Fault Tolerant Intelligent Access Control System Installation Manual REV: B

Size: px
Start display at page:

Download "Fault Tolerant Intelligent Access Control System Installation Manual REV: B"

Transcription

1 Fault Tolerant Intelligent Access Control System Installation Manual REV: B PCSC 3541 Challenger Street Torrance, CA Phone: (310) FAX: (310)

2 First Edition: January 2010 Revision August 2011 Information in this manual is subject to change without notice and does not represent a commitment on the part of PCSC. The software described in this manual is furnished under a license agreement or nondisclosure agreement. The software may be used or copied only in accordance with the terms of the agreement. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other than specified in the agreement, without the express written permission of PCSC PCSC. All Rights Reserved. Printed in the United States of America. Published by PCSC 3541 Challenger Street Torrance, CA (310) ph/fax Publication Number: B Page 2 of 101 Fault Tolerant Controller Manual B

3 0.1 Board Diagrams The FT Printed Circuit Board Wiring Diagram Page 3 of 101 Fault Tolerant Controller Manual B

4 0.1.2 The FT Rack-Mounted Page 4 of 101 Fault Tolerant Controller Manual B

5 0.1.3 The DDM Printed Circuit Board Wiring Diagram Page 5 of 101 Fault Tolerant Controller Manual B

6 The SDM Printed Circuit Board Wiring Diagram NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 6 of 101 Fault Tolerant Controller Manual B

7 0.2 Table of Contents 1.0 Introduction Theory of Operation Redundancy Installing Power Installing Power to the FT and DDM Installing Power PCSC 3.0 Amp or 6.0 Amp Power Supply (DDM only) Installing Power SDM Installing Power- 3.0 Amp PCSC 3.0 Amp Power Supply Resetting a Panels to Default Values Wiring the Readers Grounding the Readers Properly Routing the Cables Grounding the Power and Data Lines Procedure Grounding the Pin Pad or Reader Procedure Grounding the Reader Mullion Mount Reader Connections to the DDM Reader Disconnect Resistors Compatible UL Listed Readers: Reader Connections: PR233 MiniProx / PR-733/ Reader Connections: PR-234 / PRK-234 ProxPro / PR736 / PRK Reader Connections: PR-235 MaxiProx / PR Reader Connections: Sensor Wiegand Reader Connections: VeriProx / V-Pass/ Reader Connections: iclass Reader Connections: Xceed ID SP632/SP632M/SP633/SP635/SPK Reader Connections: Biometric Wiring the Door(s) Wiring the Panel in a Fail-Safe Environment Fail Safe - DDM Fail Safe - SDM Wiring Panel in a Fail-Secure Environment Fail-Secure - DDM Fail-Secure - SDM Page 7 of 101 Fault Tolerant Controller Manual B

8 5.3 LED Arrays Using the Seven Segment LED Array Status Chart for All LED Arrays Installing Noise Suppression Device Procedure Reset button Reset button on the FT and DDM Reset Button on the SDM Communicating with the FT, DDM and SDM through TCP/IP Connecting to a Panel via TCP/IP Programming the FT Connecting to a FT Setting the Name and IP Address of a FT Configure a Network of Connected FTs Setting the Time Zone for a Particular Panel Changing the Password Specifying the IP Address to Allow FT configuration access Programming the Dual Door Module Connecting to the DDM Setting the Name and IP Address of a DDM Configure the DDM s Primary FT and Secondary FTs Setting the Time Zone for a Particular Panel Changing the Password Specifying the allowable Hosts and Workstations within a network Programming the Single Door Module Connecting to the SDM Setting the Name and IP Address of a SDM Configure the SDM s Primary FT and Secondary FTs Changing the Password on the SDM Setting the Time Zone for a Particular Panel on the SDM Setting the Panel Number for the SDM Specifying the allowable Hosts and Workstations within a network DIPswitch Addressing Location of the DIPswitch on the FT and DDM DIPswitching the Panel Address (1-63) Software Addressing of the SDM Status Lights and Dealing with Communication Errors LED and 7 Segment LED Communication Communication Errors Communication Errors FT Page 8 of 101 Fault Tolerant Controller Manual B

9 7.2.2 Communication Errors - DDM Communication Errors - SDM Sense Inputs for the DDM and SDM User Selectable Options Appendix A - FT Specifications Fault Tolerant Controller Features FT System Capacities Electrical Ratings Fault Tolerant Controller Features Dual Door Module Electrical Ratings Fault Tolerant Controller Features Single Door Module Electrical Ratings Cable Requirements and Maximum Lengths Communication Readers Tool Requirements Controller Specifications Maintenance Requirements Back-Up Memory Battery Replacement Power Supply Back Battery Replacement Page 9 of 101 Fault Tolerant Controller Manual B

10 1.0 Introduction Welcome to the PCSC Fault Tolerant Controller, the newest generation of intelligent access control systems from PCSC. This manual explains the Fault Tolerant Controller installation and connection to a network and other Fault Tolerant Controllers. The Fault Tolerant Controller Manual is divided up into six steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Unpacking the Panels Installing Power Wiring the Readers Connecting the Readers to the Dual Door Module (DDM) and Single Door Module (SDM) Wiring the Door(s) Communicating with the Fault Tolerant Controller (FT) and DDM through TCP/IP Before powering the Fault Tolerant Controller, take a moment to read through this manual. It has been designed to allow you to move through the installation and programming phase with a minimum of difficult. Should you require additional guidance during the installation process, call PCSC Technical Support at (310) NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 10 of 101 Fault Tolerant Controller Manual B

11 1.1 Theory of Operation The PCSC Fault Tolerant system is designed differently from the standard access control system in which PCSC has excelled for 25 years. A standard Host -> Controller -> Reader/Door setup has always been reliant on each device preceding it to function properly in order to maintain the integrity of the system. For example, if a controller is to fail (lose power or be disconnected from the network), the readers or door controls connected to those panels will fail to activate. The system can be increasingly problematic if multiple panels are daisy-chained together via RS-485 or standard LAN network. If a panel within the chain goes off-line, it will disrupt the connection to the network. Although this occurrence is rare, it is a weakness within the standard access control architecture. The Fault Tolerant system was designed with a LAN-based Active/Active or Active/Inactive system architecture which compensates for the possibility that a controller may go off-line. If, for any reason, a primary controller fails, an alternate controller shall automatically take over the duties of the failed controller. The progression of successors to a faulty controller shall continue to provide security without any degradation in system operations. This secure method of operation was accomplished by dividing the duties of the standard panel into two distinct panel types. The intelligence of a standard controller that is able to function independently from the Host computer has been assigned to the Fault Tolerant Controller or FT within the Fault Tolerant system. The FT, connected to the network via a LAN connection, performs as the functional brain for all its subsidiary door modules. There are two types of FT within the Fault Tolerant system. The first is a standard independent panel. The second is a rack-mounted FT which incorporates two FTs within its design. The second type of panel within the Fault Tolerant system is the Door Module. The Fault Tolerant system has two types of door modules: the Single Door Module (SDM) and the Dual Door Module (DDM). The door module is a dumb device that communicates all door and reader activity to the FT and executes any instructions commanded. FTs and door modules are connected via the network, not a hard-wired cable, so that the architecture of the Fault Tolerant system can respond immediately to any panel failure. Page 11 of 101 Fault Tolerant Controller Manual B

12 1. Redundancy The key to the FT within a Fault Tolerant network is redundancy. No FT should function independently within a PCSC Fault Tolerant system. Multiple FTs within a network allow a secondary FT to fill-in if a door module s primary FT goes off-line. Therefore, a Fault Tolerant system will only ever fail at the level of a single door module, and not affect the system as a whole. This can be illustrated by the following scenario. Assume four panels (FTs 1 4) are connected via the network. Each panel is able to see the connected FTs on the network, and will display a constant scroll of the panels to which it is connected. Also connected to the network is DDM 26, which has been assigned to FT 1. Within the scroll of FT 1, DDM 26 will also appear. Other FT panels will not see DDM 26, as DDM 26 will only being attempt to connect to FT 1. If FT 1 goes off-line, the system needs to adapt. In a standard access control scenario, FT 1 would go off-line, as would DDM 26, and the readers/doors connected to it. Within the Fault Tolerant system, DDM 26 will immediately search out the secondary FT within its programming, in this case, FT 2. The FT 2 scroll will show that it is now connected to DDM 26. Additionally, FT 1 will no longer appear on the scroll on the other FTs. Page 12 of 101 Fault Tolerant Controller Manual B

