Spencer Murray, Sr. Telecom Eng.
|
|
- Phyllis Mason
- 6 years ago
- Views:
Transcription
1 Distribution Automation Spencer Murray, Sr. Telecom Eng.
2 Why FortisAlberta choose Distribution Automation? Reliability (SAIDI, SAIFI) Operational benefits: Load balancing between substations. Real-time load values of the system. Remote Switching Reducing Customer Outage Time 2
3 FortisAlberta Restoration Permanent short circuit (fault) occurs on a distribution feeder, all or some of the customers served by the feeder will experience a loss of power until field crews are able to restore service. Field crew activities : 1) Traveling to the general vicinity of the feeder fault, based on customer calls and feeder protective devices 2) Patrolling the feeder to determine the exact location of the fault 3) Isolate the damaged section by performing manual switching and restoring customers as quickly as possible. 4) Repairing the damage 5) Performing manual switching to restore the feeder to its original configuration. This restoration can take 30 minutes or longer. 3
4 Distribution Automation Restoration Distribution automation provides a means to perform activities 1 through 3 listed on the previous page. With S&C Electric automated switches and the IntelliTeam software will restore some of the customers on the feeder in one minute or less. The fault is isolated between two switches which decrease the patrolling and the restoration time. Fewer customers are affected by the fault and the customers that are affect are restored quicker. This improves our customer satisfaction, SAIDI and SAIFI. 4
5 Our Obstacles: No Control Center No Communications Infrastructure No Substation RTU How do we know a switch operated or Normally Opened moved because of fault How can we perform switching operations remotely? 5
6 S&C Electric Company Equipment (25KV) Padmounts: PMH-9, PMH-10 & PMH-11 SCADA-Mate Switch, 3 pole switch IntelliRupter Pulse Closer IntelliTEAM II Automatic Restoration System 6
7 Monitoring Control Application (MCA) Requirements Report switch status and also something we could use to operate the switches. Accessible by our PLTs from their trucks because we have no control center. Visual of the substation and real time load values of the feeders, but no control of anything in the sub. 7
8 Bow Networks elan Front End Processor (FEP) Acts as a SCADA master retrieving point data from the field devices Issues control commands to the field devices elan HMI Provides a secure web-launch visualization of the field data Provides a single line diagram of Airdrie and St. Albert Universal DNP Gateway (UDG) Collects real-time data from the GE D20 s in the substation 8
9 9
10 Airdrie MCA 10
11 199s Substation 11
12 5803 Control/Padmount PMH-11 12
13 View Detail Summary 13
14 IntelliRupter PulseCloser 14
15 St Alberta MCA 15
16 Communications: Switches Airdrie DA UtiliNet Radio Mhz 96Kbps 9.6Kbps Node Identification is a GPS coordinates St. Albert DA SpeedNet Radio Mhz 650Kbps IP Address 16
17 Communications: Head End HeadEnd Radio: Located at service point office Backhaul the data to elan FEP where Bow Networks host our elan HMI for Airdrie and St. Albert PLT Access Every PLT has a laptop and EVDO modem in their truck that t allows the access to the server. Citrix 17
18 Reliability Airdrie DA installed late Total unplanned outages: 25087hours Saved 8574 customer hours, 25% 2009 Added 2 new feeders from 186S Dry Creek sub in 2009 We have had a couple of operations due to public contact and weather Overall our SAIDI/SAIFI has not improved but we also have realized that our SAIDI/SAIFI results would be worse if we didn t have DA. 18
19 Our Experiences PLTs use it as a remote switching tool PLT s use it to look at loading conditions New set of tools required for Metering Group Radio s Ethernet Addressing If the same fault occurred a the same spot it doesn t mean the DA will heal itself the same way as last time. 19
20 Questions? 20
IntelliTeam II Automatic Restoration System
No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer
More informationS&C 6801M Automatic Switch Operator
S&C 6801M Automatic Switch Operator for Overhead Distribution Switches and Disconnects Simple, Economical Switch Automation S&C s 6801M Automatic Switch Operators make it easy to automate new or existing
More informationThe Reliability Switch
AUGUST 2006 TM www.tdworld.com TXU Electric Delivery Flips The Reliability Switch by Alan Bern, TXU Electric Delivery Distribution automation system rollout reduces feeder outage times. IN AN EFFORT TO
More information2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation
More informationCIGRE U.S. National Committee
CIGRE U.S. National Committee 2014 Grid of the Future Symposium October 20, 2014 Houston, TX New Tools for Managing Smart Switching Devices Chris McCarthy, Jason Lombardo S&C Electric Company CWG/9416P
More informationFAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY
FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY Fahrudin Mekic Ken Alloway Cleber Angelo Robert Goodin ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com.ken.alloway@us.abb.com
More informationDNP Points List and Implementation
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2
