Isolation of Electrical Energy Guidance

Size: px
Start display at page:

Download "Isolation of Electrical Energy Guidance"

Transcription

1 Page 1 of 8 i ii Isolation of Electrical Energy Guidance 1. Scope 1.1. This document provides guidance on the various methods of isolation of electrical energy and highlights some (not all) of the limitations of these methods and the equipment typically in service at Dow facilities. These guidelines DO NOT address the training requirements, skill requirements, electric shock hazards, arc flash hazards or PPE requirements to perform any task or activity mentioned herein. For electrical safety requirements refer to the Global Electrical Safe Work Standard This document will also address Isolation of Electrical Energy where electrical energy is converted to mechanical energy and where the mechanical energy is of the primary concern. The typical example here is an electric motor application where the driven equipment or mechanical equipment requires the isolation i.e. electrical work is not being performed Other parts of the document will also provide additional guidance where an electrical task or work is required. In all cases, the Isolation of Energy Standard (IEOS) applies. 2. Introduction 2.1. First and foremost when isolating energy on any system or piece of equipment, practice Leadership and Engagement as follows: 2.2. Make it Personal Know what you are isolating and why you are isolating it Review the Safety Electrical One-Line Diagram (SEOLD) and/or equipment schedules. Look for the electrical sources and isolation devices to be used. Equipment labels and SEOLD equipment labels need to be the same. Look at the one-line diagram and make sure the drawing has been recently updated before initiating any isolation activity If you have a visible air gap or other confirmed isolation, stop and think about what could lead to the sudden disappearance of the air gap or loss of that isolation (stored energy devices, some parts of control power remaining that can reactivate the circuit, etc). Note that confirmation that an isolation switch is off or even if there is a visible air gap is not the same thing as confirmation of isolation. Test before touch is required for electrical work and a try test or observance of a visible gap local to the equipment is required for mechanical work. Do not proceed until you are absolutely confident that the isolation is confirmed and cannot be compromised (Prevention of compromise of the isolation is typically accomplished by mechanical restraint or by rendering the operator non-functional) Ask open ended questions Ask the person you are isolating this equipment for, what they are going to be doing, and how they will be doing the work safely. Ask probing, open ended, questions such that the person must clearly explain their

2 Page 2 of 8 work and boundaries. If you do not feel they understand what they are doing, stop the job, assess and escalate as appropriate Create and foster and environment where everyone can ask questions. When you are isolating a system or piece of equipment, encourage questions from the person you are isolating it for. Create an environment where the person feels comfortable asking you such questions about how you are going to clear the equipment for their safety Escalate If there is anything you do not feel comfortable in isolating, then stop and escalate. If you do not trust the one-line diagram, you feel rushed, feel uncertain about what you are doing, or you feel the individual you are performing the isolation for is rushed, uncertain, etc., then stop and escalate. 3. Identifying the equipment 3.1. The most critical item when dealing with electrical energy isolation is correct equipment identification The electrical isolation device (switch, circuit breaker etc) and the associated equipment (load) being isolated must have unique and easily reconcilable identifiers linking their operation. If at any time, the labeling of the equipment is ambiguous or the identification of the equipment is unknown, stop the isolation process until you have a clear understanding. Refer to EMETL G7M to determine the isolation device identification Avoid the use of the same or confusing equipment identifications within the facility. When performing and validating the isolation be sure to read equipment labels/ids/tag Numbers carefully, write them down and compare both the ID of the isolation device and the equipment/circuit being isolated. As required by the IOES standard at least two people (typically this is the Facility Representative and the Job Representative), must agree on the equipment identification when performing and validating the isolation. If needed, follow the MOC process and label equipment with unique equipment identifiers Knowledge of key interlock (Kirk Key or similar) systems. Some systems rely on these key interlock systems to force a particular sequence of operation as part of isolating electrical equipment. Procedures must exist and shall be followed explicitly when operating these key interlock systems. If you do not have a procedure or do not understand what the procedure is indicating, stop and escalate. 4. De-energize, Tag and Try of electrical energy sources 4.1. De-energize, Tag and Try has proven an acceptable and effective method of isolation of electrical energy for non-electrical work. However, understanding the limitations outlined in the following, is important: 4.2. Interlocks and control circuits cannot be the primary means of isolating any equipment. Mechanical isolation means must be used. This is a minimum IOES requirement Proper identification of the equipment is always required.

