Dorman Smith Switchgear Product Portfolio

Size: px
Start display at page:

Download "Dorman Smith Switchgear Product Portfolio"

Transcription

1 Dorman Smith Switchgear Product Portfolio

2 How to use this catalogue This catalogue has been designed to enable users to access the information on the whole product range in a straight-forward and logical manner. We are conscious that the needs of our customers vary considerably and that, as our markets continue to grow, many will be dealing with our systems and products for the first time. Where product codes are already well known, the Product and Parts Locator at the back of the catalogue will direct you to the pages relevant to each occurrence of a particular item. Each main product or system category has its own section. The sections are arranged such that those detailing the simpler and smaller systems are at the beginning. Exploded views of typical system configurations are given as a guide, near to the front of each section. In order to help you to build a system, there are detailed Selection Charts at the end of each section. Again, these are formatted in a logical manner, from main housings to incomers, outgoing devices to their accessories. Once a reasonable level of familiarity with the TE Connectivity Dorman Smith product range has been attained, complete circuit distribution systems can be readily configured directly from the Selection Charts alone. Following the main products sections, the Technical Data and Applications section provides a high level of detail on both specific products and the principles of circuit protection in general. We trust you will find this catalogue informative, helpful and a quick and easy-touse tool whenever you need to configure MCB or MCCB distribution schemes.

3 Electrical Distribution and Circuit Protection Product Catalogue How to use this catalogue Contents 1 TE Connectivity/Dorman Smith 3 Contents SP&N Distribution Systems (A-type) 5-14 TP&N Distribution Systems (B-type) MCCB Panel Boards (250A & 400A) Fuse Switch Panel Boards (800A) MCCB Panel Boards (400A & 800A) Fuse Combination Units Dorman Smith Circuit Protection and Modular Devices 7 MCB and MCCB General Purpose Enclosures Technical Data & Applications Products & Parts Locator L LM4 LM50 LM60 LM2P LM3P10 LM3P20 LM3P30 LM3P40 MMB2 1 B

4 Solutions for Current Regulations TE Connectivity provides solutions for easy compliance of current regulations within electrical installations by utilising products from both the Dorman Smith and Crompton Instruments brand portfolios. Enhancing the design of Dorman Smith products to incorporate metering and surge protection facilities has made it easy and more economical to comply with the necessary regulations. Easy Compliance 17th Edition IEE Wiring Regulations Part L2 Building Regulations Protection Against Lightning Electrical and Electronic Systems with Structures BS EN To find out more, please contact our sales team Tel: +44 (0) Fax: +44 (0) TE connectivity (logo), TE Connectivity and Dorman Smith are trademarks. Crompton is a trademark of Crompton Parkinson Ltd., and is used by TE Connectivity under licence. 2

5 TE Connectivity With a 50-plus year history of leadership, TE Connectivity is a global, $12.1 billion company that designs and manufactures over 500,000 products that connect and protect the flow of power and data inside the products that touch every aspect of peoples lives. Our nearly 100,000 employees partner with customers in virtually every industry from consumer electronics, energy and healthcare, to automotive, aerospace and communication networks enabling smarter, faster, better technologies to connect products to possibilities. TE Energy connecting the world of power TE Energy, a global operating unit within TE Connectivity, is focused on providing products and systems for the electrical power industry. TE Energy products are extensively used by power utilities, equipment manufacturers, railways and by a wide range of industries. Each Business Unit within the TE Energy comes with a specialised product line and focused set of application skills for its specific market niche. Thus TE Energy is able to bring innovative and technology driven products efficiently to market by synchronising the product development and manufacturing facility capabilities. TE Energy is a global supplier of: Cable accessories Connectors and fittings Insulators and insulation Surge arresters Switching, protection and lighting Power measurement and control Dorman Smith Switchgear Dorman Smith Switchgear has been a part of TE Connectivity since With over 130 years of experience in switchgear design and production, Dorman Smith business unit continues to bring high quality electrical distribution and circuit protection equipment to market. Dorman Smith business unit's line-up of electrical equipment begins with simple SP&N distribution boards and extends to custom designed, factory built, lowvoltage switchboards for a broad range of commercial and industrial applications. Dorman Smith and Crompton Instruments products combine through shared technologies and close co-operation a complementary portfolio of low voltage power measurement and protection products for energy applications worldwide. The extensive array of electrical distribution systems suited to a broad scope of, commercial and industrial applications, together with instruments for measurement of key electrical parameters ensures unrivalled capability to fulfil the most demanding specifications. End user applications for the company s products and systems are found in rail transportation, building management, utilities and infrastructure, together with the manufacturing sector and many parts of the process industry. The Dorman Smith product range includes: MCB distribution board systems MCCB panel board systems Fuse combination switch units Modular control devices Digital metering panel instruments 3

6 Dorman Smith Modis Switchboards The range of Modis LV distribution switchboard systems is designed and engineered by Dorman Smith business unit and this range of fully type tested assemblies comprehensively covers all low-voltage switchboard requirements up to 3200 amps! The Modis range of LV distribution switchboard systems is available as wall-mounted or floor standing with front or rear access. Assembled by our trained certified partners, the Modis range of LV distribution switchboards is more than capable of satisfying individual customer needs, for the control and protection of the power distribution system in commercial and industrial applications. To find out more, please contact our sales team Tel: Fax: TE connectivity (logo), TE Connectivity, Dorman Smith and Modis are trademarks. 4

7 Section 1 SP&N Distribution Systems Loadlimiter 63 Range of SP&N Distribution Systems (A-type)

8 Overview Key Features Distribution board has 125A rated busbars Distribution boards can be stacked Choice of switch disconnector or RCCB incomer Boards have standard height (250mm) and depth (116mm) Available Options Distribution boards provide from 6 to 22 outgoing ways Incomer can be double-pole switch disconnector up to 125A or double-pole RCCB up to 100A Outgoing ways can be configured with 10kA-rated MCBs or RCBOs Matching service centres equipped with 8 to 24 modular ways Additional Features Single module shunt trip and auxiliary contacts easily fitted to MCBs Neutral and earth terminal for each single-pole way IP4X Ingress Protection The Dorman Smith Loadlimiter 63 distribution system includes a versatile range of MCB distribution boards and components for constructing comprehensive SP&N circuit management solutions. The system is designed for applications demanding up to 125A incoming and 63A outgoing capacity and the distribution board exceeds the requirements of EN The array of circuit devices includes an extensive range of MCBs, RCBOs, RCCBs and switch disconnectors. The system ensures simple configuration and quick installation as demanded by today s new and retrofit, commercial and industrial applications. The standard finish is epoxy powder coating in light grey RAL Compliance Distribution boards EN MCBs EN Contactors EN RCBOs EN RCCBs EN

9 SP&N Distribution System A-type Distribution Boards Service centres Stacking kits Incoming Devices Switch disconnectors Residual current circuit breakers - RCCB Circuit Protection Devices Miniature circuit breakers Residual current circuit breaker with overcurrent protection - RCBO Residual current circuit breakers - RCCB Modular Devices Surge protection Metering Contactors Timer Residual current circuit breaker 7

10 Loadlimiter 63 A-type Distribution Boards and Accessories A-type Distribution Boards Exceeds the requirements of EN A rated Neutral and earth terminal for each single-pole way 6-22 single-pole outgoing ways IP4X Ingress Protection Outgoing Width Weight Cat. no. 1-pole ways (mm) (kg) DA06X DA09X DA12X DA15X DA18X DA22X A-type Service Centre Accepts all DIN-rail mounting devices 8-24 modular ways IP4X Ingress Protection Modular ways Width (mm) Weight (kg) Cat. no DAS08X DAS11X DAS14X DAS17X DAS20X DAS24X Accessories for A-type Distribution Boards Description Picture Cat. no. Vertical stacking kits Stacking kit for 270mm width 1 DAXSK08 Stacking kit for 323mm width 1 DAXSK11 Stacking kit for 377mm width 1 DAXSK14 Stacking kit for 430mm width 1 DAXSK17 Stacking kit for 484mm width 1 DAXSK20 Stacking kit for 555mm width 1 DAXSK24 Earth bar kits Earth bar 3 DAXEB Earth bar isolation kit 3 DBXL Door lock kits Cylinder door lock 4 DBXCL Padlock bracket kit 4 DBXPL Blanking kits 10 busbar terminal blanks 2 DAXTP MCB blanks 4xTP MCB + 12 busbar terminal blanks 5 DBXBP 5x1P MCB + 5 busbar terminal blanks 6 DBXBM 5x 1 2 MCB blanks - DBXBH 8

11 Loadlimiter 63 A-type Distribution Boards Incoming Options Switch Disconnector Exceeds the requirements of EN mm 2 cable capacity Duty category of AC22 Incoming Current Poles Max. cable Cat. no. device type rating (A) (mm 2 ) Switch disconnector AV2100 Switch disconnector AV2125 Double-pole RCCB Exceeds the requirements of EN Equipped with transient suppression filter Voltage 230/400V 50/60 Hz Double module for both type AC Terminal capacity: top 25mm 2 Terminal capacity: bottom 35mm 2 Incoming Current Sensitivity Device Cat. no. device type rating (A) (ma) type RCCB AC EE63/30/2 RCCB AC EE63/100/2 RCCB AC EE63/300/2 RCCB AC EE80/30/2 RCCB AC EE100/30/2 RCCB AC EE100/100/2 RCCB time delay AC EES100/100/2 Direct Connection Incoming device type Max. cable (mm 2 ) Pic number Cat. no. 1 Direct connection 35 1 DBXD0 Direct connection 70 2 DAXD1 2 Surge Protection Plug-in surge protection modules Integral protection status indicator Operating range V rms max Hot working replaceable modules Terminals 35mm 2 max See page 116 for more information. Device type SP + NE surge protection MOV replacement plug-in module MOV neutral/earth replacement plug-in module Cat. no. DSPM1PN DSPML DSPMNE Note: It is recommended that SPM surge protectors are installed on the load side of a MCB - type C, MCCB or a fused disconnector 63A to provide isolation and protection. 9

12 Loadlimiter 63 A-type Outgoing Devices Single-pole MCBs Exceeds the requirements of EN kA rated breaking capacity to EN kA rated breaking capacity to EN Contact position indicator 35mm 2 cable capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no. 6 K1PB06 K1PC06 K1PD06 10 K1PB10 K1PC10 K1PD10 13 K1PB13 K1PC13-16 K1PB16 K1PC16 K1PD16 20 K1PB20 K1PC20 K1PD20 25 K1PB25 K1PC25 K1PD25 32 K1PB32 K1PC32 K1PD32 40 K1PB40 K1PC40 T1PD40* 50 K1PB50 K1PC50 T1PD50* 63 K1PB63 K1PC63 T1PD63* * 6kA/10kA - EN60898/EN Single Module RCBOs Exceeds the requirements of EN Single module: type AC 10kA rated breaking capacity Terminal capacity: top terminals 10mm 2 Terminal capacity: bottom terminals 35mm 2 Current rating (A) Sensitivity (ma) B type cat. no. C type cat. no KR1PB0630 KR1PC KR1PB1030 KR1PC KR1PB1630 KR1PC KR1PB2030 KR1PC KR1PB3230 KR1PC KR1PB4030 KR1PC KR1PB4530 KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC40100 Double Module RCBOs Exceeds the requirements of EN 61009, IEC SP&SwN configuration Rated breaking capacity up to 10kA Contact position indicator Rated voltage Ue ~230V Rated frequency 50Hz Energy limiting class 3 Type AC Terminal capacity: outgoing terminals 35mm 2 Terminal capacity: busbar side terminals 35mm 2 Current rating (A) Sensitivity (ma) B type cat. no. C type cat. no KR2PB0630 KR2PC KR2PB1030 KR2PC KR2PB1630 KR2PC KR2PB2030 KR2PC KR2PB3230 KR2PC KR2PB4030 KR2PC

13 Loadlimiter 63 A-type Metering and Accessories Accessories for MCBs and RCBOs Auxiliary equipment Picture Cat. no. MCB shunt trip (240V AC) 1 KST240 MCB auxiliary/switching contact KAUX1 Padlocking Picture Cat. no. 1 MCB dolly locking device 2 KDL Padlock for dolly locking device XPL 2 DIN-rail Mounted Meters DIN-rail mountable in Loadlimiter 63 service centres Device type Outputs Width Cat. no. (mm) 3-phase analogue 1 pulse 71 DRK-3PCT-415 kwh meter 3-phase digital kwh meter 1 pulse 71 DRK-3PCT-415-LCD 1-phase/3-phase digital 1 pulse & 71 RI3-01 multi-function meter 1 modbus 1-phase digital kwh meter 1 pulse 54 DRK-1P-230-D63 with integral 63A current transformer Measuring Current Transformers System voltage up to 720V Secondary output of 5A Operating temperature range of 20 C to +70 C Description Cable aperture Height Width Cat. no. (mm) (mm) (mm) 100A current transformer M53Q-100/5 125A current transformer M53Q-125/5 DIN-rail clip M30-DINCLIP 11

14 Loadlimiter 63 Selection Chart - A-type Distribution Boards Busbar rating Outgoing ways Width (mm) Weight (kg) Cat. no. 125A DA06X 125A DA09X 125A DA12X 125A DA15X 125A DA18X 125A DA22X Service Centres For DIN-rail modules Modular ways Service centre DAS08X Service centre DAS11X Service centre DAS14X Service centre DAS17X Service centre DAS20X Service centre DAS24X Incoming Devices Device type Current rating (A) Sensitivity (ma) Max. cable (mm 2 ) Switch disconnector AV2100 Switch disconnector AV2125 RCCB, type AC EE63/30/2 RCCB, type AC EE63/100/2 RCCB, type AC EE63/300/2 RCCB, type AC EE80/30/2 RCCB, type AC EE100/30/2 RCCB, type AC EE100/100/2 RCCB type AC time delay EES100/100/2 Direct connection DBXD0 Direct connection DAXD1 Surge Protection SP + NE surge protection MOV replacement plug-in module MOV neutral/earth replacement plug-in module DSPM1PN DSPML DSPMNE Accessories for DA Type Distribution Boards Vertical stacking kits Stacking kit for 270mm width Stacking kit for 323mm width Stacking kit for 377mm width Stacking kit for 430mm width Stacking kit for 484mm width Stacking kit for 555mm width Blanking kits Busbar terminal blanks (set of 10) Earth bar kits Earth bar Earth bar isolation kit Door lock kits Cylinder door lock Padlock bracket kit DAXSK08 DAXSK11 DAXSK14 DAXSK17 DAXSK20 DAXSK24 DAXTP DAXEB DBXL DBXCL DBXPL 12

15 Loadlimiter 63 Selection Chart - A-type SP&N MCBs B, C & D types 10kA/15kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no. 1-pole 6 K1PB06 K1PC06 K1PD06 1-pole 10 K1PB10 K1PC10 K1PD10 1-pole 13 K1PB13 K1PC13 K1PD13 1-pole 16 K1PB16 K1PC16 K1PD16 1-pole 20 K1PB20 K1PC20 K1PD20 1-pole 25 K1PB25 K1PC25 K1PD25 1-pole 32 K1PB32 K1PC32 K1PD32 1-pole 40 K1PB40 K1PC40 T1PD40* 1-pole 50 K1PB50 K1PC50 T1PD50* 1-pole 63 K1PB63 K1PC63 T1PD63* 6kA/10kA - EN60898/EN SP&N RCBOs B & C types 10kA breaking capacity Current rating (A) Sensitivity B type C type Device type (ma) cat. no. cat. no. Single module, type AC 6 30 KR1PB0630 KR1PC0630 Single module, type AC KR1PB1030 KR1PC1030 Single module, type AC KR1PB1630 KR1PC1630 Single module, type AC KR1PB2030 KR1PC2030 Single module, type AC KR1PB3230 KR1PC3230 Single module, type AC KR1PB4030 KR1PC4030 Single module, type AC KR1PB4530 KR1PC4530 Single module, type AC KR1PC06100 Single module, type AC KR1PC10100 Single module, type AC KR1PC16100 Single module, type AC KR1PC20100 Single module, type AC KR1PC32100 Single module, type AC KR1PC40100 Accessories for MCBs and RCBOs Description Auxiliary equipment MCB shunt trip (240V ac) MCB auxiliary/switching contact Padlocking MCB dolly locking device Padlock for dolly locking device Blanking pieces MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) MCB blanks (5x 1 2 MCB ways) Cat. no. KST240 KAUX1 KDL XPL DBXBP DBXBM DBXBH Metering Description Outputs Width (mm) Cat. no. 3-phase analogue kwh meter 1 pulse 71 DRK-3PCT phase digital kwh meter 1 pulse 71 DRK-3PCT-415-LCD 1-phase/3-phase digital multi-function meter 1 pulse & 1 modbus 71 RI phase digital kwh meter with integral 63A current transformer 1 pulse 54 DRK-1P-230-D63 Current transformer, 100A - - M53Q-100/5 Current transformer, 125A - - M53Q-125/5 13

16 Loadlimiter 63 Outline Drawings and Dimensions A-type Distribution Boards 1-pole ways Width (mm) Weight (kg) Cat. no DA06X DA09X DA12X DA15X DA18X DA22X All dimensions in mm A-type Service Centres Modular ways Width (mm) Weight (kg) Cat. no DAS08X DAS11X DAS14X DAS17X DAS20X DAS24X 14

17 Section 2 TP&N Distribution Systems Loadlimiter 63 Range of TP&N Distribution Systems (B-type)

18 Overview Key Features Conforms to EN ASTA certified busbars rated at 10kA for 250ms Neutral and earth terminal 25mm 2 for each single-pole way Clean earth facility Enclosures are 484mm wide x 159 deep 4 to 24 TP&N outgoing ways IP4X Ingress Protection Double earth kits available Extended service centres with fitted earth and neutral terminals Available Options Incomer can be switch disconnector, contactor, fuse switch, MCCB or RCCB Outgoing ways can be configured with 10/15kA-rated MCBs or RCBOs Matching service centres equipped with one or two rows of 18-pole ways Surge protection modules can be accommodated within standard configuration Modular DIN-rail meter fits within standard configuration Benefits Extra spreading room for single module RCBOs Multi incoming options Earth/neutral close to phase terminal MCBs with symmetrical dual terminals Integral metering options Exceptional flexibility The Dorman Smith Loadlimiter 63 TP&N distribution board system excels in providing flexible and cost effective final circuit management solutions for commercial and industrial applications. Featuring a comprehensive range of TP&N distribution boards rated at 250A and a wide array of circuit devices the system ensures simple configuration as well as quick assembly for new and retrofit applications. To suit current industry regulation requirements the range has been extended to offer a vast collection of metering accessories including fully assembled metered power and lighting distribution boards. This range consists of both stocked and customised options providing an easy and flexible solution to comply with Part L2 Building Regulations and specification requirements. The standard finish is epoxy powder coating in light grey RAL Applications Commercial and industrial final circuit protection Part L2 building regulations 17th edition wiring regulations Compliance Distribution boards MCBs Contactors RCBOs RCCBs EN EN60898 EN61095 EN61009 EN

19 TP&N Distribution System B-type Distribution Boards Service centres Stacking kits Assembled metered boards Metering enclosures Incoming Devices Switch disconnectors - modular 125A max Switch disconnectors - MCCB 250A max Residual current circuit breakers - RCCB Fuse switch Moulded case circuit breakers Contactors Circuit Protection Devices Miniature circuit breakers Residual current circuit breaker with overcurrent protection - RCBO Residual current circuit breaker - RCCB Modular Devices Surge protection Meters, current transformers and wiring looms Contactors Timer Residual current circuit breaker 17

20 Loadlimiter 63 B-type Distribution Boards and Enclosures B-type Distribution Boards Exceeds the requirements of EN ASTA certified busbars rated at 10kA for 250mS Neutral and earth terminal 25mm 2 for each single-pole way Integral clean earth facility Enclosure are 484mm wide x 159mm deep 4-24 TP&N outgoing ways IP4X Ingress Protection Outgoing Height Weight Cat. no. 3-pole ways (mm) (kg) DBX04R DBX06R DBX08R DBX12R DBX16R DBX20R DBX24R Double earth bar kits are available Order as DBTE**X, where ** = 04 to A Incoming Housing Enclosure to mount any YA3 Frame MCCB up to 250A Facility to mount two panel mounted meters (using available knockouts) Incomer Height (mm) Weight (kg) Cat. no. 3-pole unit DBXYA3 4-pole unit DBXYA3 Note: Devices to be ordered separately. Triple-pole device requires neutral link YA3NL to be ordered separately. Description YA3 neutral link Cat. no. YA3NL Service Centres for all B-type Distribution Boards Accepts all DIN-rail mounting devices 18 or 36 modular ways IP4X Ingress Protection General purpose enclosure includes facility to mount two panel mounted meters and DIN-rail for current transformers Neutral and earth bars fitted as standard Modular ways Height (mm) Weight (kg) Cat. no. 18 x 1-pole ways (single row) DBS18X 36 x 1-pole ways (double row) DBS36X General purpose enclosure DBMSB Supplied without top or bottom plate. Intended for use with removable plate from distribution board. 18

21 Loadlimiter 63 B-type Distribution Boards Accessories Description Picture Cat. no. Conversion kits plus spares TP&N to SP&N conversion kit 1 DBXTS Spare end plate 2 DBXEP Fixing kit for 24 way distribution boards DBX24FK Blank way label for 24 way distribution boards DBX24WL DA18X to B type board stacking kit DBXSKA Blanking pieces MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) 8 DBXBP MCB blanks (5x1P MCB ways + 5 busbar terminal blanks) 9 DBXBM MCB blanks (5x 1 2 MCB Ways) DBXBH Joining kit Kit for vertically joining two distribution boards 3 DBXJK Terminal bars Terminal bar for 6 ways (6 useable 1P ways) 6 DBXT06 Terminal bar for 12 ways (12 useable 1P ways) 6 DBXT12 Terminal bar for 18 ways (18 useable 1P ways) 6 DBXT18 Terminal bar for 24 ways (24 useable 1P ways) 6 DBXT24 Blanking kits Busbar terminal blanks (set of 10) 4 DAXTP Earth bar kits Earth bar 7 DAXEB Earth bar isolation kit 5 DBXL Double earth bar facility Earth bar kit with terminal for each outgoing way (where ** = 04, 06, 08, 12, 16, 20 or 24 ways) DBTE**X Door lock kits Cylinder door lock 10 DBXCL Padlock bracket kit 11 DBXPL

22 Loadlimiter 63 B-type Incoming Options Switch Disconnector 125A Max Exceeds the requirements of EN mm 2 cable capacity Duty category of AC22 Switch disconnector Device type Max. cable Sensitivity Incoming Connection (mm 2 ) (ma) device cat. no. kit cat. no. 100A, 3-pole 50 - AV3100 N/A 100A, 4-pole 50 - AV4100 DBXCKR 125A, 3-pole 50 - AV3125 N/A 125A, 4-pole 50 - AV4125 DBXCKR RCCBs Exceeds the requirements of EN Double width module, 35mm Type AC Terminal capacity: 40A-63A: 25mm 2 Terminal capacity: 100A: 35mm 2 4-pole RCCB Cat. no. 40A, type AC EE40/30/4 DBXCKR 40A, type AC EE40/100/4 DBXCKR 63A, type AC EE63/30/4 DBXCKR 63A, type AC EE63/100/4 DBXCKR 63A, type AC EE63/300/4 DBXCKR 100A, type AC EE100/30/4 DBXCKR 100A, type AC EE100/100/4 DBXCKR 100A, type AC EE100/300/4 DBXCKR 100A, type AC, EES100/100/4 DBXCKR time delay Contactors DIN-rail Mounted Exceeds the requirements of EN May require de-rating when used with inductive loads see Contactor De-rating table in the Technical Applications section Contactor Cat. no. 40A, 4-pole - - EE4P40CO DBXCKR 63A, 4-pole - - EE4P63CO DBXCKR Fuse Combination Units Fuse switch Cat. no. 100A, 3-pole 70 - HBF3P100N DBXLSA1 200A, 3-pole HBF3P200N DBXLSA2 20

23 Loadlimiter 63 B-type Incoming Options and Surge Protection YA3 frame MCCB - 250A Max Standard cable termination 95mm 2 Cable clamps termination - 120mm 2 Maximum cable termination is 150mm 2 using reduced palm width M8 cable lugs MCCBs have thermal and magnetic overloads except switch disconnector To be mounted in incoming housing (DBXYA3) Device type Max. cable I cu Incoming device (mm 2 ) cat. no. 63A, 3-pole 150* 25kA YA3N3P63T 63A, 4-pole 150* 25kA YA3N4P63T 100A, 3-pole 150* 25kA YA3N3P100T 100A, 4-pole 150* 25kA YA3N4P100T 125A, 3-pole 150* 25kA YA3N3P125T 125A, 4-pole 150* 25kA YA3N4P125T 160A, 3-pole 150* 25kA YA3N3P160T 160A, 4-pole 150* 25kA YA3N4P160T 200A, 3-pole 150* 25kA YA3N3P200T 200A, 4-pole 150* 25kA YA3N4P200T 250A, 3-pole 150* 25kA YA3N3P250T 250A, 4-pole 150* 25kA YA3N4P250T 250A, 3-pole 150* - YA3B3P250D switch disconnector 250A, 4-pole 150* - YA3B4P250D switch disconnector * 150mm 2 based on using reduced palm width cable lugs Direct Connection Terminal Kits Description Max. cable (mm 2 ) Picture Cat. no. 2 3 Terminals 35 1 DBXD0 Terminals 70 2 DBXD1 Terminals DBXD2 1 Surge Protection Plug-in surge protection modules Integral protection status indicator Thermal and current overload fusing Three-phase operating range, V rms max Hot working replaceable modules Device type Width (mm) Cat. no. 3-phase with neutral/earth surge protection module 54 DSPM3PN MOV replacement plug-in SPM 17.5 DSPML MOV neutral/earth replacement plug-in SPM 17.5 DSPMNE Note: Connection kit DBXCKR must be ordered to provide the additional DIN-rail needed to mount this device in the distribution enclosure below the incoming device (for 125A max only). For 250A applications devices should be mounted in a service centre. 21

24 Loadlimiter 63 DB-type Outgoing Devices Single-pole MCBs Exceeds the requirements of EN kA rated breaking capacity to EN kA rated breaking capacity to EN Contact position indicator 35mm 2 cable capacity Current B type C type D type rating (A) cat. no. cat. no. cat no. 6 K1PB06 K1PC06 K1PD06 10 K1PB10 K1PC10 K1PD10 13 K1PB13 K1PC13 N/A 16 K1PB16 K1PC16 K1PD16 20 K1PB20 K1PC20 K1PD20 25 K1PB25 K1PC25 K1PD25 32 K1PB32 K1PC32 K1PD32 40 K1PB40 K1PC40 T1PD40* 50 K1PB50 K1PC50 T1PD50* 63 K1PB63 K1PC63 T1PD63* Triple-pole MCBs Current B type C type D type rating (A) cat. no. cat. no. cat no. 6 K3PB06 K3PC06 K3PD06 10 K3PB10 K3PC10 K3PD10 13 K3PB13 N/A N/A 16 K3PB16 K3PC16 K3PD16 20 K3PB20 K3PC20 K3PD20 25 K3PB25 K3PC25 K3PD25 32 K3PB32 K3PC32 K3PD32 40 K3PB40 K3PC40 T3PD40* 50 K3PB50 K3PC50 T3PD50* 63 K3PB63 K3PC63 T3PD63* * 6kA/10kA - EN60898/EN

25 Loadlimiter 63 B-type Outgoing Devices and Accessories Single Module RCBOs Exceeds the requirements of EN Single module: Type AC 10kA rated breaking capacity Terminal capacity: outgoing terminals 10mm 2 Terminal capacity: busbar side terminals 35mm 2 Current Sensitivity B type C type rating (A) (ma) cat. no. cat no KR1PB0630 KR1PC KR1PB1030 KR1PC KR1PB1630 KR1PC KR1PB2030 KR1PC KR1PB3230 KR1PC KR1PB4030 KR1PC KR1PB4530 KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC40100 Double Module RCBOs Exceeds the requirements of EN 61009, IEC SP&SwN configuration Rated breaking capacity up to 10kA Contact position indicator Rated voltage Ue ~230V Rated frequency 50Hz Energy limiting class 3 Type AC Terminal capacity: outgoing terminals 35mm 2 Terminal capacity: busbar side terminals 35mm 2 Current rating (A) Sensitivity (ma) B type cat. no. C type cat. no KR2PB0630 KR2PC KR2PB1030 KR2PC KR2PB1630 KR2PC KR2PB2030 KR2PC KR2PB3230 KR2PC KR2PB4030 KR2PC4030 Accessories for MCBs and RCBOs Auxiliary equipment Picture Cat. no. MCB shunt trip (240V AC) 1 KST240 MCB auxiliary/switch contact KAUX1 Padlocking Picture Cat. no. 1 MCB dolly locking device 2 KDL Padlock for dolly locking device XPL 2 23

26 Loadlimiter 63 B-type Modular Devices Double-pole RCCBs Exceeds the requirements of EN Voltage 230/400V 50/60Hz Type AC Terminal capacity: 40A-63A: 25mm 2 Terminal capacity: 100A: 35mm 2 Current rating (A) Sensitivity (ma) Type Width (mm) Cat. no AC 35 EE40/30/ AC 35 EE40/100/ AC 35 EE63/30/ AC 35 EE63/100/ AC 35 EE63/300/ AC 35 EE100/30/ AC 35 EE100/100/2 100, time delay 100 AC 35 EES100/100/2 Four-pole RCCBs Current rating (A) Sensitivity (ma) Type Width (mm) Cat. no AC 70 EE40/30/ AC 70 EE40/100/ AC 70 EE40/300/ AC 70 EE63/30/ AC 70 EE63/100/ AC 70 EE63/300/ AC 70 EE100/30/ AC 70 EE100/100/ AC 70 EE100/300/4 100, time delay 100 AC 70 EES100/100/4 Programmable Timers DIN-rail Mounted 250V ac 50/60Hz Running reserve of 3 years Switching capacity 150mA Current rating (A) Function Width (mm) Cat. no. 16A (AC7A) 1 or 2 channel 35 DRT-DW2R When controlling highly inductive loads, a suitably rated contactor should be employed with timers, programmers and relays. Contactors DIN-rail Mounted Exceeds the requirements of EN May require de-rating when used with inductive loads see Contactor De-rating table in the Technical Applications section Current rating (A) Width (mm) Contacts Cat. no. 20A P N/O EE2P20CO 20A 35 2P N/C EE2P20CC 25A 35 4P N/O EE4P25CO 25A 35 4P N/C EE4P25CC 40A 54 4P N/O EE4P40CO 40A 54 4P N/C EE4P40CC 63A 54 4P N/O EE4P63CO 63A 54 4P N/C EE4P63CC Venting kit * 9 - LLMV 24 * Ventilation module must be fitted between alternate pairs of contactors to prevent overheating.

