Metasys Integrator 300 Series Commissioning

Size: px
Start display at page:

Download "Metasys Integrator 300 Series Commissioning"

Transcription

1 Metasys Connectivity Technical Manual Section Technical Bulletin Issue Date 0900 TECHNICAL BULLETIN 300 Series Commissioning 300 Series Commissioning...3 Introduction...3 Key Concepts...5 Related Information... 5 Software... 5 Component Requirements... 5 Port Connections... 6 VT100 Terminal Emulator Setup... 8 Vendor Communication Tables (.VCT)... 8 Advanced Diagnostics... 9 Procedure Overview...10 Detailed Procedures...11 Inspecting the Installation Configuring a VT100 Terminal Emulator for the Unit Using the Commissioning Menu Setting Up Ports Installing DOWNPC and Vendor Communication Tables (.VCT) Downloading Vendor Communication Tables (.VCT) Connecting Vendor-Specific Cabling Adding Vendor Devices to the Network Deleting Vendor Devices Modifying Vendor Devices Verifying Vendor Device Communications Johnson Controls, Inc. Code No. LIT

2 2 Verifying Point Data Saving Configuration Restarting Software Troubleshooting...26 Verifying N2 Bus Communication Using the N2 Bus Checkout Tool Using the Serial Data Analyzers Collecting Screen Data Using Advanced Diagnostics Troubleshooting Commissioning Problems... 34

3 300 Series Commissioning Series Commissioning Introduction Commissioning the unit begins after the installation procedures are complete. For information on those procedures, refer to the 300 Series Installation Technical Bulletin (LIT ) in this manual. This document explains commissioning of 300 Series. Use this document with the vendor-specific application notes, which contain specific details about integrating vendor equipment (e.g., cable pinouts and point mapping tables). For information on vendor controllers, see vendor documentation (obtainable from your vendor representative). This technical bulletin describes how to: inspect the installation configure a VT100 Terminal Emulator for the unit use the Commissioning menu set up ports install DOWNPC and vendor communication tables (.VCT) download vendor communication tables connect vendor-specific cabling add vendor devices to the network delete vendor devices modify vendor devices verify vendor device communications

4 4 verify point data save configuration restart software After commissioning the hardware and software, map the vendor controller points to the Metasys controller. These procedures are described in the various network setup technical bulletins. For information on installing a unit and setting up a site, please refer to Table 1.

5 300 Series Commissioning 5 Key Concepts Related Information Table 1: Related Information Table 1 describes where to find information on how to perform tasks other than commissioning a unit. Description Tab Document Mounting an EN-EWC25-0 Enclosure Installing a Unit UPM Universal Packaging Module Technical Bulletin (LIT , FAN 636.3) 300 Series Installation Technical Bulletin (LIT , FAN 629.5) Point Mapping 300 Series Point Mapping Technical Bulletin (LIT , FAN 629.5) Specific Vendor Application Information The appropriate vendor application note (FAN 629.5) Software The firmware on the electronics board contains: commissioning software (for defining and downloading vendor configuration) vendor and N2 open protocol support software In addition, there is one CD-ROM containing the download software,.vct files, the N2 Bus Checkout Tool, and software models in DDL syntax for all applications. The Performance Support Tool (TL-PSTMIG-0) is also available. This tool is a full-featured electronic performance support system that supports the installing, commissioning, and servicing of the unit and standard Metasys Integrator applications. Component Requirements Besides the properly installed vendor equipment and Metasys Integrator unit, the following is required: software CD-ROM labeled Tables and Models. Use software CDs with a revision number that matches the firmware revision number shown on the top line of the commissioning interface.

6 6 N2 Bus for connecting the unit to the Metasys or Metasys Companion Network. See the N2 Communications Bus Technical Bulletin (LIT ) in the Metasys Companion Technical Manual (FAN 628.1) for information. RS-232 cable for connecting the unit to vendor equipment. You will find pinouts for this cable in the vendor-specific application note. (For example, cable pinouts for connecting Fireye equipment are in the Fireye Application Application Note [LIT ] located in the Metasys Connectivity Technical Manual [FAN 629.5].) portable DOS-compatible Personal Computer (PC) with hard drive (4 Mb available disk space) VT100 Terminal emulation software for commissioning and setup of panel or Performance Support Tool (PST) RS-232 cable for connecting the portable PC to the Metasys Integrator unit. The pinouts for this cable are described in Terminating Wire Connections in the 300 Series Installation Technical Bulletin (LIT ). Port Connections The unit has an N2 port, a commissioning port, and two vendor ports. It connects to the Metasys N2 bus via the N2 terminal block. An external 24 VAC power supply is connected to the power connector. 24 VAC N2 Port Commissioning Port (Port 1) Vendor Port A (Port 2) Vendor Port B (Port 3) 300_side.cdr Figure 1: Unit Connections

7 N Series Commissioning 7 Commissioning Port Cabling Figure 2 shows an overview of how to connect a Personal Computer (PC) with a VT100 Terminal Emulator to the commissioning port on the unit. PC with VT100 Terminal Emulator 9-pin to 9-pin Null Modem Cable 300cable Figure 2: Cabling Overview An RS-232 cable is required between the Commissioning Port and the portable PC s serial port, (for example, COM1). Direct connections between the unit and the portable PC can have a distance of up to 13 feet. Figure 1 shows the location of the commissioning port (Port 1) on the electronics board. Figure 3 shows cable pinouts for a portable PC with either a 9-pin serial port or a 25-pin serial port. If the PC has a 9-pin port, use this cable: If the PC has a 25-pin port, use this cable: Terminal Port on Serial Port 1 or 2 on Portable PC Terminal Port on Serial Port 1 or 2 on Portable PC DB-9 Female DB-9 Female DB-9 Female DB-25 Female Signal DCD RD TD DTR GND DSR RTS CTS Pin RS-232 (13 ft maximum) Pin Signal DTR TD RD DCD GND DSR CTS RTS Signal DCD RD TD DTR GND DSR RTS CTS Pin RS-232 (13 ft maximum) Pin Signal DTR TD RD DCD GND DSR CTS RTS intech9 Figure 3: Unit to PC Cable Pinouts

8 8 Vendor Port Cabling An RS-232 cable is required between Vendor Ports A and B (P2 and P3) and the vendor communications interface. For pinouts for this cable, see the vendor-specific application note for the vendor equipment you are integrating. The RS-232 cable length between the unit and the vendor communications interface may not exceed 50 feet. IMPORTANT: For baud rates faster than 19,200 bps, the serial cables must be shorter than 4 m (13 ft). VT100 Terminal Emulator Setup The Performance Support Tool (MS-PSTMIG-0) includes a VT100 Terminal Emulator that is already configured to communicate with the unit. You can use any terminal emulation software, provided that it supports the VT100 Terminal type. Table 2: VT100 Terminal Emulator Configurations Field Value Data Bits 8 Parity Stop Bits 1 Baud Rate Flow Control No Same baud rate as the unit (57,600 default) Software flow control Vendor Communication Tables (.VCT) The.VCT files contain information that allows the unit to communicate with vendor equipment. The unit can contain up to 36.VCT files. See the vendor-specific application documents for the name of the.vct files you will need to download.

9 300 Series Commissioning 9 Advanced Diagnostics You can view the unit s operational status by selecting Advanced Diagnostics from the main menu. Resetting the Unit Advanced Diagnostics in the main menu provides a reset function to restart the software. See the Restarting Metasys Integrator Software section in this document. The Error Log screen will help you to determine the cause of the last reset. Recommissioning the Unit The unit must be recommissioned in the following circumstances: upgrading to a new firmware revision (refer to Project Builder User s Guide [LIT ]) located in the M-Tool Manual [FAN 693] for information on how to download code to a unit) downloading updates to an application previously downloaded The downloaded vendor communication tables (.VCT files) are stored in backed-up Random Access Memory (RAM) (provided the battery is good). Error Log Pressing F2 from the Advanced Diagnostics screen can access the Error Log screen. The Error Log displays the cause of the last reset, as well as any other serious errors that may have occurred since the log was last cleared. Note: If the error log contains an Exception Occurred! error, contact the Field Support Center. The log contains up to 256 entries. Once the error log contains 256 entries, it will no longer add new entries. A full error log must be cleared by selecting Yes from the Clear Error Log prompt before it will log any more errors.

