Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010

Size: px
Start display at page:

Download "Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010"

Transcription

1 Ontario Electrical Safety Code - Bulletins Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010 Scope (1) Introduction (2) Wiring methods within a photovoltaic array (a) Acceptable wiring methods within a photovoltaic array (b) PV wire or cable approved to UL standard UL 4703 (c) Combiner box (d) Cable support (e) Attachment plugs (3) Single-line diagram and labels (a) Single-line diagram of the interconnected renewable system (b) Labels (4) Voltage rating of photovoltaic circuit (5) Electricity meters (a) Neutral connection for electricity meters (b) Generator metering connection (c) Tapping to the load side of the service box for a parallel metering connection (6) AC modules and micro-inverters (a) Disconnecting means (b) Overcurrent protection (c) Marking of photovoltaic circuit 50 (1) Introduction With the introduction of the Green Energy Act and Feed in Tariff (FIT) program that was launched in Ontario, many renewable energy projects are under development. Electrical contractors and PV installers have asked questions and raised some issues that are addressed in this Bulletin. In addition to this Bulletin, the following documents provide additional information on the installation of solar photovoltaic systems: ESA SPEC-004 Electrical Guidelines for Inverter-Based Micro Generation Facilities ESA SPEC- 005 Process Guideline for the Installation of Parallel Generating Systems (10kW or Greater) Bulletin 50-2-* Grounding and Bonding of Solar Photovoltaic Systems Bulletin 84-1-* Interconnection of Electric Power Production Sources 2) Wiring methods within an array (a) Acceptable wiring methods within a photovoltaic array Acceptable wiring methods for use within a photovoltaic array are: Flexible cords for extra-hard usage as per Rule requirements; Conductors approved for exposed installations where subject to the weather as listed in Table 19. Although not listed in Table 19, type RWU conductors shall also be permitted. PV wire or cable approved to UL standard UL 4703 Page 1 of 8

2 Ontario Electrical Safety Code - Bulletins (b) PV wire or cable approved to UL standards Direction 1 In Ontario, in addition to cables permitted by OESC, PV cables approved to UL Standard, UL 4703 Outline of Investigation for Photovoltaic Wire is an acceptable wiring method within a PV array. PV cables approved to UL Standard UL 4703 have the following characteristics: Voltage Rating: 600 V, 1000 V and 2000 V Temperature Rating: 90 C wet and 90, 105, 125 or 150 C dry Number of conductors: single, insulated, stranded copper conductor, size 18 4/0 AWG Sunlight resistant and marked as Sunlight Resistant or Sun Res. Marked as PV Wire, PV cable, Photovoltaic Wire or Photovoltaic Cable.. Rationale PV cables certified to UL Standard UL 4703 are designed for rooftops tough environments, often subject to snow, ice and scorching heat. Cables marked as PV Wire, PV cable, Photovoltaic Wire or Photovoltaic Cable have 30 C higher temperature rating compared with extra-hard usage outdoor flexible cords and with the option to even withstand 150 C. There is no equivalent Canadian standard for PV cables. The Photo B1 shows typical construction details for PV cable. Photo B1 - Typical construction details for PV cable (c) Combiner box Appendix B note to Rule shows the diagram of a typical solar photovoltaic system and a device referenced as a combiner box. ESA SPEC 004 defines a combiner box as A box used in solar installations to combine the multiple photovoltaic arrays to produce one circuit. It often contains generator overcurrent devices. The combiner box is permitted to be installed on the roof and it is preferred to be as close as possible to the PV modules forming an array. The purpose of the combiner box is to group the wiring from the array into one cable run to the inverter, which reflects the logic to have the combiner box as close as possible to the array (on the roof), as per the Photo B2. Direction 2 Wiring methods specified above (subject (2)(a) of this Bulletin) are acceptable for interconnecting PV modules within array. Therefore, if the combiner box is located outside of a building or a structure and within 1 m from the physical edge of the PV modules, acceptable wiring methods within array shall be permitted to be extended. Page 2 of 8

