Binary Input (BI) Object

Size: px
Start display at page:

Download "Binary Input (BI) Object"

Transcription

1 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 1199 Binary Input (BI) Object Introduction Page 3 Quick Start *3 Engineering Overview 9 Overview of Operation *9 Hardware Interface *12 Input Processing *23 Triggers and History *38 Reference Tables 43 BI Attribute Table *43 BI Command Table *53 * Indicates those sections where changes have occurred since the last printing 1999 Johnson Controls, Inc. 1 Code o. LIT

2 2 Objects Binary Input (BI) Object

3 Introduction A Binary Input (BI) object is the software representation of a hardware sensor that is monitoring a 2-state (on/off) field condition. The primary function of a BI object is to convert the raw hardware signal (i.e., changes in contact condition) from a binary input device to data that can be used in operator displays, alarm analysis, and control processes. Typical applications for a BI object include a water flow switch, a filter differential pressure switch, a level switch, auxiliary contacts from a chiller control panel, a motion detector, and a door switch. Quick Start Defining the BI This section tells you how to quickly define the BI from the Operator Workstation. Since most of the fields in the Definition window are already filled in with default values, all you need to do is fill in the fields without defaults, and make any necessary changes. The BI object can be defined: online, using the Operator Workstation BI Object Definition window. See the Operator Workstation User s Manual (FA 634) for instructions. offline, using the Graphic Programming Language (GPL) Database Template. See the GPL Programmer s Manual (FA 631) for instructions. offline, using the Data Definition Language (DDL). See the DDL Programmer s Manual (FA 630) for instructions. To define a BI object online at the workstation: 1. Go to the summary of the system in which you want to add the object. 2. Select Item from the Menu bar. Then select ew from the Item menu. A dialog box for selecting object type appears. 3. Select Binary Input from the list of object types. Then, in the Hardware System and Hardware Object fields, type the system/object name of the device the BI object will be mapped to. This must be an already defined device. (If the device is not defined, you must define it before you define the BI. See the device s technical bulletin for more information.) 4. Click OK. The Binary Input (XM) Definition window appears (as shown in Figure 1). Objects Binary Input (BI) Object 3

4 Binary Input (XM) Definition Help BLDG-1 AHU-1 AHU-1 System ame Object ame Expanded ID AHU-1 Comm. Disabled Graphic Symbol # Operating Instr. # 0 0 Hardware: XB, XRM, XRL System ame C5 Object ame XB1 Point Type SIGLE 1 Slot umber 24 Debounce Filter Y LED On when Relay Closed Flags Auto Dialout Enable PT History Save PT History Latching Point Y Parameters ormal State OE Alarm Delay (sec) 30 Alarm Delay Active Y Delay All Alarms Engineering Data State 0 (STOP) units State 1 (START) units off on Report Type ORMAL ALARM OVERRIDE OE OE OE Messages ALARM # 0 bieng1 Figure 1: BI Input (XM) Definition Window Displaying Default Settings ote that some of the fields are blank and some are already filled in. You must fill in the blank attribute fields (e.g., Object ame) because they do not have default settings. The attribute fields that are already filled in contain default settings, which you can either accept or change. Table 1 explains the attributes without default settings. Table 3 describes all BI object attributes. The Operator Workstation User s Manual (FA 634) tells you how to enter and change data. 4 Objects Binary Input (BI) Object

5 Table 1: Attributes without Default Settings Attribute Label Description Entry System ame Object ame Expanded ID (optional) H/W System ame H/W Object ame Has to be the name of an existing system, such as AHU_1 or AIR_SYS. When using GPL or DDL, you must define the System ame. When using the BI Object Definition window, the System ame contains a default setting. The object name cannot already exist under the given system name. This name defines the object, such as AIR_FLOW (for air flow switch). This is an expanded version of the object name. Appears at the Object Focus window, GPL template, and summaries. More clearly identifies the object. For example, AIR FLOW SWITCH. Must be the name of an existing DCM, DCM140, XM, ASC, System 9100 Controller, LOWORKS compatible device, IAC-600, DSC8500, or FPU System ame. Must be the name of an existing DCM, DCM140, XM, ASC, System 9100 Controller, LOWORKS compatible device, IAC-600, DSC8500, or FPU Object ame. Once the H/W System ame and Object ame are entered, the Definition window will display the appropriate default values in the remaining H/W fields, including Point Type, Slot umber, Subslot, Debounce Filter, and LED On. 8 alphanumeric characters 8 alphanumeric characters 24 alphanumeric characters 8 alphanumeric characters 8 alphanumeric characters 5. To save the new BI object, select Item from the Menu bar. Then select Save. The new BI object is added to the operational database in the etwork Controller (C). Objects Binary Input (BI) Object 5

6 GPL Template Default attribute settings are also available in the GPL template. Figure 2 shows the GPL Database Template for the BI object. BIARY IPUT OBJECT (BI) IDETIFICATIO EGIEERIG DATA System ame = State 0 Units = OFF Object ame = State 1 Units = O Expanded ID = HARDWARE System ame Object ame H/W Type Slot umber Point Type Debounce Filter LED On When Relay CLO = = = = = = = DCM 1 BI 2 sec Y F10 - SAVE, ESC/mouse click - CACEL, PGD - PAGE BIARY IPUT OBJECT (BI) FLAGS REPORT TYPE Auto Dialout = ormal = OE Enable PT History = Y Alarm = OE Save PT History = Override = OE Comm Disabled = Latching Point = MESSAGES PARAMETERS ormal State Alarm Delay = = OE 30 sec Alarm # = Graphic Symbol # = Operating Instr. # = F10 - SAVE, ESC/mouse click - CACEL, PGUP - PAGE bieng2 Figure 2: BI GPL Database Template Displaying Default Settings 6 Objects Binary Input (BI) Object

7 Modifying and Monitoring the BI Once the BI is defined, you can modify its attributes using the BI Focus window. You also use the Focus window to monitor and command the BI. You ll find information on using Focus windows in the Operator Workstation User s Manual (FA 634). You can modify the BI object: online, using the Operator Workstation BI Object Focus window offline, using the Graphic Programming Language (GPL) Database Template offline, using the Data Definition Language (DDL) This is the end of the Quick Start section. If you need more information on data entry procedures, see the Operator Workstation User s Manual (FA 634) and GPL Programmer s Manual (FA 631). For additional information on BI attributes, see the remainder of this document, which explains the relationship between various BI attributes from an applications perspective. In addition, you ll find an alphabetized listing of all BI attributes and commands (with descriptions and acceptable entries) at the end of this document. ote: Refer to the Control System (CS) Object Technical Bulletin (LIT ) for corresponding point mapping tables. Objects Binary Input (BI) Object 7

8 8 Objects Binary Input (BI) Object

9 Engineering Overview Overview of Operation Functional Flow Diagram BI software functions can be divided into four basic categories: Hardware Interface--A binary input device, such as a switch, is connected to one of the following hardware devices: Digital Control Module (DCM101 or DCM140), Point Multiplex Module (XM), 2OPE Application Specific Controller (AHU, UT, VAV, VMA, PHX, MIG, VD), System 9100 Controller (LCP, DX9100, DX91ECH, DC9100, DR9100, TC9100, XT9100, XTM), LOWORKS Device (LOTCU, LOTCUA, LOVMA, LOVMAA), Access Control System (IAC-600), FPU, or DSC8500. The device, in turn, is connected to the etwork Control Module through the 2 or S2 Bus. When the input device physically changes state (e.g., switching from an open to a closed condition), this information is detected by the hardware. ote: LOWORKS Devices LOTCUA and LOVMAA apply to American sites only. All other sites use LOTCU and LOVMA. Input Processing--The hardware input is processed by software functions, such as the debounce filter and Override command. Alarm Analysis--The BI current value is compared against a user-defined normal state to determine the object s ormal or Alarm status. A BI mapped to an 2OPE device that supports Trouble, or FPU BIF101, BIS101, or SST102 point modules, also has Trouble status, determined by supervised monitoring of the device circuit. The status (a COS [Change-of-State] report) and associated message is routed to operator devices. Triggers and History--BI attribute changes can be used for other purposes, including triggering control processes and historical archiving. Figure 3 illustrates the general operation of a BI object. The blocks represent the functions performed by the software. Each major block is summarized after the figure and explained in detail in this document. Objects Binary Input (BI) Object 9