13 2.0 Installing Power 2.1 Installing Power to the FT and DDM The Fault Tolerant Controller (FT) can be powered via two different methods: UL 294 Listed, power-limited, Power Over Ethernet (POE) injector (such as Altronix Model NetWay 8, 15.4 Watt minimum) UL Listed Sunny Electronics Corp. Switching Adapter (Model SYS T3) The Dual Door Module (DDM) can be powered via two different methods: UL 294 Listed, power-limited, Power Over Ethernet (POE) injector (such as Altronix Model NetWay 8, 30 Watt minimum) UL 294 Listed PCSC Power Supply (such as Model PS300/12 or PS600/12) Installing Power The FT can be powered by a Sunny Electronics Corp. switching adapter, and will be connected to a 12VDC connector located in the back of the unit. Wiring will be set at the factory. Disconnect power mains from the supply before making any adjustments to the wiring. FT Primary operating supply manufactured by Sunny Electronics Corp., Model SYS T3, rated at 12VDC, 2A (secondary). The DDM can be powered by a PCSC power supply, and will be connected to a 12VDC power supply at P2 at midlevel along the board. Wiring will be set at the factory. Disconnect power mains from the supply before making any adjustments to the wiring. DDM Primary operating supply manufactured by PCSC, Model PS300/12, rated at 12VDC, 3A (secondary) or Model PS600/12, rated at 12VDC, 6A (secondary). For installation, refer to the ESD SPS-3.6M2E Power Supply installation instructions (P/N: SPS36 Instructions Rev: 04/15/02). DDM Secondary operating supply via sealed lead-acid rechargeable battery, rated 12VDC, 8Ah (providing a minimum 4 hours battery standby power) NOTE: Power supply cable connections are non power-limited outputs. For more information, please refer to the power supply installation manual. Page 13 of 101 Fault Tolerant Controller Manual B

14 2.1.2 PCSC 3.0 Amp or 6.0 Amp Power Supply (DDM only) Page 14 of 101 Fault Tolerant Controller Manual B

15 2.2 Installing Power SDM The SDM can be powered via two different methods: Power Over Ethernet (POE) PCSC Power Supply Shown below are the 3.0A PCSC power supplies. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations Installing Power- 3.0 Amp Should the SDM be powered by an independent power supply, the panel will be connected to a 12VDC power supply at P2 at midlevel along the board. Wiring will be set at the factory. Disconnect power mains from the supply before making any adjustments to the wiring. For installation, refer to the ESD SPS-3.6M2E Power Supply installation instructions (P/N: SPS36 Instructions Rev: 04/15/02). NOTE: Power supply cable connections are non power-limited outputs. For more information, please refer to the power supply installation manual. Page 15 of 101 Fault Tolerant Controller Manual B

16 2.2.2 PCSC 3.0 Amp Power Supply NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 16 of 101 Fault Tolerant Controller Manual B

17 2.3 Resetting a Panels to Default Values This feature will be available in the future. Page 17 of 101 Fault Tolerant Controller Manual B

18 3.0 Wiring the Readers PCSC has designed its products to withstand most inductive voltage spikes without effect. However, some noise found in power supplies and door strikes, in addition to static discharge, may cause the control unit to momentarily shut down, lockup, or in extreme cases, to become damaged. Unexplained lockups and intermittent system behavior are common symptoms of static or noise problems. If cycling power will remedy your problem, carefully follow these instructions: 1. Install Metal Oxide Varistors (MOVs) (Siemens S10K30 or equivalent) at each Door Strike. When installed, they will suppress the feedback coming from door strikes, and limit most errors. 2. Readers should be properly earth-grounded for uninterrupted reads. Please be aware that operation is affected by the amount of static present during certain times of the year. 3. Properly grounding all readers and hardware, in addition to suppressing noise in the peripheral equipment, should allow for many problem free years of use with PCSC products. 4. In addition, PCSC recommends using a separate filtered, electronically regulated output, switchable power supply for door strikes. 5. Before installing the reader, please read the following instructions. Damage may occur if this is disregarded. 6. Installation must meet all local, state, and federal regulations and codes for electrical installation. If these codes conflict with the installation methods described in this manual, please call your service representative. Page 18 of 101 Fault Tolerant Controller Manual B

19 3.1 Grounding the Readers Do not route data and power cables in the same conduit. Crosstalk and transmission of electrical noise may result. The controller will become damaged if the power cable grounds to the data cable. NOTE: High Voltage and Low Voltage wiring must be routed separately and maintain a minimum spacing of 0.25 inches. 3.2 Properly Routing the Cables Each cable has a set of drain lines that can be attached on the Host or controller end of the cable to any screws mounted in the optional enclosures. If other non-metallic enclosures are used for controller housing, ensure that an alternative source for earth grounding is available. 3.3 Grounding the Power and Data Lines Each cable has a set of drain lines that can be attached on the Host or controller end of the cable to any screws mounted in the optional enclosures. If other non-metallic enclosures are used for controller housing, ensure that an alternative source for earth grounding is available Procedure 1. At the Reader side, it is important to be aware of both the static generated from the user end as well as electrical grounding from the data and power cabling. If at all possible, the reader mounting plate should be attached to a grounded junction box or to another source, if the junction box is nonmetallic. This alleviates the possible damage caused by static electricity. NOTE Leave the drain line taped back and floating at the reader site. 2. If grounding locally is not possible, connect drain wires to the provided Electro Static Discharge (ESD) hardware at the Controller side (enclosure) or to earth grounded conduit. As each reader port is progressively farther away from the ESD hardware location, allow for enough drain line to reach the ESD hardware on the controller end of the cable. Allow enough strain relief to avoid touching other circuitry or creating excessive tension. NOTE: High Voltage and Low Voltage wiring must be routed separately and maintain a minimum spacing of 0.25 inches. 3. On a permanently connected product, a terminal intended solely for the connection of an equipment grounding conductor shall be capable of securing a conductor of the size suitable for the particular application in accordance with the National Electrical Code, ANSI/NFPA On a permanently connected product, a wire binding screw intended for the connection of an equipment grounding conductor shall have a green colored head that is hexagonal, slotted, or both. A pressure wire connector intended for connection of such a conductor shall be plainly identified such as by being marked G GR, GROUND, or GROUNDING, or the like, or by a marking on a wiring diagram provided on the product. The wire binding screw or pressure wire connector shall be secured to the frame or enclosure of the product and shall be located so that it is unlikely to be removed during service operations such as replacing fuses, resetting manual-reset devices, or the like. Page 19 of 101 Fault Tolerant Controller Manual B

20 5. If a pressure wire connector intended for grounding is located where it could be mistaken for a neutral conductor of a ground supply, it shall be identified by a marking EQUIPMENT GROUND or with a green color identification, or both. 6. On a permanently connected product, the surface of an insulated lead intended solely for the connection of an equipment grounding conductor shall be finished in a continuous green color or a continuous green color with one or more yellow stripes, and no other lead shall be so identified. 3.4 Grounding the Pin Pad or Reader Procedure 1. Orient the mounting plate so that the protruding ears are on top and facing the back of the reader or PIN Pad. Attach the mounting plate to the junction box using two screws. The mounting plate should be earth ground either to a ground junction box or directly to an earth ground source (especially if the junction box is not metal). 2. Connect the cable to the rear of the reader. Secure the shield drain lines to one of the grounding screws in the Fault Tolerant Controller enclosure or other appropriate location. 3. Place mounting holes on the back of the reader over the latches on the mounting plate, and then position the unit so that the cover is flush with the mounting plate. 4. Secure the unit to the mounting plate by inserting the special security fastener through the hole in the bottom of the reader. Tighten it using the security driver Grounding the Reader Mullion Mount The reader may be attached to a glass or door mullion separator (either vertically or horizontally) by using the Mullion Bracket Adapter Kits ( for horizontal mounting or for vertical mounting) Procedure 1. At the Fault Tolerant Controller end, secure the drain lines to one of the ESD grounding screws in the Fault Tolerant Controller box. At the reader end, leave the drain line floating. It is recommended that the mullion adapter be affixed to an earth ground or to the incoming conduit. 2. Mount the reader to the J-box or mullion bracket. Page 20 of 101 Fault Tolerant Controller Manual B

21 4.0 Reader Connections to the DDM Reader Disconnect Resistors If an external power supply and a reader disconnect feature is required, place an appropriately sized resistor (not supplied) at the reader. However, if the reader is using an external power supply, then the resistor should be installed at the reader port on the panel. NOTE: Reviewer points this out as contradictory. Externally powered readers usually will not have the reader connect/disconnect due to the fact that feature is in the panels. If an external power supply is required, a resistor can be placed at the reader port to eliminate the Reader Disconnect message in the logger. NOTE: For use in the following diagrams, resistors are shown connected to the boards. However, for best operation, resistors should be placed where they are the most effective. NOTE: A second reader is not available with the SDM* at this time. However, Model SDM is not UL Listed or intended to be used in UL 294 Installations Compatible UL Listed Readers: These are the only readers/keypads to be used in UL Installations, and all others must be removed or explicitly stated as such. Manufacturer Applied Wireless Identification Group (AWID) XceedID Corp. HID Corp. Model SR-2400 XF AxN Page 21 of 101 Fault Tolerant Controller Manual B