10 10 Procedure Overview Table 3: 300 Series Commissioning To Do This Inspect Installation Configure a VT100 Terminal Emulator for the Metasys Integrator Unit Use the Commissioning Menu Set Up Ports Install DOWNPC and Vendor Communication Tables (.VCT) Download Vendor Communication Tables (.VCT) Connect Vendor-specific Cabling Add Vendor Devices to the Network Delete Vendor Devices Modify Vendor Devices Verify Vendor Device Communications Verify Point Data Save Configuration Restart Software Follow These Steps: Remove the enclosure door. Examine the N2 terminal block. Check the wire insulation. Verify the wire polarity of the N2 Bus connection. Verify that the power cable is properly connected. Configure the VT100 Terminal Emulator. Connect the VT100 Terminal Emulator to the commissioning port. Press Enter when the option you choose is highlighted, or type the first letter of the menu option. From the Commissioning menu, select Port Configuration. Enter information in fields. Match the settings you enter to the vendor equipment settings. Save the information to database. Insert the CD-ROM labeled Tables and Models. Run the setup.exe file on the CD-ROM and follow the on-screen instructions. Make sure the portable PC is properly connected to Commissioning Port. Exit the terminal emulation software and go to DOS. Change the directory to the directory where you installed the DOWNPC software. Type DOWNPC. Accept the default serial port or select the port on the PC that connects to Commissioning Port. Press Enter when the correct port displays. Select the correct baud rate and press Enter. Select the.vct file to be downloaded. Press Y to confirm the file. When the download is complete, press any key. Restart the VT100 Terminal Emulation software. Enter F1 to refresh the main menu. Refer to the vendor-specific application notes for the cable pinouts. Assemble and connect the cabling. Disconnect the N2 Bus connection from unit until proper communication with the vendor equipment has been verified. From the Commissioning menu, select the Network Modify/Add/Delete option. Specify the network configuration for each of the vendor devices. To display the next screen of network addresses, press F3. To go to a specific N2 address, press F4. Save the information to database and return to the Commissioning menu. Move the cursor to the Interface Type field of the device you want to delete. Scroll through the options until a blank name is selected. Save the changes. Move the cursor to the Interface Type field of the device whose settings you want to change. Scroll through the options until a blank name is selected. Delete the device. Add the device. Save the changes. Display the Device Diagnostics screen. Enter the device s N2 address and press Tab or Enter twice. Press F2 to display the device specific data analyzer. Press F3 to view statistics for the next N2 address. Display the Vendor and N2 Port Diagnostics screen if no devices for the vendor port are online. Press F2 or F3 to display the port analyzer. From the Commissioning menu, select the Show Point Data option. Enter the point s network address, point type, and point address. To accept the default, press Enter. After you specify the point, press Enter. After viewing the points you wish to see, return to the Commissioning menu. Collect screen data. From the Advanced Diagnostics screen, press F3. Change the reset option. Press Enter to select and execute the option.

11 300 Series Commissioning 11 Detailed Procedures Inspecting the Installation To inspect the connections and wire terminations on the electronics board: 1. If the unit is enclosed, remove the enclosure door. 2. Examine the N2 terminal block for stray wire strands, loose screw terminals, and nicked, loose, or broken wires. 3. Check the wire insulation to ensure that it has not been stripped back so far as to cause a short, or that it is not tucked under a screw terminal. 4. Verify the wire polarity of the N2 Bus connection. (Check that each screw terminal of the N2 block has the same wire color entering as it does exiting.)! CAUTION: Ground yourself before handling the electronics board. 5. Verify that the power cable is properly connected. Configuring a VT100 Terminal Emulator for the Unit A pre-configured VT100 Terminal emulator is available in the Performance Support Tool (PST). You can use any terminal emulation software, provided that it supports the VT100 Terminal type. Terminal emulation software that has been successfully used is shown in Table 4. For more information on terminal emulation software setup, see the respective terminal emulator literature.

12 12 1. To configure a VT100 Terminal Emulator for the Metasys Integrator unit: Table 4: Terminal Emulation Software Setup Parameters Setting Value Command Used ProComm Plus for DOS by Datastorm Technologies, Inc. Baud Rate 57,600 Data Bits 8 Line/Port Setup (Alt-P) Parity Stop Bits 1 Flow Control Terminal Emulation None Xon/Xoff VT100 or VT102 Setup Facility, Terminal/General Options (Alt-S) ProComm Plus for Windows by Datastorm Technologies, Inc. Baud Rate 57,600 Data Bits 8 Parity None Setup/Extended Menu/Port Setting Stop Bits 1 Flow Control Xon/Xoff Current Terminal VT100 Setup/Extended Menu/Terminal Options HyperTerminal for Windows 95 by Hilgraeve, Inc. Bits Per Second 57,600 Data Bits 8 Parity None Stop Bits 1 Flow Control Xon/Xoff Emulation VT100 Properties/Settings Terminal for Windows by Microsoft Corporation Baud Rate 57,600 Data Bits 8 Properties/Phone Number/Configure/Port Settings Parity None Settings/Communications Stop Bits 1 Flow Control Xon/Xoff Emulation DEC VT100 Settings/Terminal Emulation 2. Connect the VT100 Terminal Emulator to the commissioning port (Port 1).

13 300 Series Commissioning 13 Using the Commissioning Menu When you connect a portable PC with VT100 Terminal emulation software to the unit, the Commissioning menu shown in Figure 4 appears. Use this menu to set up the unit. Commissioning Menu REL 9.00 Mon Aug 16, :47 Show Point Data Network Modify/Add/Delete Port Configuration Device Diagnostics Vendor and N2 Port Diagnostics Advanced Diagnostics Quit Standard Firmware F1 Refresh Menu Press F1 to refresh or to return to this menu at anytime. Figure 4: Commissioning Menu To move the highlight between menu options, use the arrow keys or the space bar. To select a menu option, press Enter when the first letter of the menu option is highlighted, or type the first letter of the menu option. (For example, type S to choose Show Point Data.)

14 14 Table 5: Commissioning Menu Options Menu Option Description Commissioning Show Point Data Displays data about available points in vendor device. Allows you to verify proper operation of vendor equipment (e.g., whether points are online and normal). Network Modify/Add/Delete Port Configuration Device Diagnostics Vendor and N2 Port Diagnostics Advanced Diagnostics Quit Allows you to add vendor devices to the network. You specify the interface type, vendor address, trunk, timeout, and poll delay for each N2 address. Allows you to set up ports for communication with the portable PC (commissioning device) and two vendor trunks. You specify baud rate, word length, stop bits, parity, and interface type for each vendor port. Displays statistics for communications between the Metasys Integrator unit and vendor device at a specified N2 address (e.g., writes, commands, and retries). Helps you verify network communication and diagnose problems. Allows you to reset statistics and activate serial data analyzer for a specific device. Displays communication statistics for each vendor port and the N2 port. Serial data analyzers, which display all activity on an entire vendor port, are also available. Displays the operational status of the unit, and provides access to the Error Log and Reset screens. Exits Commissioning menu.

15 300 Series Commissioning 15 Setting Up Ports To set up the port and baud rate for communication between the unit and the vendor devices: 1. From the Commissioning menu, select Port Configuration. The Port Configuration screen appears, as shown in Figure 5. Port Configuration REL 9.00 Mon Aug 16, :47 Port/Usage Baud Rate Word Length Stop Bits Parity Interface PO - N2 [ 9600] [8] [1] [None] [RS485] P1 - Commissioning [57600] [8] [1] [None] [RS232] P2 - Vendor A [ 9600] [8] [1] [None] [RS232] P3 - Vendor B [ 9600] [8] [1] [None] [RS232] F1 Cancel F2 Save Select baud rate (300,600,1200,2400,4800,9600,19200,38400,57600) Figure 5: Port Configuration Screen 2. Either type the information or use the space bar to scroll through the valid options to enter information in a field. To move between fields, press Enter or Tab, or use the arrow keys. The help line at the bottom of the screen displays information about the field where the cursor is. The N2 Port (P0) has fixed settings. Changing the P1 commissioning port settings can prevent you from communicating using the VT-100 Emulator software. For Vendor Ports A and B (P2 and P3), make sure the settings you enter match the vendor equipment settings. The vendor equipment settings are listed in the vendor-specific application note. If your application has an RS-485 interface, set the vendor port to RS-485, and use an external RS-232 to RS-485 converter. This converter is described in the vendor-specific application note. 3. Press F2 to save the information to database. The Commissioning menu appears.

16 16 Installing DOWNPC and Vendor Communication Tables (.VCT) Install the DOWNPC software on your portable PC before downloading the.vct files. Have the CD-ROM labeled Tables and Models on hand. To install the download software on your portable PC: 1. Insert the CD-ROM labeled Tables and Models in the CD-ROM drive. 2. Run the setup.exe file on the CD-ROM and follow the on-screen instructions. Alternatively, you can manually copy the files that you need from the Tables and Models CD-ROM. If you do not know what files you need, run setup.exe. Downloading Vendor Communication Tables (.VCT) After installing the DOWNPC software, download the appropriate.vct files to the unit. Up to 36.VCTs may be downloaded. To download the.vct files: 1. Make sure the portable PC is properly connected to Metasys Integrator commissioning port. 2. Exit the terminal emulation software and go to DOS. 3. Change to the directory where you installed the DOWNPC software. The default is C:\\MIG9\Tables. 4. Type DOWNPC (not case sensitive). The following appears: Download Utility (c) Johnson Controls Inc. Revision 9.00 Serial Port: COM1 (COM1 or COM2) Select Baud: (9600, 19200, 38400, 57600) File Name:.VCT (Select from the list) 5. Accept the default (COM1) serial port or type COM2 to select the port on the PC that connects to commissioning port. Press Enter when the correct port displays.