3 Ontario Electrical Safety Code - Bulletins to the combiner box Where a combiner box is not located within 1 m of PV modules or where conductors are run inside the building or a structure, wiring methods specified in Section 12 are required. Photo B2 Combiner box (d) Cable support Cables and conduit shall be properly supported and shall not lie loosely on the roofing material. Notwithstanding Rule requirements for open wiring support, acceptable supporting means are considered to be straps or other devices located within 300 mm of every box or fitting and at intervals of not more than 1.5 m throughout the run. This requirement is similar to supporting requirements for non-metallic-sheathed cable as defined by Rule (1). Photo B3 is an example of unacceptable cable support. 50 Photo B3 Unacceptable cable support (e) Attachment plugs As per Rule , the plug-in connectors are required to be of the locking type and be rated for the voltage and current of the circuit in which they are installed. Photo B4 shows an example of a connector that meets Rule (d) requirement. Locking connectors required by Rule (d) do not need a tool to unlock. They shall incorporate a suitable latching mechanism between the mated pair. Attachment plugs may not be rated for interrupting the current and be marked with a warning indicating that disconnection under no load is necessary. In this case, the modules must be disabled before disconnecting the connectors. Page 3 of 8

4 Ontario Electrical Safety Code - Bulletins Photo B4 Example of a PV wire connector (3) Single-line diagram and labels (a) Single-line diagram of the interconnected renewable system Question 1 Does Diagram B1 meet the requirements of Rule (2) for the single-line diagram of the interconnected system that is located at the supply authority disconnect switch? Diagram B1 Typical single-line diagram of the interconnected system with parallel meter connection Answer 1 Yes, this meets the minimum single-line diagram requirements of Rule (2). Note: The system ratings required by Rule are not required to be displayed at the supply authority disconnect or on the single-line diagram. The label required by Rule shall be posted at the generator (Source) disconnecting means. (b) Labels Question 2 What Codes or Standards provide requirements for labels, e.g. DG SOURCE DISCONNECT, UTILITYINTERCONNECTED, DG SYSTEM DISCONNECT WARNING TWO POWER SOURCES? Does the code require specific wording? Answer 2 Rules and require the labels. However, the rules do not specify the specific wording. The wording provided in ESA SPEC-004 can be used as an example. Page 4 of 8

5 Ontario Electrical Safety Code - Bulletins The following markings are applicable CSA Part 2 standards requirements and can be used as guidance: CSA Standard C22.2 No. 257 defines Distributed generation (DG) as an electric generation facilities connected to a distribution system through the point of common coupling. In Annex B of Standard C22.2 No. 257 that is informative shows similar labels as in ESA SPEC-004, i.e. DG - source disconnect means. CSA Standard C22.2 No , Clause requires When the unit complies with Clause 15, it shall be marked: UTILITY - INTERCONNECTED, or the equivalent, and Clause specifies: A utilityinterconnected inverter shall be marked: WARNING - POWER FED FROM MORE THAN ONE SOURCE, or the equivalent. Question 3 What is considered acceptable for exterior, weatherproof labels required by Section 84? Does the code specify letters size? Answer 3 The Code does not provide specific requirements; the labels need to be able to withstand the elements, be permanent and legible, for example: lamacoid, engraved metal plate, or equivalent. Additionally, the label has to satisfy the local supply authority requirements. (4) Voltage rating of photovoltaic circuit Rule requires the voltage rating of photovoltaic source circuits to be the rated open-circuit voltage of the photovoltaic power source multiplied by 125%. A PV source is not a constant-voltage source and increases with decreasing temperature. The 125% safety factor is based on a minimum module temperature of - 40 C. 50 Notwithstanding Rule requirements, when open-circuit voltage temperature coefficients at - 40 C are different than 125% as supplied in the manufacturer s instructions for certified PV modules, ESA will consider the deviation to use the designed open-circuit voltage temperature coefficients at - 40 C instead of using the 125% factor. The deviation request should be issued to ESA in accordance with Bulletin 2-21-*. (5) Electricity meters (a) Neutral connection for electricity meters Question 4 For a parallel metering connection, where the generation meter is on the supply side of the service disconnecting means, do all 4-jaw revenue meters require a neutral conductor to be terminated in the meter base? Answer 4 No. According to Rule (2), the grounded conductor on the supply side of the service disconnecting means is permitted to be used as a bonding conductor for the revenue meter device. In this case the grounded conductor is required to be bonded to the meter mounting device. However, when the grounded conductor is not used as a bonding conductor for the revenue meter device, the grounded conductor can be run through the meter base without being terminated and a separate bonding conductor shall be provided between the service and the meter. Page 5 of 8