22 4.1 Reader Connections: PR233 MiniProx / PR-733/732 NOTE: The AWID readers (PR733 and PRK732) have a brown LED wire. Page 22 of 101 Fault Tolerant Controller Manual B

23 4.2 Reader Connections: PR-234 / PRK-234 ProxPro / PR736 / PRK-736 NOTE: The AWID readers (PR736 and PRK736) have a brown LED wire. Page 23 of 101 Fault Tolerant Controller Manual B

24 4.3 Reader Connections: PR-235 MaxiProx / PR-735 NOTE: The AWID readers (PR735) have a brown LED wire. Page 24 of 101 Fault Tolerant Controller Manual B

25 4.4 Reader Connections: Sensor Wiegand Page 25 of 101 Fault Tolerant Controller Manual B

26 4.5 Reader Connections: VeriProx / V-Pass/ Page 26 of 101 Fault Tolerant Controller Manual B

27 4.6 Reader Connections: iclass Page 27 of 101 Fault Tolerant Controller Manual B

28 4.7 Reader Connections: Xceed ID SP632/SP632M/SP633/SP635/SPK635 Page 28 of 101 Fault Tolerant Controller Manual B

29 4.8 Reader Connections: Biometric Page 29 of 101 Fault Tolerant Controller Manual B

30 5.0 Wiring the Door(s) Step 1. Step 2. When power is interrupted from the Fault Tolerant Controller, the door relay de-energizes and continuity (conduction path) exists between the Common (Com.) and Normally Closed (N.C.) relay contacts. Should this loss-of-power situation arise, it must be determined whether the door(s) controlled by the Fault Tolerant Controller will become unlocked (or a Fail-Safe environment), or locked (or a Fail-Secure environment). Refer to the two types of door hardware below and the circuit conditions that coincide with the state of the locks. Case A. Door Strike hardware requires continuity to unlock (for strikes that require power to lock, follow the outline given for maglocks). This is provided by a closed circuit condition (Normally Closed [N.C.]). Case B. Door Strike hardware does NOT require continuity to lock (for strikes that require power to lock, follow the outline given for maglocks). This is provided by an open circuit condition (Normally Open [N.O.]). Case C. Magnetic lock hardware requires continuity to lock. This is provided by a closed circuit condition (Normally Closed [N.C.]). Case D. Magnetic lock hardware does NOT require continuity to unlock. This is provided by an open circuit condition (Normally Open [N.O.]). Step 3. For Fail-Safe operation, wire the appropriate door lock hardware to accommodate an unlocked condition upon interruption of Fault Tolerant Controller power. This is implemented by: For door strikes, wire between the Common and Normally Closed Door Relay contacts. For Magnetic Locks, wire between the Common and Normally Open Door Relay contacts. For Fail-Secure operation, wire the appropriate door lock hardware to accommodate a locked condition upon interruption of Fault Tolerant Controller power. This is implemented by: For door strikes, wire between the Common and Normally Open Door Relay contacts. For Magnetic Locks, wire between the Common and Normally Closed Door Relay contacts. NOTE: When using a Fail-Secure operation, UL Listed panic hardware shall be used to allow emergency exit from the protected area. Step 4. Next page NOTE For both conditions (Fail Safe and Fail Secure) it is presumed that Lock Power is battery backed. Page 30 of 101 Fault Tolerant Controller Manual B

31 Step 4. Program the quiescent (INACTIVE) state of the door output relay to provide a locked door state. For Fail-Safe environments, the quiescent state of the door output relay should be ENERGIZED. For Fail-Secure environments, it should be DE-ENERGIZED. NOTE: When using a Fail-Secure operation, UL Listed panic hardware shall be used to allow emergency exit from the protected area. Consult the LiNC-NXG User Manual s Door Overview/Hardware section for programming information. Open Collector Output: Open collector outputs are designed to drive an external relay. This technique can be used to control devices which exceed the relay capacity of those on board the Fault Tolerant Controller. The open collector outputs are capable of 100 ma 12VDC. Page 31 of 101 Fault Tolerant Controller Manual B

32 5.1 Wiring the Panel in a Fail-Safe Environment Fail Safe - DDM Page 32 of 101 Fault Tolerant Controller Manual B

33 5.1.1 Fail Safe - SDM NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 33 of 101 Fault Tolerant Controller Manual B

34 5.2 Wiring Panel in a Fail-Secure Environment Fail-Secure - DDM NOTE: When using a Fail-Secure operation, UL Listed panic hardware shall be used to allow emergency exit from the protected area. Page 34 of 101 Fault Tolerant Controller Manual B

35 Page 35 of 101 Fault Tolerant Controller Manual B

36 5.2.2 Fail-Secure - SDM NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. NOTE: When using a Fail-Secure operation, UL Listed panic hardware shall be used to allow emergency exit from the protected area. Page 36 of 101 Fault Tolerant Controller Manual B

37 5.3 LED Arrays Using the Seven Segment LED Array The proper settings for this feature will be available in the future Status Chart for All LED Arrays The proper settings for this feature will be available in the future. 5.4 Installing Noise Suppression Device To install a MOV to suppress noise and avoid problems related to spikes, follow the instructions below and refer to the diagrams on the following pages Procedure The most effective location for a suppression device is at the source; in this case, at the door strike. 1. Remove the strike-locking device and find the wire connector that attaches the lock wires to the lock. 2. Install an MOV (Siemens S10K30 or equivalent) in parallel with the load. The MOV is a nonpolarized device and will work with both AC and DC locks. NOTE Use an additional MOV if you experience further noise at the strike. NOTE For further protection on DC units, a reverse biased diode may be installed (We suggest types 1N4004 to 1N4007 be used) also in parallel with the load. 3. Note the wiring set-up of your particular system. Connections can be made either to the normally open (fail secure) contact or to the normally-closed (fail-safe) configuration whereby an isolation relay is used and a MOV is added for noise suppression. Page 37 of 101 Fault Tolerant Controller Manual B

38 5.5 Reset button In situations where a panel is malfunctioning or a panel has been re-programmed, (see Section 6.0) it may be necessary to reset a panel to return it to its programmed state Reset button on the FT and DDM Page 38 of 101 Fault Tolerant Controller Manual B

39 5.5.2 Reset Button on the SDM NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 39 of 101 Fault Tolerant Controller Manual B

40 6.0 Communicating with the FT, DDM and SDM through TCP/IP Communication with each Fault Tolerant Controller is based on three forms of identification: The panels name (optional) The panel s unique IP Address The panel s DIPswitch number NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations Connecting to a Panel via TCP/IP Programming of the FT, DDM and SDM controllers is done directly through the TCP/IP and a standard internet browser. When communicating with a panel via TCP/IP, it is possible to do the following: Set IP Address and Name Configure a network of connected FTs Specify a primary FT (DDM and SDM only) Specify secondary FTs (DDM and SDM only) Specifying the allowable Hosts and Workstations within a network Set the panel s Time Zone Set the DIPswitch number (SDM Only) Changing the password Page 40 of 101 Fault Tolerant Controller Manual B

41 6.1 Programming the FT Connecting to a FT All FTs are factory set with an IP Address of as the default IP. NOTE: Default NTP server IP Address is Connect a computer to a network switch via a CAT5 cable. 2. Connect the panel to a switch via a CAT5 cable. 3. Open an internet browser, such as Internet Explorer. 4. Type into the address bar. 5. A security window will appear. The defaults are: User Name: admin Password: PYMTF 6. Press the OK button. Page 41 of 101 Fault Tolerant Controller Manual B

42 7. The PCSC FT Controller screen will appear. All necessary programming options will be available from this screen. NOTE: Not all features listed are for standard usage. Only those that are discussed in this section are for standard use. Page 42 of 101 Fault Tolerant Controller Manual B

43 6.1.2 Setting the Name and IP Address of a FT 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC FT Controller screen will appear. 4. From the PCSC FT Controller screen, select Configure Primary Networks. The following screen will appear. 5. In the Host Name text box, insert the proper name for the panel. 6. In the IP address text box, insert the proper IP address. 7. In the Gateway IP, Subnet address, NTP server IP, TFTP server IP, insert the proper IP Addresses. 8. Press the Apply button to set up. Page 43 of 101 Fault Tolerant Controller Manual B

44 9. The secondary Ethernet configuration defaults to a blank screen by PCSC (manufacturer) Page 44 of 101 Fault Tolerant Controller Manual B

45 10. In the IP address text box, insert the proper IP address. 11. In the Broadcast IP and Subnet address, insert the proper IP Addresses. 12. Press the Apply button to save. (This save will not be effective until you re-boot the panel.) 13. A Saving configuration page will appear. Press the home link to return to the main PCSC FT Controller page. Page 45 of 101 Fault Tolerant Controller Manual B

46 NOTE: All panels within a network must have separate IP addresses. It is recommended that panels within the same clique have IP addresses that are in some way aligned. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. Page 46 of 101 Fault Tolerant Controller Manual B

