How to Set up a TS2 Type 1 Cabinet
|
|
- Alvin Cross
- 5 years ago
- Views:
Transcription
1 2015 How to Set up a TS2 Type 1 Cabinet TS2 Set-up cheat sheet Clues for diagnosing malfuctions March 17, 2015
2 TS2 Type 1 Cabinet Tech Tip Sheets The following is a compendium of items that will help to understand the setup of a TS2 Type 1 cabinet using a Siemens EPAC M50 controller. Cabinet: BIU Bus Interface Unit. This is a digital to analog, or analog to digital converting device. In this case RS485 serial communications protocol is the digital, and 24VDC ground true logic switching is the analog. A BIU is a NEMA device in that it can be used in any BIU socket in any manufacturers cabinet. The controller identifies the BIU by its address. The BIU s address is not on the BIU itself, but is hardwired into the socket of the BIU. NEMA defined addresses: 0 Terminal and Facility 1 (including Load Switches 1 thru 8) 1 Terminal and Facility 2 (including Load Switches 9 thru 16) 2 Terminal and Facility 3 (if used, provide I/O as defined by NEMA) 3 Terminal and Facility 4 (if used, provide I/O as defined by NEMA) 8 Detector BIU 1 (includes Vehicle detectors 1-16) 9 Detector BIU 2 (includes Vehicle detectors 17-32) 10 Detector BIU 3 (includes Vehicle detectors 33-48) 11 Detector BIU 4 (includes Vehicle detectors 49-64) 16 Malfunction Management Unit BIU 18 Controller MMU Malfunction Management Unit replaces the Conflict Monitor and can be used in a TS1 cabinet as a CMU. Pin HH in the large connector is logic grounded in a TS2 cabinet to select it as a MMU, whereas Pin HH is unused (therefore not grounded) in a TS1 cabinet. An indicator (LED or LCD) on the MMU indicates that it is a Type 12 when used in a TS1 cabinet. As a MMU, the unit has 16 channels with three inputs per channel (red (don t walk), yellow, green(walk)). As a CMU the unit has 12 channels with four inputs per channel (red, yellow, green, and walk).
3 Detector Rack (See TS2 Detector setup document) Detector Amplifiers must be TS2 compliant to run in a TS2 Detector Rack. TS2 Detector Amplifiers are downward compatible with TS1 cabinets. TS1 Detector Amplifiers are not compatible with a TS2 Detector Rack. Typically, rack mount Detector Amplifiers manufactured within the last 5 years are TS2 compliant. Big difference is that TS1 Detector Amplifiers require 24VDC to operate, whereas TS2 Detector Amplifiers can operate with 12VDC or 24VDC. Also, TS2 detectors have diagnostics built in that will report thru the BIU to the controller. These include Open Loop, Shorted Loop, and Inductive Change greater than 25%. Ped Detectors Pedestrian Detectors 1 thru 4 are located on the Terminal Facility. As they represent phases 1 thru 4, they must be reassigned in the EPAC to phases 2, 4, 6, and 8. 3 PHASE DATA, 8 SPECIAL DETECTOR, 9 PED1-8, assign ped detector 1 to phase 2, ped detector 2 to phase 4, ped detector 3 to phase 6, and ped detector 4 to phase 8. Zero out the others. Preempt I/O Preemption Inputs and Outputs are located on the Terminal Facility and Expander Panel. Preempts 1 thru 4 are on the TF, and Preempts 5 and 6 are located on the Expander Panel. Many jurisdictions reserve Preempts 1 and 2 for Railroad. Preempts 3 thru 6 are used for Emergency Vehicle Preemption. TS2 Power Supply In TS2, a power supply is required to supply operating voltage to thet&f BIU s, Detector Rack BIU s, and the Detector Amplifiers. - The Detector Rack utilizes 24VDC to run the BIU. - The Detector Rack utilizes 12VDC to run the Detector Amplifiers. - Pedestrian pushbuttons utilize 12VAC. Line Frequency is utilized by the BIU s to reference the 60 Hz. utility line for circuit timing synchronization. (SDLC Synchronous Data Link Communication) Port 1 SDLC This is the RS485 serial communications running at 156kbps. All SDLC cables in the cabinet are wired in parallel. Even though the cables may be labeled, any SDLC cable can be used on any SDLC port. The controller transmit (TX) line goes to all SDLC cable receive (RX) lines. The controller RX line goes to all SDLC cable TX lines. This communication will be explained in the controller section.
