ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below:

Size: px
Start display at page:

Download "ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below:"

Transcription

1 ADDENDUM NO. 1 ITB-DOT BAT To: All Prospective Proposers From: Ashley Henning District Five Contractual Services Date: March 25, 2016 RE: ITB-DOT BAT ITS Battery Installation You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below: 2) TIMELINE Provided below is a list of critical dates and actions. The location of all meetings will be at the address listed on the Cover Sheet, unless specified otherwise below. These dates are subject to change. Notices of changes (Addenda) will be posted on the Florida Vendor Bid System at (click on BUSINESS, click on Doing Business with the State, under Everything for Vendors and Customers, click on Vendor Bid System (VBS), click on Search Advertisements ) under this bid number. It is the responsibility of all potential bidders to monitor this site for any changing information prior to submitting your bid. The Technical Memorandum dated 3/15/16 included in Exhibit A, Scope of Services is replaced in its entirety by the attached Technical Memorandum dated 3/25/16. TO ACKNOWLEDGE RECEIPT OF THIS NOTICE AND ALL CHANGES, PLEASE SIGN AND RETURN BY E-FAX TO THIS OFFICE AT BY April 12, Name of Company: Authorized Signature: Date: FAILURE TO FILE A PROTEST WITHIN THE TIME PRESCRIBED IN SECTION (3), F.S. SHALL CONSTITUTE A WAIVER OF PROCEEDINGS UNDER CHAPTER 120, F.S. Addendum No. 1, ITB-DOT BAT Page 1 of 1

2

3 Table of Contents Table of Contents i List of Acronyms ii 1.PROJECT OVERVIEW 1 2.EXISTING ELECTRICAL CONDITIONS 1 3.EXISTING PANELBOARD ANALYSIS 1 4.PROPOSED MODIFICATIONS TO MAIN PANELBOARD 4 5.ESTIMATED MATERIAL LIST 7 6.RECOMMENDATIONS AND CONCLUSION 8 APPENDIX A N.E.C. TABLE (B)(16) 9 APPENDIX B ELECTRICAL PLANS 10 Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers i

4 List of Acronyms AMPS ATS FPL I KCMIL KVA KW NA NEC P UPS V XFRM Watts Amperes Automatic Transfer Switch Florida Power & Light Current Thousand Circular Mils Thousand Volt-Amps Thousand Watts Not Applicable or Not Available National Electrical Code Power Uninterruptible Power Supply Volts Transformer Wattage Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers ii

5 1. PROJECT OVERVIEW The work performed as part of this report includes analyzing the as-built documentation and field reviewing the existing electrical system of the existing District 5 Headquarters located at 719 South Woodland Blvd., Deland, Florida to determine what electrical system modifications are required to accommodate additional proposed equipment power loads to be added to the existing electrical system and back-up generator power. In addition, this report will also determine the electrical elements to connect the new load, including wire and conduit sizes and length, panelboard and breaker sizes. 2. EXISTING ELECTRICAL CONDITIONS In order to document the existing condition of the building power system, a panel schedule of the main panelboard was developed. The main panelboard matrix shown in Section 3 includes sub panel names, circuits, wire sizes and loads. Due to the age of the building, no as-builts or panel schedules were available to verify the design load information. Therefore, intensive field reviews were performed to determine wire sizes, circuit breaker sizes, and to measure actual loads (using a Multimeter). The District 5 building is powered utilizing one main distribution panel, called Main Panelboard. The Main Panelboard is rated at 4000 Amps and its bus is rated 2000 Amps. The Main Panelboard is located in the Main Electrical Room on the first floor and it is 3 phase 277/480 Volts. The Main Panelboard line wires are 4 sets of 500 Kcmil wires. The main panel board is fed from both utility power and back-up power system via an Automatic Transfer Switch (ATS). The back-up generator is rated at 800 KW and the ATS has a 1200 Amp capacity. (See Appendix B for existing electrical room floor and electrical riser diagram). Prior to designing the installation of the new electrical system, the existing system was analyzed for available expansion as well as any potential deficiencies. This analysis included verification of wire sizes, circuit breaker sizes, panelboard ratings, and generator ratings. 3. EXISTING PANELBOARD ANALYSIS There are a total of four existing panelboards (LE, LIC, HE and Main) located inside the District 5 building Main Electrical Room. These existing panel boards were evaluated to make sure they adhered to NEC code requirements. There was one NEC violation found within these panels: Panel HE circuit 25: There are 2 wires connected to this circuit. Per the NEC Article only one wire shall be connected to a breaker lug. Recommendation: relocate one of the wires to circuit 24 (open breaker spare). Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 1