6 Ontario Electrical Safety Code - Bulletins (b) Generator metering connection Direction 3 The requirement in the ESA SPEC-004 is to always have the Line side of the metering cabinet connected to the utility and the Load side connected to the customer to ensure consistency and safety, as per Diagram B2. Diagram B2 Generation meter connection Rationale When pulling a meter, the standard practice is that the Load side of the metering cabinet will be de-energized and caution is taken around the Line side as it maybe energized. The ESA guideline is consistent with the Ontario Power Authority s (OPA s) microfit Contract which requires bi-directional metering for the generator facility. (c) Tapping to the load side of the service box for a parallel metering connection Question 5 In installations where the existing customer load meter is downstream of the main service disconnect, does the code permit tapping to the load side lugs of the service disconnect for a FIT or microfit installation with a parallel metering configuration, as per attached Diagram B3? Diagram B3 Tapping to the to the load side lugs of the service disconnect Page 6 of 8

7 Ontario Electrical Safety Code - Bulletins Answer 5 Yes; According to Bulletin 6-7-*, maximum one tap is permitted per service box. Therefore, the generator meter in a parallel configuration is allowed to be connected to the load side lugs of service disconnect and be terminated in accordance with Bulletin 6-7-*. (6) AC modules and micro-inverters Rule defines AC module as a complete, environmentally protected assembly of interconnected solar cells, inverter, and other components designed to generate ac power. AC modules are designed to generate AC power when exposed to sunlight and do not have accessible, field installed DC wiring (as shown in the Photo B5). (a) Disconnecting means For AC modules where the inverter is an integral part of the generator (as shown on Photo B5), and the combined unit is approved, there is no requirement for a disconnecting means as required by Rule (1). However, if any other electric power production source is interconnected with an AC module, the disconnecting means in accordance with Rule is required for all production sources. Photo B5 AC module where the inverter is an integral part of the generator 50 For Micro-inverters, inverters plugged into the photovoltaic panels (as shown on Photo B6), no additional disconnect switch is required Photo B6 Micro-inverter (b) Overcurrent protection Page 7 of 8

8 Ontario Electrical Safety Code - Bulletins The output circuits of AC modules shall have overcurrent protection according to Rule requirements (c) Marking of photovoltaic circuit Question 6 Does the OESC require marking of PV system with AC modules when interconnecting to the supply authority? Answer 6 Yes. Although requirements of Rule for marking of photovoltaic output circuit at generator disconnecting means are not applicable to AC modules, according to Rule 2-100, PV installations utilizing AC modules connected to the supply authority shall be marked to identify PV system rating and suitability for the particular installation. Question 7 What is the required marking for PV system with AC modules? Answer 7 According to Rule and the intent of Rule , the required marking for PV installations utilizing AC modules connected to the supply authority are: rated AC output current nominal operating AC voltage Question 8 Where is the marking for PV system with AC modules required to be located? Answer 8 The required marking for PV installations utilizing AC modules connected to the supply authority shall be located at the supply authority disconnect; or be included in the single-line diagram required by Rule (2). Page 8 of 8

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

PV Rapid Shutdown device

PV Rapid Shutdown device PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.

More information

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN This Inspection Checklist for Rooftop Photovoltaic (PV) Systems is based on the Model Inspection Checklist

More information

Stalking the Elusive and Somewhat Strange PV System

Stalking the Elusive and Somewhat Strange PV System A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles PERSPECTIVES ON PV Stalking the Elusive and Somewhat Strange PV System Photo 1. Framed PV modules

More information

Rapid Shutdown Requirements for NEC 2017

Rapid Shutdown Requirements for NEC 2017 2017 AEESOLAR DEALER CONF. Rapid Shutdown Requirements for NEC 2017 Presented by: Bill Brooks, CMP 4 2017 NEC Statistics for Article 690 Whole article was reduced from 11,000 words to about 8,000 words.

