Test report number CRT-001 Project number CRT-001
|
|
- Louisa Eaton
- 6 years ago
- Views:
Transcription
1 3933 U Route 11 Cortland, NY 1345 Telephone: (7) Facsimile: (7) January 6, 2 L-Com Inc 45 Beechwood Drive L-Com Global Connectivity North Andover, MA 1845 Test report number 1892CRT-1 Project number TET: 1892CRT-1 Competitive performance testing of telecommunication patch cords to the requirements of ANI/TIA-568- C.2 for Category 5e patch cords. TANDARD UED: ANI/TIA-568-C.2-29: Balanced Twisted-Pair Telecommunications Cabling and Components tandards, dated August 29 ECTION: 6.9 Cords and Jumpers Transmission Performance (6.9.1 to 6.9.2) AUTHORIZATION: The project was authorized by Mr. David Gallagher, representing the client, L-Com Inc, with signed quotation number AMPLE DECRIPTION: The client supplied five (5) samples of 2 meter length patch cords identified as part number TRD815R-7 and five (5) samples of 2 meter length patch cords identified as part number UCA5-7-BL. The samples were received on December 22, 211 and were in good condition. EQUIPMENT LIT: The following equipment was employed in conducting the tests. Equipment used Model number Control number Calibration date Calibration due date Fluke Networks field tester DTX-18 N1134 /5/2/5/2 DATE OF TET: January 6, 211 TET REPORT REVIION HITORY: First Issue: January 6, 2 Original Document Page 1 of 2 This report is for the exclusive use of Intertek s Client and is provided pursuant to the agreement between Intertek and its Client. Intertek s responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only the sample tested. This report by itself does not imply that the material, product or service is or has ever been under an Intertek certification program. Intertek Testing ervices NA, Inc.
2 L-Com Inc Test report number 1892CRT-1 January 6, 2 REULT: ee appendixes A and B for the test results. CONCLUION: The telecommunication patch cords, identified as part number TRD815R-7, did comply with the indicated applicable transmission requirements. The telecommunication patch cords, identified as part number UCA5-7-BL failed the Return Loss parameter. The testing was performed at Intertek located in Cortland, New York. The procedures and requirements were taken from the standard referred to on page 1. Reviewed and Approved By: Antoine Pelletier Engineer Global Cabling Products Testing John Cash Technician Global Cabling Products Testing Page 2 of 2 Intertek Testing ervices NA, Inc.
3 L-Com Inc Test report number 1892CRT-1 January 6, 2 Appendix A Test results for part number TRD815R-7 This appendix contains 5 pages. Intertek Testing ervices NA, Inc.
4 Cable ID: 1892CRT-1-A-1 Date / Time: 1/6/2 9:7:26am Headroom: 5.3 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: PA Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ].5 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () PA MAIN R MAIN Worst Pair 78 () Freq. (MHz) Limit () R ite: Client Name
5 Cable ID: 1892CRT-1-A-2 Date / Time: 1/6/2 9:11:52am Headroom: 6.5 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: PA Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ].4 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () PA MAIN R MAIN Worst Pair 78 () Freq. (MHz) Limit () R ite: Client Name
6 Cable ID: 1892CRT-1-A-3 Date / Time: 1/6/2 9:13:14am Headroom: 5.5 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: PA Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ].4 PA MAIN R MAIN R Worst Pair () 5..5 Freq. (MHz) Limit () PA MAIN R MAIN Worst Pair () Freq. (MHz) Limit () R ite: Client Name
7 Cable ID: 1892CRT-1-A-4 Date / Time: 1/6/2 9:31:4am Headroom: 4.4 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: PA Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ].4 PA MAIN R MAIN R Worst Pair () 4..4 Freq. (MHz) Limit () PA MAIN R MAIN Worst Pair 45 () Freq. (MHz) Limit () R ite: Client Name
8 Cable ID: 1892CRT-1-A-5 Date / Time: 1/6/2 9:32:23am Headroom: 4.3 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: PA Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ].4 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () PA MAIN R MAIN Worst Pair () Freq. (MHz) Limit () R ite: Client Name
9 L-Com Inc Test report number 1892CRT-1 January 6, 2 Appendix B Test results for part number UCA5-7-BL This appendix contains 5 pages. Intertek Testing ervices NA, Inc.