6 The entire building is backed-up by the generator system and the Main panelboard has space available for a new circuit breaker. The Main panelboard will be used to add the additional loading of future equipment data room. See the Main panelboard schedule below. EXISTING CIRCUITS IN MAIN PANEL BOARD Mounting 277/480 Volts PANELBOARD MAIN 4000 Main Lug Floor 3 Ph. 4 sets of #500 Cmil LOCATION ELECTRICAL ROOM 2000 Bus Size Amps Frame Breaker Number Wire Size Circuit # Destination Phase A Phase B Phase C Size Size Poles AWG or Kcmil x 3/0 1 Panel "LA" x 3/ x 3/ Panel "TI B" /0 3 Panel "H1A" /0 20 1/ x 3/0 4 Panel "HE" x 3/ x 3/0 56 1/0 5 FIRE PUMP /0 56 1/ EL EOC Disconnect /0 8 T1 A / / EL SPACE N. EL CORE 75 KVA XFMR /0 12 UNKNOWN / / SPACE 0 0 Total Connected (AMPS) : AMPS TOTAL Connected Load (KVA): KVA Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 2

7 The contents of the panelboard are described below: The top section of the panel schedule spreadsheet provides basic information for the panelboard such as mounting type, panel name, main lug size, bus size, voltage, number of phases, number of wires, size of the wires, and the location where the panelboard was installed. The body of the spreadsheet identifies the panelboard and its individual circuits. Please note that when field reviewing the panelboards, it was observed that some labels located at the panelboards were inaccurate. Therefore some circuits were named Unknown : Circuit number: The number of the circuit within the panelboard. Destination: Description of the load. Amp (per phase): This is equivalent to amperage. Note that these numbers were obtained by amp probe reading. They are not design loads. Frame Size: The frame size to hold the circuit breaker. Breaker Size: The circuit breaker is for overload protection. When designing a new circuit, the load was verified to be a maximum of up to 80% of the circuit breaker rating. For example, if the circuit breaker is a 20A single pole, the load should be a maximum of 16A. Number of Poles: This is the number of poles of the breaker. It can be 1, 2 or 3. Wire size AWG or Kcmil: Proper wire size is critical to the circuit. When calculating the wire size, the maximum amperage per wire size allowed by NEC can be found on Table (B) (16)) (See Appendix A). To finalize the panelboard analysis, the Total measured Load (AMPS) and Total measured Load (KVA) of the panelboard was calculated. The total KVA load is the sum of all three phases times the voltage per phase (277V) divided by 1,000. The total measured load is determined by utilizing the field measurements. The total AMPS are the total KVA divided by (for 277V/480V). Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 3

8 4. PROPOSED MODIFICATIONS TO MAIN PANELBOARD After performing an analysis of the existing power system, an analysis of the future needs for the electrical system, the UPS system, and the generator system was conducted. In particular, the effect of implementing a new data room on the first floor and the associated servers, and the addition of equipment required for implementing the overall system was reviewed and analyzed. The new data room will include new equipment as well as some existing equipment to be relocated from the second floor data room. The exact anticipated loads for the new data room are not yet known as the equipment has not yet been determined. However, the installation of a 225 Amp panel, ITS UPS 1, with four 60 Amp circuit breakers will be capable of powering all proposed and existing equipment to be installed in the 1 st floor data center. The installation of a 225 Amp panel, ITS UPS 2, with two 60 Amp circuit breakers will power existing equipment previously powered by the UPS. The assumption for the calculations used in this report is that all the proposed power loads are to be backed-up by a new 100 KW UPS system. The existing 2 nd floor data center has a measured load of a maximum of 80 Amps/phase (including the existing UPS). Therefore, the load for the new data center will be assumed to be a maximum of 160 Amps/phase (design load). The load for the new data center was added to the Main panelboard schedule and it is shown on the following page. Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 4

9 EXISTING AND PROPOSED CIRCUITS IN MAIN PANEL BOARD Mounting 277/480 Volts PANELBOARD MAIN 4000 Main Lug Floor 3 Ph. 4 sets of #500 Cmil LOCATION ELECTRICAL ROOM 2000 Bus Size Amps Frame Breaker Number Wire Size Circuit # Destination Phase A Phase B Phase C Size Size Poles AWG or Kcmil x 3/0 1 Panel "LA" x 3/ x 3/ Panel "TI B" /0 3 Panel "H1A" /0 20 1/ x 3/0 4 Panel "HE" x 3/ x 3/0 56 1/0 5 FIRE PUMP /0 56 1/ EL EOC Disconnect /0 8 T1 A / / EL /0 10 ITS UPS (1ST FLOOR) / / N. EL CORE 75 KVA XFMR /0 12 UNKNOWN / / SPACE 0 0 Total Connected (AMPS) : AMPS TOTAL Connected Load (KVA): KVA Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 5