3 Page 3 of Be cautious and questioning when verifying de-energization, tag and try method after an equipment trip. Fuses can blow, overload relays can operate, circuit breakers can trip that will turn power off to the load. These devices must be reset or fuses replaced to actually validate the try step. Failure to do so, in conjunction with any equipment ID confusion may lead to improper isolation of electrical energy Equipment (typically motors) with computer/plc control may have permissives in control circuits that make it more difficult to perform the try test. Sometimes these systems may not have a field switch or the field switch function is Auto- Off only. In these circumstances, the following options can be considered: Install a field switch that has Hand (Jog) Off Auto position, where a spring loaded Hand(Jog) position wired to bypass permissives and computer control Install an isolation device (such as a motor safety switch or local motor disconnect) at the equipment. This allows for local visual inspection of isolation and better certainty that the equipment is isolated. Application of this method requires confirmation with appropriate SMEs and documentation that the local switch isolation is confirmed in this case to be the equivalent of a try test Local safety switches with factory installed viewing windows offer an effective method for external non-contact confirmation of a visible air gap when this gap is required for electrical isolation Where applicable, local isolation switches must meet the requirements of IEC Develop and use TRY procedures to identify the permissives (computer/plc inputs and outputs) that are to be overridden or place in manual as part of the try. This would be considered a critical procedure and will require consultation with plant process control focal points For non-electrical work, these key steps that must be included into the facility Try procedure/process for equipment that is currently operating: Two people (Facility Rep and Job Rep typically) are required to identify the equipment and associated isolated devices. The identification of isolation device, motor/equipment, field control switch, and or other controllers must match. Use your SEOLD, MCC data sheets, panel schedules, etc. as needed Use the identified field control switch or process control logic; stop the motor/equipment Isolate red tag and/or lock out the identified isolation device(s) Attempt to start the identified motor/equipment with the field switch or process control computer. Do not proceed if equipment starts. Contact an Electrical Skilled Person to help in identifying the correct isolation device (See G7M ) Some process equipment may not be capable of the try process due to material plugging or physical damage. Performing the electrical test before

4 Page 4 of 8 touch by an Electrically Skilled Person (ESP) or Electrically Instructed Person (EIP) is an accepted practice if all starter isolation devices are locked out / tagged out in accordance with IOES Some US Plants have installed specialty voltage indicating devices and have demonstrated effective alternate try procedures for verifying isolation of energy for mechanical work. For application assistance in this area, please contact a member of the GESMN. 5. Isolation Device Limitations 5.1. Isolation devices for electrical equipment are mechanical devices and are subject to failure. The operators for most isolation devices are located externally to the equipment. The actual isolation device is typically within the enclosure with a mechanical linkage between the external operator and the electrical contact part of the isolation device (typically a switch or circuit breaker) 5.2. Being familiar with the operation of these devices is essential. Use your senses to feel and hear the operation of the device. You should feel resistance when operating the device. You should hear and feel a click or noise when the switch/cb operates. If you are not sure how the devices should feel or sound, get with your Facility Electrical Representative (FER) and practice on a spare de-energized piece of equipment. You should suspect a mechanical failure of the operator if you do not get the usual feedback from the operation. The key message here is that just because the operator is in the off position does not mean that the circuit is off or isolated Likewise, do not trust your senses explicitly and assume the device operated properly when you hear the click or feel resistance. The switch or CB itself can also fail mechanically. For example: The device may break and open only 2 of the 3 phases. The circuit is still energized, but 3 phase motors will not turn under this condition The device may break and open only 1 of the 3 phases. The circuit is still energized, but 3 phase motors should not start from zero speed under this condition Another good indication that the isolation device operated is that indicator lights, meters, metering etc. should go off/out when the device is turned to the off position Some local isolation practices require confirmation of a visible air gap for electrical work. For NEMA/ANSI type equipment, open the equipment door (if not provided with a window) and inspect the CB or switch. The CB should be in the OFF position or all knife blades or contacts of the switch should be visibly open i.e. air gap. Caution! Opening electrical equipment doors may be energized electrical work. Additional PPE may be required and ESP/EIP qualifications are required For IEC low voltage MCC s, the blades or contacts of the switch cannot normally be seen. Typically, a mechanical indicator of the breaker/switch position is visible from outside the cabinet.

