TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY"

Transcription

1 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Version: 2 Issued: October 2017 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

2 Approval Amendment Record Approval Date Version Description 18/03/ Initial issue under MTM. Replaces MainCo document MESP0013. Corporate number changed from L2-ELN-SPE /10/ Restructured and revised throughout to emphasise required functionality over anticipated construction and improve alignment with standards. Arc fault containment requirements added. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 32

3 Table of Contents 1 Purpose Scope Abbreviations Definitions Standards Assembly Configuration Cubicle Configuration Operating Conditions Service Conditions Electrical Conditions Ratings Circuit Breaker Characteristics & Ratings Arc Chute Auxiliary Contacts Overcurrent Releases Operation Mechanical Indications Bus Tie Disconnection Facility Application General Interlocking Auxiliary Contacts Switchgear or Link Trucks General Truck Positions Truck Access & Interlocking Truck Isolation PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 32

4 13 Power Cable Connection General Terminal Requirements Positive Busbar V Positive Busbar Bus Measurement Transducers Negative Strip Short Circuiting Facilities Line Short Circuiting Facility Bus Short Circuiting Facility Fixed Short Circuit Switch Requirements Short Circuit Truck Requirements Short Circuiting Facility Requirements Short Circuit Switch Lighting Control, Protection & Measurement General Indicating Lights Control Switches Rectifier Control System Integration SCADA Interface Feeder Protection & Measurement System Protection Relay Requirements Measurement Transducers Protection Functions Contacts Wiring Test Links Construction General Labelling Testing Type Tests Control Circuits Power Frequency Voltage Withstand Arc Containment Type Test PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 32

5 19.2 Routine Tests Test Certificates Documentation and Support Collaboration Contract Documentation Design Documentation Delivery Documentation Design Drawings Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instructions Manual Training Material Tools & Equipment Documentation Requirements Drawing Format Appendix A Technical Data Schedule Form Compliance General DCCB Cubicles Bus Tie Disconnection Cubicles Control Supply Protection System DCCB Bus Tie Disconnection Facility Short Circuit Switches List of Tables Table 1: Cubicle Functionality... 7 Table 2: Assembly Ratings... 9 Table 3: Circuit Breaker Ratings... 9 Table 4: Circuit Breaker Auxiliary Contact Requirements Table 5: Disconnection Ratings Table 6: Cable Connection Requirements Table 7: Short Circuiting Facility Ratings Table 8: Control & Protection Functionality Table 9: Drawing Requirements PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 32

6 1 Purpose This document is the MTM technical specification for an indoor metal-clad 1500V DC switchgear assembly containing mechanical high speed DCCBs and disconnectors suitable for use in the MTM Electrical Network. 2 Scope This document applies to the supply of 1500V DC switchgear for use in new substation installations or for renewals of existing equipment on the MTM network. 3 Abbreviations ACCB - Alternating Current Circuit Breaker CT - Current Transformer/Transducer DCCB - Direct Current Circuit Breaker Electrol - Electrical Systems Control Centre MTM - Metro Trains Melbourne SCADA - Supervisory Control and Data Acquisition RTU - Remote Terminal Unit (of the SCADA system) VT - Voltage Transformer/Transducer 4 Definitions For technical terms refer to BS EN Bus Tie DCCB Feeder DCCB High Voltage Rectifier DCCB Shall Short-Circuit Switch Should means a High Speed Interconnector Circuit Breaker in conformance with BS EN (H/I) means a High Speed Line Circuit Breaker in conformance with BS EN (H/L/U 1 ) means (for the purposes of these procedures), a difference of potential normally existing between conductors and conductors and earth of 650V and above (AC or DC) means a High Speed Rectifier Circuit Breaker in conformance with BS EN (H/R/U 1 ) is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. is a fault-make switch used to connect a line or bus to negative. is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. should can also be used if a requirement is a design goal but not a mandatory requirement. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 32

7 5 Standards The assembly shall comply with BS EN Railway Applications Fixed Installations DC Switchgear. All materials and components shall comply with the relevant Australian Standard or, where these do not exist, shall comply with the relevant IEC or EN standard. Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. 6 Assembly Configuration The switchgear assembly shall consist of a number of Feeder DCCB, Rectifier DCCB, Bus- Tie DCCB, and Bus-Tie DC Disconnection cubicles. The number of each type of cubicle in an assembly is dependent on the site configuration and will be described in a specific scope of works document. 7 Cubicle Configuration Each cubicle shall be self-supporting, floor mounted, and metal-clad, containing all of the components necessary for the proper operation of the equipment. Each cubicle shall contain at least the four following metallically partitioned compartments: switchgear compartment control compartment busbar compartment power cable connection compartment The functionality required within each cubicle is dependent upon the type of cubicle and is shown in the table below: Table 1: Cubicle Functionality Feeder DCCB Cubicle Rectifier DCCB Cubicle Bus Tie DCCB Cubicle Withdrawable DCCB Bus Tie Disconnection Facility Bus Tie DC Disconnection Cubicle Positive Busbar Power Cable Connection Line Short Circuiting Facility Control, Protection & System Preferred A bus voltage transducer and busbar short circuiting facility shall be provided for each assembly. These may either be provided in a dedicated cubicle, or within a single Feeder DCCB cubicle, designated the Master Feeder. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 32