10 After entering all information into the panelboard schedule as described above and verifying the information in the field, the proposed connected load for the data center was added to the spreadsheet and analyzed to ensure the existing generator, ATS, and main panelboard would be able to accommodate the additional equipment. An additional 25% of capacity was added to the total existing load for contingency, since the loads used were measured loads and not design loads. The results are the following: EXISTING ITEM CAPACITY MEASURED LOAD Add. 25% PASS/FAIL 1 EXISTING MAIN PANEL WIRE SIZE (AMPS) PASS 2 ATS 80% PASS 3 EXISTING GENERATOR 80% PASS PROPOSED ITEM CAPACITY DESIGN LOAD Add. 25% PASS/FAIL 4 NEW CIRCUIT WIRE SIZE (AMPS) NA PASS 5 NEW CIRCUIT BREAKER 80% NA PASS To calculate the capacity from the table above, the following criteria were used: 1. Wire size: 4 Sets of 500 kcmil Per N.E.C TABLE (B)(16): Each 500 Kkcmil max ampacity = 380 Amps ATS size = 1200 Amps Capacity = 80% of ATS Ampacity % Generator size = 800 KW Capacity = 80% of Wattage % Wire size: 4/0 AWG Per N.E.C TABLE (B)(16): 4/0 AWG max ampacity = 230 Amps 5. Breaker size = 200 Amps Capacity = 80% of Breaker Ampacity % 160 Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 6

11 5. ESTIMATED MATERIAL LIST Power Equipment Description Quantity 225A 3 Pole circuit breaker enclosure 200A Breaker (480/277V) 1 225A 3 Pole 42 Circuit Panelboard (208/120V) 1 100A 3 Pole 42 Circuit Panelboard (208/120V) 1 60A Pole breaker (208/120V) 6 2.5" RGS Conduits #4/0 AWG 80 1 #4 AWG 80 4 #2 AWG 20 1 #8 AWG 20 Incidental Materials 1 Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 7

12 6. RECOMMENDATIONS AND CONCLUSION Information for the panelboards, while graphically showing their respective relations to each other, the UPS, the generator and the utility power are shown in form of a riser diagram. The riser diagram also shows information of the new panel schedule and locations for the installation, including conduit sizes. Based on existing as-built research, revisions and Multimeter results, the existing generator and main service panel are capable of powering the proposed equipment and service panels. Utilizing a spare circuit in the main panel, a 200A 3-pole 277/480V breaker will be installed to power a proposed 100 KW ITS UPS to be housed in the first floor data center. The UPS will then power a 3-phase transformer which will then power two proposed service panels: ITS UPS 1 and ITS UPS 2 (See Appendix B for Electrical Plans). Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 8

13 APPENDIX A N.E.C. TABLE (B)(16) Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 9

14 APPENDIX B ELECTRICAL PLANS Addition of UPS and Panel Boards Serving 1st and 2nd Floors Data Centers 10

15

16

17

18

19

ADDENDUM NO. 5 DATE: January 14, 2015

ADDENDUM NO. 5 DATE: January 14, 2015 FLORIDA DEPARTMENT OF TRANSPORTATION Procurement Office 605 Suwannee Street, MS 20 Tallahassee, Florida 32399-0450 Phone: (850) 414-4568 Fax: (850) 414-4951 ADDENDUM NO. 5 DATE: January 14, 2015 BID#:

More information

ME-000A ME-ECSA ELECTRICAL COVER SHEET REV PROFESSIONAL SEAL 05-CO-012 AS NOTED

ME-000A ME-ECSA ELECTRICAL COVER SHEET REV PROFESSIONAL SEAL 05-CO-012 AS NOTED ME-000A RIDGE AVE PITTSBURGH, PA ELECTRICAL COVER SHEET DATE BY DESCRIPTION CCAC ME-ECSA CCAC 1 KEY PLAN - SSC ME-00A NO SCALE 2 KEY PLAN - PE ME-00A NO SCALE 3 KEY PLAN - JH ME-00A NO SCALE 4 KEY PLAN