47 6.1.3 Configure a Network of Connected FTs 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC FT Controller screen will appear. 4. From the PCSC FT Controller screen, select Edit Configuration Files. The following screen will appear. 5. Select Hydra configuration from the drop-down menu. 6. Press the Edit button. Page 47 of 101 Fault Tolerant Controller Manual B

48 Within the Hydra configuration screen, it is possible to edit which FTs the current panel will be able to see on the network. Only FTs can see other FTs. It is not necessary for an FT to see DDM or an SDM. 7. Change or add the IP address of the peer FTs on the network. All FTs that can see each other will form a clique. Page 48 of 101 Fault Tolerant Controller Manual B

49 Programmed for dual Ethernet 8. Once all FTs have been entered, press the Save File button. Page 49 of 101 Fault Tolerant Controller Manual B

50 Before panel programming/reboot NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. Page 50 of 101 Fault Tolerant Controller Manual B

51 After programming/reboot NOTE: A panel s own IP address must be listed within the Hydra configuration screen. Page 51 of 101 Fault Tolerant Controller Manual B

52 6.1.4 Setting the Time Zone for a Particular Panel 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC FT Controller screen will appear. 4. From the PCSC FT Controller screen, select Edit Configuration Files. The following screen will appear. 5. Select Time zone from the drop-down menu. 6. Press the Edit button. Page 52 of 101 Fault Tolerant Controller Manual B

53 The established time zone for the panel will be listed. 7. Change the time zone of the panel, if necessary. 8. Once the range has been entered, press the Save File button. NOTE: A network can have multiple cliques with independent ranges that allow for additional growth without impacting on its neighbors. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures North American Time Zones NST3NDT Newfoundland Standard Time/ Newfoundland Daylight Time AST4ADT Atlantic Standard Time/ Atlantic Daylight Time EST5EDT Eastern Standard Time/ Eastern Daylight Time CST6CDT Central Standard Time/ Central Daylight Time MST7MDT Mountain Standard Time/ Mountain Daylight Time PST8PDT Pacific Standard Time/ Pacific Daylight Time AKST9AKDT Alaska Standard Time/ Alaska Daylight Time HAST10HADT Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time Page 53 of 101 Fault Tolerant Controller Manual B

54 6.1.5 Changing the Password 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC FT Controller screen will appear. 4. From the PCSC FT Controller screen, select Change password. Page 54 of 101 Fault Tolerant Controller Manual B

55 The following screen will appear. 5. Enter the new username. 6. Enter the old password. 7. Enter the new password. 8. Confirm the new password. 9. Press the Apply button. The system will store the updated username and password until NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. Page 55 of 101 Fault Tolerant Controller Manual B

56 6.1.6 Specifying the IP Address to Allow FT configuration access 10. Confirm that the computer and the appropriate panel are connected through a functioning switch. 11. Open an internet browser, such as Internet Explorer. 12. Type into the address bar. The PCSC FT Controller screen will appear. 13. From the PCSC FT Controller screen, select Edit Configuration Files. The following screen will appear. 14. Select /etc/hosts.allow from the drop-down menu. 15. Press the Edit button. Page 56 of 101 Fault Tolerant Controller Manual B

57 The Hosts Allow screen allow access of the IE computer to edit the FT configuration.. The default is for ALL : ALL, which would allow any networked computer to edit configuration. NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation. 16. To limit the number of computers that can change the FT configuration add the IP address of each PC. Page 57 of 101 Fault Tolerant Controller Manual B

58 17. Once the IP Address(es) has been entered, press the Save File button. NOTE: All changes to the panel are temporary until the panel is RESET. Push Reset Button as seen in Section 5.4. Page 58 of 101 Fault Tolerant Controller Manual B

59 6.2 Programming the Dual Door Module Connecting to the DDM All Dual Door Modules are factory set with an IP Address of as the default IP. 1. Connect a computer to a network switch via a CAT5 cable. 2. Connect the panel to a switch via a CAT5 cable. 3. Open an internet browser, such as Internet Explorer. 4. Type into the address bar. 5. A security window will appear. The defaults are: User Name: admin Password: PYMTF 6. Press the OK button. Page 59 of 101 Fault Tolerant Controller Manual B

60 7. The PCSC DualDoorModule screen will appear. All necessary programming options will be available from this screen. NOTE: Not all features listed are for standard usage. Only those that are discussed in this section are for standard use. Page 60 of 101 Fault Tolerant Controller Manual B

61 6.2.2 Setting the Name and IP Address of a DDM 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC DualDoorModule screen will appear. 4. From the PCSC DualDoorModule screen, select Configure Primary Networks. The following screen will appear. 5. In the Host Name text box, insert the proper name for the panel. 6. In the IP address text box, insert the proper IP address. 7. In the Gateway IP, Subnet address, NTP server IP, TFTP server IP, insert the proper IP Addresses. Page 61 of 101 Fault Tolerant Controller Manual B

62 8. For the Secondary Ethernet configuration, in the IP address text box, insert the proper IP address. 9. In the Broadcast IP, and Subnet address, insert the proper IP Addresses. 10. Press the Apply button to set up. Page 62 of 101 Fault Tolerant Controller Manual B

63 11. A Saving configuration page will appear. Press the home link to return to the main PCSC DualDoorModule page. NOTE: All panels within a network must have separate IP addresses. It is recommended that panels within the same clique have IP addresses that are in some way aligned. NOTE: All changes to the panel are temporary until the panel is RESET. Push the Reset button as seen on Section 5.4. Page 63 of 101 Fault Tolerant Controller Manual B

64 6.2.3 Configure the DDM s Primary FT and Secondary FTs 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC DualDoorModule screen will appear. 4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select Hydra configuration from the drop-down menu. 6. Press the Edit button. Page 64 of 101 Fault Tolerant Controller Manual B

65 The following screen will appear. Each DDM must have a Primary server (FT). Additionally, a DDM should have one (or more) Secondary server(s) in order of listed hierarchy. A DDM will only look for the expected FTs and will never look for the other DDMs and SDMs on the network. Prior to being programmed Page 65 of 101 Fault Tolerant Controller Manual B

66 Programmed 7. Change the IP Address for the Primary server. 8. Change or add the IP Address(es) for the Secondary server. 9. Once all IP Addresses of the appropriate FTs have been entered, press the Save File button. Page 66 of 101 Fault Tolerant Controller Manual B

67 Applied Page 67 of 101 Fault Tolerant Controller Manual B

68 Prior to reboot NOTE: All changes to the panel are temporary until the panel is RESET. Push the reset button as seen in Section 5.4. Page 68 of 101 Fault Tolerant Controller Manual B

69 After reboot Page 69 of 101 Fault Tolerant Controller Manual B

70 6.2.4 Setting the Time Zone for a Particular Panel 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC DualDoorModule screen will appear. 4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select Time zone from the drop-down menu. 6. Press the Edit button. Page 70 of 101 Fault Tolerant Controller Manual B

71 The established time zone for the panel will be listed. 7. Change the time zone of the panel, if necessary. 8. Once the range has been entered, press the Save File button. NOTE: A network can have multiple cliques with independent ranges that allow for additional growth without impacting on its neighbors. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures North American Time Zones NST3NDT Newfoundland Standard Time/ Newfoundland Daylight Time AST4ADT Atlantic Standard Time/ Atlantic Daylight Time EST5EDT Eastern Standard Time/ Eastern Daylight Time CST6CDT Central Standard Time/ Central Daylight Time MST7MDT Mountain Standard Time/ Mountain Daylight Time PST8PDT Pacific Standard Time/ Pacific Daylight Time AKST9AKDT Alaska Standard Time/ Alaska Daylight Time HAST10HADT Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time Page 71 of 101 Fault Tolerant Controller Manual B

72 6.2.5 Changing the Password 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC DualDoorModule screen will appear. 4. From the PCSC DualDoorModule screen, select Change password. Page 72 of 101 Fault Tolerant Controller Manual B

73 The following screen will appear. 5. Enter the new username. 6. Enter the old password. 7. Enter the new password. 8. Confirm the new password. 9. Press the Apply button. The system will store the updated username and password until NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. Page 73 of 101 Fault Tolerant Controller Manual B

74 6.2.6 Specifying the allowable Hosts and Workstations within a network 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC DualDoorModule screen will appear. 4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select /etc/hosts.allow from the drop-down menu. 6. Press the Edit button. Page 74 of 101 Fault Tolerant Controller Manual B

75 The Hosts Allow screen will give the range of all CPUs allowed to access the LiNC-NXG panels as hosts or workstations. The default is for ALL : ALL, which would allow any networked computer to function as a host or workstation. NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation. 7. To limit the number of computers that can function as hosts or workstations, change or add the IP address of each CPU. 8. Once the IP Address(es) has been entered, press the Save File button. NOTE: A network can have multiple cliques with independent ranges that allow for additional growth without impacting its neighbors. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. Page 75 of 101 Fault Tolerant Controller Manual B

