IPSUM » COMMISSIONING GUIDE. IPSUM Optimizer IPSUM Connection unit IPSUM Router AIR COMFORT AIR MANAGEMENT IPSUM OPTIMIZATION SYSTEM

Size: px
Start display at page:

Download "IPSUM » COMMISSIONING GUIDE. IPSUM Optimizer IPSUM Connection unit IPSUM Router AIR COMFORT AIR MANAGEMENT IPSUM OPTIMIZATION SYSTEM"

Transcription

1 AIR COMFORT AIR MANAGEMENT OPTIMIZATION SYSTEM» COMMISSIONING GUIDE Optimizer Connection unit Router

2 Content 1 Introduction Web interface Compact mode Step by step guide Full mode Step by step guide Setting up the network for Modbus for Addressing the components STRA-04 and STRA-14 Room controllers Compact controllers 227VM and 227PM Optimizer and Router Connecting to the web server Commissioning mode, Optimizer Log in to Optimizer Admin settings General settings Settings AHU Settings Setting up eq, eql & eq for Building Management Settings Users/Groups Optimization settings Settings for Pressure Optimization General settings Linear Optimization Mode Step Optimization Mode Settings for Temperature Optimization scan Fläkt Woods 9403 GB We reserve the right to alter specifications.

3 1 Introduction This document contains information, guides and tips which are needed for commissioning the system. In this document there is a brief overview to the Modbus protocol, how to set up the Modbus network for including detailed information how to set the Modbus parameters for each of the products, how to connect to the building management system, how to control an air handling unit and detailed information how to select optimization variables and system settings. Separate documentation is also available for Cabling, Installation and Operating & Maintenance as well as datasheets. For installation, setting up functionalities and detailed product information, please see separate documents. 1.1 Web interface The system has a built-in web interface. This interface is used to change settings, monitor system status and monitor energy savings. The interface is designed to be simple to use showing only the essential information. Figure 1. Web interface Fläkt Woods 9403 GB We reserve the right to alter specifications.

4 1.2 Compact mode Step by step guide This Chapter and the next Chapter helps you to outline steps which are needed when the commissioning takes place. Please go through each step of the list carefully. 1. Connect the components, check that the connections are all correct and switch on the power, see separate Installation Guide. 2. Set Modbus addresses and communication parameters for each component in the sys tem, see Chapter 2.1 in this document. The communication parameters must be the same for all devices on a Modbus Serial line. 3. Set hardware settings (sensors connected, output signals, etc.) for room controllers, see STRA-manuals 4. Connect your computer to the Optimizer, see Chapter in this document 5. Set date and time, see Chapter 3.1 in this document 6. Set system mode to Compact, see Chapter 3.2 in this document 7. Set communication to the air handling unit, see Chapter 3.3 in this document 8. Set BMS/SCADA settings if necessary, see Chapter 3.4 in this document 9. Create user accounts and change default passwords or remove the default users, see Chapter 3.5 in this document 10. Set basic Optimization settings, see Chapter 4.1 for pressure optimization and Chapter 4.2 in this document for temperature optimization 11. Run Scan, see Chapter 5 in this document 12. Fix possible errors and check from the web view that all products and accessories were found correctly. Run Scan again if any issues were found. 13. Rename rooms and branches, and adapt the web interface view, see Operation & Maintenance manual 14. Set pressure, flow, temperature, etc. settings and setpoints for each device, see Operation & Maintenance manual 15. Fine tune the optimization parameters if necessary 16. Fill in the commissioning protocol 1.3 Full mode Step by step guide 1. Connect the components, check that the connections are all correct and switch on the power, see separate Installation Guide 2. Set Modbus addresses and communication parameters for each component in the system, see Chapter 2.1 in this document. The communication parameters must be the same for all devices on a Modbus Serial line 3. Set hardware settings for room controllers (sensors connected, output signals, etc.), see STRA-manuals 4. Connect your computer to the Optimizer, see Chapter in this document 5. Set Routers communication settings, see Chapter in this document 6. Set date and time, see Chapter 3.1 in this document 7. Set system mode to Full, see Chapter 3.2 in this document 8. Set communication for the air handling unit, see Chapter 3.3 in this document 9. Set BMS/SCADA settings if necessary, see Chapter 3.4 in this document 10. Create user accounts and change default passwords or remove the default users, see Chapter 3.5 in this document 11. Set basic Optimization settings, see Chapter 4.1 for pressure optimization and Chapter 4.2 in this document for temperature optimization 12. Run Scan, see Chapter 5 in this document 13. Fix possible errors and check from the web view that all products and accessories were found correctly. Run Scan again if any issues were found. 14. Rename rooms and branches, and adapt the web interface view, see Operation & Mainte nance manual 15. Set pressure, flow, temperature, etc. settings and setpoints for each device, see Operation & Maintenance manual 16. Fine tune the optimization parameters if necessary 17. Fill in the commissioning protocol Fläkt Woods 9403 GB We reserve the right to alter specifications.

5 2. Setting up the network for In this Chapter you will find information on how to set up the network for the system, how communication parameters for each of the components are set, how to connect to the web interface and how to modify the view of the web interface. 2.1 Modbus for Modbus is a widely used, openly published and a royaltyfree Master-Slave serial line communication protocol. The system uses Modbus protocol to communicate between components such as Optimizer to Routers, Optimizer/Routers to room controllers and dampers/diffusers as well as to gather information from the system. The Modbus specification defines transmission protocol, the structure of the message and the transmission modes. All serial parameters must be the same for all devices on a Modbus Serial line. Adjustable serial parameters in the system are baud rate, parity and stop bits. These need to be set separately for each device. The transmission modes are RTU and ASCII. Default transmission mode for all Fläkt Woods products is RTU. The devices must also have an individual address. Modbus Serial Master-Slave protocol means that only one master device can be connected to the bus at a Addressing the components Addresses in a slot must be set so that in Slot 1 the address of the controller is 1 and the addresses of the products are 2 (Supply) and 3 (Extract), in Slot 2 the address of the controller is 6 and the addresses of the products are 7 (Supply) and 8 (Extract), etc. The printime. The master will first send a request message and then listen for the reply from the slave. In compact mode, Optimizer is master to products on the system side. In a full mode, Optimizer is master to the Routers and the Routers are masters to products on the system side, and thus the Optimizer does not have direct contact to the components. The Modbus specification specifies that a transmission line must be terminated near each of the 2 ends of the bus to avoid reflection. Optimizer, Router and Connection Unit s have built-in terminal resistors. The termination can be activated by switching on a dip-switch. has multiple automatic functions to ensure that setting up the system is as simple as possible. The system identifies the components connected to the internal communication bus and there are clever rules to check that components are correctly connected. ciple of the addressing is illustrated in Figure 2. If the product seen in the Figure is not installed in the system, the address is left unused. If a room/branch have more than 1 supply or extract damper, the address for the extra dampers must be taken from next slots. Figure 2. Addressing for Fläkt Woods 9403 GB We reserve the right to alter specifications.

6 Example 1: A branch with 1 supply pressure damper and 1 extract pressure damper, and a room with a room controller, 1 VAV supply damper and 1 VAV extract damper. Branch: An address of the supply pressure damper is 2 and an address of the extract pressure damper is 3 Room: An address of the room controller is 6, an address of the supply damper is 7 and an address of the extract damper is 8. Figure 3. Example 1: Modbus addresses for a branch and a room Fläkt Woods 9403 GB We reserve the right to alter specifications.

7 Example 2: A system contains a room 1 with 2 VAV supply dampers, 1 VAV extract damper and 1 room controller, and a room 2 with 1 CAV supply damper and 1 CAV extract damper. Room 1: An address of the room controller is 1, an address of the first supply damper is 2, an address of the second supply damper is 7 and an address of the extract damper is 3. Room 2: An address of the supply damper is 12 and an address of the extract damper is 13. Figure 4. Example 2: Modbus addresses for VAV room and CAV room Fläkt Woods 9403 GB We reserve the right to alter specifications.