10 Hardware Input Hardware Interface Debounce Filter Override Command Current Value Point History Alarm Analysis Control Process Triggering Alarm Delay Latch Function Change-of-State Reporting bieng3 Figure 3: Binary Input Functional Flow Diagram Hardware Interface Hardware Input--A binary input device, such as a switch, changes state, (e.g., switching from an open to closed contact condition.) This contact change is sensed by the XM, DCM, DCM140, 2OPE ASC, System 9100 Controller, IAC-600, DSC8500, or FPU. On a LOWORKS compatible device, the hardware input is a etwork Variable (V) in the device. Input Processing Debounce Filter--XM, DCM, and DCM140 only. Changes resulting from fluttering of contacts or process noise may be ignored by using a debounce filter. The filter is actually a time period set in software. The BI contact value is read only after this period has lapsed. 10 Objects Binary Input (BI) Object

11 Override Command--You can issue a manual Override command from an Operator Workstation (OWS). If you override the BI, you tell the system to ignore the actual physical open/closed condition of the object. The software will treat the BI as though it is in the state specified by the Override. Software processing of the Override command occurs at the etwork Control Module (CM). (ot available for BIs mapped to System 9100 or LOWORKS compatible devices.) Current Value--The BI current contact value becomes either: the data coming in from the field, filtered or unfiltered; or the value set with an Override command. Alarm Analysis Alarm Analysis--You may define a ormal State (attribute) for the binary input during database generation. Alarm analysis compares the BI contact value against the user-defined ormal State. (If the BI is used as feedback for a BO, the BO can also alter the ormal State attribute of the BI.) For BIs mapped to 2OPE devices that support Trouble, or FPU BIF101, BIS101, or SST102 point modules, supervised monitoring detects when the device circuit is abnormal and flags the status as Trouble. Alarm Delay--This function delays alarm reporting of the BI object for a user-specified period of time. The purpose of alarm delay is to prevent nuisance reports that could result from a BI current value change when the BI object is used as feedback for a BO object, or when the source value of the BI comes from a contact that may change its state either momentarily or several times before settling to the new condition (flutter contact). The alarm delay is not activated by an Override command from an operator to the BI object. See the Binary Output (BO) Object Technical Bulletin (LIT ) in the Metasys etwork Technical Manual (FA 636) for information on feedback. Latch Function--This function causes the BI object to stay in Alarm or Trouble once it changes to an Alarm or Trouble state. (The latching of the Trouble state applies only to BIs mapped to FPU BIF101 point modules.) Latching ensures that BI Alarm or Trouble states are acted upon by an operator or control process before the object returns to a normal state. Only an Unlatch command from an operator or control process can release the latched state. In the case of a BI mapped to an FPU BIF101, the Unlatch command is sent to the hardware. Change-of-State (COS) Reporting--If an alarm is detected, it may be reported at one or more Operator Workstations or printers. Operator Workstations and printers only receive the alarm report if they were defined as report destinations for that particular report type during the database generation process. Objects Binary Input (BI) Object 11

12 Triggers and History Control Process Triggering--An Alarm condition and other attribute changes can trigger (cause) a control process to run. Point History--Attributes of the BI object may be sent to a point history file. Hardware Interface The BI can map to the following hardware devices: DCM, DCM140, 2OPE ASCs (AHU, UT, VAV, VMA, MIG, PHX, VD), System 9100 Controller (LCP, DX9100, DX91ECH, DC9100, DR9100, TC9100, XT9100, XTM), LOWORKS compatible device (LOTCU, LOTCUA, LOVMA, LOVMAA), Smart Terminal Interface (IAC-600 system), FPU, and DSC8500. ote: LOWORKS compatible devices LOTCUA and LOVMAA apply to American sites only. All other sites use LOTCU and LOVMA. Mapping means: The binary input device is connected to a specific place on a specific controller. This place is referenced in software so that the BI object knows where to receive input signals. Figure 4 is a flow diagram of BI hardware interface. The blocks represent software functions. The dashed boxes represent the attributes that define or control the functions. 12 Objects Binary Input (BI) Object

13 Function Attribute Hardware Input Hardware System ame HVAC Application Specific Controller Point Type Point Address XM Hardware Object ame Slot umber LED On When Relay Closed IAC-600 Access Control System RDR umber BI Point Input Type System 9100 or LOWORKS Controller Point Type Hardware Reference Hardware Interface PT Enabled FPU Slot umber Binary Type Slot umber DCM and DCM140 LED On When Relay Closed Point Type DSC8500 Logical Point Type Logical Point umber bieng4 Figure 4: Binary Input Hardware Interface This section explains the attributes you ll use to establish the hardware interface between the BI and the appropriate device. The following two attributes, Hardware System ame and Hardware Object ame, are common to all devices: Hardware System ame must be of an existing system, such as C5. It might represent the control panel or etwork Control Module that s handling the BI. Hardware Object ame is the name of the hardware object (e.g., the name of the XM, DCM, DCM140, ASC, IAC-600, DSC8500, or FPU) that the object is mapped to. This object must be already defined. If it is not defined, define it before you define the BI. The remaining hardware interface attributes depend on which type of device you specify for the Hardware Object. For example, if you specify a DCM, the Slot umber attribute is applicable. If you specify a DSC8500, Logical Point Type and Logical Point umber attributes are applicable. Objects Binary Input (BI) Object 13

14 Mapping to a DCM and DCM140 A BI maps to any one of the ten universal inputs on the Digital Control Module (DCM101 and DCM140). (If an IB is used, 20 BIs can be mapped to the 10 universal inputs on the DCM.) ote: For the BI object, the DCM101 and DCM140 operate the same. Therefore, in this section, DCM indicates both DCM101 and DCM140. The DCM reads the BI hardware input, debounces filtering, and determines the current contact value of the BI. This contact value is then sent to the CM where alarm analysis, report routing, triggering, and historical data gathering take place. An Input Function Module (FM) provides the interface between the binary input and DCM. Each FM accepts one input, except for the IB FM, which accepts two inputs. See the Control Modules and Function Modules sections of this manual for additional DCM and FM information. Attributes Linking the DCM and the BI Object Besides the Hardware System and Object names, four attributes link the BI and the DCM: Point Type Slot umber Subslot umber LED On When Relay Closed Point Type identifies the type of FM used by the DCM. Enter BI for a single input FM. Enter MBI for a double input FM. The default is BI. An IB FM accepts two binary inputs. All other FMs accept only one. Slot umber represents the Function Module slot (1 through 10) where the BI device is connected. The BI is actually wired to a terminal on the terminal strips. This terminal is electrically connected to a specific FM slot. Enter a value from 1 to 10. The default is 1. Subslot umber only applies if the BI is connected to an IB Function Module at the DCM. An IB Function Module accepts two binary inputs. The subslot numbers (1 and 2) represent the two inputs on the IB. (Both 1 and 2 reside in the same FM slot.) The default setting is 1. LED On When Relay Closed determines if the input Light-Emitting Diode (LED) of the DCM is on or off when the BI relay is closed. Enter Y (yes) if you want the LED on when the relay is closed. Enter (no) if you want the LED off when the relay is closed. The default setting is Y (yes). This attribute setting does not apply when the BI is connected to an IB Function Module. The IB contains its own two LEDs, which are On when the relay is closed. 14 Objects Binary Input (BI) Object