8 8 Operating Conditions 8.1 Service Conditions The Assembly will be installed indoors in a railway traction substation or tie station building. The normal indoor service conditions as detailed in Clause 4 of BS EN :2003 shall apply, except that the absolute maximum ambient temperature (Θ a ) shall be taken to be 45 C. The nominated performance of all components and devices shall be guaranteed at this ambient temperature. 8.2 Electrical Conditions The Assembly will be used to supply 1500V DC power to trains on the MTM network. This electrical network consists of traction substations and tie-stations and a 1500V DC overhead contact wire distribution system. The substations contain rectifier units with continuous power ratings of between 1.5MW and 4.0MW. The voltage of the 1500V DC network at the substations and tie-stations typically varies between 1000V DC and 1800V DC. The overhead contact wire distribution system typically consists of sections between 2 and 5 km in length. It is susceptible to lightning and short-circuits, typical of this type of construction and use. The maximum prospective fault current of the 1500V DC network adjacent to a substation is typically in the range of 30,000 A to 120,000 A. The time constant of the fault current is generally in the range of 5 to 20 milliseconds. The maximum prospective fault current through the Feeder DCCBs for a fault at the distant end of an overhead section is typically in the range of 3,000 A to 15,000 A with a time constant of 15 to 50 milliseconds. The assembly enclosure will typically be electrically insulated from the floor, and connected to the substation 1500V DC negative bus at a minimum of two points. Alternatively it may be insulated from the floor and connected to the substation earth via a single frame leakage relay for the assembly. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 32

9 9 Ratings The assembly shall comply with the following minimum ratings: Table 2: Assembly Ratings Rating Requirement Nominal Voltage 1,500V Service Current 4,000A Overload Duty Cycle 200% for 1 minute, preceded and followed by 100% continuously Insulation Voltage 3,000V Power Frequency Withstand 9,200V at 50Hz Impulse Withstand Voltage 20,000V Power Frequency Withstand across an isolation 11,000V at 50Hz Impulse Withstand Voltage across an isolation 24,000V Control Voltage 48V DC (preferred), 110V DC or 125V DC Minimum clearance between positive and negative conductors 36mm Minimum clearance between positive conductor and frame 36mm Minimum clearance between negative conductor and frame 36mm The assembly shall be arc fault contained it shall attain IAC AFLR in accordance with AS The internal arc shall be 125kA for 0.25s. 10 Circuit Breaker 10.1 Characteristics & Ratings The DCCB shall be a single pole high-speed current limiting circuit breaker which shall comply with BS EN The interrupting medium shall be air. The DCCB shall be trip-free and fail-safe. It shall be withdrawable and truck mounted (refer section 11 for requirements), located within the switchgear compartment. The DCCB shall comply with the following ratings: Table 3: Circuit Breaker Ratings Rating Requirement Maximum Arc Voltage 6,000V Rated Short Circuit Current 125 ka Rated Track Time Constant 63ms Mechanical Endurance without replacement of parts 20,000 operations Test Duty Cycle Duty 2 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 32

10 10.2 Arc Chute The arc chute of the DCCB shall be mounted on the circuit breaker. It shall be attached to the circuit breaker with hinges for ease of inspection and maintenance. The arc chute shall be able to be lifted/opened easily for inspection or maintenance by one person without any special tools or lifting devices and without removal of any other parts of the DCCB or its truck Auxiliary Contacts The following number of voltage free auxiliary contacts shall be provided on the respective circuit breakers, in addition to those required for operation and local indication. Table 4: Circuit Breaker Auxiliary Contact Requirements No. Of Auxiliary Contacts Circuit Breaker Type Normally Open Normally Closed Feeder DCCB 3 3 Rectifier DCCB 6 6 Bus-Tie DCCB Overcurrent Releases Feeder DCCBs shall be fitted with a direct acting series overcurrent release which shall be uni-directional, operating on current flowing away from the busbar, towards the load. The release shall have a setting range between 3,000 and 8,000 amperes in 500 ampere steps. Rectifier DCCBs shall automatically trip by a uni-directional direct acting series overcurrent release. The uni-directional release shall operate on a current flowing away from the busbar, towards the rectifier. The release shall have a single setting which shall be as low as practicable and shall not exceed 2,000 amperes. Bus-Tie DCCBs do not require a direct acting overcurrent release Operation The DCCB shall be able to be manually and electrically opened and shall be able to be electrically closed. The manual opening of the DCCB shall be performed from the front of the cubicle with all doors closed and shall be achieved by depressing a trip button coloured red Mechanical Indications A mechanical indication of the open/closed status of the DCCB and the truck position shall be visible from the front of the cubicle at a reasonable height above floor level. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 32

11 11 Bus Tie Disconnection Facility 11.1 Application The disconnection facility is provided within the switchgear compartment for connecting multiple 1500V DC buses together. On one busbar, a bus tie DCCB will be provided, and on the other, a bus tie disconnection facility, with a cable connection between the two General The bus tie disconnection facility shall be comprised either of a withdrawable link truck or a fixed mounted single pole DC Disconnector. Fixed disconnectors shall be able to be manually operated from the front of the cubicle with the compartment door closed. The disconnection shall comply with the rated values shown in Table Interlocking Table 5: Disconnection Ratings Rating Service Current Minimum Clearance Across Isolation Requirement 4,000A 43mm The bus tie disconnection facility shall be either electrically or key interlocked with its corresponding bus tie DCCB to prevent it being used to make or break current Auxiliary Contacts There shall be 3 normally open and 3 normally closed voltage free auxiliary contacts provided on the disconnection facility, in addition to those required for local indication. 12 Switchgear or Link Trucks 12.1 General Trucks shall be provided for DCCBs and may be used for bus tie disconnection facilities and/or bus short circuiting facilities. The trucks shall be inserted into the switchgear compartment. Each truck shall be provided with ergonomically designed and positioned handles for positioning and moving. All trucks of the same type shall be interchangeable. Trucks of different types shall not be interchangeable, e.g. a Rectifier DCCB truck shall not be able to be inserted into a Feeder DCCB cubicle. Trucks shall be clearly marked with their type in accordance with MESP Substation Signage and Labelling. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 32

