1 1
2 Rittal Cooling Solutions Presented by Adam Tropp 2
3 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3
4 Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Benefits Increased airstream management Supply air and return air do not mix Uniform distribution of cold air Higher delta T for increased efficiency Modular, scalable, and retrofittable Can be used with perimeter-based cooling Can be used with row-based cooling 4
5 Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. When to use aisle containment Issues with bypass air Issues with hot air recirculation Issues with hot spots Issues with uneven cold air distribution Issues with maximum cooling capacity * Image from 42U.com 5
6 Cooling strategies. Aisle containment. Hot and cold air distribution with and without containment. 6
7 Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Why aisle containment works Prevents hot and cold air from mixing Higher supply air temperatures Increased energy savings! Increased economizer hours Increased energy savings! Increased cooling efficiency Increased energy savings! 7
8 Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Cold aisle containment benefits Precise, targeted cooling Consistent air temperature Eliminates hot spots No raised floor required Minimal infrastructure requirements Creates easy retrofit installations Using only doors shows increased efficiency Prevents end of row recirculation 8
9 Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Hot aisle containment benefits Work environment is flooded with cold air Hot air can be ducted back to CRAC Increased efficiency Consistent air temperature Eliminates hot spots * Image from 42U.com 9
10 Cooling strategies. Aisle containment. * Image from EDS Plano TX * Image from CoreSite Los Angeles CA 10
11 Cooling strategies. Aisle containment. * Images from State Department Richmond VA 11
12 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 12
13 Cooling strategies. Chimney solution. Deployment Requirements Return vents for equipment not equipped with chimneys Return extensions for CRAC units Chimney installed on rack Drop ceiling installed in data center Benefits Increased airflow efficiency Minimal hot/cold air intermixing Increased cooling capacity Hot aisle containment 13
14 Cooling strategies. Chimney solution. 14
15 Cooling strategies. Chimney solution. 15
16 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 16
17 Cooling strategies. Airstream management. Rack-Level Air Containment Benefits Increased airflow efficiency Minimal hot/cold air intermixing Can be set into traditional raised floor Passive components No energy consumption Reduce point of failure Can accommodate blade chassis Cold aisle containment 17
18 Cooling strategies. Airstream management. 18
19 Cooling strategies. Airstream management. 19
20 Agenda Cooling Strategies Rittal Liquid Cooling Packages LCP Extend & LCP Passive CW LCP+ General Features LCP+ Cooling Applications Data Monitoring 20
21 Rittal Liquid Cooling Packages. LCP Passive CW Rear Door LCP Inline EC Open Loop LCP Hybrid EC LCP+ EC Hybrid Closed Loop 0 Tons Tons 0 kw kw 21
22 Rittal Liquid Cooling Packages. LCP Passive CW. Features Passive rear doors are designed to be installed as a replacement rear door for the racks on which they are installed A passive rear door simply has the fan system removed from the equation, allowing the server fans to do the necessary work of moving the air through the heat exchanger Maximum energy efficiency as there is no electrical power consumption Uses chilled water as the rejection medium HxWxD: 80x24x6 in. (2000x600x170 mm) 20 kw cooling capacity * Image from Sun Microsystems 22
23 Agenda Cooling Strategies Rittal Liquid Cooling Packages LCP Extend & LCP Passive CW LCP+ Cooling LCP+ General Features Applications Data Monitoring 23
24 Rittal Liquid Cooling Packages. LCP+ Cooling. Open Loop (Inline) Open front Open return More units are required to achieve N+1 Hybrid System Open front Closed return Better redundancy can be accomplished at row and room level Closed Loop Closed front Closed return Ultra high density Door release option must be used 24
25 Rittal Liquid Cooling Packages. LCP+ General Features. Features System Capacity: 30 kw Typical High efficiency heat exchanger developed to operate with 59 F chilled water Microprocessor controller LCD touch screen 2-way modulating valve 6 EC fans, N+1 design, hot-swappable Can be monitored remotely via web browser or SNMP via TCP/IP HxWxD: 80x12x48 in. (2000x300x1200 mm) 42 in. (1050 mm) depth also available Available in sand texture black or IBM white 25
26 Rittal Liquid Cooling Packages. 26
27 Rittal Liquid Cooling Packages. LCP+ General Features. Heat Exchanger 9.5 deep x 12.5 wide x 70 tall 27
28 Rittal Liquid Cooling Packages. LCP+ General Features. Electrical Design Wide input voltage range 208V, 230V, 400V EC fan technology 1 year ago: step motor technology Rated current: 6.5A 1 year ago: 11.5A Power rating: 1050W 1 year ago: 2650W 5 pole terminal block Fuses are easy accessible by opening the rear door Every unit comes high voltage tested EMC tested configuration 28
29 Rittal Liquid Cooling Packages. LCP+ General Features. 29
30 Rittal Liquid Cooling Packages. LCP+ General Features. Features Summary Auto-Temperature-Control: Cold air inlet temperature automatically controlled via integrated controller board Monitoring: Integrated controller with Rittal Basic CMC Intelligent sensor network: Fault tolerant sensors for water inlet/outlet temperatures, air inlet/outlet temperatures, water flow rates, leakage, etc. Fault tolerant controller boards and systems: In the case of electronic failures the valves will open and the fans will provide maximum airflow Alarm / events / sensor logging Three fan controller boards + one water controller board (individually fused) 30
31 Agenda Cooling Strategies Rittal Liquid Cooling Packages and their Energy Efficiency LCP Extend & LCP Passive CW LCP+ Cooling LCP+ General Features Applications Data Monitoring 31
32 Rittal Liquid Cooling Packages. Applications. Low Density (<5 kw) Application Networking switches, half-equipped server racks Products Fans Baffles Aisle Containment Mid Density (5-10 kw) Application Server and small blade servers Products LCP Inline LCP Hybrid Aisle Containment Chimney High Density (10+ kw) Application Blade servers and fully equipped server racks Products LCP Inline LCP Hybrid LCP+ Closed Loop Aisle Containment 32
33 Customers Using the LCP Family. 33