5 Page 5 of After the internal visual inspection, close the door and apply locks/red tags as needed. If a deficiency is found contact your Electrical Skilled Person (ESP) for resolution/repairs Some low voltage MCCs are designed with the isolation device handle mounted to the enclosure door. Once the isolation device has been switched off and locked in the off position, the door is mechanically held captive and cannot be opened. For work in this enclosure, a red tag cannot be applied and the work must be performed as Energized Electrical Work. If the work location needs to be left unattended for any reason, the door must be secured, the circuit deenergized and Red Tagged by operations Other LV MCCs are also designed with the isolation device handle mounted on the enclosure door but can be opened when switched off by defeating the mechanical interlock. For this type of equipment, opening the door while Red Tagged is considered a violation of the IOE Standard. If work is required inside the enclosure the following two options are allowed: Use the Red Tag addendum process to temporarily remove the tag or Reconcile the red tag and use the Electrical safe Work Standards to complete the task 5.9. Many LV panel boards have a dead front guarding that protects a worker from contacting exposed and energized components. Some of these panels also have breaker locking mechanisms that are integral to this cover. If a single or multiple breakers are Red Tagged and locked using a device that relies on the cover being in place, removing this cover is a violation of the IEO Standard. The only three options are: Use the red tag addendum process to temporarily remove and relocate the tag or Reconcile the locks and tags and use the Electrical Safe Work Standards to complete the work If the breakers are Red tagged only, and the tag can slip through the breaker opening in the cover, the cover can be removed as long as the circuit that remains tagged is not disturbed and the tag remains visible. 6. Molded Case Circuit Breakers (MCCB) 6.1. MCCBs are totally enclosed, often non removable and one cannot see the electrical contacts within. They are typically utilized at low voltages (up to 690V) principally as a short circuit and/or over-current protection means. In some cases, depending on the design standard the MCCB complies with, it can be suitably used as an isolating device (e.g. if the device is recognized as suitable for isolation in accordance with IEC or other industry standards) MCCBs being enclosed, as such the try part of De-energize, Tag and Try and ID of the equipment is critical for non-electrical work For electrical work behind an MCCB, some EIP or ESPs may require establishment of an air gap, particularly at voltages above 300 volts. This typically requires load side cable removal, which may be undesirable for several reasons. Some alternates to this are discussed below:

