1 A BSRIA Guide BG 8/2004 FREE COOLING SYSTEMS BSRIA 2004 Free Cooling Systems By Tom De Saulles Supported by BG 8/2004

2 CONTENTS 1 INTRODUCTION 1 2 WATER-SIDE SYSTEMS Indirect water-side systems Load shaving Direct water-side systems Performance issues Payback for a water-side free cooling system Thermosyphon systems 40 3 AIR-SIDE SYSTEMS Introduction Recirculation systems Full fresh air systems 58 4 MISCELLANEOUS SYSTEMS Direct groundwater cooling Fan coils Chilled ceilings and beams Dry coolers Free cooling chillers Evaporative pre-coolers Evaporative coolers 72 5 KEY SYSTEM ATTRIBUTES 74 6 CASE STUDIES 75 GLOSSARY 90 REFERENCES 91 APPENDICES APPENDIX A: Enthalpy and moisture content, air-side control strategy 88 TABLES Table 1: Results of energy saving calculation 38 Table 2: Results of financial savings and payback calculation 39 Table 3: An energy saving example of a free-cooling chiller 70 Table 4: List of case studies 75 Table 5: Annualised system performance 80 Table 6: Life-cycle costing calculation for the data centre 81 Table 7: Control logic sequences 89 FREE COOLING SYSTEMS

3 FIGURES FIGURES Figure 1: Categories of free cooling systems 2 Figure 2: Main types of water-side free cooling (blue line denotes free cooling flow) 5 Figure 3: Basic configuration of an indirect tower-based free cooling system 6 Figure 4: General control strategy for indirect tower-based free cooling 9 Figure 5: Exploded view of a typical plate heat exchanger showing the path of flow on hot and cold sides (supporting frame not shown for clarity) 10 Figure 6: Relationship between approach and area/cost for a typical plate heat exchanger 12 Figure 7: Relationship between additional savings and plate heat exchanger cost for approach temperatures below 3 K 12 Figure 8: Relationship between flow and cost for a typical plate heat exchanger 12 Figure 9: Use of eccentric reducers to improve liquid-solid separation in side stream filtration 15 Figure 10: Load shaving system using existing cooling towers 17 Figure 11: Basic configuration of a direct tower-based free cooling system 18 Figure 12: Direct free cooling using a common condenser water header 20 Figure 13: Direct free cooling using a dedicated tower and chiller arrangement 20 Figure 14: Automatic back-flushing single-element filters 22 Figure 15: Internal view an automatic back-flushing singleelement filter 23 Figure 16: Configuration of hydrocyclone separator to reclaim water used for flushing 24 Figure 17: Example of two installed variable-gap filters 25 Figure 18: Variable gap filter screen depicted in the filtration mode on the left, and back-flushing mode on the right 25 Figure 19: Annual hours the ambient wet bulb temperature is at or below a given value (bassed on data for heathrow airport ) 28 Figure 20: Monthly average wet bulb temperatures for London, Manchester and Edinburgh ( ) 28 Figure 21: Free cooling availability at varying wet bulb temperatures (Heathrow) 30 Figure 22: Optimal chilled water temperature control diagram (for a constant volume system) 33 Figure 23: Approach of a typical cooling tower operating at varying loads and wet bulb temperatures 34 Figure 24: Cooling tower over-sizing margin at varying loads and values of approach 35 Figure 25: A basic thermosyphon chiller arrangement (arrows indicate flow in thermosyphon mode) 41 Figure 26: Hysteresis effect at start of the thermosyphon process 42 Figure 27: Boiling at the enhanced surface of evaporator tubes 42 Figure 28: A multiple chiller thermosyphon system 44 Figure 29: The three port change over valve in an ammonia based system 44 FREE COOLING SYSTEMS 03/11/04 FREE COOLING Systems