More informationApplication of Distributed Intelligence to Automatic Distribution Reconfiguration for Reliability Improvement
Application of Distributed Intelligence to Automatic Distribution Reconfiguration for Reliability Improvement Doug Staszesky Director Product Management Automation Systems Division S&C Electric Company
More informationFault and outage management
WEBINAR, SEPTEMBER 2017 Distribution Automation for electrical grids Fault and outage management Alain Aurus, Theodoros Oikonomou, Yasmine Vögele Introduction Facility Management Use the detach button
More informationSpecifications. S&C IntelliNode Interface Modules. Conditions of Sale
Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheets 150 and 181 apply, except as modified by the SPECIAL WARRANTY PROVISIONS and WARRANTY QUALIFICATIONS
More informationIntelligent Grid and Lessons Learned. April 26, 2011 SWEDE Conference
Intelligent Grid and Lessons Learned April 26, 2011 SWEDE Conference Outline 1. Background of the CNP Vision for Intelligent Grid 2. Implementation of the CNP Intelligent Grid 3. Lessons Learned from the
More informationSpecifications. S&C IntelliNode Interface Modules
Specifications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheets 150 and 181 apply, except as modified by the SPECIAL WARRANTY PROVISIONS and WARRANTY QUALIFICATIONS
More informationSmart Distribution Technology
Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications
More informationQUALITY OF SERVICE INDICATORS UNDER CYBER ATTACKS BY RAO SIMULATOR
QUALITY OF SERVICE INDICATORS UNDER CYBER ATTACKS BY RAO SIMULATOR Multitel (S.Iassinovski) Multitel Research Center Parc Initialis, rue Pierre et Marie Curie n 2 B-7000 Mons, Belgium iassinovski@multitel.be
More informationProduct Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet
S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................
More informationAdvanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric
More informationS&C IntelliRupter PulseCloser. Outdoor Distribution 14.4 kv and 25 kv
S&C IntelliRupter PulseCloser Outdoor Distribution 14.4 kv and 25 kv Descriptive Bulletin 766-30 February 7, 2006 New Publication 2006 IntelliRupter PulseCloser Tomorrow s Technology Available Now S&C
More informationImproving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management
Improving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management David Lyons Georgia Power Brad Williams Oracle Kevin Costin - Oracle Southern
More informationJussi Ahola, ABB Oy A self healing power system for the accurate fault location and zone concept T&D Smart Grids Europe 2012
Jussi Ahola, ABB Oy A self healing power system for the accurate fault location and zone concept T&D Smart Grids Europe 2012 October 16, 2012 Slide 1 Introduction Why self-healing? Needs to improvements
More informationDan Murray, Siemens Energy Management Division
Design and Implementation of a Communication Network to Support Real-time Distribution Feeder Automation, SCADA Integration and Backhaul of Substation and Metering Data Dan Murray, Siemens Energy Management
More informationSouth Tulsa Switch Automation Pilot
South Tulsa Switch Automation Pilot Presented by: Bret Goodwin, P.E., Distribution System Planning Supervisor AEP-Public Service Company of Oklahoma May 2010 SWEDE Conference Abstract for SWEDE, 2010 Title:
More informationEvaluation of Business Cases for Smart Grid Solutions Kenny Mercado, Senior VP Electric Operations
Evaluation of Business Cases for Smart Grid Solutions Kenny Mercado, Senior VP Electric Operations April 21, 2015 CenterPoint Energy (CNP) Headquartered in Houston, Texas Serving 5.7 million electric &
More informationOperating and Diagnostic Instructions for IntelliTeam SG Automatic Restoration System
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Operating and Diagnostic Instructions for IntelliTeam SG Automatic Restoration System Table of Contents
More informationRoad Map to Grid Modernization
Road Map to Grid Modernization APIC, University of Alberta May 5 th, 2016 Presenter: Chris Chapelsky, MSc., P.Eng. Operations 1 Engineer About EPCOR Water & Power Transmission & Distribution in Edmonton
More informationKarl Iliev, San Diego Gas & Electric Company
INTEGRATING DER THROUGH DISTRIBUTION SYNCROPHASORS Karl Iliev, San Diego Gas & Electric Company 2002 San Diego Gas and Electric Co. and Southern California Gas Company. All copyright and trademark rights
More informationSmall Generator Interconnection System Impact Study Report. Completed For Q0047
Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection
More informationEPB UPDATE. North American Power Credit Organization September 12, 2013
EPB UPDATE North American Power Credit Organization September 12, 2013 1 FIBER OPTICS 2 Chattanooga s Fiber Network Fiber-To-The-Home A GPON-Gigabit Passive Optic Network Two multiple 10 gig fully redundant
More informationSpecifications. S&C 6801 Automatic Switch Controls
Specifications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the SPECIAL WARRANTY PROVISIONS and WARRANTY QUALIFICATIONS
More informationFCIs reduce fault-locating times and improve reliability metrics, especially the Customer Average Interruption Duration Index (CAIDI).