More information

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D. Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

Distributor Information Bulletin Distributed Generation (Codes, Publications & Standards)

Distributor Information Bulletin Distributed Generation (Codes, Publications & Standards) GENERAL: This bulletin highlights some of the most commonly referenced technical codes, publications and standards when reviewing a connection to under the Feed-in Tariff (FIT) Program, including micro-fit.

More information

Replacing the Power Supply

Replacing the Power Supply APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Microinverters And The Solar Industry

Microinverters And The Solar Industry Microinverters And The Solar Industry Peter Lum Senior Learning And Development Professional Assistant Professor Skyline College Solar Continues Its Growth 2 Significant Growth Of Microinverters in Solar

More information

This Special Provision refers to the following standards, specifications or publications:

This Special Provision refers to the following standards, specifications or publications: OUTDOOR CLOSED CIRCUIT TELEVISION CAMERAS - Item No. Special Provision No. 684S01 September 2007 1. SCOPE This Special Provision covers the requirements for the installation and testing of CCTV camera

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

More Questions from Inspectors Numerous PV Systems Pose Issues

More Questions from Inspectors Numerous PV Systems Pose Issues Perspectives on PV More Questions from Inspectors Numerous PV Systems Pose Issues by John Wiles 76 IAEI NEWS March. April 2012 www.iaei.org Photovoltaic (PV) systems prices continue to drop and inspectors

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

M215 Microinverter Installation Planning

M215 Microinverter Installation Planning TECHNICAL BRIEF M215 Microinverter Installation Planning The M215 Microinverter The M215 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60- cell PV modules

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

Enphase S-Series Microinverter and Engage Cable Safety

Enphase S-Series Microinverter and Engage Cable Safety SAFETY Enphase S-Series Microinverter and Engage Cable Safety Important Safety Information (S280-60-LL and S230-60-LL) This document contains important instructions to use during installation of the Enphase

More information

DOWNLOAD PDF ENPHASE M250 INSTALLATION GUIDE

DOWNLOAD PDF ENPHASE M250 INSTALLATION GUIDE Chapter 1 : Enphase Energy MLL-S22 Grid-Tied Microinverter An Enphase team member may follow up with you about your feedback. The M maximizes the energy production of cell solar panels, working best with

More information

Installation Guide for America Solar Wholesale Photovoltaic Modules

Installation Guide for America Solar Wholesale Photovoltaic Modules Installation Guide for America Solar Wholesale Photovoltaic Modules Mono Module Poly Module 1 ASW Photovoltaic Module Installation Guide Installation guide for American Solar Wholesale Photovoltaic modules

More information

Standards Update Notice (SUN) Issued: July 28, 2017

Standards Update Notice (SUN) Issued: July 28, 2017 Standard Information Standard Number: CSA C22.2 No. 107.1 Standard Name: Power conversion equipment Standard Edition and Issue Date: 4 th Edition Dated June 2016 Date of Issue: June 2016 Date of Previous

More information

M250 (M LL) Safety

M250 (M LL) Safety M250 SAFETY M250 (M250-60-2LL) Safety Important Safety Information This document contains important instructions to use during installation of the Enphase M250 Microinverter. To reduce the risk of electrical

More information

Rev1 QP-10-IM21UL/Rev Rev2 QP-10-IM21UL/Rev Rev3 QP-10-IM21UL/Rev Rev4 QP-10-IM21UL/Rev4

Rev1 QP-10-IM21UL/Rev Rev2 QP-10-IM21UL/Rev Rev3 QP-10-IM21UL/Rev Rev4 QP-10-IM21UL/Rev4 Installation and Operation Manual UL1703 VERSION 2018 5.11.13 Rev1 QP10IM21UL/Rev1 21.12.14 Rev2 QP10IM21UL/Rev2 11.2.16 Rev3 QP10IM21UL/Rev3 2.4.16 Rev4 QP10IM21UL/Rev4 1.5.16 Rev5 QP10IM21UL/Rev5 3.05.16