12 12.2 Truck Positions The truck shall have three positions: the service position, the test position and the disconnected position. In the test position, only the power circuit shall be disconnected to permit off-load testing of the DCCB and the control and protection system. In the disconnected position, the truck may be removed completely from its compartment and the control circuitry shall also be disconnected Truck Access & Interlocking The switchgear compartment shall be provided with an interlocked front door. Alternatively the compartment door may be integrated into the truck. The interlock shall prevent movement of the truck or opening of the door if the DCCB is not open and prevent the DCCB from closing when not properly positioned in the service, test or disconnected position. The compartment shall be provided with automatic shutters to separate the compartment from the busbar and the power cable connection when the truck is not in the service position. The shutters shall be made of a transparent insulating material to allow a visual inspection of the fixed contacts. The shutters shall be lockable in the closed position using a safety padlock, which shall prevent a truck from being racked in. It shall be possible to place a padlock to prevent a truck being placed into the service position Truck Isolation In both the test and disconnected positions, an isolation shall be provided between the DCCB and both the bus and the line, and between the bus and the line. Both the bus and line shutters shall be closed. The power frequency withstand across the isolation shall be a minimum of 11,000V at 50Hz and the impulse withstand voltage shall be a minimum of 24,000V. 13 Power Cable Connection 13.1 General The power cable connection facilities shall be provided within the power cable connection compartment. It shall be possible for the power cable to enter the cubicle from below or above the assembly. The compartment shall contain a facility for the connection of cable screens to the negative bus. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 32

13 13.2 Terminal Requirements The terminal shall be suitable for the termination of the following number of power cables: Table 6: Cable Connection Requirements Cubicle Type No. of Cables Feeder DCCB 6 Rectifier DCCB 8 Bus-Tie DCCB 8 Bus-Tie DC Disconnection 8 The standard type of cable used is 500 mm² aluminium conductor, 3.8/6.6 kv XLPE insulated, 90 mm² copper screened and PVC/HDPE sheathed cable, terminated with appropriate cable lugs. The cables may be connected back to back. Holes shall be drilled in the terminal suitable for connection of lugs as shown in Figure 1 below. 14mmØ >70mm 20mm 50mm Figure 1: Cable Lug An allowance of 400 mm length to a gland or cable support should be made for the cable termination. Appropriate brackets and clamps shall be provided to adequately support the cables in the compartment so that the weight of the conductor is not taken by the terminal or lug. Sufficient clearance shall be provided between the cable screens and positive conductors, and between cable screens and the switchgear frame such that the minimum clearance distance of 36mm as specified in Table 2 is not compromised, allowing for installation tolerances. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 32

14 14 Positive Busbar V Positive Busbar Each cubicle shall contain a single busbar, mounted in the busbar compartment. The busbar shall be designed to facilitate simple connections between any two adjacent cubicles Bus Measurement Transducers A bus voltage transducer (VT) shall be provided in the busbar compartment of one cubicle per bus, for connection to protection and measurement systems. The VT should be accessible from the front of the cubicle. 15 Negative Strip A negative strip shall be provided through the assembly in the power cable connection compartments. It shall be insulated from the cubicle frame but provided with facility for connection in each cubicle. The negative strip shall be able to be simply connected or disconnected to adjacent cubicles at the cubicle edges, similarly to the positive busbar. It shall be painted mid blue in accordance with AS 2700S:2011 (B15). The negative strip shall be of a minimum cross sectional area of 185mm 2 and shall be capable of carrying 125kA fault current for 0.25s. The negative strip shall be constructed so as to facilitate the connection of cable screens to the strip without any modification required. 16 Short Circuiting Facilities 16.1 Line Short Circuiting Facility A fault make short circuiting facility shall be provided to short circuit the line/power cable connection in each DCCB cubicle. This shall be provided in the form of a fixed fault make short circuit switch or other fixed fault make arrangement, complying with the requirements in section Interlocking shall be provided to ensure that it is impossible to apply a short circuit when the line is not isolated from the bus. It shall not be possible to remove the isolation between bus and line while the short circuit is applied. On Feeder DCCBs, the short circuiting facility shall be electrically interlocked to prevent the application of a short circuit onto a live line. The short circuit shall be able to be manually applied and removed locally. It shall be possible to utilise a safety padlock to prevent the short circuit being removed. It shall be possible to remotely electrically short circuit the line on Feeder DCCB cubicles through one or more control operations. It shall be possible to remotely electrically remove the short circuit. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 14 of 32

15 16.2 Bus Short Circuiting Facility A fault-make busbar short-circuiting facility shall be provided for the assembly. This facility should be fixed mounted switch in a dedicated compartment in accordance with section , however a Bus Short Circuiting Truck which can rack into a Feeder DCCB cubicle (in place of the circuit breaker truck) may be acceptable in accordance with section The facility shall comply with the requirements in section The short circuit shall be able to be manually applied and removed locally. It shall be possible to utilise a safety padlock to prevent the short circuit being removed Fixed Short Circuit Switch Requirements The short circuit switch shall be interlocked with all DCCB trucks and disconnectors on the bus. It shall only be able to be closed when all trucks are in the test or disconnected position and all disconnectors are locked in the open position. It shall not be possible to move any trucks to the service position or to close a disconnector when the bus short circuit switch is closed Short Circuit Truck Requirements The short circuit switch shall be interlocked with its truck, and shall only be able to be racked into and out of the service position with the short circuit switch open. The truck shall be painted red and labelled Bus Short Circuiting Switch Short Circuiting Facility Requirements The short circuiting facility shall achieve the ratings specified in Table 7: Table 7: Short Circuiting Facility Ratings Rating Line Short Circuiting Bus Short Circuiting Rated Making Capacity 50kA 125kA Rated Short Time Withstand Current 50kA for 0.1s 125kA for 0.25s It should be possible to directly view the contacts required to make the short circuit from the front of the assembly. Where the contacts are not visible from the front of the cubicle, mechanical semaphores shall be provided at the front of the cubicle. Where the contacts are directly visible, but not easily able to be viewed using only ambient light, internal lighting shall be provided in accordance with section Where a mechanical semaphore is provided, it shall be connected to the contacts by a direct and simple mechanical linkage. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 15 of 32

