G2-2 ControlNet 2005/2012 Series Technical Manual

Size: px
Start display at page:

Download "G2-2 ControlNet 2005/2012 Series Technical Manual"

Transcription

1 G2-2 ControlNet 2005/202 Series Technical Manual LT2005/202CNTECH- 0/03

2 Table of Contents 2005/202 Series ControlNet Technical Manual PAGE About ControlNet... 3 Overview... 3 G2-2 ControlNet Features... 3 Segment lengths (as defined by ControlNet specification) /202 and G2-2 Introduction... 4 Product Overview /202 and G2-2 Electronics Modularity... 5 Discrete I/O... 5 Pneumatic Valve Manifold... 6 Distributing I/O with G2-2 Electronics... 7 G2-2 ControlNet System Versatility /202 Valve Unit... 9 Z-Board and Solenoid Coil Connections to Output Drivers... 9 Z-Board Connectors...0 Z-Board and Ribbon Cable Example:... Z-Board and Ribbon Cable with Valve Side Sub-d Example:...2 Module Configurations and Pinouts...3 ControlNet Communication Module (Node)...3 Connector Types...3 Auxiliary Power Connector Pin Out...4 Rotary Switches...5 Rotary Switch Settings...5 Rotary Switch Settings Example...6 Comm. Module...7 Discrete I/O Modules...8 Rules...8 Module Types...8 Input Modules:...9 Output Modules Electrical Connections Power Supply Wiring Diagrams Power Consumption Auxiliary Power Connection Discrete I/O Module(s) Power Jumper Power Rating Recommended External Fuses: Discrete I/O Power Jumper Discrete Sub-D Output Power Jumper Power Consumption and External Fuse Sizing Guide Chart I/O Module(s) Wiring Diagrams Definitions Sinking Description Sourcing Description Sinking (NPN) Input Connection Sourcing (PNP) Input Connection Sinking (NPN) Output Connection Sourcing (PNP) Output Connection ControlNet Configuration and Mapping...3 EDS File...3 I/O Setup LT2005/202CNTECH- 0/03 Page

3 Outputs Inputs I/O Sizes I/O Size - Manifold I/O Size - Valve Side I/O Size - Discrete I/O Side Manifold I/O Sizing Worksheet Mapping Rules Valve Side Discrete I/O Side I/O Mapping Example # Example # Example #3...4 Diagnostics Comm. Module / Power Module LED Functions Internal Fuses Output Short Circuit Protection Status Action During Fault Condition Appendix System Specifications Factory Defaults Settings Troubleshooting Glossary of Terms Technical Support LT2005/202CNTECH- 0/03 Page 2

4 About ControlNet Overview 2005/202 Series ControlNet Technical Manual ControlNet is a serial communication protocol used to network devices that wish to exchange time-critical application information in a deterministic and predictable manner and also eliminate labor intensive and expensive point to point wiring schemes. Allen Bradley originally developed ControlNet, but it is now supported by a multitude of manufacturers. ControlNet International is an independent organization that governs the ControlNet specification and oversees conformance testing for products, which will be used in a ControlNet system. ControlNet uses a RG-6 quad shield coax cable and can have up to 99 nodes. The protocol can transfer a maximum of 50 bytes of data per node cycle with a communication (baud) rates of 5 Mbit/ sec.. Maximum distance is depended upon cable media type and number of nodes. Refer to the section below for details. More information about ControlNet International can be obtained from the web site G2-2 ControlNet Features Features Address Setting Baud Rates Supported Bus Topology CE Connection Sizes Minimum requested packet interval (RPI) NAP Port Physical Media Redundant Media Termination Resistor (external) Description Via Rotary Switches 5 Mbit/sec. Linear bus, Tree, Star, mix of all three CE compliant 6 Words (32 Bytes) of Input Data and 6 Words (32 Bytes) of Output Data 5ms Network Access Port allows a temporary network connection at the node. The NAP uses a standard 8-pin RJ-45 connector. Coax RG-6 quad shield, Single or Dual Redundant Media The node supports redundant media. Two coax connectors are provided (Trunk Line A & B). A 75 ohms resistor is required at each end of each segment. Segment lengths (as defined by ControlNet specification) 000 Segment length (m) Number of taps LT2005/202CNTECH- 0/03 Page 3

5 2005/202 and G2-2 Introduction Product Overview 2005/202 Series ControlNet Technical Manual The 2005/202 is a valve product line featuring a variety of valve configurations and electronic interface options. These include several Fieldbus communication protocols that can control up to 32 valve solenoid coils, on the valve side of the assembly, and up to 32 I/O points of I/O on the Discrete I/O side. This manual addresses the specifics of configuring and commissioning the Numatics 2005/202 Series product line configured with the ControlNet communication interface. For more information relating to pneumatic valving and valve manifold assemblies, please refer to the Numatics 2005 & 202 Series catalog, No. LT2005/202-. LT2005/202CNTECH- 0/03 Page 4

6 2005/202 and G2-2 Electronics Modularity Discrete I/O The 2005/ 202 product line is a completely modular system. As shown below, all of the G2-2 electronic modules plug together, allowing easy assembly and field changes. Additionally, all the PC boards containing active electronics (i.e. communication, I/O and MCM) are also modular allowing changes to be made without the need to dismantle the manifold. LT2005/202CNTECH- 0/03 Page 5

7 Pneumatic Valve Manifold The pneumatic valve manifold is also modular. The valve solenoid coil connections are made automatically using Z-Board technology (plug together PC boards which allow internal connection from solenoid coils to output drivers without the use of wires). This allows easy assembly and field changes. LT2005/202CNTECH- 0/03 Page 6

8 Distributing I/O with G2-2 Electronics The G2-2 series fieldbus manifold allows its discrete I/O points to be distributed from the central manifold by using various I/O modules (see pages 8-23). This distribution capability can be made at any time, even after the manifold has been installed and commissioned, although, network or communication rack configurations may be affected depending on the new total number of I/O points configured. The distributed I/O points can be used for various input devices and loads with many different termination options, including additional manifolds with Sub-D connector option. Please refer to Figure on the following page for a sample configuration layout. LT2005/202CNTECH- 0/03 Page 7

9 G2-2 ControlNet System Versatility 2005/202 Series ControlNet Technical Manual Figure Example of network to PLC/IPC with distributed valve manifolds and I/O devices. LT2005/202CNTECH- 0/03 Page 8

10 2005/202 Valve Unit 2005/202 Series ControlNet Technical Manual Z-Board and Solenoid Coil Connections to Output Drivers Z-Board plug together technology connects all valve solenoids to the valve coil output drivers, located in the communication node. The valve solenoid coil output drivers are divided into 2 separate 6 bit groups. Output group # is comprised of the first output word, bits 0-5, and output group #2 is comprised of the second output word, bits 6-3. Output group # connects directly to the Z-Boards, while output group #2 is connected to Z-Boards via an internal ribbon cable or Valve Side Sub-D. The first output connects to the 4 (A) solenoid on the valve closest to the communication node. The 7 th 32 nd solenoids interconnect via the Z-Boards to output group #2. For the maximum capability of 32 solenoids, the 6 th and 7 th solenoid coils must NOT be on the same sub-base. Output Group # Connector Plug-in Manifold with Integral Z-Board Eliminates Wiring Output Group #2 Connector Single solenoid Z-Board Double solenoid Z-Board Earth Ground Pin #3 Common Pin #4 4(A) Solenoid Pin # 2(B) Solenoid Pin #2 LT2005/202CNTECH- 0/03 Page 9

11 Z-Board Connectors The 2005/202 valve series utilizes 2 different Z-Boards designs to achieve the single and double solenoid output functions that yield the possible 32 single, 6 double, or any combination of valve solenoid coil output capabilities. Single Z-Board Part # (202) Part # (2005) Double Z-Board Part # (202) Part # (2005) single double Ribbon Connection Single Z-Board Part # (202) Part # (2005) Ribbon Connection Double Z-Board Part # (202) Part # (2005) The 7 th solenoid (output group #2 s first bit) must be accessed via either the valve side sub-d output module or a ribbon connector type Z-board. LT2005/202CNTECH- 0/03 Page 0

12 Z-Board and Ribbon Cable Example: If fourteen (4) single solenoid and one () double solenoid valves are connected directly to the communication node via their Z-Boards, and one () single solenoid and four (4) double solenoid valves are connected to the communication node via the ribbon cable, the following would be the valve side bit map: S= Sgl. Sol. With Single Z-Board D= Dbl. Sol. With Double Z-Board D S Output Group # Connector to Z-Board Output Group #2 Connector to Ribbon Cable Output Group #2 Ribbon Connector Z-Board Output # Solenoid Coil Output # n/a n/a n/a n/a n/a n/a n/a In the above example, Output s #5 and #26 thru #3 are allocated but not used. LT2005/202CNTECH- 0/03 Page

13 Z-Board and Ribbon Cable with Valve Side Sub-d Example: If sixteen (6) single solenoid valves are connected directly to the communication node via their Z-Boards, and a valve side sub-d connector is connected to the communication node via the ribbon cable, the following would be the valve side bit map: S= Sgl. Sol. With Single Z-Board Coil Outputs 7-32 Output Group # Connector to Z-board Output Group #2 Connector to Ribbon Cable Output # Solenoid Coil Output # LT2005/202CNTECH- 0/03 Page 2

14 Module Configurations and Pinouts ControlNet Communication Module (Node) This module is the communication interface to the manifold. It contains communication electronics and short circuit protected solenoid coil output drivers Factory Defaults Settings Type Value Description Baud Rate 5M bit/sec. Data Rate is 5 Mbit/s Node Address 00 Node Address value Input/ Output Connection Sizes 8 In / 4 Out Bytes (4 In / 2 Out Words) + Discrete I/O The Input and Output Connection Size of the manifold system. The total number of I/O that the manifold is configured for, including diagnostic Status Input bits and. (See Mapping Section For Additional Information) LED Display Connector Types An Industry standard mini connector is used for auxiliary power. The Aux. Power is a single keyway 4 pin male connector. The two ControlNet communication connectors are BNC type connectors. LT2005/202CNTECH- 0/03 Page 3

