2002 Series DeviceNet Technical Manual

Size: px
Start display at page:

Download "2002 Series DeviceNet Technical Manual"

Transcription

1 2002 Series DeviceNet Technical Manual

2 Table of Contents 2002 Series DeviceNet Technical Manual 2002 Introduction...4 Product Overview...4 About DeviceNet...5 Overview DeviceNet Features...5 Cabling and Drop Line Lengths (as defined by DeviceNet specification)...5 Maximum Main Trunk Cable Length...5 Drop Line Cable Length Modularity...6 Discrete I/O...6 Pneumatic Valve Manifold...7 Distributing I/O with DeviceNet System Versatility...8 Distributed I/O Example Valve Unit...10 Z-Board and Coil Connections to Output Drivers...10 Z-Board Connectors...10 Module Configurations and Pinouts DeviceNet Communication Module Factory Default Settings LED Display Connector Types DeviceNet Communication Connector Pin Out...12 Power Connector Pin Out...12 MCM - Manual Configuration Module (Optional)...13 Rotary Switch Settings (SW1 & SW2)...13 DIP Switch Settings (SW3)...14 MCM Settings Example...15 Discrete I/O Modules...16 Rules...16 Module Types...16 Module Pinouts...17 Sub-D Output & I/O Modules...18 Examples of Sub-D Module Applications...19 Power Supply Wiring Diagrams...20 Single Power Supply Example (Male connector view)...20 Separate Power Supply Example (Male connector view)...20 Power Consumption...21 Power Connector Power Pins...21 Power Ratings...21 Recommended External Fuses:...21 Power Consumption and External Fuse Sizing Guide...22 I/O Module Wiring Diagrams...23 Definitions...23 Sinking (NPN) Input Connection...23 Sourcing (PNP) Input Connection...23 Sinking (NPN) Output Connection...24 DeviceNet Configuration and Mapping...25 EDS File...25 I/O Message Types...25 I/O Setup...25 Page 2

3 Outputs (Tx)...25 Inputs (Rx)...25 Assembly Parameter (User Configurable Parameter #241)...26 I/O (Rx/Tx) Sizes...27 Manifold Assembly - I/O (Rx/Tx) Size...27 Valve Side - I/O (Rx/Tx) Size...27 Discrete I/O Side - I/O (Rx/Tx) Size...27 Rx/Tx Size Calculation Errors...27 Bit Mapping Rules...28 Valve Side...28 Discrete I/O Side...28 Manifold I/O Sizing Worksheet...29 I/O Mapping...30 Example # Example #1 I/O Table...31 Example # Example #2 I/O Table...33 Example # Example #3 I/O Table...35 User Configurable Parameters...36 Example 2: Setting Output Idle Action Attribute Idle Action and Fault Action Parameters...37 Idle Action Sequence...38 Fault Action Sequence...39 Diagnostics...40 LED Functions...40 Internal Fuses...41 Output Short Circuit Protection...41 Appendix...42 System Specifications...42 Factory Default Settings...43 Troubleshooting...44 Glossary of Terms...45 Technical Support...46 Page 3

4 2002 Introduction Product Overview The 2002 is a sub-miniature valve product line featuring a variety of valve configurations and uses our G2-1 electronics. These include several serial / bus communication protocols which can control up to 24 valve solenoid coils on the valve side of the assembly and up to 16 points on the discrete I/O side. Points on the discrete I/O side may be inputs or outputs in groups of two. An optional sub-d jumper module allows these discrete I/O points to control an additional remote valve manifold with up to 16 valve solenoids. The Numatics Inc DeviceNet node is designed to DeviceNet specification, release 2.0 and supports the following I/O Message types: Polled, Change of State (COS), Cyclic and Combinations (i.e. Outputs can be set for Polled while Inputs can be set for COS for improved system response time). This manual addresses the specifics of configuring and commissioning the Numatics 2002 Series product configured with the DeviceNet communication interface. For more information relating to pneumatic valving and valve manifold assemblies, please refer to the latest Numatics 2002 Series catalog. Discrete I/O Connectors I/O Point LED Indicator(s) LED's Valve End Plates Valve AUX. POWER AUX POWER EXT FAULT MODULE NETWORK COMM. Manual Override Slave I/O Modules Slave I/O Modules Master I/O Modules Manual Configuration Module (MCM) LED Indicators Communications Module Page 4

5 About DeviceNet Overview DeviceNet is a bus communication protocol used to network industrial devices to eliminate labor intensive and expensive point to point wiring schemes. It is based on the CAN (Controller Area Network) protocol. Allen Bradley originally developed DeviceNet, but it is now supported by a multitude of manufacturers. The ODVA (Open DeviceNet Vendor Association) is an independent organization that governs the DeviceNet specification and oversees conformance testing for products which will be used in a DeviceNet system. DeviceNet uses a powered 4-wire network and can have up to 64 nodes. The protocol can transfer a maximum of 8 bytes of data per node cycle with three selectable communication (baud) rates; 125 Kbps, 250 Kbps, or 500 Kbps. Maximum trunk cable distance depends upon baud rate and cable media type. Refer to the table below for details. More information about DeviceNet and ODVA can be obtained from the ODVA web site DeviceNet Features Features Description DeviceNet Spec. Supported Designed to DeviceNet Specification Revision 2.0 Bus Topology Straight with restricted drops Baud Rates Supported 125Kbps, 250 Kbps and 500 Kbps and Autobaud Duplicate address detection If a duplicate address is detected on power up, duplicates will not progress to run mode Error Correction Yes, if an error is detected, sender is requested to repeat the message Address Setting Done via Software or optional Manual Configuration Module (MCM) Termination Resistor (external) A 121 ohm, 1%, ¼ Watt resistor is required at each end of the trunk line ADR Support Auto-Device Replacement is supported when the MCM is disabled or not present (see page 41 for assistance) I/O Message Types Polled, Cyclic, Change of State (COS) or Combinations Supported Cabling and Drop Line Lengths (as defined by DeviceNet specification) Maximum Main Trunk Cable Length Baud Rate Thick Trunk Cable Thin Trunk Cable Flat Trunk Cable 125 Kbps 1640 ft (500 m) 328 ft (100 m) 1246 ft (380 m) 250 Kbps 820 ft (250 m) 328 ft (100 m) 656 ft (200 m) 500 Kbps 328 ft (100 m) 328 ft (100 m) 246 ft (75 m) Drop Line Cable Length Maximum Drop Cumulative Drop Baud Rate Length Length 125 Kbps 20 ft (6 m) 512 ft (156 m) 250 Kbps 20 ft (6 m) 256 ft (78 m) 500 Kbps 20 ft (6 m) 128 ft (39 m) Page 5

6 2002 and G2-1 Electronics Modularity Discrete I/O The 2002 product line is a completely modular system. As shown below, all of the electronic modules plug together, allowing easy assembly and field changes. Page 6

7 Pneumatic Valve Manifold The pneumatic valve manifold is also modular. The valve solenoid coil connections are made automatically using Z-Board technology (plug together PC boards which allow internal connection from solenoid coils to output drivers without the use of wires). This allows easy assembly and field changes. Page 7

8 Distributing I/O with G2-1 Electronics 2002 DeviceNet System Versatility The 2002 series fieldbus manifold allows its discrete output points to be distributed from the central manifold by using the Sub-D Jumper option (see page 17). This distribution capability does not affect any network or communication node settings, and can be made at any time, even after the manifold has been installed and commissioned. The distributed I/O points can be used for various output devices, including additional manifolds with a Sub-D connector option. Please refer to Figure 1 on the following page for sample configuration layouts. Page 8

9 AUX POWER EXT FAULT MODULE NETWORK AUX POWER EXT FAULT MODULE NETWORK AUX POWER EXT FAULT MODULE NETWORK 2002 Series DeviceNet Technical Manual Distributed I/O Example Example #1 24 Valve Coil Outputs 16 Local, Discrete I/O AUX. POWER COMM. Example #2 24 Valve Coil Outputs 16 Remote Valve Coil Outputs AUX. POWER COMM. Example #3 24 Valve Coil Outputs 8 Local, Discrete I/O 8 Remote Valve Coil Outputs AUX. POWER COMM. Figure 1 Page 9

10 2002 Valve Unit Z-Board and Coil Connections to Output Drivers Z-Board plug together technology connects all valve side solenoids to the valve coil output drivers located in the communication node. Valve side outputs can be configured by software setting the assembly parameter or by manually setting the dip switches in the optional manual configuration module (MCM). Valve side outputs can be set to 0, 8, 16 or 24 outputs. The first output (BYTE 0, BIT 0) connects to the 14 (A) solenoid coil on the valve closest to the communication node. Plug-in Manifold with Integral Z-Board Eliminates Wiring Z-Board Connectors Double solenoid Single solenoid Z-Board Z-Board (White Valve Connector) (Black Valve Connector) Valve connector color visible from top of manifold block. DOUBLE SINGLE A(14) Negative (-) B(12) Negative (-) Common Positive (+) Page 10

11 Module Configurations and Pinouts DeviceNet Communication Module This module is the communication interface to the manifold. It contains communication electronics and solenoid coil output drivers. This communication module can be configured via software, or manually through the optional Manual Configuration Module (MCM). Factory Default Settings Type Value Description Baud Rate Autobaud Autobaud enabled (automatically detects 125Kbps, 250Kbps and 500Kbps) Node Address 63 MAC ID value Assembly Parameter #241 Rx/Tx 5/5 I/O Message Type LED Display 24 Valve Coils 16 Discrete I/O Polled Selects the required I/O allocation, in bytes. (See Page 24) The produced (Tx) and consumed (Rx) values of the manifold system. The total number of I/O that the manifold is configured for including diagnostic input bits. (See Configuration and Mapping for additional information on page 23) Communication connection Power Connector AUX. POWER LED s AUX POWER EXT FAULT MODULE NETWORK COMM. Communication Connector Connector Types Industry standard 12mm, micro connectors are used for communication and auxiliary power. The DeviceNet communication connector is a single keyway 5-pin male connector while the Aux. Power connector is a single keyway 4-pin male connector. Page 11