4 Siemens Eagle EPAC M52 Controller TS2 Fundamentals Tech Tips When receiving an M50 controller right out of the box, the first to do include: 1) From Main Menu, go to 2 UTILITIES, 6 LOAD DEFAULT and press E. This ensures that the controller is running factory default settings. This sets the controller up as a vanilla 8 phase quad, no Overlaps, no Time Base, no Preemption, etc. 2) Go to Main Menu. Look to see if the operating mode is FIO or TS2. Factory default is FIO. To change, go to 2 UTILITIES, 6 LOAD DEFAULT, C CHANGE CURRENT SOFTWARE OPTION, from this screen select 2 TS2. This selection turns on the SDLC communications in the EPAC. SDLC Communication As briefly mentioned in the cabinet section, the SDLC is Synchronous Data Link Communications transmitted via a RS485 serial port. In a TS2 cabinet this is referred to as Port 1. The data is transmitted from the EPAC as COMMAND FRAMES. The EPAC broadcasts Command Frames, some of which are global to all devices and some which are specific to a device such as the MMU, T & F BIU s, or Detector BIU s. The EPAC then waits to receive Response Frames from the device to which a Command Frame was sent. This communication is performed at 156kbps. Following is a listing of the most utilized COMMAND and RESPONSE FRAMES: Command Frames Type Destination Address ALL 255 T & F BIU 1 0 T & F BIU 2 1 Det BIU 1 2 Det BIU 2 3 Det BIU 1 8 Det BIU 2 9 Function Load Switch Drivers MMU Status MMU Programming Date & Time Broadcast T & F BIU 1 Outputs T & F BIU 2 Outputs Detector BIU 1 Inputs Detector BIU 2 Inputs Detector BIU 1 Resets Detector BIU 2 Resets
5 Response Frames Type Source Address Function 128 Acknowledgement to Command Frame Acknowledgement to Command Frame Acknowledgement to Command Frame T & F BIU 1 0 Ack. to Command Frame T & F BIU 2 1 Ack. to Command Frame Detector BIU 1 8 Ack. to Command Frame Detector BIU 2 9 Ack. to Command Frame Detector BIU 1 8 Ack. to Command Frame Detector BIU 2 9 Ack. to Command Frame 25 Frame Faults Occasionally there might be a malfunction of one of the devices in the cabinet, whether it is the controller, the MMU, a T & F BIU, or a Detector BIU. The failure could also be a mechanical failure of a SDLC connector. Clues for diagnosing this will start by looking at the MMU and the Active Status on the EPAC. If the MMU shows no fault, but is in CVM flash, then look at the Active Status on the EPAC. This is located in the EPAC by going to the Main Menu under 1 Active Status, 1 Ring Timers, 1 Rings On the bottom of this screen it will say TS2 Diagnostic Flash. The diagnostic that indicates which device is causing the CVM TS2 Diagnostic flash is located in the EPAC Alarm Log. This is located in the EPAC by going to the Main Menu under 9 Reports, 4 Local Alarms. In this log you may see Frame Faults, which will be indicated by the number of the fault, such as Frame Fault 138. The preceding fault would indicate that the T & F BIU 1 is not operating properly. Controller and Cabinet Interface: In a TS2-Type 1 cabinet, the sequence setup and controller setup are much more restricted than we were used to in a TS1 cabinet. If we don t have the controller unit sequence set to match what the cabinet is set up for, we will expect to get a MMU Utilization Error when we try to run the cabinet. In other words, the sequence in the controller must exactly match the controller cabinet sequence. If there are no provisions for phase 1 in the cabinet, we must eliminate phase 1 from the controller sequence. For general house keeping in the controller program, and to eliminate any possibility for programming error, we typically eliminate any channel assignment that does not exist in the sequence. All of the preceding are requirements defined by NEMA. A diagnostic tool used to help set up the MMU program card is located in the EPAC menu under, 4 UNIT DATA, 5 RING STRUCTURE, then press D. This screen header reads OUTPUT CHANNEL COMPATIBILITIES and shows exactly what jumpers need to be soldered onto the MMU program card.