34 Agenda Cooling Strategies Rittal Liquid Cooling Packages Data Monitoring CMC III RiZone 34
35 Data monitoring. CMC III. CMC 3rd generation, the monitoring system for IT, building services, and industry. Monitors and measures up to 32 sensors. Enclosure and room temperature Humidity Vandalism Air flow Differential pressure Current, voltage, frequency, and energy Cooling units 35
36 Data monitoring. CMC III. CMC 3rd generation, the monitoring system for IT, building services, and industry. Control system for: Handles / Doors Fans Sockets Control system with: 8 digital inputs 4 relay outputs 2 energy outputs 36
37 Data monitoring. RiZone. RiZone is Rittal software for the monitoring and management of the IT infrastructure in data centers Power supply and reliability Cooling output and distribution Rack status Data center security (access, temperature, etc.) Efficiency and energy consumption Optimization Efficiency 37
38 Data monitoring. RiZone. RiZone Functions How efficient is the data center? How efficient is the UPS? How efficient is the chiller? How efficient is the cooling chain? How efficient is the power chain? What is the actual monthly / yearly power consumption? RiZone Benefits Higher visibility of systems inside the data center Historical data trending Making the data center more reliable and efficient 38
39 Data monitoring. RiZone. Definition of PUE/DCiE DCiE = Data Center Infrastructure Efficiency DCiE = IT Load (Server-Load) Entire Electrical Load of Data Center PUE = Power Utilization Effectiveness Entire Electrical Load of Data Center PUE = IT Load (Server-Load) PUE and Total Power Consumption are the basis for Data Center optimization. 39
40 Data monitoring. RiZone. Server, Infrastructure, And Total Power Consumption PUE CO 2 -Emission Power Costs 40
41 Any Questions? Thank you for attending and listening. 41
42 Rittal The System. Faster better worldwide. 42
Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationIT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day
IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationOne Stop Cooling Solution. Ben Tam Business Development Manager
One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationRittal LCP T3+ High-availability IT cooling with no compromise
Rittal LCP T3+ High-availability IT cooling with no compromise LCP T3+, the climate for maximum availability... in the financial world Admittedly, we have no solution for overheated markets. But we do
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationWhite paper adaptive IT infrastructures
Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationHigh Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach
High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationAvoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRiMatrix S Make easy.
RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power
More informationData Center Optimized Controls
Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.
More informationWhite Paper RiZone The Rittal Management Software for IT infrastructures
White Paper RiZone The Rittal Management Software for IT infrastructures Bernd Hanstein Markus Schmidt Thorsten Weller Copyright 2009 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg 35745
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationData Centre In A Box
Data Centre In A Box Data Centre In A Box Rittal s Data Centre In A Box replicates all of the key data centre capabilities but on a smaller scale. The Data Centre In A Box mitigates risk and provides compelling
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationSTULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling
STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationCooling Case Studies
Cooling Case Studies About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We produce affordable,
More informationIT monitoring. CMC III Monitoring system CMC III system representation CMC III system overview CMC III Processing Unit/Compact...
IT monitoring Monitoring system system representation...446 system overview...448 Processing Unit/Compact...450 sensors/accessories control units/ sensors...45 Interface for CMC II sensors...45 Access
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationEffectiveness and Implementation of Modular Containment in Existing Data Centers
WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com
More informationRittal RiZone Data Centre Management Software
Rittal RiZone Data Centre Management Software The efficient route to peak performance within data centre infrastructure management RiZone The new link between IT and building What can the RiZone Data Centre
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationTrends in Data Center Energy Efficiency
Trends in Data Center Energy Efficiency Presented by: Todd Boucher Better Building by Design 2012 1 Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationR4 Ventures LLC White Paper
R4 Ventures LLC PR ODUCT IN HARD COPY OR DIGITAL FORM. ALL OFFENDERS WILL BE SUED IN A COURT OF LAW. R4 Ventures LLC White Paper Comparison of energy consumption in kw per ton of cooling Real Time Data
More information) ) page 04. page 07. page 10. page 10. page 12. page 14. page 14. page 16. page 18. page 19. page 19. page 20. page 21. page 22
english version SAIFOR ADVANCED COOLING SOLUTIONS HDC AISLE HIGH DENSITY COOLING MDC AISLE HDC RACK MDC RACK CUBO KEEP-COOL HTRD CADU MAIN FEATURES CONFIGURATIONS & ACCESSORIES CUBO ACCESSORIES ) ) MEDIUM
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationLiebert. CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment LIEBERT CRV ROW-BASED COOLING System Overview The Liebert CRV is a multi-option, precision data center cooling solution
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1, 2N, 2(N+1) UPS topologies Large Free standing
More informationEnabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific
Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationZTE ZXCR Series DX In-Row Air Conditioning Product Description
ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationData center solutions for successful companies Cooling solutions
Data center solutions for successful companies Cooling solutions WeRackYourWorld.com great lakes cooling solutions Power and cooling are of prime importance to anyone working in a data center. As information
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationRittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy
Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More information