27 Loadlimiter 63 Meters, Current Transformers and Wiring Looms DIN-rail Mounted Meters for Incoming Circuits 4 modules width Fully programmable CT ratios Device type Outputs Width (mm) Cat. no. 3-phase analogue kwh meter 1 pulse 71 DRK-3PCT phase digital kwh meter 1 pulse 71 DRK-3PCT-415-LCD 1-phase/3-phase digital 1 pulse 71 RI3-01 multi-function meter & 1 Modbus Note: Connection kit DBXCKR must be ordered to provide the additional DIN-rail needed to mount these devices integral to distribution board below the incoming disconnector. Panel Mounted Meters for Incoming Circuits 96mm x 96mm dimensions Low profile Fully programmable CT ratios Can be configured single or three phase Device type Outputs Width (mm) Cat. no. 1-phase/3-phase digital 1 pulse 96 CI1-01-PUL kwh meter 1-phase/3-phase digital 1 pulse 96 INT-1630-M-5-M-100 multi-function meter 1-phase/3-phase digital 1 pulse & 96 INT-1630-M-5-M-110 multi-function meter 1 Modbus 1-phase/3-phase digital 1 pulse 96 CI3-01-PUL multi-function meter Optional pulse plug-in CI-PUL-01 module for Ci meter RS485 Modbus plug-in CI-MOD-01 module for Ci meter DIN-rail Mounted Kilowatt Hour Meters for Outgoing Circuits In-built current transformers, direct connection DIN-rail mountable in Loadlimiter 63 service centres Phase cable hole diameter 12.5mm Device type Outputs Width (mm) Cat. no. 1-phase digital kwh meter 1 pulse 54 DRK-1P-230-D63 with integral 63A current transformer 3-phase digital kwh meter 1 pulse 126 DRK-3P-400-D100 with integral 100A current transformers 25

28 Loadlimiter 63 Meters, Current Transformers and Wiring Looms Measuring Current Transformers Up to Class 0.5 accuracy System voltage up to 720V Secondary output of 5A Operating temperature range of 20 C to +70 C Description Max Cable mm 2 Cat. no. 100A 3-in-1 CT case size 35mm 95*/150** M3N /5 125A 3-in-1 CT case size 35mm 95*/150** M3N /5 200A 3-in-1 CT case size 35mm 95*/150** M3N /5 250A 3-in-1 CT case size 35mm 95*/150** M3N /5 Meter spreader box - DBMSB * 95mm 2 using standard cable lugs **150mm 2 using reduced palm width lugs Wiring Looms for TP&N Applications (refer to page 33 for application details) 1A fuse (rated 400V) metering harness Current transformer harness Description For use with Suitable meter Cat. no. distribution boards Wiring loom DBX04R DBX16R Any Crompton DBXW16 for single meter Instruments meter Wiring loom DBX20R DBX24R Any Crompton DBXW24 for single meter Instruments meter Wiring loom for DBX04R DBX16R Any Crompton DBXW16T single meter for Instruments meter top distribution board (vertical stacking) Note: Meters, current transformers and enclosure to be ordered separately. Power Loom for Sub-Metered Distribution Boards (refer to page 33 for application details) 125A and 250A power loom for joining two distribution boards Description Current rating Cat. no. Power loom for sub metered 125A max DBXWP125 distribution board Power loom for sub metered 250A max DBXWP250 distribution board 26

29 Loadlimiter 63 B-type Assembled Boards Range 125A - Horizontal Arrangement with Two Multi-function Meters Two 125A switch disconnectors fitted: One for isolation of whole arrangement One for isolation of lighting circuits only Two meter displays for separate readings of power and lighting consumption All power and control wiring fully tested and fitted Multi-function meter with pulse output for connection to a compatible BMS system Customised assembled boards available No. of power No. of TP Dimensions Cat. no. TP ways lighting ways H x W x D x 968 x 160 DBXC06NAH06CA x 968 x 160 DBXC12NAH12CA 125A - Vertical Arrangement with One Multi-function Meter (Lighting Only) Two 125A switch disconnectors fitted: One for Isolation of whole arrangement One for isolation of lighting circuits only One meter display for readings of lighting consumption only All power and control wiring fully tested and fitted Multi-function meter with pulse output for connection to a compatible BMS system No. of power No. of TP Dimensions Cat. no. TP ways lighting ways H x W x D x 484 x 160 DBXC08NNV06CA x 484 x 160 DBXC12NNV08CA 125A - Vertical Arrangement with Two Meters (kwh or Multi-function) Two 125A switch disconnectors fitted: One for Isolation of whole arrangement One for isolation of lighting circuits only Two meter displays for separate readings of power and lighting consumption All power and control wiring fully tested and fitted Both meters have a pulse output for connection to a compatible BMS system Meter No of power No of TP Dimensions Cat. no. type TP ways lighting ways H x W x D Multi-function x 484 x 160 DBXC06NAV04CA Multi-function x 484 x 160 DBXC08NAV06CA Multi-function x 484 x 160 DBXC12NAV08CA kwh x 484 x 160 DBXC08NJV06CJ kwh x 484 x 160 DBXC12NJV08CJ 250A - Vertical Arrangement with Two Meters (kwh or Multi-function) One 250A switch disconnector fitted providing isolation for whole arrangement Two meter displays for separate readings of power and lighting consumption All power and control wiring fully tested and fitted Both kwh and multi-function meters have a pulse output for connection to a compatible BMS system Meter No. of power No. of TP Dimensions Cat. no. type TP ways lighting ways H x W x D Multi-function x 484 x 160 DBXE08NAV06NA Multi-function x 484 x 160 DBXE12NAV08NA kwh x 484 x 160 DBXE08NJV06NJ kwh x 484 x 160 DBXE12NJV08NJ 250A - Horizontal Arrangement with Two Multi-function Meters One 250A switch disconnector fitted providing isolation for whole arrangement Two meter displays for separate readings of power and lighting consumption All power and control wiring fully tested and fitted Both kwh and multi-function meters have a pulse output for connection to a compatible BMS system No. of power No. of TP Dimensions Cat. no. TP ways lighting ways H x W x D x 968 x 160 DBXE08NAH08NA

30 Loadlimiter 63 Selection Chart - B-type B-type Distribution Boards (without incoming device) Busbar rating TP outgoing ways Height (mm) Weight (kg) Cat. no. 250A DBX04R 250A DBX06R 250A DBX08R 250A DBX12R 250A DBX16R 250A DBX20R 250A DBX24R B-type Incoming YA3 MCCB Enclosure Height (mm) Weight (kg) Cat. no. 3-pole housing DBXYA3 4-pole housing DBXYA3 B-type Service Centres For use with DIN-rail modules Height (mm) Weight (kg) Cat. no. 18 x 1-pole ways (single row) DBS18X 36 x 1-pole ways (double row) DBS36X Cable spreader box DBMSB B-type Distribution Boards (complete with incoming device/s) Busbar rating TP outgoing ways Height (mm) Width (mm) Arrangement Meters Cat. no / Horizontal 2 x MF DBXC06NAH06CA / Horizontal 2 x MF DBXC12NAH12CA 125 8/ Vertical 1 x MF DBXC08NNV06CA / Vertical 1 x MF DBXC12NNV08CA 125 6/ Vertical 2 x MF DBXC06NAV04CA 125 8/ Vertical 2 x MF DBXC08NAV06CA / Vertical 2 x MF DBXC12NAV08CA 125 8/ Vertical 2 x kwh DBXC08NJV06CJ / Vertical 2 x kwh DBXC12NJV08CJ 250 8/ Vertical 2 x MF DBXE08NAV06NA / Vertical 2 x MF DBXE12NAV08NA 250 8/ Vertical 2 x MF DBXE08NJV06NJ / Vertical 2 x MF DBXE12NJV08NJ 250 8/ Horizontal 15 x MF DBXE08NAH08NA Accessories for all B-type Distribution Boards Description Conversion kits plus spares TP&N to SP&N conversion kit Spare end plate RCCB, Contactor, 4-pole switch disconnector connection kit Fixing kit for 24 way distribution boards Blank way label for 24 way distribution boards Blanking pieces MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) MCB blanks (5x 1 2 MCB Ways) Joining kit Mechanical joining kit (For joining two distribution boards vertically) Terminal bars Terminal bar for 6 ways Terminal bar for 12 ways Terminal bar for 18 ways Terminal bar for 24 ways Blanking kits Busbar terminal blanks (set of 10) Earth bar kits Earth bar Earth bar isolation kit Double earth bar facility Earth bar kit with terminal for each outgoing way (where ** = 04, 06, 08, 12, 16, 20 or 24 ways) Door lock kits Cylinder door lock Padlock bracket kit Cat. no. DBXTS DBXEP DBXCKR DBX24FK DBX24WL DBXBP DBXBM DBXBH DBXJK DBXT06 DBXT12 DBXT18 DBXT24 DAXTP DAXEB DBXL DBTE**X DBXCL DBXPL 28

31 Loadlimiter 63 Selection Chart - B-type Incoming Devices Device type Max. cable Sensitivity Incoming device Connection kit (mm 2 ) (ma) cat. no. cat. no. Switch disconnector 100A, 3-pole 50 - AV3100 N/A 100A, 4-pole 50 - AV4100 DBXCKR 125A, 3-pole 50 - AV3125 N/A 125A, 4-pole 50 - AV4125 DBXCKR 250A, 3-pole YA3B3P250D DBXYA3 250A, 4-pole YA3B4P250D DBXYA3 4-pole RCCB 40A, type AC EE40/30/2 DBXCKR 40A, type AC EE40/100/2 DBXCKR 63A, type AC EE63/30/4 DBXCKR 63A, type AC EE63/100/4 DBXCKR 63A, type AC EE63/300/4 DBXCKR 100A, type AC EE100/30/4 DBXCKR 100A, type AC EE100/100/4 DBXCKR 100A, type AC EE100/300/4 DBXCKR Contactor 40A, 4-pole - - EE4P40CO DBXCKR 63A, 4-pole - - EE4P63CO DBXCKR Fuse switch 100A, 3-pole 70 - HBF3P100N DBXLSA1 200A, 3-pole HBF3P200N DBXLSA2 Direct connection Max. cable (mm 2 ) Cat. no. Terminals 35 DBXD0 Terminals 70 DBXD1 Terminals 150 DBXD2 Surge suppression Connection kit for surge suppression 3-phase with neutral/earth surge protection module MOV replacement plug-in SPM MOV neutral/earth replacement plug-in SPM Cat. no. DBXCKR DSPM3PN DSPML DSPMNE Current Transformers Description Cable Height Weight Cat. no. aperture (mm) (mm) (kg) 100A current transformer <1 M3N /5 125A current transformer <1 M3N /5 200A current transformer <1 M3N /5 250A current transformer <1 M3N /5 B-type Metering Device type Outputs Width (mm) Cat. no. 3-phase DIN-rail mounting analogue kwh meter 1 pulse 71 DRK-3PCT phase DIN-rail mounting digital kwh meter 1 pulse 71 DRK-3PCT-415-LCD 1-phase/3-phase DIN-rail mounting digital multi-function meter 1 pulse & 1 Modbus 71 RI phase/3-phase digital kwh meter 1 pulse 96 CI1-01-PUL 1-phase/3-phase digital multi-function meter 1 pulse 96 INT-1630-M-5-M phase/3-phase digital multi-function meter 1 pulse & 1 Modbus 96 INT-1630-M-5-M phase/3-phase digital multi-function meter 1 pulse 96 CI3-01-PUL Optional pulse plug-in module for Ci meter CI-PUL-01 RS485 Modbus plug-in module for Ci meter CI-MOD-01 1-phase DIN-rail mounting digital kwh meter 1 pulse 54 DRK-1P-230-D63 with integral 63A current transformer 3-phase DIN-rail mounting digital kwh meter 1 pulse 126 DRK-3P-400-D100 with integral 100A current transformers 29

32 Loadlimiter 63 Selection Chart - B-type TP&N B, C & D types 10kA/15kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no. 1-pole 1-pole 6 K1PB06 K1PC06 K1PD06 1-pole 10 K1PB10 K1PC10 K1PD10 1-pole 13 K1PB13 K1PC13 N/A 1-pole 16 K1PB16 K1PC16 K1PD16 1-pole 20 K1PB20 K1PC20 K1PD20 1-pole 25 K1PB25 K1PC25 K1PD25 1-pole 32 K1PB32 K1PC32 K1PD32 1-pole 40 K1PB40 K1PC40 T1PD40* 1-pole 50 K1PB50 K1PC50 T1PD50* 1-pole 63 K1PB63 K1PC63 T1PD63* 3-pole 3-pole 6 K3PB06 K3PC06 K3PD06 3-pole 10 K3PB10 K3PC10 K3PD10 3-pole 13 K3PB13 N/A N/A 3-pole 16 K3PB16 K3PC16 K3PD16 3-pole 20 K3PB20 K3PC20 K3PD20 3-pole 25 K3PB25 K3PC25 K3PD25 3-pole 32 K3PB32 K3PC32 K3PD32 3-pole 40 K3PB40 K3PC40 T3PD40* 3-pole 50 K3PB50 K3PC50 T3PD50* 3-pole 63 K3PB63 K3PC63 T3PD63* * 6kA/10kA - EN60898/EN RCBOs 10kA breaking Current Sensitivity B type C type capacity, AC type rating (A) (ma) cat. no. cat. no. 1-pole 6 30 KR1PB0630 KR1PC pole KR1PB1030 KR1PC pole KR1PB1630 KR1PC pole KR1PB2030 KR1PC pole KR1PB3230 KR1PC pole KR1PB4030 KR1PC pole KR1PB4530 KR1PC pole KR1PC pole KR1PC pole KR1PC pole KR1PC pole KR1PC pole KR1PC40100 Accessories for MCBs and RCBOs Auxiliary equipment MCB shunt trip (240V AC) MCB auxiliary/switch contact Padlocking MCB dolly locking device Padlock for dolly locking device Blanking pieces MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) MCB blanks (5x 1 2 MCB ways) Cat. no. KST240 KAUX1 KDL XPL DBXBP DBXBM DBXBH 30

33 Loadlimiter 63 Selection Chart - B-type 2-pole RCCB Description Current rating (A) Function Width (mm) Cat. no. Type AC 40 30mA 35 EE40/30/2 Type AC mA 35 EE40/100/2 Type AC 63 30mA 35 EE63/30/2 Type AC mA 35 EE63/100/2 Type AC mA 35 EE63/300/2 Type AC 80 30mA 35 EE80/30/2 Type AC mA 35 EE100/30/2 Type AC mA 35 EE100/100/2 Type AC time delay mA 35 EES100/100/2 4-pole RCCB Description Current rating (A) Sensitivity Width (mm) Cat. no. Type AC 40 30mA 70 EE40/30/4 Type AC mA 70 EE40/100/4 Type AC 63 30mA 70 EE63/30/4 Type AC mA 70 EE63/100/4 Type AC mA 70 EE63/300/4 Type AC 80 30mA 70 EE80/30/4 Type AC mA 70 EE100/30/4 Type AC mA 70 EE100/100/4 Type AC time delay mA 70 EES100/100/4 Programmable Timer Timer 16A (AC7A) 1 or 2 channel 35 DRT-DW2R Contactor Current Rating (A) Contacts Width (mm) Cat. no. Modular contactor, 20 2P N/O 17.5 EE2P20CO AC1 230V Modular contactor, 20 2P N/C 17.5 EE2P20CC AC1 230V Modular contactor, 25 4P N/O 35 EE4P25CO AC1 400V Modular contactor, 25 4P N/C 35 EE4P25CC AC1 400V Modular contactor, 40 4P N/O 35 EE4P25CC AC1 400V Modular contactor, 40 4P N/C 35 EE4P40CC AC1 400V Modular contactor, 63 4P N/O 54 EE4P63CO AC1 400V Modular contactor, 63 4P N/C 54 EE4P63CC AC1 400V Venting kit 9 LLMV 31

34 Loadlimiter 63 Outline Drawings and Dimensions B-type Distribution Boards (without incoming device) 3-pole ways Drawing Height Weight Cat. no. no. (mm) (kg) DBX04R DBX06R DBX08R DBX12R DBX16R DBX20R DBX24R YA3 Frame MCCB Enclosure for B-type Distribution Boards Incomer Drawing Height Weight Cat. no. no. (mm) (kg) 3-pole MCCB DBXYA3 4-pole MCCB DBXYA3 2 Modular ways Height (mm) Weight (kg) Cat. no x 1-pole ways (single row) DBS18X 36 x 1-pole ways (double row) DBS36X General purpose enclosure DBMSB All dimensions in mm Supplied without top or bottom plate. Intended for use with removable plate from distribution board. 32

35 Loadlimiter 63 Metering Selection Chart Split Metered Power & Lighting Board Select dist board x2 DBX04R DBX06R DBX08R DBX12R DBX16R DBX20R DBX24R Select incomer Single Board Select dist board x1 DBX04R DBX06R DBX08R DBX12R DBX16R DBX20R DBX24R Select incomer 125A 250A 125A Incomer 250A Incomer Switch disconnectors (125A max) AV3125 AV3100 AV4125 AV4100 Switch disconnectors (250A max) Switch disconnectors Switch disconnectors YA3B3P250D YA3B4P250D Or any YA3 MCCB AV3100 AV3125 AV4100 AV4125 YA3B3P250D YA3B4P250D Or Any YA3 MCCB Meter enclosure (125A) Meter enclosure (250A) Spreader box Integral Meter enclosure (250A) DBMSB x1 DBXYA3 x1 Meter enclosure DIN-rail DBXYA3 (125A) mounting kit Power loom (125A) DBXWP125 x1 Power loom (250A) DBXWP250 x1 DBMSB DBXCK ** Cable connection terminals DBXD0 see table 1 Current transformers (125A) M3N /5 M3N /5 Cable connection terminals DBXD0 see table 1 Current transformers (250A) M3N /5 M3N /5 INT-1630-M-5-M-100 CI1-01-PUL RI3-01 Select meter Modbus available CI3-01-PUL Vertical Arrg t Select meter x2 INT-1630-M-5-M-100 (Multi-function) CI3-01-PUL Modbus available CI1-01-PUL Horizontal Arrg t Vertical joining kit Meter enclosure (DB 2) DBXJK DBMSB Select CT x3 Current transformers M3N /5 M3N /5 Select meter wiring loom x1 DBXW16 OR DBXW24 M3N /5 M3N /5 Select meter wiring loom x1 for bottom board DBXW16 OR DBXW24 DBXW16 OR DBXW24 Select meter wiring loom x2 Cable connection terminals DBXD0 see table 2 Select meter wiring loom x1 for top board DBXW16T* ** Meter RI3-01 only Select outgoing devices Select outgoing devices * Top board max size 16 way (vertical arrangement only) Table 1 Table 2 Quantity of AV DBXD0's DBXD0'S DBXCK (switch disconnectors) required (125A) required (250A) required N/A 1 DBXD0 s DBXD0 DBXWP125 required 125A required 250A (125A rated only) Main incomer mounted in DBMSB Main incomer mounted in standard position 33

36 Flow Chart Examples Example 1 Requirement Vertically stacked, 125A split metered power and lighting distribution board 8 way TP&N power board 6 TP&N lighting board Multi-function meters Example 1: Bill of Material List Cat. no. Quantity Description Split metered 125A DBX08R 1 8 way TP&N distribution board DBX06R 1 6 way TP&N distribution board AV A 3P switch disconnector DBMSB 1 Spreader box with facility to mount 2 panel mounted meters DBXJK 1 Mechanical joining kit for joining two vertically stacked distribution boards DBXWP125 1 Power loom for split metered distribution board (125A) INT-1630-M-5-M Phase Integra 1630 multi-function meter with 1 pulse output DBXW16 1 Wiring loom for single meter DBXW16T 1 Wiring loom for single meter for top distribution board when vertically stacked DBXD0 5 Cable joining terminal kit M3N / A 3-in-1 current transformers Example 2 Requirement Single Metered Distribution Board (250A) 24 way TP&N distribution board KWh meter Example 2: Bill of Material List Cat. no. Quantity Description Split metered 250A DBX24R 1 24 way TP&N distribution board YA3B3P250D 1 250A 3P MCCB switch disconnector DBXYA A incoming enclosure with facility to mount 2 panel mounted meters CI1-01-PUL 1 3-phase Kilowatt hour meter with 1 pulse output (panel mounted) DBXW24 1 Wiring loom for single meter DBXD0 1 Cable joining terminal kit M3N / A current transformers Single metered 125A & 250A 34

37 Section 3 MCCB Panel Boards Loadbank 125 Range (250A and 400A Ratings)

38 Overview Key Features ASTA certified busbars with a short circuit rating of 25kA for 1 second (250A) and 25kA for 3 seconds (400A) Shunts, UVRs and auxiliaries are common for YA2, YA3 and YA5 MCCBs Single frame size outgoing MCCBs from 16A to 125A Generous cable-spreading space for incoming and outgoing cables Common width (700mm) and depth (190mm) for all enclosures A single part number identifies the complete main enclosure Available Options 250A panel boards with 6, 8 or 12 triple-pole outgoing ways can choose incoming devices from the YA3 MCCB range or a direct connection 400A panel boards with 6, 8, 12 or 16 triple-pole outgoing ways can choose incoming devices from the YA5 MCCB range or a direct connection Panel build options include: Cable spreader box Service centre with 24 single-pole ways Integra metering housing YA3 frame outgoing housing Featuring busbar ratings of 250A and 400A with seven MCCB panel board designs Loadbank 125 system offers an uncomplicated solution for power distribution in commercial and industrial applications. Outgoing devices consist of a single frame size utilising the Loadline YA2 frame as a cost effective option for circuit protection. New developments include ASTA certified busbars with a short-circuit withstand rating of 25kA-3sec (400A busbars only) and Form 3 separation is now as standard. Available options now include a versatile range of accessories for both incoming and outgoing metering for compliance with Part L2 Building Regulations. A multitude of add-on enclosures, including service centres and a unique outgoing housing for 160A to 250A YA3 frame MCCB matching the dimensional profile of the standard enclosure. The standard finish is epoxy powder coating in light grey RAL Additional Features Neutral and earth terminal for each single-pole way Clean earth facility 250A panels use YA3 MCCBs for incoming devices 400A panels use YA5 MCCBs for incoming devices All versions use YA2 MCCBs for outgoing devices All triple-pole MCCBs have adjustable overload and instantaneous trips Compliance Panel boards EN MCCBs EN

39 MCCB Panel Boards (250A and 400A Rating) MCCB Panel Boards Service centres Metering enclosures Incoming Devices Switch disconnector Moulded case circuit breakers Circuit Protection Devices Moulded case circuit breakers (125A max) Modular Devices Surge protection Meters, current transformers and wiring looms Contactors Timer Earth leakage device 37

40 Loadbank A Panel Board Enclosures Form 3 25kA-1sec 250A Panel Board Enclosures ASTA certified busbars rated 25kA-1sec Form 3 with outgoing terminals shields fitted IP4X protection rating Optional incoming terminal shield available Accepts single frame size YA2 MCCB (Max 125A) outgoing devices No. of TP Incoming device Height Width Depth Cat. no. outgoing ways type (mm) (mm) (mm) 6 YA3 frame PB206YA 8 YA3 frame PB208YA 12 YA3 frame PB212YA 250A Panel Board Accessories Description 3-pole incoming terminal shroud 4-pole incoming terminal shroud Door cylinder lock Door padlock device 3-pole blanking piece 4-pole incoming connection kit Cat. no. YA3TS3P YA3TS4P DBXCL DBXPL LBYA2BP3P PB4PNC A Panel Board Incoming Devices Standard cable termination 95mm 2 Maximum cable termination is 150mm 2 using reduced palm width M8 cable lugs MCCBs have thermal and magnetic overloads except switch disconnector Four-pole incoming devices require adapter kit YA3 cable clamp termination 120mm 2 (sold separately) Incoming Current rating No. of poles Cat. no. device type (A) Switch disconnector YA3B3P250D MCCB YA3N3P160T MCCB YA3N3P200T MCCB YA3N3P250T Switch disconnector YA3B4P250D MCCB YA3N4P160T MCCB YA3N4P200T MCCB YA3N4P250T 250A and 400A Panel Board Accessories Add-on Units Cable spreader box 24 way service centre Housing to accommodate outgoing YA3 MCCB Description Height (mm) Cat. no. Cable spreader box 270 PBYA2CSB Service centre with 24-1 pole ways 270 PBYA2SC24 160A 250A YA3 outgoing housing 450 PBYA2OG 38

41 Loadbank A Panel Board Enclosures Form 3 25kA-3secs 400A Panel Board Enclosures ASTA certified busbars rated 25kA-3secs Form 3 as standard IP4X protection rating Optional incoming terminal shield available Accepts single frame size YA2 MCCB (Max 125A) outgoing devices No. of TP Incoming device Height Width Depth Cat. no. outgoing ways type (mm) (mm) (mm) 6 YA5 frame PB406YA 8 YA5 frame PB408YA 12 YA5 frame PB412YA 16 YA5 frame PB416YA 400A Panel Board Accessories Description Picture number Cat. no. 3-pole incoming terminal shroud 1 YA5TS3P 4-pole incoming terminal shroud YA5TS4P Door cylinder lock 2 DBXCL Door padlock device 3 DBXPL 3-pole blanking piece LBYA2BP3P 4-pole incoming connection kit PB4PNC A Panel Board Incoming Devices Standard cable termination 95mm 2 Maximum cable termination is 185mm 2 using reduced palm width M8 cable lugs MCCBs have thermal and magnetic overloads except switch disconnector Four-pole incoming devices require adapter kit 3 Incoming Current rating No. of poles Cat. no. device type (A) Switch disconnector YA5B3P400D MCCB YA5N3P250T MCCB YA5N3P400T Switch disconnector YA5B4P400D MCCB YA5N4P250T MCCB YA5N4P400T Direct connection 400 3/4 PBYA2DC4 39

42 Loadbank A/400A Surge Protection and Metering Accessories Surge Protection Mounting Kits Easily installed inside panelboard closely located to incoming device DIN-rail mounting for triple-pole MCB C/W 30kA three-phase surge protector Remote status indication Site fault indication Description Height (mm) Cat. no. Surge protection Loadbank 125 mounting kit c/w surge protector and remote indicator 435 PBSM Metering Housing New stackable meter housing for incoming and outgoing metering Designed to fit up to six DIN-rail mounted meters (4 mod max) Can be mounted top or bottom Includes DIN-rail for facility to mount current transformers and fuses Description Height (mm) Weight Cat. no. Meter housing PBYA2MB Four Module DIN-rail Meter Description Digital multi-function meter with 1 pulse and 1 RS485 Modbus ouput Analogue kwh meter with 1 pulse Cat. no. RI3-01 DRK-3PCT-415 Incoming Current Transformers Description Max cable size mm 2 Cat. no. 250A 3-in-1 CT case size M3N /5 400A 3-in-1 CT case size M3N /5 Outgoing Current Transformers Description Max cable size mm 2 Cat. no. 60A 3-in-1 current transformer 50 M3N /5 Case size 25mm 100A 3-in-1 current transformer 50 M3N /5 Case size 25mm 125A 3-in-1 current transformer 50 M3N /5 Case size 25mm Metering Harnesses A collection of meter harnesses for metering incoming and outgoing circuits Please refer to page 44 for easy selection chart Description Incoming meter loom Voltage tap off loom for outgoing metering CT harness for 1 meter Power loom for 6 outgoing meters Cat. no. PBWI PBWP PBWCT PBWM6 40

43 Loadbank A/400A Outgoing Devices and Accessories Outgoing Devices Standard cable termination 35mm 2 Maximum cable termination is 70mm 2 using reduced palm width M8 cable lugs 3-pole MCCBs have thermal and magnetic overloads 1-pole MCCBs have fixed thermal and magnetic overloads Device type Current rating 1-pole cat. no. 3-pole cat. no. (A) (fixed overloads) (adjustable) YA2 frame 16 YA2N1P16T N/A YA2 frame 20 YA2N1P20T YA2N3P20T YA2 frame 32 YA2N1P32T YA2N3P32T YA2 frame 40 YA2N1P40T - YA2 frame 50 YA2N1P50T YA2N3P50T YA2 frame 63 YA2N1P63T YA2N3P63T YA2 frame 80 YA2N1P80T - YA2 frame 100 YA2N1P100T YA2N3P100T YA2 frame 125 YA2N1P125T YA2N3P125T Accessories Description Panel board 3P blanking piece YA3 4-pole MCCB incoming kit YA5 4-pole MCCB incoming kit (pic 2) YA2 cable clamps (1.5-50mm 2 ) YA3 cable clamps (35-120mm 2 ) YA5 cable clamps (95-240mm 2 ) YA2 1-pole terminal shroud YA2 3-pole terminal shroud YA3 1-pole terminal shroud YA3 3-pole terminal shroud (pic 1) YA5 3-pole terminal shroud YA3 4-pole terminal shroud YA5 4-pole terminal shroud Door cylinder lock Door padlock device lock YA2 1-pole dolly lock YA2 3-pole dolly lock Cat. no. LBYA2BP3P PB4PNC250 PB4PNC400 YA2CC3P YA3CC3P YA5CC3P YA2TS1P YA2TS3P YA3TS1P YA3TS3P YA5TS3P YA3TS4P YA5TS4P DBXCL DBXPL Y2DL YADL1 1 Shunt trips YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip 24V DC Under-voltage release YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release 24V DC YAST115AC YAST240AC YAST450AC YAST24DC YAUVR120AC YAUVR240AC YAUVR450AC YAUVR24DC 2 YADL1 fitted without padlock 41

44 Loadbank 125 Selection Chart - Panel Boards 250A Panel Boards Busbar rating ASTA busbar Incoming device Outgoing ways Cat. no. short circuit rating 250A 25kA for 1 second YA3 MCCB/switch disconnector 6 PB206YA 250A 25kA for 1 second YA3 MCCB/switch disconnector 8 PB208YA 250A 25kA for 1 second YA3 MCCB/switch disconnector 12 PB212YA Incoming Devices for 250A Panel Boards Device type Current rating (A) Frame size No. of poles MCCB I cu Cat. no. Switch Disconnector 250 YA3 4 N/A YA3B3P250D MCCB 125 YA3 4 25kA YA3N3P125T MCCB 160 YA3 4 25kA YA3N3P160T MCCB 200 YA3 4 25kA YA3N3P200T MCCB 250 YA3 4 25kA YA3N3P250T Switch Disconnector 250 YA3 4 N/A YA3B4P250D MCCB 125 YA3 4 25kA YA3N4P125T MCCB 160 YA3 4 25kA YA3N4P160T MCCB 200 YA3 4 25kA YA3N4P200T MCCB 250 YA3 4 25kA YA3N4P250T 400A PBYA2DC4 400A Panel Boards Busbar rating ASTA busbar Incoming device Outgoing ways Cat. no. short circuit rating 400A 25kA for 3 seconds YA5 MCCB/switch disconnector 6 PB406YA 400A 25kA for 3 seconds YA5 MCCB/switch disconnector 8 PB408YA 400A 25kA for 3 seconds YA5 MCCB/switch disconnector 12 PB412YA 400A 25kA for 3 seconds YA5 MCCB/switch disconnector 16 PB416YA Incoming Devices for 400A Panel Boards Device type Current rating (A) Frame size No. of poles MCCB I cu Cat. no. Switch Disconnector 400 YA5 3 N/A YA5B3P400D MCCB 250 YA5 3 25kA YA3N3P250T MCCB 400 YA5 3 25kA YA3N3P400T Switch Disconnector 400 YA5 4 N/A YA5B4P400D MCCB 250 YA5 4 25kA YA3N4P250T MCCB 400 YA5 4 25kA YA3N4P400T Auxiliary Units for both 250A & 400A Panel Boards Description Cable spreader box Service centre with 24 1-pole ways YA3 MCCB outgoing housing Cat. no. PBYA2CSB PBYA2SC24 PBYA2OG Surge Protection Mounting Kits for 250A and 400A Panelboards Description Height (mm) Cat. no. Surge protection Loadbank 125 mounting kit c/w surge protector & remote indicator 435 PBSM 42

45 Loadbank 125 Selection Chart - Panel Boards Outgoing Devices for 250A & 400A Panel Boards Device type Current rating (A) Frame size MCCB I cu 1-pole cat. no. 3-pole cat. no. MCCB 16 YA2 25kA YA2N1P16T N/A MCCB 20 YA2 25kA YA2N1P20T YA2N3P20T MCCB 32 YA2 25kA YA2N1P32T YA2N3P32T MCCB 40 YA2 25kA YA2N1P40T N/A MCCB 50 YA2 25kA YA2N1P50T YA2N3P50T MCCB 63 YA2 25kA YA2N1P63T YA2N3P63T MCCB 80 YA2 25kA YA2N1P80T N/A MCCB 100 YA2 25kA YA2N1P100T YA2N3P100T MCCB 125 YA2 25kA YA2N1P125T YA2N3P125T Selection Chart - Accessories Description Panel board 3-pole blanking piece YA3 4-pole MCCB kit YA5 4-pole MCCB kit YA2 cable clamps (1.5-50mm 2 ) YA3 cable clamps (35-120mm 2 ) YA5 cable clamps (95-240mm 2 ) YA2 1-pole terminal shroud YA2 3-pole terminal shroud YA3 1-pole terminal shroud YA3 3-pole terminal shroud YA5 3-pole terminal shroud 70mm 2 outgoing cable clamps for neutral earth YA3 4-pole terminal shroud YA5 4-pole terminal shroud Door cylinder lock Door padlock device lock YA2 1-pole dolly locking device YA2 3-pole dolly locking device Shunt trips YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip 24V DC Under-voltage release YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release 24V DC Cat. no. LBYA2BP3P PB4PNC250 PB4PNC400 YA2CC3P YA3CC3P YA5CC3P YA2TS1P YA2TS3P YA3TS1P YA3TS3P YA5TS3P PBYA2NA YA3TS4P YA5TS4P DBXCL DBXPL Y2DL YADL1 YAST115AC YAST240AC YAST450AC YAST24DC YAUVR120AC YAUVR240AC YAUVR450AC YAUVR24DC Metering Accessories Description Metering enclosure for upto 6 meters Incoming meter loom Voltage tap off loom CT harness for 1 meter Power loom for 6 outgoing meters 250A 3-in-1 CT case size 3 400A 3-in-1 CT case size 3 60A 3-in-1 current transformer case size 25mm 100A 3-in-1 current transformer case size 25mm 125A 3-in-1 current transformer case size 25mm Digital multi-function meter with 1 pulse and 1 RS485 Modbus ouput Analogue kwh meter with 1 pulse output Cat. no. PBYA2MB PBWI PBWP PBWCT PBWM6 M3N /5 M3N /5 M3N /5 M3N /5 M3N /5 RI3-01 DRK-3PCT

46 Loadbank 125 Meter Selection Process Loadbank 125 MCCB Panel Board System The Loadbank 125 metering facilities consist of DIN-rail mounted meters used within a housing which can fit up to 6 meters of four modules. The meter housing can be stacked top or bottom with facility to mount current transformers and fuses. We recommend that for applications with more than 6 outgoing meters the Loadbank 250 system with metering accessories should be used. For applications which require single phase metering please contact the sales office. Panel Board PB206YA PB208YA PB212YA PB406YA PB408YA PB412YA PB416YA Panel-board enclosures Description Cat. no. 250A, 6 TP way PB206YA 250A, 8 TP way PB208YA 250A, 12 way PB212YA 400A, 6 way PB406YA 400A, 8 way PB408YA 400A, 12 way PB412YA 400A, 16 way PB416YA Description Meter housing for up to 6 meters Cat. no. PBYA2MB Meter Box Outgoing: PBYA2MB Incoming: PBYA2MB Outgoing: PBYA2MB Incoming: PBYA2MB Description Cat. no. Incoming meter loom Voltage tap off loom for outgoing metering CT harness for 6 outgoing meters Power loom for 6 outgoing meters PBWI PBWP PBWCT PBWM6 Power Tap Off Harness PBWP 1 Off Description Digital Multi-function meter with 1 pulse output and 1 Modbus output Analogue kilowatt hour meter with one pulse output Cat. no. RI3-01 DRK-3PCT-415 Incomer Harness Outgoing Meter Arrangement Incoming Meter Arrangement PBWI 1 Off Description 3-in-1 60A current transformers 3-in-1 100A current transformers 3-in-1 125A current transformers 3-in-1 200A current transformers 3-in-1 250A current transformers 3-in-1 400A current transformers Cat. no. M3N /5 M3N /5 M3N /5 M3N /5 M3N /5 M3N /5 Meter Power Harness Meters Up to 6 Meters: PBWM6 1 Off Above 6 Meters: PBWM6 2 Off DRK-3PCT-415 Ri3-01 DRK-3PCT-415 Ri3-01 CT Harness PBWCT 1 per Meter Current Transformers M3N /5 M3N /5 M3N /5 M3N /5 M3N /5 M3N /5 44 For single phase metering use: 1 CT per phase INT-1630-M-5-M-100 Integra meter only

47 Section 4 Fuse Switch Panel Boards Loadbank 200 Range (800A Rating)

48 Overview Key Features ASTA certified short circuit withstand rating Allows inclusion of TP&N and four-pole fuse switch distribution Generous cable-spreading space for incoming and outgoing cables Common width (750mm) and depth (200mm) for all enclosures Available Options 800A panel boards with 6 or 10 outgoing fuse switch ways 400A, 630A or 800A fuse switch incomers Panel build options include: SP&N MCB distribution board for 17 ways TP&N distribution board with 6 and 12 ways TP&N distribution board with double banks of 12 ways General purpose enclosures with uncut front plates Metering housings and service centres Current transformers Based on the modular system employed within Loadbank 250 panel board, Loadbank 200 panel board is designed to fulfil the need for fuse switch panelboards upto 800A. Panel board enclosures are available in either 6 or 10 TP&N outgoing ways featuring devices from 63A to 200A. Form 2 separation is provided as standard, with Form 4 shielding as an available option. Several incoming options can be selected from 200A to 800A and a comprehensive range of metering facilities for compliance with Building Regulations Part L2 completes this versatile panel board system. The standard finish is epoxy powder coating in light grey RAL Additional Features Add-on incomer units include all copper connections and incoming cable shrouds Panel and distribution boards exceed EN requirements Fully shielded busbars and interconnections on distribution boards Various locking options IP4X Ingress Protection Compliance Switch fuse panel boards EN Skeleton switches EN

49 Fuse Switch Panel Board System (800A) Fuse Switch Panel Boards General purpose enclosures Cableway extention enclosures Stacking kits Incoming Devices Fuse switches (200A-800A) Circuit Protection Devices Fuse switches (63A-200A) Modular Devices Surge protection Meters, current transformers and wiring looms Contactors Timer Residual current circuit breaker 47

50 Loadbank 200 Fuse Switch Panel Board System Form 2 and 4 50kA-1sec 800A Panel Board Enclosures Form 2 as standard Form 4 with optional shielding IP3X (IP4X with door kit fitted) Ingress Protection 750mm wide x 200mm deep Integral incoming option available using 200A fuse switch in available outgoing way No of TP Modular Height Weight Cat. no. Optional outgoing ways height (mm) (kg) door kit LF806A MXD LF810A MXD10 Fuse Switch Panel Board Accessories Description Form 4 shielding for cable up to 70mm 2 (1 per device required) Form 4 shielding for outgoing cables to 150mm 2 (1 per device required) Vertical stacking connection kit Blank cover for fuse switch handle Cat. no. LFS41A LFS42A LCFVK LFXHBA Add-on Incoming Enclosures Excludes incoming device (to be ordered separately) Supplied with all necessary copper connections Incoming terminations fully shrouded Supplied with two side plates only IP4X Ingress Protection Current Modular Height Weight Device type Cat. no. rating height (mm) (kg) (A) L frame fuse switch LF1F4A 630/ N frame fuse switch LF1F8A 400A Fuse Switch Incoming Devices 400A incoming devices for LF1F4A enclosure Standard cable termination 300mm 2 Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Incoming Current No. of poles Max cable Cat. no. device type rating (A) termination (mm 2 ) L frame fuse switch 400 TP&N 300 SL3P400N L frame fuse switch SL4P A/800A Fuse Switch Incoming Devices 630A/800A incoming devices for LF1F8A enclosure Standard cable termination 630mm 2 Incoming Current No. of Max cable Cat. no. Cable device type rating poles termination terminals (A) (mm 2 ) N frame fuse switch 630 TP&N 630 SN3P630N SNCET N frame fuse switch 800 TP&N 630 SN3P800N SNCET N frame fuse switch SN4P630 SNCET N frame fuse switch SN4P800 SNCET 48