12 DeviceNet Communication Connector Pin Out Pin # Function Description 1 Drain Drain or shield 2 V+ Bus Power, 11-25VDC 3 V- Bus Power, Common 4 CAN_H Controller Area Network High, Communication Line 5 CAN_L Controller Area Network Low, Communication Line Power Connector Pin Out Pin # Function Description 1 +24VDC (Valves) Voltage Used to Power Valves 2 Earth Ground Protective Earth 3 0VDC Common 0VDC Common, for Valve and I/O Power 4 +24VDC (Node and Discrete I/O) Voltage Used to Power Discrete I/O and Node Electronics Net TM 3 AUX MALE 1 2 PIN 1= +24VDC (VALVES) PIN 2= EARTH GROUND PIN 3= COMMON 0VDC PIN 4= +24VDC (I/O) 4 3 COM PIN 1= DRAIN NOT USED PIN 2= V+ PIN 3= V- PIN 4= CAN_H PIN 5= CAN_L 4 MALE! ATTENTION Maximum pin capacity on pin #3 (0VDC common) of auxiliary power connector is 4 Amps. The combined draw of Pin #1 (Valves) and pin #4 (I/O) cannot exceed 4 Amps, at any given moment in time. power connector Pin #4 supplies power to node electronics. This pin must be powered at all times for communication node to be functional Page 12

13 MCM - Manual Configuration Module (Optional) DIP Switch SW3 All switches shown in the ON position Rotary Switch SW2 (Ones) Rotary Switch SW1 (Tens) The MCM is an optional module that allows the user to manually set baud rate, MAC ID and other user definable options, without the need for software configuration. If software configuration is preferred, this module is not necessary. The MCM consists of two rotary switches, SW1 & SW2, and one DIP switch, SW3. DIP and rotary switch settings do not take effect until power is cycled (turned OFF and ON). Rotary Switch Settings (SW1 & SW2) MAC ID (Network Address): Switch SW1 SW2 Description Sets the Tens Digit (MSD) Sets the Ones Digit (LSD) Address is set to a default setting of 63 prior to shipment. Rotary switch settings over 63, default to 63. Node address may only be assigned once per scanner card. EDS files may be downloaded from our web site at Page 13

14 DIP Switch Settings (SW3) Continued Baud Rate: Reserved: SW3-1 SW3-2 Kbaud *Off *Off 125 Off On 250 On Off 500 On On 500 Switch SW3-3,4 Manual or Software Configuration: Switch Setting SW3-5 Off SW3-5 *On Autobaud (Rev. 2.6 & higher): Description Not Used Reserved for future use Description MCM Not Enabled; Ignore MCM Settings (Software Configured) MCM Enabled; Use MCM Settings (Manually Configured) Switch Setting Description SW3-6 *Off Autobaud Enabled (baud rate configures automatically for 125 Kbps, 250Kbps and 500Kbps) SW3-6 On Autobaud disabled (set the baud rate manually either through switches or software) I/O Allocation (Rev. 2.4 & higher): Valve Side Discrete SW3-7 SW3-8 SW3-9 SW3-10 Coil Outputs I/O *Off *Off *Off *Off Off Off Off On 24 8 Off Off On Off 24 0 Off Off On On Off On Off Off 16 8 Off On Off On 16 0 Off On On Off 8 16 Off On On On 8 8 On Off Off Off 8 0 On Off Off On 0 16 On Off On Off 0 8 Any Other Setting Assembly Parameter 241 *Factory Default Settings coil output drivers are factory allocated to 24. Changes to this setting can be made via DIP switch SW3 (Bits 7-10) or by using DeviceNet software and choosing the appropriate Assembly Parameter value within the user configurable parameter options. See page 24. Page 14

15 MCM Settings Example The example below shows the correct settings for the following requirements: Baud Rate = 500 Kbaud; MCM = Enabled; Assembly Parameter = 24 Valve Coils and 16 Discrete I/O; Address = 23 Switch Settings: Switch Setting Description SW1 2 Sets the Tens Digit of MAC ID to Two (2) SW2 3 Sets the Ones Digit of MAC ID to Three (3) SW3-1 SW3-2 On On Sets Baud Rate to 500 Kbps SW3-5 On Use MCM Settings (Manual Configuration Enabled) SW Off Assembly Parameter = 24 Valve Coils and 16 Discrete I/O (Factory Default) Page 15

16 Discrete I/O Modules Rules The maximum number of I/O modules that can be used on the discrete I/O side of the manifold is 8 (Two masters and six slaves). Modules can be connected in any combination and sequence of inputs and outputs up to the logical limitations of 16 I/O. The first, and if required the fifth, module must be a master module. A master module differs from a slave module in that it contains the necessary circuitry to drive up to 8 I/O points. After 8 I/O points are used (1 master and 3 slaves) another master module is required. Each master or slave module allows for two I/O connections. The Sub-D type modules function as a master module. These modules may be located in either 1 st, 2 nd, 3 rd, 4 th, or 5 th positions. In the 1 st position, the Sub-D module may drive up to 16 I/O points. However, if the Sub-D module is located after the 1 st master module, it can drive only 8 I/O points. The Sub-D module must be the last module on the discrete I/O side. Discrete I/O Connectors I/O Point LED Indicator(s) LED's Valve End Plates Valve AUX. POWER AUX POWER EXT FAULT MODULE NETWORK COMM. Module Types Module Part # Slave I/O Modules Slave I/O Modules Master I/O Modules Manual Configuration Module (MCM) I/O Points Module Type Connection Type I/O Type Manual Override LED Indicators Communications Module Internal Bits Input 2 Master Input 2 x 12 mm (Micro) Sourcing (PNP)/ 2 inputs per module Sinking (NPN) N/A Input 2 Slave Input 2 x 12mm (Micro) Sourcing (PNP)/ 2 inputs per module Sinking (NPN) N/A 2 x 12 mm (Micro) Output 2 Master Output 2 inputs per module Sinking (NPN) 2 2 x 12 mm (Micro) Output 2 Slave Output 2 inputs per module Sinking (NPN) Output 8/16 Sub-D 25-Pin Sub-D (w/o din rail) Sinking (NPN) 8/ Output 8/16 Sub-D 25-Pin Sub-D (w/ din rail) Sinking (NPN) 8/ Input/ PNP (for Outputs) 8/16 8/16 Sub-D 25-Pin Sub-D (w/o din rail) Output NPN (for Inputs) for Out only Input/ PNP (for Outputs) 8/16 8/16 Sub-D 25-Pin Sub-D (w/ din rail) Output NPN (for Inputs) for Out only Page 16

17 Module Pinouts Part # Description Part # Description Master Input (Sinking-NPN/Sourcing-PNP) Slave Input (Sinking-NPN/Sourcing-PNP) Inputs/Module 2 Inputs/Module Part # Description Part # Description Master Output (Sinking-NPN) 2 Outputs/Module Slave Output (Sinking-NPN) 2 Outputs/Module Part # Description Part # Description Sub-D Output Module w/o Din Rail 8/16 Outputs (Sinking-NPN) w/ Din Rail w/o Din Rail w/ Din Rail Sub-D I/O Module 8/16 (NPN Out/PNP In) SUB-D CONNECTOR PINS 1-16 OUTPUTS SINKING (NPN) SUB-D CONNECTOR PINS 1-16 PIN 21 0VDC PINS VDC PIN 25 EARTH GROUND PIN 21 0VDC PINS VDC PIN 25 EARTH GROUND Page 17

18 Sub-D Output & I/O Modules There are two Sub-D module versions available: a Sub-D Output module, which can be used to drive up to 16 NPN Output points, and a Sub-D I/O module that can be used to access up to 16 remote discrete I/O points. Inputs are PNP (sourcing), Outputs are NPN (sinking, positive common). The Sub-D Output module allows the user to connect an additional valve manifold to the node. This increases the total number of valve solenoid outputs to 40. Sub-D I/O module can be used as an Output only device, an Input only device or a combination of Inputs and Outputs. However, the I/O module has two groups of eight selectable 2.7K ohm pull-down resistors for all 16 I/O points. These resistors are used for 2-wire sensors that need a small quiescent current to power their Input LED. The pull down resistors can also be used with 3-wire sensors, but are typically not needed. If the I/O module is used to control outputs, the resistors should be disabled to prevent trickle currents to connected loads. The factory default setting is with the (jumpers) shunts in the DISABLED position. To enable the resistors; move the (jumpers) shunts on the circuit board (inside the module) to the ENABLED position. There are two shunts; one enables/disables resistors for the first group of I/O (pins 1-8) and the other enables/disables resistors for second group of I/O (pins 9-16). Care should be taken to insure that total current draw from the Aux. Power connector does not exceed a combined maximum rating of 4 amps on the valve and discrete I/O pins. Sub-D Output & I/O Module s discrete points are available in groups of 8, depending on the number of discrete I/O master modules that are used. If no I/O master modules are used, there are 16 I/O points available through the Sub-D module. If a single discrete I/O master module is used, there are 8 I/O points remaining that are available through the Sub-D module. If two discrete I/O masters are used, there are no Output points available for use with the Sub-D module. (See table below) Discrete I/O Master Modules Used Discrete Output Points Available with Sub-D Module 16 8 N/A Pin Number N/A Master modules reserve 8 I/O points regardless of whether Slave modules are present. Page 18