17 300 Series Commissioning Select the correct baud rate to match the baud rate of the commissioning port on the unit and press Enter. The screen shown in Figure 6 appears, displaying currently available vendor communication table files. Download Utility (c) Johnson Controls Inc. Revision 9.00 Serial Port:COM1 (COM1 or COM2) Select Baud:57600 (9600, 19200, 38400, 57600) File Name:.VCT (Select from the list) Vendor Communication Table Files (.VCT) AD_AUTPX CA_DUAL CA_S2100 CA_SIGL CB_HAWK CB_NHBP CB_NHGP CC_FHVC CC_FRPC FE_E501 FE_E503 GE_EPIC IQ_1000 IQ_ADVA IQ_AEM IQ_AEMDI IQ_AEMDP IQ_DATA IQ_GENE LI_LEV0 LI_LEV1 LI_LEV2 MS_CHILL SG_CENC SG_RCPC SG_RTUA SG_UVNT SG_WSHP SG_XLWC SQ_CM100 TA_FHVC TS_8650 TS_8670 VM_EVPCD VM_RECIP VM_SSCRW M_TSCRW..End.. Page 1 of 1 Figure 6: Download Screen 7. Select a.vct file to download in one of two ways: Type the name of the file to download in the File Name field. This name must match the name in the.vct file list displayed on the Download screen. Select the file name from the.vct file list by pressing the Tab key once, then using the function keys listed in Table Press Enter. The screen shown in Figure 7 displays for.vct files, briefly describing the selected file. Table 6: Download Select Function Keys Key Tab Backspace A through Z PGUP (Page Up) PGDN (Page Down) Space Bar F1 Key or Esc Function Highlights the next file name in the list. Highlights the previous file name in the list. Highlights the first file name beginning with that letter, if one exists. Displays the previous page of file names. Displays the next page of file names. Highlights the next file name in the list. Exits without downloading.

18 18 Download Utility (c) Johnson Controls Inc. Revision 9.00 Set to Download table to Integrator Panel Carrier DC Chiller OK To Download (Y/N) Figure 7: Download Confirm Screen 9. Press N to return to the.vct file name list shown in Figure 6. Press Y to begin downloading. The screen in Figure 8 displays. Download Utility (c) Johnson Controls Inc. Revision 9.00 Serial Port: COM1 Select Baud: Word Length: 8 Stop Bits: 1 Parity: None File Name: CA_DUAL.VCT Table Size: 1048 ooooooooooooooooooooooooooooooooooooooooo 0 Percent Complete Figure 8: Download in Progress Screen The solid bar moves right across the screen as the download continues. When complete, the following appears: Download completed without errors Press Any Key To Exit Download Note: If there is an error, attempt the download again. 10. Press any key. To download another table, type DOWNPC and start the procedure again. Note: Do not download the same table more than once. A single table can be used for multiple vendor devices of the same type. 11. Restart the VT100 Terminal emulation software.

19 300 Series Commissioning Press F1 to refresh the Commissioning menu. Connecting Vendor-Specific Cabling To connect vendor-specific cabling: 1. Refer to the vendor-specific application notes for the cable pinouts. 2. Assemble and connect the cabling between the unit and the vendor equipment. Adding Vendor Devices to the Network See the vendor-specific application note for the correct vendor address and timeout values. To add a vendor device to the network, you must have already downloaded its vendor communication table (.VCT file). To add the device to the network: 1. To avoid annoying messages at the Metasys system, disconnect the N2 Bus connection from the unit until proper communication with the vendor equipment has been verified (see Verifying Vendor Device Communications and Verifying Point Data in this document). 2. From the Commissioning menu, select the Network Modify/Add/Delete option. The screen shown in Figure 9 appears. Network Modify/Add/Delete REL 9.00 Mon Aug 16, :47 N2 Address Interface Type Vendor Address Port Timeout Poll Delay Retry 0 [ ] [ ] [A] [ ] [ ] [ 3] 1 [Carrier DC Chiller] [A ] [A] [ 8000] [ 550] [ 3] 2 [Carrier SC Chiller] [B ] [A] [ 8000] [ 550] [ 3] 3 [CB Hawk Boiler Ctl] [0,1 ] [B] [ 5000] [ 55] [ 3] 4 [ ] [ ] [A] [ ] [ ] [ 3] 5 [ ] [ ] [A] [ ] [ ] [ 3] 6 [ ] [ ] [A] [ ] [ ] [ 3] 7 [ ] [ ] [A] [ ] [ ] [ 3] Available Vendor Interface Types Carrier DC Chiller Carrier SC Chiller CB Hawk Boiler Ctl F1 Cancel F2 Save F3 More F4 Go to N2 Address Select a vendor interface type from the list Note: Make sure these N2 addresses match the N2 addresses defined at the Metasys system. Figure 9: Network Modify/Add/Delete Screen

20 20 Deleting Vendor Devices Modifying Vendor Devices 3. Specify the network configuration for each of the vendor devices. To enter information in a field, you can either type the information or use the space bar to scroll through the valid options. To move between fields, press Enter or Tab, or use the arrow keys. The help line at the bottom of the screen displays information about the field where the cursor is. Note: N2 Address 0 can be defined at the unit, but cannot be used at the Metasys system. 4. To display the next screen of network addresses, press F3. Pressing F3 also saves the current screen of data. 5. To go to a specific N2 address, press F4. Pressing F4 will save the current screen of data. 6. To save the information to database and return to the Commissioning menu, press F2. To delete a device: 1. Move the cursor to the Interface Type field of the device you want to delete. 2. Press the space bar to scroll through the options until a blank name is selected. 3. Press F2 to save the changes. Note: If a scan is in progress for a deleted device, it will be deleted after the scan is complete. To modify the settings for a vendor device, delete the device and add the device with the new settings: 1. Move the cursor to the Interface Type field of the device whose settings you want to change. 2. Press the space bar to scroll through the options until a blank name is selected. 3. Press F2 to delete the device. 4. Add the device by filling in the new settings. 5. Press F2 to save the changes. Note: If communication is still in progress with the device deleted in Step 3, the unit will display the following error message: cannot add until previous delete is completed.

21 300 Series Commissioning 21 Verifying Vendor Device Communications To verify vendor device communication: 1. Display the Device Diagnostics screen (Figure 10). 2. Enter the device s N2 address and press Tab or Enter twice. 3. If the vendor device is offline, press F2 to display the device specific data analyzer to determine if there is any communication. 4. Press F3 to view the statistics for the next N2 address that has been defined at this unit. 5. If no devices for the vendor port are online, display the Vendor and N2 Port Diagnostics screen (Figure 11) for vendor port statistics. 6. From the Vendor and N2 Port Diagnostics screen, press F2 or F3 to display the port analyzer. This will help you to determine if there is any communication with any vendor device on the port. Device Diagnostics REL 9.00 Mon Aug 16, :47 N2 Address [ 1] Reset Statistics [No ] CB Hawk Boiler Ctl at N2 Address [ l] on Vendor Port A: Online [Yes] Transmissions/Minute [ 5] Writes [ 17] Scan Time (seconds) [ 12] Commands [ 2] Retries [ 1] Offline [ 0] Errors [ 1] F1 Cancel F2 Data Analyzer F3 Next N2 Address Select an N2 address (0-255) Figure 10: Device Diagnostics Screen

22 22 Port Diagnostics REL 9.00 Mon Aug 16, :47 Reset Statistics [No ] Vendor Port A Vendor Port B N2 Port Transmissions/Minute [ 38] [ 0] Scan Time (seconds) [ 2] [ 0] Port Buffer Overruns [ 0] [ 0] [ 0] LINE STATUS ERRORS *Suspect Bytes Received [ 0] [ 0] [ 0] *Framing Errors [ 0] [ 0] [ 0] *Parity Errors [ 0] [ 0] F1 Cancel F2 Port A Analyzer F3 Port B Analyzer Select from (No, Yes) Figure 11: Vendor and N2 Port Diagnostics Screen For additional information on diagnostics fields, see Table 7 and Table 11. For additional information on the serial data analyzer, see the Using the Serial Data Analyzers section in this technical bulletin.

23 300 Series Commissioning 23 Table 7: Diagnostics Fields Field Description Normal Readings Device Vendor and N2 Port Vendor Device Statistics for Selected N2 Address N2 Address Online Writes Selected N2 Address (with vendor table name) Indicates whether device is currently online Number of general communications messages Commands Number of commands to device X Retries Errors Offline Reset Statistics Transmissions Per Minute Point Scan Time (seconds) Port Buffer Overruns LINE STATUS ERRORS: Suspect Bytes Received Framing Errors Parity Errors Number of retries for polls and writes for online devices only Number of times a returned message from vendor device had an error (for example, a CRC or checksum error) Number of online to offline transitions for device at this vendor address Yes 0 is ideal. X 0 is ideal. X 0 is ideal. X Allows you to reset statistics to zero No is default. X X Port Statistics Number of polls and writes that occurred in last minute Number of seconds it takes for all points on this vendor trunk to be scanned Number of Vendor Port A, Vendor Port B, and N2 Port input buffer overruns on the UART s First In-First Out (FIFO) Number of line status errors in general Number of line status errors caused by framing errors Number of line status errors caused by parity errors Depends on vendor device response time and poll delay Depends on transmissions per minute, vendor device response time, and poll delay 0 is ideal. X 0 is ideal. X 0 is ideal. X 0 is ideal. X X X X X X X X