15 Auxiliary Power Connector Pin Out Pin # Function Description +24VDC Voltage used to power outputs (valve coils and discrete (Valves and Outputs) outputs) 2 Earth Ground Protective Earth (case) 3 0VDC Common 0VDC Common, for valve and I/O power 4 +24VDC Voltage used to power discrete inputs and node (Node and Inputs) electronics 3 2 POWER 4 MALE! ATTENTION Maximum current capacity on pin #3 (0VDC common) of auxiliary power connector is 8 Amps. The combined draw of Pin # (Valves & Outputs) and pin #4 (Node & Inputs) cannot exceed 8 Amps, at any given moment in time. Auxiliary power connector pin #4 supplies power to node electronics. This pin must be powered at all times for communication node to be functional. LT2005/202CNTECH- 0/03 Page 4

16 Rotary Switches The Rotary switches allow the user to set the node address. Rotary Switch Settings Network Address: Switch NA 0 Sets the Ones Digits NA 0 Sets the Tens Digits Description! Address is set to a default setting of 00 prior to shipment. Rotary switch settings do not take effect until power is cycled (turned OFF and ON). ATTENTION LT2005/202CNTECH- 0/03 Page 5

17 Rotary Switch Settings Example The example below shows the correct settings for the following requirements: Node Address = 73 Switch Settings: Switch Setting Description NA 0 3 Sets the Ones Digits of MAC ID to Three (3) NA 0 7 Sets the Tens Digits of MAC ID to Two (2) LT2005/202CNTECH- 0/03 Page 6

18 Comm. Module Replacement and / or spare parts for the G2-2 ControlNet module can be purchased by ordering the entire module (communications and power module), or by specifying individual components (see chart below). LT2005/202CNTECH- 0/03 Page 7

19 Discrete I/O Modules Rules The maximum number of I/O modules that can be used on the Discrete I/O side of the manifold is 6. Modules can be connected in any combination and sequence of inputs and outputs up to the logical limitations of 32 I/O. Damage will occur if Discrete I/O and MCM Modules are inserted or removed with power applied. Module Types Module Part # Replacement I/O Board Part # I/O Points Module Size Connection Type I/O Type Internal Status s Input 4 Narrow 4 x 2mm ( input per conn.) Sinking (NPN) N/A Input 4 Narrow 4 x 2mm ( input per conn.) Sourcing (PNP) N/A Input 8 Narrow 4 x 2mm (2 input per conn.) Sinking (NPN) N/A Input 8 Narrow 4 x 2mm (2 input per conn.) Sourcing (PNP) N/A Input 8 Wide 8 x 2mm ( input per conn.) Sinking (NPN) N/A Input 8 Wide 8 x 2mm ( input per conn.) Sourcing (PNP) N/A Input 6 Wide 8 x 2mm (2 input per conn.) Sinking (NPN) N/A Input 6 Wide 8 x 2mm (2 input per conn.) Sourcing (PNP) N/A Input 6 Narrow Dual 5 Pin Sub-D (8 inputs per Sub-D) Sinking (NPN) N/A Input 6 Narrow Dual 5 Pin Sub-D (8 inputs per Sub-D) Sourcing (PNP) N/A Input 6 Narrow 25 Pin Sub-D (6 inputs) Sinking (NPN) N/A Input 6 Narrow 25 Pin Sub-D (6 inputs) Sourcing (PNP) N/A Output 4 Narrow 4 x 2mm ( input per conn.) Sinking (NPN) Output 4 Narrow 4 x 2mm ( input per conn.) Sourcing (PNP) Output 8 Narrow 4 x 2mm (2 input per conn.) Sinking (NPN) Output 8 Narrow 4 x 2mm (2 input per conn.) Sourcing (PNP) Output 8 Wide 8 x 2mm ( input per conn.) Sinking (NPN) Output 8 Wide 8 x 2mm ( input per conn.) Sourcing (PNP) Output 6 Wide 8 x 2mm (2 input per conn.) Sinking (NPN) Output 6 Wide 8 x 2mm (2 input per conn.) Sourcing (PNP) Output 22 Wide 25 Pin Sub-D w/aux Power (22 outputs) Sourcing (PNP) 6 LT2005/202CNTECH- 0/03 Page 8

20 Input Modules: Part # Description Part # Description Inputs (Sinking-NPN) - Input/Connector Inputs (Sinking-NPN) - Input/Connector Part # Description Part # Description Inputs (Sourcing-PNP) - Input/Connector Inputs (Sourcing-PNP) - Input/Connector Part # Description Part # Description Inputs (Sinking-NPN) 2 Inputs/Connector Inputs (Sinking-NPN) - 2 Inputs/Connector LT2005/202CNTECH- 0/03 Page 9

21 Part # Description Part # Description Inputs (Sourcing-PNP) - 2 Inputs/Connector Inputs (Sourcing-PNP) - 2 Inputs/Connector Part # Description Inputs (Sinking-NPN) 8 Inputs/Connector Byte X Byte X+ Part # Description Inputs (Sourcing-PNP) 8 Inputs/Connector Byte X Byte X+ LT2005/202CNTECH- 0/03 Page 20

22 Part # Description Inputs (Sinking-NPN) 6 Inputs/Connector Part # Description Inputs (Sourcing-PNP) 6 Inputs/Connector! ATTENTION Damage will occur if Discrete I/O and MCM Modules are inserted or removed with power applied. LT2005/202CNTECH- 0/03 Page 2

23 Output Modules 0.5 Amps per Output. (Consult factory for output loads greater than 0.5 Amps.) Over current and short circuit protected Status for Short or Open Circuit - Sinking Outputs utilize one status input for each output. - Sourcing Outputs utilize one status input for every four outputs Part # Description Part # Description Outputs (Sinking-NPN) - Output/Connector Outputs (Sinking-NPN) - Output/Connector NOT FOR NEW APPLICATIONS Part # Description Part # Description Outputs (Sourcing-PNP) - Output/Connector Outputs (Sourcing-PNP) - Output/Connector! Damage will occur if Discrete I/O and MCM Modules are inserted or removed with power applied! ATTENTION LT2005/202CNTECH- 0/03 Page 22

24 Part # Description Part # Description Outputs (Sinking-NPN) 2 Outputs/Connector Outputs (Sinking-NPN) - 2 Outputs/Connector NOT FOR NEW APPLICATIONS Part # Description Part # Description Outputs (Sourcing-PNP) - 2 Outputs/Connector Outputs (Sourcing-PNP) - 2 Outputs/Connector Part # Description Part # Description 22 Outputs (Sourcing-PNP) 6 Outputs (Sinking-NPN) Outputs/Connector 6 Outputs/Connector (Valve side only) Valve Side Sub-D PIN 25 PIN SUB-D CONNECTOR 4 PIN POWER CONNECTOR PIN PIN SUB-D FEMALE CONNECTOR PIN 25 PIN LT2005/202CNTECH- 0/03 Page 23

25 Electrical Connections Power Supply Wiring Diagrams Single Power Supply Example (Male connector view)! ATTENTION Please see page 28 for external fuse sizing guide. When using molded connector power cables, Do Not rely on wire colors for Pinout. Always use pin number references. LT2005/202CNTECH- 0/03 Page 24

26 Power Consumption Auxiliary Power Connection Aux. Power Connector Pin # Description 24 VDC Power for Valves & s 4 24 VDC Power for Inputs & Node Electronics Discrete I/O Module(s) Power Jumper All of Numatics, Inc., G2-2 I/O modules have a selectable power source jumper. This jumper determines which Aux. Power connector pin ( or 4) will power these modules. This option allows the user to select how each specific module will be powered during different conditions (i.e. E-Stop). Each I/O module can be set-up independently allowing individual Output and/or Input modules to remain active if needed. Power Rating Maximum system current capability is 8 amps. Care should be taken not to exceed 8 amp draw through pin #3 0VDC common (Current of pin # and pin #4 combined). Discrete I/O current draw is dependent on the device(s) connected. It is critical to know what these values are in order to remain safely within the 8 amp limitation. Loads should not draw more than 0.5 amps of current from any one individual discrete output point. (Contact factory for higher current capabilities) Auxiliary Power Connector Volts Tolerance Current Power Pin +24VDC (Valves & Outputs) Solenoid Valve Coil 202 (Each) 24VDC +0%/-5% 0.05 A 2.5 Watts Solenoid Valve Coil 2005 (Each) 24VDC +0%/-5% 0.042A.0 Watts 24VDC A max. * 2 Watts max. * Pin 4 +24VDC (Node & Inputs) Node 24VDC +/- 0% A 2.3 Watts Discrete I/O Module (Each) 24VDC A 0.4 Watts Discrete I/O Status LEDs (Each) 24VDC A 0.36 Watts! ATTENTION * Power consumption for each Discrete I/O point is dependent on the specific current draw of input sensor devices and output loads. Please consult the factory for output current requirements greater than 0.5 amps. Recommended External Fuses: External fuses should be chosen based upon the physical manifold configuration. Please refer to page 28 for the fuse sizing chart. LT2005/202CNTECH- 0/03 Page 25