16 16.4 Short Circuit Switch Lighting The illumination shall be provided by a double insulated non-metallic light fitted to the compartment. The light shall be able to be switched from outside the cubicle and should operate on a timer. A single switch may be provided on the assembly to switch all of the illumination lights. 17 Control, Protection & Measurement 17.1 General Each cubicle shall include a control system. The control system components shall be located so far as practicable within the control compartment at the front of the cubicle. Access to the compartment shall be by a hinged, dustproof door with a non-locking handle. The following components shall be located or viewed from the front of the compartment: Control Switch (Device 72CS) Indicating Lights C & I Isolating Switch (Device 230) or Local/Remote Switch (Device 72LR) Protection Relay (Device 76) All other equipment shall be mounted inside the compartment. The control system shall be designed such that all external connections (for example, to the substation battery or SCADA system) are isolated or insulated to 2kV from the switchgear frame. All connections to high voltage equipment shall be insulated to 2kV from both the positive and negative conductors. The control system should be provided using relay logic - the use of PLCs is not preferred. The functionality required for each cubicle is described in Table 8 below. Table 8: Control & Protection Functionality Feeder DCCB Cubicle Rectifier DCCB Cubicle Bus Tie DCCB Cubicle Bus Tie DC Disconnection Cubicle Indicating Lamps Control Switches Rectifier Control System Integration SCADA Interface Feeder Protection & Measurement System PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 16 of 32

17 17.2 Indicating Lights Indicating lights shall be provided to indicate: Open (green) and Closed (red) position of the DCCB or DC Disconnector, Line Short Circuited (blue), Line Alive (red), and Bus Alive (red) (one per bus). They shall be provided by long life, high reliability, and replaceable LED lights. A lamp test facility shall be provided. A single pushbutton should be provided for testing all lights in the assembly. The open and closed indications of the DCCB and DC Disconnector shall be provided using dedicated auxiliary contacts Control Switches Each DCCB shall be locally controlled by a control switch on the compartment door. It shall be a spring return to neutral type with a pistol grip handle. The two positions shall be labelled Trip and Close. The switch shall be turned anticlockwise to trip and clockwise to close. For Feeder and Bus Tie DCCBs, a two position C & I Isolating Switch with a yellow escutcheon shall be provided to isolate the control and indication functions (by breaking the common) of the DCCB and DC Disconnector from the RTU. The switch shall also isolate the control function of the line short circuiting facility. The switch positions shall be labelled Isolated and Normal. For Rectifier DCCBs, a two position Local/Remote Switch shall be provided to enable or disable operation of the DCCB as a slave of the corresponding Rectifier ACCB. In the Remote position, the local control switch shall be disabled, and in the Local position, remote control shall be disabled Rectifier Control System Integration The Rectifier DCCB shall act as a slave of the Rectifier ACCB. The Rectifier DCCB shall be closed by the successful closing of the Rectifier ACCB and opened by the opening of the Rectifier ACCB. It shall be provided with a single normally open auxiliary contact of the Rectifier ACCB to achieve this functionality. Tripping of the Rectifier DCCB via its direct acting overcurrent release shall cause lockout of the rectifier unit. This functionality shall be provided by the Rectifier Unit Control System via an auxiliary contact, in accordance with MESP Technical Specification for a Rectifier Unit Control & Protection System for use in the 1500V DC Traction System. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 17 of 32

18 17.5 SCADA Interface Each cubicle shall include a SCADA interface. All points that are to be controlled by or indicated to the SCADA system shall be connected by a 3-wire system in accordance with MESP Technical Specification for SCADA Cabling in Substations Each point to be controlled shall be operated via interposing relays. The relay coils of each controlled point shall be connected to an independent common. The current consumption of the Interposing Relay coil shall be ma at the Control Voltage. The SCADA RTU provides a 1 second duration pulse to the Interposing Relay. Hardwired indications shall be provided as pairs of voltage free contacts, such that failure is indicated by an invalid combination. Each point shall have its own independent common connection Each point that is both controlled and indicated shall be brought to sequential terminals on a terminal strip. The following indications must be provided as hard wired points: DCCB or Disconnector position Line Short Circuit Switch position Line Alive Protection Relay Healthy Bus Alive Bus Short Circuit Switch position (if fixed) 17.6 Feeder Protection & Measurement System Each of the Feeder DCCB Cubicles shall be provided with a measurement and protection system. This system shall comply with EN : Measurement, Control and Protection of DC Traction Systems - Section 1: Application Guide. The system shall be microprocessor based, and shall have a user-friendly interface. It shall provide line current and line voltage measurements, and the protection functions listed in section Since there is no backup protection provided, the system shall be failsafe. Failure of any of the following shall cause the DCCB to trip: Loss of control supply Failure of protection relay Failure of CTs or VTs PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 18 of 32

19 Protection Relay Requirements The protection relay shall be a digital multifunction DC protection relay with multiple, selectable setting groups. As a minimum, the protection functionality described in section shall be provided, with each function able to be selected to either provide a trip or an alarm. It shall have a self-testing watchdog function, which shall provide an alarm if there is a failure of the system or any of its component functions, including a loss of connection to the measurement transducers. Failure of any critical part of the system shall cause tripping of the DCCB. The relay shall permanently record the number of each type of trip given to the DCCB. The most recent trips (minimum 20) shall be recorded together with the measured voltages and currents at the time of tripping. The relay shall provide oscillographic recordings, able to be configured to trigger from any combination of the protection functions provided. The recordings shall include the value of all analogue measurements and digital inputs and outputs. The relay shall store a minimum of 10 recordings of 0.3 seconds each in duration. The relay shall have an integrated display and use a plain language menu system. The display shall provide indications of the current line current and voltage measurements, and allow for viewing of the most recent events and alarms. It shall be possible to enable and disable protection functions and alter protection settings from the integrated display. Software and an appropriate interface shall be provided for interacting with the protection relay from a computer. Software and access shall be provided for MTM to make changes to all settings and configure the protection system as required. It shall be possible to view all data and view or modify all settings within the protection relay from the software provided. The relay shall communicate with the SCADA RTU using a suitable protocol over a serial or Ethernet interface over optic fibre. The preferred protocol is DNP3. It shall be possible to remotely set the relay s clock via the SCADA communication protocol. The following indications shall be provided as soft points as a minimum: Line voltage Line current Bus voltage Measurement Transducers Current and Voltage Transducers shall be provided for connection to protection and measurement systems. These shall comply with EN , sections 2 and 3 respectively. The Line CTs and VTs should be located on the DCCB truck to facilitate ease of access and maintenance. Where CTs and VTs are located within the cubicle, they shall not be located within the busbar or control compartments. It shall be possible to easily access VT fuses from the front of the cubicle. The CTs and VTs shall be isolated to a minimum of 9kV from associated measurement and protection devices. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 19 of 32