Traffic Signal Troubleshooting. Charles DeVitis Upper Merion Township Traffic Signal Supervisor
Traffic Signal Troubleshooting Charles DeVitis Upper Merion Township Traffic Signal Supervisor December 6 th 2018 What does the Signal Tech really need to know. Controllers Conflict Monitors Battery Back
More informationNEMA TS2 Standards. Standardization & Multiple Sourcing. Enhanced Safety & Reduced Liability. The Intelligent Cabinet
NEMA TS2 Standards The Intelligent Cabinet Standardization & Multiple Sourcing TS2 specifies controllers and cabinets more fully than the TS1 or 170/179 standards by covering auxiliary functions such as
More informationCopyright EDI
MMU2-16LE SmartMonitor Advanced Signal Monitor Overview Eberle Design Inc. Copyright EDI 2013 050813 Managing Cabinet Malfunctions The signal monitor has three basic important tasks to perform: Detect
More informationNaztec Version 50 Software TS-1, TS-2, 170E, 2070N. Training Unit 1 Basic Features
NAZTEC.now Naztec Version 50 Software TS-1, TS-2, 170E, 2070N Training Unit 1 Basic Features HARDWARE FEATURES Meets or exceeds NEMA TS-1 and TS-2 specifications Socket mounted IC's for easy servicing
More informationTOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT
TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT 06045-0191 TRAFFIC SIGNAL INSTALLATIONS MIDDLE TURNPIKE EAST AT SUMMIT STREET MIDDLE TURNPIKE EAST AT
More informationMMU-16LE Series SmartMonitor
MMU-16LE Series SmartMonitor NEMA TS-2 Enhanced Malfunction Management Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE MMU-16LE and MMU16LEip SmartMonitor SERIES MALFUNCTION MANAGEMENT UNIT. REVISION:
More informationEberle Design Inc. MMU-16LE SmartMonitor Configuration & Installation
Eberle Design Inc. MMU-16LE SmartMonitor Configuration & Installation Overview 040313 EDI 2013 Topics Configure the SmartMonitor for Field Use Configuration Parameters Configuration Programming Methods
More informationModel MMU-516L-E. TS2 MMU RS232 and Ethernet (Malfunction Management Unit)
Naztec Operations Manual For Model MMU-516L-E TS2 MMU RS232 and Ethernet (Malfunction Management Unit) Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 240-7233 Fax: (281)
More informationCopyright EDI MMU2-16LE SmartMonitor Malfunction Management Unit - Training Seminar -
1 043013 Copyright EDI 2013 MMU2-16LE SmartMonitor Malfunction Management Unit - Training Seminar - Table of Contents Understanding Voltage Root Mean Squared MMU Training FYA (Flashing Yellow Arrow) Training
More informationTS2 Virtual Cabinet Model TVC-3500
TS2 Virtual Cabinet Model TVC-3500 User's Manual Revision 1.0 Table of Contents Table of Contents 1. Explanation of Symbols and Terms...2 2. Introduction to TS2 Virtual Cabinet...3 3. Installing TS2 Virtual
More informationMMU-16E. NEMA TS-2 Malfunction Management Unit Operations Manual
MMU-16E NEMA TS-2 Malfunction Management Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE MMU-16E SERIES MALFUNCTION MANAGEMENT UNIT. INCLUDED ARE GENERAL DESCRIPTION, OPERATIONAL DESCRIPTION, INSTALLATION,
More informationModel NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by
Naztec Operations Manual For Model NM512 TS1 Conflict Monitor Standard 12 Channel Unit Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 2407233 Fax: (281) 240-7238 Copyright
More informationEagle 2070 Reference Manual Sepac Controller Software TACTICS Software
Eagle 7 Reference Manual Sepac Controller Software TACTICS Software O:\TRAFFIC\SIGNALS\Training\Eagle 7 - SEPAC - TACTICS Steps to follow for new 7 controllers out of the box. Access Code From the main
More information3000 Series TS-2 Firmware v3.6
3000 and 3000E Traffic Controllers 3000 Series TS-2 Firmware v3.6 Peek Traffic is pleased to announce the release of Version 3.6 of the TS-2 firmware for the 3000 Series Traffic Controllers. The primary
More informationROAD COMMISSION FOR OAKLAND COUNTY SPECIAL PROVISION FOR DIGITAL / ITS TYPE NEMA TS2 TYPE 1 CONTROLLER AND CABINET
RCOC/TOC: DD Page 1 of 49 RCOC12T820H This special provision outlines the Road Commission for Oakland County s specifications for the traffic signal controller and cabinet. The traffic signal controller
More informationNSM-E Series. NEMA TS-1 Enhanced Signal Monitor Operations Manual
NSM-E Series NEMA TS-1 Enhanced Signal Monitor THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE NSM-6E and NSM-12E SERIES SIGNAL MONITOR. REVISION: MARCH 2012 pn 888-1206-002 THE NSM-E SERIES SIGNAL
More informationProject Documentation TMIB Data Sheet
