1 Switch to Perfection
2 Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set
3 The challenge a thermal image Front View of Rack Actual Air Temperature: C Cold Aisle Hot Aisle Cold Aisle Hot Aisle Cold Aisle
4 Hot Spot Study 90% of data centers have far more cooling capacity than they need. Although the data centres studied had 2.6 times as many cooling units as they required, hot spots could still be identified, making up 10% of the total floor space. ~ Uptime Institute Increase in room temperature 1 K 2 K 3 K 4 K 5 K Energy saving for climate control 4 % 8 % 12 % 16 % 20 % Source: Swiss Federal Energy Supply Office
5 Electronic Failures List Source: BBC, Inc, Report GB-185R
6 Solving Hot Spots Saving Energy The Challenge of the modern Data Center: 1. Eliminating Existing Hot Spots whilst conserving energy. 2. Increasing Heat Density (See below)
7 Future Data Centre Server Heat
8 So Much Confusion
9 Facts about Data Centres and Power Power capacity is not only an Eskom / SA Problem. One BT Data Centre has a larger carbon foot print than all the Scottish distilleries put together The new Norwich Union Data Centre pulls 10% of the Norwich's overall power demand We need to make the most out of the power that we have available It is now estimated that Data Centres are responsible for a bigger carbon footprint than the Airline Industry
10 Let s look at the energy in a Data Centre Cooling IT Components Power Distribution
11 Add Cold Aisle Containment Very simple to deploy / retrofit Hot and cold aisles physically separated Greater watts per rack approx 10 or even more Over sizing of the CRAC is reduced CRAC efficiency is increased due to a higher delta T Increase air inlet temperatures CRAC fan speed can be reduced which provides:- Reduced running costs Increased MTBF
12 Tuning the CRAC with Cold Aisle Containment Fan Power Fan Power Fan Power Delta TDelta T Delta T Air Inlet Temperatur e Air Outlet Temperatur e Fan Power Standard Cold Aisle Hot Aisle Containment Cold Aisle Cold Aisle increases Containment Configuration Delta T by increases 10 o C but Delta by Delta 10 increased 15 o T C5 o C Outlet Temperature CRAC Rating Fan Power 20 o C 15 o C o C 15 o C o C 15 o C o C 20 o C Delta T Hot Aisle Cold Aisle Cold Aisle Containment
13 Summary of tuning the CRAC Inlet Temperature Outlet Temperature Rating Fan Power 20 o C 15 o C o C 15 o C o C 15 o C o C 20 o C Increasing delta T can increase cooling capacity of the CRAC, or reduce CRAC fan speed Increasing air outlet temperature/ increases water temp which in turn helps improves the effectiveness of Free Cooling
14 Advantages of Cold Aisle Containment Cold Aisle Containment You have a choice, either:- Same capacity but greater efficiency, or Greater capacity, but same efficiency Even airflow of air means a reduction in hot spots Greater heat load per cabinet, 10 plus Reduced foot print compared to hot aisle cold aisle? Reduced noise levels Greater MTBF on the CRAC/ IT Cold Aisle Containment really allows the existing infrastructure to be stretched even further
15 New Build Medium to High Density
16 If the predicted demand is less than 10 per enclosure Implement or have the ability to upgrade to Cold Aisle Containment
17 Depending on the site Cold Aisle Containment with LCP In line For high density applications without raised floors Cooling capacity up to 30 (10kw per rack) Ambient air is extracted from the warm aisle or room through the perforated rear door, cooled and blown into the cold aisle Supports existing room climate control In conjunction with Cold Aisle Containment, provides significant increase in cooling capacity per server rack
18 Liquid cooling systems Combination of LCP Inline + Cold Aisle Containment LCP Inline Top view Cold aisle containment LCP In line either assists existing CRACs or removes the need
19 Benefits of Free Cooling Liquid Cooling Packages
20 Benefits of adding Free Cooling? Johannesburg Temperatures % of the year your temperature is less or equal than 10 degrees Max C Mean C Min C
21 Now the cost of running the system for a year 100% free cooling 30% of the year Chiller capacity Energy needed to run the chiller Not using the Free Cooler Chiller capacity 150 Energy needed to run the chiller 62 Numbers of hours running per year 8784 Cost per h (day /night) R 0.5 Total cost of running per year R272, Numbers of hours running per year 6228 Cost per h (day/night) R 0.5 Cost of running the chiller R 193,068 Cost of running Free Cooling (10.4kw) R 13,291 Total cost of running per year R 206,359 Incorporating Free Cooling reduces energy costs by 25%
22 There are additional benefits of Free Cooling Even when temp is between 20 0 C and 16 0 C Free Cooling still reduces chiller usage It also improved the MTBF of the chiller. Which in turn lowers maintenance costs Increase your Return on Investment More importantly it gives you a degree of redundancy If you are using water Free Cooling is a logical solution
23 High Density Data Centres and Liquid Cooling When going above 10 per rack a new cooling method needs to be deployed. Direct water cooling to the cabinet is the next step Increased load up to 30 Increased efficiency 35-45% reduction in required real estate 10-20% reduction on total annual fan power consumption 30-45% reduction in light related cost % reduction in power delivered to mechanical chilled water plant Higher cooling capacity, with reduction in hotspots
24 So how does it work? Single Cabinet Cooling LCP+ unit in its own right and can be connected to a standard Rittal TS8 enclosure. Water is physically separated away from the server. 30 of cooling Dual Cabinet Cooling LCP+ can be placed between two racks and share the cooling capability. 15 per enclosure
25 System Resilience So how does it work? LCP+ can be mounted to both sides of the TS 8 to provide an N+1 resilience. In case of a chiller failure the second LCP+ has the ability to still maintain the cabinet temperature Fan Resilience Each fan is a single phase fan but fed from a three phase source. In the event of a phase failure, 2/3rds of your fans are able to operate.