19 Examples of Sub-D Module Applications The following are 3 examples showing various uses of the Discrete I/O Sub-D Module: AUX. POWER AUX POWER EXTFAULT MODULE BUS ERROR COMM. This example shows the Discrete I/O Sub-D Module being used to remotely control a 16-point PNP input distribution block. This example shows the Discrete I/O Sub-D Module being used to remotely control a 16-point PNP input distribution block. AUX. POWER AUX POWER EXT FAULT MODULE BUS ERROR COMM. AUX. POWER COMM. This example shows the Discrete I/O Sub-D Module being used to control a variety of PNP inputs and NPN outputs wired through a remote terminal strip. AUX POWER EXT FAULT MODULE BUS ERROR This example shows the Discrete I/O Sub-D Module being used to control a variety of PNP inputs and NPN outputs wired through a remote terminal strip. AUX. POWER AUX POWER EXT FAULT MODULE BUS ERROR COMM. This Example shows the Discrete I/O Sub-D Module being used to control a remote manifold with 16 (sinking type) coils. Page 19

20 Electrical Connections Power Supply Wiring Diagrams Single Power Supply Example (Male connector view) External Fuses Separate Power Supply Example (Male connector view) External Fuses! ATTENTION Please see page 20 for external fuse sizing guide. When using molded connector power cables, Do Not rely on wire colors for Pin-Out. Always use pin number references. Page 20

21 Power Consumption Power Connector Power Pins Power Ratings Aux. Power Description Connector Pin # 1 Powers Outputs (Valves) 4 Powers Discrete I/O and Node Electronics Maximum system current capability is 4 amps. Care should be taken not to exceed 4 amp draw through pin #3, 0VDC common (pin #1 and pin #4 combined). Discrete I/O current draw is dependent on the device(s) connected. It is critical to know what these values are in order to remain safely within the 4 amp limitation. Loads should not draw more than 0.5 amps of current from any one individual discrete output point. (Contact factory for higher current requirements) Power Connector Volts Tolerances Current Power Pin 1 +24VDC (Valves) Valve Coil 2002 (Each) 24VDC +10%/-15% A.75 Watts Pin 4 +24VDC (Node & I/O) Node 24VDC +/- 10%.015A.36 Watts Discrete Output 24VDC A max. * 12 Watts max. * Discrete I/O LEDs (Each) 24VDC A 0.36 Watts Communication Connector Volts Tolerances Current Power Pins 2 & 3 Bus Power (V+ and V-) 24VDC VDC A 0.6 Watts Power consumption of each Discrete I/O point is dependent on the specific current draw of input sensor devices and output loads. Please consult the factory for output loads greater than 0.5 amps. Recommended External Fuses: External fuses should be chosen based upon the physical manifold configuration. Please refer to the following pages for the fuse sizing guide. Page 21

22 Power Consumption and External Fuse Sizing Guide Power Consumption - Aux. Power Connector Pin #1 (Valves) Description Current Number of Valve Coils Energized Simultaneously X A = Amps Total Valve Current*: Amps Surge Compensation: X 1.25 Suggested External Pin #1 Fuse Value: Amps Power Consumption - Aux. Power Connector Pin #4 (Node and Discrete I/O) Description Current Communication Node Power Consumption =.015 Amps + Total load current drawn by simultaneously energized Discrete Outputs = Amps + Total load current drawn by Sensor Devices from Discrete Inputs = Amps Total I/O Current*: Amps Surge Compensation: X 1.25 Suggested External Pin #4 Fuse Value: Amps *The combination of total valve current and total I/O current must not exceed 4 Amperes. At any given moment in time, the combined current draw through pin #1 (Valves) and pin #4 (Node & Discrete I/O) cannot exceed 4 amperes. Therefore, the combined value of the two fuses on pin #1 and pin #4 should not exceed 5 amperes (4 amperes max by 1.25 surge compensation). Page 22

23 I/O Module Wiring Diagrams Definitions Sinking Description NPN Switching Negative Positive Common LOAD Sourcing Description PNP Switching Positive Negative Common LOAD Sinking (NPN) Input Connection Electronic Sensor Type Mechanical Sensor Type Input/Signal INPUT MODULE INPUT MODULE 4 (NPN) LOAD FEMALE 1 PIN 1=+24VDC PIN 3=COMMON OVDC PIN 4=INPUT 1 FEMALE PIN 1=+24VDC PIN 3=COMMON OVDC PIN 4=INPUT Sourcing (PNP) Input Connection Electronic Sensor Type Mechanical Sensor Type Input/Signal INPUT MODULE INPUT MODULE (PNP) LOAD FEMALE PIN 1=+24VDC PIN 3=COMMON OVDC PIN 4=INPUT FEMALE PIN 1=+24VDC PIN 3=COMMON OVDC PIN 4=INPUT Page 23

24 Sinking (NPN) Output Connection OUTPUT MODULE 3 4 FEMALE 1 OVDC LOAD PIN 1=+24VDC (COMM) PIN 3=NOT USED PIN 4=OUTPUT (SINKING).5A MAX. +24VDC Page 24

25 DeviceNet Configuration and Mapping EDS File The EDS file contains configuration information required to establish communication to a node on a DeviceNet network. An EDS stub file is loaded into the communication node prior to shipment and can be uploaded from the node with appropriate DeviceNet software (i.e. DeviceNet Manager, RS NetWorx, etc ). There are two EDS file s available for download, for the G2-1 series, the standard and the extended version. The standard EDS file contains s all parameters except the idle and fault action parameters. This allows efficient use of ADR function. The extended EDS file contains the idle and fault action parameters. These EDS files are available on the Numatics, Inc., website at or on the ODVA website at I/O Message Types The Numatics, Inc series DeviceNet communication node supports 3 different I/O message types. Below are brief definitions for the supported types: Polled The poll command is an I/O message that is transmitted by the Master. A Poll Command is directed towards a single, specific Slave (point to point). A Master must transmit a separate Poll Command Message for each one of its Slaves that is to be polled. The slave can respond with an I/O Message that is transmitted back to the Master. Cyclic The Cyclic message is transmitted by either the Master or the Slave. An Acknowledge Message may be returned in response to this message. The message is sent based on the value of a cyclic timer, which is set by the user. Change of State The Change of State message is transmitted by either the Master or the Slave. An Acknowledge Message may be returned in response to this message. The message is sent whenever a change of state occurs (i.e. an input changes from On to Off ). I/O Setup Outputs (Tx) Outputs are defined as any valve solenoid coil and/or any output point from a discrete output module. The output byte size (Tx) depends upon the physical configuration of the manifold as well as the Assembly Parameter settings (see the following explanation of Assembly Parameter). Please reference the following pages for a detailed explanation for calculating the output byte size (Tx). Inputs (Rx) Two types of inputs are recognized, discrete inputs and internal inputs. Discrete inputs are defined as input points from discrete input modules. Internal inputs are defined as input bits produced by output drivers. Thus the input byte size (Rx) will include discrete input points, as well as, internal inputs ( input bits). Please reference the following pages for a detailed explanation for calculating the input byte size (Rx). Page 25

26 Assembly Parameter (User Configurable Parameter #241) The Assembly Parameter is a user programmable option that allows the user to allocate the available I/O to valve coil outputs and discrete I/O as shown below. This allows the user to optimize the I/O byte size (Rx/Tx) to meet application requirements. The Assembly Parameter can be set via DIP switch SW3, Bit 7-10 (with node firmware Revision 2.4 or above, see page 13). Alternately, the Assembly Parameter can be easily set (in all node firmware revision levels) with appropriate DeviceNet Software (i.e. RS Networx, DeviceNet Manager, etc ), by sending an explicit message to the device: Send a set service to the Assembly Class (4), Instance (100), Data Attribute (3) using the Assembly Parameter data in the following table. Assembly Parameter 241 Valve Side Discrete Output Driver Bits Coil Outputs I/O Minimum Maximum * *Factory Default Setting The total number of input bits will be affected when changing Assembly Parameter data. Each assigned solenoid coil driver has an associated input bit which can be used for diagnostic purposes. These bits are mapped as inputs and are considered when calculating Input Byte Size (Rx). Page 26

27 I/O (Rx/Tx) Sizes Manifold Assembly - I/O (Rx/Tx) Size The overall size of the Input/Output (Rx/Tx) data for the manifold consists of the valve side data plus the discrete I/O side data. In the 2002 Series DeviceNet node, the Input/Output (Rx/Tx) size can vary from 0 to 5 bytes. Since there are many physical configuration possibilities for the 2002 series, the worksheet on page 27 will allow accurate sizing of the Input/Output (Rx/Tx) byte requirements. Valve Side - I/O (Rx/Tx) Size The Rx/Tx byte size for the valve side of the manifold consists of an output bit for each valve coil driver and an input bit for the corresponding input. The value for the valve side Rx/Tx byte size is determined by the user configurable Assembly Parameter (which is factory set to 5 bytes, 24 valve coil outputs and 16 discrete I/O) or by the manual dip switch settings in the Manual Configuration Module (MCM). Discrete I/O Side - I/O (Rx/Tx) Size The Rx/Tx byte size for the discrete I/O side of the manifold is configured based on the choice of I/O and/or Sub-D I/O modules, which are installed. The output (Tx) size will consist of an output bit for each output point. The input (Rx) size will consist of an input bit for each discrete input point and an input bit for each input from a corresponding discrete output. Sinking (NPN) outputs will return one bit for each output bit. The Assembly Parameter affects the I/O allocation of a manifold assembly. Sinking (NPN) output modules return one bit for each output bit. Rx/Tx Size Calculation Errors When the required manifold Input/Output (Rx/Tx) byte sizes are incorrectly set in the Allen- Bradley DeviceNet Configuration Software (i.e. RS Networx, DeviceNet Manager, etc.), the A-B DeviceNet scanner will error. The expected error code for this situation will be Error 77 Data Size Return Does Not Match Entry. Review your Rx/Tx size calculation to be sure they match the physical configuration of the manifold. Although the Rx/Tx values must be declared in the DeviceNet software for proper operation, they do not have to be mapped in the scanner. Page 27