20 Protection Functions The protection functions provided by the protection relay in addition to the direct acting releases on the DCCBs shall include the following as a minimum: Uni-Directional Falling Voltage Overcurrent / Instantaneous Impedance Trip The uni-directional falling voltage overcurrent characteristic images the resistance of the overhead network section. It shall be possible to set a section resistance (R) and arc voltage (V a ) and have the relay issue a trip command instantaneously where RR VV VV aa. II 1500V DC Under-Voltage Release The 1500V DC under-voltage release shall cause a trip when the bus and line voltages drop below a set value. The setting shall be adjustable between 100V and 800V and should have a hysteresis characteristic. It shall be failsafe. Thermal Overload The thermal overload setting is an inverse-time overcurrent characteristic that images the thermal characteristics of the overhead wiring. The characteristics of the thermal curve shall be adjustable. Rate of Rise (di/dt) and ΔI Protection The protection functionality described in Annex B of EN :2003 shall be available within the protection relay. Control Voltage Under-Voltage Release The control voltage under-voltage release shall trip when the control voltage is insufficient to guarantee the correct operation of the circuit breaker and the measurement and protection system. It shall be failsafe. Circuit Breaker Failure The system shall have a function that checks the resultant opening of the DCCB. If the DCCB does not open, a backup tripping system shall be initiated. This may involve other DCCBs. Automatic Reclosure An automatic reclosure function shall be provided for Feeder DCCBs that should operate when both the bus voltage and line voltage are normal after an automatic trip, provided there has not been a control trip. The function shall be able to be switched on and off by the SCADA System Contacts All auxiliary contacts of switchgear and contacts of control relays for connection to external devices shall be suitable for carrying 20A and breaking 5A at the control voltage. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 20 of 32

21 17.8 Wiring All conductors used for control voltage secondary wiring shall be stranded and have a cross sectional area of not less than 1.5 mm². A system of permanent labelling for identification of all cables shall be used in accordance with MESP The label shall appear on each end of each wire. The label shall be securely attached to the cables and be easily readable. The control and auxiliary terminations for connection to external circuits shall be provided at a convenient and accessible position inside the Control Compartment Test Links Test links shall be provided to facilitate testing of the control, protection and measurement system. The preferred test link types are Phoenix URTK/S slide links or Weidmüller WT series test terminals. As a minimum, test links shall be provided for all inputs/outputs of the protection relay. Links shall be mounted such that the field/primary system/earth connection is physically located on the right side, or the bottom side of the terminal rail. The device/secondary connection shall be located on the top or left side. Slide links shall be opened by sliding towards the top or left. 18 Construction 18.1 General The assembly shall be constructed in such a manner that any cubicle can be removed from the assembly, and in particular, if an internal arcing fault develops inside a cubicle it shall not damage the adjacent cubicles and shall not prevent the cubicle from being subsequently removed. The assembly shall be as compact as possible. It is desirable that the switchgear is constructed such that all installation and maintenance tasks are able to be completed from the front of the cubicle. The assembly shall provide a minimum ingress protection of IP 21 in accordance with AS on all accessible faces, with the circuit breaker trucks in any position. The top of the switchgear shall be constructed so as to prevent the ingress of dust a horizontally mounted mesh shall not be used. All metalwork shall be suitably prepared and painted to protect it against corrosion for the expected life of the equipment. The method shall be submitted and shall be approved in writing. The external colour shall be mid blue in accordance with AS 2700S:2011 (B15). Where provision is made for padlocks, the holes for the padlocks shall be 10 mm in diameter. A lifting facility shall be provided for each cubicle. The entire assembly (including all trucks, interrupters and cubicles) shall contain no asbestos or materials containing asbestos fibres. A statement certifying that the product is free of asbestos containing materials must be completed and signed, and shall be delivered to MTM prior to despatch. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 21 of 32

22 18.2 Labelling All cubicles, compartments, control switches, components and indicators shall be labelled in accordance with MESP Substation Signage and Labelling and have appropriate warning signs. The external labels shall be of the Traffolyte type and shall be fastened by screws. Each cubicle will be assigned a section number as part of the 1500V DC traction supply system. 19 Testing 19.1 Type Tests The Feeder, Rectifier and Bus-Tie DCCBs, Bus Tie Disconnection Facilities, and Short Circuiting Facilities shall have type test certificates complying with BS EN The tests shall be performed with the device in its cubicle and all power cables connected. The certificates shall include oscillograms and drawings of the test circuit. Copies of these certificates shall be supplied with the tender documentation. The following type test certificates shall be provided as a minimum: DCCBs: o Verification of conformity (clause of EN ), o Mechanical operation (clause of EN ), o Impulse withstand voltage (clause of EN ), o Power frequency withstand voltage (clause of EN ), o Temperature rise (clause of EN ), o Electrical endurance (clause of EN ), o Mechanical endurance (clause of EN ), o o o o o Verification of DCCB making and breaking characteristics (clause of EN ), Verification of short time withstand current of rectifier DCCB (clause of EN ), Verification of behaviour under short time withstand current (clause of EN ), Verification of the adjustment of relays and releases (clause of EN ), and Search for critical currents and low current test duty (clause of en ). Fixed Disconnectors and Short Circuit Switches o Verification of conformity (clause of EN ), o Mechanical operation (clause of EN ), o Impulse withstand voltage (clause of EN ), PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 22 of 32