4 FIGURES Figure 30: Single chiller Thermosyphon system with a thermal buffer (arrows indicate flow in thermosyphon mode) 46 Figure 31: Modulating damper system without humidity control 50 Figure 32: Damper operation within an ambient psychrometric envelope 51 Figure 33: Modulating damper system operating under dewpoint control 54 Figure 34: Dewpoint control summer 54 Figure 35: Dewpoint control (spring/autumn) 55 Figure 36: Dewpoint control (winter) 55 Figure 37: Modulating damper system operating under moisture content and enthalpy control 56 Figure 38: Enthalpy and moisture content control 56 Figure 39: Moisture content control 56 Figure 40: Static pressure drop (constant pressure operation) 57 Figure 41: Full fresh air system with air-to-air plate heat exchanger and indirect evaporative cooling 60 Figure 42: Psychrometric process for system depicted in figure Figure 43: Sprayed plate cooler in operation 61 Figure 44: Desiccant cooling system incorporating thermal wheel and evaporative humidification in supply and extract 62 Figure 45: Psychrometric process for a desiccant cooling system depicted in figure Figure 46: A central air handling plant cooling coil used to provide free cooling in a fan coil system 65 Figure 47: Load shaving with a dry cooler 67 Figure 48: Simplified free-cooling chiller, with the free-cooling coil operational 68 Figure 49: Typical free-cooling chiller operation at varying ambient temperatures (based on weather data for London) 69 Figure 50: Example of a free cooling chiller 69 Figure 51: Typical application of evaporative pre-coolers 71 Figure 52: Terminal 1, Heathrow Airport 76 Figure 53: One of the induced-draught cooling towers 77 Figure 54: British Airways Data Centre, Cranebank, Heathrow 78 Figure 55: Two views of one of the thermosyphon chillers installed at the data centre 78 Figure 56: Condenser and chiller capacities for a range of dry bulb and chilled water temperatures at the data centre 79 Figure 57: Portcullis House, Westminster 82 Figure 58: The borehole cap at Portcullis House 83 Figure 59: Simple basket strainer used to filter the groundwater water 84 Figure 60: PHEs exchange heat between the groundwater and chilled water circuit 84 Figure 61: Learning Centre - Main Entrance Interior, Leeds Metropolitan 86 Figure 62: The spray nozzles on the underside of the evaporative coolers at the Leeds Metropolitan University Learning Centre 87 Figure 63: Control logic flow diagram 88 FREE COOLING SYSTEMS

5 INTRODUCTION INTRODUCTION INTRODUCTION The ongoing drive to reduce the environmental impact of the UK building stock has increased the pressure on architects, engineers and building operators to avoid the use of air conditioning in favour of more passive cooling solutions - such as natural ventilation and the use of thermal mass. Good progress has been made in this direction, but many passive solutions are limited to new build projects, which only represent 2-3% of the UK building stock. For existing buildings, and those for which mechanical air conditioning cannot be avoided, other options must be considered. Unfortunately, mechanical air conditioning is often perceived as a system for which only very limited energy saving measures can be applied. This is rarely the case, as the incorporation of a free cooling capability can significantly improve overall efficiency. Free cooling in the context of this Guide can be broadly defined as that amount of cooling which can be obtained to wholly or partly offset the load on mechanical refrigeration plant. With the exception of two systems, the techniques covered in this guide satisfy this definition. The exceptions are ground water and desiccant cooling, which have nevertheless been included for their relevance. Free cooling systems take advantage of favourable weather conditions to enable chiller plant to be shut down for long periods, saving significant amounts of energy and cutting carbon emissions. The technology associated with free cooling is neither complex or new, but opportunities to make use of it are often overlooked or not understood. The purpose of this Guide is to help address the problem by providing free cooling design and application information for designers, technically-aware clients and building operators. The basic free cooling techniques detailed in this Guide each have particular attributes suited to many different types of air conditioning systems. This makes free cooling a very versatile energy saving measure that is not limited to new buildings. The business case for retrofitting free cooling is often quite compelling, and the payback period can be short. Disruption to business activities during installation is often minimal, as most of the plant can often be installed alongside existing plant and interconnected at the end of the installation process. Due to the bespoke nature of free cooling systems, no single guide can anticipate the circumstances and demands of all applications. However, this Guide is intended to provide a general insight into the main free cooling techniques that can be applied. The content has not been divided between new build and retrofit projects as much of the guidance is applicable to both, although where this is of particular relevance the distinction is made. The report provides an understanding of the types of system and their associated advantages and limitations, the requirements for effective application, the methods of system control, and general guidance on system design and sizing of components. FREE COOLING SYSTEMS 1