More information

File E28476 Project 01ME June 27, 2001 REPORT COMPONENT - CONNECTORS FOR USE IN DATA, SIGNAL, CONTROL AND POWER APPLICATIONS

File E28476 Project 01ME June 27, 2001 REPORT COMPONENT - CONNECTORS FOR USE IN DATA, SIGNAL, CONTROL AND POWER APPLICATIONS File E28476 Project 01ME05381 June 27, 2001 REPORT On COMPONENT - CONNECTORS FOR USE IN DATA, SIGNAL, CONTROL AND POWER APPLICATIONS Tyco Electronics Corp., Harrisburg, PA Copyright 2001 Underwriters Laboratories

More information

HT2000 Transverter Installation & Operation Manual

HT2000 Transverter Installation & Operation Manual HT2000 Transverter Installation & Operation Manual 1 A message from the team at Heart Transverter S.A. Thanks for your recent purchase of the HT2000 Power inverter in combination with the HTREM Remote

More information

Conergy PH Series Modules. Solar module user manual

Conergy PH Series Modules. Solar module user manual Conergy PH Series Modules Solar module user manual 1 Introduction 1.1 Short description Conergy PH modules are solar modules for installation in photovoltaic systems. 1.2 About this manual 1.2.1 Subject

More information

M215 (M215-60) Safety

M215 (M215-60) Safety M215 QUICK INSTALL GUIDE M215 (M215-60) Safety Important Safety Information This document contains important instructions to use during installation and maintenance of the Enphase M215 Microinverter. To

More information

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template.

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template. 6. ENGINEERING SYSTEMS REQUIREMENTS G40 SITE ELECTRICAL UTILITIES SYSTEMS REQUIREMENTS SITE ELECTRICAL UTILITIES TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Photovoltaic Equipment No. 5 Date: September 21, 2015 See Attachment 1 for Effective Dates. See Attachment 1 for Application Due Dates Announcing: Publication of List

More information

Power Supply Installation

Power Supply Installation Power Supply Module Overview, on page Installation Guidelines, on page 4 Installing or Replacing an AC Power Supply, on page 6 Installing a DC Power Supply, on page 7 Finding the Power Supply Module Serial

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

KANEKA CORPORATION 3-2-4, NAKANOSHIMA, KITA-KU OSAKA , JAPAN

KANEKA CORPORATION 3-2-4, NAKANOSHIMA, KITA-KU OSAKA , JAPAN KANEKA Thin Film PV Installation Manual MODULE TYPE: GSA KANEKA CORPORATION 3-2-4, NAKANOSHIMA, KITA-KU OSAKA 530-8288, JAPAN reference No. GSA211.001 Warning Meaning of signs Not Allowed No Disassembly

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

FAQ about Drives Technology

FAQ about Drives Technology FAQ about Drives Technology Power supply systems MICROMASTER 4 SINAMICS G120 ID: 25220071 Warranty, liability and support We do not accept any liability for the information contained in this document.

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 March 13 Rev A1 SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

Model Number Electrical Compatibility Module Connector Type M LL-S22 M LL-S22-NA M LL-S23 M LL-S23-NA

Model Number Electrical Compatibility Module Connector Type M LL-S22 M LL-S22-NA M LL-S23 M LL-S23-NA M215 Microinverter Installation Planning The Enphase M215 Microinverter The M215 Microinverter is Enphase s most powerful and efficient model yet. This grid-tied microinverter is compatible with most 60-cell

More information

Solarlok PV BAR Junction Box Assemblies

Solarlok PV BAR Junction Box Assemblies Application Specification 114-137167 8 October 2018 Rev. C Solarlok PV BAR Junction Box Assemblies Application Specification 1. Introduction This specification covers the installation of the TE Connectivity

More information

SAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS OUTDOOR HARDWIRE INSTALLATION INSTRUCTIONS Please read and save these instructions. Read carefully before using product. Protect yourself and others by observing all safety information, warnings and cautions.

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SUN KTL-USH0 Quick Guide. Issue: 01 Part Number: Date: HUAWEI TECHNOLOGIES CO., LTD.