10 Cable ID: 1892CRT-1-B-1 Date / Time: 1/6/2 9:33:49am Headroom: 4.9 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: FAIL Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair 78] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ] 1.6 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () FAIL MAIN R MAIN Worst Pair () -8.7 F -8.7 Freq. (MHz).1.1 Limit ().. R ite: Client Name
11 Cable ID: 1892CRT-1-B-2 Date / Time: 1/6/2 9:55:16am Headroom: 4.3 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% 8 ft Test ummary: FAIL Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 8 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] Resistance (ohms) [Pair 78] 1.6 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () FAIL MAIN R MAIN Worst Pair () -7.7 F -7.7 Freq. (MHz).4.4 Limit ().. R ite: Client Name
12 Cable ID: 1892CRT-1-B-3 Date / Time: 1/6/2 9:56:52am Headroom: 4.7 ( -) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: FAIL Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 7 Prop. Delay (ns) [Pair 45] 11 Delay kew (ns) [Pair 45] 1 Resistance (ohms) [Pair 78] 1.7 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () FAIL MAIN R MAIN Worst Pair () -7.1 F -7. Freq. (MHz) Limit () R ite: Client Name
13 Cable ID: 1892CRT-1-B-4 Date / Time: 1/6/2 9:58:16am Headroom: 2.9 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% 8 ft Test ummary: FAIL Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair ] 8 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] Resistance (ohms) [Pair 45] 1.8 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () FAIL MAIN R MAIN Worst Pair () -7.5 F -7.3 Freq. (MHz) Limit () R ite: Client Name
14 Cable ID: 1892CRT-1-B-5 Date / Time: 1/6/2 1::2am Headroom: 3.7 ( -45) Test Limit: TIA Patch Cord Cat5e 2.m PA oftware Version: 2.52 Limits Version: 1.7 NVP: 69.% Test ummary: FAIL Model: DTX-18 Main /N: Remote /N: Length (ft) [Pair 45] 7 Prop. Delay (ns) [Pair ] 11 Delay kew (ns) [Pair ] 1 Resistance (ohms) [Pair ] 1.7 PA MAIN R MAIN R Worst Pair () Freq. (MHz) Limit () FAIL MAIN R MAIN Worst Pair () -6.5 F -6.4 Freq. (MHz) Limit () R ite: Client Name
Test Report Number: G CRT-039g
3933 US Route 11 Cortland, New York 145 Telephone: +1 () 345-3851 Facsimile: +1 (7) 758-6637 www.intertek.com Project Number: G28364 Certificate of Conformance Number: 324722CRT-1f Date Issued: 5/29/15
More informationAMENDED FINAL REPORT FOR:
731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton Manufacturing Co. 417 Stone Drive
More informationAMENDED FINAL REPORT FOR:
731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: Leviton Manufacturing Co. 417 Stone Drive St. Charles,
More informationAMENDED FINAL REPORT FOR:
731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek-etlsemko.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton 2222 222nd St. SE Bothell,
More informationTest Report modcon - PS88A6M
modcon - PS886M Transmission Characteristics of PS886M /CT6 PS886M shielded CT6 plug fulfills the requirements for electrical transmission performance according to IEC 663-7-51; detail specification for
More informationREPORT INTERTEK TESTING SERVICES, INC.
REPORT INTERTEK TESTING SERVICES, INC. 3933 US ROUTE 11, CORTLAND, NEW YORK 13045 ORDER NO.: J20042193-406 DATE: March 19, 2001 REPORT NO.: J20042193-004 RENDERED TO: Tyco Electronics 3700 Reidsville Rd.