15 Mapping to an XM A BI maps to any of the: 32 inputs on the XB Point Multiplex Module 8 inputs on the XRM Point Multiplex Module 8 inputs on the XRL Point Multiplex Module 8 inputs on the XRE Point Multiplex Module ote: An XRE is defined as an XRL. Point Multiplex Modules (XMs) read the BI hardware input, perform debounce filtering, and determine the current contact value of the Binary Input. This contact value is then sent to the etwork Control Module where alarm analysis, report routing, triggering, and historical data gathering take place. XMs in Slots 1 and 5 of a 5-slot CM, and in Slot 1 of a 2-slot CM, require Function Modules (FM). Otherwise, XMs do not require Function Modules. If FMs are not used, the binary input devices connect directly to XMs via terminal strips on the CU or EU. For further hardware information, see the Control Modules and Function Modules sections of this manual. Attributes Linking the BI and XM Besides Hardware System and Object names, three attributes link the BI and XM: Point Type Slot umber LED On When Relay Closed Point Type signifies the type of contact. Enter Single for a single input, Form A contact. Enter Formc for a double input, Form C contact. The default setting is Single. Slot umber represents the input address (terminal strip location) where the BI is connected. For the XB, enter For the XRM, XRL, or XRE, enter 1-8. The default setting is 1. (If an IU Function Module is required, the slot number represents one of the two FM subslots.) LED On When Relay Closed determines if the input LED (of the XM) is on or off when the BI relay is closed. Enter Y (yes) if you want the LED on when the relay is closed. Enter (no) if you want the LED off when the relay is closed. The default setting is Y (yes). This attribute setting does not apply when the BI is connected to an IB Function Module. The IB contains its own two LEDs, which are on when the relay is closed. Objects Binary Input (BI) Object 15

16 Mapping to 2OPE ASCs BI objects can map to the following 2OPE Application Specific Controllers: AHU, UT, VAV, VMA, MIG, PHX, and VD. Attributes Linking the BI Object and the 2OPE ASC Besides the Hardware System and Object ames, two attributes link the BI object and the 2OPE ASC: Point Type Point Address Point Type identifies the type of point in the controller the BI is mapped to. It must be a Binary Input (BI) point. Point Address specifies the address of the BI point in the controller that the BI will map to. The range depends on the type of ASC the BI is mapped to: AHU: BI 1 to 8 UT: BI 1 to 12 VAV: BI 1 to 12 VMA:BI 1 to 3 MIG: 1 to 256 PHX: 1 to 37 VD: 1 to 256 IMPORTAT: If you are mapping a CS object attribute and a standard object to the same hardware reference (the hardware reference is the combination of the point type and point address), make sure the Override and Adjust flags are set to o (False) for the CS object attribute. This is to ensure that there is only one command path to the hardware reference. Mapping to a System 9100 Controller BI objects can map to System 9100 Application Specific Controllers (LCP, DX9100, DX91ECH, DC9100, DR9100, TC9100, XT9100, XTM). ote: A BI can map to a System 9100 Controller that is connected to a Fire or Access CM200. However, a BI cannot map to a System 9100 Controller that is connected to a Fire CM101. A System 9100 CM101 does not support the TC9100. The Echelon 2E Bus version of the DX controller (DX91ECH) must be connected to an CM300 or CM Objects Binary Input (BI) Object

17 Attributes Linking the BI Object and the System 9100 Controller Besides the Hardware System and Object ames, two attributes link the BI object and the System 9100 Controller: Hardware Device Type Hardware Reference Hardware Device Type identifies the type of System 9100 Controller the BI is mapped to. The options are LCP, DX9100, DX91ECH, DC9100, DR9100, TC9100, XT9100, and XTM. Hardware Reference specifies the address of the point in the controller the BI is mapped to. The range depends on the type of System 9100 Controller. Valid System 9100 device types and hardware references are: LCP\DC9100 DI1-8, LCM1-4 DX9100 DI1-8, LRS1-32, XT1-8DI1-8 DX91ECH DI1-8, LRS1-64, XT1-8DI1-8 DR9100 WI, OCC, AIRQ TC9100 WI, OCC, AIRQ, ALM, AFM, L1A, L3A XT9100 1DI1-8, 2DI1-8 XTM 1DI1-8, 2DI1-8 Mapping to a LOWORKS Compatible Device BI objects can map to LOWORKS devices. ote: LOWORKS devices must be connected to a CM350. Attributes Linking the BI Object and the LOWORKS Compatible Device Besides the Hardware System and Object ames, two attributes link the BI object and the LOWORKS compatible device: Hardware Device Type Hardware Reference Hardware Device Type identifies the type of LOWORKS compatible device the BI is mapped to. At present, device types include LOTCU, LOTCUA, LOVMA, and LOVMAA. ote: LOWORKS compatible devices LOTCUA and LOVMAA apply to American sites only. All other sites use LOTCU and LOVMA. Objects Binary Input (BI) Object 17

18 Hardware Reference specifies the address of the point in the controller the BI is mapped to. The range depends on the type of LOWORKS device. Valid LOWORKS compatible device hardware references are: xxbixxx (the xs are placeholders for specific addressing numbers and characters; see the device s technical bulletin for details) Mapping to an IAC-600 Access Control System BI objects can map to an IAC-600 Access Control System. More specifically, a BI object represents a binary alarm point circuit located within a Smart Terminal Interface (STI). ote: Before defining BI objects, you should be familiar with the main components of the IAC-600 system and how they function (i.e., D600 Controller, STIs, card readers, and binary inputs). Each STI has eight binary input circuits. These eight circuits monitor any type of alarm detector that provides a normally closed dry contact that opens to indicate an Alarm state. While input points are typically used for alarm detectors, they can also be used to monitor status changes for any device that provides a normally closed, dry contact output. For more information about STIs and Card Reader objects, refer to the Access Control System Objects Technical Bulletin (LIT ) in the Metasys etwork Technical Manual (FA 636). 18 Objects Binary Input (BI) Object

19 Attributes Linking the BI Object and the IAC-600 System Besides the Hardware System and Object ames, four attributes link the BI object to an STI. For information on other IAC-600 system attributes, see the Alarm Analysis section of this document. RDR umber BI Point umber Input Type PT Enabled RDR umber identifies the STI/card reader for which you wish to define this binary alarm point. The range is 1 to 16. The number you enter corresponds to the physical connection of the STI to the D600 Controller (i.e., 1 to 8 on MTI Board 1, 9 to 16 on MTI Board 2). BI Point umber identifies the terminal in the STI that the binary input circuit connects to. The range is 1 to 8. Input Point 1 at each STI is factory set for use as a door open detector because it works in conjunction with the Access Timer, Alarm Shunt Delay, and the Anti-Tailgate Check attributes of the Card Reader object. ote that if you wish to use Input Point 1 for any other purpose, an abnormal COS at that input point still generates a Door Open report. In addition, if you use this input point for other uses, be sure the Card Reader object s Alarm Shunt Delay attribute is set to zero, and its facility code on Backup attribute is set to o. Input Point 2 at each STI is factory terminated to the tamper switch of the STI enclosure. However, Input Point 2 is not different than Input Points 3 to 8, and may be used for any other purpose if an enclosure tamper is not required. Input Points 3 to 8 are intended for general purpose alarm detection. Input Type identifies the type of input--2-state. This attribute is predefined and cannot be changed. PT Enabled identifies whether the binary alarm point is recognized (enabled) or ignored (disabled) by the D600 Controller. Once enabled (Y), the binary alarm point status changes are always reported to the D600 Controller unless you use a time zone to suppress it. The settings for this attribute are Y (enabled) or (disabled). For a definition of an Alarm Suppression Time Zone, see the Alarm Analysis section of this document. Objects Binary Input (BI) Object 19