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

DHSMV ITN FRVIS Equipment Refresh Addendum No. 5

DHSMV ITN FRVIS Equipment Refresh Addendum No. 5 DHSMV ITN 001-19 FRVIS Equipment Refresh Addendum No. 5 SEPTEMBER 19, FAILURE TO FILE A PROTEST WITHIN THE TIME PRESCRIBED IN SECTION 120.57(3), FLORIDA STATUTES, OR FAILURE TO POST THE BOND OR OTHER SECURITY

More information

More Questions from Inspectors Numerous PV Systems Pose Issues

More Questions from Inspectors Numerous PV Systems Pose Issues Perspectives on PV More Questions from Inspectors Numerous PV Systems Pose Issues by John Wiles 76 IAEI NEWS March. April 2012 www.iaei.org Photovoltaic (PV) systems prices continue to drop and inspectors

More information

Instruction Manual HPH-8

Instruction Manual HPH-8 Specifications HPH-8 Trigger cable 120-volt, Nema 1-15 Main Power 50-amps @ 240-volt AC Power receptacles (4) Nema 5-15 or 6-15 Maximum HID wattage 8000 watts (on 240-volt) 4800 watts (on 120-volt) Maximum

More information

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.

More information

Spring Test 5 due 4/26/2013

Spring Test 5 due 4/26/2013 Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof

More information

Carina Grega Food Network Space Final Thesis Report Electrical Overview. Electrical Overview. Existing System Overview

Carina Grega Food Network Space Final Thesis Report Electrical Overview. Electrical Overview. Existing System Overview Electrical Overview Existing System Overview Chelsea Market is served by Consolidated Edison, the electric utility for most of New York City. The Food Network space is supplied by two separate radial systems

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

May 28, The enclosed information has been provided for consideration in the preparation of your response to the above-referenced RFP.

May 28, The enclosed information has been provided for consideration in the preparation of your response to the above-referenced RFP. May 28, 2015 To: Prospective Vendor Subject: Solicitation Number: DHSMV RFP 030-15 Driver License Equipment and Software Addendum No. 1 The enclosed information has been provided for consideration in the

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

Electrical Service Change-Tn Neenah

Electrical Service Change-Tn Neenah Electrical Service Change-Tn Neenah Permit # Owners name Project address Contractors name Contractors address Fax #: Type of occupancy Job description New construction Main panel Single phase Additional

More information

NEW ERA METER. Installation & Operation Guide NE METER

NEW ERA METER. Installation & Operation Guide NE METER NEW ERA METER Installation & Operation Guide NE METER Autoranging Power Supply Installation Diagnostics Per Phase Voltage & Current kwh, Demand and TOU 0.2% Accuracy -40 C to +85 C Watertight Enclosure

More information

Purchasing Department Finance Group INVITATION TO BID

Purchasing Department Finance Group INVITATION TO BID Purchasing Department Finance Group September 20, 2012 INVITATION TO BID The City of Norwalk, Information Technology Department, is soliciting bids for Computer Software Microsoft Server 2008 plus SQL

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

ITS DEVICE INTEGRATION AND TESTING

ITS DEVICE INTEGRATION AND TESTING TECHNICAL SPECIAL PROVISION FOR ITS DEVICE INTEGRATION AND TESTING FINANCIAL PROJECT NO.: 428213-2-52-02 MARION COUNTY The official record of this Technical Special Provision is the electronic file signed

More information

1-Line Load Calculation Software. User s Manual APPROVED. Copyright 2013 Durand & Associates. Page 1

1-Line Load Calculation Software. User s Manual APPROVED. Copyright 2013 Durand & Associates. Page 1 1-Line 2014 Load Calculation Software User s Manual APPROVED Copyright 2013 Durand & Associates Page 1 1-LINE 2014 COPYRIGHT 2013 - DURAND & ASSOCIATES This software and manual are protected by Federal

More information

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Powering HP BladeSystem c7000 Enclosures

Powering HP BladeSystem c7000 Enclosures Powering HP BladeSystem c7000 Enclosures HOWTO Abstract... 2 Power draw of HP BladeSystem c7000 Enclosure... 2 Power Distribution...2 Uninterruptible Power Supplies... 6 For more information... 9 Call

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 16420 - ELECTRICAL EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified

More information

Spring Test 16 due 06/14/2013

Spring Test 16 due 06/14/2013 Spring Test 16 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. Figure 234.142 1. Refer to the information shown in Figure 234.142. Motor 1

More information

CenterPoint Energy P O Box 1700 Houston, TX

CenterPoint Energy P O Box 1700 Houston, TX CenterPoint Energy P O Box 1700 Houston, TX 77251-1700 IF YOU ARE APPLYING FOR DISTRIBUTED GENERATION, PLEASE FOLLOW THE INSTRUCTIONS IN THE PARAGRAPHS BELOW. YOU WILL NEED TO COMPLETE AND SIGN AND THEN