8 2.1.2 STRA-04 and STRA-14 Room controllers STRA-04 and STRA-14 are room controllers which handle heating, cooling and ventilation. The room controllers ensure that the room air climate meets the requirements in the most energy efficient way. STRA-04 is optimized for Variable Air Volume applications and STRA-14 is optimized for Chilled Beam applications. Changing parameters The communication parameters can easily be set in a parameter menu shown on the display using the buttons of the controller. This parameter menu is accessed by simultaneously pressing the INCREASE and DECREASE buttons for about 5 seconds until the Service indication lights up in the display and after that, pressing the INCREASE button twice. A parameter number (P01, P02, P03, etc.) is shown in the parameter menu. The parameters are scrolled by pressing the INCREASE and DECREASE buttons. When the right parameter has been selected, press the Function button. The parameter value will be shown and the parameter number will disappear. The parameter value is changed using the INCREASE and DECREASE buttons, and the change is confirmed with the Function button. Before con- firming the change by pressing the Funtion button, he original value can be retrieved by simultaneously pressing the INCREASE and DECREASE buttons. The original value will be shown on the display. Pressing simultaneously INCREASE and DECREASE buttons while the parameter menu is active will return the controller to the main display. This will also happen after 1 minute of inactivity or by selecting the EXIT option with the INCREASE and DECREASE buttons and then pressing the Function button. Figure 5. Buttons of the Room Function button INCREASE DECREASE Modbus parameters The communication parameters are presented in Table 1. The Address of the room controllers must be changed according to Section and the baud rate checked/changed as below. Default values for Modbus timeout and Modbus response delay are recommended minimums. Parameter number Description Values Type STRA Default 69 Modbus address N/A Set by production Configuration for 70 Modbus parity 0=None, 1=Odd, 2=Even N/A Modbus Timeout Milliseconds Modbus Response Delay 114 Port Mode 119 Communication speed Table 1. Modbus Settings for STRA room controllers 0=EXOline/Modbus, 1=BACnet 0=9600, 1=19200, 2=38400, 3=76800 (BACnet) As Milliseconds 5 5 N/A 0 0 N/A 0 1 Functional settings After setting the communication parameters, set functional parameters such as Operation Mode, setpoints, etc, if necessary. For more information, see STRA documentation or contact Fläkt Woods technical support. Fläkt Woods 9403 GB We reserve the right to alter specifications.

9 2.1.3 Compact controllers 227VM and 227PM Fläkt Wood s compact controller 227VM is a complete unit comprising an actuator, a dynamic differential pressure sensor for pressure-independent control and user interface with 3-digit display which enables monitoring the air flow and setting up values without the need for any external equipment. (1) (2) (3) Fläkt Wood s compact controller 227PM is a complete unit comprising an actuator, a dynamic differential pressure sensor for pressure-dependent air flow control and a user interface with a 3-digit display which makes it possible to monitor pressure and set values without the need for any external equipment. Figure VM User Interface The compact controllers are used to control air flow to and from the rooms or branches. A setpoint for the controllers can be set via the IPSUM web interface or the room controller. User interface The User interface on the 227VM is seen in Figure 6 and the user interface on the 227PM is seen in Figure 7. The user interfaces have three parts; value selector (1), function selector (2) and display (3). (1) (2) (3) Figure PM User Interface Modbus parameters Modbus address is set by turning the function selector to Adr and then turning the value selector to get the desired address. After the value flashes twice, the value is stored. Default address is 1. Modbus communication parameters are located in a sub-menu. The sub-menu is accessed by turning the function selector to Adr and then turning the value selector until the parameter 2in is seen on the display. When the sub-menu is open, a small circle can be seen on the display. When the Function selector is turned to Adr in submenu, the communication parameters can be set with the value selector. Default Modbus settings Communication Speed and Even parity corresponding to number 5 in Adr. Parameter location Adr Sub-menu Adr Description Values Default Modbus address Communi cation parameters 5 = 19.2kbaud, Even parity and 1 stop bit Table 2. Modbus Settings for 227PM and 227VM 1 Use with IPSUM As Chapter Functional settings For more information, see documents EMSS and EMPA documentation or contact Fläkt Woods technical sales support. Turn the Function selector to Flow in 227VM or to Pres/Unit in 227PM to exit from the sub-menu. Fläkt Woods 9403 GB We reserve the right to alter specifications.

10 2.2 Optimizer and Router This Section shows how to connect to the web server, how the Optimizer and Router are connected and how the system communication parameters are changed. Settings for connecting to the air handling unit and building management system are detailed in Chapters 3.3 and Connecting to the web server Connection to the web interface is handled via the Supervisor Ethernet port. The web server supports both static and DHCP addressing. The default is that DHCP addressing is activated. The NetBIOS name of the Optimizer and Router is fwg-ipsum-xxxx, where xxxx is unique for each device and is made up of the last 4 digits of the MAC address. The MAC address can be found in a sticker located on the side of Optimizer. To connect to the Optimizer s in-built web pages you connect a computer directly to the Optimizer s supervisor ethernet port using a crossover patch cable. Connect the Optimizer to a network with fixed IP addresses or to a network using DHCP where the Optimizer is given an IP address (default). If a fixed IP address is needed to get first contact with the Optimizer to setup any of the above then Optimizer can be put in to Commissioning mode using the Comm/Reset push button. Figure 8. Sticker located on the side of the Optimizer Commissioning mode, Optimizer The Supervisor Ethernet Port can also be forced to a fixed address for a period of time to allow connecting a computer directly with a crossover cable for commissioning or diagnostics with a following procedure: Press Comm/Reset-button (item 10 in Figure 9) for 5 seconds to put Optimizer to Commissioning mode. s green LED will flash when the Optimizer is in the Commissioning mode Connect one end of the cross-over cable to Optimizer Ethernet port (item 3 in Figure 9) and another end to computer s Ethernet port. Ethernet ports green and yellow LEDs will be lit when the cable is connected Write IP-address to browser s address bar to open a log in page Fixed IP-address in the commissioning mode is and Supervisor port Modbus communication parameters are 19,200 baud rate, Even Parity, 1 Stop bit and address vac/dc PE N L GO/-G/+ GO/-G/+ Ethernet Alarm C 230vac/ In 24vac/dc 24vac/dc Output In Out Fire Free Cooling 230vac Power Supervisor Active C B/- A/+ Supervisor IPSUM Optimizer Air Handling Unit / Air Handling Unit SA Fan EA Fan Temp 0-10v 0-10v 0-10v Comm/ Ethernet Active A/+ B/- C SD Card Reset HMI Ethernet Active A/+ B/- C Figure 9. Commissioning mode 13 Fläkt Woods 9403 GB We reserve the right to alter specifications.

11 2.2.3 Log in to Optimizer Login screen is seen in Figure 10. Language of the web pages can be changed from drop -down menu in top right corner. Log in with username superadmin (password = superadmin) when doing the commissioning. All pages and fields are visible only for superadmin user group. Figure 10. Web page log in page Addressing the Routers for network: The Optimizer is connected from the port to the Router s Optimizer/Supervisor Port, see Figure 11. Routers default communication parameters for the port in a full mode are 38,400 baud rate, Even Parity, 1 Stop bit and address 1. Note that all Routers connected to network must have unique Modbus address and therefore the default address must be reviewed. To set the address, connect the computer to Router s Optimizer/Supervisor port. Use Modbus master software, such as Modbus Poll, to communicate to the Router. Write desired address to Router s holding register 51. If the address or the communication parameters is unknown, the Router can be set to the commissioning mode for a period of time by holding the Comm/ Reset button for 5 seconds. Supervisor port s Modbus communication parameters in the commissioning mode are 19,200 baud rate, Even Parity, 1 Stop bit and address 40. PE N L 24vac/dc GO/-G/+ GO/-G/+ Ethernet Alarm C 230vac/ In 24vac/dc 24vac/dc Output In Out Fire Free Cooling 230vac Power Supervisor Active Supervisor IPSUM Optimizer Air Handling Unit / Air Handling Unit SA Fan EA Fan Temp 0-10v 0-10v 0-10v Comm/ Ethernet Active A/+ B/- C SD Card Reset HMI Ethernet Active A/+ B/- C PE N L 24vac/dc GO/- G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc24vac/dc 1 In Out 230vac Power Ethernet 2 In Active Out PE N L 24vac/dc GO/- G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc24vac/dc 1 In Out 230vac Power Ethernet 2 In Active Out IPSUM Router IPSUM Router SD Card Comm/ Reset HMI Active A/+ B/- C Active A/+ B/- C SD Card Comm/ Reset HMI Figure 11. Optimizer to router TIA/EIA (RS)-485 Fläkt Woods 9403 GB We reserve the right to alter specifications.