Project Documentation TMIB Data Sheet Project Number: SMS Project Number: Project Title: Traffic Management Interface Board Keyword(s): TMIB Traffic Management Interface Board NEMA TS1 Loop Detector Output
More informationBIUT TS2 Bus Interface Unit Tester. User's Manual Revision 1.0
BIUT- 820 TS2 Bus Interface Unit Tester User's Manual Revision 1.0 Table of Contents 1. Explanation of Symbols, Terms, and Abbreviations...3 2. Safety Information...5 3. Introduction...6 4. BIUT-820 Software
More informationNEMA Standards Publication TS Traffic Controller Assemblies with NTCIP Requirements Version 03.07
NEMA Standards Publication TS 2-2016 Traffic Controller Assemblies with NTCIP Requirements Version 03.07 Published by: National Electrical Manufacturers Association 1300 North 17 th Street, Suite 900 Rosslyn,
More informationModel NM512-E123. TS1 Conflict Monitor Enhanced 12 Channel Unit With LCD Display. Naztec Operations Manual. For. Published by
Naztec Operations Manual For Model NM512-E123 TS1 Conflict Monitor Enhanced 12 Channel Unit With LCD Display Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 2407233 Fax:
More informationNew York City s Advanced Traffic Controller Procurement Project (ASTC)
New York City s Advanced Traffic Controller Procurement Project (ASTC) Session August 6, 2002 Bob Rausch robert.rausch@transcore.com 1 Outline Background and history of the project Approach to the use
More informationADU-2220 & ADU Auxiliary Display Unit
ADU-2220 & ADU Auxiliary Display Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE ADU-2220 and ADU AUXILIARY DISPLAY UNIT FIRMWARE VERSION 012x MANUAL REVISION: MAY 2016 pn 888-2220-001 ADU-2220
More informationOPERATIONS MANUAL. n.form I/O Expander (RACK MOUNT) Document Number: Rev B
OPERATIONS MANUAL n.form I/O Expander (RACK MOUNT) Document Number: 200-0009 Rev B table of contents INTRODUCTION FEATURES & CAPABILITIES 1 WIRING General I/O Configuring The System Using The System 4
More informationrdczbk User Manual ZigBee to RS-232 / RS-485 Converter
1. Product Overview rdczbk User Manual ZigBee to RS-232 / RS-485 Converter Robust DataComm Pte Ltd The rdczbk is basically a XBee / XBee Pro carrier board that provides either RS-485 or RS-232 connectivity
More informationin3 (3 Wire Ordering)
5X7 in3 (3 Wire Ordering) 1. Use inavigator Order form to order Push Button Station (This will formulate exact model number, including sign sizing) 2. Order Ped Head Control Unit (iphcu3w) 9X12 9X15 3.
More informationAirTest Model CN9000 Series Sensor Controller
AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller THEORY OF OPERATION A basic CN9000 configuration consists of Input/Process/Display combination modules, a 3 relay
More informationTraffic Signal Controllers
Traffic Signal Controllers Course No: C02-056 Credit: 2 PDH Jeffrey W. Buckholz, PhD, PE, PTOE Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800
More informationTech Note 3011 NTCIP Database Guidelines Part II
Tech Note 3011 NTCIP Database Guidelines Part II This Tech Note extends the controller operation described in Tech Note 3010 Guidelines for NTCIP Databases Part I. These enhancements are recommended for
More informationHigh Voltage Power Supply (MMPS) - Troubleshooting Guide
High Voltage Power Supply (MMPS) - Troubleshooting Guide LAST UPDATED: 09/19/2018 High Voltage Power Supply (MMPS) - Troubleshooting Guide Overview The High Voltage Power Supply (MMPS - MINIMILL Power
More informationNEMA TS2-Type 1, P Cabinet Assembly City of San Jose Specification Rev date. November 20, 2015
NEMA TS2-Type 1, P Cabinet Assembly City of San Jose Specification Rev date. November 20, 2015 Page 1 of 13 City of San Jose P TS2-1 Cabinet Specification A. Cabinet Minimum General Requirements The cabinet
More informationCabinet Interface Device
Cabinet Interface Device Click 650 The Click 650 provides streamlined communication for SmartSensor Matrix and Advance to traffic controllers in one compact case. This module communicates directly to the
More informationKRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-74DL Master Room Controller. P/N: Rev 5
KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-74DL Master Room Controller P/N: 2900-000691 Rev 5 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance 2 2.2 Safety Instructions
More informationF271XA Fiber-Optic Telephone Modem Technical Manual
F271XA Fiber-Optic Telephone Modem Technical Manual Revision B August 2011 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com Safeguarding Communications Since 1958 PROPRIETARY