24 24 Verifying Point Data Before mapping vendor points to the Metasys Network, verify that vendor equipment and processes are operating properly. To view point data use the Show Point Data screen, which displays current point data in the vendor controllers: 1. From the Commissioning menu, select the Show Point Data option. The following fields appear, prompting you to specify a point: N2 Address [ 1] Point Type [AI ] Point Address [ 1] 2. Enter the point s network address, point type, and point address. To accept the default, press Enter. (If the cursor is in the N2 Address field, press Enter three times to accept the default.) To move between fields, press Enter or Tab, or use the arrow keys. To scroll through the Point Type options (AI, BI, AO, BO, ADF, ADI, BD), press the space bar repeatedly when the cursor is in the Point Type field. 3. After you have specified the point, press Enter. The Show Point Data screen appears. Figure 12 shows an example of a Show Point Data screen for an AI point. (Each Show Point Data screen displays data appropriate to the point type.) Show Point Data REL 9.00 Mon Aug 16, :47 Network Address: N2 Address [ 1] Point Type [AI ] Point Address [ 1] N2 Address [ 1] Point Type [AI ] Point Address [ 1] Point Label LCW TEMP Value High Alarm Limit Undefined High Warning Limit Undefined Differential Undefined Low Warning Limit Undefined Low Alarm Limit Undefined COS Enable False Alarm Enable False Warning Enable False Unreliable False Override Active False Out-of-Range High False Out-of-Range Low False COS Status Normal F1 Cancel F3 More Select a N2 network address (0-255) Figure 12: Show Point Data Screen

25 300 Series Commissioning Press F3 More to view the next point, which scrolls through the points. When the last point of a type is reached, the first point of the next type is displayed. 5. Press F1 Cancel to return to the Commissioning menu. Saving Configuration Record the settings for configuration. You can do this manually, or use a screen capture utility. See Collecting Screen Data in the Troubleshooting section of this document for additional information. Restarting Software To restart software: 1. From the Advanced Diagnostics screen in the main menu, press F3. The Reset screen displays. 2. Change the reset option by using the space bar. 3. Press Enter to select and execute the option you choose.

26 26 Troubleshooting This section provides troubleshooting information for the commissioning process. Verifying N2 Bus Communication The N2 network is confirmed when you invoke the head-end workstation software (for example, Metasys Operator Workstation [OWS]), define vendor devices and points, and display information about the points on the workstation screen. If something does not work correctly: 1. Verify that the vendor equipment is energized. 2. Verify that the vendor points are appropriately defined in software. 3. Recheck the N2 wiring connections throughout the network, including the N2 terminal blocks on the electronics board. Using the N2 Bus Checkout Tool Some jobs require extensive end-to-end checkout on site with vendor equipment and a supervisory system. The N2 Bus Checkout Tool allows engineers to do the checkout at the Metasys Integrator panel with a tool that uses the same table loaded in the panel. You can check out the vendor system and its interface with the unit all the way from the Metasys Integrator N2 terminals to the vendor equipment. The user interface accepts any N2 address and a Release 5.0 or greater.vct table as inputs.

27 300 Series Commissioning 27 The N2 Bus Checkout Tool requires the following: a laptop with an available serial port an RS-232 to RS-485 converter (You can use the MM-CVT101. The cable for the MM-CVT101 is defined in Figure 13.) Serial Port 1 or 2 on Portable PC DB-9 Female RS-232 Connector on MM-CVT101 Converter DB-25 Male Signal RD TD GND RTS Pin RS-232 Pin Signal RD TD GND RTS (50 ft maximum) intconv Figure 13: Cable Pinouts Between Unit and Converter The cable connects the serial port on the laptop to the 25-pin RS-232 serial connector on the MM-CVT101. The RS-485 (N2) connection from the MM-CVT101 is then attached to the panel N2 connections. See Terminating Wire Connections in Metasys Integrator 300 Series Installation Technical Bulletin (LIT ) for additional information. Table 8 shows the available mouse sensitive operation fields displayed between the dashed delimiter lines. Click the mouse on these items to execute the function. Table 8: Mouse Sensitive Function Keys Function Key AI BI AO BO ADF ADI BD RSt Operation Performed Select AI points for display. Select BI point for display. Select AO points for display. Select BO points for display. Select ADF points for display. Select ADI points for display. Select BD points for display. Reset N2 statistics. NuAdr Select a new N2 address (1 to 255). NuVct Pgdn PgUp Exit Select a new.vct file name. Page down the points list. Page up the points list. Return to DOS (the Alt-X key does the same).

28 28 Table 9 shows the statistics that are displayed on the right-hand side of the screen. The N2 Statistics values will roll over at Table 9: Point Counts and N2 Statistics Point Counts AI BI AO BO ADF ADI BD N2 Statistics Poll Data OvrC RelC COSs NAks CksE LnSE RTry OffL Description Count of Analog Inputs in current table Count of Binary Inputs in current table Count of Analog Outputs in current table Count of Binary Outputs in current table Count of Analog Data Floats in current table Count of Analog Data Integers in current table Count of Binary Data (Byte) in current table Description Number of polls Number of data requests Number of override commands Number of release commands Number of change-of-state responses Number of negative acknowledge responses Number of checksum errors Number of line status errors Number of retries Number of offline occurrences Figure 14 shows a screen snapshot of the tool in use. N2 Bus Checkout Tool at address 1 using rileyhsp.vct AI BI AO BO ADF ADI BD RSt NuAdr NuVct PgDn PgUp Exit AO PICU 1 Supply Airflow Setpoint... -Pt Count- AO PICU 1 Min Exhaust Airflow Setpoint... AI 30 AO PICU 2 Supply Airflow Setpoint... BI 16 AO PICU 2 Min Exhaust Airflow Setpoint... AO 32 AO Anteroom Supply 1 Airflow Setpoint... BO 0 AO Anteroom Supply 2 Airflow Setpoint... ADF 0 AO Anteroom Min Exhaust Airflow Setpoint. ADI 0 AO PICU 1 Pressure Setpoint... BD 0 AO PICU 2 Pressure Setpoint... AO Anteroom Pressure Setpoint... -N2 Stats- AO Iso-Tek 0 High Alarm Setpoint... Poll 0 AO Iso-Tek 0 Low Alarm Setpoint... Data 0 AO Iso-Tek 1 High Alarm Setpoint... OvrC 0 AO Iso-Tek 1 Low Alarm Setpoint... RelC 0 0 AO Iso-Tek 2 High Alarm Setpoint... COSs 0 0 AO Iso-Tek 2 Low Alarm Setpoint... Naks 0 AO PICU 3 Supply Airflow Setpoint... CksE 0 AO PICU 3 Min Exhaust Airflow Setpoint... LnSE 0 X AO PICU 4 Supply Airflow Setpoint... RTry 100 Figure 14: N2 Bus Checkout Tool Screen

29 300 Series Commissioning 29 To perform the check: 1. Remove all N2 connections other than the RS-485 connection from the MM-CVT101 that is attached to the panel. 2. Start the N2 Bus Checkout Tool from the DOS command line by typing the command N2CHECK 1 for COM1 or N2CHECK 2 for COM2. 3. Click NuAdr to select an N2 address. 4. Click NuVct to select the same.vct that you downloaded into the panel. 5. Use the mouse to select the point type you want to inspect or command. Command AO and BO point types by clicking on the point line and entering a new value. Click on the point line and pressing the Esc key to perform a release command. 6. Press the Alt+X key to exit to DOS. Using the Serial Data Analyzers The commissioning software provides serial data analyzers for troubleshooting communication between the unit and the vendor devices. The serial data analyzers collect data from the devices on a vendor port. This aids in establishing whether or not communication is occurring. To access the device specific serial data analyzer from the Device Diagnostics screen, enter F2. To access the vendor port serial data analyzer from the Port Diagnostic screen, enter F2 for Vendor Port A or F3 for Vendor Port B. To pause the flow of data, press F4. To resume the flow of data, press F4 again. To exit the serial data analyzer, press F1. To return to the Diagnostics screen, press F2. To view a log of the last abnormal events that occurred on a particular port, press F3 from that port s serial data analyzer screen. To record the data being sent to the screen in a text file, use the logging capabilities of your VT100 Terminal emulation software (for example, ProComm Plus Log File function). Note: Recording more than one screen of data requires ProComm Plus for DOS or the Performance Support Tool. If you need help interpreting the data, call your product supplier.

30 30 Collecting Screen Data You may need to collect screen data when getting help from a technical support person. The PST or ProComm Plus for DOS Version 2.01 is required for log file captures. We do not recommend ProComm Plus for Windows, HyperTerminal for Windows 95 by Hilgraeve, Inc., and Terminal for Windows by Microsoft Corporation. Table 10 shows the available Capture Data commands. Table 10: Capture Data Commands Command Used Description of Operation Performance Support Tool VT100 Emulator (Ctrl-I) Starts VT100 Terminal Emulator. Log File Pause Logging Resume Logging Create log file name, or browse to select an existing log file. Check Append to add data to end of an existing file. Click OK to start capture. All screens opened after clicking OK are saved to the log file. Pauses log file capture. Resumes log file capture. Stop Logging Stops log file capture. ProComm Plus for DOS by Datastorm Technologies, Inc. Screen Snapshot (Alt-G) Log File On (Alt-F1) System will reply: Enter log filename, or CR for default:. The default log file name is PCPLUS.LOG. The status line will show LOG OPEN. Log File Off (Alt-F1) The status line will show LOG CLOSED. The file can be found at C:\PCPLUS\PCPLUS.LOG if default file name was used. ProComm Plus for Windows by Datastorm Technologies, Inc.* Online / Capture (Alt-F1) Status line shows Capture File Opened - pwxx.cap where pwxx is the capture file name defaulted by the system. Online / Capture (Alt-F1) Status line shows Capture File Closed File can be found at C:\PROWIN2\CAPTURE\PWxx.CAP * Captures only the first screen of analyzer data.