6 1 INTRODUCTION Figure 1 shows the various free cooling systems included in the Guide, and the three ways in which they have been categorised. The main characteristics of each system are provided in a summary table located at the end of the Guide (see Table 7). Figure 1: Categories of free cooling systems. Important requirements for effective free cooling Selecting a water-side free cooling technique appropriate to a particular project is relatively straightforward, as it is largely dictated by the type of installed or proposed air conditioning system. Assessing the likely energy saving potential is a little more involved. However, there are several essential questions which are relatively easy to answer, and will provide an indication of whether it is worth continuing with a more detailed assessment. These questions are summarised below, and given more detailed coverage in Section 2, which concludes with a worked example of a payback calculation. The following questions should be answered to determine whether a water-side free cooling system may be effective: Is there a significant cooling load during the winter months, for instance greater than 20% of the design full cooling load? Is the installed capacity of the chiller plant greater than approximately 1 MW? Is the winter cooling load present on a 24h basis? 2 FREE COOLING SYSTEMS

7 INTRODUCTION 1 Is a relatively high chilled-water temperature acceptable? Is there spare cooling tower capacity such as a standby tower, and/or are the tower(s) known to be oversized or more than adequate to meet the peak summer load? If the answers to these questions reveals a potential for free cooling, it will be necessary to obtain detailed load profile data and performance information for the towers in order to make a more detailed assessment (see Section 2.4, page 28). Airside systems must be addressed in a different manner, as the majority of devices and techniques that can be used to provide free cooling in airside systems can also provide heat recovery in the winter. In fact, it is the heat recovery capability that is likely to save the most energy and determine the approach used. In modern design practice it is very unlikely that an air-side system would be designed without some form of free cooling or heat recovery capability. As it is standard practice to incorporate some form of heat recovery/free cooling capability into airside systems, the key design issue is not whether to incorporate such a capability, but rather which technique to use. This question is examined in Section 3. FREE COOLING SYSTEMS 3

8 2 WATER-SIDE SYSTEMS WATER-SIDE SYSTEMS 2 2 WATER-SIDE SYSTEMS The term water-side system in the context of free cooling systems describes free cooling techniques that can be applied in centralised chilled water installations incorporating cooling towers or evaporative coolers (see Figure 2). Water-side systems can be divided into two types: direct and indirect. Direct water-side systems (Section 2.3) physically interconnect the chilled water and condenser water circuits during free cooling operation, enabling heat to be rejected directly by the cooling towers without the need to run the chillers. The main benefit of this technique is that the chilled water to ambient wet-bulb approach temperature is kept to a minimum, which in turn maximises free cooling availability. The drawback of direct interconnection is the need for a strict water treatment regime to reduce the risk of corrosion and prevent dirty water from the cooling tower fouling the chilled water circuit. This risk has led to a decline in the application of direct systems. Although briefly popular in the 1980 s, direct systems have since been largely overshadowed by indirect systems. A variation on the water-side technique described above is the loadshaving system (Section 2.2). This makes use of one or more cooling towers or evaporative coolers to pre-cool the return chilled water before it reaches the chiller(s), and consequently reduces the mechanical cooling load. This technique ensures that, even during marginal ambient conditions, some free cooling (load shaving) is possible, which is not the case for direct and indirect water-side systems. Under favourable ambient conditions some load shaving systems can also provide full free cooling, enabling the chiller(s) to be shut down. An example of a load shaving system is described later (see Section 2.2). Indirect water-side systems (Section 2.1) avoid the problem of fouling by maintaining the chilled water circuit as a closed loop and rejecting heat to the cooling towers via a plate heat exchanger (plate heat exchanger). Alternatively, an indirect system may incorporate one or more closed circuit cooling towers or evaporative coolers. The disadvantage of indirect systems is the introduction of an additional heat transfer surface, which increase the chilled water to ambient wet-bulb approach temperature, resulting in a slight reduction in free cooling availability. Thermosyphon systems (Section 2.6) can also be described as an indirect water-side system, as the chilled water circuit remains hydraulically isolated at all times. This technique uses the difference in temperature/pressure between the evaporator and condenser during cooler weather to drive refrigerant around the circuit without the need to operate the compressor. Thermosyphon systems can be particularly effective as they offer both a free cooling and load shaving capability. 4 FREE COOLING SYSTEMS