28 Bit Mapping Rules Bit mapping for the 2002 series varies with the physical configuration of the manifold and the Assembly Parameter or dip switch configuration setting. The following is a breakdown of the bit mapping rules associated with the 2002 valve manifold. Valve Side Outputs (Tx) 1. coil outputs are distributed to the valve coils using the Z-Boards. 2. The valve solenoid coil output portion of the total output bytes (Tx) is dependent only on the Assembly Parameter setting or the dip switch configuration setting. Refer to page 13 for details. 3. Each solenoid coil output has an associated input bit (refer to Output Short Circuit r functional details). This will affect the overall input byte count (Rx). 4. coil output addressing begins at the first subbase nearest the node and continues in ascending order away from the communication node. 5. Each subbase is allocated 1 or 2 output bits, depending on the Z-Board type installed. Single Z-Board allocates 1 output bit, double Z-Board allocates 2 output bits. 6. Z-Boards can be used in any arrangement (all singles, all doubles, or any combination). Single solenoid valves can be used with double Z-Boards TM. However, one of the 2 available outputs will remain unused. Discrete I/O Side Outputs (Tx) 1. The discrete output byte size portion of Tx is always configured in byte increments, thus Master Module output bits, configured as a group of two, will always utilize a full byte (8 bits) when mapped. Although not used, the additional six bits in that byte are reserved for slave modules. 2. Discrete output bits are mapped in ascending order (away from the communication node) starting after the highest valve side output bit, which is dependant upon the Assembly Parameter setting or dip switch module configuration setting. (see page 13). 3. All discrete output modules have an associated internal input bit, which will affect the total number of input bytes (Rx). Note: Sinking (NPN) output modules allocate one internal input bit for every output point. Inputs (Rx) 1. The discrete input byte size portion of Rx is configured in byte increments. 2. Internal input bits, associated with the valve side output drivers, are always mapped before any physical input points. The quantity of these internal input bits depends upon the Assembly Parameter setting or dip switch module configuration setting. (see page 13.) Sinking (NPN) output modules allocate one internal input bit per output point for every output point. Page 28

29 1 Manifold I/O Sizing Worksheet Choose the appropriate Manifold Valve Configuration and place the corresponding Rx (Input byte) and Tx (Output byte) in the boxes labeled, Valve Byte Requirements at the bottom of the page. Choose up to two modules that you want to include on the discrete I/O side of the manifold and place the sum of the corresponding Rx (Input bytes) and Tx (Output bytes) in the boxes labeled, Discrete I/O Byte Requirements at the bottom of the page. Total the Rx (Input bytes) and Tx (Output bytes) values from the boxes labeled Discrete I/O Byte Requirements and Valve Byte Requirements in the boxes labele (Input/Output Bytes) for Manifold. This is the total Rx/Tx value required for the configured manifold. Valves Assembly Parameter Manifold Valve Configuration Rx (Input Bytes) Tx (Output Bytes) 0 Coils Up to 8 Coils 1 1 Up to 16 Coils 2 2 Up to 24 Coils 3 3 Master I/O Module Module # Description Rx (Input Bytes) Tx (Output Bytes) Master Input Module Master Output Module 1 1 Sub-D I/O Module Module # Description Rx (Input Bytes) Tx (Output Bytes) / Sub-D (with no Master I/O Module-up to 8 outputs) / Sub-D (with no Master I/O Module-up to 16 outputs) / Sub-D (with one Master I/O Module) 1 1 Summary Module Position Description Rx (Input Bytes) Tx (Output Bytes) 1st Master I/O or Sub-D I/O Module 2nd, 3rd, 4th or 5th Master I/O or Sub-D I/O Module Total Discrete I/O Byte Requirements: Total Valve Byte Requirements: Total Rx/Tx (Input/Output Bytes) for Manifold 3 2 Page 29

30 I/O Mapping Example #1 Assumed Settings - Assembly Parameter 241 set to 24 valve coils and 16 discrete I/O or MCM SW3-7, 8, 9, 10 set to OFF. Total Rx=5 and total Tx=5 Bytes. - Single Z-Boards TM used with single solenoid valves - Double Z-Boards TM used with double solenoid valves Discrete I/O Configuration I/O Sta. # I/O Type Part # Rx Tx 1 Input Master Input Slave Input Slave Input Slave Input Master Input Slave Input Slave Input Slave Manifold I/O Configuration Outputs and Mapping Location Total Outputs = 24 -Valve Outputs = 24 Bytes 0-2, Bits 0-7 -Discrete Outputs = 0 Inputs and Mapping Location Total Inputs = 40 - Inputs = 24 Bytes 0-2, Bits 0-7 -Discrete Inputs = 16 Bytes 3-4, Bits 0-7 Note: Output Drivers have input bits which show whether loads (coils) are open or shorted. These Input Bits are allocated and mapped before the physical discrete inputs. I/O Station #8 I/O Station #7 I/O Station #6 I/O Station #5 I/O Station #4 I/O Station #3 I/O Station #2 I/O Station #1 Valve Station #1 Valve Station #2 Valve Station #3 Valve Station #4 Valve Station #5 Valve Station #6 Valve Station #7 Valve Station #8 Valve Station #9 Valve Station #10 Valve Station #11 Valve Station # COMM AUX POWER EXT FAULT MODULE NETWORK AUX. POWER Input Slave (Byte 4, Bit 6 & 7) Input Slave (Byte 4, Bit 4 & 5) Input Slave (Byte 4, Bit 2 & 3) Input Master (Byte 4, Bit 0 & 1) Input Slave (Byte 3, Bit 6 & 7) Input Slave (Byte 3, Bit 4 & 5) Input Slave (Byte 3, Bit 2 & 3) Input Master (Byte 3, Bit 0 & 1) Bit 1 Bit 0 Valve Output Bit Number (Byte 0, Bit 0 & 1) (Byte 0, Bit 2 & 3) (Byte 0, Bit 4 & 5) (Byte 0, Bit 6 & 7) (Byte 1, Bit 0 & 1) (Byte 1, Bit 2 & 3) (Byte 1, Bit 4 & 5) (Byte 1, Bit 6 & 7) (Byte 2, Bit 0 & 1) (Byte 2, Bit 2 & 3) (Byte 2, Bit 4 & 5) (Byte 2, Bit 6 & 7) Page 30

31 Example #1 I/O Table Output Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil #1 1 Coil #16 Coil #15 Coil #14 Coil #13 Coil #12 Coil #11 Coil #10 Coil #9 2 Coil #24 Coil #23 Coil #22 Coil #21 Coil #20 Coil #19 Coil #18 Coil # Input Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil # Coil #16 Coil #24 Discrete Input #8 Discrete Input #16 Coil #15 Coil #23 Discrete Input #7 Discrete Input #15 Coil #14 Coil #22 Discrete Input #6 Discrete Input #14 Coil #13 Coil #21 Discrete Input #5 Discrete Input #13 Coil #12 Coil #20 Discrete Input #4 Discrete Input #12 Coil #11 Coil #19 Discrete Input #3 Discrete Input #11 Coil #10 Coil #18 Discrete Input #2 Discrete Input #10 Coil #9 Coil #17 Discrete Input #1 Discrete Input #9 Page 31

32 Example #2 Assumed Settings - Assembly Parameter 241 set to 24 valve coils and 16 discrete I/O or MCM SW3-7, 8, 9, 10 set to OFF. Total Rx=5 and total Tx=5 Bytes. - Single Z-Boards TM used with single solenoid valves - Double Z-Boards TM used with double solenoid valves Discrete I/O Configuration I/O Sta. # 1 I/O Type Part # Rx Tx Sub-D Module Valve Station #8 Valve Station #7 Valve Station #6 Valve Station #5 Valve Station #4 Valve Station #3 Valve Station #2 Valve Station # Aux. Valve Output Bit Number (Byte 4, Bit 6 & 7) (Byte 4, Bit 4 & 5) (Byte 4, Bit 2 & 3) (Byte 4, Bit 0 & 1) (Byte 3, Bit 6 & 7) (Byte 3, Bit 4 & 5) (Byte 3, Bit 2 & 3) (Byte 3, Bit 0 & 1) Manifold I/O Configuration Outputs and Mapping Location Total Outputs = 40 -Valve Outputs = 24 Bytes 0-2 Bits 0-7 -Discrete Outputs = 16 Bytes 3-4, Bits 0-7 Inputs and Mapping Location Total Inputs = 40 - Inputs = 40 Bytes 0-4 Bits 0-7 -Discrete Inputs = 0 -- Sub-D Module Note: Output Drivers have input bits which show whether loads (coils) are open or shorted. These Input Bits are allocated and mapped before the physical discrete inputs. COMM. NETWORK MODULE EXT FAULT AUX POWER AUX. POWER Valve Output Bit Number Valve Station #1 Valve Station #2 Valve Station #3 Valve Station #4 Valve Station #5 Valve Station #6 Valve Station #7 Valve Station #8 Valve Station #9 Valve Station #10 Valve Station #11 Valve Station # (Byte 0, Bit 0 & 1) (Byte 0, Bit 2 & 3) (Byte 0, Bit 4 & 5) (Byte 0, Bit 6 & 7) (Byte 1, Bit 0 & 1) (Byte 1, Bit 2 & 3) (Byte 1, Bit 4 & 5) (Byte 1, Bit 6 & 7) (Byte 2, Bit 0 & 1) (Byte 2, Bit 2 & 3) (Byte 2, Bit 4 & 5) (Byte 2, Bit 6 & 7) Page 32

33 Example #2 I/O Table Output Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil #1 1 Coil #16 Coil #15 Coil #14 Coil #13 Coil #12 Coil #11 Coil #10 Coil #9 2 Coil #24 Coil #23 Coil #22 Coil #21 Coil #20 Coil #19 Coil #18 Coil #17 3 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil #1 4 Coil #16 Coil #15 Coil #14 Coil #13 Coil #12 Coil #11 Coil #10 Coil #9 Input Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil # Coil #16 Coil #24 Coil #8 Coil #16 Coil #15 Coil #23 Coil #7 Coil #15 Coil #14 Coil #22 Coil #6 Coil #14 Coil #13 Coil #21 Coil #5 Coil #13 Coil #12 Coil #20 Coil #4 Coil #12 Coil #11 Coil #19 Coil #3 Coil #11 Coil #10 Coil #18 Coil #2 Coil #10 Coil #9 Coil #17 Coil #1 Coil #9 Page 33