More information

HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems

HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device

More information

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series Installation Manual APEX Series Silicon and MOV Panel Protection APEX Series APEX Series Installation Guide 2 Table of Contents Mechanical Installation 3 Table One - Application Rating 3 Figure 1 - Mounting

More information

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD) File E248748 Project 05NK27956 Issued: 2007-11-01 Revised: 2009-12-04 REPORT on SURGE PROTECTIVE DEVICES/PANELBOARD EXTENSION MODULES, CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD) GE ZENITH CONTROLS

More information

ASCO SERIES 300 Manual Transfer Switch Solutions

ASCO SERIES 300 Manual Transfer Switch Solutions ASCO SERIES 300 Manual Transfer Switch Solutions When power fails, businesses suffer. For some organizations, a permanent generator is too costly. Instead, permanent means for quickly connecting a portable

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Purchasing Department Finance Group INVITATION TO BID. PROJECT # 3299 Document length seven (7) pages DEADLINE 2:00 PM May 2, 2013

Purchasing Department Finance Group INVITATION TO BID. PROJECT # 3299 Document length seven (7) pages DEADLINE 2:00 PM May 2, 2013 Purchasing Department Finance Group April 18, 2013 INVITATION TO BID The City of Norwalk is soliciting bids for the City s Information Technology Department for Data Center Core Switch Equipment for the

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide. .2 Overview Product Selection Guide BR Loadcenters Description Service Single-phase, three-wire, 20/240 Vac Short-Circuit Current Rating 0 kaic: All single- and three-phase loadcenters 70 225A, 8 to 42

More information

ADDENDUM NO. 1. Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri Point to Point Fiber Connection

ADDENDUM NO. 1. Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri Point to Point Fiber Connection Issue Date: December 9, 2016 ADDENDUM NO. 1 Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri 64108 Project #16-7029-25 This Addendum is hereby made a part of

More information

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

MEMORANDUM SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS

MEMORANDUM SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS MEMORANDUM DATE: December 15, 2013 TO: Campus Community FROM: Tim Ridley, CSP, ARM-P Director, Safety and Risk Management SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS Safety & Risk Management inspections

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D. Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT CAPACITY WITH OPTION TO SEGMENT CHANNELS FIBER CABLE TO UPGRADE CURRENT BUILDING NETWORK

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide. .2 Loadcenters and Circuit Breakers Overview Product Selection Guide BR Loadcenters Description Service Single-phase, three-wire, 20/240 Vac Short-Circuit Current Rating 0 kaic: All single- and three-phase

More information

Residential 1-Line Multifamily Instructions. User s Manual APPROVED. Copyright 2016 Durand & Associates. Page 1

Residential 1-Line Multifamily Instructions. User s Manual APPROVED. Copyright 2016 Durand & Associates. Page 1 Residential 1-Line 2017 Multifamily Instructions APPROVED User s Manual Copyright 2016 Durand & Associates Page 1 Using Residential 1-Line 2017 with Excel Excel 1997-2003 This product was designed with

More information

HP Uninterruptible Power Supplies Overview

HP Uninterruptible Power Supplies Overview NOTE: Additional information on these and additional HP UPS products at: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html Description HP rack mountable UPSs, designed

More information

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F:

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F: ADDENDUM COVER & RECEIPT CONFIRMATION SHEET 169 Main Street 700 Plaza Middlesex Middletown, CT 06457 T: 860-343-8297 F: 860-343-9504 www.wright-pierce.com DATE: 9/6/16 ADDENDUM CONSISTS OF (Including this

More information

Anna Independent School District

Anna Independent School District Anna Independent School District 501 S. Sherley Avenue Anna Texas 75409 www.annaisd.org Phone: 972-924-1000 Fax: 972-924-1001 Request for Proposals (RFP) Spring 2015 Computer Hardware Refresh The Technology

More information

Rapid Shutdown Requirements for NEC 2017

Rapid Shutdown Requirements for NEC 2017 2017 AEESOLAR DEALER CONF. Rapid Shutdown Requirements for NEC 2017 Presented by: Bill Brooks, CMP 4 2017 NEC Statistics for Article 690 Whole article was reduced from 11,000 words to about 8,000 words.