6 Page 6 of For electrical work behind a MCCB, one potential alternative to establishment of an air gap is to attach a Personnel Protective Ground (PPG) per the strict requirements in EWP-33 on the load circuit. The PPG can be thought of as similar to a bleed valve on a piping system and will divert hazardous electrical energy to ground in the event of inadvertent reenergization. Any PPG used in this fashion must be red tagged since it is being used as an isolation device. Attachment of PPGs to circuits downstream of smaller MCCBs, in many cases, is impractical The isolation device upstream of the MCCB may be used if any doubt exists on proper function of the MCCB. This may also cause electrical outages to other equipment A MCCB in a control panel will sometimes feed a series of fuses/fuse blocks for distribution of associated circuits within or external to the panel. In these cases, removal of these fuses can be applied to establish an air gap After operating the MCCB to the Open position, the load side of the MCCB can be tested by an ESP or EIP to verify voltage is not present and that the breaker operated properly Some MCC buckets using circuit breakers as the isolating device are designed to be partially withdrawn from the power bus and locked in a neutral position. This prevents the stabs from contacting the bus and assures a safe, but mostly invisible air gap. 7. Variable Frequency Drives 7.1. Variable frequency drives are frequently controlled by DCS or panel mounted Loop Controllers. In this control scheme, a speed setpoint is provided to the controller either automatically or manually. The output is controlled based on the selected mode of the controller. When placed in automatic mode, the controller will adjust the output to the VFD to satisfy the speed setpoint based on the speed feedback designed into the controller. When in manual, the speed output is manually entered. Many DCS programs will set the speed to zero to initialize the VFD when not in use. This makes the try step in IOE difficult because the controller output must be known and set to a sufficient speed to observe motor shaft movement The VFD may also lack the typical field stop / start or stop / jog pushbuttons and speed control potentiometer. Lacking local controls for the verify step of IOE requires the use of reviewed verification procedures. These can guide the authorized procedure user through the proper steps to assure the correct energy isolation device was operated Bypass contactors VFDs can be installed with separately powered bypass contactors to increase the driven equipment reliability in the event of a VFD failure. The bypass contactor allows the motor to operate at rated motor speed by running at full supply voltage and frequency. When isolating this type of installation, both power supply energy sources must be tagged and verified to be de-energized.

7 Page 7 of 8 8. Electrical Work 8.1. Only EIPs or ESPs may perform energized electrical work Test each conductor before touch! Regardless of method or approach used to isolate electrical energy, one must test (with an approved meter) each and every conductor before touching them in accordance with the Global Electrical Safe Work Standard requirements. 9. Safety Notes 9.1. In many cases the line (source) side of the isolation device can remain energized after operation of the isolation device to isolate the load side. Hazardous voltages can still exist within the enclosure and while in most cases these are guarded from inadvertent touch by means of barriers or shrouds it needs to be understood that guards can break or be unintentionally left off from previous maintenance activities. Understanding the fundamental design of the equipment is important to safe and reliable operation Multiple sources of power may be present inside enclosures and starters. Sources may include DC control voltages, auto transfer switches, and electrical interlock/control circuits from other equipment etc. This means that hazardous voltages may still exist within the equipment enclosure even when the main source of power has been safely isolated. Virtually every automatic transfer switchgear system will contain some control voltage within the switchgear cell even if the main power source has been disconnected from one of the sources. It is important and in some countries a legal requirement to label the equipment with a warning indicating that it has multiple/ alternate sources of electrical power. Text for an example warning would be This equipment has an alternate source of power and is fed from list circuit ID and isolation device. For switchgear systems, multiple sources of power are likely within a circuit breaker cell or within the equipment, such warning signs are not necessary but in all cases, the isolation and associated work permits must caution the worker that other sources of control power are likely to be found within the switchgear or circuit breaker cell These guidelines DO NOT address the electric shock or arc flash hazard PPE requirements to perform any task or activity mentioned herein. Refer to the Global Electrical Safe Work Standard as needed. 10. Summary (or Applying Layers of Protection) Dialog and questions Use of documents and drawings to include SEOLD, MCC data sheets, panel schedules, etc Use of electrical or other resources to assist (i.e. escalate) Accurate name plates and identification tags of equipment and equipment isolation devices.