34 Example #3 Assumed Settings Aux. Valve Output Bit Number - Assembly Parameter 241 set to 8 valve coils and 16 discrete I/O or MCM SW3-7 and 10 set to OFF and SW3-8 and 9 set to ON. Total Rx=3 and total Tx=3 Bytes. - Single Z-Boards TM used with single solenoid valves - Double Z-Boards TM used with double solenoid valves Valve Station #4 Valve Station #3 Valve Station #2 Valve Station # (Byte 1 Bit 6 & 7) (Byte 1 Bit 4 & 5) (Byte 1 Bit 2 & 3) (Byte 1 Bit 0 & 1) Discrete I/O Configuration I/O Sta. # I/O Type Part # Rx Tx 1 Input Master Input Slave Input Slave Input Slave Sub-D Module Manifold I/O Configuration Outputs and Mapping Location Total Outputs = 16 -Valve Outputs = 8 Bytes 0, Bits 0-7 -Discrete Outputs = 8 Bytes 2, Bits 0-7 Inputs and Mapping Location Total Inputs = 24 - Inputs = 16 Bytes 0-1 Bits 0-7 -Discrete Inputs = 8 Bytes 2 Bits 0-7 I/O Station #4 I/O Station #3 I/O Station #2 I/O Station #1 Sub-D Module Input Slave (Byte 2 Bit 6 & 7) Input Slave (Byte 2 Bit 4 & 5) Input Slave (Byte 2 Bit 2 & 3) Input Master (Byte 2 Bit 0 & 1) Bit 1 Bit 0 Note: Output Drivers have input bits which show whether loads (coils) are open or shorted. These Input Bits are allocated and mapped before the physical discrete inputs. Valve Station #1 Valve Station #2 Valve Station #3 Valve Station #4 Valve Station #5 Valve Station #6 Valve Station #7 Valve Station #8 Valve Station #9 Valve Station #10 Valve Station #11 Valve Station #12 COMM. NETWORK MODULE EXT FAULT AUX POWER AUX. POWER Valve Output Bit Number (Byte 0, Bit 0) (Byte 0, Bit 1) (Byte 0, Bit 2) (Byte 0, Bit 3) (Byte 0, Bit 4) (Byte 0, Bit 5) (Byte 0, Bit 6) (Byte 0, Bit 7) Page 34

35 Example #3 I/O Table Output Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil # Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil #1 Input Table BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Coil #8 Coil #7 Coil #6 Coil #5 Coil #4 Coil #3 Coil #2 Coil #1 1 Discrete Discrete Discrete Discrete Discrete Discrete Discrete Discrete Input #8 Coil #8 Input #7 Coil #7 Input #6 Coil #6 Input #5 Coil #5 Input #4 Coil #4 Input #3 Coil #3 Input #2 Coil #2 Input #1 Coil #1 Page 35

36 User Configurable Parameters The Numatics 2002 DeviceNet manifold allows the user to set many options which define how the manifold behaves in certain instances. The following is a description of these options (parameters). All of these configurable parameters can be adjusted using appropriate DeviceNet configuration software (i.e. RS Networx, DeviceNet Manager, etc ) and initiating the explicit messaging function. Some parameters can also be adjusted using the optional manual configuration module. Parameter # User configurable parameters are divided into seven groups, which are described in the following table. Name Description MCM Settings Explicit Message Information Class Instance Attribute - MAC ID Node address SW3 & Baud Rate Network speed SW1-1, Outputs 1-40 Allows outputs 1-40 to be forced on and off. N/A Inputs Monitor / Read only (Not Configurable) N/A Output 0-40 Idle Determines whether to use idle Action Attribute value attribute or hold last state N/A Output 0-40 Idle Value Attribute Defines state of output point N/A Output 0-40 Fault Determines whether to use idle Action Attribute value attribute or hold last state N/A Output 0-40 Fault Value Attribute Determines whether to use fault value attribute or hold last state N/A Assembly Parameter Allocates how many valve output drivers are mapped (0,8,16,24,32) SW Autobaud Determines whether Autobaud is enabled or disabled Note: Above table assumes EDS file version 2.6 or above. SW Explicit messages provide multi-purpose, point-to-point communication paths between two devices. These messages use the typical request/response-oriented network communication used to perform node configuration and problem diagnosis. Explicit messages typically use low priority identifiers and contain the specific meaning of the message as part of the data field; including the service to be performed and the specific object attribute address. Each explicit message uses a four level address; Node Address (MAC ID), Object Class Identifier, Instance and Attribute. Example 1: Change MAC ID Setting- To set the MAC ID for a node specify the appropriate node address (MAC ID), service code 16 (Set Attribute Single), Object Class Identifier 3 (see chart), Instance 1 (see chart), Attribute 1 (see chart) and Data to the MAC ID (node address) desired. Example 2: Setting Output Idle Action Attribute- To set the idle action attribute to hold last state for valve coil #4 specify the appropriate node address (MAC ID), service code 16 (Set Attribute Single), Object Class Identifier 9 (see chart), Instance 4 (see chart), Attribute 7 (see chart) and Data 1. Page 36

37 Idle Action and Fault Action Parameters Parameters are used to describe characteristics or behaviors of specific output points (bits). The parameters shown below are used to determine what happens to a particular output as a result of what occurs in the system. The two actions that provide for output determination are Idle and Fault. The output Idle and Fault parameters allow individual control of each output point on the manifold. The user, through configuration software, can determine how a specific output behaves when a fault or idle action occurs. These settings are non-volatile and thus will not change upon loss of power. The 3 behavior options are: 1) Hold Last State 2) De-Energize 3) Energize Page 37

38 Idle Action Sequence Idle Action and Idle Value attributes determine what the outputs do if the device encounters an Idle Event. An Idle Event is defined as a transmitted message with no application I/O data, for example, this could occur if the PLC is put into program mode. The process for determining the output status during an Idle Action is as follows: 1) The device receives an Idle. 2) The device determines what action to take based on the Idle Action attribute setting. 3) If the Idle Action attribute is 1, the output holds its last state. 4) If the Idle Action attribute is 0, the Idle Value is checked. a) If the Idle Value attribute is 0, the output de-energizes b) If the Idle Value attribute is 1, the output energizes Page 38

39 Fault Action Sequence Fault Action and Fault Value attributes determine what the outputs do if the device encounters a Fault Event. A Fault Event is defined as one or more of the I/O connections timing out. This could be caused by a failure of the node, failure of the master, or problems with the network communication and/or wiring. The process for determining the output status during a Fault Action is as follows: 1) A Fault occurs (timer has timed out) for the device. 2) The device determines what action to take based on the Fault Action attribute setting. 3) If the Fault Action attribute is 1, the output holds its last state. 4) If the Fault Action attribute is 0, the Idle Value is checked. a) If the Fault Value attribute is 0, the output de-energizes b) If the Fault Value attribute is 1, the output energizes Page 39

40 Diagnostics LED Functions Upon power up, the LED s indicate the status of the unit. There are four LED s on the 2002: network status, module status, auxiliary power and external fault. Power Connector AUX. POWER AUX POWER EXT FAULT MODULE NETWORK Communication Connector COMM. LED Name Color Description Network Module Aux Power Ext Fault Green Red Green Green Red OFF ON FLASHING ON FLASHING ON OFF ON OFF ON OFF Device is not on-line. Bus power not applied; Physical problem with network; Improper baud rate. Normal operation. Device is on-line and has established a connection. Device is on-line but has no established connections. The device has detected a bus error that has rendered it incapable of communicating on the network; Duplicate MAC ID; Bus Off condition; Physical problem with network. Communication failure one or more I/O connections have timed out. Normal operation. The device is operating properly. Critical hardware fault. Microprocessor is not running. DC Power applied to pin 1 on Aux. Power Connector. No DC Power present to pin 1 on Aux. Power connector. Discrete Input shorted Discrete Inputs are normal Page 40

41 Internal Fuses An internal fuse provides node protection in the event of a discrete input short. The external fault LED indicates the status of the discrete inputs. The internal fuse will reset when the short condition is corrected. Output Short Circuit Protection Bit Action During Fault Condition Output Type Valve Coil Driver or Sinking (NPN) Discrete Outputs Output State ON OFF Fault Condition Bit 0 No Fault 1 Fault - Short Circuit, Over Temp/Over Current 0 No Fault 1 Fault - Open Load Page 41

42 Appendix System Specifications Supply Voltage Bus (Network) Power Current Draw Current Recommended External Fuse Spike Suppression Discrete Outputs (Sinking (NPN) Operating Temperature for Electronic Components Electrical Valves: 24 VDC +/- 10% Discrete I/O: 24 VDC +/- 10% Bus: 11 to 25 VDC 25ma 24 VDC Total current on the Aux. Power Connector ( Valves & Outputs - Pin#1 and Node & Discrete I/O - Pin4) must not exceed 4 amperes. External fuses should be chosen depending upon manifold configuration. Please refer to power consumption chart on page 19 for additional fuse sizing information. Output spike suppression is internally provided for both discrete and valve outputs. Maximum 0.5 amperes per output Sinking (NPN). All outputs are short circuit protected. Contact factory for higher current requirements. 23 to 114 F (-5 to 46 C) Page 42

43 Factory Default Settings Description Default Node Address 63 Baud Rate Autobaud enabled Assembly Parameter Valve Coils, 16 Discrete I/O Valve Side - I/O (Rx/Tx) Sizing 3/3 I/O Side - I/O (Rx/Tx) Sizing 2/2 See Page 25 Output Idle Action Attribute 0 Output Idle Value Attribute 0 Output Fault Action Attribute 0 Output Fault Value Attribute 0 I/O Message Type Polled Page 43