27 Discrete I/O Power Jumper I/O Power from pin # I/O Power from pin #4 of Aux. Power Connector of Aux. Power Connector Please refer to the table below for jumper setting and description. Jumper Jumpered Setting Pins Description Output Module Input Module Jumper Pos SP Jumper Pos 2 UP Jumper Pos 2 UP Jumper Pos SP "S" & "P" "U" & "P" "U" & "P" "S" & "P" Factory Default - Output power is supplied by Pin # of Aux. Power Connector. This allows discrete outputs to be disabled without disabling power to communication node. Output power is supplied by Pin # 4 of Aux Power Connector. This allows discrete outputs to be supplied by the same connection that powers the communication node. Outputs will not be disabled separately from the communication node. Factory Default - Input power is supplied by Pin # 4 of Aux. Power Connector. This allows Input power to be supplied by the same connection which powers the communication node. Input power is supplied by Pin # of Aux Power connector. This allows Input power to be supplied by the same connection that powers the valve coils and discrete outputs. Wide I/O Modules (Modules with eight 2mm connectors) contain two jumpers; one for each group of four connectors. LT2005/202CNTECH- 0/03 Page 26

28 Discrete Sub-D Output Power Jumper Local 2mm Aux. Power Connector (See Pg. 23 for Pin-Out) Fuse (4.0A) Output Power from pin # of Mini Aux. Power Connector Output Power from pin #4 of Mini Aux. Power Connector Output Power from pin # of local 2mm Aux. Power Connector Please refer to the table below for jumper setting and description. Jumper Jumpered Setting Pins Description Jumper Pos SP "S" & "P" Output power is supplied by Pin # of Aux. Power Connector. This allows all valves and discrete outputs to be disabled without disabling power to communication node. Output Module Jumper Pos 2 UP "U" & "P" Output power is supplied by Pin # 4 of Aux Power Connector. This allows all valves and discrete outputs to be supplied by the same connection that powers the communication node. Outputs will not be disabled separately from the communication node. Jumper Pos 3 XP X & P Factory Default - Output power is supplied by pin # of local 2mm Aux Power Connector. Outputs can be enabled/disabled via Local 2mm Aux Power Connector. LT2005/202CNTECH- 0/03 Page 27

29 Power Consumption and External Fuse Sizing Guide Chart Power Consumption - Aux. Power Connector Pin # (Valves and Outputs) Description Current Number of Solenoid Valve Coils Energized Simultaneously X 0.05 A (202 Series) = Amps X A (2005 Series) = Amps + Total load current drawn by simultaneously energized s = Amps with s Power Jumper in "SP" Position (Factory Default). Total load current drawn by Sensor Devices from s source = + Amps with Power Jumper in "SP" Position. Total: Amps Surge Compensation: X.25 Suggested External Pin # Fuse Value: Amps Power Consumption - Aux. Power Connector Pin #4 (Node and Inputs) Description Current Communication Node Power Consumption = Amps + Total load current drawn by simultaneously energized s = Amps with s Power Jumper in "UP" Position. + Total load current drawn by Sensor Devices from s source = Amps with s Power Jumper in "UP" Position (Factory Default). + Number of I/O modules installed X A = Number of Discrete I/O Status LEDs simultaneously on X 0.05 A = Amps + Amps Total: Amps Surge Compensation: X.25 Suggested External Pin #4 Fuse Value: Amps The standard power jumper configuration for all Output Modules is SP. The standard power jumper configuration for all Input Modules is UP. At any given moment in time, the combined current draw through pin # (Valves & Outputs) and pin #4 (Node & Inputs) cannot exceed 8 amperes. Therefore, the combined value of the two fuses on pin # and pin #4 should not exceed 0 amperes (8 ampere max by.25 surge compensation). LT2005/202CNTECH- 0/03 Page 28

30 I/O Module(s) Wiring Diagrams Definitions Sinking Description NPN Switching Negative Positive Common LOAD Sourcing Description PNP Switching Positive Negative Common LOAD Sinking (NPN) Input Connection Electronic Sensor Type Mechanical Sensor Type Input/Signal INPUT MODULE INPUT MODULE 4 (NPN) LOAD FEMALE PIN =+24VDC PIN 3=COMMON OVDC PIN 4=INPUT (SINKING) FEMALE PIN =+24VDC PIN 3=COMMON OVDC PIN 4=INPUT (SINKING) Sourcing (PNP) Input Connection Electronic Sensor Type Mechanical Sensor Type Input/Signal INPUT MODULE INPUT MODULE 4 (PNP) LOAD FEMALE PIN =+24VDC PIN 3=COMMON OVDC PIN 4=INPUT (SOURCING) FEMALE PIN =+24VDC PIN 3=COMMON OVDC PIN 4=INPUT (SOURCING) LT2005/202CNTECH- 0/03 Page 29

31 Sinking (NPN) Output Connection OUTPUT MODULE 3 4 FEMALE OVDC LOAD PIN =+24VDC (COMM) PIN 3=NOT USED PIN 4=OUTPUT (SINKING).5A MAX. +24VDC Sourcing (PNP) Output Connection OUTPUT MODULE 3 4 OVDC LOAD FEMALE +24VDC PIN =NOT USED PIN 3=COMMON OVDC PIN 4=OUTPUT (SOURCING).5A MAX. LT2005/202CNTECH- 0/03 Page 30

32 ControlNet Configuration and Mapping Configuration with RSLOGIX 5000 When setting up your node, specific values must be entered for the assembly instance with regards to Inputs, Outputs and Configuration (these values will remain constant for all Numatics G2-2 ControlNet nodes). The minimum Size values are determined from the actual physical configuration of the manifold. Please see the diagram below for an example taken from Allen Bradley s RSLogix 5000 programming software. Connection Parameters Assembly Instance values: Sizes: Description Decimal Hexadecimal Input Output Configuration Description Input Output Configuration Size (6 bits= word) Total Input Size value (in words) from manifold configuration (including status Input bits) + 2 Words of ControlNet (overhead). This is a minimum value; larger values may be specified for future expansion purposes. Total Output Size value (in words) from manifold configuration. This is a minimum value; larger values may be specified for future expansion purposes. 0 (8 bits) Comm Format: Description Comm. Format Data Data INT LT2005/202CNTECH- 0/03 Page 3

33 EDS File I/O Setup 2005/202 Series ControlNet Technical Manual The EDS file contains configuration information required to establish communication to a node on a ControlNet network. The EDS file is available on the Numatics, Inc., website at Outputs Inputs Outputs are defined as any valve solenoid coil and/or any output point from a discrete Output module. The Output connection size depends upon the physical configuration of the manifold. Please reference the following pages for a detailed explanation for calculating the Output connection size. Inputs are defined as discrete (points from discrete Input modules) and internal (Status Input bits produced by Output drivers). Thus, the Input connection size will include discrete Input points, internal Inputs (Status Input bits), and 4 bytes of. Please reference the following pages for a detailed explanation for calculating the Input connection size. If you want to mask off the run/idle header for clarity, create a user defined type with 2 members HEADER, type DINT; and DATA type INT <input assembly size 2>]. Copy the data from the actual input tag to a tag of this structure, and then you can reference the structure s DATA member using the element numbers LT2005/202CNTECH- 0/03 Page 32

34 I/O Sizes I/O Size - Manifold The overall size of the Input/Output data for the manifold consists of the valve side size plus the Discrete I/O side size. In the G2-2 Series ControlNet node, the Input/Output size can vary from 8 to 32 bytes (4 to 6 words). Due to the many physical configuration possibilities of the G2-2 series, the worksheet on page 34 will allow accurate sizing of the Input/Output byte requirements. I/O Size - Valve Side The Connection size for the valve side of the manifold consists of an output bit for each valve solenoid coil driver and an input bit for the corresponding Status Input bit. The value for the valve side connection size is 4 bytes (2 words) of inputs and outputs. I/O Size - Discrete I/O Side The connection size for the Discrete I/O side is automatically configured based on the I/O modules installed. The output connection size will consist of an output bit for each output point. The input connection size will consist of an input bit for each input point plus Status Input bits for corresponding outputs. Sinking (NPN) outputs will return one Status bit for each output bit. Sourcing (PNP) outputs will return one Status bit for every four output bits. Sinking (NPN) output modules return one Status bit for each output bit. Sourcing (PNP) output modules return one Status bit for every four output bits. LT2005/202CNTECH- 0/03 Page 33

35 Manifold I/O Sizing Worksheet : Choose up to six modules that you want to include on the Discrete I/O side of the manifold and place the sum of the corresponding Input bytes and Output bytes in the boxes labeled, Discrete I/O Byte Requirements at the bottom of the page. 2 : Total the Input byte and Output byte values from the boxes labeled Discrete I/O Byte Requirements, Run /Idle (Required) and Valve Byte Requirements. This is the total Input / Output byte values required for the configured manifold Narrow Module (4 Connector - 4/8 Points) Module # I/O Board # Description Input Bytes Output Bytes Inputs (Sinking-NPN) Inputs (Sourcing-PNP) Inputs (Sinking-NPN) Inputs (Sourcing-PNP) Outputs (Sinking-NPN) Outputs (Sourcing-PNP) Outputs (Sinking-NPN) Outputs (Sourcing-PNP) Wide Module (8 Connector - 8/6 Points) Module # I/O Board # Description Input Bytes Output Bytes Inputs (Sinking-NPN) Inputs (Sourcing-PNP) Inputs (Sinking-NPN) Inputs (Sourcing-PNP) Outputs (Sinking-NPN) Outputs (Sourcing-PNP) Outputs (Sinking-NPN) Outputs (Sourcing-PNP) 2 Sub -D I/O Modules Module # I/O Board # Description Input Bytes Output Bytes Inputs - Dual 5 Pin Sub-D (Sinking-NPN) Inputs - Dual 5 Pin Sub-D (Sourcing-PNP) Inputs - 25 Pin Sub-D (Sinking-NPN) Inputs - 25 Pin Sub-D (Sourcing-PNP) Outputs - 25 Pin Sub-D (Sourcing-PNP) 3 Station # Module # Input Bytes Output Bytes Discrete I/O Byte Requirements Valve Byte Requirements Run Idle (Required) 4 0 Total Input/Output Bytes for Manifold 2 Bytes = Word LT2005/202CNTECH- 0/03 Page 34