8 Page 8 of Two people (Facility Rep and Job Rep) validate isolation device and equipment identifications. For any discrepancy use G7M to determine proper isolation device Operate isolation device and isolate in accordance with IOES Training knowledge and skills with the equipment involved. Use your human senses to hear, feel and see the isolation device operate Use of a TRY process or procedure. In some cases, these may be considered critical procedures. Do not proceed if equipment starts/runs Test for electrical energy isolation (test before touch) before any electrical work. Do not proceed if electrical energy is on. i ; MOC 2012_11300; By: Joe Beam; Supersedes Issue Date 19-JUN-2009; Major revisions to entire document including additions, deletions and clarifications throughout. Key areas of change include: Section 2.2.2: Improved guidance for reliance on visible air gaps. Section 4.5: Added information for installation of alternate IOES verification devices. Section 4.6: Added information for use of test before touch method. Added information of alternate IOES verification devices. Section 5 Added IOE guidance for MCCs that do not allow internal access when locked and red tagged. Added IOE guidance for MCCs that disconnect the tagged operating devices from the isolation device. Section 6.3.5: Added IOE paragraph for MCC buckets using circuit breakers as isolating devices. Added section 7 for Variable Frequency Drives isolation. ii 19-JUN-2009; MOC 2009_07439; By: Don Hull; New practice. This guidance document is provided by the Global Electrical Safety and Maintenance TRN in association with Personal Safety Expertise Isolation of Energy Standard Owner.

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission.

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission. Switchgear Interlock Applications Data Sheet Industries Power Distribution Power Generation Power Transmission Type DM Access Interlock with Spring Bolt Type PPS Interlock Quick-Trip ARC Flash Reduction

More information

LV MCC with Arc Flash Mitigation (AFM) Units

LV MCC with Arc Flash Mitigation (AFM) Units LV MCC with Arc Flash Mitigation (AFM) Units Technical Tuesday June 30, 2015 Imagination at work. Markets Oil and Gas Petro-Chemical Mining and metals Pulp and paper Mass-production manufacturing Water

More information

Starter and Circuit Breaker Application with PowerFlex 7000

Starter and Circuit Breaker Application with PowerFlex 7000 Application Technique Starter and Circuit Breaker Application with PowerFlex 7000 Bulletins 7000A, 7000, 7000L Topic Page General Precautions 2 Document Scope 2 Purpose 3 Drive Associated MV Starters and

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

C. New or replacement products installed in existing facilities shall be consistent with existing equipment. September 2012, rev 00 26 2923 Variable Frequency Controllers PART 1. GENERAL 1.01 Description A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08 DNB Power and Control System Information and Interim Safety Procedures Version draft 5/06/08 DNB Power and Control System Information There are four sources of power for the DNB in the power supply and

More information

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example Introduction 1 Application example 2 Industrial Controls Motor management and control devices SIMOCODE pro - Application examples Application Manual Example circuits control functions 3 Further application

More information

110.4 Use of Equipment.

110.4 Use of Equipment. 110.4 Use of Equipment. (A) Test Instruments and Equipment. 1 Testing. Only qualified persons shall perform tasks such as testing, troubleshooting, and voltage measuring within the limited approach boundary

More information

1. Introduction. 2. Design. Safety and Emergency Stop Circuit Design Standard. Safety and Emergency Stop Circuit Design Standard.

1. Introduction. 2. Design. Safety and Emergency Stop Circuit Design Standard. Safety and Emergency Stop Circuit Design Standard. Safety and Emergency Stop Circuit Design Standard The Safety and Emergency Stop Circuit Design Standard provide design criteria and specifications for safety and emergency stop circuits used in General

More information

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear EMMS-T40013-01-4A00 SIERS Siemens integrated electrical racking system instruction manual usa.siemens.com/mvswitchgear SIERS Siemens Integrated Electrical Racking System Instruction Manual Hazardous voltages

More information

MODELS: STEAM FIRED YPC-ST-14SC & YPC-ST-16SL Thru YPC-ST-19S

MODELS: STEAM FIRED YPC-ST-14SC & YPC-ST-16SL Thru YPC-ST-19S Supersedes: 155.19-W1 (407) Form: 155.19-W1 (812) TWO-STAGE ABSORPTION CHILLERS WIRING DIAGRAMS CONTRACTOR ORDER NO. JCI CONTRACT NO. JCI ORDER NO. PURCHASER JOB NAME LOCATION ENGINEER REFERENCE DATE APPROVAL