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationSECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION
SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction
More informationPANGEN SYSTEM WARRANTY. Warranty Guide
PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &
More informationSUPPLEMENTARY TYPE EXAMINATION CERTIFICATE
1. SUPPLEMENTARY TYPE EXAMINATION CERTIFICATE 2. Equipment or Protective System Intended for use in Potentially Explosive Atmospheres Directive 94/9/EC 3. Type Examination Certificate Number: ITS13ATEX47876X/1
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationLanTEK III FiberTEK III. Certifier for Copper and Fibre Cabling. Proof of Performance
LanTEK III FiberTEK III Certifier for Copper and Fibre Cabling Proof of Performance LanTEK III FiberTEK III The LanTEK III is an easy to use cable certifier that meets existing TIA and ISO/IEC performance
More informationLanTEK III FiberTEK III. Certifier for Copper and Fibre Cabling. Proof of Performance
LanTEK III FiberTEK III Certifier for Copper and Fibre Cabling Proof of Performance LanTEK III FiberTEK III The LanTEK III is an easy to use cable certifier that meets existing TIA and ISO/IEC performance
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationWhite paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com
The dramatic growth of high-bandwidth wireless access points and other IP-enabled devices, such as surveillance cameras and building automation equipment has resulted in the practice of installing direct
More informationHOW DO I KNOW IF THE CABLING FIRM I AM TALKING WITH IS REALLY QUALIFIED? Wire is Wire Q & A. Cabling is an Investment. Ask the Right Questions
Wire is Wire Anybody can install it, right? Just about anyone can run wire but a proper installation by a trained installer allows your technology investment to work at its full potential! Cabling is an
More informationANSI/TIA-568-C Cat 6 Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability
More informationLANcat System 6 with C5e Performance Module. User Manual Addendum
LANcat System 6 with C5e Performance Module User Manual Addendum Datacom Textron may make improvements or additions to this publication or their products at any time without notice. Datacom Textron shall
More informationThe AMP NETCONNECT Category 6 Cabling System
The AMP NETCONNECT Category 6 Cabling System Table of Contents TABLE OF CONTENTS... 3 PERSPECTIVE... 4 WHY INSTALL NEXT GENERATION CABLING SYSTEMS?... 4 MEGAHERTZ VS. MEGABITS... 4 PLANNING FOR THE FUTURE...
More informationCertification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More informationMaestro Wireless E206XT VZW OTAID: Mob_Firm_Rev = 101 Mob_Model = 15. Tested to:
731 Enterprise Drive Lexington, KY 40510 Open Development Lab Conformance Final Report Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek-etlsemko.com Verizon Wireless 180 Washington Valley Drive
More informationDate: July 16, 2009 Reference No.: P.O. No.: Page 1 of 5. Test Report For: HUMANSCALE INCORPORATED
4700 Broadmoor SE, Suite 200 Kentwood, MI 49512 Telephone: 616-656-7401 Facsimile: 616-656-2022 www.intertek-etlsemko.com HUMANSCALE INCORPORATED Report No.: 3184747GRR-001 P.O. No.: 55982 Page 1 of 5
More informationAppendix 1 to the R&Mfreenet Warranty Program
Appendix 1 to the R&Mfreenet Warranty Program 1 R&M Certification Process The R&Mfreenet certification process is three pillars: a) Adherence to applicable standards, both for products and installations;
More informationCopper Certification Testing Best Practices Pocket Guide