20 Mapping to an FPU BI objects can map to an FPU. More specifically, a BI object represents one of the following binary point contacts in the FPU: BI101, BIF101, BIS101, SST101, or SST102. Attributes Linking the BI Object and the FPU Besides the Hardware System and Object ames, two attributes link the BI and FPU: Slot umber Binary Type Slot umber identifies the input address on the FPU where the field device is connected. The range is Binary Type specifies the type of contact in the FPU. The Binary Type can be BI101, BIF101, BIS101, SST101, or SST102. If the Binary Type is BIF101, BIS101, or SST102, the object s ormal State attribute must be State 0. If the Binary Type is BIF101, the Latching Point attribute must be set to Y (yes) to accommodate supervised monitoring of the Alarm and Trouble state at the point module hardware. For more information, see the Supervised Monitoring and Trouble Status section, under Alarm Analysis, later in this document. Mapping to a DSC8500 BI objects can map to a DSC8500. ote: When using CAL1 to define a DSC8500 point that will be mapped to a Metasys etwork object, enable status reports to the Facility Management System (FMS) for the point. Conversely, if the point will not be mapped to a Metasys object, disable status reports to the FMS for the point. Attributes Linking the BI Object and the DSC8500 Besides the Hardware System and Object ames, two attributes link the BI object and the DSC8500: Logical Point Type Logical Point umber Logical Point Type identifies the type of point in the DSC8500 the BI will be mapped to. For the BI, the LPT can be BSP, BDP, CO, or MA. Logical Point umber identifies the number of the specified LPT on the DSC8500 where the field device is connected. The range is Objects Binary Input (BI) Object

21 Unreliable and Communication Status Unreliable Status The BI object may become unreliable due to an offline condition (communication break) or faulty field hardware. When the BI object is unreliable, the following attributes that are derived from the contact value also become unreliable: Current Value Status Display ASCII Representation Value ormal Status * Alarm Status * Trouble Status * * These attributes are hidden. They do not appear as fields at the BI Object Focus window or T display. However, you might use them in control process programming. Keep in mind that if these attributes become unreliable, they can affect the results of the control process. See Table 3 at the end of this document for additional information on these attributes. You can determine if a Binary Input is unreliable by looking at its Focus window or any summary containing information about the object. When the object is unreliable, the Current Value and Status attributes will display???? (question marks) rather than a value in the BI Focus window and in summaries. Figure 5 shows a Focus window for an unreliable, offline object. Communication Status The Comm. Status field in the object Focus window is used for both online/offline status and disconnect status. (Disconnect status applies to 2 Dialer Module (DM) applications only.) An object is offline when there is a communications break between the controller the object is mapped to and the CM or DM the controller is connected to. If an object is offline, OFFLIE appears in the Comm. Status field of the object s Focus window. Figure 5 shows a Focus window for an object that is offline and unreliable. In addition, an offline object appears in the Offline summary. In DM applications, if the remote DM is disconnected from the local DM, DISCOCT appears in the Comm. Status field. If the DMs are connected, either OLIE or OFFLIE appears in the field, depending on whether the controller the object is mapped to is online. Objects Binary Input (BI) Object 21

22 Binary Input (XM) Focus Item Edit View Action GoTo Accessory Help BLDG-1 AHU-1 SF-STS Supply Fan Status AHU-1 Point History Current Trend System ame Object ame Expanded ID Current Value???? AHU-1 SF-STS SUPPLY FA STATUS Reports Locked Trigger Locked Comm. Disabled Comm. Status S/W Override Status OFFLIE???? Graphic Symbol # Operating Instr. # 0 15 Hardware: XB, XRM, XRL System ame FLOOR1 Object ame BI1 Point Type SIGLE Slot umber 1 Debounce Filter 24 LED On when Y Relay Closed Flags Auto Dialout Save PT History Latching Point Alarm Latched Parameters ormal State Alarm Delay (sec) Delay All Alarms off 30 Engineering Data State 0 (STOP) units State 1 (START) units off on Report Type ORMAL ALARM OVERRIDE OE CRIT2 CRIT3 bieng5 Figure 5: Focus Window of an Offline, Unreliable Binary Input 22 Objects Binary Input (BI) Object

23 Input Processing The figure below is a flow diagram of BI object input processing. The blocks represent software functions. The dashed boxes represent the attributes that define or control the functions. Hardware Input Function DCM, DCM140, and XM Debounce Filter Debounce Filter Attribute Override command from operator Override Command Current Value Status S/W Override State 0 (Off) Units State 1 (On) Units Current Value Current Value Alarm Analysis bieng6 Figure 6: BI Input Processing Functional Flow Debounce Filter ote: The following information on debounce filtering applies only to a BI mapped to a DCM, DCM140, or XM. Mechanical contacts often bounce a few times when they close. This contact flutter can cause excessive alarm reporting. An optional software debounce filter function may be used to avoid analyzing these nuisance contact changes, and to prevent unnecessary communication traffic on the 2 Bus. The debounce filter is an attribute of the BI object that is set when the object is defined. You specify the debounce filter as a time period. Contact fluctuations are ignored and, thus, filtered during this time period. Objects Binary Input (BI) Object 23

24 Attributes to Set for Debounce Filter The Debounce Filter attribute affects the Debounce Filter function: Debounce Filter defines the period of time the software waits before reading the value of a fluttering (bouncing) contact. If the BI device is wired to a DCM or DCM140, enter the time period in seconds (1-255). If the BI is wired to an XM, enter the time period in milliseconds ( ), in multiples of 12 such as 12, 24, 36, and 48. ote: If you don t want to use a debounce filter, specify 1 second for the DCM/DCM140 or 12 milliseconds for the XM. How the Debounce Filter Works Debounce filter processing takes place at the DCM, DCM140, or XM, where the BI device is connected. Debouncing works as shown in Figure 7. Actual Contact Debounce Time Debounce Time bieng7 Filtered Output Figure 7: Debounce Filter Timing Diagram The debounce filter works as follows: 1. A Binary Input object is assigned a debounce filter time of, for example, 24 milliseconds. 2. When the contact changes state, the debounce timer starts. 3. The contact may be fluttering during the debounce time period of 24 milliseconds. The software ignores the contact value during this period. 4. When the debounce filter times out at 24 milliseconds, the contact value is read by the software. 5. This filtered contact reading becomes the current contact value of the BI object. This value is sent to the CM where alarm analysis occurs. 24 Objects Binary Input (BI) Object