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 (S285-80-1) COOPER POWER SERIES DC motor operator control installation and operation instructions DISCLAIMER OF WARRANTIES AND

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,

More information

User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP

User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP Quantum III The drive stop and start inputs should not be relied upon alone to ensure the safety of personnel. If a safety hazard

More information

DPM Active Harmonic Filter Quick Start Instructions

DPM Active Harmonic Filter Quick Start Instructions DPM Active Harmonic Filter Quick Start Instructions These instructions will guide you through installing, testing your installation, and starting up your DPM. For additional information please refer to

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

Autoranging True RMS Multimeter User Manual

Autoranging True RMS Multimeter User Manual Autoranging True RMS Multimeter User Manual Please read this manual before switching the unit on. Important safety information inside. Contents Page 1. Safety Information... 4 2. Safety Symbols... 5 3.

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

Best practices for making switchgear safer.

Best practices for making switchgear safer. Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Refurbishment of Switchgear and Switchgear Devices

Refurbishment of Switchgear and Switchgear Devices White Paper Refurbishment of Switchgear and Switchgear Devices Low and Medium Voltage Products Introduction There are many suppliers who suggest to users that switchgear assemblies, circuit breakers, and

More information

Conext CL-60 Inverter Firmware Upgrade Process

Conext CL-60 Inverter Firmware Upgrade Process Conext CL-60 Inverter Firmware Upgrade Process http://solar.schneider-electric.com 976-0380-01-01/B August 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER

More information

Variable Frequency Drive Design Guidelines

Variable Frequency Drive Design Guidelines Variable Frequency Drive Design Guidelines The Variable Frequency Drive Design Standard provides design criteria and specifications used in the procurement and application of variable frequency drives

More information

1. Summary. 2. Contacts. Safety Controls Guidelines. Table of Contents

1. Summary. 2. Contacts. Safety Controls Guidelines. Table of Contents The provide design criteria and specifications for safety circuit in compliance with ISO 13849-1 PL d Safety of machinery, used in General Mills manufacturing facilities. Table of Contents 1. Summary 2.

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

FT Flexitest Family. Switches, Covers and Test Plugs

FT Flexitest Family. Switches, Covers and Test Plugs FT Flexitest Family Switches, Covers and Test Plugs FT Flexitest Switches Description The flexibility provided by the FT case design evolved into a separate family of molded base test switches for testing

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and IEC 60309 H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and amperage to prevent interchangeability of voltages Watertight

More information

Install Motor Controller User Manual

Install Motor Controller User Manual Property of Motion Laboratories, Inc. Install Motor Controller User Manual 2014 Motion Laboratories, Inc. Created By: Michael Shaw Approved By: John Coppolecchia Page: 1 Page: 2 2014 Motion Laboratories,

More information

ZC Series Zone Monitoring Controllers

ZC Series Zone Monitoring Controllers ZC Series Zone Monitoring Controllers Installation Instructions MANUAL Reset Controllers Model Description Part Number ZC-1 1 Zone Controller 0421 ZC-2 2 Zone Controller 0422 ZC-3 3 Zone Controller 0423

More information

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

StruxureWare Power Monitoring Expert 8.0 Data Center Edition StruxureWare Power Monitoring Expert 8.0 Data Center Edition Breaker Performance Guide 7EN02-0367-01 06/2015 Safety information Important information Read these instructions carefully and look at the

More information

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN Padmounted switchgear MN285011EN Effective May 2017 Supersedes November 2004 (S285-10-4) Visible-Break switch accessory operation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

CENTERLINE 2500 Motor Control Centers

CENTERLINE 2500 Motor Control Centers CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed

More information

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN Deadbreak Apparatus Connectors MN650022EN COOPER POWER Effective March 2016 Supersedes S600-14-1 June 2010 SERIES 600 A U-OP visible break connector system operation instructions DISCLAIMER OF WARRANTIES

More information

30-Cycle Rated Switchboards - Selectivity Tradeoffs

30-Cycle Rated Switchboards - Selectivity Tradeoffs 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted

More information

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY Technical Manual HA09 Issue 008 Parker SSD Drives, a division of Parker Hannifin Ltd. All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Set up and verify the operation of basic motor starters. Understand the purpose of a separate control circuit.