76 6.3 Programming the Single Door Module Connecting to the SDM All Dual Door Modules are factory set with an IP Address of as the default IP. 1. Connect a computer to a network switch via a CAT5 cable. 2. Connect the panel to a switch via a CAT5 cable. 3. Open an internet browser, such as Internet Explorer. 4. Type into the address bar. 5. A security window will appear. The defaults are: User Name: admin Password: PYMTF 6. Press the OK button. Page 76 of 101 Fault Tolerant Controller Manual B

77 7. The PCSC SingleDoorModule screen will appear. All necessary programming options will be available from this screen. NOTE: Not all features listed are for standard usage. Only those that are discussed in this section are for standard use. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 77 of 101 Fault Tolerant Controller Manual B

78 6.3.2 Setting the Name and IP Address of a SDM 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Configure Primary Networks. The following screen will appear. 5. In the Host Name text box, insert the proper name for the panel. 6. In the IP address text box, insert the proper IP address. 7. Press the Apply button to set up. NOTE: All panels within a network must have separate IP addresses. It is recommended that panels within the same clique have IP addresses that are in some way aligned. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. NOTE: It is not recommended to change the NTP and TFTP server IP address without specific knowledge. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 78 of 101 Fault Tolerant Controller Manual B

79 6.3.3 Configure the SDM s Primary FT and Secondary FTs 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select Hydra configuration from the drop-down menu. 6. Press the Edit button. Page 79 of 101 Fault Tolerant Controller Manual B

80 The Hydra Configuration screen will appear. Each SDM must have a Primary server (FT). Additionally, a SDM should have one (or more) Secondary server(s) in order of listed hierarchy. An SDM will only look for the expected FTs and will never look for the other DDMs and SDMs on the network. 7. Change the IP address for the Primary server. 8. Change or add the IP Address(es) for the Secondary server. 9. Once all IP addresses of the appropriate FTs have been entered, press the Save File button. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 80 of 101 Fault Tolerant Controller Manual B

81 6.3.4 Changing the Password on the SDM 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Change password. Page 81 of 101 Fault Tolerant Controller Manual B

82 The following screen will appear. 5. Enter the new username. 6. Enter the old password. 7. Enter the new password. 8. Confirm the new password. 9. Press the Apply button. The system will store the updated username and password until NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 82 of 101 Fault Tolerant Controller Manual B

83 6.3.5 Setting the Time Zone for a Particular Panel on the SDM 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select Time zone from the drop-down menu. 6. Press the Edit button. The established time zone for the panel will be listed. 7. Change the time zone of the panel, if necessary. 8. Once the range has been entered, press the Save File button. NOTE: A network can have multiple cliques with independent ranges that allow for additional growth without impacting on its neighbors. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 83 of 101 Fault Tolerant Controller Manual B

84 North American Time Zones NST3NDT Newfoundland Standard Time/ Newfoundland Daylight Time AST4ADT Atlantic Standard Time/ Atlantic Daylight Time EST5EDT Eastern Standard Time/ Eastern Daylight Time CST6CDT Central Standard Time/ Central Daylight Time MST7MDT Mountain Standard Time/ Mountain Daylight Time PST8PDT Pacific Standard Time/ Pacific Daylight Time AKST9AKDT Alaska Standard Time/ Alaska Daylight Time HAST10HADT Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time Page 84 of 101 Fault Tolerant Controller Manual B

85 6.3.6 Setting the Panel Number for the SDM Because there is no DIPswitch within the SDM, a Panel number (separate from the IP Address) needs to be assigned to the SDM for use with LiNC-NXG. 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Change Unit number. The following screen will appear. 5. A Unit configuration screen for the panel will appear. Select the proper Unit (or Panel) number for use with NXG. 6. Press the Apply button. Page 85 of 101 Fault Tolerant Controller Manual B

86 7. A confirmation screen will appear. If it is correct, press the Save File button. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4 for proper resetting procedures. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 86 of 101 Fault Tolerant Controller Manual B

87 6.3.7 Specifying the allowable Hosts and Workstations within a network 1. Confirm that the computer and the appropriate panel are connected through a functioning switch. 2. Open an internet browser, such as Internet Explorer. 3. Type into the address bar. The PCSC SingleDoorModule screen will appear. 4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following screen will appear. 5. Select /etc/hosts.allow from the drop-down menu. 6. Press the Edit button. Page 87 of 101 Fault Tolerant Controller Manual B

88 The Hosts Allow screen will give the range of all CPUs allowed to access the LiNC-NXG panels as hosts or workstations. The default is for ALL : ALL, which would allow any networked computer to function as a host or workstation. NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation. 1. To limit the number of computers that can function as hosts or workstations, change or add the IP address of each CPU. 2. Once the IP Address(es) has been entered, press the Save File button. NOTE: A network can have multiple cliques with independent ranges that allow for additional growth without impacting its neighbors. NOTE: All changes to the panel are temporary until the panel is RESET. See Section 6.4 for proper resetting procedures. NOTE: Model SDM is not UL Listed or intended to be used in UL 294 Installations. Page 88 of 101 Fault Tolerant Controller Manual B

89 6.4 DIPswitch Addressing Panels will also need to have a unique DIPswitch address to function properly with the LiNC-NXG network. It should be noted that the SDM does not have a DIPswitch. It is necessary to program the DIPswitch via the TCP/IP programming as noted in Section Location of the DIPswitch on the FT and DDM Page 89 of 101 Fault Tolerant Controller Manual B

90 6.4.2 DIPswitching the Panel Address (1-63) The dipswitch is located at SW1, on the left of the board. There are eight switches. For the binary number one (1), flip the switch to the left. For zero (0), flip the switch to the right. The address in 10+ will be in Hexadecimal format. Page 90 of 101 Fault Tolerant Controller Manual B

IQX and NRX Series Intelligent Access Control Systems IQX and NRX Series Installation Manual REV: D

IQX and NRX Series Intelligent Access Control Systems IQX and NRX Series Installation Manual REV: D IQX and NRX Series Intelligent Access Control Systems IQX and NRX Series Installation Manual 33-10039-001 REV: D PCSC 3541 Challenger Street Torrance, CA 90503 Phone: (310) 638-0400 FAX: (310) 638-6204

More information

IQ-400 ELV - Elevator Control Module

IQ-400 ELV - Elevator Control Module IQ-400 ELV - Elevator Control Module Installation Manual 33-10066-001 REV: A PCSC 3541 Challenger Street Torrance, CA 90503 Phone: (310) 303-3600 FAX: (310) 303-3600 Page 1 of 87 First Edition: March 2006

More information

TruPortal Dual Door Interface Module Quick Reference

TruPortal Dual Door Interface Module Quick Reference TruPortal Dual Door Interface Module Quick Reference en-us Packing List Introduction The TruPortal Dual Door Interface Module (TP-ADD-2D) can support two complete door configurations, with up to two readers

More information

Supervised Input Module Installation Manual

Supervised Input Module Installation Manual Intelligent Access Control Systems Supervised Input Module Installation Manual 33-10037-001 REV: B PCSC 3541 Challenger Street Torrance, CA 90503 Phone: (310) 638-0400 FAX: (310) 638-6204 www.1pcsc.com

More information

-Series Intelligent Access Control Systems

-Series Intelligent Access Control Systems -Series Intelligent Access Control Systems IQ Series Installation Manual 33-10036-001 REV: G PCSC 3541 Challenger Street Torrance, CA 90503 Phone: (310) 638-0400 FAX: (310) 638-6204 www.1pcsc.com i First

More information

6222 Two Door Module Technical Operations Manual

6222 Two Door Module Technical Operations Manual 6222 Two Door Module Technical Operations Manual TABLE OF CONTENTS Specifications...3 Overview...4 Operations...5 Custom Access Mode...5 Standard Access Mode...5 Offline Access Mode...5 Offline Memory...5

More information

Innovative Electronics for a changing world MANUAL POE 4+4 GM

Innovative Electronics for a changing world MANUAL POE 4+4 GM Innovative Electronics for a changing world MANUAL POE 4+4 GM Index: Description Technical and connections Screen shots Physical Description: The POE 4 +4 GM is an 4+4 = 8 Channel Gigabit DC passive power

More information

Expandable Power Systems

Expandable Power Systems Expandable Power Systems Installation Guide Models Include: Maximal11EV 12VDC @ 4A or 24VDC @ 3A. 12VDC @ 4A or 24VDC @ 3A. Maximal33EV 12VDC or 24VDC @ 6A. 12VDC or 24VDC @ 6A. Maximal37EV 24VDC @ 10A.