More informationMODEL DSU Kbps Rack Mount CSU/DSU OPERATOR S MANUAL. 280 I-80 West Exit 1 PO Box 1330 Verdi NV 89439
MODEL DSU-56 56 Kbps Rack Mount CSU/DSU OPERATOR S MANUAL 280 I-80 West Exit 1 PO Box 1330 Verdi NV 89439 TEL: 775-345-8000 FAX: 775-345-8010 E-MAIL: SUPPORT @S.NET DSU-56 Rack Mount TABLE OF CONTENTS
More informationProcurement Specification DA-300
Procurement Specification DA-300 V 5 20170925 Procurement Specification for DA-300 Table of Contents Contents Introduction... 3 1) Hardware... 3 2) Functionality... 6 3) Cabinet interfaces... 8 4) LED
More informationOPERATIONS MANUAL SSM-18LEPR CONFLICT / VOLTAGE MONITOR
SSM-18LEPR CONFLICT / VOLTAGE MONITOR THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE FOLLOWING SERIES OF CONFLICT/VOLTAGE MONITORS: SSM-18LEPR. INCLUDED ARE GENERAL DESCRIPTION, OPERATIONAL DESCRIPTION,
More informationinavigator 2 Wire System Manual
Polara inavigator 2 Wire System Manual For Use with iccu-s and iccu-c Rev. J 11/9/2017 Page 1 of 84 Contents 1. Safety Information 5 2. inavigator System Description 6 2.1 in2 Accessible Pedestrian Signal
More informationVersaMax IP Input Module
Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm
More informationDomain 3000 Back Panel
Domain 3000 Back Panel The Domain 3000 has 25 I/O ports plus a connector for an external power supply (included) and an LED to indicate that the power is on. Typically, it is placed on a shelf or equipment
More information180 Series Keypad. Handbook. Revision 2.1
180 Series Keypad Handbook Revision 2.1 Revision History Revision 1.0 Initial release Revision 2.0 Major update with addition of 180-40 Added 180-40 to document and various headings Note regarding unique
More informationATC I/O D
Quick Contents Table of Figures... viii Preface About This Manual... 1 Chapter 1 Introduction to the ATC-1000... 5 Chapter 2 Quick Start: Getting a Unit Up and Running... 41 Chapter 3 Introduction to the
More informationInstallation Quick Start Guide for in2/iccu-s System
Installation Quick Start Guide for in2/iccu-s System See inavigator 2 Wire System Manual Rev. J or newer for complete Installation and Operation instructions. Sections referenced below are from this manual.
More informationAI-917-A0. Analogue Input Module (4x 0-20 ma)
General Specifications GS48D17A00-00E-N AI-917-A0 Analogue Input Module (4x 0-20 ma) GENERAL Figure 1 This module has four analogue inputs and four logic pulse outputs. AI-917-A0 Analogue Input Module
More informationSCB-C08 USB to RS232/422/485 Converter
SCB-C08 USB to RS232/422/485 Converter USB Interface RS-232 signal RS-422 signal: RS-485 signal: Cable Type Transmission distance Signal LED Direct power from USB port Power consumption: Compliant with
More informationLIST OF APPENDICES APPENDIX A: DRAWING NO. TTD R2 - COMMUNICATION TERMINAL BLOCK COMPARTMENT APPENDIX B: CONTROLLER PROGRAMMING SHEET
TABLE OF CONTENTS 1. SCOPE...1 2. REFERENCES...1 3. GENERAL TECHNICAL REQUIREMENTS...2 4. ADDITIONAL REQUIREMENTS FOR TS2, TYPE 1 TRAFFIC SIGNALS CONTROL UNIT...6 5. ADDITIONAL TECHNICAL REQUIREMENTS FOR
More informationAdvanced Transportation Controller Cabinet (ATCC) Component Overview
Advanced Transportation Controller Cabinet (ATCC) Component Overview 081716 EDI Background Material This ATCC Component webinar assumes a basic knowledge of the ATC Cabinet architecture and features. Links
More informationINSTRUCTION MANUAL. Card Revision: Software 2.1 Card Revision: Hardware B(2.0) DOCUMENT SES-KS-2422-E REV. 3
2422 DIGITAL OUTPUT CARD 16 CHANNELS INSTRUCTION MANUAL Card Revision: Software 2.1 Card Revision: Hardware B(2.0) DOCUMENT SES-KS-2422-E REV. 3 2422 DIGITAL OUTPUTS CARD 16 CHANNELS SES-ASA ENGINEERING
More informationGeneric Procurement Specification for a Video Detection Solution for Roadway Applications
Generic Procurement Specification for a Video Detection Solution for Roadway Applications 1 of 10 Video Detection System This specification sets forth the minimum requirements for a video detection system
More informationLVX Control Unit. Features:
Date 2013-02-28 Control Unit Features: Most parameters can be defined as required for your interfaces. You decide which information is output and how. Fast cycle times, just a few µs/beam. Maximum beam-count
More informationINSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3
INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page
More informationDUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS
LD220 DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS USER MANUAL P.O.Box 24 STANFIELD 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com 18/08/2005
More informationIM IM in the RS485 variants features: 9-pin Sub-D socket for connection to PROFIBUS DP
IM 151-1 Design The IM 151-1 interface modules are directly snapped onto the standard mounting rail. IM 151-1 modules feature: DIP switch for setting the PROFIBUS DP station address (1 to 125) Diagnostics
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR ACCESSIBLE PEDESTRIAN SIGNAL SYSTEM
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR ACCESSIBLE PEDESTRIAN SIGNAL SYSTEM SIG:EMS 1 of 6 APPR:LWB:DBP:07-17-14 FHWA:APPR:07-30-14 a. Description. This work consists of either furnishing
More informationM82xxD Fiber Optic RS-232 MicroModem Technical Manual
M82xxD Fiber Optic RS-232 MicroModem Technical Manual Revision C August 2016 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com Safeguarding Communications Since 1958 PROPRIETARY
More informationSecurity Management System by Diebold, Inc. LINX System Hardware Installation Guide
Security Management System by Diebold, Inc. LINX System Hardware Installation Guide INSTALLATION GUIDE LINX Integrated Security System WSD 2000 Weatherized Status Display Table of Contents Introduction
More informationinavigator 2 Wire System Manual
Polara inavigator 2 Wire System Manual For Use with iccu-s and iccu-c Rev. P 11/20/2018 Page 1 of 96 Contents 1. Safety Information 6 2. inavigator System Description 7 2.1 in2 Accessible Pedestrian Signal
More informationUSER MANUAL. RC-74DL Master Room Controller MODEL: P/N: Rev 4
KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-74DL Master Room Controller P/N: 2900-000691 Rev 4 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance 2 2.2 Safety Instructions
More informationinavigator 2 Wire System Manual
Polara For Use with iccu-s and iccu-c Rev. N 8/23/2018 Page 1 of 87 Contents 1. Safety Information 5 2. inavigator System Description 6 2.1 in2 Accessible Pedestrian Signal Push Button Station (PBS) 6
More informationVersaMax IP I/O Module
Module accepts four digital input signals and provides four digital outputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by a Profibus Interface Unit (IC677PBI001)
More informationThis Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V.
This Datasheet for the IC670ALG310 Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V http://www.qualitrol.com/shop/p-14493-ic670alg310.aspx Provides the wiring diagrams and installation guidelines for
More informationTEL: (203) FAX: (203) WEB:
TEL: (203)-634-3900 FAX: (203)-238-2425 EMAIL: HIGHPOWER@HIGHPOWERSECURITY.COM WEB: WWW.HIGHPOWERSECURITY.COM MODEL 3500 ONLINE DOOR CONTROLLER WITH DOOR STATUS FOR OEM & DEVELOPER APPLICATIONS HARDWARE
More informationTable of Contents. Automatic Transfer Switch. User Manual ATS-16A/20A/30A/32A
Table of Contents 1. Important Safety Instructions... 2 2. Overview... 3 3. Product Functional Description... 4 3.1. Front Panel... 4 3.2. LCD Display Description... 5 3.3. Rear Panel... 6 3.4. Communication
More informationOpportunities To Succeed
Harris County ITS Deployments Presented by Wayne Gisler Manager Harris County Traffic & Operations Section Ron Johnson Quality Control Coordinator Harris County Traffic & Operations Section Our Goal To
More informationModicon Premium PLCs TSX CSY 84 / 85 / 164
Modicon Premium PLCs TSX CSY 84 / 85 / 164 SERCOS Motion Control Quick reference guide Edition June 2009 Contents General Safety Advice for Users 2 Presentation of the TSX CSY 84/85/164 Modules 4 General
More informationUSER MANUAL. RC-76R/RC-78R Room Controllers MODEL: P/N: Rev 2
KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-76R/RC-78R Room Controllers P/N: 2900-300253 Rev 2 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance 2 2.2 Safety Instructions
More informationBL compact fieldbus station for DeviceNet 4 Analog Inputs for Current or Voltage and 8 Configurable Digital PNP Channels BLCDN-8M12L-4AI-VI-8XSG-PD
On-machine Compact fieldbus I/O block DeviceNet slave 125 / 250 / 500 kbps Two 5-pole M12 connectors for fieldbus connection 2 rotary switches for node address IP67, IP69K M12 I/O connectors LEDs indicating
More informationF271XAD Fiber-Optic Telephone Modem with RS485 Data Technical Manual
F271XAD Fiber-Optic Telephone Modem with RS485 Data Technical Manual Revision A January 2014 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com Safeguarding Communications Since
More informationData sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!