More information

Request for Proposal Palos Heights School District 128 Network Infrastructure and WIFI E-Rate Form 470: Palos Heights, IL 60463

Request for Proposal Palos Heights School District 128 Network Infrastructure and WIFI E-Rate Form 470: Palos Heights, IL 60463 Request for Proposal Network Infrastructure and WIFI E-Rate Form 470: 170062975 Date of Bid Due: On or before March 3, 2017 at 11:00 AM is requesting bids for E-Rate Category 2 Internal Connections as

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical Spec Interpretation The purpose of this PowerPoint is to highlight the areas of the written spec and electrical drawings which contain the information required to determine a TPS part number for quoting

More information

Answers to questions asked prior to the deadline of 5pm, November 14, 2018;

Answers to questions asked prior to the deadline of 5pm, November 14, 2018; Office of the Vice President 971 Elmore Drive and Chief Financial Officer PO Box 115250 Procurement Services Gainesville, FL 32611-5250 http://procurement.ufl.edu/ (352) 392-1331 Fax 352-392-8837 November

More information

Electrical Plan Review

Electrical Plan Review Electrical Plan Review Overcurrent Protection and Devices, Short-Circuit Calculations, Component Protection, Selective Coordination, and Other Considerations Table of Contents Part I: Overcurrent Protection

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

Avtec, Inc. Lighting Systems

Avtec, Inc. Lighting Systems 6 Industrial Park Cahokia, IL 62206 Phone (618) 337-7800 Fax (618) 337-7976 E-Mail tech_info@avteclighting.com Report No. INSTALLATION OPERATION MAINTENANCE MANUAL, LED STRIP LIGHT, P/N 01-11-0010 P/N

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Liebert Precision Power Center

Liebert Precision Power Center AC Power Systems For Business-Critical Continuity Liebert Precision Power Center Packaged Power Distribution For Higher Power Quality Liebert Delivers The Packaged Power Solution Creating high quality

More information

Purchasing Department Finance Group INVITATION TO BID

Purchasing Department Finance Group INVITATION TO BID Purchasing Department Finance Group August 7, 2012 INVITATION TO BID The City of Norwalk, Information Technology Department, is soliciting bids for Computer Server Hardware and VMware vsphere Enterprise

More information

IS-IR SAUNA ROUGH-IN- ###############

IS-IR SAUNA ROUGH-IN- ############### IS-IR SAUNA ROUGH-IN- ############### 115 Bowes Rd, Unit 2, Concord, ON. L4K 1H7 Ph:905-738-4017 / 800-387-7029 sales@saunafin.com www.saunafin.com Infrared saunas are much more time consuming to install

More information

CONSTRUCTION PLANS FOR MADERA COUNTY FOR THE CSA 19 (ROLLING HILLS) WELL SITE NO. 3

CONSTRUCTION PLANS FOR MADERA COUNTY FOR THE CSA 19 (ROLLING HILLS) WELL SITE NO. 3 CONSTRUCTION PLANS FOR MADERA COUNTY FOR THE CSA 19 (ROLLING HILLS) WELL SITE NO. 3 COUNTY OF MADERA ENGINEERING DEPARTMENT 2037 W. CLEVELAND AVE. MADERA, CALIFORNIA 93637 PLAN REVISION COUNTY OF

More information

ADDENDUM #001. Medical Supplies. July 24, 2018 at 2:00 p.m., Eastern Time

ADDENDUM #001. Medical Supplies. July 24, 2018 at 2:00 p.m., Eastern Time ADDENDUM #001 Solicitation : Solicitation Title: Opening Date/Time: Medical Supplies July 24, 2018 at 2:00 p.m., Eastern Time Addendum : 001 Failure to file a protest within the time prescribed in Section

More information

Community Hospital Torrington, Wyoming

Community Hospital Torrington, Wyoming Community Hospital Torrington, Wyoming Essential Electrical System Power Quality Issues PREPARED BY: CHEYENNE, WYOMING PO Box 20221, Cheyenne, WY 82003 307-638-6911 powerquality.gcoffman@gmail.com Table

More information

Message Board Questions and Answers

Message Board Questions and Answers Message Board Questions and Answers Addendum No. 1 State of Florida Department of Management Services INVITATION TO BID Commercial Off-The-Shelf (COTS) Software ITB No.: 01-252-035-M December 16, 2013

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs) Models beginning with 2M, 2L or 2X Series 2000 Multiple Meter Units (MMUs) Product Description Technical Specifications Installation Instructions February 28 th, 2013 List of Figures...2 List of Tables...2

More information

Avtec, Inc. Lighting Systems

Avtec, Inc. Lighting Systems 6 Industrial Park Cahokia, IL 62206 Phone (618) 337-7800 Fax (618) 337-7976 E-Mail tech_info@avteclighting.com Report No. INSTALLATION OPERATION MAINTENANCE MANUAL, LED STRIP LIGHT, P/N 01-11-0007 P/N