26 Space Comparison 60 load Conventional Hot Aisle Cold Aisle Cold Aisle Containment Water Cooled Change starts when someone sees the next step William Drayton
27 Summary of Stage 3 Making Legacy more efficient 9% Saving 25% Saving Cooling IT Components Power Distribution New Build High Density Increased load up to 30 Increased efficiency Better utilisation of Free Cooling 35-45% reduction in required real estate 10-20% reduction on total annual fan power consumption 30-45% reduction in light related cost % reduction in power delivered to mechanical chilled water plant 25% in overall energy consumption
28
29 Lets look at the energy in a Data Centre Cooling IT Components Power Distribution
30 Transformer-less UPS & Modularity
31 Advantages of Modularity - Redundancy - Easy Serviceability 40 kva (N+1) 40kVA (2+1) 48kVA (4+1)
32 Advantages of Modularity - Scalability Scalability Pay as you grow Easy budgeting Maximises inverter efficiencies (Full load is 95%) Reduces long-term energy costs Available space Scalability Demmand
33 Advantages of Modularity - Efficiency 120kVA conventional UPS (N+1) At full load, each system is only at 50% Traditional UPS systems are designed for maximum efficiency at >95% load There is a waste in energy PMC kVA UPS (N+1) At full load, each system is only at 75% At 75% load, UPS is still 95% efficient Therefore saving energy
34 Advantages of Modularity - Availability Traditional Free Standing 2x120kVA (1+1) Redundant Configuration Advanced Modular (3+1) Redundant Configuration Spare 40kVA Module 40kVA Module 40kVA Module 40kVA Module 120kVA 120kVA LOAD 120kVA LOAD 120kVA Availability: A=MTBFUPS/(MTBFUPS+MTTRUPS) MTBF MTTR Availability Non-Modular (1+1) Redundant Configuration 600,000 6h 0, (5 nines) Non-Modular (3+1) Redundant Configuration 500, h 0, (6 nines)
35 "Total Cost of Ownership" Rittal PMC 200 PMC 200 Efficiency of consumers in UPS efficiency in % (with partial load) 95.0% Input in UPS heat loss in 8.4 /h per year 73,768 Electricity costs in EUR per /h Additional costs owing to heat loss per year (without cooling) 4,124 /h per year with cooling 103,276 Cooling required for heat loss, factor 0.4 1,649 Additional cost per year including cooling 5,773 A Nother UPS % , , ,695 2,359 8,256 During 5 years 28,866 More than 10 years 57,731 Additional cost compared with PMC 200 UPS during 10 years 41,281 82,562 24,831 CO2 emissions per year 1 Kilowatt hour (h) of electr. = 0.6 kg CO ,965 88,617 kg Source: Internationales Wirtschaftsforum Regenerative Energien (IWR) Difference in CO2 per year 26,652 kg Equals an annual car mileage with a Golf FSI (1.6 engine petro): 165,539 km 102,861 miles Difference in CO2 throughout 10 years of operation 266,518 kg
36 Summary of Power Savings 9% Saving 25% Saving Cooling IT Components Power Distribution 30% Saving 15% in overall energy consumption 47% Saving30%
37 15% overall saving... is it worth it? Yes Design life of the data centre is 10 years Energy costs are rising 24% increase last year 31% increase this year What is happening next year? Long-term operating costs now out weigh initial Data centre Capex,
38 Summary In Legacy Sites:- Making it Greener Simple reduce the amount of air mixing Block of air leakages Incorporate aisle containment Install new lower energy CRAC systems Implement Free Cooling In Legacy Sites - Getting more Cooling Capacity Incorporate Aisle containment In New Builds:- Making it Greener and Future Proof Learn from the Legacy Deploy water cooling Use Free Cooling Reducing Power Consumption Transformer less UPS are more efficient Modularity future proofs Little things do make a difference Change the colour of your racks from black to grey, gives you approx a 40% saving on your lighting circuits Some people change when they see the light, others when they feel the heat. Caroline Schoeder
39 Rittal together + + = Complete IT Competence Thank you for your Time Quintin Lamprecht
Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationWhite Paper - Infrastructure in an energy-efficient data centre
White Paper - Infrastructure in an energy-efficient data centre Verena Schwalfenberg Dipl.-Ing. Markus Schmidt Copyright 2008 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationPerfect Cooling. A perfect climate for high performance servers
Perfect Cooling A perfect climate for high performance servers High Performance Cooling Modular, scalable, efficient Despite a dramatic rise in climate control requirements, cooling practice in many companies