44 Troubleshooting Symptom Possible Cause Solution Will not accept I/O data Scanner Error 77 Rx/Tx values not set correctly Resize Rx/Tx values in the DeviceNet software to match the physical configuration of the manifold. Refer to page 25 for further details. Won t go on-line. Network LED is Red & Module LED is Green Network LED off All LED s off Duplicate MAC ID CAN_HI / CAN_LO Reversed Power not properly applied With MCM: Change address and cycle auxiliary power. Without MCM: Disconnect node from network, change address, and reconnect node on network. Reverse wiring for proper connection Power must be applied to both pin #2 on the communication connector and pin #4 on the auxiliary power connector for the node to function properly. Pin #4 of the auxiliary power connector must have power even if Discrete I/O modules are not installed. The wrong valve solenoid coils are being energized. Z-Board TM type mismatch. Single Z-Board TM present where double Z-Board TM expected or vice versa. Check that correct Z-Board TM types are installed. See page 26 for bit mapping rules Device ID information doesn t match electronic key in scan list table entry Scanner Error 73 In RSNetWorx for DeviceNet Major and minor rev. boxes are checked in the Electronic Key of the scan list. For simplicity when using the ADR function leave the major and minor rev. boxes unchecked in the scan list s electronic key Valve outputs do not energize. All node LEDs normal. Output power not present or connected improperly on Aux. Power connector. Check for 24VDC on pin #1 of Aux. Power connector. Page 44

MPCR Series DeviceNet Technical Manual

MPCR Series DeviceNet Technical Manual MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction...3 Product Overview...3 About DeviceNet...4 Overview...4 MPCR DeviceNet Features...4 Cabling and Drop Line Lengths (as

More information

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths

More information

2005/2012 Series Profibus DP Technical Manual

2005/2012 Series Profibus DP Technical Manual 2005/2012 Series Profibus DP Technical Manual LT2005/2012PBTECH-1 04/02 www.numatics.com Table of Contents 2005/2012 Series Profibus DP Technical Manual PAGE About Profibus DP... 3 Overview... 3 G2-2 Profibus-DP

More information

G3 Series DeviceNet TM Technical Manual

G3 Series DeviceNet TM Technical Manual G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined

More information

G2-2 ControlNet 2005/2012 Series Technical Manual

G2-2 ControlNet 2005/2012 Series Technical Manual G2-2 ControlNet 2005/202 Series Technical Manual LT2005/202CNTECH- 0/03 www.numatics.com Table of Contents 2005/202 Series ControlNet Technical Manual PAGE About ControlNet... 3 Overview... 3 G2-2 ControlNet

More information

MPCR Series Profibus-DP Technical Manual

MPCR Series Profibus-DP Technical Manual MPCR Series Profibus-DP Technical Manual TDMPCRPBTECH-1 12/04 www.numatics.com Table of Contents MPCR Series Introduction...3 Product Overview...3 About Profibus...4 Overview...4 MPCR Profibus Features...4

More information

G3 Series PROFIBUS DP Technical Manual

G3 Series PROFIBUS DP Technical Manual G3 Series PROFIBUS DP Technical Manual Table of Contents G3 Series PROFIBUS DP Technical Manual PAGE About PROFIBUS-DP...3 Overview...3 G3 PROFIBUS-DP Features...3 Cabling and Drop Line Lengths (as defined

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your 2004 Series valve manifold with integrated Numatics G2- A-B 77 Remote I/O communication protocol.

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Getting Started This is a brief document designed to quickly get you started setting up your 200/2012 Series valve manifold with integrated Numatics G2-2 Profibus-DP communication protocol. Please note

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Getting Started This is a brief document designed to quickly get you started setting up your 2002 Series valve manifold with integrated Numatics G2-1\2 Profibus-DP communication protocol. Please note that

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. I P MAC AD D RE S S Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics G2-2 Series EtherNet/IP communication node. 1)

More information

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling MATERIAL HANDLING MANIFOLDS WITH DeviceNet INTERFACE 01348(N or G) MH** -- Material Handling 01351(N or G) MH** -- Material Handling Note: N = NPT ports G = BSPP ports SOL 14 SOL 12 Station #3 SOL 14 SOL

More information

Quick Start Manual G2-2 Series with Ethernet Interface

Quick Start Manual G2-2 Series with Ethernet Interface Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with integrated G2-2 series EtherNet/IP communication protocol. 1) Initial Unpacking and Inspection

More information

01325T -- Robot Welder

01325T -- Robot Welder WELDING MANIFOLDS WITH DeviceNet INTERFACE 01325T -- Robot Welder 01326T -- Pedestal Welder Station #2 (WELD) SOL 14 Station #1 (BACKUP) SOL 14 SOL 12 Prop. Reg. Water Saver Inputs Power (Aux.) DeviceNet

More information

G3 Series EtherNet/IP TM Technical Manual

G3 Series EtherNet/IP TM Technical Manual G3 Series EtherNet/IP TM Technical Manual Conditions for use of this product G3 Series EtherNet/IP Technical Manual () Numatics G3 Manifold ("the PRODUCT") shall be used in conditions; i) Where any problem,

More information

Type-5500 with Profibus-DP Interface Quick Start Manual

Type-5500 with Profibus-DP Interface Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your Type-5500 manifold with integrated Profibus-DP communication protocol. Please note that this document is not

More information

Table of Contents. Fieldbus Electronics and I/O G2-1 Electronics G2-2 Electronics Individual Base Node...

Table of Contents. Fieldbus Electronics and I/O G2-1 Electronics G2-2 Electronics Individual Base Node... Table of Contents Fieldbus Electronics and I/O............................... - G- Electronics..................................................................... - Features and Benefits..................................................................................

More information

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008 Elco BradControl DEVICENET ACTIVE 60mm Input/ Interface Block May, 2008 1. INTRODUCTION The following product numbers are covered by the information presented in this booklet: PART NUMBER BCDN-1600P-M12

More information

Table of Contents. Individual Base Node Direct to PLC Cables and Accessories

Table of Contents. Individual Base Node Direct to PLC Cables and Accessories Table of Contents Fieldbus Electronics and I/O...- G- Electronics....- Features and Benefits... Communication Protocols...-8 How to Order.... AKC Communication Module... 0 LH Mounting Cover Kit... 0 Fieldbus

More information

1782-JDC DeviceNet/Serial Gateway User s Manual

1782-JDC DeviceNet/Serial Gateway User s Manual 1782-JDC DeviceNet/Serial Gateway User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

DeviceNet - ODVA Conformance Test Results

DeviceNet - ODVA Conformance Test Results Test Information Scheduled Test Date July 9, 2012 Composite Test Revision 23 ODVA File Number 10105.06 Test Type Single Product DeviceNet - ODVA Conformance Test s Vendor Information Vendor Name Bronkhorst

More information

MAC VALVES, INC. A ENGINEERING RELEASE TRJ B EDS UPDATE / NAME CHANGE BI 284 TJR/KD. User s Manual for MAC Valves DeviceNet

MAC VALVES, INC. A ENGINEERING RELEASE TRJ B EDS UPDATE / NAME CHANGE BI 284 TJR/KD. User s Manual for MAC Valves DeviceNet MAC VALVES, INC. DOCUMENT NUMBER TITLE: User s Manual for MAC Valves DeviceNet PAGE 1 OF 24 UI-20 SM16 Manifold REVISION LEVEL DATE RELEASED CHANGE ECN NUMBER P.E. APPROVAL P.D. APPROVAL A 7-21-99 ENGINEERING

More information

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison DNETEXT-C CAN Bus Extender, Version 3 User s Manual Brad Harrison Although every effort has been made to insure the accuracy of this document, all information is subject to change without notice. Woodhead

More information

L5351 DeviceNet Communications Interface

L5351 DeviceNet Communications Interface L5351 DeviceNet Communications Interface Technical Manual HG353798 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

DeviceNet - ODVA Conformance Test Results

DeviceNet - ODVA Conformance Test Results DeviceNet - ODVA Conformance Test s Test Information Scheduled Test Date January 12, 2015 Composite Test (CT) Revision CT26 ODVA File Number 11368.01 Test Type Single Product Vendor Information Vendor

More information

DeviceNet Module. User Manual. 1 Important User Information. 2 Installation

DeviceNet Module. User Manual. 1 Important User Information. 2 Installation User Manual 1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. It is the installer's

More information

Diagnostics (Logical) Diagnostics (Physical)

Diagnostics (Logical) Diagnostics (Physical) Enclosure Mounted Input/Output Stations In-Cabinet I/O IP 20 Protection Ideal for Retrofits Automatic Baud Rate Sensing FDN20-4S-4XSG FDN20-4S-4XSG-E* FDN20-4S-4XSG-DIN* * Not UL Electrical Operating Current:

More information

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB BridgeWay PROFIBUS to DeviceNet Gateway User Manual Part No. AB7605 Pyramid Solutions 1850 Research Drive, Suite 300 Troy, Michigan 48083 Phone 248-524-3890 Web www.pyramid-solutions.com Publication PUB-AB7605-005

More information

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block USER S MANUAL FX2N-64DNET DeviceNet Interface Block FX2N-64DNET DeviceNet Interface Block Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation

More information

1782-JDO DeviceNet-to-Optomux Gateway User s Manual

1782-JDO DeviceNet-to-Optomux Gateway User s Manual 1782-JDO DeviceNet-to-Optomux Gateway User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

GE FANUC Parts 1. DeviceNet Network Master/Slave August 2002 GFK-1539A. Quick Start Guide. Product Description. Specifications. Preinstallation Check

GE FANUC Parts 1. DeviceNet Network Master/Slave August 2002 GFK-1539A. Quick Start Guide. Product Description. Specifications. Preinstallation Check Product Description Revision Letter: BA Firmware version: 1.10 Firmware upgrades: DeviceNet Certification: Product Name: None Certificate available upon request. DeviceNet Network Control Module (NCM)

More information

DeviceNet Expansion Board

DeviceNet Expansion Board DeviceNet Expansion Board Catalog No. EXBD05 Installation and Operating Manual 10/02 Table of Contents Section 1 General Information................................................... 1 1 Introduction.......................................................