SUN KTL-USH0 Quick Guide. Issue: 01 Part Number: Date: HUAWEI TECHNOLOGIES CO., LTD. SUN2000-100KTL-USH0 Quick Guide Issue: 01 Part Number: 31509347 Date: 2018-02-08 HUAWEI TECHNOLOGIES CO., LTD. NOTICE The information in this document is subject to change without notice. Every effort

More information

PV Module Installation Instructions

PV Module Installation Instructions Name 1601A Page 1 / 8 Name 1601A Page 2 / 8 1 Introduction Thanks for purchasing PV modules of HT SOLAR ENERGY JOINT STOCK COMPANY This manual refers to PV modules manufactured and sold by HT Turkey. This

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

Installation/User Manual

Installation/User Manual Installation/User Manual APsystems YC500-A Photovoltaic Grid-connected Inverter Version 4.1 8/15 APsystems 600 Ericksen Ave. NE Ste 200 Seattle, WA 98110 TEL: 844-666-7035 EMAIL: info@apsystems.com WEB:

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Enphase Engage Cable and Accessories

Enphase Engage Cable and Accessories INSTALLATION MANUAL Enphase Engage Cable and Accessories 141-00013, Rev 04 Contact Information Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954 http://www.enphase.com info@enphaseenergy.com

More information

TECHNICAL AND GENERAL BID REQUIREMENTS

TECHNICAL AND GENERAL BID REQUIREMENTS TECHNICAL AND GENERAL BID REQUIREMENTS The following specifications are similar to those used by several utilities in procuring photovoltaic systems. These specifications help insure the bidders turn in

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

KUANTECH (SHEN ZHEN) COMPANY LIMITED KSAFD W1UK

KUANTECH (SHEN ZHEN) COMPANY LIMITED KSAFD W1UK 1 GENERAL... 2 1.1 Description... 2 2 INPUT REQUIREMENTS... 2 2.1 Input Conditions... 2 2.2 AC Inrush Current... 2 3 OUTPUT REQUIREMENTS... 2 4 MECHANICAL... 3 4.1 Enclosure And Layout... 3 4.2 Input and

More information

Standards Update Notice (SUN) Issued: January 11, 2016

Standards Update Notice (SUN) Issued: January 11, 2016 Standard Information Standard Number: UL 962A Standard Name: Furniture Power Distribution Units Standard Edition and Issue Date: 3 rd Edition Dated September 29, 2014 Date of Revision: September 8, 2015

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

Standards Update Notice (SUN) Issued: April 25, 2017

Standards Update Notice (SUN) Issued: April 25, 2017 Standard Information Standard Number: UL 1951 Standard Name: Electric Plumbing Accessories Standard Edition and Issue Date: 2 nd Edition Dated July 22, 2011 Date of Revision: February 21, 2017 Date of

More information

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Technical Information Product Details Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Contents The Sunny String Monitor SSM24 11 is specifically designed for monitoring large PV generators.

More information

Series Amp Quick Connect Input and Output Power Panels

Series Amp Quick Connect Input and Output Power Panels Series 300 1200-1600 Amp Quick Connect Input and Output Power Panels DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury. WARNING is

More information

Oncor Residential/Small Commercial Project Requirements

Oncor Residential/Small Commercial Project Requirements Oncor Residential/Small Commercial Project Requirements Revised: March 26, 2018 In Effect: May 1, 2018 Equipment (Including all associated equipment) o Batteries o Utility Meter o Generators o Visible

More information

VRp Three-Phase Precision AC Voltage Regulator

VRp Three-Phase Precision AC Voltage Regulator VRp-22500-0338 Three-Phase Precision AC Voltage Regulator INSTALLATION INSTRUCTIONS Inspection and Unpacking Please inspect the wooden crate for obvious shipping damage. Some crates contain up to six (6)

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

CenterPoint Energy P O Box 1700 Houston, TX

CenterPoint Energy P O Box 1700 Houston, TX CenterPoint Energy P O Box 1700 Houston, TX 77251-1700 IF YOU ARE APPLYING FOR DISTRIBUTED GENERATION, PLEASE FOLLOW THE INSTRUCTIONS IN THE PARAGRAPHS BELOW. YOU WILL NEED TO COMPLETE AND SIGN AND THEN