Set up and verify the operation of basic motor starters. Understand the purpose of a separate control circuit. Exercise 3-1 Motor Starters EXERCISE OBJECTIVE Set up and verify the operation of basic motor starters. Understand the purpose of a separate control circuit. DISCUSSION OUTLINE The Discussion of this exercise

More information

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95 Part 1 - GENERAL ASEA BROWN BOVERI ABB Industrial Systems Inc. Standard Drives ACH500-06E Effective 6/1/95 Sample Specification for Adjustable Frequency Drives (2 to 400 HP) for Variable Torque Applications

More information

CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B

CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B (Supersedes GEI-100182A) CONTACTOR DRIVER BOARD DS200CDBAG1A and DS200CDBAG1B These instructions do not purport to cover all details or variations in equipment, nor to provide every possible contingency

More information

Best practices for making switchgear safer

Best practices for making switchgear safer Best practices for making switchgear safer White Paper Introduction What could be more important than protecting the safety of our most valuable assets, our people? Today s workers hold the keys to an

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION OPERATING INSTRUCTION AUTORANGING MULTIMETER MAX Ω F C 10A MAX every 15 min. COM V SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation

More information

Time delay undervoltage module

Time delay undervoltage module Supersedes December 2010 Power Defense ICCB Series NRX IZMX Instructions apply to: UL489 IEC UL1066/ANSI : PD-NF, Series NRX NF : PD-NF, IZMX16 : Series NRX NF UL489 : PD-RF IEC : PD-RF, IZMX40 120VAC

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

3- and 4-pole switching in UPS installation

3- and 4-pole switching in UPS installation Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton

More information

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C Instruction Manual Electrical Management System (EMS) EMS-HW30C & EMS-HW50C EMS-HW50C EMS-HW30C! CAUTION These instructions are intended to provide assistance with the installation of this product, and

More information

700 Series 200 Amp Clamp Meters

700 Series 200 Amp Clamp Meters 700 Series 200 Amp Clamp Meters #61-700 #61-701 #61-702 1 2 3 6 5 7 4 8 1. Non-contact voltage (NCV) (#61-701 and #61-702) With the NCV tab on the tip of the clamp close to an AC voltage, press the NCV

More information

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR AUGUST 14, 2001 REVISION 1 Publication: SE-135-M Document: S95-C135-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Vista SD Portable Remote Control Pendant

Vista SD Portable Remote Control Pendant S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Styles Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Vista

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS SINAMICS G130 Operating instructions 03/2011 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Galaxy Shore Connection 500 kva. Operation 04/

Galaxy Shore Connection 500 kva. Operation 04/ Galaxy 7000 Shore Connection 500 kva Operation 04/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123 Product: High Voltage AC Test Set Type: P123 Bicotest High Voltage Products Ltd Hellesdon Park Road, Drayton High Road, Norwich NR6 5DR United Kingdom Phone

More information

E1 Plus Electronic Overload Relay

E1 Plus Electronic Overload Relay ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION E1 Plus NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific installations

More information

Converter SINAMICS G150. Type 6SL37102G

Converter SINAMICS G150. Type 6SL37102G Tests carried out on drives This documentation pertains to LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Converter SINAMICS G150 Type 6SL37102G Edition 02/2019 www.siemens.com/drives

More information

For normal duty, design the VFD voltage level at 480 Volt, 3 Phase, 60 Hertz. (In Canada, 600 Volt, 3 Phase, 60 Hertz.)