Copper Certification Testing Best Practices Pocket Guide Cabling certification is a best practice of world class installers because it shows the true quality of the installation and reduces the risk of
More informationCable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification
General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from
More informationLANmark-6 10G LANmark-6 A
Field-testing procedure of LANmark-6 10G LANmark-6 A Cabling System Technical Paper Nexans Cabling Solutions March 2006 - Revision 1.1 Table of Contents 1 Introduction 3 2 How to proceed? 4 2.1 Introduction
More informationIndependent Testing - For End User Confidence
Independent Testing - For End User Confidence QUALIFICATION TESTING OF SCREENED CATEGORY 6 A ISO/IEC, CENELEC & TIA CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF EDITION 2.2 OF ISO/IEC 11801, CENELEC
More informationStandard COM-002-2a Communications and Coordination
A. Introduction 1. Title: Communication and Coordination 2. Number: COM-002-2a 3. Purpose: To ensure Balancing Authorities, Transmission Operators, and Generator Operators have adequate communications
More informationQualified Partner Programme QPP. Cat.6 Channel Meassurement Issues Felice Guarna
Qualified Partner Programme QPP Cat.6 Channel Meassurement Issues Felice Guarna Agenda Channel and link definitions Why measure a channel? Patch cord affects on link performance The challenge of channel
More informationUSB Ranger 422 User Guide
USB Ranger 422 User Guide Featuring ExtremeUSB Technology USB Ranger 422 Thank you for purchasing the USB Ranger. Please read this guide thoroughly before installation. This document applies to Part Numbers:
More informationThe following pages contain a guide for the installation
INDEX The goal of this section is to illustrate how Siemon Company products can be used to support some of the most popular and emerging networks on the market. Section Contents 100Base-T....................................
More informationStandards Update. by Paul Kish NORDX/CDT
Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline
More informationThe AMP NETCONNECT Category 6 Cabling System
The AMP NETCONNECT Category 6 Cabling System 2 Table of Contents TABLE OF CONTENTS...3 PERSPECTIVE...4 WHY INSTALL NEXT GENERATION CABLING SYSTEMS?...4 MEGAHERTZ VS. MEGABITS...4 PLANNING FOR THE FUTURE...5
More informationCHAPTER 7 Copper Cable Testing
CHAPTER 7 Copper Cable Testing Lesson Objective After completing this lesson, you should be able to: i. Explain the various terms and instruments used to test copper cabling system. Cable Testing Cables
More informationDATWYLER SYSTEM WARRANTY
DATWYLER SYSTEM WARRANTY Copper Cabling System Appendix A2 Acceptance Requirements July 2014 Appendix A2_Acceptance Requirements Cu_July_2014_V01_EN.doc Seite 1/8 Contents 1. Acceptance of the transmission
More informationField-testing procedure of. LANmark-6 10G. Cabling System. Technical Paper Nexans Cabling Solutions June Revision 1.4
Field-testing procedure of LANmark-6 10G Cabling System Technical Paper Nexans Cabling Solutions June 2007 - Revision 1.4 Table of Contents 1 Introduction 3 2 How to proceed? 4 2.1 Introduction 4 2.2 Permanent
More informationLN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note
LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note LN-IOE400-0, LN-IOE410-0, LN-IOE420-0, LN-VAVCF-12, LN-PRGxxx-12
More informationFamily of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits
SYSTIMAX Structured Cabling Systems Family of Cords Quality Stranded and Solid Cords That Connect Data and Voice Circuits Lucent Technologies Family of Stranded Cords includes 110 patch, modular and adapter