51 Loadbank 200 Outgoing Devices 63/125A Skeleton Switches Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Current rating (A) 1-pole+N cat. no. 3-pole+N cat. no. 4-pole cat. no SF3P63N SF4P SF3P100N SF4P SF3P125N SF4P /200A Skeleton Switches Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Current rating (A) 1-pole+N cat. no. 3-pole+N cat. no. 4-pole cat. no SF3P160N SF4P SF3P200N SF4P200 Loadbank 200 Outgoing Devices Accessories Accessories for Outgoing/Incoming Skeleton Switches Description Current rating (A) Picture Cat. no. 1 Solid links (set of 1) 63 1 HFL63 Solid links (set of 1) 100/200 1 HFL200A 2-bank auxiliary switch 63/200 2 SAUX2F 4-bank auxiliary switch 63/200 2 SAUX4F Terminal shrouds and barriers 63/200 SFTSS Terminal barriers (set of 3) 63/200 SFTB Cable extension terminals 630/800 SNCET (set of 8) Solid links (set of 1) HLL400 Solid links (set of 1) 630/800 1 HNL bank auxiliary switch 400/630/800 2 SAUX2N 4-bank auxiliary switch 400/630/800 2 SAUX4N 6-bank auxiliary switch 400/630/800 2 SAUX6N Terminal shrouds and barriers 400 SLTS Terminal shrouds and barriers 630/800 SNTS Terminal barriers (set of 3) 400 SLTB Terminal barriers (set of 3) 630/800 Supplied 49

52 Loadbank 200 Add-on Enclosures General Purpose Enclosures IP4X Ingress Protection Enclosures are 750mm wide x 200 deep No top or bottom plates supplied (supplied with panel board) Description Modular height Height (mm) Cat. no. General purpose enclosure LEBM1 General purpose enclosure LEBM2 General purpose enclosure LEBM3 General purpose enclosure LEBM4 General purpose enclosure LEBM5 General purpose enclosure LEBM6 Cableway Extension Enclosures IP4X Ingress Protection Recommend for cables above 70mm 2 250mm wide x 200mm deep No side plates supplied (supplied with panel board) Description Modular height Height (mm) Cat. no. Cableway LECM1 Cableway LECM2 Cableway LECM3 Cableway LECM4 Cableway LECM5 Cableway LECM6 Cableway LECM8 MCB Distribution Board and Service Centre IP3X (IP4X with door fitted) Ingress Protection MCB distribution boards have fully shielded busbars and interconnections Space saving twin option TP&N distribution board option Description Modular Height Cat. no. Door kit height (mm) cat. no. 17 MCB way SP&N distribution board LDS17 LD1DS 6 TP way TP&N distribution board LDT106X LD1D06X 12 TP way TP&N distribution board LDT112X LD1D12X 2 x 12 TP way TP&N distribution board LDT212X* LD2D12X 24 way modular service centre LDS24 LD1DS *Only double module RCBOs can be fitted in this enclosure. 1 Transient Voltage Surge Protector Cableway Mounting Kits Easily installed within a standard cableway (2 modules onward) DIN-rail mounting for triple-pole MCB C/W 30Ka three-phase surge protector Remote status indication Site fault indication Description Height (mm) Cat. no. 2 Cableway mounting frame c/w surge protector & remote indicator (1) 304 LECK2SM 2 module enclosure c/w surge protector & remote indicator (2) 304 LECK2SP 50

53 Loadbank 200 Metering Accessories For easy selection of metering please refer to the charts on pages 56. Cableway Metering Door Kits Incoming and outgoing metering utilises cableway extension boxes Metering door kits are available sized to the cableway extension boxes and are designed for panel mounted meters Includes DIN-rail for facility to mount current transformers and fuses Description Height Cat. no. 2 module metering door kit, excluding CTs and control wiring 2 LECMD2 3 module metering door kit, excluding CTs and control wiring 3 LECMD3 4 module metering door kit, excluding CTs and control wiring 4 LECMD4 5 module metering door kit, excluding CTs and control wiring 5 LECMD5 6 module metering door kit, excluding CTs and control wiring 6 LECMD6 8 module metering door kit, excluding CTs and control wiring 8 LECMD8 Metering Description Digital multi-function meter with one pulse output Digital multi-function meter with one pulse output and one RS485 output Digital kilowatt hour meter with pulse output Digital multi-function meter with pulse output Pulse Output for Ci meter RS485 Modbus Output for Ci meter Cat. no. INT-1630-M-5-M-100 INT-1630-M-5-M-110 CI1-01-PUL CI3-01-PUL CI-PUL-01 CI-MOD-01 Incoming Current Transformers Description Max cable size mm 2 Cat. no. 400A current transformer (sold singular) 185*/240** M63N-400/5 600A current transformer (sold singular) 185*/240** M63N-600/5 800A current transformer (sold singular) 240 M93L-800/5 Outgoing Current Transformers Description Max cable size mm 2 Cat. no. 100A 3-in-1 CT Case size 35mm 95*/150** M3N /5 125A 3-in-1 CT Case size 35mm 95*/150** M3N /5 200A 3-in-1 CT Case size 35mm 95*/150** M3N /5 250A 3-in-1 CT Case size 35mm 95*/150** M3N /5 *Using standard lugs **Using reduced palm width lugs Metering Harnesses Description Incoming meter loom Voltage tap off loom for outgoing metering CT harness for 1 outgoing meters Power loom for 6 outgoing meters Cat. no. LBWI LBWP LBWCT LBWM6 51

54 Loadbank 200 Selection Chart - Enclosures 800A Panel Boards - Form 2 Outgoing device Outgoing ways Height (mm) Weight (kg) Cat. no. Fuse switch 6 5 modules 59 LF806A Fuse switch 10 8 modules 98 LF810A 800A Panel Boards - Form 4 Conversion Form 4 shields for outgoing cables up to 70mm 2 Form 4 shields for outgoing cables up to 150mm 2 Vertical connection kit for 800A panelboard Blank cover plate for fuse switch handle Cat. no. LFS41A LFS42A LCFVK LFXHBA Incoming Units Device type Current Height Weight (kg) Cat. no. housing rating (A) Fuse switch modules 48.5 LF1F4A Fuse switch 630/800 6 modules 66.5 LF1F8A Cableways Height Weight (kg) Cat. no. 1 module 2 LECM1 2 modules 4 LECM2 3 modules 6 LECM3 4 modules 8 LECM4 5 modules 8 LECM5 6 modules 12 LECM6 8 modules 14 LECM8 Surge Protection Cableway Mounting Kits Description Height (mm) Cat. no. Cableway mounting frame c/w surge protector & remote indicator 304 LECK2SM 2 module enclosure c/w surge protector & remote indicator 304 LECK2SP General Purpose Enclosures Height Weight (kg) Cat. no. 1 module 4 LEBM1 2 modules 10 LEBM2 3 modules 16 LEBM3 4 modules 22 LEBM4 5 modules 28 LEBM5 6 modules 34 LEBM6 Service Centres Type Outgoing ways Height Weight (kg) Cat. no. Door kit Service centre (DIN units) 24 DIN 1 module 10 LDS24 LD1DS MCB Distribution Boards SP&N Outgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no module 15 LDS17 LD1DS TP&N Outgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no. 6 2 modules 23 LDT106X LD1D06X 12 3 modules 30 LDT112X LD1D12X 2x12 4 modules 35 LDT212X LD2D12X 52

55 Loadbank 200 Selection Chart - Incoming Devices and Accessories Loadbank 200 Incoming Devices Fuse Switches Device type Current rating (A) 3-pole+N cat. no. 4-pole cat. no. Skeleton switch 200 SF3P200N SF4P200 Skeleton switch 400 SL3P400N SL4P400 Skeleton switch 630 SN3P630N SN4P630 Skeleton switch 800 SN3P800N SN4P800 Accessories for Incoming Skeleton Switches Description Current rating (A) Picture Cat. no. Cable extension terminals (set of 8) 630/800 SNCET Solid links (set of 1) HLL400 Solid links (set of 1) 630/800 1 HNL800 2-bank auxiliary switch 400/630/800 2 SAUX2N 4-bank auxiliary switch 400/630/800 2 SAUX4N 6-bank auxiliary switch 400/630/800 2 SAUX6N Terminal shrouds and barriers 400 SLTS Terminal shrouds and barriers 630/800 SNTS Terminal barriers (set of 3) 400 SLTB Terminal barriers (set of 3) 630/800 Supplied Metering Description Height Height Current rating Cable size Cat. no. (modules) (mm) (A) (mm) Metering door kit LECMD2 Metering door kit LECMD3 Metering door kit LECMD4 Metering door kit LECMD5 Metering door kit LECMD6 Metering door kit LECMD8 Incoming meter loom LBWI Voltage tap off for outgoing meter LBWP CT harness for 1 outgoing meter LBWCT Meter power loom for 1 outgoing meter LBWM6 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 Current transformer M63N-400/5 Current transformer M63N-600/5 Current transformer M93L-800/5 1-phase/3phase kwh meter with pulse CI1-01-PUL 1-phase/3phase MF meter with pulse INT-1630-M-5-M phase/3phase MF meter with pulse and Modbus INT-1630-M-5-M phase/3phase MF meter with pulse CI3-01-PUL Optional pulse plug in module for Ci meter CI-PUL-01 Optional RS485 Modbus plug in module CI-MOD-01 for Ci meter 53

56 Loadbank 200 Selection Chart - Outgoing Fuse Switches and Accessories 800A Panelboard Description Vertical connection kit Blank cover plate for fuse switch handle Cat. no. LCFVK LFXHBA Main Enclosures - Insulation & Plates Horizontal insulation kit Steel end plate MXEPF LGES Door Locking Door lock/key kit Padlocking kit for door kits DBXCL DBXPL Outgoing Fuse Switches Device Current rating (A) 1-pole+N cat.no. 3-pole+N cat. no. 4-pole cat. no. Skeleton switch 63 - SF3P63N SF4P63 Skeleton switch 100 SF1P100N SF3P100N SF4P100 Skeleton switch SF3P125N SF4P125 Skeleton switch SF3P160N SF4P160 Skeleton switch SF3P200N SF4P200 Accessories Description Current rating (A) Cat. no. Solid links (set of 1) 63 HFL63 Solid links (set of 1) 100/200 HFL200A 2-bank auxiliary switch 63/200 SAUX2F 4-bank auxiliary switch 63/200 SAUX4F Terminal shrouds and barriers 63/200 SFTSS Terminal barriers (set of 3) 63/200 SFTB 54

57 Loadbank 200 Dimensions and Outline Drawings LF810A 8 modules LF806A 5 modules LF1F8A 6 modules LF1F4A 5 modules 200mm 10/6 Outgoing Ways 200A Max. 98kg 59kg 630A/800A Switch 66.5kg* 400A Switch 48.5kg* LEBM6 6 modules LEBM5 5 modules LEBM4 4 modules LEBM3 3 modules LEBM2 2 modules LEBM1 1 module 200mm 34kg 28kg 22kg 16kg 10kg 4kg LECM8 8 modules LECM6 6 LECM5 5 LECM4 4 LECM3 3 LECM2 2 LECM1 1 Standard Cableways 14kg 12kg 10kg 8kg 6kg 4kg 2kg Cableway 250mm Main Enclosure 750mm 8 Module Height-1219mm 6 Module Height-914mm 5 Module Height-762mm 4 Module Height-609mm 3 Module Height-457mm 2 Module Height-304mm 1 Module Height-152mm Depth of all enclosures 200mm 55

58 Loadbank 200 Metering Selection Loadbank 200 The Loadbank 200 metering facilities utilise standard cableway extension enclosures with optional door kits designed for panel mounted meters. The size of the cableway will determine the corresponding metering door kit. Where cable sizes exceed 70mm a recommendation would be to include two cableway extension enclosures to facilitate easy wiring. The same could be advised when fully populating an 18 way panel board with meters. Current transformers and fuses can be DINrail mounted within the cableways using the facilities provided within the optional door kits. Panel-board enclosures Description Cat. no. 800A, 6 way, Form 4 LF806A 800A, 10 way, Form 4 LF806A Cableway Door LF806A LF810A LF806A:-LECMD5 x 2 LF810A:-LECMD8 x 2 LF1F4A:-LECMD5 x 1 LF1F8A:-LECMD6 x 1 Left Side Outgoing Meter Arrangement Right Side Outgoing Meter Arrangement Incoming Meter Arrangement Description Cat. no. 2 module metering mounting kit, (2 meter positions) LECMD2 3 module metering mounting kit, (3 meter positions) LECMD3 4 module metering mounting kit, (4 meter positions) LECMD4 5 module metering mounting kit, (6 meter positions) LECMD5 6 module metering mounting kit, (6 meter positions) LECMD6 8 module metering mounting kit, (9 meter positions) LECMD8 Description Cat. no. LBWP 1 Off Up to 6 Meters: LBWM6 1 Off Above 6 Meters: LBWM6 2 Off LBWP 1 Off Up to 6 Meters: LBWM6 1 Off Above 6 Meters: LBWM6 2 Off LBWP 1 Off LBWI 1 Off 3-in-1 100A current transformers 3-in-1 125A current transformers 3-in-1 200A current transformers 3-in-1 250A current transformers 400A current transformer (sold singular) 630A current transformer (sold singular) 800A current transformer (sold singular) Description Digital multi-function meter with one pulse outputs Digital multi-function meter with one pulse output and one RS485 output Digital kilowatt hour meter with one pulse output Digital multi-function meter with one pulse output M3N /5 M3N /5 M3N /5 M3N /5 M63N-400/5D M63N-600/5D M93L-800/5D Cat. no. INT-1630-M-5-M-100 INT-1630-M-5-M-110 CI1-01-PUL CI3-01-PUL CI1-01-PUL CI3-01-PUL INT-1630-M-5-M-*** LBWCT 1 per Meter M3N /5 M3N /5 M3N /5 M3N /5 CI1-01-PUL CI3-01-PUL INT-1630-M-5-M-*** LBWCT 1 per Meter M3N /5 M3N /5 M3N /5 M3N /5 CI3-01 CI1-01 INT-1630-M-5-M-*** M53J-200/5D 3 per Meter M53J-250/5D 3 per Meter M63N-400/5D 3 per Meter M63N-600/5D 3 per Meter M63N-800/5D 3 per Meter M93L-600/5D 3 per Meter M93L-800/5D 3 per Meter 56

59 Section 5 MCCB Panel Boards Loadbank 250 Range (400A and 800A Ratings)

60 Overview Key Features ASTA certified busbars with a short-circuit withstand rating of 36kA for 1 second (400A) ASTA certified busbars with a short-circuit rating of 50kA for 1 second (800A) Allows mounting of YA3, Y5, Y6 or Y7 MCCBs and switch disconnectors Single frame size for outgoing 16A to 250A MCCBs Generous cable-spreading space for incoming and outgoing cables Common width (750mm) and depth (200mm) for all enclosures Available Options 400A and 800A panel boards with 6, 12 or 18 triple-pole outgoing ways with Y6/Y7 or YA3 incoming devices, with Form 3 separation 800A panel boards with 6 or 10 TP&N or four-pole outgoing ways with fuse switch/mccb incomer, with Form 4 separation Panel build options include: Range of MCB distribution boards General purpose enclosures with uncut front plates Metering housings and service centres Current transformers Cableway enclosures Loadbank 250 modular enclosure system is engineered to provide unrivalled flexibility and build simplicity needed to produce a wide range of power distribution solutions. TP&N busbars of 400A and 800A comprising of three sizes of 6, 12, 18 TP outgoing ways allow installers to cover a multitude of commercial and industrial applications. Featuring circuit breakers from 16A to 400A to be fitted as outgoing circuits, integral MCB distribution boards, contactors, timers complemented by a new range of incoming and outgoing metering facilities completes the Loadbank 250 panel board range. Loadbank 250 panel boards house the incomer and outgoing units in separate, adjoining enclosures to allow the widest range of possible circuit permutations, including oversized outgoing circuits, to be accommodated within a common format. The standard finish is epoxy powder coating in light grey RAL Loadbank 250 single module is 152mm high. Compliance Panel boards EN MCCBs EN MCBs EN RCCBs EN RCBOs EN Skeleton Switches

61 MCCB Panel Boards (400A and 800A Rating) MCCB Panel Boards Service centres Cableway extension chambers General purpose enclosures TP&N distribution boards Incoming Devices Switch disconnector Moulded case circuit breakers Fuse combination units Circuit Protection Devices Moulded case circuit breakers (upto 250A or 400A max) Modular Devices Surge protection Meters, current transformers and wiring looms Contactors Timer Earth leakage device 59

62 Loadbank A/400A Panel Board Form 3 36kA-1sec 400A Panel Board Enclosures Form 3 as standard Incoming enclosures and devices to be ordered separately ASTA certified busbars rated at 36kA-1sec No of TP Modular Height Width Depth Cat. no. Door kit outgoing ways height (mm) (mm) (mm) cat. no LB406YA3 LBDD LB412YA3 LBDD LB418YA3 LBDD18 400A Panel Board Accessories Fitted with incoming housing and metering Description Door cylinder lock Door padlock device 3-pole blanking piece Steel end plate Panel board stacking kit Busbar extension terminals with shields to connect to top of panel board 250A/400A Add-on Incoming Enclosures Supplied with all necessary connections Incoming devices to be ordered separately Cat. no. DBXCL DBXPL LBBP3PYA3 LGES LBCK4 LBSKE Current rating Device type Modular Height Cat. Neutral height (mm) no. link 250 YA3 MCCB LB1YA3 YA3NL 400 Y6 MCCB LB1Y6 Standard 400 Direct connection LBDR4 Standard 200 F frame fuse switch LB1F2A Standard 400 L frame fuse switch LB1F4A Standard 250A Max Incoming Devices Up to 250A Incoming devices for LB1YA3 Standard cable termination 95mm 2 Maximum cable termination is 150mm 2 using reduced palm width M8 cable lugs MCCBs have thermal and magnetic overloads except switch disconnector Incoming device type Current rating (A) No. of poles Cat. no. Switch disconnector YA3B3P250D MCCB YA3N3P160T MCCB YA3N3P200T MCCB YA3N3P250T Switch disconnector YA3B4P250D MCCB YA3N4P160T MCCB YA3N4P200T MCCB YA3N4P250T 400A Incoming Devices 400A Incoming devices for LB1Y6 Standard cable termination 240mm 2 Incoming device type Current rating (A) No. of poles Cat. no. Switch disconnector Y6B3P400D MCCB Y6H3P400T5 Switch disconnector Y6B4P400D MCCB Y6H4P400T5 200/400 Fuse Switch Devices 200A Incoming devices for LB1F2A 400A Incoming devices for LB1F4A 60 Incoming device type Current rating (A) No. of poles Cat. no. F frame fuse switch ex fuses 200A 3 SF3P200N F frame fuse switch ex fuses 200A 4 SF4P200 L frame fuse switch ex fuses 400A 3 SL3P400N L frame fuse switch ex fuses 400A 4 SL4P400

63 Loadbank A Panel Board Form 3 50kA-1sec 800A Panel Board Enclosures Form 3 as standard Incoming enclosures and devices to be ordered separately ASTA certified busbars rated at 50kA-1sec No of TP Modular Height Width Depth Cat. no. Door kit outgoing ways height (mm) (mm) (mm) (mm) cat. no LB806YA3 LBDD LB812YA3 LBDD LB818YA3 LBDD18 800A Panel Board Accessories Description Door cylinder lock Door padlock device 3-pole blanking piece Panel board stacking kit Busbar extension terminals with shields to connect to top of panel board Steel end plate Horizontal insulation kit Cat. no. DBXCL DBXPL LBBP3PYA3 LBCK8 LBSKE LGES MXEPF 400A/800A Add-on Incoming Enclosures Supplied with all necessary connections Incoming devices to be order separately Current rating Device type Modular Height Cat. no. Neutral height (mm) link 800A Panel boards 400/630A Y6 MCCB LB1Y6 Standard 800A Direct connection LBDR8 Standard 800A Y7 MCCB LB1Y7 Standard 630A Incoming Devices 630A Incoming devices for LB1Y6 Standard cable termination 240mm 2 Upto 250A or 400A Incoming Current rating No. of poles Cat. no. device type (A) Switch disconnector Y6B3P630D MCCB Y6H3P630T5 Switch disconnector Y6B4P630D MCCB Y6H4P630T5 800A Incoming Devices 800A Incoming devices for LB1Y7 Standard cable termination 300mm 2 LB1Y7 Neutral link supplied Incoming Current rating No. of poles Cat. no. device type (A) Switch disconnector Y7B3P800D MCCB Y7J3P1000E* Switch disconnector Y7B4P800D MCCB Y7J4P1000E* * MCCB must be set for 800A maximum. 61

64 Loadbank A and 800A, Form 3 Outgoing Devices and Accessories Outgoing YA3 MCCB Devices Standard cable termination 95mm 2 Maximum cable termination is 150mm 2 using reduced palm width M8 cable lugs Triple-pole MCCBs have thermal and magnetic overloads Single-pole MCCBs have fixed thermal and magnetic overloads Device Current 1-pole 3-pole, 25kA 3-pole, 36kA 3-pole, 65kA type rating cat. no. cat. no. cat. no. cat. no. (A) (fixed (adjustable (adjustable (adjustable overloads) overloads) overloads) overloads) YA3 frame 16 YA3N1P16T YA3 frame 20 YA3N1P20T YA3N3P20T YA3S3P20T YA3J3P20T YA3 frame 32 YA3N1P32T YA3N3P32T YA3S3P32T YA3J3P32T YA3 frame 40 YA3N1P40T YA3 frame 50 YA3N1P50T YA3N3P50T YA3S3P50T YA3J3P50T YA3 frame 63 YA3N1P63T YA3N3P63T YA3S3P63T YA3J3P63T YA3 frame 80 YA3N1P80T YA3 frame 100 YA3N1P100T YA3N3P100T YA3S3P100T YA3J3P100T YA3 frame 125 YA3N1P125T YA3N3P125T YA3S3P125T YA3J3P125T YA3 frame 160 YA3N1P125T YA3N3P160T YA3S3P160T YA3J3P160T YA3 frame YA3N3P200T YA3S3P200T YA3J3P200T YA3 frame YA3N3P250T YA3S3P250T YA3J3P250T Outgoing YA5 MCCB Devices Standard cable termination 95mm 2 Maximum cable termination 185mm 2 using reduced palm width M8 cable lugs MCCBs have adjustable overloads For use with LB802YA5 (twin YA5 outgoing housing - page 66) Device type Current rating (A) 25kA cat. no. 50kA cat. no. YA5 Frame 160A-250A YA5N3P250T YA5H3P250T YA5 Frame 250A-400A YA5N3P400T YA5H3P400T YA3 and YA5 MCCB Accessories Description Cat. no. YA3 3P cable clamps (35-120mm 2 ) YA3CC3P YA3 4P cable clamps (35-120mm 2 ) YA3CC4P YA5 3P cable clamps (95-240mm 2 ) YA5CC3P YA5 4P cable clamps (95-240mm 2 ) YA5CC4P Dolly locking device YADL V AC shunt trip YAST115AC V AC shunt trip YAST240AC V AC shunt trip YAST450AC 24V DC shunt trip YAST24DC V AC under-voltage release YAUVR120AC V AC under-voltage release YAUVR240AC V AC under-voltage release YAUVR450AC 24V DC under-voltage release YAUVR24DC YA3 3P terminal shield YA3TS3P YA3 4P terminal shield YA3TS4P YA5 3P terminal shield YA5TS3P YA5 4P terminal shield YA5TS4P 62

65 Loadbank A Form 4 MCCB Panel Board The Form 4 panel board range features a 800A TP&N four-pole busbar assembly comprises of two stackable designs of 6 and 10 TP&N ways. Three incoming enclosures are available with MCCB or fuse switch incoming options offering a cost effective, off the shelf solution for projects which require Form 4 separation. A comprehensive range of general purpose add-on units and cableways with metering options complete this versatile range. Features Exceeds EN ASTA certified busbars with a short-circuit withstand rating of 50kA-1sec Form 3 as standard Form 4 with Form 4 shielding fitted IP4X Ingress Protection Single frame size outgoing triple-pole MCCBs from 16A-250A Common width (750mm) and depth (200mm) for all enclosures Fully rated neutrals Does not accept 1-pole outgoing devices 63

66 Loadbank A Panel Board Form 4 50kA-1sec 800A Panel Boards - Form 4 No provision for 1-pole MCCBs Form 3 as standard Form 4 with optional shielding IP3X (IP4X with door kit fitted) Ingress Protection 750mm wide x 200mm deep Spare busbar terminal covers/blanking plates are to be ordered separately No of TP Modular Height Weight Cat. no. Optional outgoing ways height (mm) (kg) door kit LF806YA MXD LF810YA MXD10 800A Panel Board Accessories Description Form 4 shielding for cable up to 70mm 2 Form 4 shielding for outgoing cables to 150mm 2 Vertical stacking connection kit Blanking plate for unused way Cat. no. LFS41YA LFS42YA LCFVK YA3F4BP Add-on Incoming Enclosures Form 4 as standard IP4X Ingress Protection Current Modular Height Weight Device Cat. no. Connection rating height (mm) (kg) type kit required (A) L frame fuse LF1F4A - switch 630/ N frame fuse LF1F8A - switch Y6 MCCB/ MMS15Y* MCFMY6 MCCB switch disconnector *Neutral link supplied 400A Fuse Switch Incoming Devices 400A Incoming devices for LF1F4A enclosure Standard cable termination 240mm 2 Incoming device type Current rating (A) No. of poles Cat. no. L frame fuse switch 400 TP&N SL3P400N L frame fuse switch SL4P400N 64

67 Loadbank A Panel Board Incoming and Outgoing Devices 630A/800A Fuse Switch Incoming Devices 630A/800A Incoming devices for LF1F8A enclosure Standard cable termination 630mm 2 Incoming Current No. of Max cable Cat. no. Cable device type rating poles termination terminals (A) (mm 2 ) N frame fuse switch 630 TP&N 630 SN3P630N SNCET N frame fuse switch 800 TP&N 630 SN3P800N SNCET N frame fuse switch SN4P630N SNCET N frame fuse switch SN4P800N SNCET Incoming MCCB Devices 400A-800A Incoming devices for MMS15Y enclosure Standard cable termination 240mm 2 Triple-pole and four-pole MCCBs have adjustable thermal and magnetic overloads Incoming Current No. of Max cable Cat. no. device type rating (A) poles termination (mm 2 ) Y6 frame switch disconnector Y6B3P400D Y6 frame MCCB Y6H3P400T5 Y6 frame MCCB Y6H3P630T5 Y6 frame MCCB Y6H3P800T5 Y6 frame switch disconnector Y6B4P400D Y6 frame MCCB Y6H4P400T5 Y6 frame MCCB Y6H4P630T5 Y6 frame MCCB Y6H4P800T5 Outgoing MCCB Devices Standard cable termination 95mm 2 Maximum cable termination is 150mm 2 using reduced palm width M8 cable lugs Triple-pole MCCBs have adjustable thermal and magnetic overloads Device type Current 3-pole, 25kA 3-pole, 36kA 3-pole, 65kA rating (A) cat. no. cat. no. cat. no. (adjustable (adjustable (adjustable overloads) overloads) overloads) YA3 frame YA3 frame 20 YA3N3P20T YA3S3P20T YA3J3P20T YA3 frame 32 YA3N3P32T YA3S3P32T YA3J3P32T YA3 frame YA3 frame 50 YA3N3P50T YA3S3P50T YA3J3P50T YA3 frame 63 YA3N3P63T YA3S3P63T YA3J3P63T YA3 frame YA3 frame 100 YA3N3P100T YA3S3P100T YA3J3P100T YA3 frame 125 YA3N3P125T YA3S3P125T YA3J3P125T YA3 frame 160 YA3N3P160T YA3S3P160T YA3J3P160T YA3 frame 200 YA3N3P200T YA3S3P200T YA3J3P200T YA3 frame 250 YA3N3P250T YA3S3P250T YA3J3P250T 65

68 Loadbank A and 800A, Form 3 and 4, Panel Board Add-on Enclosures General Purpose Enclosures IP4X Ingress Protection Enclosures are 750mm wide x 200 deep No top or bottom plates supplied (supplied with panel board) Description Modular height Height (mm) Cat. no. General purpose enclosure LEBM1 General purpose enclosure LEBM2 General purpose enclosure LEBM3 General purpose enclosure LEBM4 General purpose enclosure LEBM5 General purpose enclosure LEBM6 Cableway Extension Enclosures IP4X Ingress Protection Recommend for cables above 70mm 2 250mm wide x 200mm deep No side plates supplied (supplied with panel board) Description Modular height Height (mm) Cat. no. Cableway LECM1 Cableway LECM2 Cableway LECM3 Cableway LECM4 Cableway LECM5 Cableway LECM6 Cableway LECM8 MCB Distribution Board and Service Centre IP3X (IP4X with door fitted) Ingress Protection MCB distribution boards have fully shielded busbars and interconnections Space saving twin option TP&N distribution board option Description Modular Height Cat. no. Door kit height (mm) cat. no. 17 MCB way SP&N distribution board LDS17 LD1DS 6 TP way TP&N distribution board LDT106X LD1D06X 12 TP way TP&N distribution board LDT112X LD1D12X 2 x 12 TP way TP&N distribution board LDT212X* LD2D12X 24 way modular service centre LDS24 LD1DS *Only double module RCBOs can be fitted in this enclosure. Twin YA5 Outgoing Housing (not design for use with Form 4 panel boards) Can be mounted direct to incoming enclosure without connection kit When mounting to 800A panelboard connection kits are required (LBSKE and LBCK8) Cableway extension enclosures are necessary to assist with cabling Terminal shields required per MCCB (YA5TC3P) Devices to be ordered separately (page 62) Description Modular Height Weight Cat. no. Door kit height (mm) (kg) cat. no. Twin YA5 (400A max each) 3 modules LB802YA5 LBDD02 66

69 Loadbank A and 800A, Form 3 and 4, Panel Board Metering Accessories For easy selection of metering please refer to the chart on pages 80. Cableway Metering Door Kits Incoming and outgoing metering utilises cableway extension boxes Metering door kits are available sized to the cableway extension boxes and are designed for panel mounted meters Includes DIN-rail for facility to mount current transformers and fuses Description Height Cat. no 2 module metering door kit, excluding CTs and control wiring 2 LECMD2 3 module metering door kit, excluding CTs and control wiring 3 LECMD3 4 module metering door kit, excluding CTs and control wiring 4 LECMD4 5 module metering door kit, excluding CTs and control wiring 5 LECMD5 6 module metering door kit, excluding CTs and control wiring 6 LECMD6 8 module metering door kit, excluding CTs and control wiring 8 LECMD8 Panel Mounted Meters for Incoming Circuits 93mm x 96mm dimensions Low profile Fully progammable CT ratios Can be configured SP or TP Device type Outputs Width (mm) Cat. no. 1-phase/3-phase digital kwh meter 1 pulse 96 CI1-01-PUL 1-phase/3-phase digital 1 pulse 96 INT-1630-M-5-M-100 multi-function meter 1-phase/3-phase digital 1 pulse & 96 INT-1630-M multi-function meter 1 Modbus 1-phase/3-phase digital 1 pulse 96 CI3-01-PUL multi-function meter Optional pulse plug-in module CI-PUL for Ci1 meter Optional RS485 Modbus plug-in CI-MOD-01 module for Ci meter 1 Surge Protection Cableway Mounting Kits Optional Modbus plug-in module for Ci meter Easily installed within a standard cableway (2 modules onward) DIN-rail mounting for triple-pole MCB C/W 30Ka three-phase surge protector Remote status indication Site fault indication Description Height (mm) Cat. no. 2 Cableway mounting frame c/w surge protector 304 LECK2SM & remote indicator (1) 2 module enclosure c/w surge protector 304 LECK2SP & remote indicator (2) 3-in-1 Current Transformers Description Max cable size mm 2 Cat. no. 100A current transformer (sold singular) 95*/150** M3N /5 125A current transformer (sold singular) 95*/150** M3N /5 200A current transformer (sold singular) 95*/150** M3N /5 250A current transformer (sold singular) 95*/150** M3N /5 400A current transformer (sold singular) 185*/240** M63N-400/5D 630A current transformer (sold singular) 240 M63N-600/5D 800A current transformer (sold singular) 240 M93L-800/5D * Using standard cable lugs. **Using reduced palm width cable lugs. Metering Harnesses Description Incoming meter loom Voltage tap off loom for outgoing metering CT harness for 1 outgoing meters Power loom for 6 outgoing meters Cat. no. LBWI LBWP LBWCT LBWM6 67

70 Loadbank 250 Selection Chart - 400A Panel Boards and Incomer Housings 400A Panel Boards - Form 3 ASTA busbar short circuit Outgoing Outgoing Height Weight Panel Door kit rating of 36kA for 1 second device ways (kg) cat. no. cat. no. Rating 250A outgoing MCCB/YA3 6 4 modules 36 LB406YA3 LBDD06 250A outgoing MCCB/YA modules 52 LB412YA3 LBDD12 250A outgoing MCCB/YA modules 66 LB418YA3 LBDD18 Incomer Housings - Form 3 Incoming device type Current Height Weight (kg) Cat. no. rating (A) MCCB/YA modules 26 LB1YA3 MCCB/Y modules 45 LB1Y6 Direct connection modules 18 LBDR4 Fuse switch modules 37.5 LB1F2A Fuse switch modules 48.5 LB1F4A Cableways - Form 2/3 Housing type Standard Height Weight (kg) Cat. no. apertures Cableway Yes 1 module 2 LECM1 Cableway Yes 2 modules 4 LECM2 Cableway Yes 3 modules 6 LECM3 Cableway Yes 4 modules 8 LECM4 Cableway 5 modules 8 LECM5 Cableway Yes 6 modules 12 LECM6 Cableway 8 modules 14 LECM8 Surge Protection Cableway Mounting Kits Description Height (mm) Cat. no. Cableway mounting frame c/w surge protector and remote indicator 304 LECK2SM 2 module enclosure c/w surge protector and remote indicator 304 LECK2SP Housed Fuse Switch Adaptor kits Current rating (A) Cat. no. Kit for HBF3P200N, incl. connections 200 LBSK2B Kit for HBF3P400N, incl. connections 400 LBSK4B General Purpose Enclosures Housing type Height Weight (kg) Cat. no. General purpose uncut front plate 1 module 4 LEBM1 General purpose uncut front plate 2 modules 10 LEBM2 General purpose uncut front plate 3 modules 16 LEBM3 General purpose uncut front plate 4 modules 22 LEBM4 General purpose uncut front plate 5 modules 28 LEBM5 General purpose uncut front plate 6 modules 34 LEBM6 68