More information

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08 DNB Power and Control System Information and Interim Safety Procedures Version draft 5/06/08 DNB Power and Control System Information There are four sources of power for the DNB in the power supply and

More information

Panelboard and switchboards series rating information manual

Panelboard and switchboards series rating information manual Information Manual 1C96944H02 Effective April 2014 Supersedes March 2011 Panelboard and switchboards series rating information manual Play it safe...read this manual! Panelboard and Effective: April 2014

More information

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 0CT00R/0 0 CONTENTS Description..............................................Page Description.............................................

More information

INVITATION FOR BIDS For RO PLANT #2 PLC SYSTEMS UPGRADE (CIP# WTR1702)

INVITATION FOR BIDS For RO PLANT #2 PLC SYSTEMS UPGRADE (CIP# WTR1702) INVITATION FOR BIDS For RO PLANT #2 PLC SYSTEMS UPGRADE (CIP# WTR1702) BID SUBMITTAL DATE, TIME, & LOCATION: EMAIL QUESTIONS TO: December 8, 2017 @ 2:00 PM Mount Pleasant Waterworks Operations Center 1619

More information

Gaston County Schools

Gaston County Schools Gaston County Schools 2008 Gaston County Schools Date: 5/4/2008 RFP #: S2008 Request for Proposal Project Name: Cisco Switch Purchase Facilities: Bessemer City High School Chapel Grove Elementary School

More information

Tender Number: 4638 Date Created : April 3, 2017 Contact Person: John Brennan Telephone: (902)

Tender Number: 4638 Date Created : April 3, 2017 Contact Person: John Brennan Telephone: (902) Tender Number: 4638 Date Created : April 3, 2017 Contact Person: John Brennan Telephone: (902) 368-5138 Email jebrennan@gov.pe.ca Procurement Services Request for Quotation (RFQ) Tender Source: PROCUREMENT

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT 26 05 73 POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT Delete the following current section in its entirety (deletions are shown struck through)..01 General A. Short circuit Studies,

More information

Taxonomies, Classifications, and Categories Category Description PANELBOARD BRANCH BREAKERS V Molded case circuit breaker

Taxonomies, Classifications, and Categories Category Description PANELBOARD BRANCH BREAKERS V Molded case circuit breaker 4 South Street 7964-76, TX Nacogdoches Phone: 96-69-794 Fax: 96--468 GHB00 P 0A 77/4V Breaker Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Features amperage rating

More information

Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 2

Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 2 A E 481 THESIS TECHNICAL REPORT TWO Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 2 Shepherdstown, West Virginia Lighting/ Electrical Option Professor Dannerth November 3,

More information

REQUEST FOR INFORMATION (RFI) ELECTRONIC FORMS AUTOMATION DEP Solicitation Number: C

REQUEST FOR INFORMATION (RFI) ELECTRONIC FORMS AUTOMATION DEP Solicitation Number: C Request for Information Electronic Forms Automation DEP RFI No.: 2016040C REQUEST FOR INFORMATION (RFI) ELECTRONIC FORMS AUTOMATION DEP Solicitation Number: 2016040C This is a Request for Information (RFI)

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

CREATIVE SERVICES MAILHOUSE SERVICES BID #BC P ADDENDUM # 3 Page 1 of 3

CREATIVE SERVICES MAILHOUSE SERVICES BID #BC P ADDENDUM # 3 Page 1 of 3 DATE: April 13, 2012 TO: FROM: RE: All Prospective Proposers Delores R. Pertee CREATIVE SERVICES MAILHOUSE SERVICES BID #BC-20787-P ADDENDUM # 3 Page 1 of 3 The following amends the above referenced Bid

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Product Data Sheet Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ZEE BIPLANE IECAX480V225A Main Disconnect Panel Bevco Engineering Company, Inc. CONFIDENTIAL

More information

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching Liebert STS2/PDU, Static Transfer Switch 2/Power Unit A Streamlined Package For Power And Source Switching An All-In-One Power System With A Smaller Footprint And A Smaller Price Tag Liebert is making

More information

1995 Metric CSJ 's & SPECIAL PROVISION ITEM 4. Scope of Work

1995 Metric CSJ 's & SPECIAL PROVISION ITEM 4. Scope of Work 1995 Metric CSJ 's 0015-13-235 & 3136-01-098 SPECIAL PROVISION TO ITEM 4 Scope of Work For this project, Item 4, "Scope of Work", of the Standard Specifications, is hereby amended with respect to the clauses

More information

M215 Microinverter Installation Planning

M215 Microinverter Installation Planning TECHNICAL BRIEF M215 Microinverter Installation Planning The M215 Microinverter The M215 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60- cell PV modules

More information

Addendum # 2. RFB #237 Alys Stephens Center Brochure Opening: 2:00 pm. The following questions were received for review.