More informationTO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled:
ADDENDUM NO. 2 TO THE BID PACKAGE FOR February 6, 2006 This addendum is being issued to modify portions of the Bid Package for the Project entitled: Receipt of this Addendum should be acknowledged by inserting
More informationTEST REPORT. STANDARD : RTCA/DO-160D:1997 Section 21.4
TEST REPORT STANDARD : RTCA/DO-16D:1997 Section 21.4 Applicant FUJITA ELECTRIC WORKS,LTD 945, Yamanishi,Ninomiya-machi, Naka-gun,Kanagawa 259-124 Japan Tel : +81 463 71 2541 Testing Laboratory Intertek
More informationINTERNATIONAL STANDARD
INTERNATIONAL TANDARD IEC 9- First edition 00-0 Generic cabling systems pecification for the testing of balanced communication cabling in accordance with IO/IEC 0 Part : Patch cords and work area cords
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Exploration Drive Aberdeen Science and Energy Park Aberdeen AB23 8HZ Contact: Mr Graham Robertson Tel: +44(0)1224 708500 Fax: +44(0)1224 772
More informationSCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 INTERTEK TESTING SERVICES NA INC. 3933 U.S. Route 11 Cortland, NY 13045 Terence O Beirne Phone: 607 758 6316 www.intertek.com ELECTRICAL Valid To: March 31,
More informationNew standards that have led to higher speeds and new cable categories. Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks
New standards that have led to higher speeds and new cable categories Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks Three Realities of Networking #1 - Networks Never Go Slower Plan for higher
More informationPCS PATCH CORD SOLUTIONS PATCH CORD SOLUTIONS
Structured Cabling Solutions PCS PATCH CORDS. HiPerlink 6 Colored Patch Cords- 35,36 HiPerlink 1000 Category 5e Colored Patch Cords- 35,36 Snap-in Icons 36 ScTP Category 5 Patch Cord 37 Category 5 Colored
More informationDatasheet: DSX CableAnalyzer Series
Datasheet: DSX CableAnalyzer Series Datasheet: DSX CableAnalyzer Series The DSX CableAnalyzer Series is the copper certification solution of the Versiv cabling certification product family. The DSX Series
More informationJamey Calloway, RCDD Product Management Specialist Optical Cable Corporation
Testing and deployment of direct attach and the impact of category 8 Thursday, 10 August 2017, 3:50-4:40 P.M. Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Overview Traditional
More informationCOMMONWEALTH OF KENTUCKY BEFORE THE PUBLIC SERVICE COMMISSION
COMMONWEALTH OF KENTUCKY BEFORE THE PUBLIC SERVICE COMMISSION In the Matter of: PETITION BY ALLTEL CORPORATION TO ) ACQUIRE THE KENTUCKY ASSETS OF ) CASE NO. VERIZON SOUTH, INCORPORATED ) 2001-399 SECOND
More informationWireScope 155 SCOPE. Agilent Wirescope 155 Specs Provided by The Performance Leader in Hand-Held Network Tools
Agilent Wirescope 155 Specs Provided by www.aaatesters.com WireScope 155 Tests installed cabling for compliance with TIA 568A Category 5 and ISO 11801 Class D specifications. Fully implements TIA TSB-67
More informationWhite Paper: Audio / Video (AV) Cabling Considerations
White Paper: Audio / Video (AV) Cabling Considerations Whether it s distance learning in the classroom, a video conference in the boardroom, or digital signage in the cafeteria, more and more enterprise
More information11/09/2007 Letter Report No NYM-001
11/09/2007 Letter Report No. 3137704NYM-001 Revision: 11/12/2007: Page 43 Revision: 11/14/2007: Page 13, 27, 33, 35 Project No. 3137704 Revision: 12/17/2007: Page 2, 6, 38, 39, 40, 41, 42 Revision: 04/10/2008:
More informationAgilent RF Network Analyzers PNA Series