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TM REPLACEMENT PARTS FOR USE WITH CX SERIES PANELS INSTALLATION INSTRUCTIONS Hubbell Control Solutions 9601 Dessau Road Building One Suite 100 Austin, TX 78754 Toll Free: 888-698-3242 Fax: 512-450-1215

More information

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP NEC 2008 Code Changes Top 20 Revisions By: Rafi Wartan, PE, LEED AP #1 Article 210.4 MULTIWIRE BRANCH CIRCUITS The rule on simultaneous disconnecting means requirements for multiwire branch circuits was

More information

System Design Guide. APsystems YC Photovoltaic 3-Phase Grid-connected Microinverter. APsystems. Version 1.1 3/15

System Design Guide. APsystems YC Photovoltaic 3-Phase Grid-connected Microinverter. APsystems. Version 1.1 3/15 System Design Guide APsystems YC1000-3 Photovoltaic 3-Phase Grid-connected Microinverter Version 1.1 3/15 APsystems 600 Ericksen Ave NE. Ste 200; Seattle, WA 98110 TEL: 844-666-7035 EMAIL: info@apsystems.com

More information

M215-Z Safety Information (M LL-IG-ZC)

M215-Z Safety Information (M LL-IG-ZC) M215-Z SAFETY M215-Z Safety Information (M215-60-2LL-IG-ZC) This document contains important instructions to use during installation of the M215-Z Zep Compatible Microinverters. To reduce the risk of electrical

More information

S66 Series Electronic Fan Speed Control

S66 Series Electronic Fan Speed Control FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,

More information

Series Amp Pad Mount Quick Connect Input and Output Power Panels

Series Amp Pad Mount Quick Connect Input and Output Power Panels Series 300 2000-4000 Amp Pad Mount Quick Connect Input and Output Power Panels DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7) File E3456 Project 08NK10151 November 24,09 REPORT ON TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7) *********************************************************** Complementary Product Category ELECTROMAGNETIC

More information

Installation and Operations Manual Micro-Inverter M S

Installation and Operations Manual Micro-Inverter M S Installation and Operations Manual Micro-Inverter M175-24-240-S Release 1.3 Page 1 Copyright Enphase Energy Inc. 2008 Release 1.3 Contact Information Enphase Energy Inc. 201 1 St Street, Suite 111 Petaluma,

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 1.0 SCOPE This secondary Type 1 surge protective device specification covers

More information

Installation/User Manual

Installation/User Manual Installation/User Manual APsystems YC500i Photovoltaic Grid-connected Inverter Version 1.0 7/16 APsystems 600 Ericksen Ave. NE Ste 200 Seattle, WA 98110 TEL: 844-666-7035 EMAIL: info@apsystems.com WEB:

More information

Installation Job Aid for Ethernet Routing Switch 3600 Series

Installation Job Aid for Ethernet Routing Switch 3600 Series Installation Job Aid for Ethernet Routing Switch 3600 Series Notices NN47213-303 Issue 03.01 November 2017 Notice paragraphs alert you about issues that require your attention. Following are descriptions

More information

Installation Instructions & User Manual

Installation Instructions & User Manual Installation Instructions & User Manual ZONEMASTER PRO AC Panel Transient Voltage Surge Suppressors The Wiremold Company In US: 60 Woodlawn Street, West Hartford, CT 06110 800-621-0049 FAX 860-232-2062

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 June 13 Rev B SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

Girard Awnings R ACMC Motor Controller (Last revised on May 10, 2008) A Visionary Awning Control by

Girard Awnings R ACMC Motor Controller (Last revised on May 10, 2008) A Visionary Awning Control by Girard Awnings R ACMC Motor Controller (Last revised on May 10, 2008) R A Visionary Awning Control by Girard AC Motor Controller Installation Guide ACMC Revision 2.08 May 10, July 2008 ACMC Installation

More information

Protection against electric shock

Protection against electric shock Protection against electric shock BS EN 61140 tells us that hazardous live parts shall not be accessible and that accessible conductive parts shall not be hazardous live, when in use without a fault or