More information

How to Install a PowerNet IPBridge

How to Install a PowerNet IPBridge How to Install a PowerNet IPBridge Copyright 2013, ISONAS Security Systems All rights reserved Table of Contents 1: INTRODUCTION... 4 1.1: BEFORE YOU BEGIN... 4 1.2: GENERAL REQUIREMENTS:... 5 1.3: POWERNET

More information

Quick Start Guide. SEB-710 I/O Expansion board. Introduction

Quick Start Guide. SEB-710 I/O Expansion board. Introduction SEB-710 I/O Expansion board Revision 1.0 - (March, 2011) Saflec Systems (Pty) Ltd Quick Start Guide Introduction The SEB-710 is an I/O expansion device for additional inputs and outputs. It has eight relay

More information

INSTALLATION INSTRUCTIONS Model 930 EntryCheck

INSTALLATION INSTRUCTIONS Model 930 EntryCheck SECURITY DOOR CONTROLS 3580 Willow Lane, Westlake Village, CA 91361-4921 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS Model 930 EntryCheck

More information

Access Control System Document Number: , Rev. D. Installation Guide. Essential Essential Plus Elite 36 Elite 64

Access Control System Document Number: , Rev. D. Installation Guide. Essential Essential Plus Elite 36 Elite 64 Essential Essential Plus Elite 36 Elite 64 Access Control System Document Number: 620-100239, Rev. D Installation Guide USA & Canada (800) 421-1587 & (800) 392-0123 (760) 438-7000 - Toll Free FAX (800)

More information

NetGen Hardware Installation Guide. for NetGen Ethernet Door Controllers

NetGen Hardware Installation Guide. for NetGen Ethernet Door Controllers NetGen Hardware Installation Guide for NetGen Ethernet Door Controllers 0613 Table of Contents BLUEWAVE SYSTEM OVERVIEW...2 THE WI-FI LOCK AND SECURITY COMPANY...2 NETGEN DOOR CONTROLLERS...2 INSTALLATION

More information

CRC220 and CRC221 INSTALLATION GUIDE. REF No.: DOC0014 ISSUE: 09

CRC220 and CRC221 INSTALLATION GUIDE. REF No.: DOC0014 ISSUE: 09 CRC220 and CRC221 INSTALLATION GUIDE REF No.: DOC0014 ISSUE: 09 30th July 2015 2 Contents CRC220 & CRC221 INSTALLATION GUIDE 1. Scope 1-1 2. Introduction 2-1 2.1 Features 2-1 2.1.1. PCB Features 2-1 2.1.2.

More information

UC-2000 Installation Manual Unicorn Computers Technology Limited

UC-2000 Installation Manual Unicorn Computers Technology Limited UC2000 Installation Manual Copyright 2003. All rights reserved. Table of Contents Specifications 2 Enclosure for the UC2000 Controller 3 Unicorn Access Control System Configuration 4 UC2000 Controller

More information

MR51e Reader Interface

MR51e Reader Interface J4 J TB6 TB5 TB4 TB3 VIN VO TB2 TB J7 2.75 [69.85] 0.2 [5.08] 2.35 [59.69] J3 MR5e Reader Interface Installation and Specifications. General: www.mercury-security.com 2355 MIRA MAR AVE. LONG BEACH, CA

More information

Quick Start Installation Guide

Quick Start Installation Guide apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building

More information

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications 12 Universal Expander Module. Installation Notes. Revision 1.2 August. 2003. 1 Reporting Reporting with most Contact ID maps will treat the Mini Expander, Exp32 and Exp16 as the same. (With the exception

More information

Innovative Electronics for a changing world MANUAL. POE 4 GM PCB only

Innovative Electronics for a changing world MANUAL. POE 4 GM PCB only Innovative Electronics for a changing world MANUAL POE 4 GM PCB only Index: Description Technical and connections Screen shots Physical Description: The POE 4 GM is an 4 Channel Gigabit DC passive power

More information

C5S120 Installation and Connection Guide

C5S120 Installation and Connection Guide C5S120 Installation and Connection Guide Version: V1.1 1. Cautions Please note the following cautions. Mis-operation may lead to personal injury or equipment failure: 1) Do not energize the system before

More information

SECURA KEY CARD ACCESS CONFIGURATION GUIDE Multi-Reader Systems with NOVA.16 (SK-MRCP) 16-Door Panel

SECURA KEY CARD ACCESS CONFIGURATION GUIDE Multi-Reader Systems with NOVA.16 (SK-MRCP) 16-Door Panel SECURA KEY CARD ACCESS CONFIGURATION GUIDE Multi-Reader Systems with (SK-MRCP) -Door Panel WITH RS- GATEWAY CONNECTED DIRECTLY TO A PC RS- GATEWAY POWER: EIGHT (8) SMART READERS EVENLY SPACED UP TO 000

More information

Installation Manual for D244X Series 24-volt Power Supplies

Installation Manual for D244X Series 24-volt Power Supplies Installation Manual for D244X Series 24-volt Power Supplies D2441-B D2441-C D2443-B D2443-C D2445-B D2445-C D2400 Series 1A 24 volts 1A 24 volts 3A 24 volts 3A 24 volts 5A 24 volts 5A 24 volts Dycon Power

More information

SNAP, CLICK, DONE. Getting Started Guide

SNAP, CLICK, DONE. Getting Started Guide SNAP, CLICK, DONE. Getting Started Guide Introducing Sateon Advance Sateon Advance offers a flexible new approach to access control, with a new range of hardware and software products. The hardware is

More information

January 2013 PRICE SCHEDULE A 2.0. Access Plus Telephone Entry & Access Control

January 2013 PRICE SCHEDULE A 2.0. Access Plus Telephone Entry & Access Control January 2013 PRICE SCHEDULE A 2.0 Section A4 Date Page Comment 1 1 13 All January, 2013 Price Schedule update. 2 13 13 6 Removed 1812 092 from 1812 145 kit. Added 1812 092 to 1812 147 kit. 2 13 13 9 P/N

More information

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT Installation Instructions i-net Access Control Units Part Code: IA-PCB IA-ACB IA-ACU IA-KIT This device is configured for DHCP. Identity Access software will find this device, go to setup and controller,

More information

Wiring Guide. EP.NMiNi 2. Version 1.04 Last Updated:

Wiring Guide. EP.NMiNi 2. Version 1.04 Last Updated: Wiring Guide EP.NMiNi 2 Version 1.04 Last Updated: 31-01-2013 Before you begin Technical Support If you cannot find the answer to your question in this manual or in the Help files, we recommend you contact

More information

Installation Instructions

Installation Instructions Alliance Arming Station AL-1111, AL-1116 1048520C September 2006 Copyright 2006, GE Security Inc. Introduction This is the GE Alliance Arming Station for models AL-1111 (four-line LCD) and AL-1116 (four-line

More information

VertX. V100, V200 and V300. Installation Guide Barranca Parkway Irvine, CA USA. November Rev A.1

VertX. V100, V200 and V300. Installation Guide Barranca Parkway Irvine, CA USA. November Rev A.1 15370 Barranca Parkway Irvine, CA 92618 USA VertX V100, V200 and V300 Installation Guide November 2011 6080-930 Rev A.1. Contents Introduction... 3 Parts List... 3 Product Specifications... 3 Cable Specifications...

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

AC-115 Compact Networked Single-Door Controller Hardware Installation and Programming

AC-115 Compact Networked Single-Door Controller Hardware Installation and Programming AC-115 Compact Networked Single- Controller Hardware Installation and Programming Copyright 2013 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to REL,

More information

Digital Keypad Introduction

Digital Keypad  Introduction K2 Digital Keypad Introduction The K02 uses the latest microprocessor technology to operate door strikes and security systems that require a momentary (timed) or latching dry contact closure. All programming

More information

Wiring Instructions v4

Wiring Instructions v4 Wiring Instructions v4 GateKeeper h4.2 Technical Support support@gymmastersoftware.com USA: 415 678 1270 Australia: 03 9111 0323 : 03 974 9169 Copyright 2018 Treshna Enterprises. All rights reserved. 15

More information

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual This package is designed to simplify the connections to our Secured Series Hub Plus Controller. This will translate into

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

emerge Essential Access Control System

emerge Essential Access Control System emerge Essential Access ontrol System Document Number: 620-100239, Rev. Installation Guide Linear LL 1950 amino Vida Roble, Suite 150 arlsbad, A 92008-6517 www.linearcorp.com Notices All rights strictly

More information

Owner s Manual. Models 1503 and 1504 Basic Stand Alone Digital Keypad Entry Devices

Owner s Manual. Models 1503 and 1504 Basic Stand Alone Digital Keypad Entry Devices Owner s Manual Models 1503 and 1504 Basic Stand Alone Digital Keypad Entry Devices DoorKing, Inc. 120 Glasgow Avenue Inglewood, California 90301 U.S.A. Phone: 310-645-0023 Fax: 310-641-1586 www.doorking.com

More information

Intelli-M eidc Quick Start Guide. infinias

Intelli-M eidc Quick Start Guide. infinias Intelli-M eidc Quick Start Guide infinias Important Safety Instructions 1. Read these instructions. 2. Keep these instructions. 3. Heed all warnings. 4. Follow all instructions. 5. Do not use this apparatus