31 300 Series Commissioning 31 Performance Support Tool To collect data with the PST VT100 Terminal Emulator: 1. Press the F1 key to return to the Commissioning menu. 2. Click on the Data Logging menu of the VT100 Terminal Emulator. 3. Click on Start. 4. Enter a log file name and click OK to start the log file capture. We recommend giving the file name a.log extension (filename.log) to make it easier to find later. Note: Click the Browse button to select the path to the log file. You can name the log file anything and save it anywhere. 5. Cycle through each menu item starting with Port Configuration and Network Modify/Add/Delete for each N2 address for which data must be collected. 6. For each N2 address: a. Bring up the Diagnostic menu for the N2 address. This displays the current number of offlines, retries, and errors. These statistics are available only for previously defined N2 addresses. b. Set the Serial Data Analyzer to Yes. This will show the actual communications between the vendor device and the panel. c. Bring up the Diagnostic menu for the N2 address again. This displays the number of offlines, retries, and errors that can be used to determine how many of these errors occurred while saving the analyzer data. Note: Try to ensure that the collected data includes a sample of the problem you want to investigate. For example, if you are collecting data to determine the cause of offline/online transitions, ensure that the number of offlines has increased. If not, continue to collect analyzer data. 7. When all the data has been collected, click on the Data Logging menu of the VT100 Terminal Emulator. 8. Click Stop to end the log file capture. Note: The log file can be found at C:\Program Files\Johnson Controls\ Performance Support Tool\MIGData.log if the default directory and recommended file name extension were used. Otherwise, the file will appear in the directory you chose.

32 32 9. Send these files to your technical support representative via The Advisor or . ProComm Plus for DOS To collect the data with ProComm Plus for DOS: 1. Press the F1 key to return to the Commissioning menu. 2. Press Alt-F1 to start the log file capture. Note: You can name the log file if you choose; otherwise, the default name is PCPLUS.LOG. 3. Cycle through each menu item starting with Port Configuration and Network Modify/Add/Delete for each N2 address for which data must be collected. 4. For each N2 address: a. Bring up the Diagnostic menu for the N2 address. This displays the current number of offlines, retries, and errors. b. Set the serial data analyzer to Yes. This will show the actual communications between the vendor device and the panel. c. Bring up the Diagnostic menu for the N2 address again. This displays the number of offlines, retries, and errors that can be used to determine how many of these errors occurred while saving the analyzer data. Note: Try to ensure that the collected data includes a sample of the problem you want to investigate. For example, if you are collecting data to determine the cause of offline/online transitions, ensure that the number of offlines has increased. If not, continue to collect analyzer data. 5. When all the data has been collected, press Alt-F1 to close the log file and end the capture. Note: The log file can be found at C:\PCPLUS\PCPLUS.LOG if the default file name was used. Otherwise, the file appears in the PCPLUS directory under the name you assigned it. 6. Send these files to your technical support representative via The Advisor or .

33 300 Series Commissioning 33 Using Advanced Diagnostics Table 11 provides information on advanced diagnostics fields. Table 11: Advanced Diagnostics Fields Field Description Normal Readings 300 Flash Statistics MAC Address Startup Checksum/Revision Boot Code Checksum/Revision Main Code Checksum* Softscope Enabled/Disabled on Vendor Port A or B Softscope Stop at Startup? Similar to a serial number, every 300 Series has a unique 6-byte Media Access Control (MAC) address (displayed in dotted-decimal notation). Identifies the code that runs at initial power up or after a reset. Identifies the code that runs when the Metasys Integrator unit is reset to allow new main code to be downloaded. Checksum for the code. Indicates if debugging tool is enabled. If enabled, vendor communications is disabled on that port. If Yes, the unit will stop running after it is reset xxx.xxx.xxx Disabled No is default. Date of Manufacture Last four numbers represent the year that the unit was manufactured. Leading numbers represent the day of the year. CPU Utilization CPU Usage Percentage of total task utilization 0 to 100 Allocated Memory Statistics** Current Free** N2 Database Using Memory available for tables and N2 database in bytes, and as a percentage of the total allocated Memory used for the N2 database in bytes and as a percentage of total allocated. The N2 database stores point data for all vendor points. Memory is used as follows: 119 bytes overhead for each N2 address added, plus: 27 bytes for each AI point 5 bytes for each ADF point 3 bytes for each BI point 3 bytes for each BO point 3 bytes for each ADI point 7 bytes for each AO point 2 bytes for each BD point VCTs Using Amount of memory used for the downloaded vendor communication control tables in bytes and as a percentage of total allocated * The main code checksum can be verified to determine if this is standard vs. custom code. Also see the Commissioning menu, which indicates standard or custom firmware is downloaded. ** The current free allocated memory should not be less than 10%.

34 34 Figure 15 shows an example of an Advanced Diagnostics screen. Advanced Diagnostics REL 9.00 Sun Aug 15, : MAC Address: Date of Manufacture: [ ] Startup Checksum: [23E7] Startup Revision: [1.1] Boot Code Checksum: [6DB8] Boot Code Revision: [1.1] Main Code Checksum: [787B] SoftScope ENABLED on Vendor Port B. SoftScope Stop at Startup? [No]... : : : CPU Usage: [ 3.8] % : : : :...:... : M : ALLOCATED (Bytes) (%) : ACQUIRED (Bytes) (%) : : E : Current Free [475356] 95.1 : Current Free [150000] : : M : N2 Database Using [ 160] 0.0 : Largest Block Free [150000] : : O : VCTs Using [ 1599] 0.3 : Total [150000] : : R : Total [500000] : Lowest Free [149878] 99.9 : : Y : Lowest Free [475356] 95.1 : : :...:...:...: F1 Cancel F2 Error Log F3 Reset Press <TAB> or <ENTER> to refresh statistics. Figure 15: Advanced Diagnostics Screen Example Troubleshooting Commissioning Problems Table 12 lists some possible commissioning problems and solutions. Table 12: Possible Commissioning Problems Condition Problem Solution VT100 Terminal Emulation software is unable to connect to the Metasys Integrator unit. Continued on next page... There are incorrect communication settings. There is incorrect cabling. Verify that the portable PC s settings match the commissioning port settings (baud rate, bits, stop bits, parity). The default for the commissioning port is 57600,8,1,N. Verify that the Terminal emulation mode is set to VT100. Verify that the portable PC is connected to the commissioning port (P1 connector) on the electronics board. Verify that the RS-232 cable pinouts are correct as described in Figure.

35 300 Series Commissioning 35 Condition (Cont.) Problem Solution The unit cannot talk to the vendor device. Port 2 or Port 3 LED remains on. Point is unreliable (use Show Point Data menu option). Point values are incorrect, but point is reliable. The unit resets automatically. The unit resets cyclically. Continued on next page... Cable is not connected. Incorrect cable is being used. Incorrect settings are on the Port Configuration screen. An incorrect vendor address is entered in the Network Modify/Add/Delete screen. Softscope might be enabled for that port. The device is offline. The point does not exist at the vendor device. Custom firmware has not been downloaded. Commissioned with an incorrect.vct. Vendor equipment setup is incorrect. The unit has encountered a serious software error. The unit has encountered a serious software error. Verify that the cables are properly plugged into vendor ports. Verify that the vendor device is connected and powered up. Verify that the cable between the unit and vendor device matches the cable specified in the vendor application document. Verify that the vendor port setup matches the settings specified in the vendor application document. Verify that the vendor address entered in the Network Modify/Add/Delete screen is left justified. Call Field Support Center. Verify that the device is online. Verify that the point exists at the vendor device. If using a custom application that requires custom firmware, verify that this firmware has been downloaded. Verify that the correct vendor communication table (.VCT) is being used. Refer to vendor documents. View the Error Log screen (from the Advanced Diagnostics screen, press F2). Call the Field Support Center. Locate a blue button labeled SW2 on the unit circuit board. You must watch the LEDs to determine when to press the blue button. The startup sequence begins when all the LEDs light up at the same time. Each LED then lights up, individually. When the last LED turns off, wait about two seconds and then press the button. The startup sequence then should start over. When this sequence is complete, the red Fault LED turns on. Turn the unit off and then back on. It should come up with the factory default settings (no VCTs downloaded). Press A, then F2 to view the Error Log, and call the Field Support Center.

36 36 Condition (Cont.) Problem Solution Device repeatedly toggles online and offline. Database memory is not retained. Continuous line status errors occur for an RS-485 vendor trunk. Commissioned with incorrect.vct. The 485 converter is malfunctioning. The vendor device does not support commands. Battery may be dead. See the 300 Series Installation Technical Bulletin for startup Light-Emitting Diode (LED) battery failure indication. The vendor communication trunk is experiencing excessive noise or is unbalanced. Verify that the correct application for the device is being used. If a 485 or 422 port-powered converter is being used, use a converter that includes a power supply. If you are sending commands, verify that the device is commissioned to support commands. Be aware that the Auto Restore functions of Metasys NCM, Companion, or N30 will resend commands as devices report online. Replace the battery and recommission the Metasys Integrator unit. Verify End-of-Line (EOL) resistor and cable shield requirements and installation. Controls Group FAN E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Release 9.0 Milwaukee, WI Printed in U.S.A.