25 Override Command The following information on the Override command and S/W Override attribute does not apply to a BI mapped to a System 9100 Controller or LOWORKS compatible device. Use the Override command to set the BI contact to a specific value, such as Opened, Closed, On, or Off. An Override command can be issued from an Operator Workstation Command Action menu (input objects cannot be overridden from the etwork Terminal). You might decide to execute an Override command if there is faulty or offline hardware, or if you want to simulate a field condition. For example, a device that s monitoring a filter may become defective and start generating nuisance changes-of-state. In this situation, you could issue an Override to force the contact to a closed (dirty) value. What Attributes Are Affected by the Override Command? Three attributes are affected by this command: Current Value Status S/W Override Current Value is updated to reflect the new contact value you specified with the Override command. This is displayed at the BI Focus window. For example, the Current Value field could show On, Off, Open, or Closed. Status is updated to reflect the results of alarm analysis. Alarm analysis occurs because you set a new Current Value with the Override command. The Current Value is compared against a user-defined ormal state. The new status is displayed at the BI Focus window. S/W Override is changed to Y to indicate that the object is software overridden. This is displayed at the BI Focus window. If the Override command hasn t been used, this field displays an. Figure 8 shows the Focus window of a BI object that has been overridden to a Current Value of Off. Objects Binary Input (BI) Object 25

26 Binary Input (XM) Focus Item Edit View Action GoTo Accessory Help BLDG-1 AHU-1 SF-STS Supply Fan Status AHU-1 Point History Current Trend System ame Object ame Expanded ID Current Value AHU-1 SF-STS SUPPLY FA STATUS OFF Reports Locked Trigger Locked Comm. Disabled Comm. Status S/W Override Status OLIE Y ORMAL Graphic Symbol # Operating Instr. # 0 15 Hardware: XB, XRM, XRL System ame FLOOR1 Object ame BI1 Point Type SIGLE Slot umber 1 Debounce Filter 24 LED On when Y Relay Closed Flags Auto Dialout Enable PT History Save PT History Latching Point Alarm Latched Parameters ormal State Alarm Delay (sec) Alarm Delay Active Delay All Alarms off Engineering Data State 0 (STOP) units State 1 (START) units off on Report Type ORMAL ALARM OVERRIDE OE CRIT2 CRIT3 bieng8 Figure 8: BI Focus Window Displaying Status and Current Value What Happens When an Override Command Is Executed? A contact change resulting from an Override command is always processed immediately. The Commanded state becomes the current contact value, taking priority over the field contact condition. An Override command will also cancel any alarm delay timing that may be in effect. While the BI object is in an Overridden state, the software continues to monitor the physical condition of the object. However, change-of-state reporting and control process triggering from these changes are suppressed. When the Override command is released with the Auto command, the last field change that had been reported to the etwork Control Module becomes the current contact value. 26 Objects Binary Input (BI) Object

27 Current Value The current contact value read by the software is either: the actual field contact condition (filtered or unfiltered) or the contact condition set with an operator Override command--this takes priority Attributes Associated with the Current Value Three attributes are associated with the Current Value: Current Value State 0 (Off) Units State 1 (On) Units Current Value is the attribute that represents the present condition of the object, such as On or Off. This attribute is not definable. State 0 (Off) Units are ASCII alphanumeric characters that are used to represent the open contact condition. The default setting is Off. State 1 (On) Units are ASCII alphanumeric characters that are used to represent the closed contact condition. The default setting is On. Enter up to six ASCII alphanumeric characters for each of the units above. Examples include On/Off, Open/Closed, Clean/Dirty, and so on. The BI Current Value is displayed as one of these two engineering units (e.g., Off or On) at the BI Focus window, T screen, and object summaries. Objects Binary Input (BI) Object 27

28 Alarm Analysis Figure 9 is a flow diagram of BI alarm analysis. The blocks represent software functions. The dashed boxes represent the attributes that define or control the functions. Function Current Value Attribute ormal State Alarm Analysis and Supervised Monitoring Status Delay All Alarms Alarm Delay Alarm Delay Active Latch Point Latch Function Status Alarm Latched Trouble Latched Alarm if Set Quiet if Reset Local Alarm Annunciation Status Report Type ormal Report Type Alarm Report Type Override Message Alarm # Change-of-State Reporting Reports Locked Auto Dial-Out Alarm Suppression Time Zone bieng9 Figure 9: BI Alarm Analysis Functional Flow 28 Objects Binary Input (BI) Object

29 Alarm analysis is a software process that compares the BI Current Value against a user-defined ormal State attribute. The purpose of alarm analysis is to determine the BI status. The status can be: ormal--the BI contact condition matches what has been user-defined as the ormal State. Alarm--The BI contact condition doesn t match what has been user-defined as normal. Trouble-- The BI contact is experiencing abnormality in the device circuit. This status only applies to BIs mapped to FPU BIF101, BIS101, or SST102 point modules, or to 2OPE devices that support Trouble. Attributes to Set for Alarm Analysis ormal State specifies the contact value that you consider normal (State 0, State 1, or one). If the BI is mapped to an FPU BIF101, BIS101, or SST102 point module, the object s ormal State attribute must be State 0. When you specify the ormal State, instead of State 0 or State 1, you use the units assigned to these states, such as On, Off, Clean, Dirty. The three entries for ormal State are explained below: State 0 (Off) or State 1(On) Units--When you define the BI, you set two attributes--state 0 and State 1--that define the open and closed physical condition of the contact. Possibly you named them Off and On, or Stop and Start. ow you are specifying which of these physical conditions is ormal. This creates two possible logical states for the BI: Alarm or ormal. (BIs mapped to devices that support supervised monitoring have an additional state, Trouble, which is explained in this section, under Supervised Monitoring and Trouble Status.) one--this means the BI is a status-only object. Although the current contact value, such as On or Off, is reported to operator devices, alarm analysis is not performed. The status is always shown as ormal in the Focus window and on summaries. For example, let s assume you have a normally open contact monitoring air flow across a filter. You set the State 0 Units to Clean, the State 1 Units to Dirty, and the ormal State to Clean. When the contact closes, the air flow switch is in the State 1 condition--dirty. Alarm analysis compares this condition (Dirty) to what you defined as normal, which is Clean. These values don t match, so the object is considered in Alarm. Objects Binary Input (BI) Object 29

30 When Does Alarm Analysis Occur? Alarm analysis begins when: The contact value changes due to a field change. A new value is received from an operator Override command. You modify the BI ormal State attribute at an object Focus window, through an associated BO object, or within a control process. ote: An associated BO changes the BI ormal State when the Binary Input object is used as feedback for the BO object. This is explained later. Supervised monitoring of an FPU BIF101, BIS101, or SST102 point module detects device circuit trouble. Supervised Monitoring and Trouble Status For BIs mapped to devices that support Trouble status (2OPE and FPU BIF101, BIS101, and SST102 point modules), three states are possible: ormal, Alarm, and Trouble. The Trouble state indicates a problem detected in the device circuit. ote: For information on how Alarm and Trouble states can trigger processes for BI objects mapped to devices that support Trouble status, see the Triggers and History section in this document. Metasys system support of supervised monitoring and Trouble status works as follows: Status of the object (Read, ormal, Alarm, or Trouble) is returned. If the BI object s status is Trouble, the object is displayed in the online Trouble summary. Trouble status is triggerable. The Trouble Report Type is the same as the Alarm Report Type defined for the BI. For example, if the Alarm Report Type is Follow-up for the BI, the Trouble Report Type is also Follow-up. The trouble message is the same as the alarm message defined for the BI. Metasys software is not UL 864 or UL 1076 Listed as a result of support of supervised monitoring. 30 Objects Binary Input (BI) Object