23 o Power frequency withstand voltage (clause of EN ), o Temperature rise (clause of EN , for fixed disconnectors only), o Mechanical endurance (clause of EN ), o o Verification of behaviour under short time withstand current (clause of EN ), and Verification of the sturdiness of manual control device and reliability of position indicator (clause of EN ). Short Circuiting Facilities: o o Verification of the rated making and breaking capacities (clause of EN ), Verification of behaviour under short time withstand current (clause of EN ), and o Verification of the reliability of position indicator (clause of EN ). Assembly: o Verification of conformity (clause of EN ), o Operation (clause of EN ), o Impulse withstand voltage (clause of EN ), o Main circuits power frequency voltage withstand (clause of EN ), o Control circuits power frequency voltage withstand (refer section ), o Short time withstand current main circuits (clause of EN ), o Short time withstand current busbars (clause of EN ), o Short time withstand current earthing circuits (clause of EN ), o Mechanical operation (clause of EN ), o Verification of degree of protection (clause of EN ), o Temperature rise (clause of EN ), o Electrical operation (clause of EN ), and o Arc containment (refer section ) Control Circuits Power Frequency Voltage Withstand Tests shall be conducted generally in accordance with clause of EN , with the voltage applied between the control wiring, and the positive and negative busbars and cubicle frame. A minimum voltage of 2kV shall be applied for 60s. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 23 of 32

24 Arc Containment Type Test Type testing shall be conducted in accordance with Annex A of AS :2005. Tests shall be conducted with the control compartment door open. The test current shall be DC Routine Tests Access shall be AFLR, that is, authorised persons only, to the front, rear and sides of the assembly. The assembly shall be subjected to routine tests at the manufacturer s workshop complying with EN 50123, which shall include the following tests as a minimum: DCCBs: o Verification of conformity (clause of EN ), o Mechanical operation (clause of EN ), o o Power frequency withstand voltage (clause of EN ), and Verification of the adjustment of relays and releases (clause of EN ). Fixed Disconnectors and Short Circuit Switches o Verification of conformity (clause of EN ), o Mechanical operation (clause of EN ), and o Power frequency withstand voltage (clause of EN ). Assembly: o Verification of conformity (clause of EN ), o Operation (clause of EN ), o Main circuits power frequency voltage withstand (clause of EN ), and o Control circuits power frequency voltage withstand (refer section ). The Control, Protection and Measurement System shall be tested in accordance with a test plan approved by MTM. MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out routine testing. A chart of the direct acting series overcurrent release calibration charts for the full range of all settings shall be provided for every DCCB. A calibration chart showing the full range of settings shall be provided in a suitable location on the DCCB truck Test Certificates The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations. The routine test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 24 of 32

25 20 Documentation and Support 20.1 Collaboration The manufacturer should work collaboratively with MTM to refine and further develop their product to meet MTM s unique requirements Contract Documentation One set of PDF copies of the drawings and documentation described in sections 20.5 and 20.8 should be provided for review and approval by MTM approximately 4 weeks after the contract award date. No manufacture shall commence until the drawings have been approved. An allowance of ten working days should be made by the supplier for the review of submitted drawings 20.3 Design Documentation A hard copy and a soft copy of the following documentation shall be provided to MTM for every design of switchgear cubicle produced at the conclusion of design, and prior to delivery of the switchgear: Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instruction Manual Storage, handling, loading and off-loading instructions Approved drawings Training Material Whenever a design change is made, new copies of the updated design documentation shall be provided to MTM Delivery Documentation Each delivery shall include a hard copy of the following documents: Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instruction Manual Storage, handling, loading and off-loading instructions Test Certificates Approved drawings In addition, a soft copy of the test certificates shall be forwarded to MTM. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 25 of 32

26 20.5 Design Drawings The drawings described in Table 9 shall be provided to MTM at the nominated design stages for review, and at the completion of design. Drawing Table 9: Drawing Requirements Construction details of the Assembly including dimensions. Physical layout and arrangement of the components of the Assembly. Physical layout and arrangement of the DCCB and Disconnection Cubicles. Physical layout and arrangement of the Short-Circuit Facilities. The interlocking arrangement of the Trucks, DCCBs, Disconnectors and Short-Circuit Switches. Concept / Tender Preliminary Design Detailed Design Mounting requirements for the Assemblies. Control circuit diagrams of each Cubicle. Physical layout and arrangement of the Power Cable Connections. Details of control and auxiliary wiring terminations. Details of the 1500V DC Negative strip. Details of manual operation of the equipment and any tools to be provided. All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance 20.6 Technical Maintenance Plan A Technical Maintenance Plan which establishes the maintenance policy for the Assembly recommended by the supplier shall be provided. This shall detail the preventative servicing schedules and maintenance intervals for all components of the Transformer. The servicing schedules shall reference appropriate detailed instructions in the maintenance manual. The Technical Maintenance Plan shall contain a list of any spare parts, suppliers, indicative pricing, lead times and recommended spares holdings. The Technical Maintenance Plan shall detail safe disposal procedures applicable for when the Assembly is no longer serviceable (recycling, hazardous waste etc.). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 26 of 32

27 20.7 Maintenance Manual A Maintenance Manual shall be provided which shall detail: The theory of operation of the equipment. All servicing activities. Overhaul instructions. Adjustment procedures. The changing of components for repairs. Fault-finding procedures. The spares support schedule. The maintenance manual shall also include a complete set of as-built drawings and a comprehensive parts list for the Assembly. The maintenance manual shall include an instruction manual of the Control, Protection and Measurement System which details all of the viewing, setting, modification of settings, the viewing of currents and the recording of events and alarms Installation Instruction Manual An Installation Instruction Manual shall be provided The instructions shall enable the assembly to be properly installed, tested and commissioned. This shall include all necessary drawings Operating Instructions Manual An Operating Instruction Manual shall be provided which shall clearly describe the required procedures for physically operating all of the components of the Assembly. The operating procedures shall be consistent with MTM s requirements Training Material An operator training package and a maintainer training package shall be provided for the switchgear including the necessary audio-visual resources and suitable packages of the relevant information. The supplier shall provide training to MTM s nominated trainers Tools & Equipment A complete set of operating tools and any other equipment necessary to operate and maintain the assembly shall be provided with each assembly. This shall include any special device required to test the assembly. Storage facilities for the tools and equipment shall also be provided. The software and a PC interface for loading and downloading of settings and the latest fault current data to a laptop PC shall be provided. This shall include all peripheral interfacing equipment and connection cables necessary to connect and communicate with the system. Any special lifting and installation equipment shall be supplied with the assembly. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 27 of 32