More information

Allen-Bradley Automation

Allen-Bradley Automation Product Data 1791D CompactBlock I/O for DeviceNet 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. CompactBlock I/O modules are ideal

More information

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE 13050201 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN502 PRODUCT OVERVIEW 1 DN502 INSTALLATION 1 POWER

More information

DeviceNet Drive Profile CFW-09

DeviceNet Drive Profile CFW-09 Motors Automation Energy Transmission & Distribution Coatings DeviceNet Drive Profile CFW09 Communication Manual DeviceNet Drive Profile Communication Manual Serie: CFW09 Language: English Software Version:

More information

1782-JDC DeviceNet Serial Gateway User s Manual

1782-JDC DeviceNet Serial Gateway User s Manual 1782-JDC DeviceNet Serial Gateway User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO DeviceNet/PROFIBUS-DP Adapter - User Manual REV 4.0 SiboTech Automation Co., Ltd. Technical Support: +86-21-5102 8348 E-mail:gt@sibotech.net Table of Contents 1 ABOUT THIS DOCUMENT...2 1.1 GENERAL... 2

More information

Install the DeviceNet Module using the following procedure:

Install the DeviceNet Module using the following procedure: Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from

More information

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit Fieldbus system DeviceNet Compatible GW unit Operation Manual EX50-GDN URL http://www.smcworld.com Akihabara UDX 5F, --, Sotokanda, Chiyoda-ku, Tokyo 0-00, JAPAN Phone: +8-507-89 Fax: +8-598-56 Note: Specifications

More information

Mod. TCxD. DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 24

Mod. TCxD. DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 24 Mod. TCxD DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES & I/O SIGNAL Pg. 1 di 24 INDEX Important note...3 Abbreviation...3 Legend of symbols...4 Terms Definition...4 System descripiton...5 Module

More information

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output MICRO-SCREEN DIN Controllers with DeviceNet Trip Output Supplement to MICRO-SCREEN Instruction Manual P/N 48753 Features Offers all of the features of standard MICRO-SCREEN DIN controllers (see Instruction

More information

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE 13050301 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN503 PRODUCT OVERVIEW 1 DN503 INSTALLATION 1 POWER

More information

DeviceNet System Installation manual rev. 3.0

DeviceNet System Installation manual rev. 3.0 DeviceNet System INSTALLATION MANUAL rev. 3.0 page 1 of 1 0 Technical characteristics DeviceNet System Installation manual rev. 3.0 SUPPLY VOLTAGE: 24 V ± 10 % WORKING TEMPERATURE: 0 50 C PERCENTAGE OF

More information

I/O EXPANSION MODULES

I/O EXPANSION MODULES 4 Trio Motion Technology 4-2 Hardware Reference Manual General Description of I/O Modules Trio Motion Technology s range of digital and analogue input/output expansion modules are designed to enable simple

More information

TURCK Industrial I/O DeviceNet Products

TURCK Industrial I/O DeviceNet Products TURCK Industrial I/O DeviceNet Products F1 TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com Industrial Automation DeviceNet System

More information

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure:

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure: PIM-DN-01 DeviceNet Interface 1. Installation Install the DeviceNet Interface using the following procedure: 1. Remove control power and mains supply from the soft starter. 2. Attach the DeviceNet Interface

More information

Powered Roller Controller for DeviceNet

Powered Roller Controller for DeviceNet PRC-620-090 TECHNICAL DATA Description The Holjeron Powered Roller Controller for use with DeviceNet has the features needed to handle up to four zones in a material handling system. A Brushless DC Powered

More information

ZoneLink 4-Zone Controller For use with ZL.S-DK101 and Microroller

ZoneLink 4-Zone Controller For use with ZL.S-DK101 and Microroller ZLC-6320-2 0905 TECHNICAL DATA SHEET Description The enhanced Holjeron ZoneLink 4-Zone Controller for use with DeviceNet has the features needed to control up to four zones in a material handling system,

More information

THE FULL RANGE FOR PROCESS AUTOMATION. This document provided by Barr-Thorp Electric Co., Inc

THE FULL RANGE FOR PROCESS AUTOMATION.   This document provided by Barr-Thorp Electric Co., Inc THE FULL RANGE FOR PROCESS AUTOMATION www.turck.com TURCK Process Automation Networks DeviceNet Selection Guide AIM Page FDN20 Page OEM Page Discrete Input J11-J13, J29, J37 Discrete Input & Ouput J59

More information

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14 TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES Pg. 1 di 14 INDEX Legend of Symbols... 3 Conformity Declaration... 3 System Descripiton... 4 Module Specifications... 4 Installation

More information

Product Specification for CANbus to DeviceNet Transducer Gateway

Product Specification for CANbus to DeviceNet Transducer Gateway XG CANbus to DeviceNet Transducer Gateway April, 00 Product Specification for CANbus to DeviceNet Transducer Gateway The XG CANbus to DeviceNet Temposonics Gateway gathers position information from as

More information

VersaMax* DeviceNet Network Master/Slave

VersaMax* DeviceNet Network Master/Slave Product Description Quick Start Guide Revision: Firmware version: 1.10 Firmware upgrades: Specifications Operating Modes: Slaves Supported: Configuration: IC200BEM103-MA None Master only, Slave only, Combined

More information

2005 / 2012 / 2035 Series

2005 / 2012 / 2035 Series Generail Information on Fieldbus Systems FEATURES Solenoid air operated valve manifolds for date exchange via fieldbus. Internal wiring by Z-Board plug-in system. Plug-together flexibility due to different

More information

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1 Preface Thank you for purchasing the Pro-face LogiTouch Type-D DeviceNet master unit. The LogiTouch Type-D (also referred to as the LT Type-D ) allows connection to the DeviceNet Fieldbus to access many

More information

Doc. No.: EX**-OMC0024. Instruction Manual. SI Unit / DI Unit EX240-SDN2 EX240-IE1 SMC CORPORATION

Doc. No.: EX**-OMC0024. Instruction Manual. SI Unit / DI Unit EX240-SDN2 EX240-IE1 SMC CORPORATION Doc. No.: EX**-OMC00 Instruction Manual SI Unit / DI Unit EX0-SDN EX0-IE SMC CORPORATION SAFETY INSTRUCTIONS (Read carefully before use.) Thoroughly read this technical instruction manual and related manuals

More information

FC 300 DeviceNet and Allen Bradley Control logix 5550

FC 300 DeviceNet and Allen Bradley Control logix 5550 Introduction... 2 FC 300 DeviceNet card... 2 Creation of an EDS file... 4 Configuring the FC 300 with RS Networx... 7 I/O communication with RS Logix 5000... 1 0 Explicit messages with RS Logix 5000...

More information

WRC-CANR-DF-DN Series 3 CAN-Bus Fiber Optic Bus Extender User s Manual

WRC-CANR-DF-DN Series 3 CAN-Bus Fiber Optic Bus Extender User s Manual WRC-CANR-DF-DN Series 3 CAN-Bus Fiber Optic Bus Extender User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject

More information

Installation Instructions

Installation Instructions Installation Instructions 1771-SDN/B DeviceNet Scanner Module Installation Instructions 1 (Catalog Number 1771-SDN/B) Use this document as a guide to installing your 1771-SDN/B Scanner Module. Before you

More information

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB - 5G0078B0 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-/ASAB Issued on 5/06/ R. 0 This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide

More information

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those

More information

GPD 515/G5 DeviceNet Technical Manual

GPD 515/G5 DeviceNet Technical Manual GPD 515/G5 DeviceNet Technical Manual Technical References Refer to the following publications for further information about the GPD 515/G5 and DeviceNet. GPD 515/G5 Technical Manual Publication TM 4515

More information

Intelligent Devices IDI 6005 Speed Sign Controller Technical Manual

Intelligent Devices IDI 6005 Speed Sign Controller Technical Manual Intelligent Devices IDI 6005 Speed Sign Controller 4411 Suwanee Dam Road, Suite 510 Suwanee, GA 30024 T: (770) 831-3370 support@intelligentdevicesinc.com Copyright 2011, Intelligent Devices, Inc. All Rights

More information

FieldServer FS DeviceNet Master Adapter Driver

FieldServer FS DeviceNet Master Adapter Driver FieldServer FS-8700-114 DeviceNet Master Adapter Driver Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after March 2017.

More information

VLT 5000 DeviceNet and Allen Bradley Control logix 5550

VLT 5000 DeviceNet and Allen Bradley Control logix 5550 Foreword... 2 VLT 5000 DeviceNet card... 2 Configuring the VLT 5000 with RS Networx... 4 I/O communication with RS Logix 5000... 6 Explicit messages with RS Logix 5000... 8 1 Foreword This application

More information

Ordering Information Ordering Data I/O Module Part numbers 12mm (micro) connectors 8 I/O per module Singular I/O module Left hand I/

Ordering Information Ordering Data I/O Module Part numbers 12mm (micro) connectors 8 I/O per module Singular I/O module Left hand I/ Direct to PLC modules Numatics new line of with integrated I/O modules, allows a single multi-conductor cable connection to the manifold. This cable can handle the power, the valves and the sensor inputs

More information

Series SD6 with DeviceNet (Addendum)

Series SD6 with DeviceNet (Addendum) Series SD6 with (Addendum) Watlow s Series SD6 with offers excellent control and application flexibly in a 1/16th DIN panel mount package. The Series SD6 with has been successfully tested for use with

More information

Driver Manual (Supplement to the FieldServer Instruction Manual) FS X30 DeviceNet Master Adapter Driver

Driver Manual (Supplement to the FieldServer Instruction Manual) FS X30 DeviceNet Master Adapter Driver A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-114 X30 DeviceNet Master Adapter Driver APPLICABILITY & EFFECTIVITY Effective for all systems manufactured

More information

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01 ABB Drives User s Manual DeviceNet Adapter Module RDNA-01 DeviceNet Adapter Module RDNA-01 User s Manual 3AFE64504223 REV C EN EFFECTIVE: 16.11.2006 2006 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

MRUC-20 Modul-R CAN Bus Network

MRUC-20 Modul-R CAN Bus Network MRUC-20 Modul-R CAN Bus Network BALOGH This manual is based on information available at the time if its publication. Every effort has been made to provide accurate and up-to-date information. This document

More information

PROFIBUS DP/CAN Gateway PCA-100. User Manual

PROFIBUS DP/CAN Gateway PCA-100. User Manual PCA-100 REV 4.0 SiboTech Automation Co., Ltd. Technical Support: 021-5102 8348 E-mail: support@sibotech.net Catalog 1 Introduction... 2 1.1 About This Instruction... 2 1.2 Copyright... 2 1.3 Related Products...