36 Mapping Rules The bit mapping for a G2-2 manifold varies with the physical configuration of the manifold. The following is a breakdown of the bit mapping rules associated with the 2005/202 valve manifold. Valve Side ) Solenoid coil outputs are distributed to the valve coils using the Z-Boards. 2) The valve solenoid coil output portion for the total output connection size is 4 bytes (2 words). 3) Each solenoid coil output has an associated Status Input bit (refer to Output Short Circuit Protection section page 44 for functional details). This will affect the overall input connection size. 4) Solenoid coil output addressing begins at the st valve sub base nearest the node and continues in ascending order away from the communication node. 5) Each sub base is allocated or 2 output bits, depending on the Z-Board type installed. Single Z-Board allocates output bit, double Z-Board allocate 2 output bits. 6) Z-Boards can be used in any arrangement (all singles, all doubles, or any combination) as long as output group # and output group #2 bits do not overlap (i.e. combinations of Z-Boards could exist where the physical configuration of the manifold could exceed the output quantity capacity, see page 9). 7) When using valve side sub-d module the st output available will always be bit 6. Single solenoid valves can be used with double Z-Boards TM. However, one of the 2 available outputs will remain unused. LT2005/202CNTECH- 0/03 Page 35

37 Discrete I/O Side Outputs ) The discrete output connection size portion is self-configuring in byte increments once an output module is plugged into back plane and power is applied. 2) Discrete output bits are mapped, in ascending order (away from the communication node), starting at Word No.2 (third word). 3) All discrete output modules have an associated internal Status Input bit, which will affect the total value of the input connection size. Sinking (NPN) output modules allocate one internal Status Input bit per output point. Sourcing (PNP) output modules allocate one internal Status Input bit for every 4 output points. 4) Output bits are always configured in byte increments, thus four point output modules will always use a full byte (8 bits) when mapped. Although not used, the additional four bits in that byte are reserved. Inputs ) The discrete input connection size portion is self-configuring in byte increments once an input module is plugged into back plane and power is applied. 2) Internal Status Input bits, associated with the valve side output drivers, are always mapped before any physical input points. 3) All internal Status Input bits associated with any discrete output module are mapped in byte increments and in ascending order following any existing physical or internal Status Input bits. Refer to pages for sample I/O mapping. LT2005/202CNTECH- 0/03 Page 36

38 I/O Mapping Example # Assumed Settings Single Z-Boards are installed for single solenoid valves and double Z-Boards are installed for double solenoid valves. will always take up the first two words of the Input map. Status Input s are mapped after the two words of and every output device thus the first physical Input will begin at NODE6:I.DATA[4].8 in this example. Valve outputs have Status bit per output point; PNP discrete Output modules have Status bit for every 4 Output points Sample address scheme: NODE6:X.DATA[Y].Z I/O Station #3 I/O Station #2 I/O Station # (4I) NODE6:I.DATA[5].0-3 Allocated (4I): NODE6:I.DATA[5].4-7 (8I) NODE6:I.DATA[4].8-5 (6O) NODE6:I.DATA[2].0-5 Node Address or Module Tag X = (O) Output or (I) Input Y = Word No. Z = No. 25 Pin Valve Side Sub-D Output (6O) NODE6:O.DATA[].0-5 NODE6:O.DATA[0].0-5 Pos No. 2 3 Module Type 6O Sourcing (PNP) 8I Sourcing (PNP) 4I Sinking (NPN) Part No. Valve Side Solenoid Outputs Total I/O Bytes from manifold configuration. Total I/O Words (6 bits) from manifold configuration. Input Size Value Bytes Output Size Value Bytes ( Word) (2 Words) (2 Words) 4 (2 Words) Valve Station # Valve Station #2 Valve Station #3 Valve Station #4 Valve Station #5 Valve Station #6 Valve Station #7 LT2005/202CNTECH- 0/03 Page 37

39 I/O Mapping Tables Example # WORD BYTE Output Table No. 8 (Pos. No.) No. 6 (Pos. No.) No. 7 (Pos. No.) No. 5 (Pos. No.) No. 6 (Pos. No. ) No. 4 (Pos. No.) No. 5 (Pos. No.) No. 3 (Pos. No.) No. 4 (Pos. No.) No. 2 (Pos. No.) No. 3 (Pos. No.) No. (Pos. No.) No.2 (Pos. No.) No. 0 (Pos. No.) No. (Pos. No. ) No. 9 (Pos. No. ) WORD 0 BYTE Input Table Coil No. 8 Coil No. 6 Coil No. 7 Coil No. 5 Coil No. 6 Coil No. 4 Coil No. 5 Coil No. 3 Coil No. 4 Coil No. 2 Coil No. 3 Coil No. Coil No. 2 Coil No. 0 Coil No. Coil No Coil No. 24 Coil No. 32 Coil No. 23 Coil No. 3 Coil No. 22 Coil No. 30 Coil No. 2 Coil No. 29 Coil No. 20 Coil No. 28 Coil No. 9 Coil No. 27 Coil No. 8 Coil No. 26 Coil No. 7 Coil No No. 8 No. 7 No. 6 No. 5 (Pos. No.2) Status for s No.3-6 (Pos. No. ) No. 4 No. 2 Status for s No. 9-2 (Pos. No. ) No. 3 No. Status for s No. 5-8 (Pos. No. ) No. 2 No. 0 Status for s No. -4 (Pos. No. ) No. No. 9 The Status Input bits report the health of a corresponding output bit. To review the status bit action during a fault condition see page 43. LT2005/202CNTECH- 0/03 Page 38

40 I/O Mapping Example #2 Assumed Settings Double Z-Boards are installed for all valves. will always take up the first two words of the Input map. Status Input s are mapped after the two words of and every output device thus the first physical Input will begin at NODE6:I.DATA[5].0 in this example. Valve outputs have Status bit per output point; PNP discrete Output modules have Status bit for every 4 Output points Sample address scheme: NODE6:X.DATA[Y].Z I/O Station #4 I/O Station #3 I/O Station #2 I/O Station # (4I) NODE6:O.DATA[6].0-3 Allocated (4I) NODE6:O.DATA[6].4-7 (6I) NODE6:O.DATA[5].0-5 (22O) NODE6:O.DATA[2].8-5 NODE6:O.DATA[3].0-3 Allocated (2 O): NODE6:O.DATA[3].4-5 (8O) NODE6:O.DATA[2].0-7 Node Address or Module Tag X = (O) Output or (I) Input Y = Word No. Z = No. Pos No Module Type 8O Sourcing (PNP) 22O Sourcing (PNP) 6I Sinking (NPN) 4I Sinking (NPN) Part No. Valve Side Solenoid Outputs Total I/O Bytes from manifold configuration. Total I/O Words (6 bits) from manifold configuration. Input Size Value Bytes Output Size Value Bytes (2 Words) ( Word) (2 Words) (2 Words) 0 4 (2 Words) NODE6:O.DATA[0].0-5 NODE6:O.DATA[].0-5 Valve Station # Valve Station #2 Valve Station #3 Valve Station #4 Valve Station #5 Valve Station #6 Valve Station #7 Valve Station #8 Valve Station #9 LT2005/202CNTECH- 0/03 Page 39

41 I/O Mapping Tables Example #2 WORD BYTE Output Table No. 8 (Pos. No.) No. 6 (Pos. No.2) No. 24 (Pos. No.2) No. 7 (Pos. No.) No. 5 (Pos. No.2) No. 23 (Pos. No.2) No. 6 (Pos. No. ) No. 4 (Pos. No.2) No. 22 No. 30 (Pos. No.2) 2 29 No. 5 (Pos. No.) No. 3 (Pos. No.2) No. 2 (Pos. No.2) No. 29 (Pos. No.2) No. 4 (Pos. No.) No. 2 (Pos. No.2) No. 20 (Pos. No.2) No. 28 (Pos. No.2) No. 3 Pos. No.) No. (Pos. No.2) No. 9 (Pos. No.2) No. 27 (Pos. No.2) 26 No.2 (Pos. No.) No. 0 (Pos. No.2) No.8 (Pos. No.2) No. 26 (Pos. No.2) 25 No. (Pos. No. ) No. 9 No. 7 No. 25 WORD 0 BYTE Input Table Coil No. 8 Coil No. 6 Coil No. 7 Coil No. 5 Coil No. 6 Coil No. 4 Coil No. 5 Coil No. 3 Coil No. 4 Coil No. 2 Coil No. 3 Coil No. Coil No. 2 Coil No. 0 Coil No. Coil No Coil No. 24 Coil No. 32 Coil No. 23 Coil No. 3 Coil No. 22 Coil No. 30 Coil No. 2 Coil No. 29 Coil No. 20 Coil No. 28 Coil No. 9 Coil No. 27 Coil No. 8 Coil No. 26 Coil No. 7 Coil No No. 8 No. 6 No. 7 No. 5 Status for s No No. 6 No. 4 Status for s No No. 5 No. 3 Status for s No.2-24 No. 4 No. 2 No. 20 (Pos. No. 4) Status for s No No. 3 No. No. 9 (Pos. No. 4) Status for s No. 5-8 (Pos. No. ) Status for s No. 3-6 No. 2 No. 0 No. 8 (Pos. No. 4) Status for s No. -4 (Pos. No. ) Status for s No. 9-2 No. No. 9 No. 7 (Pos. No. 4) 3 LT2005/202CNTECH- 0/03 Page 40