31 The following additional points apply to BIs mapped to FPU BIF101, BIS101, or SST102 point modules: In the case of the BIF101, the Alarm or Trouble status is latched at the hardware. Only an Unlatch command can release the Alarm or Trouble status. If latched into Trouble and an alarm occurs, the hardware latches into Alarm. For BIs mapped to BIF101 point modules, the Unlatch command is sent to the hardware. For BIs mapped to FPU BIF101, BIS101, or SST102 point modules, the ormal State attribute must be set to State 0. For BIs mapped to FPU BIF101 point modules, the Latching Point attribute must be set to Y (yes). Do not use BIs mapped to FPU BIF101, BIS101, or SST102 point modules as feedback for any BO. If you must use the SST102 as feedback, make sure the BI mapped to the SST102 has its latch flag set to o. For the BIS101, the Access/Secure JC/85/40 function can be implemented on a Metasys system using the Lock Reports command. Specifically, when reports are locked for the BI mapped to a BIS101, the BI functions similar to the Access mode of the JC/85/40. When reports are unlocked, the BI functions similarly to the Secure mode. Alarm Delay This function delays alarm reporting of the BI object for a user-specified period of time. The purpose of the alarm delay is to prevent nuisance reports that could result from a BI current value change when the BI object is used as feedback for a Binary Output object, or when mapped to flutter contact. The alarm delay timer is started when the BI ormal State attribute is modified by an associated BO object. When the Delay All Alarms attribute is set, the alarm delay timer is started whenever the BI current value changes from the normal to the Alarm state except when caused by an Override command to the BI object. ote: Alarm delay processing at the etwork Control Module is different than debounce filtering at the DCM, DCM140, or XM. The debounce filter eliminates mechanical contact fluctuations from being processed by the system at a very low level. Alarm delay timing eliminates a legitimate physical change from being considered an alarm--allowing a whole mechanical system to stabilize first. Alarm Delay When the BO is Mapped to a System 9100 Controller If the BO is mapped to a System 9100 Controller and the BO s Local Control attribute is set to yes, regardless of the commanding feature, the BI used as feedback has its alarm delay activated in two situations: when the BI receives a new ormal State from the BO, and when the BI changes state as a result of polling the hardware. Objects Binary Input (BI) Object 31

32 Attributes to Set for Alarm Delay The Alarm Delay attribute affects alarm delay. It specifies the time that the software will wait before issuing an Alarm COS report. You can specify a delay time of 0 to 255 seconds. The Delay All Alarms attribute specifies if the alarm delay function should be active for all COS transitions from the normal to the Alarm state except those caused by an Override command to the BI object. Alarm Delay Active Alarm Delay Active is an output flag indicating the delay timer is running. Since this is not a configuration parameter, the user cannot change it. Application Example of Alarm Delay An application for alarm delay is shown below. The BI object has been defined with an alarm delay time of 15 seconds. CM BO BO Object DCM, XM, ASC, FPU, or DSC8500 Starter BI BI Object Fan Status Pressure Switch bieng10 L H Figure 10: Application of BI Alarm Delay In this figure, there are two separate objects: a Binary Output (supply fan), and a Binary Input (air flow switch). Although these are two distinct objects, they work together to perform one function. The BO starts the fan. The BI monitors airflow in the duct after the fan starts. This is how it works: 1. When this BO was defined, a Feedback attribute was specified. This feedback represents the Binary Input object that s monitoring airflow in the duct. 2. The BO object issues a Start command to the fan. When this happens, the BI receives a new ormal State value from the BO. The ormal state was previously defined as Open. The BO now changes it to Closed (i.e., the air flow switch closes when the fan is commanded to start). 3. When the BO sends out the new BI ormal State, the BI alarm delay timer starts. Without the timer, the BI would immediately go into Alarm. 32 Objects Binary Input (BI) Object

33 4. After the alarm delay times out, the contact value of the BI is read by the software. 5. If the contact is closed, air is flowing, and the BI status is considered ormal. If the contact is open, air is not flowing, and the BI is in Alarm. Latch Function Latching is a function that causes the BI object to stay in Alarm (or Trouble) once it changes to an Alarm (or Trouble) condition. The purpose of Latching is to ensure that BI Alarm changes are acted upon by an operator or control process before the object returns to a ormal State. For a BI mapped to a BIF101 point module, the hardware itself is latched into Alarm or Trouble. Only an Unlatch command can release the latched hardware. ote: If a ormal State isn t defined for the BI, the object can t go into Alarm. (It s a status-only object.) Under these conditions, the Latch function has no meaning and is not operational. Attributes to Set for the Latch Function The Latching Point affects latching. Enter Y (yes) to make the BI object a latching point, or (no) to not. The default setting is o. If the BI is mapped to an FPU BIF101, the Latching Point attribute must be set to Y (yes). If the BI is mapped to an FPU BIS101, setting the Latching Point attribute to Y (yes) is optional. If the BI is mapped to an SST102, setting the Latching Point attribute to Y (yes) is not recommended. How the Latch Function Works If you define a BI object as a latching point, the following occurs when the Status attribute changes to Alarm or Trouble: The Status attribute is locked (latched) into Alarm. (In the case of a BI mapped to an FPU BIF101 point module, the status attribute will also latch into Trouble. If latched into Trouble and an Alarm occurs, the object will be latched into Alarm.) ote: This also means that the hidden attributes--ormal status, Alarm status, and Trouble status--are locked. The ormal status attribute is set to false and the Alarm status or Trouble status attribute is set to true. These attributes are considered hidden because they do not appear at the BI Object Focus or Definition windows. ormal status, Alarm status, and Trouble status are mentioned here because this information may be helpful for Troubleshooting or control process programming. Field changes, as well as Override commands, don t alter the Status, ormal Status, Alarm Status, and Trouble Status attributes. Objects Binary Input (BI) Object 33

34 The Current Value continues to update. o further Alarm analysis is performed (except in the case of a BIF101 latched into Trouble. If latched into Trouble and an Alarm occurs, the object will be latched into Alarm.) Unlatch Command Only an Unlatch command from an operator or control process can release the latched state. You can issue an Unlatch command at any time. However, the object s status will not return to ormal until the Current Value (contact value) changes to what is defined as ormal. See Figure 11. When a BI object is Unlatched, the following occurs: The Status, ormal Status, and Alarm or Trouble Status attributes are unlocked. Field changes and Override commands can alter the value of these attributes. In the case of a BI mapped to an FPU BIF101 point module, the unlatch command is sent to the hardware (as a Reset Latched Point command). Alarm analysis resumes. Operator Unlatch command has no effect. Operator Unlatch command has an effect because current value = user-defined normal state. Open Contact Current Value = Off Status = ormal Latch Status = o Current Value = On Status = Alarm Latch Status = Yes Current Value = Off Status = Alarm Latch Status = Yes Current Value = Off Status = ormal Latch Status = o Closed Contact ormal state is user-defined as Off. Operator Unlatch command has no effect. bieng11 Figure 11: Timing Diagram of the Latch Function Local Alarm Annunciation This function only applies to BI objects mapped to the IAC-600 Access Control System. When a binary input is set into alarm, you may also program a normally open relay on the D600 Controller main circuit board to be switched. If this relay is switched, a COS for the BI object is reported to Operator Workstations. This relay can also be used for sounding a bell or other types of annunciating devices. When the alarm is acknowledged, the bell is also silenced. 34 Objects Binary Input (BI) Object

Analog Input (AI) Object

Analog Input (AI) Object Issue Date April 9, 2003 TECHNICAL BULLETIN Analog Input (AI) Object Analog Input (AI) Object...3 Introduction... 3 Key Concepts... 4 Defining the AI... 4 Modifying and Monitoring the AI... 6 Overview