1 Intelligent electronic devices (IEDs) are the preferred choice for modernizing the grid. Communication among networks of robust IEDs designed for protection, control, and monitoring (PCM) of the power
More informationSpecifications. S&C 6802 and 6803 Automatic Switch Controls
Specifications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the SPECIAL WARRANTY PROVISIONS and WARRANTY QUALIFICATIONS
More informationCONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM...
GENERAL INFORMATION Contents CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM... 3 COMMUNICATION... 4 BUILDING-BLOCKS... 5 NETTROLL AND NETDRAW... 5 NETALERT... 6 NETGRAPH... 7 COMTROLL OUTSTATIONS...
More informationSacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,
Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines
More informationHigh-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY
S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are
More informationAPIC FortisAlberta s SCADA FAULT INDICATOR Project
APIC 2017 FortisAlberta s SCADA FAULT INDICATOR Project Project requirements Project investigation Project evaluation Project integration Question period Who are we? Large Service Territory Wire Service
More informationA Hybrid Communications Network Approach for Advanced Applications on the Modern Grid
A Hybrid Communications Network Approach for Advanced Applications on the Modern Grid Mark A. Carella, PE Manager Distribution Control and Integration nationalgrid Private Telecom Network Key Stats Private
More informationUniSec, MV AIS for Secondary Distribution Smart Grid applications
Ing. Natalia Moizzes- Switchgear Product Specialist Chile Abril 14 th 2015 UniSec, MV AIS for Secondary Distribution Smart Grid applications Slide 1 Concept - Needs and Solutions Requests are: Manage faults
More informationS&C IntelliRupter PulseCloser Fault Interrupter
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution, 15.5 kv through 38 kv IntelliRupter PulseCloser Fault Interrupter Tomorrow s Technology Available Today S&C s IntelliRupter PulseCloser
More informationTETRA for SCADA Challenges in CLP
TETRA for SCADA Challenges in CLP CCW 2016 Amsterdam Ir. Terrance Lai Digital Systems Manager CLP Power Hong Kong Ltd CLP Group One of the largest investor-owned utility companies in Asia We generate,
More informationEvolution of Control for the Power Grid
Evolution of Control for the Power Grid Anjan Bose Washington State University Pullman, WA, USA PaiFest In Honor of Prof. M. A. Pai Urbana-Champaign, IL October 15, 2015 The Past (before 1960s) Hard
More informationA Hybrid Communications Network Approach for Advanced Applications on the Modern Grid
A Hybrid Communications Network Approach for Advanced Applications on the Modern Grid Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures should
More informationThe Smart Utility Meets The Smart tgid Grid. The Smart. Bob Uluski. Technology Quanta Technology LLC
The Smart Utility Meets The Smart tgid Grid The Smart Substation Bob Uluski Quanta Technology Why is the Smart Substation Key power apparatus important? for maintaining the reliability and efficiency of
More informationNew Tools for Managing Smart Switching Devices. C.A. MCCARTHY S&C Electric Company USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium New Tools for Managing Smart Switching Devices C.A. MCCARTHY S&C Electric Company USA
More informationAuto-Changeover & Feeder Automation. Reclosers & Sectionalizers
Auto-Changeover & Feeder Automation Reclosers & Sectionalizers WHY AUTOMATE? COMPETITION SERVICE VALUE QUALITY RELIABILITY REGULATION RATES BASED ON RELIABITY & PERFORMANCE PENALTIES REGULATION SAIDI (System
More informationBlackout 101. Dr. B. Don Russell Texas A&M University. Dr. Bruce Wollenberg University of Minnesota. Mr. John McDonald KEMA, Inc.