42 I/O Mapping Example #3 Assumed Settings will always take up the first two words of the Input map. Status Input s are mapped after the two words of and every output device thus the first physical Input will begin at NODE6:I.DATA[5].0 in this example. Valve outputs have Status bit per output point; PNP discrete Output modules have Status bit for every 4 Output points Sample address scheme: NODE6:X.DATA[Y].Z Node Address or Module Tag X = (O) Output or (I) Input Y = Word No. Z = No. I/O Station #4 I/O Station #3 I/O Station #2 I/O Station # (4I) NODE6:I.DATA[5].8- Allocated (4I) NODE6:I.DATA[5].2-5 (8I) NODE6:I.DATA[5].0-7 (6O) NODE6:O.DATA[2].8-5 NODE6:O.DATA[3].0-7 (8O) NODE6:O.DATA[2].0-7 Pos No Module Type 8O Sourcing (PNP) 6O Sourcing (PNP) 8I Sinking (NPN) 4I Sinking (NPN) Part No. Valve Side Solenoid Outputs Total I/O Bytes from manifold configuration. Total I/O Words (6 bits) from manifold configuration. Input Size Value Bytes Output Size Value Bytes ( Word) (2 Words) (2 Words) 4 (2 Words) NODE6:O.DATA[0].0-5 NODE6:O.DATA[].0-5 LT2005/202CNTECH- 0/03 Page 4

43 I/O Mapping Tables WORD Example #3 BYTE /202 Series ControlNet Technical Manual 6 3 Output Table No. 8 (Pos. No. ) No. 6 No. 24 (Pos. No.2) No. 7 (Pos. No. ) No. 5 No. 23 (Pos. No.2) No. 6 (Pos. No. ) No. 4 No No. 5 (Pos. No. ) No. 3 No. 2 (Pos. No.2) No. 4 (Pos. No. ) No. 2 No. 20 (Pos. No.2) No. 3 (Pos. No. ) No. No. 9 (Pos. No.2) 26 No. 2 (Pos. No. ) No. 0 No. 8 (Pos. No.2) 25 No. (Pos. No. ) No. 9 No. 7 WORD 0 BYTE Input Table Coil No. 8 Coil No. 6 Coil No. 7 Coil No. 5 Coil No. 6 Coil No. 4 Coil No. 5 Coil No. 3 Coil No. 4 Coil No. 2 Coil No. 3 Coil No. Coil No. 2 Coil No. 0 Coil No. Coil No Coil No. 24 Coil No. 32 Coil No. 23 Coil No. 3 Coil No. 22 Coil No. 30 Coil No. 2 Coil No. 29 Coil No. 20 Coil No. 28 Coil No. 9 Coil No. 27 Coil No. 8 Coil No. 26 Coil No. 7 Coil No No. 8 No. 7 No. 6 No. 5 Status for s No.2-24 No. 4 No. 20 (Pos. No. 4) Status for s No No. 3 No. 9 (Pos. No. 4) Status for s No. 5-8 (Pos. No. ) Status for s No. 3-6 No. 2 No. 8 (Pos. No. 4) Status for s No. -4 (Pos. No. ) Status for s No. 9-2 No. No. 7 (Pos. No. 4) The Status Input bits report the health of a corresponding output bit. To review the status bit action during a fault condition see page 43. LT2005/202CNTECH- 0/03 Page 42

44 Diagnostics Comm. Module / Power Module LED Functions Upon power up, the LEDs indicate the status of the unit. The Power Module of the G2-2 ControlNet node has four LEDs; two for internal fuse integrity and two for Aux. Power status. The Communication module also has four status LEDs Power Module LED Name Color Status Description Fuse Communication Module LED Name Color Status Description Channel & Channel or Module Status (MS) Module Owned (OWNED) Red +24V VLV / OUT Green Fuse 2 Red +24V NODE / IN Green ON OFF ON OFF ON OFF ON OFF Internal fuse F is open; No power is internally provided to valves or outputs. Communication NOT affected. Internal fuse F is OK (valid only when power is applied to +24V VLV / OUT pin on Aux. Power connector. DC Power applied to +24V VLV / OUT pin on Aux. Power Connector. No DC Power present at +24V VLV / OUT pin on Aux. Power connector. Internal fuse F2 is open; No power is internally provided to node electronics or inputs. Communication Node will not function. Internal fuse F2 is OK (valid only when power is applied to +24V NODE / IN pin on Aux. Power connector. DC Power applied to+24v NODE / IN pin on Aux. Power connector. No DC Power present at +24V NODE / IN pin on Aux. Power connector. -- OFF Module is not initialized Green/Red ALTERNATING Self test of bus controller Red ON Faulted unit, must be restarted FLASHING Incorrect node configuration; i.e. duplicate MAC ID -- OFF Channel is disabled, depending on the network configuration ON Normal operation of channel Green Temporary errors (node will self correct) or node is not configured to go FLASHING online Red FLASHING Media Fault or no other nodes on the network Green/Red FLASHING Incorrect network configuration Green ON Module is initialized FLASHING Module is waiting for initialization Red ON Major fault, module must be restarted FLASHING Minor fault, MAC ID has been changed after initialization, etc. Green OFF No connection is opened ON A connection is opened to the module LT2005/202CNTECH- 0/03 Page 43

45 Internal Fuses Fuse (F) Fuse (F2) Fuse Function and Description Fuse # Description Size Part Number Type F Fuse for Aux. Power connector Pin # (Valves & Outputs). 0 A max. fast acting Mini ATO F2 Fuse for Aux. Power connector Pin #4 (Node & Inputs). 4A max. fast acting Mini ATO Fuse Status LED - Indicates the internal fuse integrity Status Indication Description Off Internal Fuse is Intact Condition normal. Red Internal Fuse is Blown Electrical Overload / Over Current Condition Output Short Circuit Protection Status Action During Fault Condition Output Status Output Type Fault Condition State Valve Solenoid Coil Driver or No Fault 0 ON Sinking (NPN) s Fault - Short Circuit, Over Temp/Over Current Valve Solenoid Coil Driver or No Fault 0 OFF Sinking (NPN) s Fault - Open Load Sourcing (PNP) No Fault 0 ON s Fault - Short Circuit, Over Temp/Over Current LT2005/202CNTECH- 0/03 Page 44

46 Appendix System Specifications Supply Voltage Current Internal Fuses Recommended External Fuse Spike Suppression s (Sinking (NPN) or Sourcing (PNP)) Valve Solenoid Coil Output Drivers Operating Temperature for Electronic Components Electrical Valves: 24 VDC + 0%, -5% Node and Discrete I/O: 24 VDC +/- 0% Total current on the Aux. Power Connector (Pin - Valves & Outputs and Pin 4 - Node & Inputs ) must not exceed 8 amperes. Pins # and #4 on the Auxiliary Power Connector are each internally fused with a 4 and 0 ampere (maximum) MINI ATO type fuses. External fuses should be chosen depending upon manifold configuration. Please refer to power consumption chart on page 28 for additional fuse sizing information. Output spike suppression is internally provided for both discrete and valve outputs. Maximum 0.5 amperes per output (Sinking (NPN) or Sourcing (PNP)). All outputs are short circuit protected and have internal spike supression. Contact factory for higher current requirements. Maximum 0.5 amperes per output. All output points are short circuit protected and have internal spike supression. 23 to 4 F (-5 to 46 C) LT2005/202CNTECH- 0/03 Page 45

47 Factory Defaults Settings Description Default Node Address 00 Baud Rate 5 M bit/sec. Input Module Power Jumper UP Output Module Power Jumper SP Valve Side - I/O Connection Size 4/4 Bytes (2/2 Words) I/O Side - I/O Connection Size Self-Configuring. See Page 35 I/O Connection Size 4/0 Bytes (2/0 Words) LT2005/202CNTECH- 0/03 Page 46

48 Troubleshooting Symptom Possible Cause Solution Power must be present between pin #2 and pin #3 on the communication connector and between pin #4 and pin #3 on the auxiliary power connector for the node to function properly. All LEDs off Fuse LEDs displays red The wrong valve solenoid coils are being energized. Valve outputs do not energize. All node LEDs normal. Power not properly applied Blown internal fuses Z-Board TM type mismatch. Single Z-Board TM present where double Z-Board TM expected or vice versa. Output power not present or connected in properly on Aux. Power connector. 24VDC must be present between pin #4 and pin #3 of the auxiliary power connector even if Discrete I/O modules are not installed See page 3 for Details Check for external shorts to Input connector from external sensor devices or cable and repair. Replace internal fuse. If problem persists contact factory. Check that correct Z-Board TM types are installed. Check that ribbon cable (output group #2) is connected to appropriate valve station. See page 35 for bit mapping rules Check for 24VDC on pin # of Aux. Power connector of Comm. module. Check for 24VDC on Pin # of 2mm local Aux Power connector of 25 Pin Sub-D Module, if applicable LT2005/202CNTECH- 0/03 Page 47

49 Glossary of Terms The following is a list and description of common terms and symbols used throughout this document: Smallest unit of digital information either a 0 or mapping Byte Change of State Comm. Fault Cyclic Discrete I / O EDS file Chart showing which bit is connected to which physical input or output point 8 bits (/2 word) I/O message type in which either the expiration of the transmission timer or a change in input state triggers data production. One or more of the I/O connections have timed out. I/O message type in which data production is triggered by the expiration of the transmission timer. The Inputs / Outputs that are available via the Discrete I/O side of manifold Electronic Data Sheet. A text file, which contains specific product information, definitions of product capabilities and configurable parameters necessary for operation on a ControlNet network. G2-2 A Numatics product series of electronics which features modular backplane technology that allows various Discrete I/O components and Communication modules to be added, removed or changed in the field Ground This term is used to indicate an earth ground I/O Idle MAC ID Maximum Scheduled Node NEMA NUT Polled RPI RS NetWorx Sinking (NPN) Sourcing (PNP) Status Input bit Word Z-Board TM Any combination of Inputs and Outputs A zero (0) length poll massage (i.e.: scanner in program mode) Media Access Connection Identification (00-99) Node (network drop) address Node with highest MAC ID that can use scheduled time on a link. National Electrical Manufacturers Association Network Update Time. Repetitive time interval in which data can be sent on the link, I/O message type in which the devise consumes I/O data from its master and produces I/O data when the master requests it. Requested Packet Interval. The measure of how frequently the node requires the transmission of data from the target application (scanner). Allen-Bradley s ControlNet configuration software Method of connecting electrical circuits in which the zero (0) volt DC side is switched and the common is positive Method of connecting electrical circuits in which the positive side is switched and the common is zero (0) volts DC. A bit in the input table that reports the health of a corresponding output. Indicates short circuit or open coil (load) diagnostics 2 Bytes (6 bits) Circuit board installed in the valve sub-base which electrically connects the valve solenoid to the electrical /electronics interface. Available in single or double solenoid versions. LT2005/202CNTECH- 0/03 Page 48