Metasys Integrator GE Lighting Application

Metasys Integrator GE Lighting Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details

More information

Metasys Integrator Multistack Application

Metasys Integrator Multistack Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details

More information

Metasys Integrator Northern Application

Metasys Integrator Northern Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details

More information

Metasys Integrator Allen-Bradley Custom Application

Metasys Integrator Allen-Bradley Custom Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Allen-Bradley Custom Application Introduction Page 3 Application

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

Metasys Integrator Powerware Application (previously the Exide Application)

Metasys Integrator Powerware Application (previously the Exide Application) Application Note Issue Date 11/01/01 APPLICATION NOTE Metasys Integrator Powerware Application (previously the Exide Application) lntroduction Page Application Details Component Requirements 4 Vendor Contact

More information

Metasys Integrator Graham Application

Metasys Integrator Graham Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3

More information

Metasys Integrator United Power Application

Metasys Integrator United Power Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator United Power Application lntroduction Page 3 Application Details

More information

N30 Supervisory Controller Installation

N30 Supervisory Controller Installation Technical Bulletin Issue Date July 25, 2002 N30 Supervisory Controller Installation N30 Supervisory Controller Installation...2 Introduction... 2 Key Concepts... 3 Installation Site Considerations... 3

More information

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4 FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in

More information

CF Terminal User s Guide

CF Terminal User s Guide Table of Contents CF Terminal User s Guide Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 Chapter Organization...1-2 Questions or Comments...1-2 Chapter 2 Getting Started...2-1

More information

NDM Configurator. Introduction Page *3. Configuration Files 5. Downloading 17 APPLICATION NOTE

NDM Configurator. Introduction Page *3. Configuration Files 5. Downloading 17 APPLICATION NOTE System 9100 Technical Manual 636.4 Network Communications Section Application Note Issue Date 0896 APPLICATION NOTE NDM Configurator Introduction Page *3 Configuration Files 5 Hardware Requirements *5

More information

Downloading Metasys Integrator 300 Series Code

Downloading Metasys Integrator 300 Series Code M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key

More information

APPLICATION NOTE JC/85

APPLICATION NOTE JC/85 Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software

More information

Product Specification for CANbus to DeviceNet Transducer Gateway

Product Specification for CANbus to DeviceNet Transducer Gateway XG CANbus to DeviceNet Transducer Gateway April, 00 Product Specification for CANbus to DeviceNet Transducer Gateway The XG CANbus to DeviceNet Temposonics Gateway gathers position information from as

More information

FX Tools Software Package - FX CommPro N2 User s Guide

FX Tools Software Package - FX CommPro N2 User s Guide User s Guide FX CommPro N2 Issue Date September 25, 2008 FX Tools Software Package - FX CommPro N2 User s Guide FX Tools Software Package FX CommPro N2... 3 Introduction...3 Installation... 4 Installing

More information

Hardware Manual. PCMCIA 1 Port RS EDITION APRIL 1999

Hardware Manual. PCMCIA 1 Port RS EDITION APRIL 1999 Hardware Manual 232 232232 PCMCIA 1 Port RS232 1.1 EDITION APRIL 1999 Guarantee. FULL 36 MONTHS GUARANTEE. We guarantee your interface card for a full 36 months from purchase, parts and labour, provided

More information

Direct Connect and Dial-Up on Windows 98

Direct Connect and Dial-Up on Windows 98 N30 Supervisory Controller System Communications Manual 689.3 Application Notes Section Issue Date 0101 APPLICATION NOTE Direct Connect and Dial-Up on Windows 98 Direct Connect and Dial-Up on Windows 98...3

More information

Upgrading Einstein Using the Einstein 1.5 Upgrade Kit. An EAB board with Production Einstein 1.5 Software EEPROM Chips.

Upgrading Einstein Using the Einstein 1.5 Upgrade Kit. An EAB board with Production Einstein 1.5 Software EEPROM Chips. TECHNICAL BULLETIN Upgrading Einstein Using the Einstein 1.5 Upgrade Kit This bulletin explains how to use the components of the CPC Upgrade Kit to upgrade a pre-1.5 version Einstein unit to the latest

More information

Metasys and Companion

Metasys and Companion Metasys Network Technical Manual 636 App. Notes: Operator Devices Section Technical Bulletin Issue Date 0191 Metasys and Companion Application Page 3 Purpose of Application 3 Setting Up the Windows Terminal

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

TABLE OF CONTENTS. Communication Functions

TABLE OF CONTENTS. Communication Functions TABLE OF CONTENTS Chapter 1: Chapter 2: Chapter 3: Chapter 4: General Features....................................................... 1-1 Functions......................................................

More information

Metasys Integrator Cutler-Hammer Application

Metasys Integrator Cutler-Hammer Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Cutler-Hammer Application Introduction Application Details Component Requirements 9 Vendor Contact Information Design Considerations

More information

Installation and Programming Manual

Installation and Programming Manual IBSM Manual IBSM Installation and Programming Manual This Manual describes the IBSM InterBus-S Master, its uses and set up. It also describes the use of the IBSM configuration software. Effective: 12 June,

More information

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up USB-Link 2 Technical Guide USB-Link 2 Code: SS0073 Version 4.11 and up TABLE OF CONTENTS GENERAL INFORMATION... 3 USB-Link 2 Overview... 3 System Requirements... 3 QUICK GUIDE...4 USB-LINK 2 DRIVER INSTALLATION

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

Ethernet Serial Server

Ethernet Serial Server Ethernet Serial Server Users Manual Eport-101, Eport-102, Eport-104, Eport108 1 INTRODUCTION... 1 1.1 FEATURES... 1 1.2 PRODUCT SPECIFICATIONS... 2 1.3 DEFAULT SETTINGS... 3 2 COMMUNICATION MODES... 4

More information

USB-Link 2 Technical Guide

USB-Link 2 Technical Guide www.wattmaster.com USB-Link 2 Technical Guide USB-Link 2 Code: SS0073 Version 4.11 and up TABLE OF CONTENTS GENERAL INFORMATION... 3 USB-Link 2 Overview... 3 System Requirements... 3 QUICK GUIDE...4 USB-LINK

More information

Defining Points. Introduction

Defining Points. Introduction M-Series Workstation with Companion/Facilitator Manual 9-1 Chapter 9 Defining Points Introduction This chapter explains how to define software points. Points are software representations of input and output

More information

INSTALLATION AND OPERATION MANUAL FOR ACC 070 COMM LINK RS485 TO PC INTERFACE AND PRISM SOFTWARE

INSTALLATION AND OPERATION MANUAL FOR ACC 070 COMM LINK RS485 TO PC INTERFACE AND PRISM SOFTWARE SenTech Corporation 5745 Progress Road Indianapolis, Indiana 46241 888/248-1988 FAX 317/248-2014 INSTALLATION AND OPERATION MANUAL FOR ACC 070 COMM LINK RS485 TO PC INTERFACE AND PRISM SOFTWARE ii APPLICABILITY

More information

Perle Dial-Out User s Guide

Perle Dial-Out User s Guide Perle Dial-Out User s Guide 95-2345-05 Copyrights Copyright 1996-2000, Perle Systems Limited and its suppliers. IBM is the registered trademark of International Business Machines Corporation. Microsoft,

More information

MUCM ModLon Gateway. Installation and Programming Manual

MUCM ModLon Gateway. Installation and Programming Manual MUCM ModLon Gateway Application Manual MUCM ModLon Gateway Installation and Programming Manual This Manual describes the MUCM application for interfacing the Cummins ModLon Gateway to a Modbus serial network.

More information

RS-422 Code-Operated Switches

RS-422 Code-Operated Switches JUNE 2000 SW421A-R2 SW422A-R2 RS-422 Code-Operated Switches COS/4 TEXT TRANSPARENT GRAPHICS MODE RESET ST LO CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S. 24 hours, 7 A.M. Monday to midnight

More information

XT-9100 Technical Bulletin

XT-9100 Technical Bulletin System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX

More information

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 3 May 2010 David Walker Initial release.

More information

Canlan INSTALLATION MANUAL

Canlan INSTALLATION MANUAL Canlan INSTALLATION MANUAL August 2014 Table of Contents Introduction... 4 Overview... 5 RJ45 Connector and Status LEDs... 5 Power Input... 6 RS232 / RS485 Connectors... 7 Installing the Canlan Software...

More information

Quick Start Installation Guide

Quick Start Installation Guide apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building

More information

N30 Supervisory Controller Quick Start

N30 Supervisory Controller Quick Start Issue Date June 30, 2004 TECHNICAL BULLETIN N30 Supervisory Controller Quick Start N30 Supervisory Controller Quick Start...2 Introduction... 2 Key Concepts... 3 Using This Document... 3 Related Information...

More information

FX-DIS Local Controller Display Technical Bulletin

FX-DIS Local Controller Display Technical Bulletin FX-DIS Local Controller Display Technical Bulletin FX-DIS1710-0 Code No. LIT-12011666 Issued February 28, 2014 Supersedes April 12, 2011 Refer to the QuickLIT website for the most up-to-date version of

More information

DFS/Cutter. Debugging Communication Problems

DFS/Cutter. Debugging Communication Problems DFS/Cutter Technical Support Bulletin Debugging Communication Problems Abstract: This TSB is written to help users debug communication problems where the cutter appears to ignore everything the computer

More information

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 02 June 2009 David Walker Initial release.