9 WATER-SIDE SYSTEMS 2 Figure 2: Main types of water-side free cooling (blue line denotes free cooling flow). 2.1 INDIRECT WATER- SIDE SYSTEMS Case study 1 As the name suggests, indirect tower-based free cooling systems reject heat to cooling towers indirectly, typically by means of a plate heat exchanger (see Figure 3). Consequently, as the condenser and chilled water circuits are at no point interlinked during free cooling, the risk of increased fouling and corrosion associated with direct systems is avoided (see Section 2.3, Direct water-side systems). The penalty for using a plate heat exchanger is an increase in the chilled water to wet-bulb approach temperature, the size of which will cause a corresponding reduction in free cooling availability. With very few exceptions, the trade-off is generally judged to be worthwhile, as the level of maintenance and risk of fouling associated with direct systems may be regarded as too onerous. The evidence for this can be seen in the increasing number of indirect systems specified in recent years, and the almost complete absence of direct systems, which had their heyday in the early to mid-1980 s. FREE COOLING SYSTEMS 5

10 CASE STUDIES CASE STUDIES CASE STUDIES Five case studies are presented, two dealing with free cooling in waterside systems and three using other cooling techniques and equipment. Table 4: List of case studies. 1. Indirect water-side system Terminal 1, Heathrow Airport 2. Thermosyphon system British Airways Data Centre, Heathrow 3. Direct ground water cooling Portcullis House, Bridge Street, Westminster 4. Chilled ceiling Department of Trade and Industry, London 5. Evaporative cooler City Campus Learning Centre, Leeds Metropolitan University FREE COOLING SYSTEMS 75

11 4 CASE CASE STUDY STUDIES 1 Indirect water-side system for Terminal 1, Heathrow Airport Figure 52: Terminal 1, Heathrow Airport. Background Due to the increase in retail space within the Terminal 1 over the past 20 years the cooling requirements at the Terminal have changed. The cooling demand profile now means that parts of the Terminal need to be air-conditioned throughout the year. An initial feasibility study was undertaken to identify the potential for adopting a free cooling system in order to reduce costs. Power Plan Services undertook this study and the subsequent free cooling design, which was developed to coincide with the installation of a third chiller. This meant that all of the pipework modifications and connections were made such that the free cooling system could be installed with the minimum of disruption. When the cooling towers were replaced in1999, it was decided to incorporate a free cooling system. The system comprises a stainless steel plate heat exchanger adjacent to one of the chillers. The water which passes over the cooling towers is usually at 25 C, but when the outside temperature is low enough the towers can produce water at 6 C. Heat is transferred between the cooling towers and the chilled water via the plate heat exchanger. This means that the chiller, which is designed to produce water at 6 C, is replaced by the plate heat exchanger. The system functions by a series of large valves redirecting the cooling tower water and chilled water through the plate heat exchanger. The control system is linked to the BMS, which continuously monitors the outside air temperature and moisture content. When the conditions are suitable the changeover to free cooling is fully automatic. 76 FREE COOLING SYSTEMS

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable

More information

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Data Centre Solutions Expertly Engineered Indirect Adiabatic and Evaporative

More information

Indirect Adiabatic and Evaporative Data Centre Cooling

Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

Indirect Adiabatic and Evaporative Data Center Cooling

Indirect Adiabatic and Evaporative Data Center Cooling Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Ecoflair Air Economizers

Ecoflair Air Economizers Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

Saving Water and Operating Costs at NREL s HPC Data Center

Saving Water and Operating Costs at NREL s HPC Data Center Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov

More information

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen,

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen, Energy Management of the Refrigeration Systems at Zurich Airport Burkhard Bein Schaffhausen, 29.06.18 Overview Content: General Information Refrigeration concept EMS program CS program Three projects for

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

CASE STUDIES ENERGY EFFICIENT DATA CENTRES

CASE STUDIES ENERGY EFFICIENT DATA CENTRES CASE STUDIES ENERGY EFFICIENT DATA CENTRES Testimonials We are delighted that our PUE is less than 1.15 during the summer, achieving what we felt was a very ambitious programme of work with a targeted

More information

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa Freecooling, Evaporative and Adiabatic Cooling Technologies

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

MOLLIER DIAGRAM CAN BE IMPROVED!