28 20.12 Documentation Requirements All documentation shall be provided in English. Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multi-page documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present. Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders. Electronic copies of the Maintenance Manual, Installation Instructions Manual and Operating Instructions shall be provided in both PDF and Microsoft Word formats Drawing Format All drawings shall comply with PTV Infrastructure Drafting Standard and shall be submitted for MTM approval prior to manufacturing. Drawings shall be provided in Microstation format and PDF. One electronic and a minimum of two paper copies of the each document shall be provided and the content shall be identical in each copy. 21 Appendix A Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance thereof Compliance a. Does the Assembly fully comply with this Specification? YES / NO b. If not, has a list of non-compliances with justifications been provided? YES / NO c. Are type test certificates attached, including oscillograms? YES / NO d. Are general arrangement drawings attached, clearly showing the overall dimensions of the assembly and each cubicle, and details of the proposed cable terminals and cable entry requirements? YES /NO e. Are preliminary control circuit drawings attached? YES / NO f. Have relevant pamphlets and technical information for the DCCB been attached? YES / NO g. Have relevant pamphlets and technical information for the protection system been attached? h. Is an analysis of the mean time between failures (MTBF) causing the unavailability of failure of a Feeder DCCB cubicle including an analysis to the component/device level attached? YES / NO YES / NO i. Is a list of recommended spare parts, holdings and costs attached? YES / NO j. Is an explanation of the interlocking and padlocking facilities included? YES / NO PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 28 of 32

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Specification Electrical Networks L1-CHE-SPE-128 Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Version: 1 Issued: February 2016 Owner: Head of Engineering - Electrical Approved

More information

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

11 kv Indoor Switchgear - SCADA Controlled

11 kv Indoor Switchgear - SCADA Controlled Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Switch Disconnectors, Main and EMERGENCY-STOP Switches General data Overview Siemens G 2010 1 2 3 NSE0_01931b 4 5 6 7 1 uxiliary switch (3SB for 3K; 3KX for 3KE) 2 IP20 terminal cover (Operator side) 3 3K switch disconnector 4 rcing contacts (only for 3KE)

More information

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD. (INDIA) VT. LTD. 5. INCOMING SULY CONDUCTOR TERMINATIONS AND DEVICES FOR DISCONNECTING AND SWITCHING OFF 5.1 Incoming supply conductor terminations The electrical equipment of the machine shall have only

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

Innovation on Medium Voltage Switchgear

Innovation on Medium Voltage Switchgear Bruno Rivas, Guarulhos - Brazil, April 2015 Jornadas Técnicas de ABB en Chile Innovation on Medium Voltage Switchgear May 13, 2015 Slide 1 Application 13. Mai 2015 Slide 2 PPMV Brazil Factory Unigear Insourcing

More information

CENTERLINE 2500 Motor Control Centers

CENTERLINE 2500 Motor Control Centers CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A.

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A. www.moeller.co.uk Mini Panel Board Cost-effective, space-saving board up to 400A Product Catalogue and Selection Guide Mini Panel Board Miniature Circuit Breakers Moulded Case Circuit Breakers XBoard Consumer

More information

DC Substations / Supply Program

DC Substations / Supply Program DC Substations / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles and systems

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution s Sentron 3VT circuit breakers Simply Smart: First choice for power distribution www.siemens.com/industry Sentron 3VT Molded Case Circuit-Breakers - 10-1600Amperes With the standard line of 3VT molded-case

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Air-insulated medium-voltage secondary distribution switchgear

Air-insulated medium-voltage secondary distribution switchgear DISTRIBUTION SOLUTIONS Air-insulated medium-voltage secondary distribution switchgear Compact size Complete solution Factory tested Air-insulated medium-voltage secondary distribution switchgear The ABB

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 489 DIN Rail Miniature Circuit Breakers Product Overview................................................ 2 Product Selection................................................ 4 Accessories.....................................................

More information

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 9 DIN Rail Miniature Circuit Breakers Product Overview................................................ Product Selection................................................ Accessories.....................................................

More information

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors 6/4 Introduction 6/5 5TE8 control switches 6/7 5TE4 8 pushbuttons 6/9 5TE8 On/Off switches 4 6/11 5TE1 switch disconnectors 6 6/1 Switch to manual? Wherever electrical systems need to be switched on or

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

60103 Circuit Breaker

60103 Circuit Breaker 6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application Miniature Circuit Breakers Areas of Application Miniature circuit breakers (MCBs) of the N-System primarily protect cables and conductors against overload and short circuit. Thus, they also protect electrical

More information

SENTRON ATC Automatic Transfer Control Device

SENTRON ATC Automatic Transfer Control Device Siemens A 2010 SENTRON - SENTRON switching, protection and measuring devices The SENTRON, when equipped with two motor-driven circuit breakers, serves as a transfer system that automatically or manually

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SXP200002B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

Description. Installation. Power supply

Description. Installation. Power supply Air circuit breakers Special versions Series MEGT07 0V/500V/DC 50 up to 5000 A The air circuit breakers MEGT07 are suitable for use as disconnecting switch in DC distributions up to a rated voltage of

More information

Installation. Symmetra MW II kw 400 V. UPS Summary Normal Normal

Installation. Symmetra MW II kw 400 V. UPS Summary Normal Normal UPS Summary ~ ~ Normal Normal Installation Symmetra MW II 600 kw 400 V Contents Safety... IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS.......................... Symbols used in this guide.........................