More information

GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2

GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2 USER MANUAL MPI-1500/2000/3000/4000/6000 Series GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2 WWW.MPPSOLAR.COM WARNING: ONLY A CERTIFIED ELECTRICIAN OR TRAINED ASSEMBLING PROFESSIONAL SHOULD OPEN OR INSTALL

More information

Electrical Specifications

Electrical Specifications Output Power (W) Output Voltage (V) Output Current (A) Efficiency@ Max Load Max Case Tem p. ( C) Input Current Max. Input Power (W) Inrush Current (A pk/50%-µs) THD @ Max Load (%) Power Factor @ Max Load

More information

FS Series PV Modules Reverse Current Overload

FS Series PV Modules Reverse Current Overload FS Series PV Modules Reverse Current Overload Purpose The purpose of this document is: to describe the system conditions that can cause reverse current overload (RCOL) and the behavior of FS modules in

More information

Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group

Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group Table of Contents 1. Introduction... 1 2. Purpose... 1 3. Customer Eligibility...

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Distributed by: www.jameco.com 1-800-831-4242 The content and copyrights of the attached material are the property of its owner. HIGH POWER CONNECTORS Panel Mounts and Cord Plugs HPC Series Switchcraft

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).

More information

The Polarization Cell Replacement (PCRH)

The Polarization Cell Replacement (PCRH) The Polarization Cell Replacement (PCRH) Installation Instructions Introduction The Polarization Cell Replacement for use in Hazardous Locations (PCRH) is a solid-state DC isolation/ac grounding (or coupling)

More information

Installation Manual SMA SENSOR MODULE

Installation Manual SMA SENSOR MODULE Installation Manual SMA SENSOR MODULE ENGLISH MDSEN-US-40-IA-en-11 Version 1.1 Legal Provisions SMA Solar Technology America LLC Legal Provisions No part of this document may be reproduced, stored in a

More information

TWL Series Installation Guide

TWL Series Installation Guide TWL Series Installation Guide Tower Light Controller Protectors Also See TWL Datasheet and Configuration Sheet The TWL Surge Suppressor is probably different than anything you have seen before. You will

More information

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series Installation Manual APEX Series Silicon and MOV Panel Protection APEX Series APEX Series Installation Guide 2 Table of Contents Mechanical Installation 3 Table One - Application Rating 3 Figure 1 - Mounting

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

First Solar Series 3 Black Plus Module

First Solar Series 3 Black Plus Module User Guide User Guide: First Solar Series 3 Black Plus Module North America REV 1.2 PD-5-200-03 Plus NA 02811_UG_NA_Plus_9AUG16 Series 3 Black Plus Module User Guide North America Page i of 13 Table of

More information

TECHNICAL BRIEF. Planning for an IQ Microinverter System. IQ 6 and IQ 6+ Micros

TECHNICAL BRIEF. Planning for an IQ Microinverter System. IQ 6 and IQ 6+ Micros TECHNICAL BRIEF Planning for an IQ Microinverter System The Enphase IQ Microinverter system is inexpensive to install and provides a wide range of new installation options to solar professionals. The IQ

More information

M215 Safety (M LL-S22-IG / S23-IG / S24-IG)

M215 Safety (M LL-S22-IG / S23-IG / S24-IG) M215 SAFETY M215 Safety (M215-60-2LL-S22-IG / S23-IG / S24-IG) Important Safety Information This document contains important instructions to use during installation of the Enphase M215 Microinverter. To

More information

Please carefully read the following installation and safety instructions. Non-compliance with these instructions may void the module warranty.

Please carefully read the following installation and safety instructions. Non-compliance with these instructions may void the module warranty. Installation Safety instructions Maintenance Photovoltaic modules user manual ET Solar series module Please carefully read the following installation and safety instructions. Non-compliance with these

More information

sonnen Installation Practical

sonnen Installation Practical sonnen Installation Practical sonnen Components sonnenbatterie eco 8.0 Single Phase System Components 4 sonnenbatterie eco 8.0 Single Phase System Components 5 sonnenbatterie eco 8.0 Single Phase System

More information