MOLLIER DIAGRAM CAN BE IMPROVED! MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

Ecotel Free Cool 5-15kW

Ecotel Free Cool 5-15kW Precision Air Conditioning Free-cooling Ecotel Free Cool 5-15kW + + Self-contained compact outdoor cabin cooler + + 100% free-cooling + + -48V DC supply option + + Easy serviceability (front component

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England > For the latest information on our products please visit : www.airedale.com > Please refer to the technical manuals for more detailed information Your nearest Airedale distributor is: ISO 14001 EMS52086

More information

BSRIA Air Conditioning Worldwide Market Intelligence

BSRIA Air Conditioning Worldwide Market Intelligence 2013 BSRIA Air Conditioning Worldwide Market Intelligence Over 25 years experience researching key markets worldwide market intelligence in 94 Countries integrated technical and market expertise management

More information

HIGH EFFICIENCY Central Chiller

HIGH EFFICIENCY Central Chiller Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,

More information

ecoenergy Innovation Initiative Research and Development Component Public Report

ecoenergy Innovation Initiative Research and Development Component Public Report ecoenergy Innovation Initiative Research and Development Component Public Report Project: Integrated Approach to Development of a High Efficiency Energy Recovery and Intelligent Ventilation System Contents

More information

Airside Economizer Comparing Different Control Strategies and Common Misconceptions

Airside Economizer Comparing Different Control Strategies and Common Misconceptions Airside Economizer Comparing Different Control Strategies and Common Misconceptions Jijun Zhou, PE Guanghua Wei, PE W. Dan Turner, PhD, PE David E. Claridge, PhD, PE Texas A&M University College Station,

More information

Aquaflair. BREC/F and BCEC/F kw

Aquaflair. BREC/F and BCEC/F kw Aquaflair Air-cooled chillers and free-cooling chillers with screw or oil-free centrifugal compressors equipped with adiabatic system BREC/F and BCEC/F 350-1350 kw Dualism for evolution: the combination

More information

HOURLY ANALYSIS PROGRAM v5.00 and v5.01

HOURLY ANALYSIS PROGRAM v5.00 and v5.01 HOURLY ANALYSIS PROGRAM v and v5.01 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. November 3, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Chiller Features

More information

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Designing Ultra-Efficient Building Cooling Systems

Designing Ultra-Efficient Building Cooling Systems Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,

More information

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution CGWN/CCUN indoor liquid chillers The compact AquaStream² solution Plug and Play for unparalleled Certified performance Eurovent certification provides capacity and efficiency compliance, thus confirming

More information

New Design Strategies for Energy Saving. Intelligent free-cooling

New Design Strategies for Energy Saving. Intelligent free-cooling New Design Strategies for Energy Saving Intelligent free-cooling Intelligent New strategies for energy saving When designing mission critical systems for processing applications or highly technological

More information

AireFlow kW DX AIR. Data Centre Cooling Product of the Year. Indirect Adiabatic AHU

AireFlow kW DX AIR.   Data Centre Cooling Product of the Year. Indirect Adiabatic AHU IT Cooling Indirect Adiabatic AHU Data Centre Cooling Product of the Year AireFlow 100-440kW Indirect adiabatic cooling for resilient, optimised data centre cooling + Delivers all year round free-cooling*

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012 UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A 004 11 JUNE 2012 TABLE OF CONTENTS Abstract...3 Introduction...3 Methodology...4

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

Case Study The University of Warwick

Case Study The University of Warwick Data Centre Solutions...energy efficient by design Case Study The University of Warwick Workspace Technology deploys industry leading Indirect Fresh Air Cooling for the University of Warwick Workspace

More information

Precision Cooling Mission Critical Air Handling Units

Precision Cooling Mission Critical Air Handling Units M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

Airside Economizer Comparing Different Control Strategies and Common Misconceptions