More information

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual RS-232/422/485 to Copper or Fiber Ethernet Converter User s Manual Table Of Contents TABLE OF CONTENTS... 1 INTRODUCTION... 3 PRODUCT OVERVIEW... 3 PRODUCT FEATURES... 3 PACKING LIST... 4 LED INDICATORS...

More information

A66N2 Installation and Programming Manual

A66N2 Installation and Programming Manual A66N2 Manual A66N2 Installation and Programming Manual This Manual describes the A66N2 Communications Adapter for the Altivar 66 Variable Frequency Drive, its uses and set up. Effective: 14 February 2001

More information

FieldServer Driver - Serial FS Metasys N2

FieldServer Driver - Serial FS Metasys N2 Driver Version: 1.02 Document Revision: 12 FieldServer Driver - Serial FS-8700-19 Metasys N2 Description The Metasys N2 network supports communications with a diverse range of devices. Many N2 compatible

More information

Frontline Test System

Frontline Test System Frontline Test System Serialtest Async Serialtest Spy for Windows 9x/NT Manual Technical Support Frontline Test Equipment, Inc. PO Box 7507 Charlottesville, VA 22906-7507 USA Voice: (804) 984-4500 Fax:

More information

I/O Interface DNA300

I/O Interface DNA300 DNA300 OPERATIONS MANUAL 1 Ring Communications, Inc. Crisis Alert System I/O Interface DNA300 2 DNA300 OPERATIONS MANUAL 2006/06/13 DNA300 OPERATIONS MANUAL 3 Contents INTRODUCTION... 5 INSTALLATION...

More information

FERGUSON BEAUREGARD. RTU-5000 Configurator User Manual

FERGUSON BEAUREGARD. RTU-5000 Configurator User Manual FERGUSON BEAUREGARD RTU-5000 Configurator User Manual FERGUSON BEAUREGARD RTU-5000 Configurator User Manual The Ferguson Beauregard RTU-5000 Configurator program and manuals are Copyright 1997-2004 by

More information

USER MANUAL HPS-120. About this product: Your Communications Solutions Provider

USER MANUAL HPS-120. About this product:  Your Communications Solutions Provider Your Communications Solutions Provider www.industrial-grade-modem.com USER MANUAL HPS-120 About this product: Industrial Grade Modems works to provide you with reliable, easy to use, wireless serial communications

More information

RM024 DVK USER GUIDE VERSION 1.2

RM024 DVK USER GUIDE VERSION 1.2 USER GUIDE VERSION 1.2 Americas: +1-800-492-2320 Asia: +852-2923-0610 REVISION HISTORY Version Revision Date Change Description Approved By 1.0 20 Dec 2012 Initial Release Chris Downey 1.1 15 Apr 2014

More information

Korenix JetCard Series Multiport Serial Card/Ethernet Switch Card User s Manual

Korenix JetCard Series Multiport Serial Card/Ethernet Switch Card User s Manual Korenix JetCard Series Multiport Serial Card/Ethernet Switch Card User s Manual Third Edition, Dec. 2008 www.korenix.com Korenix JetCard Series Multiport Serial Card/Ethernet Switch Card User s Manual

More information

Lab and Central Plant Controller

Lab and Central Plant Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is

More information

Millennium Simplicity Elite Parameter Points and Quirks

Millennium Simplicity Elite Parameter Points and Quirks Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The

More information

MicroTech Series-100 Application Specific Controller

MicroTech Series-100 Application Specific Controller Installation & Maintenance Data IM 657-1 Group: Controls Part Number: 594861Y Date: March 1998 MicroTech Series-100 Application Specific Controller a0196 1998 McQuay International Contents Contents...2

More information

mbc082 Bus Converter

mbc082 Bus Converter BUS CONVERTER RS485 TO 1-WIRE BUS mbc082 mbc082 Bus Converter Document. 10910, Revision - February 2007 2007 CMC Industrial Electronics Ltd. This page intentionally left blank. mbc082 Bus Converter Technical

More information

Hardware Manual PCMCIA DUAL RS EDITION MAY 1999

Hardware Manual PCMCIA DUAL RS EDITION MAY 1999 Hardware Manual 232 232232 PCMCIA DUAL RS232 1.4 EDITION MAY 1999 Guarantee. FULL 36 MONTHS GUARANTEE. We guarantee your interface card for a full 36 months from purchase, parts and labour, provided it

More information

factory field upgrade

factory field upgrade CK721-A Network Controller factory field upgrade version 3.1 build 25 24-10025-75 Revision B October, 2013 Copyright 2013 Johnson Controls, Inc. All Rights Reserved No part of this document may be reproduced

More information

IDEA. User s Guide. Part No IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183)

IDEA. User s Guide. Part No IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183) IDEA User s Guide Part No. 17500IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183) 4 FOREST PARKWAY, SHELTON, CONNECTICUT 06484 TEL: 203-926-5400 FAX: 203-929-0535 This manual has been developed by Nitsuko

More information

NL6000 Wireless Modem NL6000 User Manual Rev 1.1

NL6000 Wireless Modem NL6000 User Manual Rev 1.1 NL6000 Wireless Modem NL6000 User Manual Rev 1.1 WWW.RFNEULINK.COM 6. Procedures This section includes step-by-step procedures for configuring all the parameters that control the operation of the NL6000.

More information

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA DUCM DF1 Manual DUCM DF1 Installation and Programming Manual This manual describes the DUCM application for interfacing DF1 slaves to a Modbus or RNIM serial network. Effective: February 16, 2017 Niobrara

More information

GW1000 User s Guide. Revision 1.04 Mar 30, 2008

GW1000 User s Guide. Revision 1.04 Mar 30, 2008 GW1000 User s Guide Revision 1.04 Mar 30, 2008 Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390 Table of Contents 1.0 GW1000 General Operation & Applications... 3 2.0 Hardware Specifications...

More information

Mini USB to RS-232 Serial Adapter DB-9 Male Converter. Product Manual. Coolgear Version 1.0 January 2018 Model Number: USBG-232MINI.

Mini USB to RS-232 Serial Adapter DB-9 Male Converter. Product Manual. Coolgear Version 1.0 January 2018 Model Number: USBG-232MINI. Mini USB to RS-232 Serial Adapter DB-9 Male Converter Product Manual Coolgear Version 1.0 January 2018 Model Number: USBG-232MINI 2 USBG-232MINI PRODUCT MANUAL Revision History Revision Date Author Comments

More information

TOSLINE-S20/S20LP. S20 Loader (for Windows) User's Manual

TOSLINE-S20/S20LP. S20 Loader (for Windows) User's Manual 6 F 3 B 0 3 5 7 TOSLINE-S20/S20LP S20 Loader (for Windows) User's Manual Main Menu Contents May 1998 Toshiba Corporation UM-TLS20**-E006 Contents 1. Introduction... 3 2. Before Operating... 4 2.1 What

More information

N2 Dialer Module. Features and Benefits

N2 Dialer Module. Features and Benefits Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1194 N2 Dialer Module The N2 Dialer Module (NDM) provides a low-cost method of connecting

More information

STAR Comm Modem Kit for the Micro/PX-2000: Setup Instructions

STAR Comm Modem Kit for the Micro/PX-2000: Setup Instructions STAR Comm Modem Kit for the Micro/PX-2000: Setup Instructions This STAR Comm Modem Kit was designed specifically for use with the Micro/PX-2000 micro. The STAR Comm Modem is an external modem that can

More information

EMS467 Monitoring System. Installation and Operations Manual Section 40

EMS467 Monitoring System. Installation and Operations Manual Section 40 EMS467 Monitoring System Installation and Operations Manual 00-02-0672 01-26-10 Section 40 In order to consistently bring you the highest quality, full featured products, we reserve the right to change

More information

UPDATING CONTROLLERS USING PRISM 2 Updating the VCC-X Controller

UPDATING CONTROLLERS USING PRISM 2 Updating the VCC-X Controller Using Prism 2 7. Click on the icon. The Job-Sites Window will appear. In the Type of CommLink Dialog Box, select CommLink 5 or USB Link II. The VCC-X Controller is equipped with the ability

More information

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00 g MX200 SERIES Modbus Card 50P-1105 GE Zenith Controls 50R-2200B 12/00 Operation and Maintenance Manual Table of Contents Overview...01 Page LED Indicator...02 Installation...03 Installing the Network

More information

Local Firmware Download

Local Firmware Download Local Firmware Download Help Guide Performing a local Firmware Download allows you to download the latest software version to the ipocket232 Inc. s unit using terminal emulation software, such as HyperTerminal

More information

IM3523 IM3533 IM IM3536 LCR METER IM3570 IM7580 IM3590 CHEMICAL IMPEDANCE ANALYZER IMPEDANCE ANALYZER. Communication Instruction Manual

IM3523 IM3533 IM IM3536 LCR METER IM3570 IM7580 IM3590 CHEMICAL IMPEDANCE ANALYZER IMPEDANCE ANALYZER. Communication Instruction Manual Communication Instruction Manual IM3523 IM3533 IM3533-01 IM3536 LCR METER IM3570 IM7580 IMPEDANCE ANALYZER IM3590 CHEMICAL IMPEDANCE ANALYZER November 2014 Revised edition 6 IM3570A983-06 14-11H i Contents

More information

MS Protocol Converter. User Manual. Firmware version 2.0 ISI. Instrumental Solutions, Inc.