Blackout 101 Dr. B. Don Russell Texas A&M University Dr. Bruce Wollenberg University of Minnesota Mr. John McDonald KEMA, Inc. Dr. Pete Sauer University of Illinois at Urbana-Champaign An Electric Power
More informationAMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network
AMEU 2012 FuseSaver Highest availability and cost savings for your medium voltage distribution network October Page 2012 1 Siemens IC AG LMV 2012 MV C PPM Challenges for rural networks Characteristics
More informationWi-Fi and Security Administration
S&C PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Wi-Fi and Security Administration Table of Contents Section Page Section Page Introduction Qualified Persons...2 Read
More informationDocking Station Instructions
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Docking Station Instructions Table of Contents Section Page Section Page Introduction Qualified Persons...
More informationS&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)
Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The
More informationPower System Control And Smart Grid
Power System Control And Smart Grid The Technology Journey so far... 2005-07 2007-09 2009-11 2011-12 OMS Implementation ISO 27001- Security certification Basic DMS Application,SPM JGC DMS System & Distribution
More informationSouthern Company Smart Grid
Southern Company Smart Grid Smart Grid Investment Grant Update July 25, 2011 Southern Company Southern Company is one of the nations largest generators of electricity Has 4.4 million retail customers across
More informationCentralized & Distributed Intelligence applied to Distribution Automation
Centralized & Distributed Intelligence applied to Distribution Automation Table of Contents Automated Feeder restoration, put to the test Centralized Control and Distributed intelligence Distributed intelligence
More informationSUBSTATION-BASED SELF-HEALING SOLUTION WITH ADVANCED FEATURES FOR CONTROL AND MONITORING OF DISTRIBUTION SYSTEMS
SUBSTATION-BASED SELF-HEALING SOLUTION WITH ADVANCED FEATURES FOR CONTROL AND MONITORING OF DISTRIBUTION SYSTEMS Daniel Perez DUARTE João Carlos GUARALDO Henrique KAGAN Sinapsis Brazil Sinapsis Brazil
More informationRemote Terminal Unit ER1000 APPLICATION FEATURES
Remote Terminal Unit ER1000 ERL with more than three decades of expertise in Power System Protection have developed state of the art Automation Solutions. The whole family of ERL s Remote Terminal Unit
More informationGENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault.
GENERAL INFORMATION Improve customer satisfaction Customer satisfaction is often difficult to measure. One of the key figures used to indicate the performance of a distribution network is SAIDI. SAIDI
More informationProduct brochure. Grid automation system solutions
Product brochure Grid automation system solutions Improve reliability, productivity and energy efficiency Eaton s Smart Grid solutions provide utilities with the technology they need to build, transform,
More informationS&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application
Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The
More informationg Energy Multilin Recloser Controller DGCR Communications Protection Automation & Control Security & EnerVista Software Hardware Metering & Monitoring
Multilin Recloser Controller DGCR Key Benefits 4 shot auto-recloser 3 setting groups enable different setting selections based on switched conditions Advanced logic engine and multiple IOs for creating
More informationUsing WiMAX for Distribution Automation
Using WiMAX for Distribution Automation Page 1 RuggedCom market share of > 50% in the Electric Power T&D Substations market for communications RuggedCom market share Electric Power T&D Substations market
More informationWhat You Should Know About Communication Systems: Business Strategies and Options
Doug Voda, PPMV Global Segment Leader for Smart Grid February 2015 NRECA TechAdvantage What You Should Know About Communication Systems: Business Strategies and Options The visionary Smart Grid Five Pillars
More informationSpecifications. S&C Pad-Mounted Style IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv and 27 kv)
Outdoor Distribution (155 kv and 27 kv) Specifications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheets 150 and 181 apply, except as modified by the SPECIAL
More informationActive Distribution Networks: Chad Abbey
Active Distribution Networks: Canadian Example Projects Chad Abbey Overview Background Active distribution networks integration of DER and distribution automation Canadian context Utility projects Natural
More informationIMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7
IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 LINETROLL 110Eµ 8 LINETROLL 111K 9 LINETROLL L400D 10
More informationSmart Solutions Smarter Grid
Smart Solutions Smarter Grid Optimizing Efficiency, Productivity, and Reliability Stef.Budai@CooperIndustries.com Consultant Grid Automation FECA Conference 2012 Contents Why the Smart Grid? Utility Industry
More informationPreparing for the Dynamic Grid of Future
Preparing for the Dynamic Grid of Future Peter Hoffman, P.E. Duke Energy, Grid Solutions Engineering & Technology POWERING LIVES & COMMUNITIES Environmental Stewardship Reliable Service Affordable Rates
More informationDigital Transformation of Power Delivery
Digital Transformation of Power Delivery Keynote Speech Professor Saifur Rahman, PhD Virginia Tech, USA IEEMA Engineer Infinite Conference, Delhi NCR, India, 14 March 2018 Traditional Electricity Delivery
More informationKEDS DSO Development Plan. George Karagutoff, KEDS CEO Prishtina, Kosovo 20 March, 2018
KEDS DSO Development Plan George Karagutoff, KEDS CEO Prishtina, Kosovo 20 March, 2018 1 INVESTMENTS AT A GLANCE KEDS begun its operations after the successful unbundling of Distribution and Supply business
More informationDNP Points List and Implementation
S&C 6800 Series Automatic Switch Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for 6801 Controls...1 6801 Status Points...2 6801 Double-bit Status
More informationElectro Industries GaugeTech
Bakersfield Refining Company Ensures Productive Operations with Advanced Power Monitoring Bakersfield Refining Company is part of Equilon Enterprises LLC, a partnership between Shell and Texaco. Their
More informationThis webinar brought to you by the Relion product family
This webinar brought to you by the Relion product family Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter, more flexible and more adaptable. Easy
More informationAutomation Services and Solutions
Automation Services and Solutions Automate substation data acquisition and control to improve performance Maintain uninterrupted power services with proactive grid monitoring and controlling features.
More informationSetup. S&C 5800 Series Automatic Switch Controls With IntelliTeam Automatic Restoration System. Table of Contents. Instruction Sheet
S&C 5800 Series Automatic Switch Controls With IntelliTeam Automatic Restoration System Setup Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet....
More informationCase Study Improving System Performance Using Distribution Network Automation
Case Study Improving System Performance Using Distribution Network Automation Aaron Smith, Mike Watson, Jeff Hauber, and Clayton Stubbs Westar Energy Bill Flerchinger, Dennis Haes, and Will Allen Schweitzer
More informationNpefm!681F! !!!681F!Gjcfspqujd!Usbotdfjwfs! Gjcfspqujd!Ofuxpsl!Tpmvujpo!! Model 570E Features. The Fiberoptic Communications Specialists
!!!681F!Gjcfspqujd!Usbotdfjwfs! Gjcfspqujd!Ofuxpsl!Tpmvujpo!! The Fiberoptic Communications Specialists The Model 570E offers high-speed serial communication to meet the challenging needs of distribution
More informationAUTOMATION OF POWER DISTRIBUTION USING SCADA
1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from
More informationSIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.
www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection
More informationRevised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )
Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original
More informationSensus RTM II+ Description. Applications. Features and Benefits. Smart Communication Gateway and Control DDS Features
DDS-10000-07 Sensus RTM II+ Smart Communication Gateway and Control Description The Sensus Remote Telemetry Module Plus (RTM II+) is a powerful communication solution for enabling remote monitoring and
More informationLightweight and flexible recloser control for single-phase applications
SEL-35S Kestrel Single-Phase ecloser Control Lightweight and flexible recloser control for single-phase applications Plug-and-work operation with popular single-phase reclosers simplifies new and retrofit
More informationSynchronous switching of distribution sub networks
Synchronous switching of distribution sub networks Paul Stergiou ConEdison USA Manuel P Pimenta, - ConEdison USA Sergio A Rodriguez ConEdison USA Thomas Horan ConEdison USA Andre Smit- Siemens Industry
More informationThe PowerLogic range. Gain energy insight and control
The PowerLogic range Gain energy insight and control The PowerLogic advantage PowerLogic is the world's largest and most advanced range of software and metering products for managing energy, giving suppliers
More informationSurvalentONE Distribution Management System