71 Loadbank 250 Selection Chart - 400A Panel Boards Add-on Enclosure and Accessories Metering Description Height Height Current rating Cable size Cat. no. (modules) (mm) (A) (mm) Metering door kit LECMD2 Metering door kit LECMD3 Metering door kit LECMD4 Metering door kit LECMD5 Metering door kit LECMD6 Metering door kit LECMD8 Incoming meter loom LBWI Voltage tap off for outgoing meter LBWP CT harness for 1 outgoing meter LBWCT Meter power loom for 1 outgoing meter LBWM6 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 Current transformer M63N-400/5 Current transformer M63N-600/5 Current transformer M93L-800/5 1-phase/3phase kwh meter with pulse CI1-01-PUL 1-phase/3phase MF meter with pulse INT-1630-M-5-M phase/3phase MF meter with pulse and Modbus INT-1630-M-5-M phase/3phase MF meter with pulse CI3-01-PUL Optional pulse plug in module for Ci CI-PUL-01 Optional RS485 Modbus plug in module for Ci CI-MOD-01 MCB Distribution Boards Outgoing ways SP&N Height Weight Enclosure Door kit (kg) cat. no. cat. no module 15 LDS17 LD1DS TP&N 6 2 modules 23 LDT106X LD1D06X 12 3 modules 30 LDT112X LD1D12X 2x12 4 modules 35 LDT212X LD2D12X Service Centres Type Height Weight Cat. no. Door kit (kg) cat. no. Service centre (24 DIN units) 1 module 10 LDS24 LD1DS Accessories for 400A Panel Board Systems Description Loadbank 250/distribution boards/service centres Blanking piece 3-pole MCCB (1 front shield blank) Vertical connection kit (400A) Busbar terminals - extensions with shield, to connect both ends of busbar Adaptor kit for 200A housed fuse switch Adaptor kit for 400A housed fuse switch Horizontal insulation kit Steel end plate Cat. no. LBBP3PYA3 LBCK4 LBSKE LBSK2B LBSK4B MXEPF LGES Door Locking Cat. no. Door lock/key kit Padlocking kit for door kits DBXCL DBXPL 69

72 Loadbank 250 Selection Chart - 400A Panel Board Circuit Protection Devices Incoming Devices Current rating (A) 3-pole cat. no. 4-pole cat. no. Max. Min. YA3 switch disconnector 250 YA3B3P250D YA3B4P250D YA3 frame MCCB - 25kA YA3N3P250T YA3N4P250T YA3 frame MCCB - 36kA YA3S3P250T YA3S4P250T Y6 switch disconnector 400 Y6B3P400D Y6B4P400D Y6 frame MCCB - 50kA Y6H3P400T5 Y6H4P400T5 200A skeleton switches 200 SF3P200N SF4P A skeleton switches 400 SL3P400N SL4P A direct connection 400 LBDR4 Outgoing Devices for Form 2 Panel Boards Current rating (A) 1-pole cat. no. 3-pole cat. no. Max. YA3 MCCB 25kA 16 YA3N1P16T 20 YA3N1P20T YA3N3P20T 32 YA3N1P32T YA3N3P32T 40 YA3N1P40T 50 YA3N1P50T YA3N3P50T 63 YA3N1P63T YA3N3P63T 80 YA3N1P80T 100 YA3N1P100T YA3N3P100T 125 YA3N1P125T YA3N3P125T 160 YA3N1P160T YA3N3P160T 200 YA3N3P200T 250 YA3N3P250T YA3 MCCB - 36kA 20 YA3S3P20T 32 YA3S3P32T 50 YA3S3P50T 63 YA3S3P63T 100 YA3S3P100T 125 YA3S3P125T 160 YA3S3P160T 200 YA3S3P200T 250 YA3S3P250T 70

73 Loadbank 250 Selection Chart - 400A Panel Board and Incoming Devices Accessories Accessories for 400A Skeleton Switches Description Solid links (set of 1) Terminal barriers (set of 3) Fuse shrouds Terminal shrouds and barriers 2-blank auxiliary switch 4-blank auxiliary switch 6-blank auxiliary switch Cat. no. HLL400 SLTB SLFS SLTS SAUX2N SAUX4N SAUX6N Y6 Frame Accessories Description Terminal covers 3-pole Interphase barriers (set of 2) Terminal covers 4-pole Interphase barriers (set of 3) Terminations 4-pole Extension terminal bars Locking devices Dolly padlock device Shunt trips Shunt V AC Shunt V AC Shunt 24V DC Under-voltage release UVR V AC UVR V AC UVR V AC UVR 24V DC Auxiliary switches 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Cat. no. Y5TB3P Y5TB4P Y6XT4P Y6DL Y6ST115AC Y6ST450AC Y6ST24DC Y6UVR120AC Y6UVR240AC Y6UVR450AC Y6UVR24DC Y6AUX1 Y6AUX2 Y6AUXAL 71

74 Loadbank 250 Selection Chart - 400A Panel Board Outgoing Devices Accessories Description Terminal covers 3-pole YA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3 frame long terminal shroud (set of 1) YA3 frame short terminal shroud (set of 1) Terminations 3-pole YA3 frame cable clamps mm 2 (set of 3) Terminal covers 4-pole YA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3 frame long terminal shroud (set of 1) YA3 frame short terminal shroud (set of 1) Terminations 4-pole YA3 frame cable clamps mm 2 (set of 4) Shunt trips YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip 24V DC Auxiliary and alarm switches YA frame 1AB auxiliary switch YA frame alarm switch Under-voltage release YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release 24V DC Locking devices YA frame dolly padlock device YA frame Castell* (DS1) lock direct mtg. trapped on Cat. no. YA3TB YA3TS3P YA3TS3PS YA3CC3P YA3TB YA3TS4P YA3TS4PS YA3CC4P YAST115AC YAST240AC YAST450AC YAST24DC YAAUX1 YAAL YAUVR120AC YAUVR240AC YAUVR450AC YAUVR24DC YADL1 YACL *Castell is a trademark of Castell Safety International Limited. 72

75 Loadbank 250 Selection Chart - 800A Panel Boards and Incomer Housings 800A Panel Boards Form 3 ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kit of 50kA for 1 second device ways (kg) cat. no. cat no. 250A outgoing MCCB/YA3 6 4 modules 42 LB806YA3 LBDD06 250A outgoing MCCB/YA modules 62 LB812YA3 LBDD12 250A outgoing MCCB/YA modules 78 LB818YA3 LBDD18 Incomer Housings Form 3 Incomer device type Current Height Weight Cat. no. rating (A) (kg) MCCB/Y modules 45 LB1Y6 MCCB/Y modules 69 LB1Y7 Direct connection modules 23 LBDR8 Outgoing Housings Form 3 Incomer device type Current Outgoing Height Weight Panel Door kit rating (A) ways (kg) cat. no. cat. no. 2x YA5 MCCB modules 25 LB802YA5 LBDD02 800A Panel Boards Form 4 ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kit of 50kA for 1 second device ways (kg) cat. no. cat no. 250A outgoing MCCB/YA3 6 5 modules 59 LF806YA MXD06 250A outgoing MCCB/YA modules 98 LF810YA MXD10 Incomer Housings Form 4 Device type housing Current Height Weight Cat. no. rating (A) (kg) Fuse switch 630/800 6 modules 67 LF1F8A Y6 frame MCCB modules 59 MMS15Y Y6 connection kit MCFMY6 Shielding Form 4 Description Additional Cat. no. housing 70mm 2 cables LFS41YA 150mm 2 cables Cableway LFS42YA Surge Protection Cableway Mounting Kits Description Height (mm) Cat. no. Cableway mounting frame c/w surge protector and remote indicator 304 LECK2SM 2 module enclosure c/w surge protector and remote indicator 304 LECK2SP 73

76 Loadbank 250 Selection Chart - 800A Panel Boards Add-on Enclosures and Accessories Metering Description Height Height Current rating Cable size Cat. no. (modules) (mm) (A) (mm) Metering door kit LECMD2 Metering door kit LECMD3 Metering door kit LECMD4 Metering door kit LECMD5 Metering door kit LECMD6 Metering door kit LECMD8 Incoming meter loom LBWI Voltage tap off for outgoing meter LBWP CT harness for 1 outgoing meter LBWCT Meter power loom for 1 outgoing meter LBWM6 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 3-in-1 current transformers M3N /5 Current transformer M63N-400/5 Current transformer M63N-600/5 Current transformer M93L-800/5 1-phase/3phase kwh meter with pulse output CI1-01-PUL 1-phase/3phase MF meter with pulse output INT-1630-M-5-M phase/3phase MF meter with pulse INT-1630-M-5-M-110 and Modbus output 1-phase/3phase MF meter with pulse output CI3-01-PUL Optional pulse plug in module for Ci meter CI-PUL-01 Optional RS485 Modbus plug in module for CI-MOD-01 Ci meter - MCB Distribution Boards Outgoing ways SP&N Height Weight Enclosure Door kit (kg) cat. no. cat. no module 15 LDS17 LD1DS TP&N 6 2 modules 23 LDT106X LD1D06X 12 3 modules 30 LDT112X LD1D12X 2x12 4 modules 35 LDT212X LD2D12X Service Centres Type Height Weight Cat. no. Door kit (kg) cat. no. Service centre (24 DIN units) 1 module 10 LDS24 LD1DS Accessories for 400A Panel Board Systems Description Loadbank 250/distribution boards/service centres Blanking piece 3-pole MCCB (1 front shield blank) Vertical connection kit (800A) Busbar terminals - extensions with shield, to connect both ends of busbar Adaptor kit for 200A housed fuse switch Adaptor kit for 400A housed fuse switch Horizontal insulation kit Steel end plate Door Locking Door lock/key kit Padlocking kit for door kits 74 Cat. no. LBBP3PYA3 LBCK8 LBSKE LBSK2B LBSK4B MXEPF LGES Cat. no. DBXCL DBXPL

77 Loadbank 250 Selection Chart - 800A Panel Boards Incoming Devices Incoming Devices Form 3 Panel Boards Current rating (A) 3-pole cat. no. 4-pole cat. no. Max. Min. Y6 Frame Switch Disconnector Y6B3P630D Y6B4P630D Y6 Frame MCCB Thermal/Magnetic Icu 50 ka Y6H3P630T5 Y6H4P630T5 Y6 Frame MCCB Electronic Icu 50kA Y6H3P630E Y6H4P630E Y7 Frame Switch Disconnector Y7B3P800D Y7B4P800D* Y7 Frame MCCB Electronic Icu 65kA Y7J3P1000E Y7J4P1000E* *This MCCB must be set at 800A maximum. Incoming Devices Form 4 Panel Boards Fuse Switch 3-pole+N cat. no. 4-pole+N cat. no. Current rating (A) 630 SN3P630N SN4P SN3P800N SN4P800 Y6 Switch Disconnector Panel Boards Current rating (A) 3-pole cat. no. 4-pole cat. no. 800 Y6B3P800D Y6B4P800D Y6 Frame MCCB Thermal/Magnetic Current rating (A) Max. Min Y6H3P800T5 Y6H4P800T5 Y6 Frame MCCB Electronic Current rating (A) Max. Min Y6H3P800E Y6H4P800E 75

78 Loadbank 250 Selection Chart - 800A Panel Board Incoming Accessories 630/800A Skeleton Switches Accessories Description Cable extension terminals (set of 8) Solid links (set of 1) Terminal barriers (set of 3) Fuse shrouds Cat. no. SNCET HNL800 Supplied SNFS Y6 Frame Accessories Description Terminal covers 3-pole Interphase barriers (set of 2) Terminal covers 4-pole Interphase barriers (set of 3) Terminations 4-pole Extension terminal bars Locking devices Dolly padlock device Shunt trips Shunt V AC Shunt V AC Shunt 24V DC Under-voltage release UVR V AC UVR V AC UVR V AC UVR 24V DC Auxiliary switches 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Cat. no. Y5TB3P Y5TB4P Y6XT4P Y6DL Y6ST115AC Y6ST450AC Y6ST24DC Y6UVR120AC Y6UVR240AC Y6UVR450AC Y6UVR24DC Y6AUX1 Y6AUX2 Y6AUXAL 76

79 Loadbank 250 Selection Chart - 800A Panel Board Incoming Device Accessories Y7 Frame Accessories Description Terminal covers 3-pole Interphase barriers (set of 2) Terminal covers 4-pole Interphase barriers (set of 3) Locking devices Dolly padlock device Shunt trips Shunt V AC Shunt V AC Shunt 24V DC Under-voltage release UVR V AC UVR V AC UVR V AC UVR 24V DC Auxiliary switches 3-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Auxiliary switches 4-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Cat. no. Y5TB3P Y5TB4P Y7DL Y7ST115AC Y7ST450AC Y7ST24DC Y7UVR120AC Y7UVR240AC Y7UVR450AC Y7UVR24DC Y7AUX3P1 Y7AUX3P2 Y7AUX3PAL Y7AUX4P1 Y7AUX4P2 Y7AUX4PAL 77

80 Loadbank 250 Selection Chart - 800A Panel Boards Outgoing Devices Outgoing Devices for Form 3 Panel Boards Current rating (A) 1-pole cat. no. 3-pole cat. no. Max. Min. YA3 frame MCCB - 25kA 16 - YA3N1P16T YA3N1P20T YA3N3P20T 32 - YA3N1P32T YA3N3P32T 40 - YA3N1P40T YA3N1P50T YA3N3P50T 63 - YA3N1P63T YA3N3P63T 80 - YA3N1P80T YA3N1P100T YA3N3P100T YA3N1P125T YA3N3P125T YA3N1P160T YA3N3P160T YA3N3P200T YA3N3P250T YA3 frame MCCB - 36kA YA3S3P50T YA3S3P63T YA3S3P100T YA3S3P125T YA3S3P160T YA3S3P200T YA3S3P250T Outgoing Devices for Form 4 Panel Boards Current rating (A) 4-pole 25kA 4-pole 36kA 4-pole 65kA Max. Min. cat. no. cat. no. cat. no. YA3 frame MCCB YA3N4P20T YA3N4P32T YA3N4P50T YA3S4P50T YA3J4P50T YA3N4P63T YA3S4P63T YA3J4P63T YA3N4P100T YA3S4P100T YA3J4P100T YA3N4P125T YA3S4P125T YA3J4P125T YA3N4P160T YA3S4P160T YA3J4P160T YA3N4P200T YA3S4P200T YA3J4P200T YA3N4P250T YA3S4P250T YA3J4P250T 78

81 Loadbank 250 Selection Chart 800A Panel Board Outgoing Device Accessories Description Terminal covers 3-pole YA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3 frame long terminal shroud (set of 1) YA3 frame short terminal shroud (set of 1) Terminations 3-pole YA3 frame cable clamps mm 2 (set of 3) Terminal covers 4-pole YA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3 frame long terminal shroud (set of 1) YA3 frame short terminal shroud (set of 1) Terminations 4-pole YA3 frame cable clamps mm 2 (set of 4) Shunt trips YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip V AC YA frame shunt trip 24V DC Auxiliary and alarm switches YA frame 1AB auxiliary switch YA frame alarm switch Under-voltage release YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release V AC YA frame under-voltage release 24V DC Locking devices YA frame dolly padlock device YA frame Castell* (DS1) lock to be ordered separately Motor actuator YA3 motor actuator AC V YA3 motor actuator AC V Cat. no. YA3TB YA3TS3P YA3TS3PS YA3CC3P YA3TB YA3TS4P YA3TS4PS YA3CC4P YAST115AC YAST240AC YAST450AC YAST24DC YAAUX1 YAAL YAUVR120AC YAUVR240AC YAUVR450AC YAUVR24DC YADL1 YACL YA3MA110 YA3MA240 *Castell is a trademark of Castell Safety International Limited. 79

82 Loadbank 250 Meter Selection Process Loadbank 200/250 The Loadbank 200/250 metering facilities utilise standard cableway extension enclosures with optional door kits designed for panel mounted meters. The size of the cableway will determine the corresponding metering door kit. Where cable sizes exceed 70mm a recommendation would be to include two cableway extension enclosures to facilitate easy wiring. The same could be advised when fully populating an 18 way panel board with meters. Current transformers and fuses can be DINrail mounted within the cableways using the facilities provided within the optional door kits. Panel-board enclosures Description Cat. no. Cableway Door LB406YA3 LB412YA3 LB418YA3 LB406YA3:- LECMD4 x 2 LB412YA3:-LECMD6 x 2 LB418YA3:-LECMD8 x 2 LB1YA3:-LECMD3 x 1 LB1Y6:-LECMD5 x 1 LBDR4:-LECMD2 x 1 LB1F2A:-LECMD3 x 1 LB1F4A:-LECMD5 x 1 LB806YA3 LB812YA3 LB818YA3 LB802YA5 LB806YA3:- LECMD4 x 2 LB812YA3:- LECMD6 x 2 LB818YA3:- LECMD8 x 2 LB802YA5:- LECMD3 x 2 LB1Y6:-LECMD5 x 1 LB1Y7:-LECMD6 x 1 LBDR8:-LECMD3 x 1 LF806YA LF810YA LF806YA:-LECMD5 x 2 LF810YA:-LECMD8 x 2 LF1F8A:-LECMD5 x 1 MMS15Y:-LECMD6 x 1 LF1F4A 400A, 6 way, Form 3 LB406YA3 400A, 8 way, Form 3 LB412YA3 400A, 12 way, Form 3 LB418YA3 800A, 6 way, Form 3 LB806YA3 800A, 12 way, Form 3 LB812YA3 800A, 18 way, Form 3 LB818YA3 800A, 6 way, Form 4 LF806YA 800A, 10 way, Form 4 LF810YA Description Cat. no. 2 module metering mounting kit, (2 meter positions) LECMD2 3 module metering mounting kit, (3 meter positions) LECMD3 4 module metering mounting kit, (4 meter positions) LECMD4 5 module metering mounting kit, (6 meter positions) LECMD5 6 module metering mounting kit, (6 meter positions) LECMD6 8 module metering mounting kit, (9 meter positions) LECMD8 Left Side Outgoing Meter Arrangement LBWP 1 Off Right Side Outgoing Meter Arrangement LBWP 1 Off Incoming Meter Arrangement LBWI 1 Off Description 3-in-1 100A current transformers 3-in-1 125A current transformers 3-in-1 200A current transformers 3-in-1 250A current transformers 400A current transformer (sold singular) 630A current transformer (sold singular) 800A current transformer (sold singular) Description Digital multi-function meter with one pulse outputs Digital multi-function meter with one pulse output and one RS485 output Digital kilowatt hour meter with one pulse output Digital multi-function meter with one pulse output Cat. no. M3N /5 M3N /5 M3N /5 M3N /5 M63N-400/5D M63N-600/5D M93L-800/5D Cat. no. INT-1630-M-5-M-100 INT-1630-M-5-M-110 CI1-01-PUL CI3-01-PUL Up to 6 Meters: LBWM6 1 Off Above 6 Meters: LBWM6 2 Off CI1-01-PUL CI3-01-PUL INT-1630-M-5-M-*** LBWCT 1 per Meter M3N /5 M3N /5 M3N /5 M3N /5 Up to 6 Meters: LBWM6 1 Off Above 6 Meters: LBWM6 2 Off CI1-01-PUL CI3-01-PUL INT-1630-M-5-M-*** LBWCT 1 per Meter M3N /5 M3N /5 M3N /5 M3N /5 CI3-01 CI1-01 INT-1630-M-5-M-*** M53J-200/5D 3 per Meter M53J-250/5D 3 per Meter M63N-400/5D 3 per Meter M63N-600/5D 3 per Meter M63N-800/5D 3 per Meter M93L-600/5D 3 per Meter M93L-800/5D 3 per Meter 80

83 Section 6 Fuse Combination Units Loadswitch Range (Housed Skeleton Disconnectors A)

84 Overview Key Features 80kA short-circuit capacity Housed or skeleton versions Integral cable spreading facility with choice of position AC23A utilisation category IP rated switch disconnectors Switch disconnectors in sheet steel enclosures Benefits Ease of installation Accepts large cables Rated for continuous full-rated load Compliance Fuse switches EN The Dorman Smith Loadswitch fuse combination range includes skeleton switches, housed switches and switch disconnectors. All Loadswitch fuse combination units exceed EN requirements and amply meet specifications for full uninterrupted duty to ensure that switches will maintain the maximum rated load indefinitely. Given their utilisation category of AC23A and a short-circuit capacity of 80kA, Loadswitch fuse combination devices provide complete confidence when installed in any resistive or inductive load application. Housed switches are supplied in sheet steel boxes with integral cable spreading space that can be positioned above or below the switch to suit ease of installation. The switch disconnector units are supplied in either IP65 insulated enclosures or sheet steel boxes. The robust steel enclosures are finished in light grey RAL 7035 epoxy powder coating and have doors that open 180 for ease of access. Padlocking is arranged to be off as standard and up to three padlocks can be attached with ease. 82

85 Housed Switches 32A 315/400A 160/200A 63/125A 630/800A Skeleton Switches 160/200A 63/125A 315/400A 630/800A 83

86 Loadswitch Enclosed Fuse Switch Combination Units 32A-800A Housed Switches 32A Complete with Fuses Exceeds the requirements of EN All terminals supplied with cable clamps Full withstand duty 80kA rms fused short-circuit capacity 415V AC rated voltage Supplied with fuse links, solid links are an optional accessory AC23A utilisation category IP4X Ingress Protection Not supplied with fuse links For fuse links see page 89 Current rating (A) 3-pole cat. no. 3-pole+N cat. no. 4-pole cat. no. 32 HBE3P32N Housed Switches 63/125A Complete with Fuses Exceeds the requirements of EN All terminals supplied with lug-fixing screws Full withstand duty 80kA rms fused short-circuit capacity 415V AC rated voltage Supplied with fuse links, solid links are an optional accessory AC23A utilisation category IP4X Ingress Protection Not supplied with fuse links For fuse links see page 89 Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 63 HBF3P63N HBF3P100N HBF4P HBF3P125N - Housed Switches 160/200A Exceeds the requirements of EN All terminals supplied with lug-fixing screws Full withstand duty 80kA rms fused short-circuit capacity 415V AC rated voltage AC23A utilisation category IP4X Ingress Protection Not supplied with fuse links For fuse links see page 89 Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 160 HBF3P160N HBF3P200N HBF4P200 For solid isolator links see page 85. Housed Switches 315/400A Exceeds the requirements of EN All terminals supplied with lug-fixing screws Full withstand duty 80kA rms fused short-circuit capacity 415V AC rated voltage AC23A utilisation category IP4X Ingress Protection Not supplied with fuse links For fuse links see page 89 Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 315 HBK3P315N HBL3P400N HBL4P400 For solid isolator links see page 85. Housed Switches 630/800A Exceeds the requirements of EN All terminals supplied with lug-fixing screws Full withstand duty 80kA rms fused short-circuit capacity 415V AC rated voltage AC23A utilisation category IP4X Ingress Protection Not supplied with fuse links For fuse links see page 89 Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 630 HBN3P630N HBN3P800N HBN4P For solid isolator links see page 85.

87 Loadswitch Enclosed Fuse Switch Combination Units Accessories Accessories for Housed Switches Description Current Picture Cat. no. rating (A) Cable spreader box 63/125 1 HB125CSB 160/200 1 HB200CSB 315/400 1 HB400CSB 630/800 1 HB800CSB Solid links (set of 1) 32 2 HEL HFL HFL200A 315/400 2 HLL /800 2 HNL800 Castell* lock mounting kit All SCLK Castell* lock with key (see note) All 3 FS2 2-bank auxiliary switch 63/200 4 SAUX2F 315/800 4 SAUX2N 4-bank auxiliary switch 63/200 4 SAUX4F 315/800 4 SAUX4N 6-bank auxiliary switch 315/800 4 SAUX6N Note: Standard symbol DS1, special symbols are available direct from Castell. Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65 anti-clockwise to trap key *Castell is a trademark of Castell Safety International Limited. Housed Switches Technical Data Max. current rating (A) = Rated current (A) Frame size E F F Mechanical endurance 10,000 10,000 10,000 8,000 8,000 8,000 Fused s/c current ka rms V AC Max. cable (mm 2 )* Terminals Clamp type M8 M8 M8 M8 M8 Max cable lug palm width Weight (kg) A Top and Bottom Knock Out Dimensions 3 4 Max. current rating (A) = Rated current (A) Frame size K L N N Mechanical endurance 8,000 5,000 5,000 3,000 Fused s/c current ka rms V AC Max. cable (mm 2 )* 185** Terminals M10 M10 4xM8 4xM8 M10 M10 1xM16 1xM16 Max cable lug palm width Weight (kg) * These figures are for guidance only and are dependent upon lug palm width. ** 240mm 2 with terminal barriers A Top and Bottom Knock Out Dimensions Housed Switches Dimensions Current Height Width Depth over Weight rating (A) (mm) (mm) handle (mm) (kg) A Loadswitch Terminal Spreader Box Dimensions Current Height Width Depth over Weight rating (A) (mm) (mm) handle (mm) (kg) 63A-125A HB125CSB 200A HB200CSB A HB400CSB A HB800CSB All dimensions in mm 85

88 Loadswitch Skeleton Switches (Without Fuses) Skeleton Switches 63/125A Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Lug fixings not supplied Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 63 SF3P63N SF4P SF3P100N SF4P SF3P125N SF4P125 Skeleton Switches 160/200A Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Lug fixings not supplied Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 160 SF3P160N SF4P SF3P200N SF4P200 Skeleton Switches 315/400A Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Lug fixings not supplied Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 315 SK3P315N SK4P SL3P400N SL4P400 Skeleton Switches 630/800A Exceeds the requirements of EN kA rms fused short-circuit capacity AC23A utilisation category Full uninterrupted duty 415V AC rated voltage Lug fixings not supplied Current rating (A) 3-pole+N cat. no. 4-pole cat. no. 630 SN3P630N SN4P SN3P800N SN4P800 For fuse links see page

89 Loadswitch Skeleton Switch Accessories Accessories for Skeleton Switches Description Current Picture Cat. no. rating (A) Cable extension terminals (set of 8) 630/800 SNCET Solid links (set of 1) 63 1 HFL63 100/200 1 HFL200A 315/400 1 HLL /800 1 HNL800 2-bank auxiliary switch 63/200 3 SAUX2F 315/800 3 SAUX2N 4-bank auxiliary switch 63/200 3 SAUX4F 315/800 3 SAUX4N 6-bank auxiliary switch 315/800 3 SAUX6N Castell* lock mounting kit (standard symbol DS1 see note) All SCLK Castell* lock with key 32/800 2 FS2 Handle assembly for: E frame - standard size 5 SHA1 F frame - standard size 5 SHA2 K + L frame - special reduced size 5 SHA3 KL+N frame - standard size 5 SHA4 Shaft extensions 63A - 200A 4 SXT127 for panel depth 270mm 315A - 800A 4 SXT227 Shaft extensions 63A - 200A 4 SXT160 for panel depth 600mm 315A - 800A 4 SXT Terminal shrouds 160/200 SFTSL (recommended for cable sizes above 70mm) 63/200 SFTSS 315 SKTS 400 SLTS 630/800 SNTS Terminal barriers (set of 3) 63/200 SFTB 315 SKTB 400 SLTB 630/800 Supplied Fuse shrouds (set of 3) 63/125 SFFS /200 SFFS SKFS 400 SLFS 630/800 SNFS Rating label (strip of 8) 63 6 SRLB SRLB SRLB SRLB SRLB SRLB SRLB SRLB SRLB800 Note: Special symbols are available direct from Castell. Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65 anti clockwise to trap key. *Castell is a trademark of Castell Safety International Ltd. 87

90 Loadswitch Technical Data Skeleton Switches Dimensions 630/800A Standard Terminal 630/800A extension terminal (accessory) Dimensions Frame A B C D E F G H I J K L M N O P Q W X Y Z F 63A N/A M5 170* M8 20 F A N/A M5 170* M8 20 F A N/A M5 220 M8 20 K 315A N/A M5 220 M12 35 L 400A N/A M5 220 M12 50 N A M6 270 M12 80 * Supplied suitable for an X dimension of 220mm, the drive shaft can be cut to give a minimum X dimension of 170mm. Skeleton Switches Technical Data Max. current rating (A) = Rated current (A) Frame size F F F F F Mechanical endurance 10,000 10,000 8,000 8,000 8,000 Fused s/c current ka rms V AC Max. cable (mm 2 )* Terminals M8 M8 M8 M8 M8 Max cable lug palm width Weight (kg) Max. current rating (A) = Rated current (A) Frame size K L N N Mechanical endurance 8,000 5,000 5,000 3,000 Fused s/c current ka rms V AC Max. cable (mm 2 )* 185** Terminals M12 M12 4xM8*** 4xM8*** M12 M12 1xM16*** 1xM16*** Max cable lug palm width Weight (kg) * These figures are for guidance only and are dependent upon lug palm width ** 240mm 2 with terminal barriers *** Only with cable extension terminals (SNCET) 88

91 Loadswitch Fuse Comparison Chart - 415V Standard Bussman GEC/ MEM Tag type BS88 ref Fuse fixing Inserted switch Lawson centres (mm) switch NITD2 NIT2 2SA2 NITD4 NIT4 4SA2 NITD6 NIT6 6SA2 HBE3P32N NITD10 NIT10 10SA2 OFFSET A NITD16 NIT16 16SA2 NITD20 NIT20 20SA2 NITD25 NIT25* 25SA2 NITD32 NIT32* 32SA2 AAO2 TIA2 2SB3 AAO4 TIA4 4SB3 AAO6 TIA6 6SB3 AAO10 TIA10 10SB3 HBF/SF3P63 AAO16 TIA16 16SB3 OFFSET A SFT3P63 HBF/SF3P63N AAO20 TIA20 20SB3 SFT3P63N HBF/SF4P63 AAO25 TIA25 25SB3 SFT4P63 AAO32 TIA32 32SB3 BAO40 TIS40 40SB4 BAO50 TIS50 50SB4 OFFSET A BAO63 TIS63 63SB4 TCP6* TCP10* TCP16* TCP20* HBF/SF3P100 TCP25* SFT3P100 HBF/SF3P100N CEO32 TCP32* OFFSET A4 (dia 33 max) 94.0 SFT3P100N HBF/SF4P100 CEO40 TCP40* SFT4P100 CEO50 TCP50* CEO63 TCP63* CE080 TCP80 80SD5 CEO100 TCP SD5 HBF/SF3P125 SFT3P125 HBF/SF3P125N DEO125 TFP SD6 OFFSET A SFT3P125N HBF/SF4P125 SFT4P125 HBF/SF3P160 SFT3P160 HBF/SF3P160N DEO160 TFP SD6 OFFSET A4 (dia 38 max) 94.0 SFT3P160N HBF/SF4P160 SFT4P160 HBF/SF3P200 SFT3P200 HBF/SF3P200N DEO200 TFP SD6 OFFSET A4 (dia 38 max) 94.0 SFT3P200N HBF/SF4P200 SFT4P200 CD80 TC80 80SF5 CD100 TC SF5 CENTRE B SKT3P315 HBK/SK3P315 DD125 TF SF6 SKT3P315N HBK/SK3P315N DD160 TF SF6 CENTRE B SKT4P315 HBK/SK4P315 DD200 TF SF6 HBL/SL3P400 ED250 TKF SF7 SLT3P400 HBL/SL3P400N ED315 TKF SF7 CENTRE B3 (dia 50 max) SLT3P400N HBL/SL4P400 SLT4P400 EF355 TM SH8 EF400 TM SH8 CENTRE C SNT3P630 HBN/SN3P630 FF450 TTM SH9 SNT3P630N HBN/SN3P630N FF500 TTM SH9 SNT4P630 HBN/SN4P630 FF560 TTM SH9 CENTRE C FF630 TTM SH9 HBN/SN3P800 TLM670 SNT3P800 HBN/SN3P800N GF710 TLM SH10 SNT3P800N HBN/SN4P800 TLM750 CENTRE C SNT4P800 GF800 TLM SH10 NOTE: 1. The comparative types are a guide to interchangeability, with regard to dimensions and current rating only. It is essential that rated voltage and other electrical characteristics are checked to ensure compatability. 2. Please check maximum barrel size prior to fitting. 3. *Lawson fuse reference only. 89

92 Loadswitch Switch Disconnectors in IP rated Enclosures Switch Disconnectors in IP65 Insulated Enclosures Conforms to EN Padlockable handle Rotary handle accepts three padlocks Terminals accept large cables Includes earth and neutral terminals IP65 ingress protection Current rating (A) 3-pole cat. no. Technical Data for Disconnectors in IP65 Insulated Enclosures 16 PS16NY 25 PS25NY 32 PS32NY 40 PS40NY 63 PS63NY 80 PS80NY 100 PS100NY 125 PS125NY Current rating (A) Rated insulation voltage Ui (V) Dielectric strength (kv) 50 Hz 1 min Shock resistance Uimp (kv) Operational current Ie (A) 415V AC AC21A/AC21B AC22A/AC22B AC23A/AC23B V AC AC21A/AC21B AC22A/AC22B AC23A/AC23B V AC AC20A/AC20B AC21A/AC21B AC22A/AC22B AC23A/AC23B Motor power (kw) AC23 415V AC V AC V AC Overload capacity at 415V AC Fuse rating / Short-circuit current with fuses (ka rms) / Asymmetric short time rating current (ka peak) Admissible short time current 1s (ka rms) Making and breaking characteristics Breaking capacity (A rms) 415V AC23A Making capacity (A rms) 415V AC23A Withstand Mechanical (number of operations) x Electrical (no. of operations at 415V AC23A) x Connection Maximum Cu cable section (mm 2 ) Using stranded cable (mm 2 ) Dimensions Current Height Width Depth over Weight rating (A) (mm) (mm) handle (mm) (kg)

93 Loadswitch Switch Disconnectors in Sheet Steel Enclosures Switch Disconnectors in Sheet Steel Enclosures Conforms to EN Padlockable handle Rotary handle accepts three padlocks Terminals accept large cables IP4X ingress protection Current rating (A) 3-pole cat. no. 3-pole+N cat. no. 20 HS13P20 HS13P20N 32 HS13P32 HS13P32N 40 HS13P40 HS13P40N 63 HS13P63 HS13P63N 63 HS23P63 HS23P63N 100 HS23P100 HS23P100N 125 HS23P125 HS23P125N Technical Data for Disconnectors in IP65 Insulated Enclosures Current rating (A) Rated insulation voltage Ui (V) Dielectric strength (kv) 50 Hz 1 min Shock resistance Uimp (kv) Operational current Ie (A) 415V AC AC21A/AC21B AC22A/AC22B AC23A/AC23B V AC AC21A/AC21B AC22A/AC22B AC23A/AC23B V AC AC20A/AC20B AC21A/AC21B AC22A/AC22B AC23A/AC23B Motor power (kw) AC23 415V AC V AC V AC Overload capacity at 415V AC Fuse rating / Short-circuit current with fuses (ka rms) / Asymmetric short time rating current (ka peak) Admissible short time current 1s (ka rms) Making and breaking characteristics Breaking capacity (A rms) 415V AC23A Making capacity (A rms) 415V AC23A Withstand Mechanical (number of operations) x Electrical (no. of operations at 415V AC23A) x Connection Maximum Cu cable section (mm 2 ) Using stranded cable (mm 2 ) Disconnectors Current Height Width Depth over Weight rating (A) (mm) (mm) handle (mm) (kg) Dimensions 3-pole 4-pole

94 Loadswitch Switch Disconnectors Accessories Accessories for Switch Disconnectors Description Current rating (A) Cat. no. 63A neutral link All HSNL63 125A neutral link All HSNL125 10A auxiliary switch All HSAUX Terminal shroud (set of 2): 1-pole 16/63 HSTS163 3-pole 16/63 HSTS363 1-pole 63/125 HSTS pole 63/125 HSTS