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection

More information

Conveyor Belt Alignment Switches from IDEM

Conveyor Belt Alignment Switches from IDEM Conveyor Belt Alignment Switches from IDEM Data Sheet Die-Cast Models Python Line Series Stainless Steel Models Using Conveyor Belt Alignment Switches Application: Conveyor Belt Alignment switches are

More information

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

Siemens AG SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A

Siemens AG SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A Switch Disconnectors Introduction Overview All key product features at a glance Compliant with IEC/EN 60439-1, IEC/EN 6094-3 Voltage levels up to 690 V AC Rated operational current from 160 A to 2000 A

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

IEC & 2 standard. The reference for safe and reliable LV switchboards

IEC & 2 standard. The reference for safe and reliable LV switchboards IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC

More information

G - Base. Relays THREE PHASE + NEUTRAL CURRENT PROTECTION RELAY

G - Base. Relays THREE PHASE + NEUTRAL CURRENT PROTECTION RELAY 44 Relays G - Base THREE PHASE + NEUTRAL CURRENT PROTECTION RELAY General Characteristics G-Base is the new generation of Microelettrica Scientifica s base-performance protection relays. This range is

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

UL 489 Cable-In / Cable-Out Branch Circuit Breaker

UL 489 Cable-In / Cable-Out Branch Circuit Breaker Product Overview UL 9 Cable-In / Cable-Out Branch Circuit Breaker PRODUCT OVERVIEW Optimum and Efficient Protection Features Complete range of UL 9 listed DIN rail mounted miniature circuit breakers up

More information

TM221ME32TK controller M IO transistor PNP Ethernet

TM221ME32TK controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221ME32TK controller M221 32 IO transistor PNP Ethernet Complementary Main Discrete I/O number 32 Number of I/O expansion module Supply voltage limits Inrush current

More information

Miniature Circuit Breakers for Railway Applications

Miniature Circuit Breakers for Railway Applications Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Residual Current Devices drcm Digital

Residual Current Devices drcm Digital Digital Line voltage independent RCCB for fault or additional protection with additional digital features. System Monitoring: Preventive information / warning before the RCD trips in case of leakage currents.

More information

TM221CE40T controller M IO transistor PNP Ethernet

TM221CE40T controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221CE40T controller M221 40 IO transistor PNP Ethernet Complementary Main Discrete I/O number 40 Number of I/O expansion module Supply voltage limits Inrush current

More information

Refurbishment of Switchgear and Switchgear Devices

Refurbishment of Switchgear and Switchgear Devices White Paper Refurbishment of Switchgear and Switchgear Devices Low and Medium Voltage Products Introduction There are many suppliers who suggest to users that switchgear assemblies, circuit breakers, and

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

2V67 Four Stage Over / Under Voltage Relay

2V67 Four Stage Over / Under Voltage Relay Technical Bulletin 2V67 Four Stage Over / Under Relay Features Large graphics display panel Instantaneous voltage display 2 to 13V PU setting range.1v setting resolution Adjustable pick up & drop out Adjustable

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv) Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The

More information

Traction Power Systems / Program

Traction Power Systems / Program Traction Power Systems / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles

More information

Motors Automation Energy Transmission & Distribution Coatings. DWB Molded Case Circuit Breakers DWB

Motors Automation Energy Transmission & Distribution Coatings. DWB Molded Case Circuit Breakers DWB Motors Automation Energy Transmission & Distribution Coatings DWB Molded Case Circuit Breakers DWB Molded Case Circuit Breakers Molded Case Circuit Breakers DWB Summary Presentation 0 General Characteristics

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

Residual Current Devices. Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008

Residual Current Devices. Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards,

More information

SIRCO Load break switches for power distribution from 125 to 5000 A

SIRCO Load break switches for power distribution from 125 to 5000 A The solution for Load break switches sirco_456_a_1_cat > Main switchboard > Distribution panel > Emergency breaking > Network coupling > Local safety breaking sirco-ac_001_a_1_cat SIRCO 3 x 250 A direct

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

CP30F Series Circuit Protector for Improving Safety and Wiring Workability

CP30F Series Circuit Protector for Improving Safety and Wiring Workability CP30F Series Circuit Protector for Improving Safety and Wiring Workability EMURA, Takeshi * A B S T R A C T A circuit protector is a circuit-breaker that possesses both overcurrent protection and switch

More information

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER C. Petit Schneider Electric, France Innovation in the field of medium voltage protection devices is accelerating to meet the ever growing demands

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors Close Protection from Moeller miniature branch circuit breakers miniature supplementary protectors FAZ branch circuit breakers General Information... Selection Tables Trip Characteristic C - Box terminals...

More information

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors B Curve NC100H Supplementary Protectors Rating 1P 2P 3P 4P 80 MG27164 MG27175 MG27186 MG27197 MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors C Curve NC100H Supplementary Protectors

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings Siemens AG 200 ALPHA SIMBOX Small Distribution Boards /2 Introduction /2 Introduction /3 Flush-mounting and hollow-wall distribution boards /4 Hood-type distribution boards /5 Accessories /6 Dimensional

More information

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility GE Grid Solutions MiCOM Agile P99x Test Block, Multi-finger Test Plug and Single-finger Test Plug The MiCom Agile P991 test block offers safe and configurable facilities for monitoring and secondary injection

More information

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP)

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Reference Number POP 07 - (RIC Standard: EP 99 00 00 04 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Introduction Circuit Protection

Introduction Circuit Protection Introduction Circuit Protection Weidmuller s DIN-rail mounted circuit breakers are available for use in applications where circuit protection must be able to distinguish between circuit overloads and short

More information

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation

More information

Company main topic [ Product ] TracFeed DCP2. English. Multifunctional Device for Control and Protection in DC switchgear.

Company main topic [ Product ] TracFeed DCP2. English. Multifunctional Device for Control and Protection in DC switchgear. Company main topic [ Product ] TracFeed DCP2 English Multifunctional Device for Control and Protection in DC switchgear Made in Germany 2 TracFeed DCP Our well-known brand name TracFeed DCP is a well-known

More information