Agilent RF Network Analyzers PNA Series Configuration Guide E8356A E8357A E8358A 300 khz to 3 GHz 300 khz to 6 GHz 300 khz to 9 GHz System Configuration Summary This summary lists the main components required
More informationThe High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester Our thanks to Fluke Networks for allowing us to reprint the following article. How much does it cost? That is typically the first question a cabling
More informationPerformance specification for the Fluke DSP Fluke Corporation
Performance specification for the Fluke Fluke Corporation 1. Summary This document contains the performance specifications in terms of requirements per draft TIA and IEC specifications. Since requirements
More informationCabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring
Cabling to support 802.11ac and beyond Nate Herring Sr. Product Manager Hubbell Premise Wiring IP Traffic Continues to Increase Globally, IP traffic will grow 3-fold from 2014 to 2019, a compound annual
More informationThe EB7-4W plugs onto one- or two-channel speaker or headset stations as illustrated in Figure 1. EB7-4W. Option. 4-Wire. Option
KB/HB-Series INSTALLATION INSTRUCTIONS EB7-4W Module Installation Clear-Com s EB7-4W 4-Wire Option module can be added to the KB-702, KB- 702GM, KB-701, and HB-702 products. This option allows the speaker
More informationCanadian Codes & Standards Updates
Canadian Codes & Standards Updates Canadian Codes & Standards Agenda: Which ones do we need to know? What are the latest versions What s changed in the latest versions? What did you miss? Standards Reference
More informationApplication & Electrical Performance. Category 5e Silver Solution
Application & Electrical Performance Category 5e Silver Solution CONTENTS Page No. Scope 3 Executive Summary 4 Transmission Test Method and Results 5-7 Electrical Test Method and Results 8-11 Definitions
More informationOLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide
OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide 2004-2009, AFL Telecommunications, all rights reserved. COM4-00-1001 Revision E, 2009-06-16 Specifications
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationPatch by Exception Module Jackfield User Manual
ADCP-0-00 Issue, October 99 Patch by Exception Module Jackfield User Manual Content Page TRODUCTION... Revision History.... GENERAL.... DESCRIPTION... A. Functional Description... B. Physical Description....
More informationR UNIT 2. Transmission Media DPW
UT 2 Transmission Media Topics in this Unit merican ational tandards nstitute ()/ Telecommunications ndustry ssociation (T) 568 standard nternational Organization for tandardization (O)/ nternational lecrotechnical
More informationDeviser Part No.: TC500-DL Deviser Instruments, Inc. All rights reserved.
TC500 Ethernet Cabling Certifier Operation Manual Version 1.13 Deviser Part No.: TC500-DL Deviser Instruments, Inc. All rights reserved. Warranty This instrument is guaranteed for a period of 2 years
More informationVERIZON TELEPHONE COMPANIES TARIFF FCC NO.
Director-Tariffs 1st Revised Page 19-1 600 Hidden Ridge Cancels Original Page 19-1 Irving, Texas 75038 Issued: September 28, 2001 Effective: October 13, 2001 1 (A) INTERCONNECTION BETWEEN COLLOCATED SPACES
More informationComplimentary Reference Material
Complimentary Reference Material This PDF has been made available as a complimentary service for you to assist in evaluating this model for your testing requirements. TMG offers a wide range of test equipment
More informationChanges or modifications not expressly approved by InFocus Corporation may void authority to operate the equipment.