12 PE N L 24vac/dc GO/-G/+ GO/-G/+ Ethernet Alarm C 230vac/ In 24vac/dc24vac/dc Output In Out Fire Free Cooling Ethernet 230vac PE N L 24vac/dc GO/-G/+ GO/-G/+ Ethernet Alarm C 230vac/ In 24vac/dc 24vac/dc Output In Out Fire Free Cooling 230vac Ethernet Active A/+ PE N L 24vac/dc GO/-G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc24vac/dc 1 PE N L 24vac/dc GO/-G/+GO/-G/+ In Out Ethernet 230vac/ In 24vac/dc 24vac/dc 1 230vac In Out 230vac C Active C SA Fan EA Fan Temp 0-10v 0-10v 0-10v Comm/ SD Card Reset HMI Ethernet SA Fan EA Fan Temp 0-10v 0-10v 0-10v Comm/ SD Card Reset HMI Ethernet Ethernet 2 Ethernet 2 SD Card SD Card Comm/ Comm/ Reset Reset HMI HMI Active Active A/+ B/- C Active A/+ B/- C Active Active In Active In A/+ C C B/-Out A/+ Out PE N L 24vac/dc GO/- G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc24vac/dc 1 In Out 230vac Ethernet 2 PE N L 24vac/dc GO/-G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc 24vac/dc 1 In Out 230vac SD Card Comm/ Reset HMI Active Ethernet In 2 Active SD Card Out HMI In PE N L 24vac/dc GO/-G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc 24vac/dc 1 Active In Out Out 230vac B/- Active A/+ B/- C Ethernet 2 SD Card Comm/ Reset HMI In Active Active A/+ B/- A/+ B/- B/- Active A/+ B/- C Active A/+ B/- C A/+ Comm/ B/- C Reset C Out Commissioning Ethernet The Optimizer can be connected directly to Routers by connecting the Ethernet port to the Router s Optimizer/Supervisor Ethernet Port, see Figure 12. The Optimizer will automatically set the addresses for the Routers. When the Routers are connected to an Optimizer only via ports, Shared TCP/IP Network (Admin -> ) should be inactivated (see Chapter 3.2). PE N L 24vac/dc GO/-G/+ GO/-G/+ Ethernet Alarm C 230vac/ In 24vac/dc 24vac/dc Output In Out Fire Free Cooling 230vac Power Supervisor Active Supervisor IPSUM Optimizer Air Handling Unit / Air Handling Unit SA Fan EA Fan Temp 0-10v 0-10v 0-10v Comm/ Ethernet Active A/+ B/- C SD Card Reset HMI Ethernet Active A/+ B/- C PE N L 24vac/dc GO/-G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc 24vac/dc 1 In Out 230vac Ethernet 2 In Active Out PE N L 24vac/dc GO/-G/+GO/-G/+ Ethernet 230vac/ In 24vac/dc 24vac/dc 1 In Out 230vac Ethernet 2 In Active Out Power Power IPSUM Router IPSUM Router SD Card Comm/ Reset HMI Active A/+ B/- C Active A/+ B/- C SD Card Comm/ Reset HMI Figure 12. Optimizer to Router, direct The Router can be also connected to the client/ private network, see Figure 13. The Router supports DHCP. When the Routers are connected to Optimizer also via client s Ethernet, Shared TCP/IP Network (Admin -> ) must be activated (see Chapter 3.2). Power IPSUM Optimizer Power Supervisor Supervisor Air Handling Unit Supervisor Air Handling Unit / Supervisor Client s ethernet BMS SCADA Ethernet IPSUM Optimizer Air Handling Unit / Air Handling Unit Power Power Power Power Power IPSUM IPSUM Router IPSUM Router IPSUM Router IPSUM Router Figure 13. Optimizer to Router, shared network Active Fläkt Woods 9403 GB We reserve the right to alter specifications.

13 3. Admin settings Admin settings are found on the ADMIN page. Admin settings define how different connections and external communication are is handled and what kind of permission Users and User Groups have. The Optimization Settings are also in the ADMIN area. Incorrectly set Optimization Settings can harm the ventilation system. For security and safety reasons, it is essential to check all the Admin settings. Note that not all admin pages and tabs are visible for all user groups. Figure 14. Admin tabs 3.1 General settings Set date by pressing calendar icon and time by pressing clock icon. (Fig 15) Clear Alarm Memory clears all alarms from the memory. Clear alarms from the memory when the commissioning is finished. Then the alarms tripped during the commissioning will not confuse users later. Figure 15. General settings view 3.2 setting mode is set in -tab. Default is Compact mode. No Routers are allowed when the mode is Compact. (Fig.16) The system mode can be changed by pressing pencil. This opens drop-down menu where the system mode can be selected. Figure 16. settings view Shared TCP/IP Network box will appear when Full (Up to 300 Slots) with Routers is selected and saved. (Fig.17) Shared TCP/IP network can be activated or inactivated by pressing the pencil. Select Inactive if the Optimizer is connected to Routers only via RS/ and/or directly. Then the Optimizer will not search for the Routers in the shared network during the scan. (Fig.18) Figure 17. Updating mode Figure 18. Full system mode view Fläkt Woods 9403 GB We reserve the right to alter specifications.

14 Set Shared TCP/IP network to Active when there are Routers in the same shared network as the Optimizer. The Optimizer will search for the Routers in RS/, direct network and shared network during the scan. (Fig. 19) Figure 19. Activating Shared TCP/IP Network 3.3 AHU Settings The Optimizer can be connected to an air handling unit via Modbus RTU, Modbus TCP or analogue signals. When the Communication Type is set to None, the air handling unit is controlled via analogue 0-10V signals. The analogue signals are always available despite the communication type selected. (Fig. 20) Figure 20. Air handling unit Communication view The Communication Type can be changed by pressing the pencil. This opens drop -down menu. Set correct communication type according to the system. (Fig. 21) After settings are done, use Test Communicationbutton to check the communication to the air handling unit. The test communication-button is visible if the communication type is not set to None. (Fig. 22) Figure 21. Changing Communication Type Figure 22. Test communication sequence Setting up eq, eql & eq Prime for Fläkt Woods eq, eql & eq Prime air handling units are ready to be used in the system directly. The integration just needs to be activated in the AHU menu as below. 1) Log in using the service password. (Contact Fläkt Woods support for service password) 2) Go to: Main Index -> Configuration -> Integrations -> IPSUM and change from No to Yes. 3) Scroll down to Reset required!! and restart the controller by changing it to Execute. Figure 23. Changing communication port (eq/eql/eq Prime) Communication between eq/eql/eq Prime and the Optimizer have options Ethernet and EIA/RS-485. Use EIA/RS-485 when the air handling unit is connected to the Optimizer port. The Optimizer uses the air handling unit s default communication parameters and are not changeable. (Fig. 23) Fläkt Woods 9403 GB We reserve the right to alter specifications.

15 When the communication port is selected to Ethernet, the network type can be selected to be Shared or Direct. (Fig. 24) Use Direct when the air handling unit is connected directly to the Optimizer s Air Handling Unit Ethernet port. Use Shared when both the air handling unit and the Optimizer are connected to the clients Shared Ethernet Network. IP-address or WINS name of the air handling unit is needed in the shared network type. (Fig. 25) Use IP-address only if the DHCP-server is set to give always the same IP-address to air handling unit. Use WINS name if the IP-address is not constant. Figure 24. Updating network type (eq/eql/eq Prime, ethernet) Figure 25. Setting up AHU IP/WINS 3.4 Building Management Settings The Supervisor port is where the BMS/SCADA connects to the Optimizer. The protocol can be Modbus RTU, Modbus TCP. Communitation protocols and communication parameters can be set easily via the web interface. The protocol is selected from the drop -down menus. Serial bus parameters are set on EIA/RS-485 subtab. Figure 26. BMS/SCADA-settings EIA/RS-485 view, Modbus/RTU The default communication parameters for Modbus RTU are address 69, Baud Rate, Even Parity and 1 Stop Bit (Fig.26). The parameters can be set by pressing the pencil next to fields. This opens Update settings-dialog box, from where the address, Baud rate and parity can be set. The number of stop bits is automatic set to be 1 when parity is selected to be even or odd. When the parity is selected to be none, number of the stop bits can be selected to be 1 or 2. (Fig. 27) Figure 27. Updating Modbus/RTU settings Fläkt Woods 9403 GB We reserve the right to alter specifications.