Airside Economizer Comparing Different Control Strategies and Common Misconceptions ESL-IC-8-1-54 Airside Economizer Comparing Different Control Strategies and Common Misconceptions Jijun Zhou, PE Guanghua Wei, PE W. Dan Turner, PhD, PE David E. Claridge, PhD, PE Texas A&M University

More information

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS GLOBAL PRESENCE, LOCAL SERVICE WHERE WE MAKE IT WORK WHO WE MAKE IT WORK FOR ACCREDITATIONS i-chiller -10 C to 30 C 1.7 TO 505kW i-chiller COMPACT

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from

More information

Identify the Right Applications

Identify the Right Applications providing insights for today s hvac system designer Engineers Newsletter volume 45 2 waterside economizers Keeping the "Free" In Free-Cooling This EN revisits the topic of a 2008 newsletter and provides

More information

Case study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence

Case study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence Case study: Energy efficiency improvements in a legacy data centre Robert Tozer Director Opera>onal Intelligence Objec>ves First improve air management Air supply temperature to servers Lower temperature

More information

DATA CENTER AIR HANDLING COOLING SOLUTIONS

DATA CENTER AIR HANDLING COOLING SOLUTIONS DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner

More information

CHILLERS & HEAT PUMPS DYNACIAT HIGH ENERGY PERFORMANCE WITHIN OPTIMISED FOOTPRINT

CHILLERS & HEAT PUMPS DYNACIAT HIGH ENERGY PERFORMANCE WITHIN OPTIMISED FOOTPRINT CHILLERS & HEAT PUMPS DYNACIAT HIGH ENERGY PERFORMANCE WITHIN OPTIMISED FOOTPRINT DYNACIAT: HIGH PERFORMANCE HEATING AND COOLING FOR MEDIUM-SIZED BUILDINGS To better meet customer needs and answer environmental

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Trailblazer AGZ-E air-cooled scroll chillers

Trailblazer AGZ-E air-cooled scroll chillers Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore

More information

09LD/GD. Air-Cooled Condensers/Air-Cooled Fluid Coolers. Nominal cooling capacity kw 09LD/GD 09GD

09LD/GD. Air-Cooled Condensers/Air-Cooled Fluid Coolers. Nominal cooling capacity kw 09LD/GD 09GD Air-Cooled Condensers/Air-Cooled Fluid Coolers 09LD/GD 09GD 09LD/GD Nominal cooling capacity 281-987 kw The 09LD air-cooled condensers are designed for refrigeration plants where a halogenated hydrocarbon,

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation Engineered Energy Solutions An Overview Controls, Automation and Energy Conservation Engineered Energy Solutions Independent Control System Integration and Engineering Firm specializing in the energy efficient

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

We design and produce special units for applications in air conditioning, refrigeration and air treatment systems, specifically developed to meet our

We design and produce special units for applications in air conditioning, refrigeration and air treatment systems, specifically developed to meet our We design and produce special units for applications in air conditioning, refrigeration and air treatment systems, specifically developed to meet our clients requirements and with the lowest environmental

More information

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011 Energy Study Programs December 2011 1 Agenda Energy Study Programs Overview Recommissioning Engineering Studies Data Center Studies Custom Rebates What makes a good energy study? 2 Energy Study Program

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

HVAC Energy Management System

HVAC Energy Management System HVAC Energy Management System Spotlight coordinates the complex tasks required by a building s heating, cooling, fresh air, humidification and lighting systems resulting in increased efficiencies. OVERVIEW

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Trading TCO for PUE? A Romonet White Paper: Part I

Trading TCO for PUE? A Romonet White Paper: Part I Trading TCO for PUE? A Romonet White Paper: Part I Executive Overview Most data center vendors claim to improve Power Usage Effectiveness (PUE). The problem with this is that focusing on reducing PUE makes

More information

Who are Aqua Cooling?