Data sheet MK 20 GR Customized solution or off-the-shelf: The choice is yours! MK20-GR data sheet Looking for a quick and reliable solution? Then rely on our standard products: Our universal controls provide
More informationUSER MANUAL RC-76M/RC-712M MODEL: P/N: Rev 3
KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-76M/RC-712M P/N: 2900-300329 Rev 3 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance 2 2.2 Safety Instructions 3 2.3 Recycling
More informationDGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field
DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description
More informationP/N Rev. 01. October 7, Copyright 2005 by Econolite Control Products, Inc.
P/N 00-0903-00 Rev. 0 October 7, 2005 Copyright 2005 by Econolite Control Products, Inc. Warranty Econolite Control Products, Inc. warrants, for a period as shown below, from date of shipment, all control
More informationQuick Start Installation Guide
apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building
More informationROAD COMMISSION FOR OAKLAND COUNTY SPECIAL PROVISION FOR. SOLID STATE ACTUATED CONTROLLER AND CABINET January 2007 Page 1 of 38
a. General Description ROAD COMMISSION FOR OAKLAND COUNTY Page 1 of 38 TRAFFIC SIGNAL CONTROLLER (SCATS Compatible) This specification describes an advanced traffic signal controller meeting the latest
More informationKRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-76R/RC-78R Room Controllers. P/N: Rev 5
KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-76R/RC-78R Room Controllers P/N: 2900-300253 Rev 5 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance 2 2.2 Safety Instructions
More informationeip-10 Embedded TCP/IP 10-BaseT Network Module Features Description Applications
Embedded TCP/IP 10-BaseT Network Module Features 8-bit reprogrammable Microcontroller with Enhanced Flash program memory, EEPROM and Static RAM data memory On board 10Mbps Ethernet controller, and RJ45
More informationClick! 301. Serial to Ethernet Converter
Serial to Ethernet Converter The Click! 301 converts half-duplex RS-232 & RS-485 communication to Ethernet and vice versa. This device, tested to work over a 34 C to 74 C temperature range, can be used
More informationHelios PD Large Display Meter Quick Start Guide
MeterView Pro USB Install Thank you for your purchase of the Helios PD2-6000 large display meter. This quick start guide will briefly describe some of the common setup procedures for this meter. This guide
More informationInstalling the DX LCD Display
DX LCD Display User s Guide 3-1 Chapter 3 Installing the DX LCD Display Introduction Use the DX LCD Display as either a portable device, or permanently mount it in a panel or on the wall. For panel and
More informationCOMMONLY USED 5.AFETY SENSORS. Photocell (Reflector) CLOSING Direction. Photocell (Reflector) CLOSING Direction OA4RO E.3IC-RIOIC4 EA4X IRB-RET
MLY USED 5.AFETY SENSORS 0----- OA4RO E.IC-RIOIC4 Direction. Set switch to "LIGHT ". Wire V power to photocell. Wire to photocell N0 Wire to photocell C- 4. Align photocell to reflector 5. Adjust sensitivity
More informationUser Guide Automatic Transfer Switch (ATS)
User Guide Automatic Transfer Switch (ATS) V.1.0 Table of Contents 1. Introduction... 2 2. Product Overview... 2 3. Important Safety Warnings... 3 4. Operation Indicators & Status... 3 5. Installation...
More informationSEPAC ECOM All Data. Access Code: Address: 1 1 :1200 Baud Revision: 3.34g. IP Address: :1200 Baud. 7 1-Inact. 8 1-Inact.
Intersection Name: Central & nd SEPAC ECOM All Data Intersection Alias: Cent Access Data Access Code: 9999 Channel: Address: :00 Baud Revision:.g IP Address: 0.0.. :00 Baud Initialization Data Initial
More informationMC CO MODBUS ADDRESSABLE SENSOR
MC-4210 - CO MODBUS ADDRESSABLE SENSOR Manual Part Number 180-0545A March 31, 2003 PAGE 1 TABLE OF CONTENTS TITLE PAGE Table of Contents...2 List Of Figures...4 1. Introduction...5 1.0. General...5 1.1.