95 Section 7 Dorman Smith Circuit Protection and Modular Devices

96 Circuit Protection Devices Loadlimiter 63 Miniature Circuit Breakers 10/15kA 10kA/15kA MCBs Exceeds the requirements of EN Contact position indicator 35mm 2 cable capacity Multiples of 17.5mm width 10kA rated to the requirements of EN kA rated to the requirements EN60947 Current rating (A) B type cat. no. C type cat. no. D type cat. no. Single-pole MCBs 6 K1PB06 K1PC06 K1PD06 10 K1PB10 K1PC10 K1PD10 13 K1PB13 K1PC13 N/A 16 K1PB16 K1PC16 K1PD16 20 K1PB20 K1PC20 K1PD20 25 K1PB25 K1PC25 K1PD25 32 K1PB32 K1PC32 K1PD32 40 K1PB40 K1PC40 T1PD40* 50 K1PB50 K1PC50 T1PD50* 63 K1PB63 K1PC63 T1PD63* Double-pole MCBs 6 K2PB06 K2PC06 K2PD06 10 K2PB10 K2PC10 K2PD10 13 N/A N/A N/A 16 K2PB16 K2PC16 K2PD16 20 K2PB20 K2PC20 K2PD20 25 K2PB25 X2PC25 K2PD25 32 K2PB32 K2PC32 K2PD32 40 K2PB40 K2PC40 T2PD40* 50 K2PB50 K2PC50 T2PD50* 63 K2PB63 K2PC63 T2PD63* Triple-pole MCBs 6 K3PB06 K3PC06 K3PD06 10 K3PB10 K3PC10 K3PD10 13 N/A N/A N/A 16 K3PB16 K3PC16 K3PD16 20 K3PB20 K3PC20 K3PD20 25 K3PB25 K3PC25 K3PD25 32 K3PB32 K3PC32 K3PD32 40 K3PB40 K3PC40 T3PD40* 50 K3PB50 K3PC50 T3PD50* 63 K3PB63 K3PC63 T3PD63* Dimensions 94

97 Circuit Protection Devices Loadlimiter 63 Residual Current Circuit Breaker with Overload 10kA RCBOs Exceeds the requirements of EN Single module: Type AC 10kA rated breaking capacity Terminal capacity: outgoing terminals 10mm 2 Terminal capacity: busbar side terminals 35mm 2 Current rating (A) Sensitivity B type cat. no. C type cat. no KR1PB0630 KR1PC KR1PB1030 KR1PC KR1PB1630 KR1PC KR1PB2030 KR1PC KR1PB3230 KR1PC KR1PB4030 KR1PC KR1PB4530 KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC KR1PC40100 Double Module RCBOs Exceeds the requirements of EN 61009, IEC SP&SwN configuration Rated breaking capacity up to 10kA Contact position indicator Rated voltage Ue ~230V Rated frequency 50Hz Energy limiting class 3 Type AC Terminal capacity: outgoing terminals 35mm 2 Terminal capacity: busbar side terminals 35mm 2 Current rating (A) 30m/A cat. no. 6 KR2PB KR2PB KR2PB KR2PB KR2PB KR2PB4030 Accessories for 10kA MCBs and RCBOs Auxiliary equipment MCB shunt trip (240V AC) MCB auxiliary/switch contact Padlocking MCB dolly locking device Padlock for dolly locking device Cat. no. KST240 KAUX1 KDL XPL Dimensions Single Module Double Module

98 Circuit Protection Devices Loadlimiter 63 Miniature Circuit Breakers 6kA/10kA 6kA/10kA MCBs Exceeds the requirements of EN kA rated breaking capacity to EN Contact position indicator 25mm 2 cable capacity 10kA rated breaking capacity to EN Current rating (A) B type cat. no. C type cat. no. D type cat. no. Single-pole MCBs 6 S1PB06 S1PC06 S1PD06 10 S1PB10 S1PC10 S1PD10 16 S1PB16 S1PC16 S1PD16 20 S1PB20 S1PC20 S1PD20 25 S1PB25 S1PC25 S1PD25 32 S1PB32 S1PC32 S1PD32 40 S1PB40 S1PC40 S1PD40 50 S1PB50 S1PC50 S1PD50 63 S1PB63 S1PC63 S1PD63 Double-pole MCBs 6 S2PB06 S2PC06 S2PD06 10 S2PB10 S2PC10 S2PD10 16 S2PB16 S2PC16 S2PD16 20 S2PB20 S2PC20 S2PD20 25 S2PB25 S2PC25 S2PD25 32 S2PB32 S2PC32 S2PD32 40 S2PB40 S2PC40 S2PD40 50 S2PB50 S2PC50 S2PD50 63 S2PB63 S2PC63 S2PD63 Triple-pole MCBs 6 S3PB06 S3PC06 S3PD06 10 S3PB10 S3PC10 S3PD10 16 S3PB16 S3PC16 S3PD16 20 S3PB20 S3PC20 S3PD20 25 S3PB25 S3PC25 S3PD25 32 S3PB32 S3PC32 S3PD32 40 S3PB40 S3PC40 S3PD40 50 S3PB50 S3PC50 S3PD50 63 S3PB63 S3PC63 S3PD63 Dimensions 96

99 Circuit Protection Devices Loadlimiter 63 Residual Current Circuit Breakers RCCBs Exceeds the requirements of EN Voltage 230/400V 50/60Hz Type AC Terminal capacity: top 25mm 2 Terminal capacity: bottom 35mm 2 Double-pole RCCBs Current rating (A) Sensitivity (ma) Type Width (mm) Cat. no AC 35 EE40/30/ AC 35 EE40/100/ AC 35 EE63/30/ AC 35 EE63/100/ AC 35 EE63/300/ AC 35 EE80/30/ AC 35 EE100/30/ AC 35 EE100/100/2 100, time delay 100 AC 35 EES100/100/2 Four-pole RCCBs Current rating (A) Sensitivity (ma) Type Width (mm) Cat. no AC 70 EE40/30/ AC 70 EE40/100/ AC 70 EE40/300/ AC 70 EE63/30/ AC 70 EE63/100/ AC 70 EE63/300/ AC 70 EE100/30/ AC 70 EE100/100/ AC 70 EE100/300/4 100, time delay 100 AC 70 EES100/100/4 Dimensions 4-pole 2-pole 97

100 Circuit Protection Devices Loadline Moulded Case Circuit Breakers Frame YB1N YA2N YA2S YA2J YB3N Maximum amps No. of poles Adjustable thermal N Y N Y Y Y Y Adjustable magnetics N N N Y Y Y N Rated current (A). [In] Nom Adj Nom Adj Adj Adj Adj Adj Adj Adj min max min max min max min max min max Rated impulse withstand voltage Uimp [kv] AC rated insulation voltage [Ui] AC rated breaking capacity Icu Icu Ics Icu Icu Ics Icu Ics Icu Ics Icu Ics IEC V EN V BS EN V V / / V / / V / / V V NEMA AB-1 600V 480V V Without instantaneous V DC rated 250V breaking 125V capacity [ka] Rated short time current r.m.s. [ka] [Icw] Utilisation category A A A A A Notes: *Value at1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown. 98

101 Circuit Protection Devices Loadline Moulded Case Circuit Breakers Frame YA3N YA3S YA3J YA5N YA5H Maximum amps No. of poles Adjustable thermal N Y Y Y Y Y Adjustable magnetics N N Y Y Y N Rated current Nom Adj Adj Adj Adj Adj Adj Adj Adj Adj (A). [In] min max min max min max min max min max Rated impulse withstand voltage Uimp [kv] AC rated insulation voltage [Ui] AC rated breaking capacity Icu Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics IEC V EN V CEI EN V V *** 36*** V *** 36*** V *** 36*** V V NEMA AB-1 600V 480V V Without instantaneous V DC rated 250V breaking 125V capacity [ka] Rated short time current r.m.s. [ka] [Icw] Utilisation category A A A A A Notes: *Value at1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown. ***20A and 32A only rated at 30kA at this voltage. 99

102 Circuit Protection Devices Loadline Moulded Case Circuit Breakers Frame YA5H YA5K Y6H Y6K Electronic Electronic Thermal/ Thermal/ Magnetic and Magnetic Generator Maximum A 800A amps No. of poles Adjustable Y Y Y Y thermal Adjustable Y Y Y Y magnetics Rated current Adj Adj Adj Adj Nom Adj Nom Adj (A). [In] min max min max min max min max Rated impulse withstand voltage Uimp [kv] AC rated insulation voltage [Ui] AC rated Icu Ics Icu Ics Icu Ics Icu Ics breaking symmetrical r.m.s. [ka] IEC V ** 45 23** EN V BS EN V 35 18** 65 33** 415V V V V V NEMA AB-1 600V V V V Without instantaneous V DC rated 250V breaking 125V capacity [ka] Rated short time 5 5 current r.m.s. [ka] [Icw] Utilisation category B B A A Notes: *Value at1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown. 100

103 Circuit Protection Devices Loadline Moulded Case Circuit Breakers Frame Y6H-E Y6J-E Y7J-E Y8K-E Electronic Electronic Electronic Electronic Maximum 800A 800A 1250A 1600A amps No. of poles Adjustable thermal Adjustable magnetics Rated current Nom Adj Nom Adj Nom Adj Nom Adj (A). [In] min max min max min max min max Rated impulse withstand voltage Uimp [kv] AC rated insulation voltage [Ui] AC rated Icu Ics Icu Ics Icu Ics Icu Ics breaking symmetrical r.m.s. [ka] IEC V 20 10** 20 10** 25 19** 35 35** EN V 35 18** 42 21** 45 34** 65 49** BS EN 400V V V V V V NEMA AB-1 600V V V Without instantaneous V DC rated 250V breaking 125V capacity [ka] Rated short time 10 (0.3 sec) 10 (0.3 sec) 15 (0.3 sec) 20 (0.3 sec) current r.m.s. [ka] [Icw] Utilisation category B B B B Notes: *Value at 1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown. 101

104 Circuit Protection Devices Loadline YB1 and YB3 Frame Moulded Circuit Case Breakers YB1 Frame MCCBs (Available 2012) Standard cable termination = 50mm 2 Triple-pole and four-pole have adjustable thermal overloads only Single-pole devices have fixed thermal and magnetic overloads Current rating (A) 1-pole Cat no. 3-pole Cat No. 4-pole Cat no YB1 Frame Switch Disconnector YB1B3P160D YB1B4P160D YB1 Frame MCCB Thermal/Magnetic -Icu 25kA 16 YB1N1P16T YB1N1P20T YB1N1P25T YB1N3P25T YB1N4P25T 32 YB1N1P32T YB1N3P32T YB1N4P32T 40 YB1N1P40T YB1N3P40T YB1N4P40T 50 YB1N1P50T YB1N1P63T YB1N3P63T YB1N4P63T 80 YB1N1P80T YB1N3P80T YB1N4P80T 100 YB1N1P100T YB1N3P100T YB1N4P100T 125 YB1N1P125T YB1N3P125T YB1N4P125T YB1N3P160T YB1N4P160T YB3 Frame MCCBs Standard cable termination = 95mm 2 Maximum cable termination using M8 reduced palm width cable lugs = 150mm 2 Triple-pole and four-pole have adjustable thermal overloads only Current rating (A) 1-pole Cat no. 3-pole Cat No. 4-pole Cat no YB3 Frame Switch Disconnector YB3B3P250D YB3B4P250D YB3 Frame MCCB Thermal/Magnetic -Icu 25kA 50 YB3N3P50T YB3N4P50T 63 YB3N3P63T YB3N4P63T 100 YB3N3P100T YB3N4P100T 125 YB3N3P125T YB3N4P125T YB3N3P160T YB3N4P160T 200 YB3N3P200T YB3N4P200T 250 YB3N3P250T YB3N4P250T Dimensions YB1 1-pole YB1 3-pole and 4-pole YB3 3-pole and 4-pole 102

105 Circuit Protection Devices Loadline YA2 Frame Moulded Case Circuit Breakers YA2 Frame MCCBs Exceeds EN Rated insulation voltage is 800V AC (Ui) Triple and four-pole MCCBs have both adjustable overload and instantaneous trips Standard M8 cable lug termination = 35mm 2 Maximum cable termination = 95mm 2 (using M8 reduced palm width lugs) Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no. YA2 Frame MCCB Thermal/Magnetic I cu 25kA 16 YA2N1P16T N/A N/A 20 YA2N1P20T YA2N3P20T YA2N4P20T 32 YA2N1P32T YA2N3P32T YA2N4P32T 50 YA2N1P50T YA2N3P50T YA2N4P50T 63 YA2N1P63T YA2N3P63T YA2N4P63T 80 YA2N1P80T YA2N1P100T YA2N3P100T YA2N4P100T 125 YA2N1P125T YA2N3P125T YA2N4P125T YA2 Frame MCCB Thermal/Magnetic I cu 36kA 50 YA2S3P50T YA2S4P50T 63 YA2S3P63T YA2S4P63T 100 YA2S3P100T YA2S4P100T 125 YA2S3P125T YA2S4P125T YA2 Frame MCCB Thermal/Magnetic I cu 65kA 20 YA2J3P20T YA2J4P20T 32 YA2J3P32T YA2J4P32T 50 YA2J3P50T YA2J4P50T 63 YA2J3P63T YA2J4P63T 100 YA2J3P100T YA2J4P100T 125 YA2J3P125T YA2J4P125T Dimensions YA2 1-pole YA2 3 and 4-pole 103

106 Circuit Protection Devices Loadline YA2 Frame Accessories YA2 Frame Accessories Description Cable clamps YA2 cable clamps (set of 3) YA2 cable clamps (set of 4) Terminals and protection YA2 1-pole terminal shroud YA2 3-pole terminal shroud YA2 4-pole terminal shroud YA2 terminal barrier YA2 3-pole terminal cover YA2 4-pole terminal cover YA2 3-pole rear terminals YA2 4-pole rear terminals YA2 3-pole extension terminals YA2 4-pole extension terminals Plug-in units YA2 3-pole plug-in terminals YA2 4-pole plug-in terminals YA2 3-pole plug-in base YA2 4-pole plug-in base YA2 3-pole plug-in base extension terminals YA2 4-pole plug-in base extension terminals YA2 3-pole right angle terminals YA2 4-pole right angle terminals Motors and interlocks YA2 motor actuator, V ac YA2 motor actuator, V ac YA2 mechanical changeover, link type YA2 mechanical changeover, manual slide type YA2 mechanical changeover, wire type with 1 metre cable YA2 mechanical changeover, wire type with 1.5 metre cable Auxiliaries YA2 dolly lock YA2 neutral link YA2 rotary handle standard length YA2 rotary handle long length Shunt trips **YA frame shunt trip V AC **YA frame shunt trip V AC **YA frame shunt trip V AC **YA frame shunt trip 24V DC Auxiliary and alarm switches **YA frame 1AB auxiliary switch **YA frame alarm switch Under-voltage release **YA frame under-voltage release V AC **YA frame under-voltage release V AC **YA frame under-voltage release V AC **YA frame under-voltage release 24V DC Cat. no. YA2CC3P YA2CC4P YA2TS1P YA2TS3P YA2TS4P YA2TB YA2TS3P3 YA2TS4PS YA2RT3P YA2RT4P YA2XT3P YA2XT4P YA2PT3P YA2PT4P YA2PB3P YA2PB4P YA2PXT3P YA2PXT4P YA2PRA3P YA2PRA4P YA2MA110 YA2MA240 YA2ML YA2MMS YA2MW10 YA2MW15 YADL1 YA2NL YA2R1 YA2R2 YAST115AC YAST240AC YAST450AC YAST24DC YAAUX1 YAAL YAUVR120AC YAUVR240AC YAUVR450AC YAUVR24DC ** Common to all YA2, YA3, YA5 MCCBs. 104

107 Circuit Protection Devices Loadline YA3 Frame Moulded Case Circuit Breakers YA3 Frame MCCBs Exceeds EN requirements Triple and four-pole MCCBs have both adjustable overload and instantaneous trips Rated insulation voltage 800V AC (Ui) Standard M8 cable lug termination = 95mm 2 Maximum cable termination = 150mm 2 (using M8 reduced palm width lugs) Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no. Max. Min. YA3 Switch Disconnector 250 YA3B3P250D YA3B4P250D YA3 Frame MCCB Thermal/Magnetic - Icu 25kA YA3N1P16T YA3N1P20T YA3N3P20T YA3N4P20T YA3N1P32T YA3N3P32T YA3N4P32T YA3N1P40T YA3N1P50T YA3N3P50T YA3N4P50T YA3N1P63T YA3N3P63T YA3N4P63T YA3N1P80T YA3N1P100T YA3N3P100T YA3N4P100T YA3N1P125T YA3N3P125T YA3N4P125T YA3N1P160T YA3N3P160T YA3N4P160T YA3N3P200T YA3N4P200T YA3N3P250T YA3N4P250T YA3 Frame MCCB Thermal/Magnetic I cu 36kA YA3S3P50T YA3S4P50T YA3S3P63T YA3S4P63T YA3S3P100T YA3S4P100T YA3S3P125T YA3S4P125T YA3S3P160T YA3S4P160T YA3S3P200T YA3S4P200T YA3S3P250T YA3S4P250T YA3 Frame MCCB Thermal/Magnetic I cu 65kA YA3J3P50T YA3JP50T YA3J3P63T YA34J63T YA3J3P100T YA34J100T YA3J3P125T YA34J125T YA3J3P160T YA34J160T YA3J3P200T YA34J200T YA3J3P250T YA34J250T Dimensions YA3 1-pole YA3 3 and 4-pole 105

108 Circuit Protection Devices Loadline YA3 Frame Accessories Description Cable clamps YA3 cable clamps (set of 3) YA3 cable clamps (set of 4) Terminals and protection YA3 1-pole terminal shroud YA3 3-pole terminal shroud YA3 4-pole terminal shroud YA3 terminal barrier YA3 3-pole terminal cover YA3 4-pole terminal cover YA3 3-pole rear terminals YA3 4-pole rear terminals YA3 3-pole extension terminals YA3 4-pole extension terminals Plug-in units YA3 3-pole plug-in terminals YA3 4-pole plug-in terminals YA3 3-pole plug-in base YA3 4-pole plug-in base YA3 3-pole plug-in base extension terminals YA3 4-pole plug-in base extension terminals YA3 3-pole right angle terminals YA3 4-pole right angle terminals Motors and interlocks YA3 motor actuator, V AC YA3 motor actuator, V AC YA3 mechanical changeover, link type YA3 mechanical changeover, manual slide type YA3 mechanical changeover, wire type with 1 metre cable YA3 mechanical changeover, wire type with 1.5 metre cable Castell* mounting kit (lock to be ordered separately) Auxiliaries YA3 dolly lock YA3 rotary handle standard length YA3 rotary handle long length Cat. no. YA3CC3P YA3CC4P YA3TS1P YA3TS3P YA3TS4P YA3TB YA3TS3PS YA3TS3P3 YA3RT3P YA3RT4P YA3XT3P YA3XT4P YA3PT3P YA3PT4P YA3PB3P YA3PB4P YA3PXT3P YA3PXT4P YA3PRA3P YA3PRA4P YA3MA110 YA3MA240 YA3ML YA3MMS YA3MW10 YA3MW15 YACL YADL1 YA3R1 YA3R2 Adapter Kit AA Frame to YA3 Frame For use when replacing existing AA frame with YA3 MCCBs. Description for AA frame kit Poles Cat. no. Loadbank panel board 1 YAA1PLB Loadbank panel board 3 YAA3PLB Type 2 Loadframe switchboard 3 YAA3PLFT2 *Castell is a trademark of Castell Safety International Limited. Note: Shunt trips, UVT, auxiliaries switches, alarm switches - see common accessories page

109 Circuit Protection Devices Loadline YA5 Frame Moulded Case Circuit Breakers YA5 Frame MCCBs Exceeds EN requirements Triple and four-pole MCCBs have both adjustable overload and instantaneous trips Rated insulation voltage 800V AC (Ui) Electronic MCCBs are Category B rated for discrimination No extension terminal bars supplied, see Accessories if required Standard M10 cable lug termination = 95mm 2 Maximum cable termination = 185mm 2 (using M10 reduced palm width lugs) Current rating (A) 3-pole cat. no. 4-pole cat. no. Max. Min. YA5 Switch Disconnector 400 YA5B3P400D YA5B4P400D YA5 Frame MCCB Thermal/Magnetic I cu 25kA YA5N3P250T YA5N4P250T YA5N3P400T YA5N4P400T YA5 Frame MCCB Thermal/Magnetic I cu 50kA YA5H3P250T YA5H4P250T YA5H3P400T YA5H4P400T YA5 Frame MCCB Thermal/Magnetic I cu 65kA YA5J3P250T YA5J4P250T YA5J3P400T YA5J4P400T YA5 Frame MCCB Electronic I cu 70kA YA5K3P250E YA5K4P250E YA5K3P400E YA5K4P400E Dimensions YA5 3 and 4-pole 107

110 Circuit Protection Devices Loadline YA5 Frame Accessories YA5 Frame MCCB Accessories Description Cable clamps YA5 cable clamps (set of 3) YA5 cable clamps (set of 4) Terminals and protection YA5 3-pole terminal shroud YA5 4-pole terminal shroud YA5 terminal barrier YA5 3-pole terminal cover YA5 4-pole terminal cover YA5 3-pole rear terminals YA5 4-pole rear terminals YA5 3-pole extension terminals YA5 4-pole extension terminals Plug-in units YA5 3-pole plug-in terminals YA5 4-pole plug-in terminals YA5 3-pole plug-in base YA5 4-pole plug-in base YA5 3-pole plug-in base extension terminals YA5 4-pole plug-in base extension terminals YA5 3-pole right angle terminals YA5 4-pole right angle terminals Motors and interlocks YA5 motor actuator, V ac YA5 motor actuator, V ac YA5 mechanical changeover, link type YA5 mechanical changeover, manual slide type YA5 mechanical changeover, wire type with 1 metre cable YA5 mechanical changeover, wire type with 1.5 metre cable Auxiliaries YA5 dolly lock YA5 neutral link YA5 rotary handle standard length YA5 rotary handle long length Cat. no. YA5CC3P YA5CC4P YA5TS3P YA5TS4P YA5TB YA5TC3P YA5TC4P YA5RT3P YA5RT4P YA5XT3P YA5XT4P YA5PT3P YA5PT4P YA5PB3P YA5PB4P YA5PXT3P YA5PXT4P YA5PRA3P YA5PRA4P YA5MA110 YA5MA240 YA5ML YA5MMS YA5MW10 YA5MW15 YA5DL YA5NL YA5R1 YA5R2 Note: Shunt trips, UVT and auxiliaries - see common accessories page

111 Circuit Protection Devices Loadline Y6 Frame Moulded Case Circuit Breakers Y6 Frame MCCBs Exceeds the requirements of EN Rated insulation voltage 690V AC (Ui) Electronic MCCBs have adjustable long, short and instantaneous trip functions Electronic MCCBs are Category B rated for discrimination Standard M12 cable termination = 240mm 2 Extension terminal bars to be ordered separately when not used in conjunction with Dorman Smith steel work - Y6XT4P (2 required) Current rating (A) 3-pole cat. no. 4-pole cat. no. Max. Min. Y6 Frame Switch Disconnector 630 Y6B3P630D Y6B4P630D 800 Y6B3P800D Y6B4P800D Y6 Frame MCCB Thermal/Magnetic I cu 50kA Y6H3P400T5 Y6H4P400T Y6H3P630T5 Y6H4P630T Y6H3P800T5 Y6H4P800T5 Y6 Frame MCCB Thermal/Magnetic I cu 85kA Y6K3P400T5 Y6K4P400T Y6K3P630T5 Y6K4P630T Y6K3P800T5 Y6K4P800T5 Y6 Frame MCCB Electronic I cu 50kA Y6H3P630E Y6H4P630E Y6H3P800E Y6H4P800E Y6 Frame MCCB Electronic I cu 65kA Y6J3P630E Y6J4P630E Y6J3P800E Y6J4P800E Dimensions Y6 109

112 Circuit Protection Devices Loadline Y6 Frame Accessories Description Terminal covers 3-pole Terminal shroud (set of 1) Interphase barriers (set of 2) Terminal covers 4-pole Terminal shroud (set of 1) Interphase barriers (set of 3) Terminations 3/4-pole Cable clamps 2 x 185mm 2 only Locking devices Dolly padlock device Castell* lock (DS1 direct mounting) Castell* lock (DS2 direct mounting) Castell* lock door-mounted cam for shaft only Shunt trips Shunt 24V dc Shunt V ac Shunt V ac Undervoltage release UVR 24V dc UVR V ac UVR V ac UVR V ac Motors and interlocks Motor actuator, V ac Motor actuator, V ac Changeover, rocker type Changeover, manual slide type Changeover, wire type with 1 metre cable Changeover, wire type with 1.5 metre cable Auxiliary switches 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Neutral link Y6 Neutral link Rotary handles Standard length Long length Cover flange Handle extension Cat. no. Y6TS3P Y5TB3P Y6TS4P Y5TB4P Y6CC4P Y6DL Y6CLDS1 Y6CLDS2 Y5DCLCAM Y6ST24DC Y6ST115AC Y6ST480AC Y6UVR24DC Y6UVR120AC Y6UVR240AC Y6UVR450AC Y6MA110 Y6MA240 Y6MR Y6MMS Y6MW10 Y6MW15 Y6AUX1 Y6AUX2 Y6AUXAL Y6NL Y6RH1 Y6RH2 Y5CF Y6HE *Castell is a trademark of Castell Safety International Limited. 110

113 Circuit Protection Devices Loadline Y6 Frame Moulded Case Circuit Breakers Changeover Units The changeover pairs are four-pole units fitted with mechanical and electrical interlocking mounted on a back plate. Both devices have a motor actuator and are terminated for front access. All changeover pairs utilise the Y6 range of breakers. Each breaker is fitted with: 1 - Shunt trip 240V AC - Electrical interlock 1 - AB auxiliary switch - to indicate MCCB status 1 - Alarm switch - for auto reset 1 - Motor operator spring charged 240V AC - to drive MCCB 1 - Mechanical interlock (rear) Rating (A) 400A 630A 800A Cat. no. Y6AC400 Y6AC630 Y6AC800 Remote Operation Y Frame Changeover Unit Remote Operation Changeover Unit Dimensions (mm) 111

114 Circuit Protection Devices Loadline Y7 Frame Moulded Case Circuit Breakers Y7 Frame MCCBs Exceeds EN requirements Rated insulation voltage 690V AC (Ui) Electronic MCCBs have adjustable long, short and instantaneous trip functions Electronic MCCBs are Category B rated for discrimination Current rating (A) 3-pole cat. no. 4-pole cat. no. Max. Min. Y7 Frame Switch Disconnector 1250 Y7B3P1250D Y7B4P1250D Y7 Frame MCCB Electronic Icu 65kA Y7J3P1000E Y7J4P1000E Y7J3P1250E Y7J4P1250E Y7 Frame Accessories Description Terminal covers 3-pole Terminal shroud (set of 1) Interphase barriers (set of 2) Terminal covers 4-pole Terminal shroud (set of 1) Interphase barriers (set of 3) Locking devices Dolly padlock device Castell* lock (DS1 direct mounting) Castell* lock (DS2 direct mounting) Castell* lock door-mounted cam for shaft only Shunt trips Shunt V AC Shunt V AC Shunt 24V DC Under-voltage release UVR V AC UVR V AC UVR V AC UVR 24V DC Motor actuators Motor actuator V AC Motor actuator V AC Auxiliary switches 3-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Auxiliary switches 4-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Neutral link Y7 neutral link Cat. no. Y7TS3P Y5TB3P Y7TS4P Y5TB4P Y7DL Y7CLDS1 Y7CLDS2 Y5DCLCAM Y7ST115AC Y7ST480AC Y7ST24DC Y7UVR120AC Y7UVR240AC Y7UVR450AC Y7UVR24DC Y7MA110 Y7MA240 Y7AUX3P1 Y7AUX3P2 Y7AUX3PAL Y7AUX4P1 Y7AUX4P2 Y7AUX4PAL Y7NL *Castell is a trademark of Castell Safety International Limited. Dimensions Y7 112

115 Circuit Protection Devices Loadline Y8 Frame Moulded Case Circuit Breakers Y8 Frame MCCBs Exceeds EN requirements Rated insulation voltage 690V AC (Ui) Electronic MCCBs have adjustable long, short and instantaneous trip functions Electronic MCCBs are Category B rated for discrimination Current rating (A) Type 3-pole cat. no. 4-pole cat. no. Y8 Frame Switch Disconnectors 1600 Front terminals Y8B3P1600D Y8B4P1600D 1600 Rear terminals Y8B3P1600DR Draw out Y8B3P1600DDO - Y8 Frame MCCB Electronic Icu 85kA 1600 Front terminals Y8K3P1600E Y8K4P1600E 1600 Rear terminals Y8K3P1600ER N/A 1600 Ground fault Y8K3P1600EG N/A Y8 Frame Accessories Description Terminal covers 3-pole Terminal shroud (set of 1) Interphase barriers (set of 2) Terminal covers 4-pole Terminal shroud (set of 1) Interphase barriers (set of 3) Locking devices Dolly padlock device Castell* lock (DS1 direct mounting) Castell* lock (DS2 direct mounting) Castell* lock door-mounted cam for shaft only Shunt trips Shunt V AC Shunt V AC Shunt 24V DC Under-voltage release UVR V AC UVR V AC UVR V AC UVR 24V DC Motor actuators Motor actuator V AC Motor actuator V AC Auxiliary switches 3-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Auxiliary switches 4-pole MCCB 1AB auxiliary switch 2AB auxiliary switch Alarm switch + 1 auxiliary Neutral link Y7 neutral link *Castell is a trademark of Castell Safety International Limited. Cat. no. Y7TS3P Y5TB3P Y7TS4P Y5TB4P Y7DL Y7CL Y7CLDS2 Y5DCLCAM Y7ST115AC Y7ST480AC Y7ST24DC Y7UVR120AC Y7UVR240AC Y7UVR450AC Y7UVR24DC Y7MA110 Y7MA240 Y7AUX3P1 Y7AUX3P2 Y7AUX3PAL Y7AUX4P1 Y7AUX4P2 Y7AUX4PAL Y7NL Dimensions Y MIN EARTHED BOUNDARY Mounting hole ASL 3P H L 4P HL MIN EARTHED BOUNDARY N ASL Conductor overlap max. Extension handle (removable) Insulator Mounting angle 30 M8 Mounting screw o ASL H L 4P 3P 70 ø9 Mounting angle max 15 max o

116 Circuit Protection Devices Loadmaster Miniature Circuit Breakers Loadmaster MCBs Current rating (A) 1-pole cat. no. 3-pole cat. no. 10 LM10-20 LM20 LM3P20 30 LM30 LM3P30 40 LM LM60 - Loadmaster Isolators Current rating (A) 1-pole cat. no. 3-pole cat. no LW3 Loadmaster Accessories Description Mounting bracket for MCB/isolator 2-pole Mounting bracket for MCB/isolator 3-pole Cat. no. LMMB2 LMMB3 114

117 Modular Devices DSPM Range Surge Protector DSPM Modular Series Type 2; Class II device DIN-rail mounted - EN50022 Replaceable plug-in modules Protection status indication IP20 ingress protection Remote Indication option available DSPM Surge Protectors Widths (mm) Cat. no. 40kA 1-phase with neutral/earth 35 DSPM1PN 40kA 1-phase with neutral/earth 35 DSPM1PNR & remote indication 40kA 3-phase with neutral/earth 70 DSPM3PN 40kA 3-phase with neutral/earth 70 DSPM3PNR & remote indication 40kA 1-phase 17.5 DSPM1P 40kA 3-phase 52.5 DSPM3P MOV replacement plug-in SPM 17.5 DSPML MOV neutral/earth replacement 17.5 DSPMNE plug-in SPM Dimensions Specification and Dimensions Surge handling capability (8/20µs) 40kA Surge protection technology MOV Nominal voltage rating 1-phase: 230V rms 3-phase: 415V rms Max. continuous operating voltage 1-phase: V 3-phase: V Frequency 48-62Hz Maximum current rating Not applicable (parallel connected) Nominal discharge current, In (8/20µs) 40kA Max. surge current handling, Imax (8/20µs) 40kA Response time <10ns Short-circuit withstand capability 40kA with max. backup fuse (100A gl/gg) Thermal overload protection 120 C Nominal power consumption <10µA Operating temperature -40 to +70 C Protection at 5kA, Up (8/20µs) <1100V peak Protection at Imax (8/20µs) <1600V peak Replaceable modules 2 pin pluggable module Protection status indication Mechanical flag mechanism: Green: full protection Red: no protection Remote status indication option Hard wired Remote indication connections Volt free N/O or N/C contacts Terminals Base 16-35mm 2 Remote 2.5mm 2 Max. Remote signalling terminals 230V rms 1A; 30V DC 2A Module and base material Flame retardant ABS Device style 35mm 2 DIN-rail mounted to EN Category classification (EN ) SPD Type 2 Protection rating IP mm 75 mm 17.5 mm 115

118 Modular Devices DSPE Range Surge Protector Series DSPE 600 Series Low let through voltage of 600 volts Two stage (redundant) protection, with pre-failure indication Site fault condition indicator Remote Monitoring Unit is provided with a 1 metre cable and appropriate plug and socket connectors (other lengths are available on request) Easy installation and field serviceability Compact size and small footprint DSPM Surge Protectors 30kA 2-stage, 3-pole surge protector 30kA 2-stage, 3-pole surge protector, remote terms & monitoring 30kA 2-stage, 3-pole surge protector with aux contact Enclosure for DSP3 surge protection units (240mm (h) x 190mm (w) x 90mm (d)) Cat. no. DSPE600 DSPE600R DSPE600N 2IP Dimensions Specification and Dimensions 165,00 186,50 177,00 10,00 70,00 Voltage rating (Nominal), Un 400V rms Max. continuous operating voltage, Uc L-N 300V rms L-L 500V rms Maximum load current rating Unlimited (parallel connection) Maximum surge current (8/20µs), Imax 30kA per phase Response time <10 ns Power consumption (nominal) 18mA per phase Leakage current to earth 600µA Terminals 16mm 2 max - line, neutral, earth 2.5mm 2 max - remote signalling Remote signalling terminals Rated at 230V rms 0.2A or 30V DC 2A Operating temperature -40 to +70 Celsius Light emitting diodes status indication Green: full protection Red & green: reduced protection Red - no protection Case Steel - epoxy paint Type (EN ) 2 Dimensions (mm) L 176 W 110 D 72 Weight (g)

119 Modular Devices DSPT Range Surge Protector Type 1 DSPT Type 1 Class 1; Type I device Tested to withstand 10/350µs waveforms Description 3-phase & neutral, 25kA L-N, 100kA surge protector Cat. no. DSPT3PN Specification and Dimensions Max. continuous operating voltage (Uc) 275V ac rms Temporary overvoltage (Ut), L-N 335V/5s Temporary overvoltage (Ut), N-PE 1200V/0.2s Response time L-N <25ns Response time N-PE <100ns Max. backup fuse 315A gl/gg Max. backup fuse when V connected 63A gl/gg Short-circuit withstand capability 80ka rms at max backup fuse (Ip) Lightning impulse current, 25kA 10/350µs, L-N (Iimp) - Charge (Q) 12.5As - Specific energy (W/R) 156kJ/Ω Lightning impulse current, 100kA 10/350µs, N-PE (Iimp) - Charge (Q) 50As - Specific energy (W/R) 2500kJ/Ω Total lightning current, 10/350µs 100kA (Itotal), L1,L2,L3,N-PE Max. discharge current, 8/20µs (Imax), L-N 120kA Max. discharge current, 8/20µs (Imax), N-PE 120kA Nominal discharge current, 8/20µs (In) 50kA Voltage protection level at Iimp (Up) <1.3kV Weight (g) 1125 Dimensions 117