More information

Diagnostics (Physical)

Diagnostics (Physical) DeviceNet Spanner Rugged, Fully Potted Stations IP 67 Protection Communicate Between s Connect Two DeviceNet Networks FDN-DN1 Electrical Operating Current: 125 ma from segment A, 30 ma from segment B Power

More information

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01 ABB Drives User s Manual DeviceNet Adapter Module RDNA-01 DeviceNet Adapter Module RDNA-01 User s Manual 3AFE64504223 Rev D EN EFFECTIVE: 16.07.2007 2007 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide. 1792D and 1732 Series

ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide. 1792D and 1732 Series ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide 1792D and 1732 Series 2 ArmorBlock I/O Overview The ArmorBlock family provides industrially hardened blocks of 24V dc digital I/O that can be mounted

More information

BridgeWay PROFIBUS to DeviceNet Gateway User Manual

BridgeWay PROFIBUS to DeviceNet Gateway User Manual BridgeWay PROFIBUS to DeviceNet Gateway User Manual Part No. AB7605 For Firmware Revision 2.01.01 and Later Pyramid Solutions, Inc. 30200 Telegraph Road, Suite 440 Bingham Farms, MI 48025 www.pyramidsolutions.com

More information

CDN067 DEVICENET SPECIFICATIONS

CDN067 DEVICENET SPECIFICATIONS CDN067 DEVICENET SPECIFICATIONS Revision History Revision Description Date 1.0 Initial Release Upgrade to DNet Rev. 2.0 07/20/98 Added support for status byte and status clear in poll Disallowed changing

More information

Driver Manual. FS DeviceNet Master Adapter Driver

Driver Manual. FS DeviceNet Master Adapter Driver A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-114 DeviceNet Master Adapter Driver APPLICABILITY & EFFECTIVITY Effective for all systems manufactured

More information

OPTION FOR ABB DRIVES, CONVERTERS AND INVERTERS FDNA-01 DeviceNet adapter module User s manual

OPTION FOR ABB DRIVES, CONVERTERS AND INVERTERS FDNA-01 DeviceNet adapter module User s manual OPTION FOR ABB DRIVES, CONVERTERS AND INVERTERS FDNA-01 DeviceNet adapter module User s manual List of related manuals See section Related manuals on page 15. You can find manuals and other product documents

More information

LVX Control Unit. Features:

LVX Control Unit. Features: Date 2013-02-28 Control Unit Features: Most parameters can be defined as required for your interfaces. You decide which information is output and how. Fast cycle times, just a few µs/beam. Maximum beam-count

More information

FieldServer FS DeviceNet Slave Adapter Driver

FieldServer FS DeviceNet Slave Adapter Driver FieldServer FS-8700-22 DeviceNet Slave Adapter Driver Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after December

More information

DN120 DeviceNet Gateway User Manual

DN120 DeviceNet Gateway User Manual DN120 DeviceNet Gateway User Manual DN120 PN 84-210010 Rev A Table of Contents CHAPTER 1 OVERVIEW... 4 CHAPTER 2 INSTALLATION... 5 MOUNTING... 5 WIRING... 6 DeviceNet Interface... 6 Serial Channel Interface...

More information

DC3IOB Revision User Guide Updated 3/29/10. Overview

DC3IOB Revision User Guide Updated 3/29/10. Overview Revision 080910 User Guide Updated 3/29/10 Overview The is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The integrated PLC

More information

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module Installation and Setup 1 2 In This Chapter.... Installing the H0 PSCM The Profibus Network Configuring the Module 2 2 Installing the H0 PSCM Remove the Slot Cover The first step in installing the option

More information

BNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005. User s Guide

BNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005. User s Guide BNI DNT-104-000-Z004 BNI DNT-202-000-Z005 BNI DNT-302-000-Z005 BNI DNT-305-000-Z005 BNI DNT-305-007-Z005 User s Guide Contents 1 User instructions 3 1.1. Structure of the guide 3 1.2. Typographical conventions

More information

CANOpen System Installation manual rev. 3.0

CANOpen System Installation manual rev. 3.0 CANOpen System INSTALLATION MANUAL rev. 3.0 page 1 /12 Technical characteristics CANOpen System Installation manual rev. 3.0 SUPPLY VOLTAGE: 24 V ± 10 % WORKING TEMPERATURE: 0 50 C PERCENTAGE OF HUMIDITY:

More information

X-gateway Interface Addendum DeviceNet Scanner Interface

X-gateway Interface Addendum DeviceNet Scanner Interface X-gateway Interface Addendum DeviceNet Scanner Interface Rev. 1.10 HMS Industrial Networks AB Germany Japan Sweden U.S.A + 49-721 - 96472-0 + 81-45 - 478-5340 + 46-35 - 17 29 20 + 1-773 - 404-3486 ge-sales@hms-networks.com

More information

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents Section 1.0 Description... 2 Section 2.0 Installation 2.1 Soft starter to gateway connection... 3 2.2 Soft starter configuration... 3 2.3 Gateway to DeviceNet connection... 3 2.4 Gateway configuration...

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

DeviceNet Communication Manual

DeviceNet Communication Manual DeviceNet Communication Manual Frequency Inverter Series: CFW-11 Language: English Document: 10000104642 / 00 04/2008 Summary ABOUT THIS MANUAL... 5 ABBREVIATIONS AND DEFINITIONS... 5 NUMERICAL REPRESENTATION...

More information

Products for DeviceNet

Products for DeviceNet Four-port DeviceNet Gateways W5-JDC4 The W5-JDC4 is a DeviceNet-to-serial link communications gateway that provides a flexible DeviceNet interface to as many as four different channels of ASCII devices.

More information

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) SUITABLE FOR EXTERNAL DISTRIBUTION

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) SUITABLE FOR EXTERNAL DISTRIBUTION ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 12- Relay Board P/N 103190 and 103338 PAGE 1 of 13 1. REVISI LOG... 2 2. OVERVIEW... 3 2.1. PART NUMBERS... 3 2.2. MODULE

More information

Allen-Bradley. User Manual. DeviceView Configurator (2707-DNC)

Allen-Bradley. User Manual. DeviceView Configurator (2707-DNC) Allen-Bradley DeviceView Configurator (2707-DNC) User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

DeviceNet Conformance Test Result

DeviceNet Conformance Test Result DeviceNet Conformance Test Result Test Date: 07 June 2004 Composite Test Revision: 18 Test Suite: M002 ODVA File Number: 10105 Vendor ID: 706 Vendor Name: Bronkhorst High-Tech B.V. Vendor Address: Nijverheidsstraat

More information

Table of Contents. C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3

Table of Contents. C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3 Table of Contents C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3 1. Product Overview... 3 1.1 InstaTool DeviceNet Module... 3 2. Installation... 5 2.1 Installing... 5 2.2

More information

Installation and maintenance instructions

Installation and maintenance instructions Before installation these instructions must be fully read and understood Table of contents 1. Introduction... 1 2. Operation and storage... 1 3. Distinguish OLD/NEW models... 1 4. Installation... 3 4.1

More information

How to Control and Monitor a C441 Motor Insight via DeviceNet

How to Control and Monitor a C441 Motor Insight via DeviceNet Application of DeviceNet and Motor Insight How to Control and Monitor a C441 Motor Insight via DeviceNet Application: The purpose of this application example is to demonstrate how to control and monitor

More information

DSC FIELDBUS MODULES...

DSC FIELDBUS MODULES... DSC FIELDBUS MODULES SUMMARY DSC FIELDBUS MODULES... 1 INTRODUCTION... 2 ELECTRICAL CONNECTIONS... 2 PROTOCOL DATA PACKAGE COMPOSITION... 3 Footprint in input... 4 Footprint in output... 4 MV MODULES INPUT

More information

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed.

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed. 2 The integrates position sensing, communication electronics, power outputs, auxiliary inputs and wire termination into a fully sealed compact package. The module also integrates a terminal strip directly

More information

Ocean Controls KTA-224 Modbus IO Module

Ocean Controls KTA-224 Modbus IO Module Ocean Controls Ocean Controls 8 Relay outputs (5A, 250VAC contacts) 4 Opto-Isolated Inputs with counters 3 Analog Inputs (10 bit) jumperselectable for 0-5V or 0-20mA 4 Input Counters RS485 or USB (virtual

More information

DeviceNet Communications Module

DeviceNet Communications Module DeviceNet Communications Module Catalog Number 1203-GK5 or 1336-GM5 Firmware 1.xxx-3.xxx TM CONFORMANCE TESTED User Manual Important User Information Solid state equipment has operational characteristics

More information

Fieldbus Gateway Type ME43

Fieldbus Gateway Type ME43 Fieldbus Gateway Type ME43 Gateway for Industrial Ethernet and Fieldbus standards Up to 128 input and 128 output variables can be assigned Easy integration in the process control system ensured through

More information