Addendum # 2. RFB #237 Alys Stephens Center Brochure Opening: 2:00 pm. The following questions were received for review. THE UNIVERSITY OF ALABAMA AT BIRMINGHAM Procurement Contracts Office Addendum # 2 RFB #237 Alys Stephens Center Brochure Opening: 7/27/16 @ 2:00 pm The following questions were received for review. Question:

More information

BIDDERS INSTRUCTIONS ON HOW TO ACCESS FAO TENDER DOCUMENTS and SUBMIT BIDS THROUGH UNGM

BIDDERS INSTRUCTIONS ON HOW TO ACCESS FAO TENDER DOCUMENTS and SUBMIT BIDS THROUGH UNGM BIDDERS INSTRUCTIONS ON HOW TO ACCESS FAO TENDER DOCUMENTS and SUBMIT BIDS THROUGH UNGM Last update March 2016 The registration with UNGM (https://www.ungm.org/vendor/registration) is a mandatory requirement

More information

The Different Types of AC Power Connectors in North America

The Different Types of AC Power Connectors in North America The Different Types of AC Power Connectors in North America White Paper 20 Revision 2 by James Spitaels > Executive summary A confusing array of AC power plugs and receptacles exist to deliver power to

More information

DEE JASPAR & ASSOCIATES, INC. CONSULTING CIVIL ENGINEERS 2730 UNICORN ROAD, BLDG A BAKERSFIELD, CA PHONE (661) FAX (661)

DEE JASPAR & ASSOCIATES, INC. CONSULTING CIVIL ENGINEERS 2730 UNICORN ROAD, BLDG A BAKERSFIELD, CA PHONE (661) FAX (661) DEE JASPAR & ASSOCIATES, INC. CONSULTING CIVIL ENGINEERS 2730 UNICORN ROAD, BLDG A BAKERSFIELD, CA 93308 PHONE (661) 393-4796 FAX (661) 393-4799 ARVIN COMMUNITY SERVICES DISTRICT NOTICE TO PLANHOLDERS

More information

Superseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 Effective May 27, 2010 Effective December 3, 2011

Superseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 Effective May 27, 2010 Effective December 3, 2011 Superseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 2. Initial Technical Review a. The following flowchart provides, for illustrative purposes, the major steps in the Initial Technical Review process:

More information

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide. .2 Loadcenters and Circuit Breakers Overview Product Selection Guide BR Loadcenters Description Service Single-phase, three-wire, 20/240 Vac Short-Circuit Current Rating 0 kaic: All single- and three-phase

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

The following changes or clarifications shall be made part of the Bid Documents and shall be taken into consideration when submitting bids.

The following changes or clarifications shall be made part of the Bid Documents and shall be taken into consideration when submitting bids. ADDENDUM, February 3, 0 RE: Chowchilla Elementary School District Wilson MS / Fuller ES Lease Leaseback Contractor BCA Project Number 0 / From: Bunton Clifford Associates, Inc. dba BCA Architects 0 th

More information

Core Network Switch RFP. Harrison School District Two 1060 Harrison Road Colorado Springs, CO

Core Network Switch RFP. Harrison School District Two 1060 Harrison Road Colorado Springs, CO Core Network Switch RFP Harrison School District Two 1060 Harrison Road Colorado Springs, CO 80905 Email: rfp@hsd2.org Technology Supervisor: Mike Peterson Bids DUE DATE: March 15th, 2017 Table of Contents

More information

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT 06045-0191 TRAFFIC SIGNAL INSTALLATIONS MIDDLE TURNPIKE EAST AT SUMMIT STREET MIDDLE TURNPIKE EAST AT

More information

INVITATION FOR BIDS For a Nutanix Hyper-Converged Platform (CIP# AHW1801)

INVITATION FOR BIDS For a Nutanix Hyper-Converged Platform (CIP# AHW1801) INVITATION FOR BIDS For a Nutanix Hyper-Converged Platform (CIP# AHW1801) BID SUBMITTAL DATE, TIME, & LOCATION: December 27, 2016 @ 2:00 PM Mount Pleasant Waterworks Operations Center 1619 Rifle Range

More information