Who are Aqua Cooling? Data Centre Cooling Who are Aqua Cooling? Started in 2001, head office based in Fareham, with regional offices in Midlands & North Market leaders in Air Conditioning, Industrial Cooling and Data Centre

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit

CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW The indirect evaporative free-cooling Air Handling Unit Flexible & Efficient 11 sizes from 30 kw up to 520 kw to fit your needs with maximum efficiency

More information

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS Capacity from 600 to 2,010kWr Engineered for flexibility and performance PRODUCT LEAFLET THE AWS SERIES OFFERS TOP EFFICIENCY, LOW SOUND LEVELS AND FLEXIBLE

More information

Optimiz Chilled January 25, 2013

Optimiz Chilled January 25, 2013 Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building

Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Dhayanandh Murugan 1, Gabrielle Viola McMorrow 1, Dr.Liping Wang 1, Greenberg Steve 2 1 University of Wyoming,

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Waterside Economizing in Data Centers: Design and Control Considerations

Waterside Economizing in Data Centers: Design and Control Considerations 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction,

More information

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling CHILLER PLANT CONTROLS The challenges of producing chilled water are not the same as those a decade

More information

Results of Study Comparing Liquid Cooling Methods

Results of Study Comparing Liquid Cooling Methods School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September

More information

Improving the climate for data centers

Improving the climate for data centers Maximum performance for cool computers Improving the climate for data centers We create a good indoor climate. Supply air Return air Return air Outside air Exhaust air Pressure floor Our ventilation technology

More information

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11 Table of Contents Executive Summary... 3 Site and Unit Background... 5 Chiller 1... 6 Chiller 2... 9 Appendix... 11 A Vidaris Company 2 Executive Summary New York Blood Center s facility in Long Island

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

R4 Ventures LLC White Paper

R4 Ventures LLC White Paper R4 Ventures LLC PR ODUCT IN HARD COPY OR DIGITAL FORM. ALL OFFENDERS WILL BE SUED IN A COURT OF LAW. R4 Ventures LLC White Paper Comparison of energy consumption in kw per ton of cooling Real Time Data

More information

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA 99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and

More information

Saving Energy with Free Cooling and How Well It Works

Saving Energy with Free Cooling and How Well It Works Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science

More information

Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services

Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services EMEA Roll-out 2 Main Mirror UK Swindon/Newbury area (15,000m 2 ) Germany Russelsheim(main)/

More information

After Adiabatics. How to achieve low energy cooling in high density data centres whilst minimising water usage

After Adiabatics. How to achieve low energy cooling in high density data centres whilst minimising water usage How to achieve low energy cooling in high density data centres whilst minimising water usage Stuart Kay Business Development Director After Adiabatics Global water crisis Evolution of data centre cooling

More information

How Green can you go?

How Green can you go? ASHRAE 90.1 2010 It s out..and should be our code in 3 years Work on sealing and testing building envelope, commissioning Cool Roofs..hey were already doing that Extensive Controls enhancements Equipment

More information

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers INNOVATE DESIGN APPLY www.motivaircorp.com MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers ½ - 100 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Motivair is a world-class

More information

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of

More information

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM IEM TRAINING CENTRE SDN. BHD. (127273-K) No. 33-1A (1 st Floor), Jalan 52/18, P.O. Box 224 (Jalan Sultan P.O.) 46720 Petaling Jaya, Selangor Darul Ehsan (GST ID No. 001525395456) Telephone No. 03-79586851

More information

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE 90.1-2016 Revisions to Waterside Economizer March 15, 2017 Stefan Gracik 510-663-2070 sgracik@integralgroup.com Agenda 1. Background

More information

Contents. Rev. 2, 5/12/2016 1

Contents. Rev. 2, 5/12/2016 1 Answers to Frequently Asked Questions for CTI STD-201 Thermal Certification of Cooling Towers, Closed Circuit Coolers and Evaporative Refrigerant Condensers Contents What is CTI STD-201?... 3 To what equipment

More information

i-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw

i-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw i-accurate_gb_07-2011 igh precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 Coming form 40 years experience in air conditioning and

More information

Liebert. DSE Thermal Management System Free Cooling Economization Without Using Water

Liebert. DSE Thermal Management System Free Cooling Economization Without Using Water Liebert DSE Thermal Management System Free Cooling Economization Without Using Water LIEBERT DSE THERMAL MANAGEMENT SYSTEM Liebert DSE System Overview A Highly Efficient, Self-Optimizing Solution for Thermal

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information