120 Modular Devices Switch Disconnectors, Timers, Modular Contactors Exceeds the requirements of EN mm 2 cable capacity Duty category of AC22 Current rating (A) Poles Max. cable (mm) Cat. no AV AV AV AV AV AV AV AV AV4125 Modular Programmable Timers Daily/weekly 2 relays 16A Current rating (A) Width (mm) Function Cat. no. 16A (AC7A) 1 or 2 channel 35 DRT-DW2R Modular Contactors Exceeds the requirements of EN May require de-rating when used with inductive loads see Contactor De-rating table in the Technical Applications section Current rating (A) Width (mm) Contacts Cat. no. 20A P N/O EE2P20CO 20A 35 2P N/C EE2P20CC 25A 35 4P N/O EE4P25CO 25A 35 4P N/C EE4P25CC 40A 54 4P N/O EE4P40CO 40A 54 4P N/C EE4P40CC 63A 54 4P N/O EE4P63CO 63A 54 4P N/C EE4P63CC Venting kit * 9 - LLMV * Ventilation module must be fitted between alternate pairs of contactors to prevent overheating. 118

121 Modular Devices Current Transformers Measuring Current Transformers For use with kilowatt hour metering Up to Class 0.5 accuracy System voltage up to 720V Secondary output 5A Operating temperatures from 20 C to +70 C Current Cable aperture Height Width Cat. no. rating (A) (mm) (mm) (mm) M53Q-100/ M53Q-125/ M55E-30/ M55E M53J-100/5D M53J-125/5D M53J-200/5D M53J-250/5D M63N-400/ M93L-600/ MB5D-800/5 M30-DINCLIP M50-DINCLIP DIN-rail mounting option for M63N/M93L current transformers (2 required) DIN-rail mounting option for MB5D current transformers (2 required) Dimensions M53Q M55E M53J MBD5 M63N M93L 119

122 Modular Devices 3-in-1 Current Transformers 3-in-1 Current Transformers For use with metering Space saving 3-in-1 design Up to 5A class Secondary output 5A Plug-in metal feet, DIN-rail clips and busbar mounting options supplied as standard Part number Ratio Burden VA against Aperture class index (mm) Class Class Class M3N /5 60/ @15 x 25mm M3N /5 100/ @15 x 25mm M3N /5 125/ @15 x 25mm M3N /5 160/ @15 x 25mm Part number Ratio Burden VA against Aperture class index (mm) Class Class Class M3N /5 100/ @21 x 25mm M3N /5 125/ @21 x 25mm M3N /5 160/ @21 x 25mm M3N /5 200/ @21 x 25mm M3N /5 250/ @21 x 25mm Part number Ratio Burden VA against Aperture class index (mm) Class Class Class M3N /5 250/ @31 x 31mm M3N /5 300/ @31 x 31mm M3N /5 400/ @31 x 31mm M3N /5 500/ @31 x 31mm M3N /5 630/ @31 x 31mm Dimensions M3N1-25 M3N1-35 M3N

123 Modular Devices Split Core Current Transformers A range of split core current transformers that offers a cost effective and efficient method by which the current can be measured without the need to break the conductor, thereby reducing installation and commissioning time. Accuracy Class Part number Ratio Burden VA against class index Aperture (mm) Case 1 Case 2 Case 3 Case SC1-100/5A 100/5A x 30 SC1-150/5A 150/5A x 30 SC1-200/5A 200/5A x 30 SC1-250/5A 250/5A x 30 SC1-300/5A 300/5A x 30 SC1-400/5A 400/5A x 30 SC2-250/5A 250/5A x 80 SC2-300/5A 300/5A x 80 SC2-400/5A 400/5A x 80 SC3-250/5A 250/5A x 80 SC3-300/5A 300/5A x 80 SC3-400/5A 400/5A x 80 SC3-500/5A 500/5A x 80 SC3-600/5A 600/5A x 80 SC3-750/5A 750/5A x 80 SC3-800/5A 800/5A x 80 SC3-1000/5A 1000/5A x 80 SC4-500/5A 500/5A x 120 SC4-600/5A 600/5A x 120 SC4-750/5A 750/5A x 120 SC4-800/5A 800/5A x 120 SC4-1000/5A 1000/5A x 120 SC4-1200/5A 1200/5A x 120 SC4-1250/5A 1250/5A x 120 SC4-1500/5A 1500/5A x 120 SC4-1600/5A 1600/5A x 120 Dimensions Dimension Case 1 Case 2 Case 3 Case 4 A B C D E F G H I Weight (Kg) Units of measurement mm 121

124 Earth Leakage Relay DIN-rail Mounted Precision digital protection relay Adjustable sensitivity of 30mA to 10A Adjustable time delay from 0 to 10 seconds Double-pole relay contacts 8A, 250V Supply voltage V AC/DC (50/100Hz) Frequency (Hz) Auxiliary supply (V) Cat. no AC/DC ELR1 Specification Connections Remote reset switch The equipment grounding conductor must bypass the CT Fused Auxiliary supply Relay 1 Relay 2 GND Link to energise on trip Commissioning Meter Measuring input From core balanced current transformer Overload 20 x nominal for 1 second Frequency 50Hz or 60Hz ±10% Auxiliary voltage V ac and dc Auxiliary burden Less than 1.5 Watts Trip current settings Selectable 30mA, 100mA, 200mA, 300mA, 500mA, 1A, 2A, 3A, 5A, 10A Trip accuracy 50% <trip point current <100% in accordance with IEC 1543 Trip response time <40ms (at 5 x rated trip current, ignoring the selected time delay) Time delay set points Selectable 0ms, 50ms, 100ms, 150ms, 200ms, 300ms, 400ms, 500ms, 600ms, 700ms, 800ms, 900ms, 1 second, 2 seconds, 5 seconds, 10 seconds. When 30mA leakage is selected, the time delay is disabled Indication 5 yellow LED bar graph for leakage levels Red LED indicated trip function Green LED indicated auxiliary power presence Red LED pre-alarm indication (SPCO version only) Relay contacts Standard: 2-pole change over Option: 2 1-pole change over (pre-alarm and main alarm) Relay contact rating 8 amps at 250V ac 8 amps at 30V dc resistive Relay mechanical life >100,000 operations Analogue output 0 to 1mA = 0 to 100% of selected tripping level. Compliance 1V, accuracy 10% Enclosure style DIN 43880, rail width 70mm Compliant with EMC and LVD, UL File No: E203000, CSA 22.2/ BSEN , BSEN , IEC (BS5992), IEC , BSEN (IEC 1543), BSEN (IEC 1010), EN (IEC 68) Material Flame retardant UL94V0 Terminals 1 to 4mm 2 solid or stranded conductors. IP20 protection Operating temperature 10 C to +60 C Storage temperature 20 C to +70 C Relative humidity <95% non condensing Weight <250g Dimensions 71mm wide x 90.5mm high x 73mm deep 2.79" wide x 3.56" high x 2.87" deep Dimensions 110.0mm 4.32" 73.0mm 2.87" 71.0mm 2.79" 62.5mm 2.46" 46.0mm 1.87" 90.5mm 3.56" mm 1.3" 48.0mm 1.89"

125 Modular Devices Core Balance Current Transformers Core Balanced Current Transformers For use with ELR1 earth leakage protection relay Leakage measurement range 0 to 10A Integral wire-sealable terminal cover Flame retardant, high impact moulded case Current Dim E Dim A Dim B Dim C Dim D Cat. no. rating Aperture Width Height Depth (A) (mm) (mm) (mm) (mm) CBT-94F CBT-94F CBT-94F CBT-94F-140 Specification System voltage 720V maximum Test voltage 3kV ac for 1 minute System frequency 50Hz or 60Hz Primary ratings From 30mA to 10A Secondary terminals Protected to IP20 Operating temperature 10 C to +50 C Enclosure UL94V0 flame retardant plastic Compliant with IEC185, VDE 0414 Mounting hardware Steel mounting feet for wall or base mounting Dimensions A 33 B øe C D

126 Modular Devices Integra Ci1 Energy Meter The Integra Ci1 energy meter is specially designed and developed as a cost effective Watt hour and VAr hour meter to complement the current Integra Ci digital metering system (dms). The Integra Ci1 self-contained 96mm DIN panel mounted Watt hour, VAr hour meter measures the real consumption of active and reactive energy to Class 1.0 accuracy. The backlit LCD screen displays 8 character counter indicating Watt hour or VAr hour units. The optional modules enables transfer of energy measurements to building management systems (BMS) via pulsed or digital communication options. Programmable Functions Integra Ci1 meter provides simple programming to suit single phase 2-wire, threephase three wire and three-phase four-wire un-balanced system configurations, CT ratio settings and configuration of selected communication options. To prevent unauthorised access to the product configuration settings, all set-up screens offer password protection. Display Direct access to display the programmed set CT ratio, Watt hours import and export, VAr hours import and export and the phase sequence test routine for both voltage and current phases. During the accumulation of the Wh or VArh the running icon will flash at a rate dependant on the displayed parameter. Plug-in Modules Plug-in modules allow to fit either maximum of two isolated pulsed output relays or a RS485 communication module and one isolated pulsed output relay. The communication output module can be programmed internally to respond either to Modbus RTU or Johnson Controls protocols. Panel Mounting Integral retention clips allow fast, safe and secure panel mounting in various material thicknesses without the need for external screws or clips. Product Code Parameters Button Screen Parameters CT 1 CT ratio Wh 2 IMPORT Wh 3 EXPORT Wh VArh 4 IMPORT VArh 5 EXPORT VArh TEST 6 Phase sequence diagnostic Description Integra Ci1 base unit with pulse output Options Optional plug-in pulse output module Optional RS485 Modbus plug-in module Accessories IP65 protective cover IP54 panel gasket Dimensions Part number CI1-01-PUL CI-PUL-01 CI-MOD-01 3G C34501 Running icon indicates Wh and VAhr accumulation

127 Modular Devices Integra Ci3 Digital Metering System The Integra Ci3 digital metering system (dms) represents the first model of a new generation of digital metering systems designed to complement the current Crompton Instruments Integra series. The Integra Ci3 meter is an accurate and cost effective solution for measurement and display of all major electrical and power quality parameters. Designed, developed and manufactured in the UK, the Integra Ci3 dms builds on Crompton Instruments long established reputation for metering product quality. The product features a DIN 96 panel mounted enclosure, backlit LCD screen and user programmable CT ratios, all accessible via an intuitive user interface. Integra Ci3 dms measures 17 electrical parameters including total harmonic distortion (THD) up to the 31st harmonic. Programmable Functions Integra Ci3 dms is programmable to suit single-phase two-wire, three-phase three-wire and three-phase four-wire system configurations. Programmable CT ratios enable to display any current range. Display The parameters can be viewed on a backlit LCD screen. The 15 screens are accessible via four buttons on the front panel allowing to scroll between various screens making the navigation very user-friendly, intuitive and above all simple. Plug-in Modules Integra Ci3 dms offers two output ports at the rear of the product, to allow the fitting of either two isolated pulsed output relays or a RS485 communication module such as Modbus or Johnson Controls communication output. These are configurable via internal settings. Panel Mounting Integral retention clips allow fast, safe and secure panel mounting in various material thicknesses without the need for external screws or clips. Product Code Description Integra Ci3 base unit with pulse output Options Optional plug-in pulse output module Optional RS485 Modbus plug-in module Part number CI3-01-PUL CI-PUL-01 CI-MOD-01 Accessories IP65 protective cover 3 G IP54 panel gasket 3 C Dimensions Parameters Button Screen Parameters V/Hz 1 Volts L1 - N Volts L2 - N Volts L3 - N 2 Volts L1 - L2 Volts L2 - L3 Volts L3 - L1 3 Frequency 4 Volts L1 - N THD% Volts L2 - N THD% Volts L3 - N THD% 5 Volts L1 - L2 THD% Volts L2 - L3 THD% Volts L3 - L1 THD% A 1 Current L1 Current L2 Current L3 2 Neutral current 3 L1 Current max Demand L2 Current max Demand L3 Current max Demand 4 Neutral current max demand 5 Current L1 THD% Current L2 THD% Current L3 THD% P/PF 1 kw kvar kva 2 kw Max demand 3 Power factor E 1 kwh 2 kvarh 125

128 Modular Devices Integra 1630 Digital Metering System Multi-function Integra 1630 digital metering system provides high accuracy 0.2% measurement, display and communication of all major electrical and power quality parameters including total harmonic distortion (THD) up to the 31st harmonic. To suit user requirements, the range includes single-phase, three-phase three-wire and three-phase four-wire capability, all selectable at the point of installation. Features Auxiliaries: 100/250V ac/dc (12/48V dc optional) Options: Profibus TM, Modbus TCP, Bacnet IP, RS485, Pulsed output Product Description and Order Codes Measured Parameters System (average) volts System (average) current System (total) kw System volts (average) THD% System current (average) THD% Phase neutral Voltage (VL-N) (4 wire only) Phase phase Voltage (L-L) (3 wire only) Voltage THD% (4 wire only) Phase current Current THD % Neutral current (4 wire only) Frequency Power factor (overall) kvar kva kw kwh import (7-digit resolution) kvarh import (7-digit resolution) kwh export (7-digit resolution) kvarh export (7-digit resolution) kw demand Current demand Maximum kw demand Maximum current demand Hours run Description 1-phase, 3-phase 3/4-wire, V L-L, 5A CT input, Aux V ac/dc Cat. no. INT-1630-M-5-M-option Options No options pulsed output 100 RS485 interface Modbus kWhr pulsed output Extended collar OPT-1630-collar Dimensions Modbus, Profibus TM and Bacnet are trademarks 126

129 Modular Devices Modular Devices Kilowatt Hour Energy Meters DIN-rail Self-contained energy metering system which is ideal for switchgear, plant instrumentation and process control. The range has significant advantages over the traditional energy meters with pulsed outputs, communications and direct connection all available as options. Description Cat. no. Single-phase: 230V CT Connected 5A 1-phase CT 5A pulse output DRK-1PCT-240 Pulsed output (Opto), Mechanical counter Three-phase: 400V (+N) CT Connected 5A 3-phase 3 or 4-wire system, DRK-3PCT-415 5A CT connected, pulsed output (Opto), mechanical counter 3-phase 3 or 4-wire system, DRK-3PCT-415-LCD 5A CT connected, pulsed output (Opto), LCD screen Single-phase: 230V Direct Connected 63A 1-phase 230V 63A direct DRK-1P-230-D63 connected, pulsed output (Opto) LCD screen Three-phase: 230V (400V) Direct Connected 100A 3-phase 230V L-N (400V L-L) DRK-3P-400-D A direct connected, pulsed output (Opto), LCD screen Dimensions DRK-1PCT-240 DRK-3PCT-415/ DRK-3PCT-415-LCD DRK-1PCT-230-D63 DRK-3PCT-400-D90 127

130 Modular Devices Integra Ri3 Digital Metering System The product features a DIN-rail enclosure, backlit LCD display and user programmable CT ratios, all accessible via an intuitive user interface. Integra Ri3 dms measures 17 electrical parameters including total harmonic distortion (THD) measurement up to the 31st harmonic. Specifications Features DIN-rail enclosure DIN Backlit LCD screen Programmable CT ratio True rms measurement User programmable system configuration Pulsed output and Modbus as standard Benefits Cost effective Simple navigation Crompton renowned quality UK manufactured Dimensions Input Nominal input voltage V AC L-N ( V AC L-L) Max. continuous input 120% of nominal overload voltage Max. short duration input voltage 2 x range maximum (1 second application repeated 5 times at 5 minute intervals) Nominal input voltage burden < 0.2VA per phase Nominal input current 5A AC rms Max. continuous input 120% of nominal overload current Max. short duration input current 10 x nominal (1 second application repeated 5 times at 5 minute intervals) Nominal input current burden < 0.6VA per phase Frequency 45-66Hz System CT primary values 1 to 9999 Auxiliary Operating range V AC nominal +/-10% (99-440V AC absolute limits) or V DC +/-20% (96-420V DC absolute limits) Burden < 10VA/5W Accuracy Voltage (V) 0.5% Current (A) 0.5% Neutral current calculated (A) 4% Frequency (Hz) 0.1 Hz Power factor (PF) 1% of unity Active power (W) +/- 1% of range Reactive power (VAr) +/- 1% of range Apparent power (VA) +/- 1% of range Active energy (kwh) Class 1 (IEC ) Reactive energy (kvarh) +/- 1% of range THD 1% up to 31st harmonic Response time 1sec Output Pulse output relay 1 Contact rating 50mA max at 250V AC Type Solid state relay RS485 Modbus output module 1 Modbus channel Type 2-wire half duplex Baud rate 2400, 4800, 9600, 19200, Enclosure Enclosure style DIN-rail Dimensions 72x90mm (width x height) as per DIN Front protection rating IP52 Case protection rating IP30 Material Polycarbonate to UL94V0 Weight 300g Terminals Shrouded screw-clamp mm wire Environment Operating temperature -10 C to +55 C Storage temperature -20 C to +70 C Relative humidity 0-90% non-condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz Dielectric voltage Withstand test 3.25kV rms 50Hz for 1 minute between comms and measuring inputs, comm and aux, aux and measuring inputs 128

131 Section 8 MCB and MCCB General Purpose Enclosures

132 General Purpose Enclosures 1 2 General Purpose MCB/Modular Units Enclosures Construction Picture Number HxWxD Weight Cat. no. of ways (mm) (kg) Sheet steel x134x LLMGPS6S Insulated, IP4X x50x LLMGPI2 Insulated, IP4X 4 130x86x LLMGPI4 Insulated, IP4X x214x LLMGPI8 Insulated, IP x125x LLMGPW5 Insulated, IP x214x LLMGPW8 3 4 General Purpose MCCB Enclosures A Accepts all YA3 devices up-to 250A (as per page 107) IP4X rated Spreading room for 150mm 2 Construction Device HxWxD Weight Cat. no. type (mm) (kg) Sheet steel - surface YA3 687x263x LLGPYA3 Note: LLGPYA3 requires neutral link YA3NL to be ordered separately. General Purpose MCCB Enclosures 400A-800A Accepts all YA5 & Y6 devices up-to 800A (pages 109 and 111) IP4X Neutral link included Spreading room for 240mm 2 Construction Device HxWxD Weight Cat. no. type (mm) (kg) Sheet steel YA5/6 1060x420x LLGPYA56 Note: For terminating two parallel cables with YA5 frame please order extension terminals (YA5XT3P) separately. Dimensions 130

133 Section 9 Technical Data & Applications

134 132

135 Technical Data & Applications Index Compliance with International Standards 134 Standard Terminology 135 Current Carrying and Switching Devices 137 Miniature Circuit Breakers (MCBs) 140 Residual Current Circuit Breakers (RCCBs) 145 Modular Contactors 147 Moulded Case Circuit Breakers (MCCBs) 151 Motor Starting Applications (MCCBs) 152 Discrimination and Cascading 153 System Sizing and Diversity 160 Prospective Short-circuit Current 161 Earth Fault Protection including MCCB Max Zs 164 Forms of Separation 167 Ingress Protection 169 Loadline MCCB Insulation Data 170 Loadline YA2 Frame MCCB Characteristics 171 Loadline YA3 Frame MCCB Characteristics 172 Loadline YA5 and Y6 Frame MCCB Characteristics 173 Loadline Y7 and Y8 Frame MCCB Characteristics

136 Compliance with International Standards Dorman Smith branded products comply with internationally recognised technical and quality standards to ensure that each product is fully capable of meeting the relevant standard requirements for its intended use. The design, manufacture, procurement, supply and servicing of Dorman Smith branded products is also governed by compliance to an international standard through the operation of a Quality Management System. Quality Management System BS EN ISO 9001:2008 The Institute of Electrical Engineers (IEE) British Standard BS 7671 addresses Requirements for Electrical Installations and dictates that all relevant products must comply with applicable British, International or Harmonised Standards according to the intended installation and application of the equipment. The BS 7671 document is commonly referred to as The Wiring Regulations. Products are type tested, manufactured, routinely tested and assembled in accordance and compliance with a number of relevant Harmonised Standards recognised by the electrical industry. A Harmonised Standard is a European Standard formally presented by the European Committee for Electrotechnical Standardisation, CENELEC, to the European Commission and published in its official journal. These documents are denoted by the prefix EN (European Norm). The products listed within this catalogue conform to appropriate electrical and mechanical standards as follows: MCB Distribution Boards EN Panel Boards EN MCBs EN MCCBs EN Switches EN RCCBs EN RCBOs EN Contactors EN In addition to the above, and where appropriate, Dorman Smith branded products also comply with the relevant requirements of the standard for protection against physical, mechanical and liquid ingress as follows: Ingress Protection EN

137 Standard Terminology The Harmonised Standard EN and the IEE Wiring Regulations BS 7671:2008 contain references to a set of adopted standard terminology for the principal device parameters with regard to MCBs. This terminology is also embraced by other standards with regard to MCCBs and switches (EN and EN ). The standard terminology relates to the following parameters: Rated Operational Voltage, U e Rated Insulation Voltage, U i Rated Current, I n Rated Short Circuit Capacity, I cn Rated Service Short Circuit Breaking Capacity, I cs Rated Ultimate Breaking capacity, I cu Rated Voltage and Current Rated Operational Voltage, U e The nominal voltage of the system should not exceed the stated value of U e. For example: single-pole U e = 230/400V, three-pole U e = 400V. The standardised values of 230V and 230/400V will progressively replace 240V, 220/380V and 240/415V. Rated Insulation Voltage, U i This is the voltage upon which the dielectric properties are based, using tests at high voltage and mains frequency. Unless otherwise stated, the rated insulation voltage is the value of the maximum rated voltage of the circuit breaker. In no case shall the maximum rated voltage exceed the rated insulation voltage. Rated Current, I n This is the current that the circuit breaker will carry continuously under specified conditions and upon which the time/current characteristics are based. Unless otherwise stated, this value is based upon a reference ambient temperature of 30 degrees Celsius. EN Standard refers to the following terms: Short Circuit Capacity Rated Short Circuit Capacity, I cn The calculated prospective fault current at the incoming terminals of the circuit breaker should not exceed the stated value. For example: I cn = 10kA (marked 10000). Service Short Circuit Breaking Capacity, I cs This value is the maximum level of fault current operation, after which further service of the device is assured without loss of performance. Note that there is no requirement for I cs to be marked on the device. There is a proscribed relationship between I cs and I cn, as follows: For values of I cn up to 6000A I cs = I cn For values of I cn 6000A to 10000A I cs = 0.75I cn (but with a minimum value of I cs = 6000A) For values of I cn above 10000A I cs = 0.5I cn (but with a minimum value of I cs = 7500A) 135

138 The EN and EN Standards also refer to the following terms. Isolation Suitability These define the requirements for the suitability of circuit breakers to perform isolation duty by defining tests to which such units must comply. Conforming devices must carry a standard symbol mark to show that they are suitable for isolation duty. For example, all Dorman Smith circuit breakers are so marked. Utilisation Categories The utilisation category of a circuit breaker is stated with reference to whether or not it is specifically intended for discrimination by means of an intentional time delay with respect to other circuit breakers in series on the load side under short-circuit conditions. Category A This designates circuit breakers not specifically intended for selectivity with devices on the load side. Circuit breakers will discriminate only up to certain fault levels, above which discrimination with devices on the load side cannot be guaranteed. Category B This designates circuit breakers specifically intended for selectivity with devices on the load side. Such circuit breakers will incorporate some form of time delay. EN recognises both a rated service and a rated ultimate short circuit breaking capacity for both Category A and Category B circuit breakers. Rated Service Breaking Capacity, I cs In order to define this value, the circuit breakers under test must be subjected to a test sequence of: I cs = o t co - t co, where: o = opening time under fault conditions t = time interval before re-closing (not more than 3 minutes) c = closing operation on to a fault After this test sequence, dielectric, terminal temperature and over-current tests are to be applied. The circuit breaker must meet certain test parameters to ensure that the device has not deteriorated in performance and can be put back into service. Rated Ultimate Breaking capacity, I cu In order to define this value, the circuit breakers under test must be subjected to a test sequence of: I cu = o t co. After this test sequence, dielectric and over-current tests are to be applied. The rated service breaking capacity (I cs ) applies to short circuit faults that could occur in practice; whereas the ultimate short circuit capacity (I cu ) is the maximum theoretical fault value of the installation at the point of connection. The standard defines the ratio between the two values. I cs will be shown as 25%, 50%, 75% or 100% of its I cu value for Category A devices and 50%, 75% or 100% of I cu for Category B devices. A circuit breaker can remain in service after interrupting a short circuit up to its rated value of I cs. However, where two or more faults occur between the I cs and I cu values, the capability of the device for continued operation must be verified. 136

139 Current Carrying and Switching Devices Switch A switch is a mechanical device capable of making, carrying and breaking current under normal circuit conditions. Disconnector (Isolator) A disconnector is a mechanical switching device that provides the function of circuit isolation. Switch Disconnector This device combines the functionality of the two foregoing devices; it provides making, carrying, breaking and isolation of current within a circuit. Fuses Fuses can be combined with any of the above devices in any physical order. The inclusion of a fuse will add the functionality of short circuit protection, breaking the circuit when the current flow is higher than that for which the circuit is rated. Combination Devices In order to enhance circuit protection, switches and fuses are often combined within a single device. The physical composition of the device can be identified by the literal position of the words in its description. For example, the word fuse at the beginning of the device description identifies the fuse as forming part of the moving contact system, whereas placing it at the end of the description identifies the fuse as a static link. Functional Summary Term Features Features provided not provided Switch Current rating Isolation Operational and insulation voltage Protection Making and breaking of load Short time current rating Disconnector Current rating Protection Isolation Making/breaking capability Operational and insulation voltage Short time current rating Fuse Overload protection Switching Short circuit protection Suitability for Purpose All of these devices have the ability to carry rated current either continuously or for a period of eight hours under defined conditions. Selection and specification of a specific device depends upon the circuit application. 137

140 Function Switching Applications For switching applications, the principal functions and capabilities include: Making and breaking operation A switch must have the ability to make or break defined load and overload currents at a rated operational voltage, for the useful life of the device. Short circuit action The device must have the capability of handling short circuit current and/or through fault and/or fault making. Protection The device must interrupt the circuit under overload and/or short circuit conditions. Isolation To meet this requirement, the device must ensure disconnection of the supply for safe downstream working. Facilities must be included for safety padlocking in the off position, together with positive indication of the contact position. Neutral switching Where the neutral is reliably earthed, it is accepted that the neutral need not be switched except in defined circumstances (e.g. the incoming switch disconnector in a consumer unit) even though the Wiring Regulations (BS 7671:2008) class the neutral as a current carrying conductor. In applications where the neutral cannot be confirmed as reliably earthed, the neutral should be switched simultaneously with the phase(s) or alternatively arranged to make before and break after the phase(s). Fuse Combination Unit 138

141 Utilisation Category The utilisation category defines the basic circuit conditions and the switching capability of the device. Category AC20/DC20 AC21/DC21 AC22/DC22 AC23/DC23 Circuit/application Connecting and disconnecting under no load. Assumes all switching operations are carried out by other capable devices before this device is operated. Switching of resistive loads including moderate overloads. Suitable for purely resistive type loads. Device can switch 150% of its rated current under fault conditions. Switching of mixed resistive/inductive loads, including moderate overloads. Suitable for mixed resistive/inductive loads. Device can switch 300% of its rated current under fault conditions. Switching of highly inductive loads. These devices are provided principally as back-up to other means of switching, e.g. contactors. In the event of failure of the functional device, the AC23/DC23 device can safely interrupt a stalled motor current. Where devices are the only means of controlling individual motors they should comply with the requirements of Appendix A of the EN standard. Note: Switch disconnectors for AC21/DC21, AC22/DC22 and AC23/DC23 categories also have to meet the requirements of AC20/DC20. For specific and special applications such as switching of capacitors and tungsten lamps not covered by the EN standard, the manufacturer s advice should be sought. Frequent and Infrequent Use The designation A or B should be appended to utilisation categories to indicate the suitability for frequent or infrequent use in service. The Rule of Thumb definition for full load current switching duty is: Frequent (A): Up to five times a day for small devices, say up to 100 amps, and once per week for larger devices. Infrequent (B): One per week for the smaller devices and once per month for the larger devices. 139

142 Miniature Circuit Breakers (MCBs) In general terms, circuit breakers are thermal/magnetic electromechanical devices that provide current making, carrying and breaking functions and will trip to interrupt a circuit under abnormal conditions. MCBs are equipped with positive contact indication flags: red indicates that the contact(s) are closed, green indicates the open state. The contact(s) will open when tripped due to abnormal circuit conditions or can be manually put into the open state by use of a handle. These devices are used to provide protection and control of circuits against overload and short circuit conditions. Dorman Smith MCBs are supplied with various breaking capacities, particularly for ratings of 6kA and 10kA. The lower rated devices are used typically in domestic installations, e.g. in consumer units, whereas the higher rated devices are suitable for a range of commercial and industrial circuit protection applications. The thermal and magnetic trip functions cater for different circuit abnormalities and operate as follows: Thermal Trip Function The purpose of this form of protection is to interrupt the circuit upon sensing an overload current. Typically, a bi-metallic strip is used such that it will deflect due to differential expansion of the dissimilar metals in response to the heating effect caused by the passage of current through it. The higher the current, the greater will be the heating effect and the more the deflection. At a preset point the physical deflection will be sufficient to actuate the tripping mechanism, opening the contact(s) and interrupting the circuit. Magnetic Trip Function The purpose of this form of tripping is to protect against the effects of short circuit fault currents. A wire coil or solenoid is used to provide this function, operating the trip mechanism when the over-current reaches a preset magnitude. As the fault current rapidly increases, the magnetic field also increases, energising the coil and moving a cam that is part of the contact assembly to fully open the contact(s) thereby interrupting the circuit. Characteristics MCBs are designed according to one of three distinct tripping characteristics designated B, C or D. These designations relate to the magnetic trip setting and indicate the multiple of nominal current that will be tolerated by the device before tripping. The following table illustrates these characteristics with typical duties and applications. The nominal rated current is denoted by the symbol In. Type Magnetic Application trip B 3-5 In Light duty, resistive loads C 5-10 In Fluorescent lights, small motors, inductive loads D In Sodium lights, large motors (>3kW), large inductive loads 140

143 MCB Tripping Characteristics B, C and D Types B C D The tripping time for the thermal release is defined according to specific values of applied overload current, as follows: Text current Tripping time 1.13In >1h (In < 63A) >2h (In > 63A) 1.45In <1h (In < 63A) <2h (In > 63A) 2.55In 1s<t<60s (In < 32A) 1s<t<120s (In > 32A) MCB Add-on Functions Various accessories can be added to MCBs to enable remote access and signalling. For example, the contact status could be relayed to an alarm annunciator panel or SCADA system; the circuit breaker could be controlled also from the SCADA system. Auxiliary Contacts Relaying of contact status can be achieved by the addition of an auxiliary contact and the contact form selected to suit the remote system input requirements. Shunt Trip The addition of a shunt trip allows remote access to the breaker operation, permitting the supervisory system to manually trip the breaker. The shunt trip actuator is a coil that is normally de-energised in the closed (on) state. When activated, the shunt trip will force the breaker to its off state and the toggle handle and indicator flag will move to this corresponding position. Since the fail-safe (i.e. non-powered) state of a shunt coil is with the breaker remaining closed, this precludes its use for emergency stop purposes. The interconnecting wiring could be open-circuit, for example, and would therefore not allow the shunt to open the breaker when the remote emergency switch is closed. Under-voltage Release If the supply voltage dropped to a low level and devices tripped, a dangerous situation could exist if the devices were automatically reset. For example, motors could suddenly restart or other operating machinery set in motion without warning. In the event that the mains voltage should drop significantly below its normal operating range, typically to less than 50%, an under-voltage release will force the breaker to its off state and the toggle handle and indicator flag will move to this corresponding position. Only when the supply has returned to, typically, at least 85% of normal operating voltage will the under-voltage release allow the breaker to be closed. If a break occurred in the interconnecting wiring in this case, the breaker would be tripped, just as if the voltage had fallen below the threshold value. For this reason, it is advisable to include an alarm function when using a UVR function. 141

144 I I Energy Let-through An important facet of circuit protection devices is the extent to which they limit the amount of electrical energy they allow to pass through them. This applies to fuses as well as to circuit breakers. When an electric current flows through a resistance for a certain time, energy is produced in the form of heat. This thermal effect can be measured using the formula: I 2 x R x t, to give a quantity in Watt seconds. The unit of measurement for energy is the Joule, which is equivalent to one Watt second. For all practical purposes, the resistance is treated as constant and negligible; therefore the commonly accepted term for energy let-through of a device is I 2 t since this will always be proportional to the true thermal effect. The I 2 t term is referred to as the Joule Integral since the results are expressed in integral form. Under short-circuit fault conditions there is the potential for considerable energy to be let through by a circuit protection device. Knowledge of the energy letthrough characteristics of circuit protection devices is useful for comparison between different devices and also with regard to the selection of devices that are required to act in co-ordination to produce the levels of discrimination required for fault clearance. The I 2 t characteristics of circuit breakers are depicted as curves, graphed against values of prospective short-circuit current. These characteristics are relevant to both MCBs and MCCBs as depicted in the following graphs. Energy Let-through Characteristics I t/as I t/as 4 3 Ip/A 4 3 Ip/A 2 2 M ax. operating 2 I t (A 2 s) B63 B50 B40 B32 B25 B20 B16 B10 B13 B6 M ax. operating 2 t (A 2 s) C63 C50 C40 C32 C25 C20 C16 C10 C13 C Prospective current I (A) p Prospective current I (A) p I t/as 4 3 Ip/A M ax. operating 2 t (A 2 s) D32 D25 D20 D16 D10 D13 D Prospective current I (A) p 4

145 Within the EN standard, circuit breakers with B and C characteristics are categorised into energy limiting classes 1, 2 and 3, with Class 3 denoting devices having the lowest energy let-through. The appropriate energy class is marked within a square box on conforming devices. Dorman Smith MCBs are categorised within Class 3. The following table indicates the maximum energy let-through values permissible in each class, stated in Watt-seconds. In practice, compliance with the standard is checked on the circuit breakers with the highest applicable rated current within the range, normally 40A. Rated Current Class 1 Class 2 Class 3 short- rating (A) I 2 t max. I 2 t max. I 2 t max. circuit B type and B type C type B type C type capacity C type 6kA , ,000 35,000 42, No 130, ,000 45,000 55, limits 156, ,000 54,000 66,000 10kA 1-16 specified 240, ,000 70,000 84, , ,000 90, , , , , ,000 Effect of the ambient temperature on the tripping characteristic 70 T/ C I(x C) k= I(30 C) Correction factor is valid for current with times over 30 s I(x C) - test current at x ambient temperature I(30 C) - test current at 30 C ambient temperature I n Ambient temperature T/ O C [A] ,5 0,61 0,6 0,59 0,57 0,56 0,54 0,52 0,5 0,47 0,44 0,41 0,38 1 1,22 1,2 1,18 1,15 1,12 1,09 1,05 1 0,94 0,88 0,82 0,75 1,6 1,95 1,92 1,89 1,84 1,79 1,74 1,68 1,6 1,51 1,42 1,32 1,2 2 2,44 2,4 2,36 2,30 2,24 2,18 2,1 2 1,88 1,77 1,65 1,5 4 4,88 4,8 4,72 4,61 4,49 4,36 4,20 4 3,77 3,55 3, ,32 7,2 7,09 6,91 6,73 6,54 6,31 6 5,66 5,33 4,94 4, , ,8 11,5 11,2 10,9 10,5 10 9,44 8,89 8,23 7, ,9 15,6 15,4 14,9 14,5 14,1 13, ,2 11,5 10,7 9, ,5 19,2 18,9 18,4 17,9 17,4 16, ,1 14,2 13, , , ,4 21, ,8 17,7 16, ,5 30 2,5 28, ,2 26, ,6 22,2 20,6 18, ,4 37,8 36,9 35,9 34,9 33, ,2 28,4 26, , ,8 46,1 44,9 43, ,7 35,5 32, ,1 57,6 56,1 54,5 52, ,2 44,4 41,2 37, ,9 75,6 74,4 72,6 70,7 68,7 66, , ,9 47,3 143