More information

Control System (CS) Object

Control System (CS) Object Metasys Network Technical Manual 636 Objects Section Technical Bulletin Issue Date 0101 Control System (CS) Object Introduction Page *3 Quick Start *3 Overview of Concepts *6 Software Models *9 Engineering

More information

Analog Data (AD) Object

Analog Data (AD) Object Issue Date 11/01/01 TECHICAL BULLETI Analog Data (AD) Object Introduction Page 2 Applications 2 Quick Start 3 Engineering 9 Overview of Operation 9 Input Processing 12 Alarm Limit Analysis 25 Triggers

More information

APPLICATION NOTE JC/85

APPLICATION NOTE JC/85 Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software

More information

Polling the N2 Network or Zone Bus for Devices

Polling the N2 Network or Zone Bus for Devices Metasys Checkout Tool User s Guide 3-1 Chapter 3 Polling the N2 Network or Zone Bus for Devices Introduction The first step in the checkout process is using the Metasys Checkout Tool to find and display

More information

CF Terminal User s Guide

CF Terminal User s Guide Table of Contents CF Terminal User s Guide Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 Chapter Organization...1-2 Questions or Comments...1-2 Chapter 2 Getting Started...2-1

More information

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4 FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in

More information

Introduction to the N30 Supervisory Controller

Introduction to the N30 Supervisory Controller N30 Supervisory Controller User s Manual 2-1 Chapter 2 Introduction to the N30 Supervisory Controller Introduction This chapter describes the basic functions and operation of an N30 Supervisory Controller

More information

NDM Configurator. Introduction Page *3. Configuration Files 5. Downloading 17 APPLICATION NOTE

NDM Configurator. Introduction Page *3. Configuration Files 5. Downloading 17 APPLICATION NOTE System 9100 Technical Manual 636.4 Network Communications Section Application Note Issue Date 0896 APPLICATION NOTE NDM Configurator Introduction Page *3 Configuration Files 5 Hardware Requirements *5

More information

Appendix A: N1 OPC Data Access Server

Appendix A: N1 OPC Data Access Server Issue Date July 14, 2003 TECHNICAL BULLETIN Appendix A: N1 OPC Data Access Server Appendix A: N1 OPC Data Access Server...3 Introduction... 3 Key Concepts... 4 N1... 4 OLE... 4 OPC... 4 Site... 4 N1 OPC

More information

Glossary. The hardware object that defines the interface between the D600 Controller and the NCM.

Glossary. The hardware object that defines the interface between the D600 Controller and the NCM. Metasys Network Technical Manual 636 Glossary Section Technical Bulletin Issue Date 1092 Glossary Access Controller Accumulator (ACM) ACM active hub active link AHU Controller alarm latching Analog Data

More information

Metasys Checkout Tool User s Guide

Metasys Checkout Tool User s Guide Table of Contents Metasys Checkout Tool User s Guide Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 Chapter Organization...1-2 Chapter 2 Introduction to the Metasys Checkout Tool...2-1

More information

Defining Devices. Introduction

Defining Devices. Introduction Operator Workstation User s Manual 3-1 Chapter 3 Defining Devices Introduction Devices include NCMs, OWSs (PCs or portable computers), and printers. Each network has a system called Devices, which contains

More information

Metasys System Configuration Tool (SCT)

Metasys System Configuration Tool (SCT) Product Bulletin Issue Date March 31, 2003 Metasys System Configuration Tool (SCT) As an integral part of the Metasys system extended architecture, the System Configuration Tool (SCT) supports the engineering,

More information

Digital Control Module 140

Digital Control Module 140 Metasys Network Technical Manual 636 Control Modules Section Technical Bulletin Issue Date July 28, 2003 Digital Control Module 140 Introduction Page 2 Description 2 Theory of Operation 2 Engineering 6

More information

Lab and Central Plant Controller

Lab and Central Plant Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is

More information

Johnson Controls ComBus Quick Tester

Johnson Controls ComBus Quick Tester Johnson Controls ComBus Quick Tester MS-CQT485-0 Documentation Number: MS-CQT485-0_0405m pn#6550 Contents Section 1: Introduction - Controls & Features... 1 ComBus Quick Tester... 1 Figure 1 - End & Front

More information

Extended Digital Controller

Extended Digital Controller The Metasys Extended Digital Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1093 Extended Digital Controller (DX-9100) is the

More information

Defining Points. Introduction

Defining Points. Introduction M-Series Workstation with Companion/Facilitator Manual 9-1 Chapter 9 Defining Points Introduction This chapter explains how to define software points. Points are software representations of input and output

More information

Output Relay Latched Function Module

Output Relay Latched Function Module Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0793 Output Relay Latched Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory

More information

N1 Migration with the NIE

N1 Migration with the NIE Technical Bulletin Issue Date April 29, 2003 N1 Migration with the NIE N1 Migration with the NIE...3 Introduction... 3 Key Concepts... 4 N1 Migration Overview... 4 N1 Migration Flowchart... 5 Metasys N1

More information

M-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems

M-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems Product Bulletin Issue Date July 6, 2006 Supersedes June 30, 2004 M-Tool M-Tool transforms the way you create control strategies by providing a suite of tools with an intuitive and efficient work environment.

More information

Output Relay Electrical Function Module

Output Relay Electrical Function Module Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0294 Output Relay Electrical Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory

More information

Metasys Integrator Northern Application

Metasys Integrator Northern Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details

More information

Metasys Smoke Control Wiring

Metasys Smoke Control Wiring Metasys Network Technical Manual 636 Smoke Control Section Technical Bulletin Issue Date 1199 Metasys Smoke Control Wiring Metasys Smoke Control Wiring Page 3 Overview 3 References 4 Power Entry 5 Metasys

More information

Metasys and Companion

Metasys and Companion Metasys Network Technical Manual 636 App. Notes: Operator Devices Section Technical Bulletin Issue Date 0191 Metasys and Companion Application Page 3 Purpose of Application 3 Setting Up the Windows Terminal

More information

Compass RTU Guide. Version 3.x

Compass RTU Guide. Version 3.x Compass RTU Guide Version 3.x Compass RTU Guide Ver 3.x OSSI W228 N727 Westmound Dr Waukesha WI 53186 USA TEL: 262-522-1870 FAX: 262-522-1872 Ossi-usa.com Intelli-Site Security Management Software Compass

More information

N2 Binary Input/ BACnet Binary Input

N2 Binary Input/ BACnet Binary Input Object Dictionary 1 N2 Binary Input/ BACnet Binary Input Introduction Note: The Johnson Controls Binary Input object is considered a BACnet Binary Input object, because it supports BACnet functionality.

More information

Metasys System Extended Architecture Overview

Metasys System Extended Architecture Overview Technical Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture Overview Metasys System Extended Architecture Overview...2 Introduction... 2 Key Concepts... 4 Metasys System Extended

More information

XTM Configurator. Introduction Page 3. Theory of Operation *3. Configuration Procedures 7

XTM Configurator. Introduction Page 3. Theory of Operation *3. Configuration Procedures 7 FANs 636.4, 1628.4 XTM/XPx Section Technical Bulletin Issue Date 0400 XTM Configurator Introduction Page 3 Theory of Operation *3 Configuration Procedures 7 Design Considerations 8 Start XTM Configurator

More information

Discontinuation of N2 and Select LONWORKS Field Controllers and Associated Products. Notice of Plans for Long-Term Support of N2 Devices.