16 Network settings are located on Ethernet sub-tab. (Fig. 28) When DHCP is set to Active, the Optimizer will ask IP-address and other network settings from the network server. Modbus port is the only editable field on the left column when DHCP is set to Active. Change the Modbus port if the default port is blocked by the network administrator. When DHCP is set to Inactive, the user sets the network settings for the Optimizer. Pressing pencil next to values opens Update Settings-dialog box. The editable fields are IP-address, Subnet Mask, Gateway Address and Modbus Port. (Fig. 29) Figure 28. BMS/SCADA-settings Ethernet view It is possible to limit the devices on the network that the Optimizer responds to in both DHCP modes. Limitations are set to Allowed Master IP Address and Allowed Master Subnet Mask. (Fig. 30) Default setting are This means that the Optimizer will respond to requests from any IP address. Set the limitations if the Optimizer is in a shared network, if it is unwanted that all user from the network can communicate with the Optimizer. Figure 29. DHCP Inactive, updating settings Figure 30. Updating settings for allowed Master 3.5 Users/Groups User profiles are managed from the Users/Groups tab. The default users are seen in Figure 31. The default password for a username is the same as the username. Figure 31. Default usernames Fläkt Woods 9403 GB We reserve the right to alter specifications.

17 Last two columns in the table are for managing the users. Pencil opens Edit User-dialog box and Recycle bin opens Delete User-dialog box, see Figure 33. Change default passwords for all default users or remove the default usernames. A new user can be added by pressing Add Userbutton. This opens Add user-dialog box. Username, password, name and role are required for all users. (Fig. 34) Figure 32. Managing users Figure 33. User dialogs Figure 34: Add User Fläkt Woods 9403 GB We reserve the right to alter specifications.

18 4. Optimization settings The Optimizer can be set to control supply air temperature, supply air flow and extract air flow independently with minimal energy consumption while keeping a comfortable room climate. All settings can be easily adjusted from the web pages. Optimization settings are located on the ADMIN page under the Optimization tab. Figure 35. Optimization Settings in the web page 4.1 Settings for Pressure Optimization Pressure optimization is found in Admin -> Optimization Setting -> Pressure. The basic principle of pressure optimization is that checks for the opening of the blade from each damper in the system and determines the most open. The Optimizer calculates a new setpoint for an air handling unit based on the maximum opening, gradually making the most open damper correspond to the optimization setting. The pressure optimization has a linear optimization mode and a step optimization mode. The linear optimization is based on PI-algorithm. The step optimization is based on constant control steps after a constant waiting time. Linear Optimization mode is recommended. Linear optimization is more effective than step optimization, because a size and timing of the control action is not beforehand defined and I-term removes steady-state control error. Although, tuning of the linear optimization is more complex and with poorly chosen tuning parameters the system could become unstable. To achieve a stable and effective system, the optimization parameters need to be carefully selected. The values are dependent on the system where is installed. Default values are selected to be a safe choice for most applications, but for some applications, the response of the system may not be as fast as it could be. An unnecessary slow system is not using its entire potential and therefore not all possible energy savings are achieved, and thus fine tuning of the variables would be needed. The fine tuning of the control parameters is always a tradeoff between stability and speed. An oscillating control signal to air handling unit or an oscillating airflow from the air handling unit with unwanted high amplitude are clear indicators that the control needs to be slowed down. If the system is not oscillating and the optimization is not reacting fast enough to changing demands, then faster setup values may be required. On the next page is some more detailed information on the settings and the effects they can have. Figure 36. Updating pressure optimization function Fläkt Woods 9403 GB We reserve the right to alter specifications.

19 4.1.1 General settings Parameters presented in this Section are common for both Linear and Step mode. Communication to an air handling unit can be handled via analogue 0-10V signal or via serial communication. In the following, the term IO refers to analogue and Protocol refers to serial. Pressure function The Pressure Optimization function has the options inactive, linear and step. Inactive mode is the default mode. Startup Mode The startup mode has the options % and Pa. The default setting is Pa. Start Levels The Optimizer is constantly monitoring the system to determine if the air handling unit is running and the system is operating normally. This is done by calculating the totalised airflow from the system and by monitoring pressure of the pressure dampers. When the totalised airflow first exceeds the Start Flow Level or pressure exceeds Start Pressure Level, then and the Optimizer initiates Start-up mode. The variables are set to protect the system, Start Level prevents unwanted start-ups, and therefore the values should not be set to 0 and they must be above corresponding Stop Levels. Unit Pa Default 10 Range Unit l/s Default 40 Range Stopped Levels The Optimizer stops regulating when both the totalised airflow is below the value of Stopped Flow Level and pressure is below Stopped Pressure level. The values are dependent on the size of the system. The variables are set to protect the system. Otherwise, the control signal would increase to its maximum when the air handling unit is not running. The values should not be set to 0 l/s and they must be lower than corresponding Start Levels. Unit Stopped pressure level Pa Default 0 Range Unit Stopped flow level Default 0 l/s Range Startup Delay When the Optimizer goes to Start-Up mode, a timer will start. Until the timer reaches the value of Startup Delay, a constant Start up setpoint is sent to the air handling unit. After the timer goes above the delay, normal optimization begins. Start up delay should be longer than the time required for the air handling unit to reach the Start Up setpoints (see below). Otherwise unwanted oscillation might occur during the start-up process. Unit Seconds Default 600 Range Startup Protocol Setpoint / Startup IO Setpoint During the start up, the control value from the Optimizer to the AHU is kept at a constant Startup setpoint value. If you use protocol values then select Start-Up mode to Pa. Unit When start up mode = Pa Pa Default 50 Range If you use analog output then select Start-Up mode to percentage. When start up mode = % Unit % Default 20 Range The setpoint should be selected close to the nominal operation point. Selecting the setpoint close to the nominal operation point will reduce the time for the system to achieve a stable situation. Although, setting the exact Start up setpoint is not necessary. The will eventually reach the optimal operation point. Fläkt Woods 9403 GB We reserve the right to alter specifications.

20 Damper setpoint The Optimizer controls the air flow, so that an opening of the most open damper is equal to the Damper Setpoint. Energy efficiency can be increased by increasing the Damper Setpoint. However, high setpoint means less room to manage unexpected disturbances. Higher setpoint also means more fluctuation, because small changes in blade position at damper blade end positions will have less effect to the air flow than in the middle of damper blade range. Therefore, the system can be stabilized by reducing the Damper Setpoint. Recommended setpoint should not exceed 90%. Unit % Default 80 Range Protocol Setpoint Lower Limit The lower limit is the lowest pressure value [Pa] which the Optimizer will send to the air handling unit. The lower limit must be lower than the Upper limit and lower than the start-up setpoint. Unit Pa Default 10 Range The upper limit is the highest analogue value [%] which the Optimizer will send to the air handling unit. 0 % corresponds to 0V and 100 % to 10V. The default value is 100 %. Setting the Lower Limit to 20 % and the Upper limit to 80 %, the operation range of the analogue control signal will be 2-8V. Protocol Deviation and IO Deviation The protocol control signal will be updated only if a new control signal differs from the previous control value by more than Protocol Deviation. Unit of the Protocol Deviation is Pa. The default value is 1 Pa. The analogue control signal will be updated only if a new control signal differs from the previous control value by more than IO Deviation. Unit of the IO Deviation is percent of IO setpoint Lower and Upper Limits. The default value is 1 %. The deviation can be used to slow down the system and prevent the system constantly moving up and down. The size of the deviation is limited by the largest acceptable step of the control signal Linear Optimization Mode P-Gain and I-Gain are parameters of PI-algorithm. These are the parameters which have the most effect for stability and efficiency of the optimization. Separate values can be set for supply and extract air, and when air flow is increased or decreased. Fläkt Woods recommends that the parameters for increasing air flow are selected to be higher than for decreasing air flow. This allows the Optimizer to react more aggressive if a demand for the fresh air is increasing rapidly, and thus guarantee that there will be always enough fresh air. Protocol Setpoint Upper Limit The upper limit is the highest pressure value [Pa] which the Optimizer will send to the air handling unit. The upper limit must be higher than the lower limit. Unit Pa Default 3000 Range Protocol Deviation and IO Deviation The protocol control signal will be updated only if a new control signal differs from the previous control value by more than Protocol Deviation. Unit Protocol Deviation Pa Default 0 Range The analogue control signal will be updated only if a new control signal differs from the previous control value by more than IO Deviation. Unit of the IO Deviation is percent of IO setpoint Lower and Upper Limits IO Deviation Unit % Default 0 Range The deviation can be used to slow down the system and prevent the system constantly moving up and down. The size of the deviation is limited by the largest acceptable step of the control signal. The basic principle of the use of the Deviation is shown in Figure 37. The deviation is set to be 5 Pa and the limits are shown with red lines. A blue line is setpoint calculated internally in the Optimizer. First the calculated setpoint stays within the deviation limits and therefore a constant setpoint (150 Pa) is sent to the air handling unit. After a while, the calculated setpoint goes above the limits and that triggers the Optimizer to send a new setpoint to the air handling unit (156 Pa). Figure 37. Deviation Limits Fläkt Woods 9403 GB We reserve the right to alter specifications.