SurvalentONE Distribution Management System Analyze & Optimize Critical Grid Functions for Advanced System Monitoring & Control SurvalentONE ADMS The SurvalentONE ADMS platform is a fully integrated SCADA,
More informationBlueprint Data Center
Systems and Applications for Data Center Siemens Industy 1. Overview / Purpose In EM EA the datacenter market is seen as one of the fastest growing of the energy businesses. This blueprint is designed
More informationSource-Transfer Application Guide
S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this
More informationDNP Points List and Implementation for Universal Controls
S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for Universal Controls Table of Contents Section Page Section Page DNP Points List for 6801 Universal Controls...1 6801 Status
More informationAMR and SCADA in Outage Management System for MSEDCL Sangita B. Patil 1, Bapu K. Patil 2
e-issn: 2349-9745 p-issn: 2393-8161 Scientific Journal Impact Factor (SJIF): 1.711 International Journal of Modern Trends in Engineering and Research www.ijmter.com AMR and SCADA in Outage Management System
More informationPower Distribution Automation Solution Smart Grid Data Aggregation. Patrick Pipet IEA/ADEME Workshop XVII may 18th, 2011
Power Distribution Automation Solution Smart Grid Data Aggregation Patrick Pipet IEA/ADEME Workshop XVII may 18th, 2011 The energy dilemma is here to stay The facts The need Energy demand By 2050 Electricity
More informationDemonstration of the UPGRID project urban network of the future
Demonstration of the UPGRID project urban network of the future SŁAWOMIR NOSKE, DOMINIK FALKOWSKI ENERGA-OPERATOR SA e-mail: {slawomir.noske/dominik.falkowski}@energa.pl 1. Introduction Sustainable development,
More informationLine Current Differential Protection Using Broadband Power Line Carrier Technology
Line Current Differential Protection Using Broadband Power Line Carrier Technology Nachum Sadan CEO Amperion Inc. 2013 Utilities Telecom Council Delivering Your Future About Amperion Provider of advanced
More informationSecure, Smart Grid Data Access Radically Simplified
/****** Object: View [dbo].[gs_data_view] Script Date: 06/04/20 ******/ IF EXISTS (SELECT * FROM sys.views WHERE object_id = OBJECT_ID(N [ View] )) DROP VIEW [dbo].[gs_data_view] USE [gridsenseiqobjectmodel.entitycontext]
More informationRecloser Controller for feeder protection and automation siemens.com/distribution-automation
SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast
More informationg Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications
Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy
More informationProducts Portfolio. Pole mounted Vacuum Recloser
Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,
More informationDISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT
DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT SCADA TO DG SITES DIGESTER MW AND MVAR INSTANTANEOUS READINGS FROM SEL 751 RELAY TRASK SUBSTATION LOADING DO NOT WANT TO FEED INTO
More informationENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER
smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS
More informationFOR THE NEW ENERGY GENERATION
FOR THE NEW ENERGY GENERATION SCADA, Fit for the Future? Marko Kruithof STEDIN KEY FIGURES (2015) The world is changing THE (ENERGY) WORLD IS CHANGING RAPIDLY Stedin has identified 11 influential trends
More informationTransmission Infrastructure Investment & Development in Vietnam
Transmission Infrastructure Investment & Development in Vietnam Presented by: Mr. Cao Duc Dung Expert of Technical Department National Power Transmission Corporation (NPT) 28 September, 2011 1 CONTENTS
More informationLoop Scheme Cuts Utility Customer Outage Duration BILL BARNHART HANCOCK-WOOD EC MICHAEL LABIANCO G&W ELECTRIC
Loop Scheme Cuts Utility Customer Outage Duration BILL BARNHART HANCOCK-WOOD EC MICHAEL LABIANCO G&W ELECTRIC Our Case Study Justification for SCADA and DA Improve Reliability Implement Loop-Scheme Distribution
More informationDesigning a new IEC substation architecture
Designing a new IEC 61850 substation architecture Gerrit Dogger Senior Product and Application Specialist Cooper Power Systems gerrit.dogger@cybectec.com Garry Tennese Station Integration Specialist Manitoba
More informationExchange of Data and Models between Control Centers
Exchange of Data and Models between Control Centers Anjan Bose Washington State University Pullman, WA, USA EPCC Workshop Bled, Slovenia May 18-20, 2015 West European Power Grid Balancing Authorities
More informationNEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS
NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS John DULLER Ahsan HALIM Gordon PATON UK Power Networks UK UK Power Networks UK General Electric - UK john.duller@ukpowernetworks.co.uk
More information