146 Maximum Zs for Loadlimiter MCBs Current B type C type D type rating (A) 0.4s 5s 0.4s 5s 0.4s 5s The above table is based on 230V rated voltage to earth. Minimum Fuse Rating for Discrimination Current B type C type D type rating (A) Fuse link rating (A) Maximum Back-up Fuse Rating for Protection Current B type C type D type rating (A) Fuse link rating (A)

147 Residual Current Circuit Breakers Currents of low magnitude caused by unintentional leakage paths to earth can cause deterioration within circuit wiring and components with the potential to create a rapidly escalating situation that will permit the current to reach dangerous levels. Special forms of circuit breakers are designed to use the detection of earth leakage or residual current to limit the effects of this type of fault. The generic term residual current device is used to describe a range of circuit protection devices that include the functions of sensing and measurement of a leakage current, with subsequent tripping when the magnitude of the residual current reaches a preset level. The purpose of these devices is to protect human life, livestock, property and equipment against the escalation of earth fault currents to destructive magnitudes. Two forms of technology are commonly employed in the design of residual current devices; electromagnetic and electronic. In both cases, a current transformer is used and is arranged such that normal current flows in the phase and neutral conductors cancel each other to produce a zero balance. The presence of any residual current will create an out-of-balance that can be used to signal the actuation of a mechanism for circuit interruption. In the electromagnetic type, a trip relay is used as the actuation device. The relay is powered by the fault current and therefore requires no external power source. With electronic devices internal signal amplification allows a much smaller current transformer to be used, reducing the physical size of the circuit breaker. In this case, however, the actuation power is derived from both the fault current and the mains power. Also, a separate earth reference connection may be required to ensure continuity of operation in the event that the mains neutral is lost. Residual current devices are accorded a sensitivity coding that indicates the level of residual current that would cause a trip action. Commonly, the available sensitivity ranges are 10mA, 30mA, 100mA and 300mA. In general, the 10mA and 30mA devices are used to protect human life, the 100mA and 300mA devices being applied to protect wiring, cabling and equipment. The degree of electrocution that could take place when a fault arises depends upon the combined effects of the magnitude and duration of current flow. For sensitivity levels of 30mA and below, tripping must be instantaneous to protect human life. Longer periods of residual current flow can be tolerated by equipment and the trip action may not necessarily be required to interrupt the circuit instantaneously. Residual Current Circuit Breaker The RCCB device combines the functions of a switch with those of a residual current device. It is often used in place of an incoming switch disconnector with the advantage that it functions also as a residual current protection device. The disadvantage, however, is that a residual fault will cause the device to operate interrupting ALL downstream circuits even when these circuits remain in a healthy state. Note that an RCCB should not be used as the sole means to provide complete protection. It has no overload or short circuit protection and must therefore be further protected by an upstream device having these capabilities. Frequently, the RCCB is used in consumer units and distribution boards to protect sub-circuits in a split load configuration. In these applications, the upstream back-up is provided by the Regional Electricity Company s local fuse. Residual Current Breaker with Overload Protection The RCBO combines the functions of an MCB with those of a residual current device. It will therefore provide protection against overload, short circuit and earth leakage. 145

148 RCBOs and RCCBs General These devices are furnished with a test pushbutton on the front face of the module. Operation of this button will simulate the presence of a residual fault and the test should be made frequently, say once per month, to assure continued correct functionality of the device. In addition to the range of sensitivities, RCBOs and RCCBs are available in two types, type AC and type A. These refer to the types of circuit for which the devices are suitable. Type AC: for use with residual sinusoidal ac, whether applied as a step or ramp. Type A: for use with either residual sinusoidal ac or residual chopped (pulsating) dc, whether applied as a step or ramp. A time delay facility may also be included, adjustable up to, typically, 50-70mS. This is denoted by S included within the description and also marked on the device. This function is included in order to enable the device to be used as part of a circuit device discrimination (or selectivity) arrangement. Without the time delay, residual current circuit breakers cannot be easily used within a discrimination scenario due to their inherent rapid tripping in response to residual current detection. Whereas RCBOs are single module width devices used in place of or alongside MCBs in outgoing circuits, RCCBs are available in 2-pole and 4-pole forms and are readily used in single phase and three phase distribution systems where they can function as either incoming or outgoing ways. Due to their low levels of sensitivity RCCBs are generally equipped with suppression filtering to avoid nuisance tripping that could be induced from disturbances in external or incoming circuits. 146

149 Modular Contactors Contactors are simply electromechanically controlled switches. A contactor acts as an interposing relay which, when its coil is energised, operates one or more sets of contacts that are able to carry currents of sufficient magnitude to switch power equipment such as large banks of lights, highly inductive lamps, motors and large solenoids. The current required to operate the coil is minimal, therefore a contactor can be controlled by light duty contacts in a timer, pushbutton or other control device. Generally, contactors have no latching facility, i.e. once the coil is de-energised the contact state returns to its normal condition. However, whilst there is no mechanical latching, electrical latching can be easily accomplished by using a separate relay contact to hold on the supply to the contactor s coil. Selection Criteria The correct choice of contactor depends upon a number of parameters within the intended application. These include: The form of power supply The magnitude of the power to be switched The type of load to be controlled The control voltage required The frequency of switching Since the device operates by its coil being energised for possibly lengthy periods, considerable internal heat can be generated. For this reason, a venting insert must be placed between alternate pairs of contactors or between a contactor and any other adjacent circuit device. Switching Capacity Contactor ratings are stated for AC1 type loads only (resistive). Where the load to be switched differs from this, it is likely that the contactor will have to be de-rated to ensure its performance. If the load is dc, inductive or capacitive, the degree of de-rating may be considerable. The following contactor de-rating tables indicate the maximum power/current that can be switched according to the type of load to be controlled. The figures quoted are per phase and are based upon a 230V ac supply. 147

150 Modular Contactor Technical Data MAIN CIRCUIT GENERAL Type EE2P20 EE4P25 EE4P40 EE4P63 Standards IEC/EN 61095, IEC/EN , IEC/EN Module width Mechanical op. c. 3 x 106 endurance Ambient temp. C Storage temp. C No. of contactors 40 C max. 3 no limitation max. 3 (side-by-side) C max. 2 max. 2 Contact reliability 17 V; 50 ma Min. distance of mm 3.6 open contacts Power dissipation W per pole Overload current A withstand capability Max. back-up fuse Iv A for short-circuit protection gl Coordination type 2 DC Max. operating AC-1/AC-3/ op. c./h 600 frequency AC-5b/AC-6b AC-15 1,200 no load 3,000 Weight kg Rated insulation Ui V voltage Rated impulse Uimp kv 4 withstand voltage Thermal current Ith A Rated operational Ue V voltage Rated frequency f Hz 50/60 Rated operational AC-1/AC-7a Ie A current Operational power 1-pole 230 V AC-1/AC-7a 3-pole 230 V Pe kw pole 400 V Electrical endurance AC-1/AC-7a op. c. 200, ,000 Rated operational AC-3/AC-7b Ie A current Operational power 1-phase 230 V 1.3 only for NO 1) 1.3 2) 3.7 2) 5 2) motor AC-3/AC-7b 3-phase 230 V Pe kw - 2, motor 3-phase 400 V motor Electrical endurance AC-3/AC-7b op. c. 300, , , ,000 Switching of AC-6b 230 V C µf capacitors Electrical endurance AC-6b op. c. 200, ,000 Rated operational DC-1 current 1-pole U e = 24 V DC U e = 110 V DC Ie A U e = 220 V DC poles connected U e = 24 V DC in series U e = 110 V DC Ie A U e = 220 V DC poles connected U e = 24 V DC in series U e = 110 V DC Ie A U e = 220 V DC poles connected U e = 24 V DC in series U e = 110 V DC Ie A U e = 220 V DC Electrical endurance DC-1 op. c Terminal capacity rigid mm flexible Screw M3,5 M5 Screw head PZ1 PZ2 Tightening torque Nm

151 Modular Contactor Technical Data continued Type EE2P20 EE4P25 EE4P40 EE4P63 CONTROL CIRCUIT AUXILIARY CONTACTS Rated operational Ue V voltage Rated insulation Ui V voltage Rated impulse Uimp kv 4 withstand voltage Thermal current Ith A AC-15 Rated 1-phase 230 V Ie A operational current 1-phase 400 V Electrical endurance AC-15 op. c. 300, , , ,000 Range of Uc % control voltage Control voltages Uc V 230 Surge immunity test kv 2 (1.2/50 µs), acc. to IEC/EN Coil consumption switch-on 12/10 33/25 5/5 5/5 VA/W operation 2.8/ /1.6 5/5 5/5 Make/break delays make 15 _ _ _ _ 20 ms break 10 _ _ _ _ 45 Terminal capacity rigid S flexible Screw M3,5 M3 Screw head PZ1 Tightening torque Nm 0.6 Switching of Lamps Max. number of lamps per pole at 230 V 50 Hz Type Power (W) Current (A) C (µf) EE2P20 EE4P25 EE4P40 EE4P63 Incandescent lamps (tungsten filament) Incandescent lamps uncompensated or series compensated Incandescent lamps 2 x x 30 2 x 40 2 x x 150 lead-lag circuit 2 x x 24 2 x 31 2 x 78 2 x x x 17 2 x 24 2 x 65 2 x 95 2 x x 10 2 x 14 2 x 40 2 x 60 Incandescent lamps parallel compensated Fluorescent lamps with electronic ballast units (EVG) x x 12 2 x 17 2 x 50 2 x 70 2 x x 7 2 x 10 2 x 26 2 x 38 2 x x 7 2 x 9 2 x 25 2 x 36 High-pressure mercury-vapour lamps Uncompensated High-pressure mercury-vapour lamps Parallel compensated

152 Modular Contactor Switching of Lamps continued Type Power (W) Current (A) C (µf) EE2P20 EE4P25 EE4P40 EE4P63 Halogen metal-vapour lamps Uncompensated Halogen metal-vapour lamps, parallel compensated _ _ Halogen metal-vapour lamps, integrated with electronic ballast unit PCI integrated x In lamp for 0.6 ms integrated integrated Transformers for halogen metal-vapour lamps High-pressure _ sodium-vapour lamps _ Uncompensated _ High-pressure sodium-vapour lamps _ Parallel compensated Halogen metal-vapour lamps integrated with electronic ballast unit PCI integrated x In lamp for 0.6 ms integrated integrated Low-pressure sodium-vapour _ lamps. Uncompensated _ _ _ _ _ Low-pressure sodium-vapour lamps. Compensated Lumilux T5 LUMILUX* Fluorescent lamps 22 0, T5 with electronic ballast unit 40 0,21 FC (EVG) 55 0, , , HE 28 0, , , , ,24 HO , , x 22 0,23 2 x 11 2 x 15 2 x 40 2 x 55 2 x 40 0,42 2 x FC 2 x 6 2 x 7 2 x 20 2 x 30 2 x 55 0,55 2 x 4 2 x 6 2 x 15 2 x 22 2 x 14 0,15 2 x 15 2 x 20 2 x 52 2 x 75 2 x 21 0,22 2 x 11 2 x 15 2 x 40 2 x 57 2 x HE 2 x 28 0,28 2 x 9 2 x 11 2 x 20 2 x 45 2 x 35 0,36 2 x 7 2 x 9 2 x 24 2 x 35 2 x 24 0,24 2 x 10 2 x 13 2 x 35 2 x 50 2 x 39 0,39 2 x 6 2 x 8 2 x 21 2 x 31 2 x 49 0,48 2 x HO 2 x 5 2 x 7 2 x 17 2 x 26 2 x 54 0,54 2 x 4 2 x 6 2 x 16 2 x 23 2 x 80 0,74 2 x 3 2 x 4 2 x 11 2 x *LUMILUX is a trademark of OSRAM GmbH

153 Moulded Case Circuit Breakers The operation and application of the MCCB is similar to that of the MCB, however this device has the air-break mechanism contained within a moulded case housing made from a very robust non-conducting material. Generally, MCCBs exhibit much higher breaking capacities and rated current than their smaller counterparts and can be used to perform full isolation duty. Consequently, MCCBs are employed in both incoming and outgoing circuits. MCCBs are constructed to a particular frame size and typically provide rated current in the range A. These devices can be equipped with adjustable thermal and magnetic tripping mechanisms to cater for overload and short circuit protection to meet the requirements for isolation and Category A discrimination duty. Dorman Smith electronic MCCBs provide adjustable long, short and instantaneous trip functions, allowing more complex overall tripping characteristics to be configured, allowing these devices to be used for isolation and Category B discrimination requirements. (Refer to page 136 for Category definitions). Devices equipped with the full range of adjustable trips for long, short and instantaneous durations are generally referred to as LSI-MCCBs to distinguish them from the L and I only versions employed for Category A devices. The range of accessories that can be added to MCCBs is similar to that given in the section dealing with MCBs, including shunt trips, under-voltage releases and various forms of auxiliary contacts. The physical size of triple-pole and four-pole MCCBs allows these accessories to be internally mounted, although there are some restrictions with regard to combinations of these that can be co-mounted. For example, either a shunt trip or under-voltage release can be incorporated, but not both. Also, due to the much larger physical size of these devices compared with MCBs, additional safety features normally include interphase barriers and terminal shrouds to provide IP2X ingress protection at the terminals. The tripping operation of some MCCBs is different from that of MCBs in that there are three distinct positions of the toggle or handle. Whereas MCBs are either on or off, MCCBs have a central position when they are tripped. As a further safety feature, the coloured flags indicating the on and off states are masked in the tripped state. The breaker can be reset only after it has been set into the fully off state. MCCBs are equipped with a test pushbutton that allows periodic testing of the mechanical tripping mechanism. As in the case of a fault trip, the device must be moved into the off position before it can be reset following a test. These devices conform to EN therefore the definitions that apply to some parameters differ from those of EN that apply to miniature circuit breakers. These differences are explained in the section covering Standard Terminology. Motor Control Applications The MCCB is a viable means of providing motor control switching. However, MCCBs used for this type of application are often required to provide only short circuit protection, with the overload protection catered for by a separate thermal or electronic overload relay. For this reason, specifically designed motor control MCCBs are available upon request, with only the single tripping mechanism. The range of circuit breakers for each frame size includes a basic switch disconnector version, generally in both triple-pole and four-pole variants. Devices of this type are sometimes referred to as non-auto MCCBs. 151

154 Loadline YA Frame MCCBs for Motor Starting (415 V ac) Motor Motor full Sub-transient Breaker Breaker Breaker rating load starting frame rated instantaneous current current current trip threshold (set on max.) P(Kw) Ie(A) Id"(A) In(A) Ii (lower tolerance) (A) YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA2/YA YA YA YA YA YA YA Notes 1 In>le 2 li/lower > ld" The above table is suitable for DOL and Star Delta starting. 152

155 Discrimination In the context of power distribution schemes, the term discrimination (sometimes referred to as selectivity ) describes a hierarchy of circuit devices that are arranged such that a single upstream circuit breaker can fan out to several downstream devices to act in a co-ordinated fashion should a fault occur. Under fault conditions, only the upstream protective device closest to the fault should operate to clear the fault, leaving all other healthy circuits operable. This is especially important in installations where circuit failures could be life-threatening, such as in hospitals. The concept of discrimination is similar to that of cascading, the prime difference being in the objectives of the application. Whereas discrimination is used to ensure continuity of supply to sub-circuits by limiting the disconnection to the faulted sub-circuit alone, cascading is used to buffer downstream protective devices against the effects of high prospective short circuit currents. In both cases, the protective devices are specifically selected to meet the criteria for the type of co-ordination required. When the selected devices are properly matched to fulfil the ideal discrimination principle described above, the co-ordinating devices are said to achieve total discrimination. In many practical installations, however, a partial discrimination may be satisfactory for safe continuity of supply, with an added advantage of cost savings due to selecting a lower rated upstream circuit breaker. Discrimination between two circuit breakers arranged in series may be based on either current or time. Where the magnitude of the fault current is to be used as the critical factor for selection, the co-ordination in this case is termed current discrimination. Where the basis for selection is the duration over which the upstream device can withstand the fault current, the selection is to achieve time discrimination. In some cases, time discrimination can be achieved by using an upstream device that has a built-in time delay. Current Discrimination In general, the basis for current discrimination is that the downstream protective device will have a lower current rating than the upstream device. It should also have a lower instantaneous tripping point. The discrimination tables that follow highlight the consequential increase in discrimination level as the differential in current ratings between the devices increases. Time Discrimination Discriminating by time between two devices in series relies on the operation of the upstream device being delayed at least until the downstream circuit breaker has tripped to clear the fault. The clearing time of the downstream device must be less than the time setting of the upstream device and the upstream device must also be capable of withstanding the fault current for the full duration of its time setting. There is generally no problem in achieving these conditions where the upstream device is a Category B circuit breaker specifically designed for this type of co-ordination duty. Time/Current Characteristics Comparison of the time/current characteristic graphs of the two devices proposed can give a quick check on their suitability for co-ordination in both current and time discrimination cases. Ideally, there should be no overlap of the respective curves to achieve total discrimination. If, however, the instantaneous portion of the curves do intersect, a partial discrimination will be achieved at the current level projected from the intersect point. In the tables that follow, total discrimination is indicated by the letter T in appropriate boxes. Total discrimination applies for all fault levels up to the lower breaking capacity of the two devices in co-ordination. Where a value is contained in any of the boxes, this indicates a partial discrimination of that value of current limit. If no discrimination is possible, this is shown by a dash symbol. 153

156 Note that partial discrimination infers that, above the current limit value indicated, it is possible that both devices could trip, resulting in disconnection of other sub-circuits and loss of supply continuity to those areas of the distribution system. Discrimination Tables DOWNSTREAM MCCB UPSTREAM ELECTRONIC ACB Z2 800A Z2 1250A Z2 1600A Z2 2000A Z3 2500A Z3 3200A Z3 4000A Frame Rating Model STD HIGH STD HIGH STD HIGH STD HIGH STD HIGH STD HIGH STD Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Breaking 65kA 80kA 65kA 80kA 65kA 80kA 65kA 80kA 85kA 100kA 85kA 100kA 100kA Capacity 125A 250A 400A 800A 1250A 1600A YA2N 25kA T T T T T T T T T T T T T Thermal/ Mag YA2S 36kA T T T T T T T T T T T T T Thermal/ Mag YA2J 65kA T T T T T T T T T T T T T Thermal/ Mag YA3N 25kA T T T T T T T T T T T T T Thermal/ Mag YA3S 36kA T T T T T T T T T T T T T Thermal/ Mag YA3J 65kA T T T T T T T T T T T T T Thermal/ Mag YA5N 25kA T T T T T T T T T T T T T Thermal/ Mag YA5H 50kA T T T T T T T T T T T T T Thermal/ Mag YA5H 50kA T T T T T T T T T T T T T Electronic YA5J 65kA T T T T T T T T T T T T T Thermal/ Mag YA5K 70kA T T T T T T T T T T T T T Electronic Y6H 50kA T T T T T T T T T T T T T Thermal/ Mag Y6H 50kA T T T T T T T T T T T T T Electronic Y6J 65kA T T T T T T T T T T T T T Electronic Y6K 85kA T T T T T T T T T T T T T Thermal/ Mag Y7J 65kA - - T T T T T T T T T T T Electronic Y8K 85kA T T T T T T T T T Electronic T= Total Selectivity Notes: All ACBs have instantaneous trip set to NON and the MCR set to ON. Assumes all ACB time settings are greater than MCCB. The above table is in accordance with IEC , Annex A. 154

157 Discrimination Tables DOWNSTREAM MCCB UPSTREAM ELECTRONIC MCCB Frame Rating 400A 800A 1250A 1600A Model YA5H- YA5K- Y6H- Y6J- Y7J- Y8K- Electronic Electronic Electronic Electronic Electronic Electronic Breaking 50kA 70kA 50kA 65kA 65kA 85kA Capacity YA2N 25kA T T T T T T Thermal/ Mag YA2S 36kA T T T T T T 125A Thermal/ Mag YA2J 65kA 50 T T T T T Thermal/ Mag YA3N 25kA T T T T T T Thermal/ Mag YA3S 36kA T T T T T T 250A Thermal/ Mag YA3J 65kA 50 T T 50 T T Thermal/ Mag YA5N 25kA - - T T T T Thermal/ Mag YA5H 50kA T T Thermal/ Mag 400A YA5H 50kA T T Electronic YA5J 65kA T T Thermal/ Mag YA5K 70kA T T Electronic T= Total Selectivity Notes: All pick-up current and time delay settings to be set at maximum on upstream MCCBs. Partial discrimination level is in ka. The above table is in accordance with IEC , Annex A. UPSTREAM THERMAL MAGNETIC MCCB YA2N (25kA) or YA2S (36kA) YA3N (25kA) or YA3S (36kA) YA5H (50kA) In 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 160A 200A 250A 250A 400A DOWNSTREAM K SERIES MCB 6A 260 T T T T T 260 T T T T T T T T T T 10A T T T T T T T T T T T T T 16A T T T T T T T T T T T 20A T T T T T T T T T 25A T T T T T T T T T 32A T T T T T T T 40A T T T T T 50A T T T T 63A T T T T= Total Selectivity Notes: MCBs can be of any manufacture as long as they are Energy Class 3 as defined in EN Table based on Type B & C characteristic MCBs. MCBs can be 6kA or 10kA at 400V ac. Partial discrimination level is in amps. The above table is in accordance with IEC , Annex A. 155

158 Discrimination Table UPSTREAM THERMAL MAGNETIC MCCB YA2N (25kA) or YA2S (36kA) YA3N (25kA) or YA3S (36kA) YA5H (50kA) In 16A 20A 32A 50A 63A 80A 100A 125A 16A 20A 32A 50A 63A 80A 100A 125A 160A 200A 250A 250A 400A 6A DOWNSTREAM K SERIES D TYPE MCB 10A A A A A A A A T= Total Selectivity Notes: Table based on Type D characteristic MCBs. MCBs can be 6kA or 10kA at 400V ac. Partial discrimination level is in amps. 156

159 Cascading Cascading is sometimes referred to as back-up protection. The technique of cascading is used to allow circuit breakers with a breaking capacity lower than the value of prospective short-circuit current at the connection point to be used when these are positioned downstream of a current-limiting circuit breaker of higher breaking capacity. The net result of this arrangement is that the downstream device acquires an enhanced installed breaking capacity, therefore a less expensive, lower breaking capacity breaker can be used. The upstream circuit breaker must have the normally required breaking capacity for its point of installation however, when combined with another circuit breaker downstream, the two devices in series will be able to clear a larger fault. For example: if a 10A, 6kA MCB is place downstream of a YA frame MCCB rated at 125A and 25kA, the MCB will have an installed breaking capacity of 14kA. Similarly, a 10A, 10kA MCB downstream of a YA frame MCCB rated at 250A and 25kA will have an installed breaking capacity of 25kA. It should be noted that the cascading technique is not limited to only two devices in series. The important point is that it is the upstream device that is limiting the current to a value that can be interrupted by the following device, so that the pattern of paired devices can be repeated many times in an hierarchy of devices. The following tables give installed breaking capacity values of downstream circuit breakers for both the MCCB/MCB and MCCB/MCCB pairings of cascaded devices. Note that all values shown are at 400V ac. The values for the installed breaking capacities are given in ka. Upstream YA frame MCCB with downstream S-series MCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCB YA2N YA2S YA2J YA3S YA3J YA3N YA3S YA3J (6kA) (25kA) (36kA) (65kA) (36kA) (65kA) (25kA) (36kA) (65kA) 125A 125A 125A 160A 160A 250A 250A 250A Upstream YA frame MCCB with downstream K-series MCB DOWNSTREAM MCB UPSTREAM MCCB Frame Rating 125A 250A Model YA2N T/Mag YA2S T/Mag YA2J T/Mag YA3N T/Mag YA3S T/Mag YA3J T/Mag Current Breaking 25kA 36kA 65kA 25kA 36kA 65kA Rating Capacity 6A 10kA A 10kA A 10kA A 10kA A 10kA A 10kA A 10kA A 10kA A 10kA

160 Cascading (continued) UPSTREAM MCCB Frame Rating 125A 250A Model YA2N YA2S YA2J YA3N YA3S YA3J T/Mag T/Mag T/Mag T/Mag T/Mag T/Mag Breaking 25kA 36kA 65kA 25kA 36kA 65kA Capacity DOWNSTREAM MCCB 125A 250A YA2N 25kA T/Mag YA2S 36kA T/Mag YA2J 65kA T/Mag YA3N 25kA T/Mag YA3S 36kA T/Mag YA3J 65kA T/Mag UPSTREAM MCCB Frame Rating 125A 250A Model YA5H YA5H- YA5J YA5K- Y6H- Y6J Y6J- Y7J- Y8K- T/Mag Electric T/Mag Electric Electric T/Mag Electric Electric Electric Breaking 50kA 70kA 50kA 65kA 65kA 65kA 85kA Capacity DOWNSTREAM MCCB 125A YA2N 25kA T/Mag YA2S 36kA T/Mag YA2J 65kA T/Mag YA3N 25kA T/Mag YA3S 36kA T/Mag YA3J 65kA T/Mag YA5N 25kA T/Mag YA5H 50kA T/Mag YA5J 70kA T/Mag Notes: Cascade fault level is expressed in ka. 158

161 Short-circuit Discrimination Levels Where a high prospective fault level exists at the MCB distribution point, discrimination at short-circuit levels should be considered. This will require comparison of the device I 2 t characteristics at the relevant prospective fault level. Discrimination will be obtained at all fault levels for which the MCB total operating I 2 t is lower than the pre-arcing I 2 t of the device closer to the supply. The data for typical cartridge fuses can be extracted from graphs and is presented in the following tables. MCB, type B Fuse Current sizes rating (A) MCB, type C Current rating (A) MCB, type D Current rating (A)

162 System Sizing and Diversity The adequacy of sizing and rating of power distribution systems is important to ensure supply continuity and safety in operation. A number of design parameters must be taken into account in order to ensure that the supply and safety requirements are met. These include busbar ratings, short-circuit fault levels and circuit utilisation. Once the overall loading requirements have been established, and the supply transformer selected, consideration of the circuit distribution systems follows. Distribution enclosures and their busbar systems are pre-tested to accepted norms of through-fault levels, typically 16kA, 25kA, 35kA, 50kA and 80kA. These shortcircuit ratings alone will limit the choice of switchboard, panel board or distribution board. The selection of the type and size of enclosure to be used will then depend upon the busbar current rating needed, together with availability of sufficient circuit ways of the correct type for the circuits and sub-circuits to be supplied. The busbar current rating is generally chosen to be sufficient to supply full load, plus some safety factor. For example, if the full load is expected to be 750 amps, an enclosure with a busbar rating of 800 amps may be selected. Once the busbar current rating has been nominated, the incoming device for that group of circuits will be matched to the rating. In the example cited, the incoming device would be rated at 800 amps. More than one incoming device may be required to effect proper circuit protection and isolation, such as a switch disconnector in series with a thermal fuse. In this case, the fuse link will provide the protection and the disconnector will permit isolation. Alternatively, a moulded case circuit breaker (MCCB) employed as the incoming device will provide both protection and isolation. The size and type of circuits to be supplied will further refine the eventual choice of distribution system. Automatic or manual circuit disconnection will point to an enclosure suitable for either circuit breakers or switch-fuse devices. If the requirement is for automatic disconnection, prospective fault levels at the connection point may dictate that an MCCB must be used, rather than an MCB of the same current rating. Finally, consideration is given to the degree of circuit utilisation capacity, often referred to as diversity. Notwithstanding the limitations of the busbar system and the matched protection provided by the incoming device, the outgoing circuit ways may be configured with individual circuit protection devices having an aggregate rated current capacity in excess of the rating of the incomer. The basis for this approach is that it is often reasonable to assume that not all circuits will be supplying their rated current at the same time. In this case, a diversity factor is applied during the design stage to give an overall service capacity for the outgoing circuits. The maximum current rating divided by the diversity factor will give the maximum aggregate fitted current allowed. The following table lists the factors that may be applied subject to the number of outgoing circuits to be supplied. Taking the example of a 400A panel board with 400A MCCB incomer and 6 outgoing circuits, a diversity factor of 0.7 would allow outgoing MCCBs with an aggregate of 570A capacity to be installed. The individual circuits would be protected at the level of current rating of each MCCB, with the incomer providing ultimate protection at 400A. To allow for the possibility of future expansion of a distribution system, an allowance for 25% spare capacity is often included when applying a diversity factor to the initial design. Number MCCB panel boards MCB distribution boards of circuits to EN to EN

163 Prospective Short-circuit Current The Prospective Short-circuit Current, or PSC, is the theoretical maximum fault current that could exist at any point within a complete circuit distribution system. The magnitude of the fault current at any particular point is calculated on the basis of a bolted (virtually permanent) fault path at that point and therefore assumes a constant voltage, continuous current supply feeding the fault. Using this assumption, the PSC that could possibly exist at the bolted fault path would be limited only by the sum of the circuit impedances of the complete current path, from high voltage feed to the supply transformer through to the bolted connection point. Since this assumption cannot be fulfilled in practice (for example, the voltage will not remain constant) the value of calculated PSC can never be exceeded in a practical scheme. The foregoing commentary is particularly relevant to larger commercial and industrial networks, where many sub-systems are present and often, many sub-circuits within these. For more compact arrangements, such as domestic installations, where the distribution scheme is contained within one or more consumer units, the situation is much simpler. The Regional Electricity Companies generally agree on a fixed fault level of 16kA at the local zone supply distribution point to one or more dwellings. Those dwellings that lie some distance from the zone origin point of the distributed supply will have reduced PSC due to the higher impedance of the longer run of service cable. Consumer units should therefore have a minimum short-circuit rating of 16kA. When an MCB trips, the combination of forced contact separation and rapid arc extinction produces a limiting effect on the fault current such that it will be adequately handled within the normal 6kA breaking capacity of MCBs fitted to domestic installations. PSC at the origin point In practice and with consideration of the total distribution network; the breaking capacity of an individual circuit device would normally be less than that calculated for the origin point of the scheme. PSC at the connection point The breaking capacity of individual devices must be greater than (or at least equal to) the PSC at the specific point of their connection within a scheme. Conversely, where the circuit device breaking capacity is greater than the PSC at origin, there is no need for further measurement or calculation in this regard. The PSC at any particular connection point can be estimated, calculated, or determined by measurement of the circuit impedance at that point. Measurement of the circuit impedances at all relevant connection points can be a laborious exercise; the calculation method is generally used since this can be readily carried out using one of a number of available computer software packages. PSC by calculation The magnitude of the short-circuit current (rms value of the ac component) at the connection point will depend upon: the PSC at the origin point. the total resistance in the circuit between the origin point and the relevant circuit reference point. whether the short-circuit condition is considered as phase-phase, phase-neutral or phase-earth. The maximum PSC at the origin can be calculated from the following formula: PSC (ka) = Supply transformer rating (kva) x x secondary voltage x % transformer reactance PSC by estimation To estimate the PSC, first calculate the total resistance in the LV circuit by determining the sizes and lengths of cables between the supply source and the point under consideration. Next, use the following table to find the cable resistances and summate these to obtain the total resistance. Finally, use this value to read off the estimated PSC from the following graph. 161

164 Maximum Resistance of Copper Conductors at 20 C (milli ohms) Nominal Cable length (m) cross sectional area (mm 2 ) Fault Current (ka) Total Circuit Resistance (mω) 162

165 PSC in a typical installation Note that the values on the graph assume a symmetrical fault across the three phases. In a single circuit, for line-neutral faults, the cable resistance value given in the table should be doubled. The following values of PSC would be obtained at the various circuit points marked in the above diagram: Point A PSC = approximately 27kA Point B Two cables per phase, therefore halve the value. Resistance from A to B = 0.3 Milli ohms With reference to the graph PSC can be assumed to be 25kA Point C Resistance from A to B = 0.3 Milli ohms Resistance from B to C = 10.7 Milli ohms Total circuit resistance A to C = 11.0 Milli ohms With reference to the graph PSC can be assumed to be 12kA Point D Resistance from A to B = 0.3 Milli ohms Resistance from B to C = 10.7 Milli ohms Resistance from C to D = 46.0 Milli ohms (Double the value for the 2-core cable) Total circuit resistance A to D = 57.0 Milli ohms With reference to the graph PSC can be assumed to be 3kA 163

166 Earth Fault Protection One of the most common means of protecting persons against the effects of high voltages and currents is by insulating the wiring and components. Most earth faults occur when some part of the insulation has broken down, creating the possibility of causing electric shock through indirect contact with the faulty circuit. The breakdown of insulation can often cause all or part of an enclosure or frame to become live by raising conductive parts to a hazardous voltage level. Touching any of the exposed parts of the enclosure or frame would then be highly dangerous and would most likely cause an electric shock. Whilst protective devices may open quickly to minimise the possibility of high currents flowing for any significant length of time, additional measures are necessary to limit the potential earth fault current at source. In some cases fault current limiting resistors or inductors may be installed at the transformer star point however, in all cases, it is important to ensure that the impedance of circuit conductors is kept to a minimum so that the voltage developed under fault conditions will be restricted. The earth fault loop impedance is denoted Zs and is an important circuit design parameter. Circuit designs must always ensure that the magnitude of the fault current will be sufficient to trip the over-current protective devices within acceptable times as stated in the IEE Wiring Regulations. Circuit breakers are designed to trip and therefore disconnect faulted circuits very quickly. The design value of tripping time is generally expressed in the form of a graph that maps current against time and any practical scheme can be checked against this value to ascertain conformance with the requirements. The fault current can be established very simply using Ohm s law, as follows: Fault current = Phase-to-earth voltage Zs Once this value is known, the corresponding tripping time can be read from the relevant device s time/current characteristic graph and the result compared with that given within the Wiring Regulations. In general, the higher the nominal voltage of an installation, the shorter will be the required disconnection time. For fixed equipment installations, the maximum disconnection time is stated as 5 seconds, whereas it is 0.4 seconds for portable equipment. The Regulations define portable as including fixed outlet sockets that may be used to supply apparatus that is movable or portable when in use. The following table illustrates the maximum Zs allowable for MCBs to achieve the specified disconnection times. Current rating (A) Type B max. Z s (ohms) Type C max. Z s (ohms) Type D max. Z s (ohms) Since the complete loop impedance is the sum of the individual impedances of the supply transformer winding, circuit phase conductor and protective circuit conductor, the total may be higher than that specified for in-time disconnection for the protection device proposed. In these cases, several solutions may be possible to overcome or at least assist in achieving compliance. The supply cable may be replaced by one with greater cross sectional area The short-circuit tripping threshold of the device may be set to a lower value (if it is adjustable) A Residual Current Device could be used to replace the circuit breaker in question The following tables indicate the maximum Zs for Dorman Smith s range of MCCBs. Using these tables obviates the need to determine the suitability of a device by reference to its time/current characteristic graph. 164