More information

Installation and Operation Manual. Model ER8500U / ER16500U. Patent Pending. Head-end Installation ER8500U and ER16500U. Rack Mounting Options

Installation and Operation Manual. Model ER8500U / ER16500U. Patent Pending. Head-end Installation ER8500U and ER16500U. Rack Mounting Options USA EUROPE Model ER8500U / ER16500U Installation and Operation Manual Reduce risk of fire or electrical shock. Do not expose this product to rain or moisture. Note: This installation should be made by

More information

F7_F707_F708 Installation Instruction V1.0 F7_F707_F708. Access Control Terminal. Installation Instructions

F7_F707_F708 Installation Instruction V1.0 F7_F707_F708. Access Control Terminal. Installation Instructions F7_F707_F708 Access Control Terminal Installation Instructions Revised May 2008 About this Guide This guide provides installation instructions only. For information regarding actual operation and configuration

More information

istar Pro Installation Guide

istar Pro Installation Guide istar Pro Installation Guide UM-241 Version A1 October 2010 istar Pro Installation Quick Start Guide System Components The istar Pro hardware components consist of: General Controller Module (GCM) A general

More information

CP150B Vandal & Weather Resistant Keypad Security Systems

CP150B Vandal & Weather Resistant Keypad Security Systems Vandal & Weather Resistant Keypad Security Systems EN Security System CP150B - Vandal & Weather Resistant Keypad The CP150B keypad provides alarm and or access control functionality when used on selected

More information

Installation & Operation Guide

Installation & Operation Guide Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief

More information

Quick Start Installation Guide

Quick Start Installation Guide RM-DCM-2 Quick Start Installation Guide Version G0 Document Part Number UM-215 May 2010 OVERVIEW The RM-DCM-2 is a UL294 Listed and UL1076 Listed door control module that includes the RM-4E Reader Module

More information

IEI emerge MicroNode Install and Setup Guide. Contents

IEI emerge MicroNode Install and Setup Guide. Contents IEI emerge MicroNode Install and Setup Guide Contents Connecting power and the network to the MicroNode... 2 Using Power over Ethernet (PoE)... 3 or... 3 Using a 12 VDC power supply... 3 Connecting and

More information

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2 document Page 1 of 18 TECHKNOW, INC Kiosk Order Confirmation System INSTALLATION MANUAL Revision Date: July 11, 2012 Part # Version 3.2 Techknow, Inc. 393 Mayfield Road Duncan, SC 29334 www.gotechknow.com

More information

232iLM Keypad Installation and Programming Instructions

232iLM Keypad Installation and Programming Instructions 232iLM Keypad Installation and Programming Instructions Note: This product is designed to be installed and serviced by security and lock industry professionals. Specifications Case Dimensions: 6 1 / 2

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

April 2015 PRICE SCHEDULE A 2.0 Stand-Alone Access Control

April 2015 PRICE SCHEDULE A 2.0 Stand-Alone Access Control Section A6 This Price Schedule is effective April 1, 2015. Date Page Comment 4-1-15 All April, 2015 Price Schedule update. 5-8-15 3 Removed model 1503. Added models 1509 / 1515 (Pg 15) to the TOC. 8-10-15

More information

apple Service Source Xserve RAID 17 March Apple Computer, Inc. All rights reserved.

apple Service Source Xserve RAID 17 March Apple Computer, Inc. All rights reserved. apple Service Source Xserve RAID 17 March 2003 2003 Apple Computer, Inc. All rights reserved. apple Service Source Basics Xserve RAID 2003 Apple Computer, Inc. All rights reserved. Overview Xserve RAID

More information

Power Supply Installation

Power Supply Installation Power Supply Module Overview, on page Installation Guidelines, on page 4 Installing or Replacing an AC Power Supply, on page 6 Installing a DC Power Supply, on page 7 Finding the Power Supply Module Serial

More information

apple Service Source Xserve RAID Xserve RAID and Xserve RAID (SFP) Updated: 25 May Apple Computer, Inc. All rights reserved.

apple Service Source Xserve RAID Xserve RAID and Xserve RAID (SFP) Updated: 25 May Apple Computer, Inc. All rights reserved. apple Service Source Xserve RAID Xserve RAID and Xserve RAID (SFP) Updated: 25 May 2004 2003 Apple Computer, Inc. All rights reserved. apple Service Source Basics Xserve RAID 2003 Apple Computer, Inc.

More information

ZN-7100-DE500-G V ac Wireless Access Point Quick Setup Guide

ZN-7100-DE500-G V ac Wireless Access Point Quick Setup Guide Bottom View ZN-7100-DE500-G V2 802.11ac Wireless Access Point Quick Setup Guide This Quick Setup Guide provides step-bystep instructions on how to set up your ZN- 7100-DE500-G V2 Wireless Access Point.

More information

9212i INSTALLATION. Stand-Alone Keypad. Instructions

9212i INSTALLATION. Stand-Alone Keypad. Instructions INSTALLATION 9212i Stand-Alone Keypad Instructions Features: 4 Independent Outputs 4 Independent Timers All Outputs Assignable by Code On board 5 Amp Form C Relay 120 Users Remote Triggering Input Keypad

More information

1 Description. 2 Specifications. Product Installation Document. Honeywell 12 Clintonville Road Northford, CT

1 Description. 2 Specifications. Product Installation Document. Honeywell 12 Clintonville Road Northford, CT Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULACM4CB HP600ULACM8CB Access Control Power Supply/Charger with Power Distribution Controller PN 52395:A 1/05/06 ECN

More information

PoE Managed Midspan Solution for Standard Network Infrastructure

PoE Managed Midspan Solution for Standard Network Infrastructure Power over the Ethernet PoE Managed Midspan Solution for Standard Network Infrastructure Installation Guide Models Include: NetWay8M NetWay16M - Eight (8) Port PoE Midspan Injector - Sixteen (16) Port

More information

Installing a Power over Ethernet injector

Installing a Power over Ethernet injector Installing a Power over Ethernet injector AlphaEclipse StreetSmart and RoadStar signs The instructions in this document explain how to install/replace a Power over Ethernet (PoE) injector in a StreetSmart

More information

THE BRIDGE. Make any Wiegand device wireless with the Sure-fi Bridge FEATURES. Technology

THE BRIDGE. Make any Wiegand device wireless with the Sure-fi Bridge FEATURES. Technology THE BRIDGE Make any Wiegand device wireless with the Surefi Bridge *Housing options sold separately. Keep your Wiegand system connected. Fix faulty Wiegand systems quickly and easily with our wireless

More information

INSOMNIAC CIA G-600 Gateway Installation Manual P/N CIA Revision 1.0 Date Code:

INSOMNIAC CIA G-600 Gateway Installation Manual P/N CIA Revision 1.0 Date Code: INSOMNIAC CIA G-600 Gateway Installation Manual P/N CIA-675-001 Revision 1.0 Date Code: 1-1-2018 Table of Contents Table of Figures... 3 SPECIFICATIONS:... 4 INSTALLATION... 5 General:... 5 Physical Installation

More information

Manual# Installation Manual. 200E Series. DCU 210E/208E Engine Panel RP 210E/220E Remote Panel

Manual# Installation Manual. 200E Series. DCU 210E/208E Engine Panel RP 210E/220E Remote Panel Manual# 1006495 Installation Manual 200E Series DCU 210E/208E Engine Panel RP 210E/220E Remote Panel Installation Manual for the Marine Pro 200E Series ~~~ DCU 210E/208E Diesel Engine Control Unit RP 210E/220E

More information

Wiring Guide EP.NMINI. Version 1.02 Last Updated:

Wiring Guide EP.NMINI. Version 1.02 Last Updated: Wiring Guide EP.NMINI Version 1.02 Last Updated: 14-10-2014 1 Note: See http://www.entrypass.net/ for updates, revisions, and download the latest installation manual There are currently 2 version of EntryPass

More information

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE O P E R A T I N G I N S T R U C T I O N S IRB-RET UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L 3 2 5-2 0 1 6 M O N I T O R E D DEVICE 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides

More information

January 2019 PRICE SCHEDULE A 2.0 Access Control Devices

January 2019 PRICE SCHEDULE A 2.0 Access Control Devices January 2019 PRICE SCHEDULE A 2.0 Section A3 This Price Schedule is effective January 7, 2019. Date Page Comment 1-2-19 All January, 2019 Price Schedule update. 2-5-19 13 Corrected information listed under

More information

PXL-250 Tiger Controller

PXL-250 Tiger Controller PXL-0 Tiger Controller This quick start guide is made up of specification sheets, a DO/DON T list, basic installation drawings, first time power-on instructions, and short descriptions of key terms and

More information

GateKeeperXpress Standalone or Networked Proximity Card Controller

GateKeeperXpress Standalone or Networked Proximity Card Controller RINGDALE GateKeeperXpress Standalone or Networked Proximity Card Controller Installation & User Manual Revision: 2.0 Date: August 2008 Part Number: Page 1 of 37 Table of Contents Table of Contents... 2

More information

Quick Installation Manual

Quick Installation Manual Quick Installation Manual Please Note: Full Technical guide is located on the DVD if this is your first time installing a Hartmann Controls Access Control System. It is strongly recommended you review

More information

EP1501 Intelligent Controller

EP1501 Intelligent Controller J6 BT K K2 TB5 TB 2.35 [59.69] 2.75 [69.85] EP50 Intelligent Controller with Paired Reader Interface for One Physical Barrier Installation and Specifications: www.mercury-security.com 2355 MIRA MAR AVE.