21 IO Setpoint Lower Limit The lower limit is the lowest analogue value [%] which the Optimizer will send to the air handling unit. 0% corresponds to 0V and 100% to 10V. The IO lower limit must be below IO upper limit and below IO start-up setpoint. Unit % Default 0 Range IO Setpoint Upper Limit The upper limit is the highest analogue value [%] which the Optimizer will send to the air handling unit. 0% corresponds to 0V and 100% to 10V. The IO upper limit must be higher than IO lower limit. Unit % Default 100 Range Example: Setting the IO Lower Limit to 20% and the IO Upper limit to 80%, the operation range of the analogue control signal will be 2-8V Linear Optimization Mode P-Gain and I-Gain are parameters of PI-algorithm. These are the parameters which have the most effect for stability and efficiency of the optimization. Separate values can be set for supply and extract air, and when air flow is increased or decreased. P-Gain P-term of the PI-controller is a proportional gain. The term is related to magnitude of the current error value. Increasing P-Gain will make the optimization to react more aggressively to changes in the system, but too high P-gain can make the system unstable. Supply air P-gain up default 250 P-gain down default 200 Range I-Gain I-term of the PI-controller is an integral gain. The term calculates cumulative error from magnitude and duration of the error. I-gain makes the control loop more accurate by removing a steady-state error. Increasing I-gain will remove the steady-state error faster, but the result might be higher overshoot and increase of settling time, and thus the system will be more unstable. Supply air I-gain up default 250 I-gain down default 200 Range Extract air I-gain up default 250 I-gain down default 200 Range Extract air P-gain up default 250 P-gain down default 250 Range Fläkt Woods 9403 GB We reserve the right to alter specifications.

22 4.1.3 Step Optimization Mode The Ramp Interval and IO step are tuning parameters of the step algorithm. These are the parameters which have the most effect on the stability and efficiency of the optimization. Separate values can be set for supply and extract air, and when air flow is increased or decreased. Ramp Interval When the time from the previous control action is more than the value in Ramp Interval, a new control action is made. Notice that keeping the control value the same is also a control action. The smaller the Ramp Interval is, the more often regulation is done and thus the faster the control reacts. However, if the Ramp Interval is smaller than time needed for the air handling unit and dampers to reach and stabilise to a new operation point, the system might become unstable. Unit Seconds Ramp up default 120 Ramp down default 180 Range IO step The IO step is a fixed size of a control action. The higher the IO step is, the faster the control reacts to varying demands. The highest step size is determined by the largest acceptable control action. If the IO step is selected to be too large, the system will start to fluctuate around the setpoint with unwanted high amplitude. Notice that if the IO step is higher than the IO deviation, the IO deviation is ignored. Unit % Default 5 Range Protocol Step Protocol step is a fixed size of a control action. The higher the Protocol step is, the faster the control reacts to varying demands. The highest step size is determined by the largest acceptable control action. If the Protocol step is selected to be too large, the system will start to fluctuate around the setpoint with unwanted high amplitude. Notice that if the Protocol step is higher than the Protocol deviation, the Protocol deviation is ignored. Unit Pa Default 5 Range Settings for Temperature Optimization The Temperature optimization is found under Admin -> Optimization Settings -> Temperature. The optimization can be selected active/inactive as required The basic principle of the Temperature Optimization is that monitors the cooling and heating demands from the system and calculates a totalized demand for those. Based on the totalized demand, the Optimizer adjusts a supply air temperature setpoint of the air handling unit and therefore minimizes the need for additional heating or cooling in the rooms. This can also reduce the required airflow to the rooms and thus reduce the fan energy even further. Figure 38. Updating temperature optimization settings In Figure 39 there is a simplified temperature control diagram. The temperature control has three operation areas. Each control point is determined by two adjustable variables Demand and Setpoint. The variables define amounts of the temperature compensation applied. Fläkt Woods 9403 GB We reserve the right to alter specifications.

23 The Neutral-zone is where no optimization is applied and is between Cooling start point and Heating start point. The Analogue output in the neutral-zone is 5V. The neural-zone is marked with a dashed line in the Figure. Heating Optimization starts when the totalized demand from the system is more than Heat Comp Start Demand. When the totalized demand is equal or more than Heat Comp Stop Demand, the control value is at its maximum. The Analogue output at its maximum is 10V. The temperature is adjusted linearly between these points. The area where the heating compensation is applied is marked with the red line in the Figure. Cooling Optimization starts when the totalized demand from the system is more than Cool Comp Start Demand. When the totalized demand is equal or more than Cool Comp Stop Demand, the control value is at its minimum. The Analogue output at its minimum is 0V. The temperature is adjusted linearly between these points. The area where the cooling compensation is applied is marked with a blue line in the Figure 39. Start Up Delay When the Optimizer engages Startup mode, a timer will start. Constant Startup setpoint is sent to the air handling unit until the timer reaches the value of Startup Delay. When timer exceeds, Startup Delay normal optimization begins. Startup delay should be longer that the time required for the air handling unit to reach the Startup setpoints (see below). Otherwise unwanted oscillation might occur during the start-up process. Unit Seconds Default 600 Range Heat Comp Start Demand and Heat Comp Stop Demand The Optimizer starts adjusting the temperature when the totalized heating demand is higher than Heat Comp Start Demand. The maximum compensation is achieved when the totalized demand is higher than Heat Comp Stop Demand. Notice that Heat Comp Stop Demand must be higher than Heat Comp Start Demand. Unit % Default start 60 Default stop 85 Range Figure 39. Temperature optimization Control diagram Startup Setpoint The output of the Optimizer temperature setpoint is kept in constant Startup Setpoint value until normal regulation starts. Startup Setpoint should be selected to be close to the normal operation point. This reduces the time needed to gain a steady system. The value must be set lower than Heating Compensation Start Temp and higher than Cooling Compensation Start Temp. Unit C Default 18 Range Cool Comp Stop Demand and Cool Comp Start Demand The Optimizer starts adjusting the temperature when the totalized cooling demand is higher than Cool Comp Start Demand. The maximum compensation is achieved when the totalized demand is lower than Cool Comp Stop Demand. Notice that Cool Comp Stop Demand must be higher than Cool Comp Start Demand. Unit % Default start 40 Default stop 75 Range Fläkt Woods 9403 GB We reserve the right to alter specifications.

24 Cool Stop Setpoint and Cool Start Setpoint Cool Start Setpoint determines the supply air temperature setpoint when the totalized demand is equal to Cool Comp Start Demand. Cool Stop Setpoint determines the supply air temperature setpoint when totalized demand is equal to Cool Comp Stop Demand. The temperature setpoint is adjusted linearly between the Start and Stop values. The values define the straight line between the points, and therefore define how much compensation is applied. The Analogue output is scaled such as Cool Start Setpoint is corresponding to 5V and Cool Stop Setpoint corresponds to 0V. Cool Stop Setpoint must be lower than Cool Start Setpoint. Unit C Default start 16 Default stop 12 Range Heat Comp Stop Setpoint and Heat Comp Start Setpoint Heat Start Setpoint determines the supply air temperature setpoint when the totalized demand is equal to Heat Comp Start Demand. Heat Stop Setpoint determines the supply air temperature setpoint when the totalized demand is equal to Heat Comp Stop Demand. The temperature setpoint is adjusted linearly between Stop and Start values. The values define the straight between the points, and therefore define how much compensation is applied. The Analogue output is scaled such as Heat Start Setpoint is corresponding to 5V and Heat Stop Setpoint corresponds to 10V. Heat Stop Setpoint must be higher than Heat Start Setpoint. Unit C Default start 22 Default stop 29 Range Fläkt Woods 9403 GB We reserve the right to alter specifications.

25 5. scan Next a Full system scan must be done. This will check the system and highlight any conflicts or errors with the communication, addressing, components used, components placement, etc. The Scan options are found by right-clicking the mouse on the Not configured item in the tree on the Overview tab, see Figure 40. The action is selected by left clicking the mouse on the desired option. Note that the Not configured will change to Home after the first full scan is made. Figure 40. Starting scan will show Scan results dialog after the system scan is finished. Check that all devices were found, fix possible errors and do scan again if any issues were found. The system is ready to be used if no errors are found and all devices are found from the system. Next see Operation & Maintenance manual for adapting the web view and using web page to adjust settings of the products installed to the system. Figure 41. Post Scan Results Fläkt Woods 9403 GB We reserve the right to alter specifications.