More informationBAS Router BACnet Multi-Network Router
BAS Router BACnet Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP thereby allowing the system integrator to
More informationRTU560 Connections and Settings DIN Rail RTU 560CIG10
Connections and Settings DIN Rail RTU 560CIG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CIG10 1KGT 150 719 Operation The 560CIG10 is a DIN rail
More informationInstallation & Operation Guide
Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief
More informationISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) SUITABLE FOR EXTERNAL DISTRIBUTION
ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 12- Relay Board P/N 103190 and 103338 PAGE 1 of 13 1. REVISI LOG... 2 2. OVERVIEW... 3 2.1. PART NUMBERS... 3 2.2. MODULE
More informationCHAPTER Wi r i n g NOTICE:
CHAPTER Wiring NOTICE: Information in this manual may change without notice. Midway Games West Inc. reserves the right to make improvements in equipment function, design, or components as progress in engineering
More informationEagle PT-MP1 Pan Tilt Communications Multiplexer Installation and Operations Manual Revision 3.0 August 20, 2001
Eagle PT-MP1 Pan Tilt Communications Multiplexer Installation and Operations Manual Revision 3.0 August 20, 2001 Distributed by Hitachi Denshi America Ltd. 150 Crossways Park Drive Woodbury, NY 11797 (516)
More informationPT-7728/7828 Quick Installation Guide
PT-7728/7828 Quick Installation Guide Moxa PowerTrans Switch Edition 9.0, April 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777
More informationITA NODE TYPE 1 Operating Manual
ITA NODE TYPE 1 Operating Manual Revision 1.4 May 2007 3 Raw Holdings East Calder West Lothian EH53 0HY, UK T: +44 1506 885000 F: +44 1506 885501 W: www.iconresearch.co.uk NOTICE Information contained
More informationCDN503 HIGH DENSITY I/O ADAPTER USER GUIDE
CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE 13050301 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN503 PRODUCT OVERVIEW 1 DN503 INSTALLATION 1 POWER
More informationHomeVision-Pro Overview for HomeVision Users
HomeVision-Pro Overview for HomeVision Users This document has two main purposes: 1. To describe the main differences between HomeVision and HomeVision-Pro. 2. To assist HomeVision users in converting
More informationRTU560 Remote Terminal Unit Connections and Settings
Remote Terminal Unit Connections and Settings Communication Unit 560CMG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CMG10 1KGT 150 645 Operation
More informationAmplifiers, Counters, Timers & Controls
Amplifiers, Counters, Timers & Controls Panel Meter 814 Counter/Timer/Rate Indicator 815-817 Speed Monitor 818-819 Signal Converter 820-822 Power Supplies/Amplifier 823-824 813 Panel Meter Panel Meter
More informationPAC BI-DP BIM and 8701-CA-BI Carrier
June 2013 PAC8000 8507-BI-DP BIM and 8701-CA-BI Carrier PROFIBUS DP Bus Interface Module and Carrier The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000 series
More informationExclusive 2.5 GHz Frequency Counter
Exclusive 2.5 GHz Frequency Counter with blue 2 x 16 LCD display This manual will guide you how to assemble, test and tune this frequency counter KIT. Features: Frequency range from 5 MHz to 2.5GHz Factory
More informationNEMA 4 Option Card Installation Manual
225880901 Installation Manual s! WARNING Serious or fatal electric shock may result from failure to remove electrical power from the SubDrive prior to installing the NEMA 4 Option Card. Disconnect power
More informationBL compact fieldbus station for DeviceNet 4 Analog Outputs for Voltage BLCDN-4M12S-4AO-V
On-machine Compact fieldbus I/O block DeviceNet slave 125 / 250 / 500 kbps Two 5-pole M12 connectors for fieldbus connection 2 rotary switches for node address IP67, IP69K M12 I/O connectors LEDs indicating
More informationOperating instructions. ProcessLine analogue module AC / / 2012
Operating instructions ProcessLine analogue module AC2916 739089 / 01 06 / 2012 Contents 1 Safety instructions... 3 2 Functions and features... 4 3 Operating and display elements... 4 4 Electrical connection...
More informationVISY-Output 8. Technical Documentation. 8-Channel relay output module. Version: 3 Edition: Art. no.:
Technical Documentation VISY-Output 8 8-Channel relay output module Version: 3 Edition: 2016-09 Art. no.: 350072 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel.: +49 / 40 / 39 82 07 0 Fax:
More information