More information

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-4700 PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY REVISION 2-B-032218 Copyright 2018 by Littelfuse, Inc. All rights reserved.

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UIS-WCB1 Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide as Uni-I/O

More information

PDW30 Point-to-Point Wireless Bridge Installation Guide

PDW30 Point-to-Point Wireless Bridge Installation Guide Thank you for your purchase of the PDW30 Point-to-Point Wireless Bridge. This installation guide will briefly describe some common setup procedures and best practices for this device. This guide includes:

More information

January 2018 PRICE SCHEDULE A 2.0 Access Control Devices

January 2018 PRICE SCHEDULE A 2.0 Access Control Devices Section A3 This Price Schedule is effective January 1, 2018. Date Page Comment 1-1-18 All January, 2018 Price Schedule update. 3-21-18 21 Added 1804-701, 1804-705, 1804-706 LED retrofit kits. 4-24-18 25

More information

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc. DLA DMX512 Analyzer DLA DLA-HH 1 Table Of Contents IMPORTANT SAFEGUARDS... 2 DLA OVERVIEW... 3 CONNECTION... 3 OPERATION... 3 HARDWARE SETUP... 4 DLA-HH (PORTABLE) LAYOUT... 4 CHASSIS LAYOUT... 4 DLA MENU

More information

OPLC Installation Guide

OPLC Installation Guide Samba OPLC SM35-J-R20/SM43-J-R20 SM70-J-R20 SM35-J-T20/SM43-J-T20 SM70-J-T20 OPLC Installation Guide 12 Digital Inputs, include 1 HSC/Shaft-encoder Input, 2 Analog inputs (only when the digital inputs

More information

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for

More information

Quick Start Guide. Mounting the Essential Plus and Elite

Quick Start Guide. Mounting the Essential Plus and Elite Quick Start Guide Congratulations on purchasing an Essential Plus or Elite access control system. This Quick Start Guide provides simple instructions on how to get the system up and running. For more detailed

More information

Installation Guide. Avigilon ACM Embedded Controller

Installation Guide. Avigilon ACM Embedded Controller Installation Guide Avigilon ACM Embedded Controller 2016, Avigilon Corporation. Portions 2003-2014 HID Global Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACCESS CONTROL MANAGER and ACM

More information

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION Document 476092 User and Service Manual Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

PM Series Power Meter

PM Series Power Meter PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See

More information

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015) SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication

More information

SECURITY DOOR CONTROLS 801 Avenida Acaso, Camarillo, Ca (805) Fax: (805)

SECURITY DOOR CONTROLS 801 Avenida Acaso, Camarillo, Ca (805) Fax: (805) SECURITY DOOR CONTROLS 801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS Model 931 EntryCheck The

More information

ievo ULTIMATE INSTALLATION GUIDE

ievo ULTIMATE INSTALLATION GUIDE ievo ULTIMATE INSTALLATION GUIDE DOC0066 ISSUE: 03 26th April 2017 ievo READER INSTALLATION GUIDE Issue 03 2 ievo READER INSTALLATION GUIDE Issue 03 Contents 1. Introduction 1-1 1.1 Advice on User Registration

More information

FlexPass. ASR Long Range Reader. Installation Guide Jeronimo Road Irvine, CA July 16, 2007 Document Number K , Rev B

FlexPass. ASR Long Range Reader. Installation Guide Jeronimo Road Irvine, CA July 16, 2007 Document Number K , Rev B 9292 Jeronimo Road Irvine, CA 92618-1905 FlexPass ASR-620++ Long Range Reader Installation Guide July 16, 2007 Document Number K02021-000, Rev B FlexPass ASR-620++ Long Range Reader K02021-000 Rev. B Contents

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

Research Concepts RC2500 Antenna Interface Unit (AIU) Board Set

Research Concepts RC2500 Antenna Interface Unit (AIU) Board Set Research Concepts RC2500 Antenna Interface Unit (AIU) Board Set A board set has been developed that can be incorporated into an AIU for an RC2500 antenna controller. This board set is the basis of RC2500

More information

Cerberus Division. Installation Instructions CERBERUS PYROTRONICS TM Model RDM-MXL. (Remote Diagnostics Module)

Cerberus Division. Installation Instructions CERBERUS PYROTRONICS TM Model RDM-MXL. (Remote Diagnostics Module) Cerberus Division Installation Instructions CERBERUS PYROTRONICS TM Model RDM-MXL Remote Diagnostics Module INTRODUCTION The CERBERUS PYROTRONICS TM Model RDM-MXL module (RDM for connection to the MXL

More information

CA-A480-A Elevator Controller. Reference & Installation Manual

CA-A480-A Elevator Controller. Reference & Installation Manual CA-A480-A Elevator Controller Reference & Installation Manual TABLE OF CONTENTS INTRODUCTION.................................................................. 4 Introduction.............................................................................................

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Peripheral Relay The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Up to 16 Cards can be connected to a multi-loop panel

More information

Comm. RS-232. Analog I/O I N P U T S O U T P U T S. I/O Supply. Logic Supply RET RET Fault

Comm. RS-232. Analog I/O I N P U T S O U T P U T S. I/O Supply. Logic Supply RET RET Fault Model 2220 Analog Input / Output Module Installation Guide 2701E 2203 I/O Supply Logic Supply Fault 1 5 9 13 I N P U T S 2220 Digital Out 02 04 06 08 RET RET +24 +24 Out1 Out4 Out5 Out8 Comm. RS-232 1

More information

TAC I/NETTM 1284, 1280, Security Control Unit

TAC I/NETTM 1284, 1280, Security Control Unit TAC I/NETTM The SCU () family of modular, stand-alone controllers are basic building blocks of the I/NET Seven Security Management System, and provide a flexible mix of door control and alarm monitoring

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

FEATURES AND PROGRAMMING GUIDE SELF-CONTAINED ACCESS CONTROL SYSTEMS:

FEATURES AND PROGRAMMING GUIDE SELF-CONTAINED ACCESS CONTROL SYSTEMS: FEATURES AND PROGRAMMING GUIDE SELF-CONTAINED ACCESS CONTROL SYSTEMS: 233CARDREADER DOOR-GARD SELF-CONTAINED ACCESS CONTROL SYSTEMS offer field proven reliability and cost effective solutions for residential,

More information

installation quick guide integrated access control & environmental monitoring

installation quick guide integrated access control & environmental monitoring installation quick guide integrated access control & environmental monitoring Introduction This Installation Quick Guide is suitable for standard wallmountable AX300 controllers. Illustrative technical

More information

INSTALLATION INSTRUCTIONS 921P EntryCheck TM

INSTALLATION INSTRUCTIONS 921P EntryCheck TM 80 Avenida Acaso, Camarillo, Ca. 90 (805) 494-06 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS 9P EntryCheck TM The EntryCheck 9P Indoor/Outdoor Keypad is a surface mount

More information

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-5B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual

More information

ADDJOG User Guide 7/30/10. Overview

ADDJOG User Guide 7/30/10. Overview ADDJOG User Guide 7/30/10 Overview The ADDJOG is a PLC expansion board used to add digital inputs and outputs to a compatible host PLC. The ADDJOG has 64 open collector outputs and 64 non-isolated inputs.

More information

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL Revision 2.1 July. 2014 1 Integriti 8 32 Zone LAN Expander Module Kit P/N: 996005PCB&K For Rev. B PCB. INSTALLATION MANUAL Overview The Integriti 8 Zone Expander Module provides an additional 8 Zone inputs,

More information

Beacon Power Supply Operating and Installation Instruction Manual

Beacon Power Supply Operating and Installation Instruction Manual Beacon Power Supply Operating and Installation Instruction Manual Model: BNx000 Page 1 of 27 I. Warnings and Notices I. WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

PS-4100 POWER SUPPLY MANUAL

PS-4100 POWER SUPPLY MANUAL PS-4100 POWER SUPPLY MANUAL Manual Part Number 180-0573 December 7, 2006 TABLE OF CONTENTS TITLE PAGE Table of Contents... 2 List Of Figures... 3 1. Introduction... 4 1.0. General... 4 1.1. Features...

More information