26 Notes Fläkt Woods 9403 GB We reserve the right to alter specifications.

27 Notes Fläkt Woods 9403 GB We reserve the right to alter specifications.

28 FWG-IPSUM Commissioning-GB GB Copyright 2014 Fläkt Woods Group WE BRING BETTER AIR TO LIFE IPSUM COMMISSIONING 9403GB With over a century of innovation and expertise to share with our customers, Fläkt Woods is a global leader in Air Technology products and solutions. We specialise in the design and manufacturing of a wide range of products and solutions for Air Movement, Air Treatment, Air Distribution, Air Management and Air Diffusion with focus on two major benefits Air Comfort and Fire Safety. With market presence in 65 countries we are in a unique position to be a local supplier and an international partner in our customer s projects. Our product brands such as SEMCO, eq, eq Prime, JM Aerofoil, Econet, Veloduct, Optivent, Optimix, Econovent and Cleanvent are well-known and trusted by customers all over the world to deliver high quality and energy efficient solutions.» To learn more about our offering and get in contact with your nearest sales representative please visit

IPSUM » CABLE GUIDE. IPSUM Optimizer IPSUM Connection unit IPSUM Router AIR COMFORT AIR MANAGEMENT IPSUM CABLE GUIDE

IPSUM » CABLE GUIDE. IPSUM Optimizer IPSUM Connection unit IPSUM Router AIR COMFORT AIR MANAGEMENT IPSUM CABLE GUIDE AIR COMFORT AIR MANAGEMENT CABLE GUIDE» CABLE GUIDE Optimizer Connection unit Router Fläkt Woods support: www.flaktwoods.co.uk See our global website for international support issues www.flaktwoods.com

More information

Super WISE Web Page Manual

Super WISE Web Page Manual Super WISE Web Page Manual Super WISE, program version 1.25 We reserve the right to make design modifications without prior notice. www.swegon.com 1 Contents Super WISE, program version 1.25... 1 Super

More information

Control systems. Efficient room control

Control systems. Efficient room control Control systems Efficient room control AIRCONTROL Efficient room control with X-AIRCONTROL Humidity Occupancy Increasingly demanding requirements on energy efficiency as well as the latest EU regulations

More information

Communicative controller for VAV systems

Communicative controller for VAV systems FCR015 Communicative controller for VAV systems Summary FCR015 is a communicative controller for heating and cooling panels and a VAV (variable air volume) damper. It measures temperature and CO 2 concentration

More information

SuperWISE Web Page Manual

SuperWISE Web Page Manual SuperWISE Web Page Manual SuperWISE, program version 1.14 1. General SuperWISE has a built-in web server that enables you to monitor, enter and change the settings on the various controllers in the WISE/Conductor

More information

Millennium Simplicity Elite Parameter Points and Quirks

Millennium Simplicity Elite Parameter Points and Quirks Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The

More information

CommandCenter Operator Panel

CommandCenter Operator Panel CommandCenter Operator Panel Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start

More information

STRA-17 Room controller. Installation and maintenance manual. Content

STRA-17 Room controller. Installation and maintenance manual. Content Content Installation preparations... Wiring diagram...3 Display handling...5 Technical data...6 Configuration...7 Operating modes...7 Controller modes...7 Activation operating modes...7 Control states...8

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide. MXM-50 Modbus Interface for Mitsubishi Air-Conditioning Installation and User Guide www.innon.co.uk 1. Product Overview The Black Pear MXM-50 unit allows a Modbus building management system (BMS) to monitor

More information

Installation Manual. DZK BACnet

Installation Manual. DZK BACnet Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...

More information

Control system for rotary heat exchanger EQRB, L=3,4

Control system for rotary heat exchanger EQRB, L=3,4 Installation instructions, drive system EQRB, L=3.4 sizes 005-072 General description A speed controlled drive system specifically adapted to drive rotary heat exchangers. No tuning is necessary. All control

More information

ATK3 I/O Module (Modbus Slave)

ATK3 I/O Module (Modbus Slave) ATK3 I/O Module (Modbus Slave) 2011-01-13 The ATK3 I/O Module by ElectroCom Table of contents 2011-01-13...1 The ATK3 I/O Module by ElectroCom...1 1 Hardware...2 1.1 Inputs...3 1.2 Outputs...3 1.2.1 Relay...3

More information

HLS34 Modbus FCU/VAV Controllers installation instructions

HLS34 Modbus FCU/VAV Controllers installation instructions HLS34 Modbus FCU/VAV Controllers installation instructions The HLS34 is specifically designed for individual room temperature and zone control applications. The controllers have built-in RS-485 channel

More information

Modbus for FICO, slave mode General Engineering Guide

Modbus for FICO, slave mode General Engineering Guide Modbus for FICO, slave mode General Engineering Guide 1/16 Contents 1 About this Document...3 1.1 Foreword...3 1.2 Notes on Use...3 1.3 Symbols and Abbreviations...3 1.4 Revision History...3 2 General...4

More information

Product startup: G-30 + DIGIWARE C31 - U30-3xI35

Product startup: G-30 + DIGIWARE C31 - U30-3xI35 Product startup: G-30 + DIGIWARE C31 - U30-3xI35 Date: 26/09/2014 From: ADY Verified by: To: All Copy to : The purpose of this document is to explain the setup steps in "point to point" mode or via a Diris

More information

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018 Installation Instructions February 12, 2018 OCI415.30 for use with LMV5... Linkageless Burner Management Systems OCI415.30 Description The OCI415.30 provides the LMV5... family of flame controllers with

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or

More information

CONDUCTOR W4. Installation instruction for W4.1 and W To mount the controller. Controller. Mounting on a DIN rail

CONDUCTOR W4. Installation instruction for W4.1 and W To mount the controller. Controller. Mounting on a DIN rail CONDUCTOR W Installation instruction for W. and W. 00 Controller To mount the controller. Mounting on a DIN rail Figure. Overview of the Controller. Pos. Product marking. Pos. Termination resistance. =

More information

EN TECHNICAL MANUAL. Technical manual for programming Serial Bridge Art

EN TECHNICAL MANUAL. Technical manual for programming Serial Bridge Art EN TECHNICAL MANUAL ON 1 2 3 4 5 6 Technical manual for programming Serial Bridge Art. 20003101 www.comelitgroup.com INDEX Accessing the device for the first time... 2 Description of the interface... 3

More information

METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Metasys N2 open Metasys nodes contains up to 256 Virtual Objects. These virtual objects can be either

More information

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS 100275719_2000534455_Rev A MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Power-Fin Models: 2500-5000 WARNING This manual must only be used by a qualified heating installer / service technician. Read all

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication X X testregistrierung Control system Type Central BMS interface DCP-FSL II-Stand-alone Pressure independent control valve Straight-way valve Modular, stand-alone room control system, specially for decentralised

More information

Heatmiser Netmonitor v3

Heatmiser Netmonitor v3 Heatmiser Netmonitor v3 Technical Set-Up (Firmware Version 3.5 or above) Function Page Number Connecting to your Netmonitor 2 Changing the Netmonitor IP address 4 Accessing the Netmonitor over the Internet

More information

ETH044-4 SSR (230VAC) and 4 Digital IO

ETH044-4 SSR (230VAC) and 4 Digital IO ETH044-4 SSR (230VAC) and 4 Digital IO Technical Documentation WARNING Mains Voltages can be Lethal. If you are not confident with using these voltages, please use a qualified electrician to wire this

More information

Installation, operating and maintenance ADALINK II. Web solution for LENNOX units supervision ADALINK II-IOM-1401-E. lennoxemeia.