2005/2012 Series Profibus DP Technical Manual

2005/2012 Series Profibus DP Technical Manual 2005/2012 Series Profibus DP Technical Manual LT2005/2012PBTECH-1 04/02 www.numatics.com Table of Contents 2005/2012 Series Profibus DP Technical Manual PAGE About Profibus DP... 3 Overview... 3 G2-2 Profibus-DP

More information

2002 Series DeviceNet Technical Manual

2002 Series DeviceNet Technical Manual 2002 Series DeviceNet Technical Manual Table of Contents 2002 Series DeviceNet Technical Manual 2002 Introduction...4 Product Overview...4 About DeviceNet...5 Overview...5 2002 DeviceNet Features...5 Cabling

More information

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths

More information

MPCR Series DeviceNet Technical Manual

MPCR Series DeviceNet Technical Manual MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction...3 Product Overview...3 About DeviceNet...4 Overview...4 MPCR DeviceNet Features...4 Cabling and Drop Line Lengths (as

More information

MPCR Series Profibus-DP Technical Manual

MPCR Series Profibus-DP Technical Manual MPCR Series Profibus-DP Technical Manual TDMPCRPBTECH-1 12/04 www.numatics.com Table of Contents MPCR Series Introduction...3 Product Overview...3 About Profibus...4 Overview...4 MPCR Profibus Features...4

More information

G3 Series PROFIBUS DP Technical Manual

G3 Series PROFIBUS DP Technical Manual G3 Series PROFIBUS DP Technical Manual Table of Contents G3 Series PROFIBUS DP Technical Manual PAGE About PROFIBUS-DP...3 Overview...3 G3 PROFIBUS-DP Features...3 Cabling and Drop Line Lengths (as defined

More information

Quick Start Manual G2-2 Series with Ethernet Interface

Quick Start Manual G2-2 Series with Ethernet Interface Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with integrated G2-2 series EtherNet/IP communication protocol. 1) Initial Unpacking and Inspection

More information

G3 Series DeviceNet TM Technical Manual

G3 Series DeviceNet TM Technical Manual G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. I P MAC AD D RE S S Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics G2-2 Series EtherNet/IP communication node. 1)

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Getting Started This is a brief document designed to quickly get you started setting up your 200/2012 Series valve manifold with integrated Numatics G2-2 Profibus-DP communication protocol. Please note

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your 2004 Series valve manifold with integrated Numatics G2- A-B 77 Remote I/O communication protocol.

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. Getting Started This is a brief document designed to quickly get you started setting up your 2002 Series valve manifold with integrated Numatics G2-1\2 Profibus-DP communication protocol. Please note that

More information

G3 Series EtherNet/IP TM Technical Manual

G3 Series EtherNet/IP TM Technical Manual G3 Series EtherNet/IP TM Technical Manual Conditions for use of this product G3 Series EtherNet/IP Technical Manual () Numatics G3 Manifold ("the PRODUCT") shall be used in conditions; i) Where any problem,

More information

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling MATERIAL HANDLING MANIFOLDS WITH DeviceNet INTERFACE 01348(N or G) MH** -- Material Handling 01351(N or G) MH** -- Material Handling Note: N = NPT ports G = BSPP ports SOL 14 SOL 12 Station #3 SOL 14 SOL

More information

01325T -- Robot Welder

01325T -- Robot Welder WELDING MANIFOLDS WITH DeviceNet INTERFACE 01325T -- Robot Welder 01326T -- Pedestal Welder Station #2 (WELD) SOL 14 Station #1 (BACKUP) SOL 14 SOL 12 Prop. Reg. Water Saver Inputs Power (Aux.) DeviceNet

More information

Table of Contents. Fieldbus Electronics and I/O G2-1 Electronics G2-2 Electronics Individual Base Node...

Table of Contents. Fieldbus Electronics and I/O G2-1 Electronics G2-2 Electronics Individual Base Node... Table of Contents Fieldbus Electronics and I/O............................... - G- Electronics..................................................................... - Features and Benefits..................................................................................

More information

Table of Contents. Individual Base Node Direct to PLC Cables and Accessories

Table of Contents. Individual Base Node Direct to PLC Cables and Accessories Table of Contents Fieldbus Electronics and I/O...- G- Electronics....- Features and Benefits... Communication Protocols...-8 How to Order.... AKC Communication Module... 0 LH Mounting Cover Kit... 0 Fieldbus

More information

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008 Elco BradControl DEVICENET ACTIVE 60mm Input/ Interface Block May, 2008 1. INTRODUCTION The following product numbers are covered by the information presented in this booklet: PART NUMBER BCDN-1600P-M12

More information

Type-5500 with Profibus-DP Interface Quick Start Manual

Type-5500 with Profibus-DP Interface Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your Type-5500 manifold with integrated Profibus-DP communication protocol. Please note that this document is not

More information

2005 / 2012 / 2035 Series

2005 / 2012 / 2035 Series Generail Information on Fieldbus Systems FEATURES Solenoid air operated valve manifolds for date exchange via fieldbus. Internal wiring by Z-Board plug-in system. Plug-together flexibility due to different

More information

Ordering Information Ordering Data I/O Module Part numbers 12mm (micro) connectors 8 I/O per module Singular I/O module Left hand I/

Ordering Information Ordering Data I/O Module Part numbers 12mm (micro) connectors 8 I/O per module Singular I/O module Left hand I/ Direct to PLC modules Numatics new line of with integrated I/O modules, allows a single multi-conductor cable connection to the manifold. This cable can handle the power, the valves and the sensor inputs

More information

MAC VALVES, INC. A ENGINEERING RELEASE TRJ B EDS UPDATE / NAME CHANGE BI 284 TJR/KD. User s Manual for MAC Valves DeviceNet

MAC VALVES, INC. A ENGINEERING RELEASE TRJ B EDS UPDATE / NAME CHANGE BI 284 TJR/KD. User s Manual for MAC Valves DeviceNet MAC VALVES, INC. DOCUMENT NUMBER TITLE: User s Manual for MAC Valves DeviceNet PAGE 1 OF 24 UI-20 SM16 Manifold REVISION LEVEL DATE RELEASED CHANGE ECN NUMBER P.E. APPROVAL P.D. APPROVAL A 7-21-99 ENGINEERING

More information

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14 TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES Pg. 1 di 14 INDEX Legend of Symbols... 3 Conformity Declaration... 3 System Descripiton... 4 Module Specifications... 4 Installation

More information

Allen-Bradley. User Manual. ControlNet Adapter Module. (Cat. No ACN and -ACNR Series B)

Allen-Bradley. User Manual. ControlNet Adapter Module. (Cat. No ACN and -ACNR Series B) Allen-Bradley ControlNet Adapter Module (Cat. No. 1771-ACN and -ACNR Series B) User Manual Important User Information Because of the variety of uses for the products described in this publication, those

More information

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE 13050201 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN502 PRODUCT OVERVIEW 1 DN502 INSTALLATION 1 POWER

More information

Product Description. Altus S. A. 1

Product Description. Altus S. A. 1 Product Description The PO5064 and PO5065 modules are Ponto Series modular PROFIBUS-DPV1 slave heads for PROFIBUS fieldbus that can use all I/O modules from this Series. They can be connected to HMIs (keyboards

More information

Powered Roller Controller for DeviceNet

Powered Roller Controller for DeviceNet PRC-620-090 TECHNICAL DATA Description The Holjeron Powered Roller Controller for use with DeviceNet has the features needed to handle up to four zones in a material handling system. A Brushless DC Powered

More information

DC3IOB Revision User Guide Updated 3/29/10. Overview

DC3IOB Revision User Guide Updated 3/29/10. Overview Revision 080910 User Guide Updated 3/29/10 Overview The is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The integrated PLC

More information

Installation Instructions

Installation Instructions Installation Instructions 1771-SDN/B DeviceNet Scanner Module Installation Instructions 1 (Catalog Number 1771-SDN/B) Use this document as a guide to installing your 1771-SDN/B Scanner Module. Before you

More information

A 3/15/19 ENGINEERING RELEASE GEM

A 3/15/19 ENGINEERING RELEASE GEM MAC VALVES, INC. DOCUMENT NUMBER PAGE 1 OF 34 UI-182 TITLE: Control Manual for MAC Modbus TCP MI/O-67 Manifold REVISION LEVEL DATE RELEASED CHANGE ECN NUMBER P.E. APPROVAL P.D. APPROVAL A 3/15/19 ENGINEERING

More information

BICN ControlNet Interface

BICN ControlNet Interface BICN ControlNet Interface BALOGH 7699 Kensington Court Brighton, MI 48116-8561 (248) 486-7343 Notes are used to call attention to information that is significant to the understanding and operation of equipment.