MS Protocol Converter. User Manual. Firmware version 2.0 ISI. Instrumental Solutions, Inc. MS1-2150 Protocol Converter User Manual Firmware version 2.0 ISI Instrumental Solutions, Inc. WWW.ISIDEV.NET Introduction The MS1-2150 protocol converter can take readings from 1 or more ModBus registers

More information

Product Manual. 8-Port RS-232 USB to Serial Adapter Data Control Box. Coolgear, Inc. Version 1.1 September 2017 Model Number: USB-8COM

Product Manual. 8-Port RS-232 USB to Serial Adapter Data Control Box. Coolgear, Inc. Version 1.1 September 2017 Model Number: USB-8COM 8-Port RS-232 USB to Serial Adapter Data Control Box Product Manual Coolgear, Inc. Version 1.1 September 2017 Model Number: USB-8COM 2 USB-8COM Product Manual Revision History Revision Date Author Comments

More information

ADVANCED OPERATOR PANEL (AOP)

ADVANCED OPERATOR PANEL (AOP) ADVANCED OPERATOR PANEL (AOP) Operating Instructions Issue 04/02 English Contents 1 Warnings and Notes 3 1.1 Special Key Functions 4 2 Applications Examples 4 2.1 Single drive control using the AOP 4 2.2

More information

Autologue User s Manual Portable Inventory Taker. Table Of Contents

Autologue User s Manual Portable Inventory Taker. Table Of Contents Autologue User s Manual Portable Inventory Taker Page i Table Of Contents 25. Introduction Portable Inventory Taker... 1 25.1 Accessing The Portable Inventory Program... 1 25.1.1 Data Entry... 1 25.1.1.1

More information

Troubleshooting the NAE/NIE

Troubleshooting the NAE/NIE Technical Bulletin Issue Date March 31, 2003 Troubleshooting the NAE/NIE Troubleshooting the NAE/NIE...2 Introduction... 2 Key Concepts... 3 NAE... 3 Power-Up LED Sequence... 4 System RE-BOOT Switch...

More information

User s Guide QL-720NW

User s Guide QL-720NW User s Guide QL-720NW Be sure to read and understand this guide before using the machine. We recommend that you keep this guide nearby for future reference. Not all models are available in all countries.

More information

Operating Instructions

Operating Instructions 33CS Comfort System Software CONTENTS Page GENERAL...1 OPERATION...1-11 Start-Up...1 Main Menu...2 CURSOR MOVEMENT AND FUNCTION SELECTION Initial Setup and Configuration...3 BASIC MODE EXPERT MODE MODEM

More information

RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series

RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series INSTALLATION & OPERATING GUIDE Rev. B P/N 3321515 www.securakeystore.com (800) 878-7829 sales@securakeystore.com COPYRIGHT 2001

More information

DPS INC ASCII MUX. Operation Guide. Table Of Contents. Overview. T/kda

DPS INC ASCII MUX. Operation Guide. Table Of Contents. Overview. T/kda DPS INC Operation Guide "Your Partners in Telemetry Monitoring Systems" ASCII MUX Fig. - ASCII MUX Expands T/MonXM ASCII s up to Eight Times Table Of Contents Overview... Functional Schematic... Typical

More information

UPDATING THE FIRMWARE IN FRAME BASED MODULES...

UPDATING THE FIRMWARE IN FRAME BASED MODULES... 7700/7800 MultiFrame Manual TABLE OF CONTENTS 1. OVERVIEW... 1 1.1. REQUIREMENTS... 1 1.1.1. Requirements Serial Port Upgrade Method... 1 1.1.2. Requirements FTP Upgrade Method (For VistaLINK Capable Modules

More information

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B Metasys N2 Instruction Manual VLT 6000 Adjustable Frequency Drive 12/99-6110-00 Revision B 2 Table of Contents Overview Page Introduction... 5 About this Manual... 5 References... 5 Instructions Abbreviations

More information

OPERATING MANUAL AND TECHNICAL REFERENCE

OPERATING MANUAL AND TECHNICAL REFERENCE MODEL WFG-D-130 HIGH SPEED DIGITAL 3 AXIS FLUXGATE MAGNETOMETER OPERATING MANUAL AND TECHNICAL REFERENCE December, 2012 Table of Contents I. Description of the System 1 II. System Specifications.. 2 III.

More information

Simplex 4190 TrueSite Workstation (TSW) Software Upgrade Instructions

Simplex 4190 TrueSite Workstation (TSW) Software Upgrade Instructions Simplex 4190 TrueSite Workstation (TSW) Software Upgrade Instructions Introduction This publication describes the software upgrade procedure for the Simplex 4190 TrueSite Workstation (TSW). Inspecting

More information

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above TECHNICAL BULLETIN Part #: 026-4122 Revision 0 Date: 2/5/2007 Control Techniques Variable-Speed Drive (VSD) Interface to E2 v. 2.40 and Overview Beginning with version 2.40, the E2 RX, BX, and CX series

More information

Software Details and Hardware Connections

Software Details and Hardware Connections GX-00 Software Configuration Tool User s Guide - Chapter Software Details and Hardware Connections Introduction This chapter describes the tasks you perform before using the GX Tool. This chapter describes:

More information

Sender Receiver Sender

Sender Receiver Sender EEE 410 Microprocessors I Spring 04/05 Lecture Notes # 19 Outline of the Lecture Interfacing the Serial Port Basics of Serial Communication Asynchronous Data Communication and Data Framing RS232 and other

More information

Parallel to Serial and Serial to Parallel Converter CE Model 232SPS2 Documentation Number 232SPS2-3903m

Parallel to Serial and Serial to Parallel Converter CE Model 232SPS2 Documentation Number 232SPS2-3903m Parallel to Serial and Serial to Parallel Converter CE Model 232SPS2 Documentation Number 232SPS2-3903m This product designed and manufactured in Ottawa, Illinois USA of domestic and imported parts by

More information

PCI Express 16-Port Serial I/O Cards

PCI Express 16-Port Serial I/O Cards PCI Express 16-Port Serial I/O Cards The PCIe-1600 PCI Express 16-port serial I/O card is a plug & play high-speed serial I/O expansion card for PCI Express bus. Connecting to a PCI Express bus on your

More information

MRZJW3- SETUP154E. General-Purpose AC Servo Servo Configuration Software MODEL INSTALLATION GUIDE

MRZJW3- SETUP154E. General-Purpose AC Servo Servo Configuration Software MODEL INSTALLATION GUIDE General-Purpose AC Servo Servo Configuration Software MODEL MRZJW3- SETUP154E INSTALLATION GUIDE Thank you for choosing the Mitsubishi general-purpose AC servo Servo Configuration Software. To optimize

More information

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X EtherSeries EtherSeries CR-2 & CR-2-Opto User s Guide Revised October 7, 2013 Firmware Version 1.X TABLE OF CONTENTS SECTION 1 - DESCRIPTION... 2 SECTION 2 - SPECIFICATIONS... 4 SECTION 3 - INSTALLATION...

More information

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS-2700-42 IKS to Modbus RTU Gateway CAS 2700-42 IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS 2700-42 IKS Gateway Manual Page 1 of 34 BLANK PAGE CAS 2700-42 IKS Gateway Manual Page 2 of 34 Contents

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

XT-9100 Configuration Guide

XT-9100 Configuration Guide System 9100 Technical Manual 636.4 Configuration Guides Section Configuration Guide Issue Date 0896 XT-9100 Configuration Guide XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3

More information

ATL20 ATL30 Automatic transfer switch controller

ATL20 ATL30 Automatic transfer switch controller I 194 GB 07 07 ATL20 ATL30 Automatic transfer switch controller REMOTE CONTROL SOFTWARE MANUAL Summary Introduction... 2 Minimum resources of the PC... 2 Installation... 2 Activation of the PC-ATL connection...

More information

Troubleshooting with the control panel

Troubleshooting with the control panel Troubleshooting with the control panel The tables in this section explain common messages that might appear on the control-panel display. Within each table, the messages and their meanings are listed in

More information

3.1 I-7560 Pin Assignment and Specifications: Introduction

3.1 I-7560 Pin Assignment and Specifications: Introduction 3.1 I-7560 Pin Assignment and Specifications: Introduction The I-7560 adds a Windows serial Com port via its USB connection and is compatible with new & legacy RS-232 devices. USB Plug and Play allows

More information

Installing the DX LCD Display

Installing the DX LCD Display DX LCD Display User s Guide 3-1 Chapter 3 Installing the DX LCD Display Introduction Use the DX LCD Display as either a portable device, or permanently mount it in a panel or on the wall. For panel and

More information

EtherSeries Modbus Gateway EMB-2 User s Guide

EtherSeries Modbus Gateway EMB-2 User s Guide EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

ICP PANEL-TEC PEX3000 II

ICP PANEL-TEC PEX3000 II ICP PANEL-TEC PEX3000 II MODBUS PORT EXPANDER INSTALLATION AND OPERATION GUIDE REVISION HISTORY Revision Date Author Comments 000 29 Aug 2008 Keira Majors Initial release. 001 16 Sep 2008 David Walker

More information

BACnet Flow Controller for Fan Filter Units

BACnet Flow Controller for Fan Filter Units MANUAL SERVICE + INSTALLATION BACnet Flow Controller for Fan Filter Units BFC Series v300 Issue Date: 08/23/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General

More information