Installation, operating and maintenance ADALINK II. Web solution for LENNOX units supervision ADALINK II-IOM-1401-E. lennoxemeia. Installation, operating and maintenance ADALINK II Web solution for LENNOX units supervision ADALINK II-IOM-1401-E lennoxemeia.com CONTENT 1 INTRODUCTION 1.1 - ADALINK II system description... 3 2 INSTALLATION

More information

M2500 Engine Controller Configuration Manual

M2500 Engine Controller Configuration Manual M2500 Engine Controller Configuration Manual Revision: 08-04-2011 Page 1 Contents 1 Preface... 4 2 Configuration from front panel... 5 2.1 Engine Controller Configuration... 6 2.1.1 RPM settings... 6 2.1.2

More information

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Control MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions CONTENTS Page

More information

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS 1 25 95 00 Integrated Automation Control Sequences for HVAC GENERAL The HVAC operational sequences in this guideline are commonly used by Duke University. They are being provided as a preferred design

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Login for the first time, please use http://192.168.1.100 To key in user name and password is for identifying authorization. Default

More information

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel :

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : IQ-MP Gateway Version 4.009 28. apr. 2011 Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : +45 8880 7580 www.electrocom.dk p. 2 Description The IQ-MP Gateway is a communications module, which

More information

System Controls Suggested Specification

System Controls Suggested Specification 1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall

More information

Using the LR-HVAC-230-S Thermostat w/ HomeWorks QS

Using the LR-HVAC-230-S Thermostat w/ HomeWorks QS Using the LR-HVAC-230-S Thermostat w/ HomeWorks QS 1.0 Overview Fan coil unit (FCU), split system, and radiant floor systems are commonly used for Heating, Ventilation, and Air Conditioning (HVAC). With

More information

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

Version 1.0c May 6, 2010 ATK3

Version 1.0c May 6, 2010 ATK3 Version 1.0c May 6, 2010 ATK3 Contents 1 Hardware 2 1.1 Inputs............................... 2 1.2 Outputs.............................. 3 1.3 RS485............................... 3 1.4 Ethernet..............................

More information

IP WEB User Manual V2.0

IP WEB User Manual V2.0 IP WEB User Manual V2.0 Please read carefully before installing or contacting your supplier. The information contained at the time of printing is correct, but is subject to change without notice. This

More information

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Service Bulletin SB685 Date: 8/18/2017 Subject: TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Units: All TriPac EVOLUTION Summary: This bulletin updates and

More information

Deseo KNX Manual. Deseo KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium. 1 / 65 v basalte

Deseo KNX Manual. Deseo KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium. 1 / 65 v basalte Deseo KNX basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium 1 / 65 v2.3 2012 basalte Table of contents: 1. Introduction... 5 2. Installation... 6 2.1 Identifying the parts... 7 2.1.1 Front view

More information

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide VxI Power Ltd. IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide 01/12/2015 Document Number: 14970-020A Issue Number: 2 Contents 1.0 Device Overview... 2 2.0 Getting Started... 3 2.1 Connecting the Device...

More information

Operating Instructions

Operating Instructions 33CS Comfort System Software CONTENTS Page GENERAL...1 OPERATION...1-11 Start-Up...1 Main Menu...2 CURSOR MOVEMENT AND FUNCTION SELECTION Initial Setup and Configuration...3 BASIC MODE EXPERT MODE MODEM

More information

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng IntesisBox MAPS Configuration & monitoring software of IntesisBox KNX series User's manual Issue Date: 06/17 r1.0 eng Intesis Software S.L.U. 2017 All Rights Reserved. Information in this document is subject

More information

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation.

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation. Embedded Modbus TCP Module GS11-MT User Manual REV 1.1 SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 About the Embedded Module... 4 1.1 General...4 1.2 Features... 4 1.3 Specifications...4

More information

USER S MANUAL. DAS-G01 The Power of Tomorrow

USER S MANUAL. DAS-G01 The Power of Tomorrow USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 0 USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 Page 1 USER'S MANUAL TABLE OF CONTENTS Page # 1.0 GENERAL INFORMATION...

More information

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC Installation Instructions Procon BAC-A/50 MITSUBISHI ELECTRIC BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc.) 1. Product

More information

RGX COMMUNICATIONS GATEWAY

RGX COMMUNICATIONS GATEWAY RGX COMMUNICATIONS GATEWAY BTU Ventilation Corporation 47418 US Highway 10 Perham, Mn 56573 USA Phone (218) 346-7482 Fax (218) 346-7485 http:/// Manual ver 2.1 Copyright BTU Ventilation Corp 2008 RGX Communications

More information

Domino DFWEB. DFWEB: interface module between Domino bus and Ethernet network with Web-Server function. Module Connection. Domino

Domino DFWEB. DFWEB: interface module between Domino bus and Ethernet network with Web-Server function. Module Connection. Domino : interface module between bus and Ethernet network with Web-Server function module has been developed to be used in all applications of system where it is required to control the domotic system through

More information

Appendix C: HVAC PRO Modules

Appendix C: HVAC PRO Modules FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix C: HVAC PRO Modules HVAC PRO Modules...3 Introduction...*3 Key Concepts...*4 ABS VALUE... 6 ADD... 6 ANALOG OUTPUT... 6 AND...

More information

Control engineering information VARYCONTROL VAV Units VAV Compact flow rate controller BC0 BF0

Control engineering information VARYCONTROL VAV Units VAV Compact flow rate controller BC0 BF0 Control engineering information VARYCONTROL VAV Units flow rate controller BC0 BF0 The art of handling air Contents 1 General information 3 Correct use 3 Materials 3 Maintenance 3 2 Field of application,

More information

AP-ENBD User Manual V0.2

AP-ENBD User Manual V0.2 AP-ENBD User Manual V0.2 2015/12 Catolog Catolog... 2 1 Introduction... 1 1.1 Communication Structure... 1 1.2 Internal Principle... 2 2 Installation... 2 2.1 Connect to the Same Router (or Switch )...

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS FB-MODB_100161012_2000020084_Rev L MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Crest Models: 751-6000 WARNING This manual must only be used by a qualified heating installer / service technician. Read

More information

Modbus Communication Tool. User manual

Modbus Communication Tool. User manual Modbus Communication Tool User manual 08/2015 1 Contents 1 Contents... 2 2 Introduction... 3 3 Hardware configuration... 3 4 Login, channel configuration... 4 4.1 Communication settings... 5 5 Module detection...

More information

FOCUS GUIDE NETWORK CONTROLLER. Configuration Guide for ProLon Focus Software

FOCUS GUIDE NETWORK CONTROLLER. Configuration Guide for ProLon Focus Software FOCUS GUIDE NETWORK CONTROLLER Configuration Guide for ProLon Focus Software www.proloncontrols.com info@proloncontrols.com 17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV. 6.2.0 PL-FOC-NC-C/F-EN

More information

CS2000 Automatic control V3 Quick Guide

CS2000 Automatic control V3 Quick Guide 112626E-03 2017-09 CS2000 Automatic control V3 Quick Guide ! All electrical connections must be made by an expert. 2 Contents! This quick guide only applies to software version V3.x To view current software

More information

Efficient. Innovative. Sustainable.

Efficient. Innovative. Sustainable. Efficient. Innovative. Sustainable. Controlesta RCO System Description On-line, at each time, at each place 1 CONTROLESTA RCO System Description 1. System architecture 2.1 Master Controller 2.2 Network

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

F4T Touch Screen Controller Cascade Control Addendum

F4T Touch Screen Controller Cascade Control Addendum F4T Touch Screen Controller Cascade Control Addendum Revision 3.06 and higher Firmware TestEquity LLC 6100 Condor Drive Moorpark, CA 93021 Support: 877-512-3457 Toll Free 805-480-0638 Corporate: 800-732-3457

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

RoomMaster ABR-2. Commissioning

RoomMaster ABR-2. Commissioning Commissioning Content GENERAL Locking of operating mode keys...3 Control panel...3 Function of operating mode keys, operating menu...3 Activation of setting keys...4 Locking of setting keys...4 Setting

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features...