167 Zs Values for YA2, YA3 and YA5 MCCBs Maximum Allowable Earth Loop Impedance Values, in accordance with BS7671 MCCB Reference S/C Protection Zs 230 Volts Setting In 0.4 sec 5 sec YA2 1P Fixed Mags YA2N, 25kA YA2 3P & 4P MIN Thermal Magnetic MAX MIN MAX YA2N, 25kA MIN MAX YA2S, 36kA MIN MAX YA2J, 65kA MIN MAX MIN MAX YA3 1P Fixed Mags YA3N, 25kA YA3 3P & 4P MIN Thermal Magnetic MAX MIN MAX MIN MAX YA3N, 25kA MIN MAX YA3S, 36kA YA3J, 65kA MIN MIN MAX MAX MIN MAX MIN MAX MIN MAX

168 Zs values for Y6, Y7 and Y8 MCCBs Maximum Allowable Earth Loop Impedance Values, in accordance with BS7671 Loadline MCCBs Magnetic Breaking Max Zs values adjustment In capacity (ka) 0.4 sec 5 sec Y6 Frame Y6HJK Set at maximum Thermal magnetic Set at minimum Y6HJK Set at maximum Thermal magnetic Set at minimum Y6HJK Set at maximum Thermal magnetic Set at minimum Y6HJK Set at maximum Electronic "INST/STD" Set at minimum Y6HKJ Set at maximum Electronic "INST/STD" Set at minimum Y7 Frame Y7JK Set at minimum Electronic "INST/STD" Set at minimum Y7JK Set at minimum Electronic "INST/STD" Set at maximum Y8 Frame Y8JK Set at minimum Electronic "INST/STD" Set at maximum

169 Forms of Separation The principle of separation applied to multi-cubicle switchboards and panel boards is the achievement of a high degree of safety for equipment and people during normal operation and to promote safe working during commissioning and service. The resulting concept is one of functional separation and segregation of live parts of the system into sub-units by the use of barriers or partitions. In general, separation should provide enhanced safety by: Protecting against contact with the live parts of adjacent functional units Preventing the passage of solid foreign bodies from one section of an assembly to an adjacent one Various elements of an assembly must be considered for separation from neighbouring live sections, such as busbars, terminals and functional units. The specific form of their separation can be achieved in several ways according to the particular application and the requirements for access for maintenance. The minimum degree of protection to be achieved at each barrier or partition is to IP2X as specified in the Ingress Protection standard EN Typically, this may include: PVC sleeving, wrapping or plastic coating of conductors Insulated terminal shrouds or PVC boots Rigid insulated barriers or partitions Compartments formed from earthed metal A device s integral housing There are several forms of separation, indicated by numbered category and subcategory; however the requirements for the degree of separation need to be carefully considered since the cost increases significantly with increased degree. The principal categories are: Form 1 no separation Typical applications are where the assembly is to be placed in a secure location and where failure will cause little or no additional disruption to other areas being supplied by that particular assembly. Form 2 separation of busbars from functional units Applications may be similar to those of Form 1 but where it is important that a fault need not affect all functional units being supplied by the same busbar system. Form 3 separation of busbars from functional units and the functional units from one another, but not their terminations This form should be applied where it is important to provide protection from internal live parts and where failure of functional units being supplied from the same busbar would cause unacceptable disruption. Form 4 separation of busbars from functional units and the functional units from one another, including their terminals This form should be applied where it is important to provide protection from internal live parts and where failure of functional units being supplied from the same busbar would cause unacceptable disruption. Because all the terminations are separated, it is possible to isolate and work on a single functional unit. Dorman Smith LF-type panel board systems are supplied in Form 2 as standard, with Form 4 versions achieved with simple conversion kits. However, other separation forms can be provided in special cases. With the exception of Form 1, the other separation forms have sub-categories that permit permutations of the general form to be configured according to the requirements for specific applications and to allow the accommodation of different types of protection method. The exact form of separation provided on an assembly is a matter for agreement between the manufacturer and the end user. 167

170 Sub-categories of Separation Forms Main criteria Sub criteria Form Type Construction No separation 1 Separation of Terminals for external busbars from conductors not 2a the functional separated from units busbars Terminals for external 1 Busbar separation by conductors separated 2b insulated coverings from busbars 2 Busbar separation by rigid barriers Separation of busbars from the functional units and separation of all functional units from one another. Separation of the terminals for external conductors from functional units but not from each other Terminals for external conductors not separated from busbars 3a Terminals for external 1 Busbar separation by conductors separated 3b insulated coverings from busbars 2 Busbar separation by rigid barriers Separation of busbars from the functional units and separation of all functional units from one another including terminals for external conductors which are an integral part of the functional unit Terminals for external conductors in the same compartment as the associated functional unit 4a Busbar separation by insulated coverings Cables may be glanded elsewhere Busbar separation by rigid barriers Cables may be glanded elsewhere All separation by rigid barriers The termination for each functional unit has its own integral glanding facility Busbar separation by insulated coverings Cables may be glanded elsewhere Terminals for external conductors not in the same compartment as the associated functional unit but in individual, separate, enclosed protected spaces or compartments 4b Busbar separation by rigid barriers Terminals may be separated by insulated coverings and glanded in common cabling chambers All separation by rigid barriers Cables are glanded in common cabling chambers All separation by rigid barriers The termination for each functional unit has its own integral glanding facility 168

171 Ingress Protection The EN standard describes a system for classifying degrees of protection against the ingress of foreign bodies and harmful liquids. It is intended that this standard is applied to enclosures of low voltage (LV) electrical equipment. The classification scheme comprises a designation prefixed by the upper case letters IP, followed by two numerals. The first numeral designates the degree of protection with regard to solid objects; the second numeral indicates the degree of protection against the ingress of liquid. Compliance to the standard is intended to: protect persons against access to hazardous parts inside enclosures and protect the equipment inside the enclosure against the ingress of solid foreign objects. protect the equipment inside the enclosure against harmful ingress of liquids. IP Protection Equivalent 0 No protection 1 Full entry of 50mm Back of sphere, but no hand contact with hazardous parts 2 Full entry of 12.5mm Finger sphere not allowed, but no contact with hazardous parts with jointed test finger 3 2.5mm diameter Tool access probe shall not enter 4 1mm diameter access Wire probe shall not enter 5 Limited ingress of Wire dust (no harmful deposit) 6 Total protection Wire against dust ingress X Not tested - IP Protection Equivalent 0 No protection 1 Against vertically Vertical falling water drops drips 2 As in 1, but with Slanted enclosure tilted 15 dripping degrees from vertical to 15 degrees from vertical 3 Against spray to 60 Limited degrees from spray vertical limited ingress permitted 4 Against splashing Splashing from any direction from any limited ingress direction permitted 5 Against low pressure Hosing jets from any jets from direction limited any ingress permitted direction 6 Against strong jets Power from any direction hosing from any direction 7 Against immersion Temporary up to one metre immersion 8 Against prolonged Continuous immersion under immersion pressure X Not tested - For assemblies for indoor use where there is no requirement for the protection against ingress of water, the following IP codes are preferred: IP00, IP2X, IP3X, IP4X, IP5X, IP6X. 169

172 Insulation Distances for Loadline YA Frame MCCBs The insulation distances between an MCCB and adjacent earthed metal parts and insulators shown in the diagram below must be maintained to prevent arcing faults occurring due to conductive ionised gases. In cases where requirements differ from those illustrated here, the greater distance must be maintained. Where two different YA frame devices are installed one above the other, the insulation distance between the two should be as for the lower size of MCCB. Exposed conductors must be insulated up to the barrier terminals. Interphase barriers or terminal covers are recommended. However, if terminal covers are used, the exposed conductor must be insulated until it overlaps the terminal cover. 1. Insulation plate 2. Top plate (earthed metal) 3. Interphase barriers 4. Front connected MCCB 5. Front connected MCCB with terminal bar 6. Rear connected type or plug-in type 7. Side panel (earthed metal) A. Distance from lower breaker to exposed live part of upper breaker terminal (front connected type) or from lower breaker to end face of upper breaker (rear connected or plug-in type) B1. Distance from end face of breaker to top plate B2. Distance from end face of breaker to insulation plate C. Gap between breakers D. Distance from side of breaker to side panel E. Dimensions of insulation over exposed conductors MCCB Distances Frame Poles A B1 B2 C D E Size YA2N *(1) YA2N 3/ *(1) YA2S 3/ *(1) YA2J 3/ *(1) YA3N *(1) YA3N 3/ *(1) YA3S 3/ *(1) YA3J 3/ *(1) YA5N 3/ *(1) YA5H 3/ *(1) 170 *Note: (1) Insulate the exposed conductor until it overlaps the moulded case at the terminal or terminal cover.

173 Loadline YA2 Frame MCCB Characteristics YA2 1-pole Time/Current Characteristic YA2 3 and 4-pole Time/Current Characteristic YA2 1-pole Energy Let-through YA2 3 and 4-pole Energy Let-through 171

174 Loadline YA3 Frame MCCB Characteristics 2500+/-500 YA3 1-pole Time/Current Characteristic YA3 3 and 4-pole Time/Current Characteristic YA3 1-pole Energy Let-through YA3 3 and 4-pole Energy Let-through 172

175 Loadline YA5 and Y6 Frame MCCB Characteristics YA5 3 and 4-pole Energy Let-through YA5 3 and 4-pole Time/Current Characteristic Y6 Time/Current Characteristic 173

176 Loadline Y7 and Y8 Frame MCCB Characteristics Y7 Time/Current Characteristic T IP I1 T IG I2 T2 TG I3 I Curves based on standard settings Percent rated current of base current (I0) 174 Y8 Time/Current Characteristic

177 Products & Parts Locator Section 10

TP&N Distribution Systems

TP&N Distribution Systems TP&N Distribution Systems Loadlimiter 63 Range TP&N Distribution Systems (B-type) O V E R 1 3 0 Y E A R S O F E L E C T R I C A L E X C E L L E N C E Dorman Smith Switchgear Ltd With over 130 years of

More information

Loadlimiter 63. MCB Distribution Boards

Loadlimiter 63. MCB Distribution Boards Loadlimiter 63 MCB Distribution Boards Dorman Smith Switchgear Limited With over 130 years of experience in switchgear design and production Dorman Smith Switchgear Limited continues to provide high quality

More information

Dorman Smith Loadbank 125 MCCB Panel Boards

Dorman Smith Loadbank 125 MCCB Panel Boards Dorman Smith Loadbank 125 MCCB Panel Boards Section 3 MCCB Panel Boards Loadbank 125 Range (250A and 400A Ratings) Overview Key Features ASTA certified busbars with a short circuit rating of 25kA for 1

More information

Fuse Switch Panel Boards

Fuse Switch Panel Boards Fuse Switch Panel Boards Fuse Switch Panel Boards Loadbank 200 Range O V E R 1 3 0 Y E A R S O F E L E C T R I C A L E X C E L L E N C E Dorman Smith Switchgear Ltd With over 130 years of experience in

More information

NEW Titan II A & B Distribution Boards

NEW Titan II A & B Distribution Boards A Type Board Specification: Powder Coated Epoxy Resin Finish RAL 7035 Designed and built in the UK to BS EN 60439 Maximum busbar rating 125A Degree of protection IP3X to BS EN 60529 Blank gland plates

More information

O V E R Y E A R S O F E L E C T R I C A L E X C E L L E N C E

O V E R Y E A R S O F E L E C T R I C A L E X C E L L E N C E Over 130 Years of Electrical Excellence LV Switchboards up to 3200A Panel Boards 400-1250A L2 Compliant Distribution Boards Dorman Smith Switchgear Ltd With over 130 years of experience in switchgear design

More information

Crompton Instruments Ebony Current Transformers

Crompton Instruments Ebony Current Transformers Crompton Instruments Ebony Current Transformers Moulded Case Current Transformers Ebony Series Measuring and Protection The range of Crompton Instruments Ebony current transformers offers wide system

More information

125A SPN, type A distribution boards Incoming devices Meterpack assemblies Surge protection devices... 34

125A SPN, type A distribution boards Incoming devices Meterpack assemblies Surge protection devices... 34 Memshield 3 MCB distribution boards and enclosures 2 Eaton s Memshield 3 MCB distribution boards have evolved through an intimate knowledge and feedback from electrical contractors, consulting engineers

More information

TP&N DISTRIBUTION BOARD TYPE B RANGE

TP&N DISTRIBUTION BOARD TYPE B RANGE GROUP Now included in the range: Extension Boxes Metering Kits Surge Suppression and more! TP&N DISTRIBUTION BOARD TYPE B RANGE A comprehensive distribution board range for modern commercial & industrial

More information

Energy Division. Crompton Instruments Ebony Current Transformers

Energy Division. Crompton Instruments Ebony Current Transformers Energy Division Crompton Instruments Ebony Current Transformers Moulded Case Current Transformers Ebony Series Measuring and Protection The range of Crompton Instruments Ebony current transformers offers

More information

Crompton Instruments AS Series Current Transformers

Crompton Instruments AS Series Current Transformers Crompton Instruments AS Series Current Transformers AS Series Current Transformers The range of Crompton Instruments AS series moulded case current transformers offers wide system current ratings, apertures

More information

Talisman Plus. MCB Distribution Boards & Miniature Circuit Breakers BILL MEANS BUSINESS

Talisman Plus. MCB Distribution Boards & Miniature Circuit Breakers BILL MEANS BUSINESS Distribution Boards & Miniature Circuit Breakers BI MEANS BUSINESS A Type SPN Distribution Boards B Type TPN Distribution Boards A & B Type SPSN Distribution Boards Miniature Circuit Breakers 20V/15V AC

More information

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A.

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A. www.moeller.co.uk Mini Panel Board Cost-effective, space-saving board up to 400A Product Catalogue and Selection Guide Mini Panel Board Miniature Circuit Breakers Moulded Case Circuit Breakers XBoard Consumer

More information

Sentry. The Sentry range of Consumer Units from MK Electric has been stylishly designed to blend in with its

Sentry. The Sentry range of Consumer Units from MK Electric has been stylishly designed to blend in with its Sentry 2 TECHNICAL HOTLINE +44 (0)268 563720 The Sentry range of Consumer Units from MK Electric has been stylishly designed to blend in with its environment. The curved lines and slim-line appearance

More information

LOADSTAR MCBs AND DISTRIBUTION BOARDS

LOADSTAR MCBs AND DISTRIBUTION BOARDS MCBS AND DISTRIBUTION BOARDS Devices 6kA and 10kA Ranges 6A to 63A Single, Double and Triple Pole Type B, C & D Single and Double module RCBOs 35mm 2 Cable Terminals BS EN 60898 System 125A and 250A TP

More information

QUICK REFERENCE PRICE GUIDE JUNE 2016

QUICK REFERENCE PRICE GUIDE JUNE 2016 QUICK REFERENCE PRICE GUIDE JUNE 2016 OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this Quick Price Guide carry a guarantee against defects in materials and workmanship

More information

Modis Ultra. LV Distribution System

Modis Ultra. LV Distribution System Modis Ultra LV Distribution System Dorman Smith Switchgear Limited With over 130 years of experience in switchgear design and production Dorman Smith Switchgear Limited continues to provide high quality

More information

ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS

ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS 2 ENERGY /// TE'S CROMPTON INSTRUMENTS 3 Table of contents I. Tape Wound Measuring and Protection Current MR Series Measuring

More information

SPM Series Plug-in Surge Protection

SPM Series Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution s Sentron 3VT circuit breakers Simply Smart: First choice for power distribution www.siemens.com/industry Sentron 3VT Molded Case Circuit-Breakers - 10-1600Amperes With the standard line of 3VT molded-case

More information

The right solution for every home

The right solution for every home Domae Household switchboards The right solution for every home Household guide 2002 Building a New Electric World. Household switchboards Domae The right solution for every home Household guide 2002 Building

More information

AThink future. Switch to green. MCCB Panel Boards 400A / 630A / 800A.

AThink future. Switch to green. MCCB Panel Boards 400A / 630A / 800A. www.moeller.co.uk MCCB Panel Boards 400A / 630A / 800A Product Catalogue and Selection Guide MCCB Panel Boards Moulded Case Circuit Breakers and Accessories XBoard Consumer Units XPole Miniature Circuit

More information

SPM Series. Plug-in Surge Protection

SPM Series. Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

Pan assemblies and installation accessories

Pan assemblies and installation accessories Contents Section 10 Pan assemblies and installation accessories SP&N pan assemblies 124 SP&N door and cover 124 TP&N pan assemblies 125 TP&N door and cover 125 Multiclip busbar and Polybloc 126 Comb busbars

More information

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by

More information

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip Product Managers and dedicated Business Development Managers are available to assist with all your enquiries. Technical presentations (Forms of Separation, Discrimination etc) available Site response capability

More information

TAPE WOUND, SPLIT CORE AND EBONY CURRENT TRANSFORMERS

TAPE WOUND, SPLIT CORE AND EBONY CURRENT TRANSFORMERS CROMPTON INSTRUMENTS TAPE WOUND, SPLIT CORE AND EBONY CURRENT TRANSFORMERS CONTENTS Tape Wound Measuring and Protection Current Transformers... 2 MR Series Measuring Range... 3 PR Series Protection Range...

More information

B60 Domestic Voltage Optimisation Unit. Installation Manual

B60 Domestic Voltage Optimisation Unit. Installation Manual Govna B60PVM Voltage Optimisation Unit Govna B60PVM Voltage Optimisation Unit B60 Domestic Voltage Optimisation Unit Web: www.renewableenergyhub.co.uk Email: info@renewableenergyhub.co.uk Phone: 0845 862

More information

Havells Switchgear. Trade Price List. PowerSafe - Commercial Range

Havells Switchgear. Trade Price List. PowerSafe - Commercial Range Havells Switchgear List PowerSafe - Commercial Range List Catalogue SPN Type A Distribution Boards PSA4 8906079 4 way 100A SPN Type A distribution board AA 53.73 PSA7 8906080 7 way 100A SPN Type A distribution

More information

B60 Domestic Voltage Optimisation Unit

B60 Domestic Voltage Optimisation Unit B60 Domestic Voltage Optimisation Unit Installation Manual V1.2 Nov 2013 1 P a g e PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations,

More information

Memguard Advantage DISTRIBUTION SYSTEM Product Guide. MCB Single Phase Distribution Boards MCB Three Phase Distribution Boards

Memguard Advantage DISTRIBUTION SYSTEM Product Guide. MCB Single Phase Distribution Boards MCB Three Phase Distribution Boards Memguard Advantage DISTRIBUTION SYSTEM Product Guide MCB Single Phase Distribution Boards MCB Three Phase Distribution Boards 1 Contents and Introduction Contents Page Introduction Contents and Introduction

More information

Smart solutions for electrical distribution in commercial buildings

Smart solutions for electrical distribution in commercial buildings Sub-distribution solutions MEM series MCB single phase distribution boards MCB three phase distribution boards MCCB Panelboards Switch and protection devices Control and switching devices Metering solutions

More information

Smart solutions for electrical distribution in commercial buildings

Smart solutions for electrical distribution in commercial buildings MEM Sub-Distribution Solutions MCB single phase distribution boards MCB three phase distribution boards MCCB Panelboards Switch and Protection Devices Control and Switching Devices Metering Solutions Smart

More information

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations

More information

Protect Circuit Protection

Protect Circuit Protection Circuit Protection Product Catalogue 2018 Protect Circuit Protection Deta s new range of domestic Circuit Protection provides a high quality and cost effective solution, perfect for both new build and

More information

L.V. Systems & Solutions

L.V. Systems & Solutions GE Energy Industrial Solutions L.V. Systems & Solutions Residential Components & Distribution Boards Home & Building Automation Industrial Breakers General Purpose Enclosures System Enclosures Control

More information

Smart solutions for electrical distribution in commercial and industrial applications

Smart solutions for electrical distribution in commercial and industrial applications Power distribution components MCB Distribution boards and enclosures MCCB Panelboards Switch and protection devices Industrial switch and fusegear Enclosed motor, heating and lighting control HRC cartridge

More information

ßCompliant with Amendment 3 ßBSEN for easy cabling. accommodate RCBOs. meeting current standards

ßCompliant with Amendment 3 ßBSEN for easy cabling. accommodate RCBOs. meeting current standards CHINT EUROPE (UK) LTD Chint Metal Consumer Units ßCompliant with Amendment 3 of BS 7671 : 2008 Regulation 421.1.201 ßBSEN 61439-3 3 to 36 Ways are Standard Specials to Customer Requirements ß 1mm steel

More information

mcbs, EQUIPMENT NEW PRODUCTS 2014 Voltage surge protectors & other control and signalling devices Time & light sensitive switches

mcbs, EQUIPMENT NEW PRODUCTS 2014 Voltage surge protectors & other control and signalling devices Time & light sensitive switches NEW P. 4 RX3 MCBs 63 A 4500 & 6000 prong type busbar MCBs, RCDs, add-on modules & accessories P. 9 DX3 RCBOs 63 A 6000 / 10 ka AC, A & Hpi type prong & fork type busbar P. 16 DX3 MCBs 63 A 50 ka mcbs,

More information

Isobar 4c distribution boards and devices Selection guide

Isobar 4c distribution boards and devices Selection guide Isobar 4c distribution boards and devices Selection guide Isobar 4c Type A distribution boards Standard 125A distribution boards excluding incomer SP outgoing 6 MGAN6 9 MGAN9 12 MGAN12 15 MGAN15 23 MGAN23

More information

B60 Domestic Voltage Optimisation Unit. Installation Manual

B60 Domestic Voltage Optimisation Unit. Installation Manual Installation Manual V2.2 June 2015 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations, BS7671 (17th Edition or later) and current

More information

IDE Load break switches for machine control Remotely trippable switch from 32 to 160 A

IDE Load break switches for machine control Remotely trippable switch from 32 to 160 A The solution for Load break switches > Industry. > Non critical buildings. > Public Access Sites. > High Rise Buildings. ide_021_a_1_cat ide_022_a_1_cat IDE 4x40 A External operation IDE 4x40 A Direct

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

B60 PVM Domestic Voltage Optimisation Unit. Installation Manual

B60 PVM Domestic Voltage Optimisation Unit. Installation Manual Installation Manual V2.2 November 2015 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations, BS7671 (17th Edition or later) and current

More information

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors 6/4 Introduction 6/5 5TE8 control switches 6/7 5TE4 8 pushbuttons 6/9 5TE8 On/Off switches 4 6/11 5TE1 switch disconnectors 6 6/1 Switch to manual? Wherever electrical systems need to be switched on or

More information

Doepke MAIN SWITCH OPTIONS. The insulated consumer unit range consists of four enclosure sizes to enable any combination from 1 to 16 usable ways.

Doepke MAIN SWITCH OPTIONS. The insulated consumer unit range consists of four enclosure sizes to enable any combination from 1 to 16 usable ways. Doepke The insulated consumer unit range consists of four enclosure sizes to enable any combination from 1 to 16 usable ways. Designed to meet BSEN60439-3 these easy to install consumer units accept the

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

Defender B Board. Make The Switch

Defender B Board. Make The Switch Defender B Board Make The Switch Defender B Board 1.2mm Electro Galvanised Sheet Steel Tested to BS EN61439-3 Busbar Short Time Withstand Rating Icw 20kA 0.25s Tested at 35 C Ambient Tin Plated Busbar,

More information

the Santon FCS-type switch Disconnect Superior Switch Solutions

the Santon FCS-type switch Disconnect Superior Switch Solutions the Santon FCS-type switch Disconnect Superior Switch Solutions The technical information given in this table applies to 3 and 4 pole fuse combination switches. FRAME SIZE 1 1 2 3 3 4 4a 4b 5 6 6 nominal

More information

Type B, TPN distribution boards 2.2

Type B, TPN distribution boards 2.2 M distribution boards and enclosures Type, N distribution boards 2.2 See page 8 for technical data and overall dimensions EM A/A N, type distribution boards Total no. of (A) outgoing ways 4 way N, type

More information

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches.

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches. comut_004_a_1_cat Changeover switches switches 63 to 125 A switches are manually operated three or four pole switches. They provide, source inversion or switching under load between two low voltage power

More information

Specification Sheet: HT SERIES

Specification Sheet: HT SERIES Specification Sheet: HT SERIES HT Series: High Specification 19 Enclosures Hi-tech Series of 19 enclosures, supplied in self assembly (flat pack) format for ease of transportation and storage. Manufactured

More information

US Catalog July 2016 SMISSLINE TP

US Catalog July 2016 SMISSLINE TP US Catalog July 2016 SMISSLINE TP SMISSLINE TP modular bus system Table of contents Description 2 Building a SMISSLINE TP assembly for UL 489 and UL 508 based solutions Overview and ordering information

More information

Energy Division. Crompton Instruments Integra 1630 Low Profile Digital Metering System

Energy Division. Crompton Instruments Integra 1630 Low Profile Digital Metering System Energy Division Crompton Instruments Integra 1630 Low Profile Digital Metering System DIN Integra 1630 Series Multifunction Integra 1630 digital metering system provides high accuracy 0.2% measurement,

More information

PE Range Moulded Case Current Transformers

PE Range Moulded Case Current Transformers PE Range Moulded Case Current Transformers 1 PE Range Moulded Case Current Transformers An extensive range of high quality current transformers offering comprehensive measuring class accuracies. The PE

More information

Low voltage. NG to 160 A. Modular incoming circuit breakers and switch-disconnectors for DIN-panel installation.

Low voltage. NG to 160 A. Modular incoming circuit breakers and switch-disconnectors for DIN-panel installation. Low voltage NG160 16 to 160 A Modular incoming circuit breakers and switch-disconnectors for DIN-panel installation Catalogue 2010 NG160 circuit breaker Ready to install NG160 General contents Presentation

More information

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester These modular distribution panel protectors for three phase power systems are designed to prevent damage to electrical distribution systems from mainsborne transient voltages which can occur as the result

More information

RCCB

RCCB 2000 2000 is an advanced modular consumer unit system offering either DP isolator or 2 module DP RCCB (Residual Current Circuit Breaker) incoming control in a split load and inline arrangements. 236 Enclosures

More information

Miniature circuit breakers for all applications

Miniature circuit breakers for all applications Miniature circuit breakers for all applications BETA Low-Voltage Circuit Protection Answers for infrastructure. BETA Low-Voltage Circuit Protection: Circuits under Control, Wherever, Whenever. Whether

More information

Catalogue G System Pack, wall mount and floor standing enclosures. Prisma Plus LV Switchboards Devised to save time

Catalogue G System Pack, wall mount and floor standing enclosures. Prisma Plus LV Switchboards Devised to save time Catalogue G System Pack, wall mount and floor standing enclosures Prisma Plus LV Switchboards Devised to save time General contents Index 2 General presentation 8 Pack 10 17 General presentation Installation

More information

Sentry. Flush mounting versions Flush mounting available for even neater installations.

Sentry. Flush mounting versions Flush mounting available for even neater installations. 271 range introduction features and benefits The range of Consumer Units from MK Electric has been stylishly designed to blend in with its environment. The curved lines and slim-line appearance mean it

More information

Invicta 3 Panelboards

Invicta 3 Panelboards Invicta 3 Panelboards The new range of Invicta 3 panelboards are our easiest boards ever to install, and will help you meet the needs of Part L2 of the Building Regulations. The last few years have seen

More information

MOTOR PROTECTION CIRCUIT BREAKERS

MOTOR PROTECTION CIRCUIT BREAKERS MOTOR PROTECTION CIRCUIT BREAKERS PAGE -2 PAGE -2 SMA Thermal trip adjustment ranges 9-32A (5 choices) Breaking capacity Icu at 400V: 50kA Suitable for mounting in consumer switchboards with minimum 58mm

More information

Sentry Technical. Consumer Units and Enclosures TD255. Standards and approvals. Description. Features. Technical specification

Sentry Technical. Consumer Units and Enclosures TD255. Standards and approvals. Description. Features. Technical specification TD255 Consumer Units and Enclosures Standards and approvals All Sentry consumer units are designed to fully comply with the requirements of BS EN 60439-3. Weatherproof enclosures are designed to fully

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

RCDs RCBOs MCBs Isolating Switches Switchboards

RCDs RCBOs MCBs Isolating Switches Switchboards RCDs RCBOs MCBs Isolating Switches Switchboards 1300 722 275 F: 1300 738 717 RCD 4 Pole 6KA RCDs monitors at all times the current flow and will cut the electrical supply in case of an imbalance. Suitable

More information

Miniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data :

Miniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data : Miniature Circuit Breakers reliable solutions for protection of installations against over-current phenomenon Advantages for you : Bi-connect terminals for simultaneous termination of bus bar & wires Unique

More information

RESIDUAL CURRENT CIRCUIT BREAKERS OFE (6 ka)

RESIDUAL CURRENT CIRCUIT BREAKERS OFE (6 ka) Residual current circuit breakers MINIA RESIDUAL CURRENT CIRCUIT BREAKERS OFE ( ka) They react to sine-wave residual current (type AC) For protection: against dangerous contact with live parts (I Δn 30

More information

Residential circuit protection buyers guide

Residential circuit protection buyers guide Residential circuit protection buyers guide 2 Contents The range overview... 4 Wiring regulation changes... 6 Domae consumer units... 8 Features and benefits... 9 Quick selector - reference numbers and

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information

Miniature Circuit Breakers and Supplementary Protectors. Contents

Miniature Circuit Breakers and Supplementary Protectors. Contents . Optimum and Efficient Protection for Every Application Product Overview Features Optimum product quality, tested reliability and safety stand for best protection of personnel, installations and plant.

More information

1492-SP Supplementary Protectors

1492-SP Supplementary Protectors Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Approval marks are easily visible on dome Terminal design helps prevent wiring misses Scratch-

More information

LoadCentre KQ+ Distribution boards

LoadCentre KQ+ Distribution boards LoadCentre KQ+ Distribution boards Simply safer Square D Serving Your Needs To help electrical contractors Square D provide: An extensive range of easy to install products. Readily available products from

More information

Products and solutions for generating sets

Products and solutions for generating sets Products and solutions for generating sets www.lovatoelectric.com Tra dition and Innovation Since 1922 The first LOVATO Electric headquarters founded in Bergamo (Italy) in 1922: the starting point of the

More information

ALPHA AS NF Universal Modular Distribution Boards

ALPHA AS NF Universal Modular Distribution Boards ALPHA AS NF Universal Modular Distribution Boards ALPHA Distribution Boards ALPHA AS universal modular distribution boards provide you with the best framework for currents up to 800 A. The comprehensive

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

ALPHA SIMBOX Small Distribution Boards

ALPHA SIMBOX Small Distribution Boards ALPHA SIMBOX Small Distribution Boards /2 Introduction /3 Introduction /4 Flush-mounting and hollow-wall distribution boards /5 Surface-mounting and hood-type distribution boards /6 Accessories /7 Dimensional

More information

Surge Protection for Surveillance Systems

Surge Protection for Surveillance Systems Surge Protection for Surveillance Systems 1-in-1 Protection for Network Cameras 2-in-1 Protection for Power and Audio/Video Signals 3-in-1 Protection for Power, Audio/Video and PTZ Control Signals Application:

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

EUSR. An Introduction To BS7671 Amendment 3:2015 DESIGNED FOR featuring Consumer Units for Domestic (Household) Premises as per Reg

EUSR. An Introduction To BS7671 Amendment 3:2015 DESIGNED FOR featuring Consumer Units for Domestic (Household) Premises as per Reg PR EUSR An Introduction To BS7671 Amendment 3:2015 featuring Consumer Units for Domestic (Household) Premises as per Reg. 421.1.201 DESIGNED FOR 2015 Third Amendment Update Significant Change 3rd Amendment

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Product Overview The Series 230 automatic transfer

More information

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application Miniature Circuit Breakers Areas of Application Miniature circuit breakers (MCBs) of the N-System primarily protect cables and conductors against overload and short circuit. Thus, they also protect electrical

More information

ic60n RCBO 30 ma IEC , IEC , AS/NZS

ic60n RCBO 30 ma IEC , IEC , AS/NZS ic60n RCBO 30 ma DB405571 Country approval pictograms IEC 61009-1, IEC 61009-2-2, AS/NZS 61009.1 PB110075-70 b The single-phase ic60n RCBO s self-contained residual current device provides protection of

More information

SR60 Busbar System 2/1 2/2. General Data. 2/3 Busbar routing. 2/7 Mounting components. 2/13 Accessories

SR60 Busbar System 2/1 2/2. General Data. 2/3 Busbar routing. 2/7 Mounting components. 2/13 Accessories / SR0 Busbar System General Data / Busbar routing / Mounting components / Accessories / SR0 Busbar System General Data Overview The SR0 busbar system is a modular system for busbars, for installation in

More information

LSFC Power Factor Correction Systems

LSFC Power Factor Correction Systems LSFC Ready to connect, automatic in sheet steel cabinets for floor installation. Suitable for networks without harmonic distortion. Power Range: 100 to 00 kvar Modular construction in freestanding sheet

More information

DSE201, DSE201 M Compact design with enhanced protection

DSE201, DSE201 M Compact design with enhanced protection DSE20, DSE20 M Compact design with enhanced protection Ultimate safety DSE20 and DSE20 M: the highest level of reliability The P+N electronic residual current circuit-breakers with overcurrent protection

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors Close Protection from Moeller miniature branch circuit breakers miniature supplementary protectors FAZ branch circuit breakers General Information... Selection Tables Trip Characteristic C - Box terminals...

More information

Siemens AG KD Switch Disconnectors SENTRON. Edition December Answers for infrastructure and cities.

Siemens AG KD Switch Disconnectors SENTRON. Edition December Answers for infrastructure and cities. KD Switch Disconnectors SENTRON Edition December 01 Answers for infrastructure and cities. Related catalogs Low-Voltage Power Distribution and LV 10 Electrical Installation Technology SENTRON SIVACON ALPHA

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

Coordination of Surge protection devices

Coordination of Surge protection devices Coordination of Surge protection devices Design guide Surge arresters for commercial and industrial buildings Surge protection devices: how to choose them? coordination How to choose surge protection devices?

More information

New Class II Functional Supply Points. Cost-Effective technology from the rail experts.

New Class II Functional Supply Points. Cost-Effective technology from the rail experts. New Class II Functional Supply Points. Cost-Effective technology from the rail experts. A new solution for the safe distribution of power to railway signalling and control systems. This is part of our

More information

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing MULTI-POLE Lightning Current and Surge Arresters for PHOTOVOLTAIC SYSTEMS Class I / (B+C) and Class II / (C) COMPACT and MODULAR Housing 44 PV ISPRO BS(R) 12,5 The PV ISPRO BS(R) 12,5 series of over voltage

More information

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria DRT-301 A/D Three phase four wire DIN rail energy meter (Seven modules) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Structure Diagram 1.7 Dimensions

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

3RV1 Circuit-Breakers

3RV1 Circuit-Breakers SIRIUS 3R Description Mountable accessories 3RV1 Circuit- Breakers Circuit-breaker S00 with mountable accessories 3 2 1 5.1 NSK-7715a 4 Circuit-breaker S0 with mountable accessories 1 7 3 5.2 2 6 NSK-7716a

More information

Protection Equipment

Protection Equipment Protection Equipment Price groups 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J, 143, 401 /2 Introduction Motor starter protectors/ circuit breakers SIRIUS 3RV2 motor starter protectors up to 40 A / General data

More information