More information

Allen-Bradley Automation

Allen-Bradley Automation Product Data 1791D CompactBlock I/O for DeviceNet 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. CompactBlock I/O modules are ideal

More information

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE 13050301 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN503 PRODUCT OVERVIEW 1 DN503 INSTALLATION 1 POWER

More information

mbc082 Bus Converter

mbc082 Bus Converter BUS CONVERTER RS485 TO 1-WIRE BUS mbc082 mbc082 Bus Converter Document. 10910, Revision - February 2007 2007 CMC Industrial Electronics Ltd. This page intentionally left blank. mbc082 Bus Converter Technical

More information

Diagnostics (Logical) Diagnostics (Physical)

Diagnostics (Logical) Diagnostics (Physical) Enclosure Mounted Input/Output Stations In-Cabinet I/O IP 20 Protection Ideal for Retrofits Automatic Baud Rate Sensing FDN20-4S-4XSG FDN20-4S-4XSG-E* FDN20-4S-4XSG-DIN* * Not UL Electrical Operating Current:

More information

VersaMax IP Input Module

VersaMax IP Input Module Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm

More information

PLCADD1616 User Guide 3/29/10. Overview

PLCADD1616 User Guide 3/29/10. Overview PLCADD1616 User Guide 3/29/10 Overview The PLCADD1616 is a PLC expansion board used to add digital inputs and outputs to a compatible host PLC. The PLCADD1616 has 16 relay outputs and 16 optically isolated

More information

DeviceNet Expansion Board

DeviceNet Expansion Board DeviceNet Expansion Board Catalog No. EXBD05 Installation and Operating Manual 10/02 Table of Contents Section 1 General Information................................................... 1 1 Introduction.......................................................

More information

DC3IOB Revision User Guide Updated 7/12/12. Overview

DC3IOB Revision User Guide Updated 7/12/12. Overview DC3IOB Revision 080910 User Guide Updated 7/12/12 Overview The DC3IOB is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The

More information

Mod. TCxD. DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 24

Mod. TCxD. DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 24 Mod. TCxD DeviceNet FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES & I/O SIGNAL Pg. 1 di 24 INDEX Important note...3 Abbreviation...3 Legend of symbols...4 Terms Definition...4 System descripiton...5 Module

More information

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit PRODUCT DATA SLC TM 100 Programmable Controller Processor Unit -Catalog Nos. 1745-LPI01, -LP102, -LP103, -LP104 The SLC 100 programmab/e Contro"er The SLC 100 Programmable Controller is easy to program,

More information

6053/6055 ControlNet Communications Interface

6053/6055 ControlNet Communications Interface EUROTHERM DRIVES 6053/6055 ControlNet Communications Interface Technical Manual HA468029U001 Issue 2 Compatible with Version 1.x Firmware Copyright Eurotherm Drives Limited 2003 All rights strictly reserved.

More information

Mod. TCxP PROFIBUS FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 23

Mod. TCxP PROFIBUS FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES I/O SIGNAL. Pg. 1 di 23 Mod. TCxP PROFIBUS FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES & I/O SIGNAL Pg. 1 di 23 INDEX Important note...3 Terms Definition...3 Legend of symbols...4 System descripiton...4 Module specifications...5

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those

More information

Valve island VM10 with EtherNet/IP Interface 8, 10, 12 or 16 stations. Operation & Service Manual

Valve island VM10 with EtherNet/IP Interface 8, 10, 12 or 16 stations. Operation & Service Manual Valve island VM10 with EtherNet/IP Interface 8, 10, 12 or 16 stations Operation & Service Manual Change history: The Change history reflects all changes of the, which were done after the initial release.

More information

TURCK Industrial I/O DeviceNet Products

TURCK Industrial I/O DeviceNet Products TURCK Industrial I/O DeviceNet Products F1 TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com Industrial Automation DeviceNet System

More information

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157 PRODUCT DA TA SLC 150 110 Expansion Unit Catalog Nos. 1745-151, - 152, - 153, - 154, - 156, -E157 7 : The EXpdnSiQn Unit The SLC 150 expansion unit can be used with either the SLC 150 processor unit or

More information

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison DNETEXT-C CAN Bus Extender, Version 3 User s Manual Brad Harrison Although every effort has been made to insure the accuracy of this document, all information is subject to change without notice. Woodhead

More information

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date: Class: Date: MECH1500Quiz1ReviewVersion2 True/False Indicate whether the statement is true or false. 1. The number and type of I/Os cannot be changed in a fixed PLC. 2. In a PLC system, there is a physical

More information

IC693PWR331 High Capacity Power Supply, 24 VDC Input

IC693PWR331 High Capacity Power Supply, 24 VDC Input IC693PWR331 High Capacity Power Supply, 24 VDC Input The Series 90-30 DC input High Capacity power supply (IC693PWR33) is a 30 watt wide range supply designed for 24 VDC nominal inputs. For applications

More information

AMCI NX3A1E Specifications Rev 0.0 Resolver PLS Ethernet Module

AMCI NX3A1E Specifications Rev 0.0 Resolver PLS Ethernet Module Module Overview The AMCI NX3A1E module is a single resolver input programmable limit switch module that is programmed by and communicates on Ethernet. The functionality of the NX3A1E is similar to the

More information

THE FULL RANGE FOR PROCESS AUTOMATION. This document provided by Barr-Thorp Electric Co., Inc

THE FULL RANGE FOR PROCESS AUTOMATION.   This document provided by Barr-Thorp Electric Co., Inc THE FULL RANGE FOR PROCESS AUTOMATION www.turck.com TURCK Process Automation Networks DeviceNet Selection Guide AIM Page FDN20 Page OEM Page Discrete Input J11-J13, J29, J37 Discrete Input & Ouput J59

More information

Specifications N Termination Voltage Range Current Consumption, Max. Type Number Termination. Voltage Range. Sinking Sensor Current

Specifications N Termination Voltage Range Current Consumption, Max. Type Number Termination. Voltage Range. Sinking Sensor Current Description The N24 Controller is a specialized Motorized Roller Driver Module for NorthAmCon Mech-Rollers. It includes the following features: 6 PNP Auxiliary I/O points to provide enhanced diagnostic

More information

TURCK Modular Industrial I/O PROFIBUS -DP Products

TURCK Modular Industrial I/O PROFIBUS -DP Products TURCK Modular Industrial I/O PROFIBUS -DP Products Piconet Gateways Rugged, Fully Potted Stations IP 67 Protection Small Footprint Automatic Baud Rate Sensing SDPL-0404D-0003 SDPL-0404D-0004 SDPL-0404D-1003

More information

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed.

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed. 2 The integrates position sensing, communication electronics, power outputs, auxiliary inputs and wire termination into a fully sealed compact package. The module also integrates a terminal strip directly

More information

DeviceNet Drive Profile CFW-09

DeviceNet Drive Profile CFW-09 Motors Automation Energy Transmission & Distribution Coatings DeviceNet Drive Profile CFW09 Communication Manual DeviceNet Drive Profile Communication Manual Serie: CFW09 Language: English Software Version:

More information

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output MICRO-SCREEN DIN Controllers with DeviceNet Trip Output Supplement to MICRO-SCREEN Instruction Manual P/N 48753 Features Offers all of the features of standard MICRO-SCREEN DIN controllers (see Instruction

More information

REMOTE I/O [INPUT/OUTPUT] CONTROLLER LAN NODE PCB (RIO) Part No. 46S For use on MicroTrac DSD Local Area Network

REMOTE I/O [INPUT/OUTPUT] CONTROLLER LAN NODE PCB (RIO) Part No. 46S For use on MicroTrac DSD Local Area Network RD 790-10 REMOTE DEVICE USER REFERENCE SHEET FOR REMOTE I/O [INPUT/OUTPUT] CONTROLLER LAN NODE PCB (RIO) Part No. 46S02790-0010 For use on MicroTrac DSD Local Area Network INTRODUCTION The Remote Input/Output

More information

Diagnostics (Physical)

Diagnostics (Physical) DeviceNet Spanner Rugged, Fully Potted Stations IP 67 Protection Communicate Between s Connect Two DeviceNet Networks FDN-DN1 Electrical Operating Current: 125 ma from segment A, 30 ma from segment B Power

More information

EMERALD SERIES AUTOMATION CONTROLLER JANUARY 2017 EMERALD EMC INDUSTRIAL INDEXING SYSTEMS, Inc. INSTRUCTION BOOK

EMERALD SERIES AUTOMATION CONTROLLER JANUARY 2017 EMERALD EMC INDUSTRIAL INDEXING SYSTEMS, Inc. INSTRUCTION BOOK EMERALD SERIES AUTOMATION CONTROLLER JANUARY 2017 EMERALD EMC-2100 INDUSTRIAL INDEXING SYSTEMS, Inc. Revision 0 Approved By: CME INSTRUCTION BOOK Proprietary information of Industrial Indexing Systems,

More information

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL Revision 2.1 July. 2014 1 Integriti 8 32 Zone LAN Expander Module Kit P/N: 996005PCB&K For Rev. B PCB. INSTALLATION MANUAL Overview The Integriti 8 Zone Expander Module provides an additional 8 Zone inputs,

More information

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between

More information

Table of Contents

Table of Contents Table of Contents Table of Contents Analog Input Module (12-Bit) Assembly cat. no. 1771-IF Series B and Analog Input Expander (12-Bit) cat. no. 1771-E1, -E2, -E3 are plug-in modules that interface analog

More information

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112 SELECTRONIX, INC. WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL Models: SLC2102-SLC2112 SLC2102X-SLC2112X SLC2152-SLC2162 SLC2170-xx Relay

More information

Table of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4

Table of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4 Table of Contents 1 ABOUT THIS GUIDE... 3 1.1 CONTACT INFORMATION... 3 2 ANTENNA INSTALLATION... 4 2.1 GENERAL INFORMATION... 4 2.2 SPECIFIC MOUNTING EXAMPLES... 5 2.3 CONNECTOR MOISTURE PROTECTION...