More information

Conquest Ethernet Controller Configuration Web Pages

Conquest Ethernet Controller Configuration Web Pages Conquest Ethernet Controller Configuration Web Pages Application Guide Contents Introduction...1 Login Window...2 Device Window...3 Security Window...4 Application Windows...5 Firmware Update Window...6

More information

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012 GEM-10 GPRS/Modbus Gateway User Manual Rev 1.04 05/2012 1.Introduction 1.1 General Features ENTES GEM-10 GPRS/Modbus Gateway allows you to connect to your devices which communicate using Modbus protocol

More information

Modbus TCP/RTU MP-Bus converter

Modbus TCP/RTU MP-Bus converter R060 Modbus TCP/RTU MP-Bus converter Summary R060 is a Modbus RTU / RS485 and Modbus TCP to Belimo MP-Bus converter for control of up to 8 communicative Belimo actuators. Application control and diagnostics

More information

Elotech Standard Protocol. for Single R8200 SC

Elotech Standard Protocol. for Single R8200 SC Elotech Standard Protocol interface description / network protocol for Single R8200 SC ELOTECH Industrieelektronik GmbH Verbindungsstraße 27 D - 40723 HILDEN FON +49 2103 / 255 97 0 FAX +49 2103 / 255

More information

ES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4

ES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4 Controller Instruction 1 General information ES 4000 STANDARD Printed Matter Number : 2946 7002 09 Applicable to : MB compressors Preliminary Operations: : Safety Instructions : General Persons Required

More information

P-Bus Gateway Firmware

P-Bus Gateway Firmware P-Bus Gateway Firmware PBGW2.128 Version 1.40 Easy configuration with web interface (HTML) P-busses configurable separately in master or slave mode Status display of each P-bus Fixed IP address or dynamic

More information

MLM Integration with BMS Network Protocols

MLM Integration with BMS Network Protocols MLM Integration with BMS Network Protocols The Master Comms Unit 2 (MCU) serves as a gateway to other BMS protocols such as Lontalk or BACnet. The MCU features four diffuser data channels with a capacity

More information

McQuay VAV System Controller

McQuay VAV System Controller Operation Manual OM 1092 Group: Controls Part Number: OM 1092 Date: September 2010 Supersedes: New McQuay VAV System Controller For the McQuay Delivered VAV System 2010 McQuay International Table of Contents

More information

Building Management Systems (BMS) Back to Basics. Presented By: Andrew Smith Leader Building Technologies A.G. Coombs Advisory

Building Management Systems (BMS) Back to Basics. Presented By: Andrew Smith Leader Building Technologies A.G. Coombs Advisory Building Management Systems (BMS) Back to Basics Presented By: Andrew Smith Leader Building Technologies A.G. Coombs Advisory Back to Basics. 1) What is a Building Management System (BMS)? 2) Typical Components

More information

M1000 INTELLIGENT ZONE CONTROL SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3

More information

ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide MODBUS D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 www.onicon.com sales@onicon.com 03-18 0657-9

More information

Installation and Operation Instructions

Installation and Operation Instructions 33ZC ComfortID Test and Balance Tool Software Installation and Operation Instructions Part Number 33ZCBAL-SA INSTALLATION The ComfortID Test and Balance Tool software requires no special installation.

More information

RC-SV Configuration Guide (Rev 4)

RC-SV Configuration Guide (Rev 4) Kramer Electronics, Ltd. RC-SV Configuration Guide (Rev 4) Software Version 2.1.2.69 Intended for Kramer Technical Personnel or external System Integrators. To check that you have the latest version, go

More information

Generic SCADA System. User manual. Ovak Technologies

Generic SCADA System. User manual. Ovak Technologies Generic SCADA System User manual Ovak Technologies 2017 Table of contents 1. List of abbreviations... 3 2. Terms and Definitions... 3 3. Overview... 4 4. Web GUI... 5 4.1. Authentication window... 5 4.2.

More information

E3xA, E3xB, E3xC, E3xE

E3xA, E3xB, E3xC, E3xE ZL0140-0C Page 1 of 21 2017 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0717 Commissioning Guide Power Monitoring E34E E31 * E30E & E31E E34A E30 *The CE mark indicates RoHS2

More information

Multi-purpose Manager Installation

Multi-purpose Manager Installation Multi-purpose Manager Installation Installation Guide for MPM-UN, MPM-GW and MPM-VAV MPM-UN MPM-VAV MPM-GW MPM Installation Guide 2 WHO SHOULD READ THIS GUIDE This guide is for integrators of SmartStruxureTM

More information

AHU Solutions Programmable controllers for air handling units

AHU Solutions Programmable controllers for air handling units AHU Solutions Programmable controllers for air handling units PN 04/17 APRIL Function blocks for an easy and immediate customization of the application Fast and intuitive composition of the unit via dedicated

More information

May 2016 Version 1.2.7

May 2016 Version 1.2.7 May 2016 Version 1.2.7 2 Introduction Copyright Copyright 2016 4RF Limited. All rights reserved. This document is protected by copyright belonging to 4RF Limited and may not be reproduced or republished

More information

RMX 1500 Quick Installation & Configuration Guide

RMX 1500 Quick Installation & Configuration Guide RMX 1500 Quick Installation & Configuration Guide General Safety Precautions Follow these rules to ensure general safety: Keep the area around the Polycom RMX 1500 unit clean and free of clutter and well

More information

Room controller STRA-17

Room controller STRA-17 Room controller STRA-17 Application example Room 2 Room 3 Room 4 SCADA EXOline alt. RS485 Modbus Transformer STRZ-24 (Required component) STRA-17 is a preprogrammed room controller intended to control

More information

Energy Client. Version Feb Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel:

Energy Client. Version Feb Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel: Energy Client Version 2.0.806 3. Feb. 2014 Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel: +45 88 80 75 80 www.electrocom.dk p. 2 Introduction... 3 Installation... 4 LED, Switches and Reset...

More information

Sound Manager 2 User Guide

Sound Manager 2 User Guide Sound Manager 2 User Guide Version 1.8.4 September 27 th, 2016 OVERVIEW 2 USER OPERATION 3-6 LOGIN SCREEN 7 OPTIONAL STEP 8-10 MAIN MENU 11 DEVICES TAB 11 ZONE TAB 12 EQ TAB 13 SOURCES TAB 14 SYSTEM TAB

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

MODEL CIO-EN PROGRAMMING GUIDE MODBUS/TCP, MODBUS/RTU I/O MODULE. Revision A1 Rapid City, SD, USA, 09/2008

MODEL CIO-EN PROGRAMMING GUIDE MODBUS/TCP, MODBUS/RTU I/O MODULE. Revision A1 Rapid City, SD, USA, 09/2008 PROGRAMMING GUIDE MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE Revision A1 Rapid City, SD, USA, 09/2008 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605)

More information

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above TECHNICAL BULLETIN Part #: 026-4122 Revision 0 Date: 2/5/2007 Control Techniques Variable-Speed Drive (VSD) Interface to E2 v. 2.40 and Overview Beginning with version 2.40, the E2 RX, BX, and CX series

More information

For more information Contact with details of the application.

For more information Contact with details of the application. Eaton Corporation Telecommunications Power Solutions Email: dc.info@eaton.com www.eaton.com/telecompower Application Note AN0107 SC200 Modbus Server Last updated 20 January 2017 Applicable products SC200

More information

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2 NET101 RS232 / RS422 / RS485 to Ethernet Converter User s Manual Version 1.2 Copyright Information Copyright 2004-2005, Mega System Technologies, Inc. All rights reserved. Reproduction without permission

More information

The Simply Smart Way to Optimize Building Control and Performance

The Simply Smart Way to Optimize Building Control and Performance Connected Buildings ComfortPoint Open Building Management System The Simply Smart Way to Optimize Building Control and Performance For Consultants and Specifiers ComfortPoint Open BMS. Simply Smart. Honeywell

More information

Modbus RTU Serial / Modicon Serial Device Driver Guide

Modbus RTU Serial / Modicon Serial Device Driver Guide Modbus RTU Serial / Modicon Serial Device Driver Guide Version 4.5 rev 3 Broadwin Technology, Inc. page 1-1 Table of Contents Modbus RTU Serial / Modicon Serial Device Driver Guide 1-1 1. Modbus RTU Serial

More information

BACnet FF Configuration Wizard Guide

BACnet FF Configuration Wizard Guide BACnet FF Configuration Wizard Guide TABLE OF CONTENTS SYSTEM ENGINEERING GUIDE INTRODUCTION... 3 WEBStation-AX... 3 Features... 3 BACnet FF Configuration Wizard... 3 BACnet FF Configuration Requirement...

More information

FOCUS GUIDE VAV ZONE CONTROLLER. Configuration Guide for ProLon Focus Software

FOCUS GUIDE VAV ZONE CONTROLLER. Configuration Guide for ProLon Focus Software FOCUS GUIDE VAV ZONE CONTROLLER Configuration Guide for ProLon Focus Software www.proloncontrols.com info@proloncontrols.com 17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV. 6.2.0 PL-FOC-VAV-C/F-EN

More information

BMS Interface for Panasonic Air-Conditioning

BMS Interface for Panasonic Air-Conditioning BMS Interface for Panasonic Air-Conditioning Installation and User Guide www.microtrol.co.uk BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning

More information

DOC. #TD /20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide

DOC. #TD /20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide DOC. #TD-0465 10/20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide Logic One, Lingo, and iscope are registered trademarks of Novar. Ethernet os a registered trademark of Xerox Corporation.

More information