Model: 2101 Declaration of Conformity Manufacturer: InFocus Corporation 27500 SW Parkway Avenue Wilsonville, OR 97070 We declare under our sole responsibility that this device conforms to the following
More informationCONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual
5915 SDI-12 Interface Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More informationDEALER SALES LETTER, U.S. NO. 825, CANADA NO. 900 SUBJECT: 2017 SERVICE EXCELLENCE PROGRAM / 2017 WARRANTY UPLIFT RATES
April 5, 2017 DEALER SALES LETTER, U.S. NO. 825, CANADA NO. 900 NEW HOLLAND DEALERS, NORTH AMERICA SUBJECT: 2017 SERVICE EXCELLENCE PROGRAM / 2017 WARRANTY UPLIFT RATES As announced in a prior dealer communication
More informationShadow Tracker TM Premier Base
Quick Start Users Guide Shadow Tracker TM Premier Base TM Advanced Tracking Technologies, Inc. 2003 ATTI All rights reserved Copyright 2003, Advanced Tracking Technologies, Inc. All rights reserved. No
More informationPayment Card Industry (PCI) 3-D Secure (PCI 3DS) Qualification Requirements for 3DS Assessors
Payment Card Industry (PCI) 3-D Secure (PCI 3DS) Qualification Requirements for 3DS Assessors Version 1.0 November 2017 Document Changes Date Version Description November 2017 1.0 Initial Release of the
More informationHow new testing standards affect you Singapore, Nov 2009
How new testing standards affect you Singapore, Nov 2009 Adrian Young Sr. Customer Support Engineer In this presentation, we will cover How ANSI/TIA-568-C.2 has consolidated all the different test plugs
More informationIEEE Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3
IEEE 802.3 Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire The Siemon Company Dallas, TX November 9, 2015 Page 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org
More informationIndependent Testing - For End User Confidence
Independent Testing - For End User Confidence QUALIFICATION TESTING OF SCREENED CATEGORY 5 (CAT. 5e) CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF PROPOSED CENELEC 2nd EDITION EN 50173, PROPOSED ISO/IEC
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationGetting Started Guide
TM CableIQ Qualification Tester Getting Started Guide PN 2113427 January 2005, Rev. 1 3/07 2005, 2007 Fluke Corporation. All rights reserved. Printed in China. All product names are trademarks of their
More informationTelephone - Pa. P.U.C. No. 1. Contel of Pennsylvania, Inc. Section 15 d/b/a GTE Pennsylvania Original Sheet 1
Contel of Pennsylvania, Inc. Section 15 d/b/a GTE Pennsylvania Original Sheet 1 A. GENERAL 1. This Tariff section contains regulations, rates and charges applicable to the provision of certain functional
More informationCase study of certification for telecommunications terminal equipment in Japan
Case study of certification for telecommunications terminal equipment in Japan March 26, 2010 Japan Approvals Institute for Telecommunications Equipment (JATE) Hiroshi Arakawa Equipment Approvals Dept.
More informationEnterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India
Enterprise Network Test Strategies for Network Availability and Performance A Sitaramaiah Director Fluke Networks India 1 Why is Enterprise Network Testing becoming increasingly important? IT is increasingly
More informationCase study of certification for telecommunications terminal equipment in Japan
1 Case study of certification for telecommunications terminal equipment in Japan March 26, 2010 Japan Approvals Institute for Telecommunications Equipment (JATE) Hiroshi Arakawa Equipment Approvals Dept.
More informationP.L. 2007, CHAPTER 85, approved May 4, 2007 Assembly, No. 2568
P.L. 00, CHAPTER, approved May, 00 Assembly, No. 0 0 0 0 AN ACT concerning the transmission of certain unsolicited advertisements over telephone lines and amending P.L.00, c. (C.:- et seq.). BE IT ENACTED
More informationDTX-NSM Network Service Module Getting Started Guide
DTX-NSM Network Service Module Getting Started Guide The DTX-NSM Network Service Module lets you do the following: Verify connection to the network, including connection speed, duplex configuration, link
More informationStandard COM Communication and Coordination
A. Introduction 1. Title: Communication and Coordination 2. Number: COM-002-3 3. Purpose: To ensure Emergency communications between operating personnel are effective. 4. Applicability 4.1. Reliability
More informationNGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit
NGEAB-T Use Cases Berlin, Germany February 2015 Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Scope Next Generation Enterprise Access BASE-T PHY Study Group to define use cases and deployment
More informationBLACKBOX NETWORK SERVICES. one source for worldwide infrastructure services
BLACKBOX NETWORK SERVICES one source for worldwide infrastructure services 24 Port 10/100Mbps plus 2 Gigabit TX/FX Auto-MDIX Modular Gigabit Ethernet Switch User s Manual FCC Warning This device has been
More informationTIA TR-42 Liaison to IEEE
TIA TR-42 Liaison to IEEE Val Rybinski Vice-Chair, TR-42.7 May 2005 Austin, TX Impact of PHY Capabilities Extended frequency characterization required Alien crosstalk limits and test methods required Strategies
More informationA FLUKE networks DTX 1800 Cable Analyzer és DTX Fiber Modules
A FLUKE networks DTX 1800 Cable Analyzer és DTX Fiber Modules Rövidített leírás és kezelési utasítás The DTX Series CableAnalyzers are rugged, hand-held instruments used to certify, troubleshoot, and document
More informationR ental of C ollege F acilities Policy
Title: Rental of College Facilities Policy Approval June 10, 1997 Date of Last Revision :April 27, 2006 Policy Category: Administration Number: B.3.3. Rental of College Facilities Policy Purpose To inform
More informationTesting Considerations for Beyond 10Gigabit Ethernet. Erin Hallett
Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices
More informationCategory 8 paves the way for IEEE 40GBASE-T. David Hughes RCDD/DCDC/NTS Senior Technical Manager MEA CommScope
Category 8 paves the way for IEEE 40GBASE-T David Hughes RCDD/DCDC/NTS Senior Technical Manager MEA CommScope Agenda Market need for 40 G over balanced twisted pair cabling Standards ISO/IEC 11801-99-1
More informationPhysical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks
Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Agenda New ISO/IEC 11801 Standard New Fibre standards and encoding methods Higher speeds,
More informationRequest for Proposal (RFP) Contents
Request for Proposal (RFP) Contents Introduction... 2 Proposal Requirements... 2 Deadline and Contact Information... 2 Identify Non-Eligible Services or Products... 2 Right to Reject Proposal... 2 Statement
More informationOptical Multiplexer. Quick Start Guide
Optical Multiplexer Quick Start Guide Part Number: 07M1195-QS, Rev. A Revised: February 12, 2009 Sales Office: +1 (301) 975-1000 Technical Support: +1 (301) 975-1007 E-mail: support@patton.com WWW: www.patton.com
More informationUser Manual. Unimax HSPA+ Ethernet Modem Router with I/O Board
+ Unimax HSPA+ Ethernet Modem Router with I/O Board User Manual This manual is the sole and exclusive property of Maxon Australia. Not to be distributed or divulged without prior written agreement. Unimax+
More informationCat 6 (500 MHz) UTP solid cable (PVC sheath)
JetLan is the only structured cabling system that includes all the passive elements required by the installation or modification of your data networks, as it offers all the options for high performance
More informationHygroClip DI Digital Interface for HygroClip Probes v 1.0 Instruction Manual
HygroClip DI Digital Interface for HygroClip Probes v 1.0 Instruction Manual page 2 of 15 Contents: Overview... 2 Models... 3 Power... 4 Probes... 4 Connector identification... 5 Pin-out diagrams... 6
More informationUSB/VGA Cat 5 UTP Long Range Console Extender
USB/VGA Cat 5 UTP Long Range Console Extender SV565UTPUL *actual product may vary from photos FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class B digital
More informationChapter 3 Certifying Twisted Pair Cabling
Chapter 3 Certifying Twisted Pair Cabling Setting the Reference The reference procedure sets a baseline for insertion loss, ELFEXT, and dc resistance measurements. Run the tester s reference procedure
More informationField-testing procedure. LANmark-6
Field-testing procedure LANmark-6 Technical Paper Nexans Cabling Solutions September 2006 Table of Contents 1 Introduction 3 2 How to proceed? 4 2.1 Introduction 4 2.2 Permanent link testing vs. Channel
More informationCopper Cabling Standards
Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals
More informationUSER MANUAL MODEL 570-R8/570-R R8/580-R Base-T (CAT-5) Surge Protectors
USER MANUAL MODEL 570-R8/570-R16 580-R8/580-R16 100Base-T (CAT-5) Surge Protectors C E R T I F I E D An ISO-9001 Certified Company Part #07M570/580RC-A Doc# 074101UA Revised 2/13/97 SALES OFFICE (301)
More information