PWM) adjustable speed AC drive. The ACH550 drive takes advantage of sophisticated microprocessor control

More information

MODEL K INSTRUCTION MANUAL CONTENTS

MODEL K INSTRUCTION MANUAL CONTENTS MODEL 7173 - K INSTRUCTION MANUAL CONTENTS 1. MODEL 7173 - K ELECTRONIC FFU STEERING SYSTEM 2. MODEL 7173 - K COMPONENTS 3. MOUNTING THE 7173 - K AMPLIFIER UNIT 4. MOUNTING THE FFU CONTROLLER UNITS 5.

More information

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual Manual NanoTron Dual Timer Installation Maintenance Repair Manual Advantage Controls P.O. Box 1472 Muskogee, OK 74402 Phone: 800-743-7431 Fax: 888-686-6212 www.advantagecontrols.com email: support@advantagecontrols.com

More information

UPS READY POWER DISTRIBUTION ASSEMBLY

UPS READY POWER DISTRIBUTION ASSEMBLY UPS READY POWER DISTRIBUTION ASSEMBLY FOR TRAFFIC CABINETS with LED Signals INSTALLATION & OPERATOR S MANUAL VERSION 1.2 1 Note The instructions contained in this manual are not intended to cover all of

More information