For normal duty, design the VFD voltage level at 480 Volt, 3 Phase, 60 Hertz. (In Canada, 600 Volt, 3 Phase, 60 Hertz.) Introduction The Variable Frequency Drive Design Guidelines provides design criteria and specifications used in the procurement and application of variable frequency drives (VFDs). Table of Contents 1.

More information

Solid-State Switching Devices

Solid-State Switching Devices Overview 3RF21 3RF20 3RF22 3RF23 SIRIUS 3RF2 solid-state switching devices Solid-state switching devices for resistive loads Solid-state relays Solid-state contactors Function modules Solid-state switching

More information

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter S-14 Compact Digital Multimeter S-14 Compact Digital Multimeter SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation at this meter

More information

Installation Instructions

Installation Instructions Installation Instructions (Cat. No. 1771-OBN Series B) Use this document as a guide when installing the catalog number 1771-OBN series B output module. Because of the variety of uses for the products described

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

Technical Specificaions. kwh Energy Meter

Technical Specificaions. kwh Energy Meter Technical Specificaions of kwh Energy Meter (SPK301) Class 1.0S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B SURGE PROTECTION PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) USER MANUAL Surge Protection Device B 01 156 9000 This Surge Protection Device is intended for professional use only Read this

More information

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution LXM32 Explanation for detected error E 733F Expert Support Machine Solution The information provided in this documentation contains general descriptions and/or technical characteristics of the performance

More information

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010 Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction

More information

Operating Instructions. For. Level Control Module. Model SSR 1000

Operating Instructions. For. Level Control Module. Model SSR 1000 Operating Instructions For Level Control Module Model SSR 1000 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions before unpacking and commissioning.

More information

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information

Document Owner: Name: Phil Langlois Department: Lead Electrical Engineer

Document Owner: Name: Phil Langlois Department: Lead Electrical Engineer MAINTENANCE STANDARDS SPECIFICATION TITLE Power System Study Procedure VALE # Ontario Operations MPROC-50003 VALE # October 14, 2016 PAGE 1/14 Rev 3 Training Code (not applicable) Document Owner: Name:

More information

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2 dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical

More information

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 Instruction Manual D2-3342-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH) Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power

More information

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER SAFETY INFORMATION The following safety information must be observed to ensure maximum personal safety during the operation of this meter: This meter is

More information

SECTION VARIABLE FREQUENCY DRIVES

SECTION VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 DESCRIPTION This specification section establishes the requirements for variable frequency motor drives. The associated motor(s) shall be specified separate from the drive and listed

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

5521 Potentiometer Analog Input Module

5521 Potentiometer Analog Input Module 55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) XPSMCMx Fieldbus Expansion Modules EAV8283001 12/2014 XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) 12/2014 EAV8283001.00 www.schneider-electric.com The information provided

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

EM-F-7G Safety Extension Module

EM-F-7G Safety Extension Module EM-F-7G Safety Extension Module One-channel control with four safety output channels Features Safety Extension Module provides additional safety outputs for a Primary Safety Device (for example, an E-stop

More information

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ONE ARTIS ZEEGO / ZEEGO.ZEN ARTIS ZEE MULTIPURPOSE SINGLE PLANE IECAX480V125A Main Disconnect Panel Bevco Engineering

More information

FT & RT Test Switches

FT & RT Test Switches GE Grid Solutions FT & RT Test Switches Key Benefits The FT Switches and FT Test Plugs have all the features necessary for applications involving the measurement of individual currents and voltages to

More information

Instruction Manual: IM E

Instruction Manual: IM E Innovative Technology TVSS Products The I.T. Equalizer Installation Instruction Manual: IM01005011E Rev. 2 May 2009 Contents Page 1 Introduction... 1 1.1 Scope... 1 1.2 I.T. Equalizer Catalog Numbering

More information

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C Electrical Management System (EMS) EMS-HW30C & EMS-HW50C Installation & Operating Guide for: Model EMS-HW30C Rated at 120V/30A and Model EMS-HW50C Rated at 240V/50A Surgio Says Lifetime Warranty on all

More information