More information

L5351 DeviceNet Communications Interface

L5351 DeviceNet Communications Interface L5351 DeviceNet Communications Interface Technical Manual HG353798 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

DIN Molded Cable Assemblies

DIN Molded Cable Assemblies DIN 43650 Telephone (973) 586-500 FAX (973) 596-590 DIN 43650 8mm For Solenoid Valve Applications Black PVC Cable & Connector DUAL JUMPED GROUND PINS Molded cable assemblies can be mounted with cable exiting

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements installing the module connecting the wiring using the indicators for

More information

SMARTEYE S-net with DeviceNet Interface SP4000/01 User Manual Version Revision 3

SMARTEYE S-net with DeviceNet Interface SP4000/01 User Manual Version Revision 3 SMARTEYE S-net with DeviceNet Interface SP4000/01 User Manual Version 1.0.5 Revision 3 www.smarteyecorporation.com related documents: SMARTEYE Sender/Receiver Reader User Manual The material in this manual

More information

USER MANUAL 3170-INTB

USER MANUAL 3170-INTB USER MANUAL ProSoft Technology, Inc. Phone: 661-664-7208 9801 Camino Media Fax: 661-664-7233 Suite 105 E-mail: prosoft@prosoft-technology.com Bakersfield, CA 93311 http://www.prosoft-technology.com About

More information

SMARTEYE P-Linc User Manual VERSION L1.5 Revision 4

SMARTEYE P-Linc User Manual VERSION L1.5 Revision 4 SMARTEYE P-Linc User Manual VERSION L1.5 Revision 4 www.smarteyecorporation.com related documents: SMARTEYE Electronics Assembly User Manual SMARTEYE Twin User Manual The material in this manual is for

More information

SmartWire-DT In panel and on machine wiring solutions. Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators

SmartWire-DT In panel and on machine wiring solutions. Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators SmartWire-DT In panel and on machine wiring solutions Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators SmartWire-DT Changing the way panels... Reduce cost throughout

More information

Digital Lighting Systems, Inc. PD405-DMX. Four Channel Dimmer and Switch Packs. DMX512 compatible. PD405-DMX-24DC DMX512 4 x 5 Amps Dimmer Pack

Digital Lighting Systems, Inc. PD405-DMX. Four Channel Dimmer and Switch Packs. DMX512 compatible. PD405-DMX-24DC DMX512 4 x 5 Amps Dimmer Pack Digital Lighting Systems, Inc. PD405DMX Four Channel Dimmer and Switch Packs DMX52 compatible PD405DMX24DC DMX52 4 x 5 Amps Dimmer Pack C UL US LISTED www.digitallighting.com Digital Lighting Systems,

More information

For the configuration of the I/O-modules in a control system an EDS-file is required. The names of the files are as follows:

For the configuration of the I/O-modules in a control system an EDS-file is required. The names of the files are as follows: Quick Reference for I/O-modules 0980 ESL 710 and 0980 ESL 711 This quick reference shall help to put the LioN-M I/O-modules 0980 ESL 710 and 0980 ESL 711 with Ethernet/IP interface into operation. It explains

More information

Mounting the Model 2601

Mounting the Model 2601 Control Technology Corporation Model 2601 Automation Controller Installation Guide Model 2601 Automation Controller This document is current as of the following revision levels: Controller Firmware 2.24

More information

INTELLIS. Modbus Direct Network Monitor

INTELLIS. Modbus Direct Network Monitor INTELLIS Modbus Direct Network Monitor System Installation and Operation Manual Phone: (201) 794-7650 Fax: (201)794-0913 Chapter 1 Modbus Protocol Revision History Revision 1.0 30 April, 2002 Initial Version

More information

EnerSure Installation Guide

EnerSure Installation Guide EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded

More information

M3-61B DeviceNet Slave Module. M3-61B DeviceNet Slave Module CONTROL TECHNOLOGY CORPORATION

M3-61B DeviceNet Slave Module. M3-61B DeviceNet Slave Module CONTROL TECHNOLOGY CORPORATION CONTROL TECHNOLOGY CORPORATION M3-61B DeviceNet Slave Module M3-61B DeviceNet Slave Module Copyright 2008-2010 Control Technology Corporation All Rights Reserved. Blank Control Technology Corporation 2

More information

ZoneLink 4-Zone Controller For use with ZL.S-DK101 and Microroller

ZoneLink 4-Zone Controller For use with ZL.S-DK101 and Microroller ZLC-6320-2 0905 TECHNICAL DATA SHEET Description The enhanced Holjeron ZoneLink 4-Zone Controller for use with DeviceNet has the features needed to control up to four zones in a material handling system,

More information

1395 Node Adapter Board Troubleshooting

1395 Node Adapter Board Troubleshooting 1395 Node Adapter Board Troubleshooting Specifications Electrical: Board power provided by Drive (+5V) Discrete Input 24V DC or 115V AC, jumper selectable Environmental: Ambient Operating Temperature Storage

More information

ControlNet Adapter Module

ControlNet Adapter Module ControlNet Adapter Module (Catalog Numbers 1747-ACN15, 1747-ACNR15) User Manual Important User Information Because of the variety of uses for the products described in this publication, those responsible

More information

DeviceNet System Installation manual rev. 3.0

DeviceNet System Installation manual rev. 3.0 DeviceNet System INSTALLATION MANUAL rev. 3.0 page 1 of 1 0 Technical characteristics DeviceNet System Installation manual rev. 3.0 SUPPLY VOLTAGE: 24 V ± 10 % WORKING TEMPERATURE: 0 50 C PERCENTAGE OF

More information

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00 g MX200 SERIES Modbus Card 50P-1105 GE Zenith Controls 50R-2200B 12/00 Operation and Maintenance Manual Table of Contents Overview...01 Page LED Indicator...02 Installation...03 Installing the Network

More information

TM238LFDC24DT compact base M I/O - 24 V DC supply - CANOpen - internal RAM 1000 kb

TM238LFDC24DT compact base M I/O - 24 V DC supply - CANOpen - internal RAM 1000 kb Product data sheet Characteristics TM238LFDC24DT compact base M238-24 I/O - 24 V DC supply - CANOpen - internal RAM 1000 kb Complementary Discrete input logic Number of common point Sensor power supply

More information

Advantys ETB. DATA SHEET Advantys ETB IP 67 Ethernet Digital I/O Modules. Description. Features

Advantys ETB. DATA SHEET Advantys ETB IP 67 Ethernet Digital I/O Modules. Description. Features Advantys ETB DATA SHEET Advantys ETB IP 67 Ethernet Digital I/O Modules The Advantys ETB family of IP 67 digital I/O modules with direct connection to the Ethernet ( Modbus TCP/IP ) Communication Network.

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-IR Series D) Use this document as a guide when installing the 1771-IR/D input module. The RTD input module is sensitive to electrostatic discharge. ATTENTION:

More information

L5353 Profibus-DP Communications Interface

L5353 Profibus-DP Communications Interface L5353 Profibus-DP Communications Interface Technical Manual HA470380 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

Direct Communication Modules Direct Communication Module (1747-DCM)

Direct Communication Modules Direct Communication Module (1747-DCM) Section Three Input/Output I/O connection diagrams have been moved to publication B112I/O, I/O Connection Diagrams. Overview Section Organization.............................................. 3-3 I/O Form

More information

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1 2.1 Communication Cards for PC/IPC P 2-1 2.2 Communication Modules for PAC P 2-2 2.3 Converter/Repeater/Hub/Splitter P 2-3 2.4 Termination Resistor/DC Bias Voltage P 2-5 2.5 I/O Modules P 2-6 2.6 I/O Units

More information

Ovation Compact Controller

Ovation Compact Controller Ovation Compact Controller Model OCC100 Features Secure, reliable and mission-critical control capability for remotely located plants or processes Modular I/O base design for flexible placement within

More information

RTK3 Logic Controller User Manual Revised

RTK3 Logic Controller User Manual Revised RTK3 Logic Controller User Manual Revised 6-24-08 1 of 16 svn://software/hardware/rtk3/docs/rtk3_man.doc MRR 6/24/08 9:03 AM Overview The RTK3 is intended to simplify and expedite control wiring. Centroid

More information

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE SCADA INTERFACE INSTRUCTIONS - OPTION 21P / 21Q - FOR A36D/TPSD SYSTEMS A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE OPTION 21P / 21Q INSTRUCTIONS This manual is only valid for A36D/TPSD Chargers equipped

More information

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process Answers to Chapter 2 Review Questions 1. To accept signals from the machine or process devices and to convert them into signals that can be used by the controller 2. To convert controller signals into

More information

Tritex II EtherNet/IP - Option

Tritex II EtherNet/IP - Option Tritex II EtherNet/IP - Option Tritex II Ethernet/IP Option.doc 10/15/13 REV B 952-368-3434 Tritex II EtherNet/IP Option.doc 2 10/15/13 Contents 1. General... 5 1.1. IP Address... 6 1.2. Network Classes...

More information

SMART RELAY SRW 01 V4.0X

SMART RELAY SRW 01 V4.0X Motors Automation Energy Transmission & Distribution Coatings SMART RELAY SRW 01 V4.0X Profibus DP Communication Manual Profibus DP Communication Manual Series: SRW 01 Firmware Version: V4.0X Language:

More information

Table of Contents. C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3

Table of Contents. C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3 Table of Contents C. Control and Signal Modules...3 DH9-M, DH5-T InstaTool DeviceNet Modules...3 1. Product Overview... 3 1.1 InstaTool DeviceNet Module... 3 2. Installation... 5 2.1 Installing... 5 2.2

More information

SPI Protocol Interface Module Cat. No SPI Concepts Manual

SPI Protocol Interface Module Cat. No SPI Concepts Manual Concepts Manual Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary

More information

Central-I Family. CiG1-AMP01-1A-01-00

Central-I Family. CiG1-AMP01-1A-01-00 Central-I Family CiG1-AMP01-1A-01-00 Hardware User's Manual Central-ICentral-I - Hardware Manual -Amplifier CiG1-AMP01- Page 1 Revision control table Version Description Date 1.0 Initial (based on Hardware

More information