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationHow much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)
How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationServer Room & Data Centre Energy Efficiency. Technology Paper 003
Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationRack & Enclosure Systems
Knürr CoolTherm 4 35 KW Energy-efficient Server Cabinet Technology With Outstanding Benefits, To Minimize Energy Costs In The Data Center And Help Reduce Carbon Dioxide Emmisions Rack & Enclosure Systems
More informationRethinking Datacenter Cooling
Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationKnürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems
Knürr CoolAdd The universal retrofit solution against overheating in server racks Rack & Enclosure Systems Knürr CoolAdd When cold air is no longer enough! Data centers are subject to constant changes:
More informationWhite paper adaptive IT infrastructures
Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:
More informationRittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy
Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationOne Stop Cooling Solution. Ben Tam Business Development Manager
One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One
More informationEcotel Free Cool 5-15kW
Precision Air Conditioning Free-cooling Ecotel Free Cool 5-15kW + + Self-contained compact outdoor cabin cooler + + 100% free-cooling + + -48V DC supply option + + Easy serviceability (front component
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationRittal RiZone Data Centre Management Software
Rittal RiZone Data Centre Management Software The efficient route to peak performance within data centre infrastructure management RiZone The new link between IT and building What can the RiZone Data Centre
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationIBM Integrated Server Farm (ISF)
IBM Integrated Server Farm (ISF) TSS HW Services 05/04/2005 Data Centre Trends The density of computing power in a data centre environment has steadily increased in recent years. This trend is driven by
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More informationEaton Open Data Centre Solutions. Kari Koli
Eaton Open Data Centre Solutions Presenter: Stefan Coote Kari Koli 2008 Eaton Corporation. All rights reserved. Eaton Worldwide Founded in 1911 by J.O. Eaton World Headquarters in Cleveland, Ohio USA Customers
More informationIT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day
IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches
More informationCRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS
CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationRittal LCP T3+ High-availability IT cooling with no compromise
Rittal LCP T3+ High-availability IT cooling with no compromise LCP T3+, the climate for maximum availability... in the financial world Admittedly, we have no solution for overheated markets. But we do
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationNovember/December 2011
November/December 2011 Company is justifiably proud of its new facilities Helping companies plan, design, operate, and eventually refresh or repurpose their data centers more efficiently and effectively
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationModular data centres in containers
Modular data centres in containers 2 Modular data centres Contents IT Containers based on the modular principle.. 4 5 Edge Data Center... 6 7 RiMatrix Data Center Container IT Containers 50 100 kw... 10
More informationIBM Site Enablement Services
IBM Site Enablement Services Resilience for Your Data Centre 13/05/2005 Why Site Enablement Services? Hardware and Software are becoming increasingly dependable, but the environment in which they operate
More informationData Centre Infrastructure
Data Centre Infrastructure Aisle Containment Solution Aisle Containment is a popular way of cooling high density server installations. Aisle containment can work in two ways: Cold Aisle Containment where
More informationDENSITY SOLUTIONS BASED ON PULLED FIBRE TECHNOLOGY
Pub Club Meeting DATA CENTRE Fibre Connectivity Review HIGH DENSITY SOLUTIONS BASED ON PULLED FIBRE TECHNOLOGY Andrew Black Agenda Company and Technology Overview System Features Conventional LAN solutions
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD
R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More information