Discontinuation of N2 and Select LONWORKS Field Controllers and Associated Products. Notice of Plans for Long-Term Support of N2 Devices. : December 2, 2011 Announcing: From: Released To: Advanced Notice of Product of N2 and Select LONWORKS Field Controllers. Notice Of Plans For Long Term Support Of N2 Devices Metasys System Product Management

More information

N2 Binary Output/ BACnet Binary Output

N2 Binary Output/ BACnet Binary Output Object Dictionary 1 N2 Binary Output/ BACnet Binary Output Introduction Note: The Johnson Controls Binary Output object is considered a BACnet Binary Output object because it supports BACnet functionality.

More information

Using Dial-Up with the NDM

Using Dial-Up with the NDM Operator Workstation User s Manual 16-1 Chapter 16 Using Dial-Up with the NDM Introduction This section describes using the Dial-Up feature to connect to remote devices via the N2 Dialer Module (NDM).

More information

Network Control Module 300 Series

Network Control Module 300 Series Technical Bulletin Issue Date October 20, 2004 Network Control Module 300 Series Network Control Module 300 Series...3 Introduction... 3 Key Concepts... 7 NCM... 7 ISA Bus Cards... 10 Installation Considerations...

More information

DX-9100 Digital Controller, Version 2

DX-9100 Digital Controller, Version 2 Metasys European Sales Resource Manual Application Specific Controllers Section Product Bulletin Issue Date 1298 DX-9100 Digital Controller, Version 2 The DX-9100 Digital Controller is the ideal digital

More information

Variable Air Volume Modular Assembly (VMA) 1400 Series

Variable Air Volume Modular Assembly (VMA) 1400 Series Product Bulletin Issue Date March 27, 2009 Variable Air Volume Modular Assembly (VMA) 1400 Series The Variable Air Volume Modular Assembly (VMA) Series is a family of configurable digital controllers.

More information

Configuring Door and Device Templates

Configuring Door and Device Templates CHAPTER 8 This chapter describes how to create and modify door and device templates. Device templates define common settings for device types, such as Gateways, readers and locks. Door templates define

More information

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel :

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : IQ-MP Gateway Version 4.009 28. apr. 2011 Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : +45 8880 7580 www.electrocom.dk p. 2 Description The IQ-MP Gateway is a communications module, which

More information

DSX-Soft I/O Integration Software

DSX-Soft I/O Integration Software DSX Access Systems, Inc. DSX-Soft I/O Integration Software DSX now has the ability to integrate with various different external devices through serial data streams. This integration allows other systems

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

Appendix C: HVAC PRO Modules

Appendix C: HVAC PRO Modules FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix C: HVAC PRO Modules HVAC PRO Modules...3 Introduction...*3 Key Concepts...*4 ABS VALUE... 6 ADD... 6 ANALOG OUTPUT... 6 AND...

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

What a BACnet system looks like and how it can be used generally depends. By Roland Laird

What a BACnet system looks like and how it can be used generally depends. By Roland Laird This article was published in ASHRAE Journal, November 2009. Copyright 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

FieldServer Driver - Serial FS Metasys N2

FieldServer Driver - Serial FS Metasys N2 Driver Version: 1.02 Document Revision: 12 FieldServer Driver - Serial FS-8700-19 Metasys N2 Description The Metasys N2 network supports communications with a diverse range of devices. Many N2 compatible

More information

N1 Migration with the NIE Technical Bulletin

N1 Migration with the NIE Technical Bulletin MS-NIE55xx-x, MS-NxE85SW-0, MS-NIE8500-x Code No. LIT-20535 Software Release 9.0 Issued August 207 Refer to the QuickLIT website for the most up-to-date version of this document. Document Introduction...3

More information

LIFT CONTROL WITH FLOOR BUTTON FEEDBACK (V3 OR LATER)

LIFT CONTROL WITH FLOOR BUTTON FEEDBACK (V3 OR LATER) Applications Programming Guide - LIFT CONTROL WITH BUTTON FEEDBACK. Rev 4.51 Page 1 LIFT CONTROL WITH FLOOR BUTTON FEEDBACK (V3 OR LATER) Lift control logic can be used to control Floor security for a

More information

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... P.2 2. STANDARD AND OPTIONAL PARTS LIST..... P.2 3. FEATURE DEFINITIONS... P.3 4. TERMINAL DRAWING AND SPECIAL

More information

Operating Instructions Extended Cascade Controller MCO 101

Operating Instructions Extended Cascade Controller MCO 101 Operating Instructions Extended Cascade Controller MCO 101 VLT AQUA Drive FC 200 Extended Cascade Controller Option Contents Contents 1. Safety and precautions 3 Safety Instructions 3 Avoid unintended

More information

Automationdirect.com. D i r e c t L o g i c S D S N e t w o r k M a s t e r. S m a r t D i s t r i b u t e d. S y s t e m M o d u l e

Automationdirect.com. D i r e c t L o g i c S D S N e t w o r k M a s t e r. S m a r t D i s t r i b u t e d. S y s t e m M o d u l e Automationdirect.com D i r e c t L o g i c 4 0 5 S D S N e t w o r k M a s t e r S m a r t D i s t r i b u t e d S y s t e m M o d u l e F 4 - S D S Order Number: F4-SDS-M TRADEMARKS Automationdirect.com

More information

9212i INSTALLATION. Stand-Alone Keypad. Instructions

9212i INSTALLATION. Stand-Alone Keypad. Instructions INSTALLATION 9212i Stand-Alone Keypad Instructions Features: 4 Independent Outputs 4 Independent Timers All Outputs Assignable by Code On board 5 Amp Form C Relay 120 Users Remote Triggering Input Keypad

More information

Metasys Integrator GE Lighting Application

Metasys Integrator GE Lighting Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details

More information

ATS1190 Smart Card Reader Programming Manual

ATS1190 Smart Card Reader Programming Manual ATS1190 Smart Card Reader Programming Manual Version 2.0 Aritech and Tecom are Interlogix Companies 2001 Interlogix B.V.. All rights reserved. Interlogix B.V. grant the right to reprint this manual for

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

Modules Programming Guide. paradox.com

Modules Programming Guide. paradox.com Keypad Modules Annunciator Module Motion Detector Modules Zone Expansion Modules Access Control Module Voice Assisted Modules Accessory Modules Integration Module Internet Module Modules Programming Guide

More information

XR500/XR100 Command Processor Review. a) Zone expanders c) Output expanders b) All of these d) Single point detectors

XR500/XR100 Command Processor Review. a) Zone expanders c) Output expanders b) All of these d) Single point detectors Name Answer Key Company Address City, State, Zip Instructor Date Your email User Name = Password = XR500/XR100 Command Processor Review 1. may be connected to the LX-Bus. a) Zone expanders c) Output expanders

More information

Static Pressure High Limit

Static Pressure High Limit Metasys Network Technical Manual 636 Air Handlers Section Technical Bulletin Issue Date 0590 Static Pressure High Limit Static pressure high limit File Name Path Name Main Function Accessories How It Works

More information

Remote units Hands free or telephone handset options available. Master to remote and remote to master calling

Remote units Hands free or telephone handset options available. Master to remote and remote to master calling (ORB/L/RS16 LOOP WIRED) Remote units Hands free or telephone handset options available Master to remote and remote to master calling Fully monitored for open and short circuit cable failures. Remotes connected

More information

PRO2200 Professional Modular Access Control Hardware

PRO2200 Professional Modular Access Control Hardware PRO2200 Access Control Hardware As a part of the WIN-PAK software controlled hardware family the PRO2200 professional modular access control hardware is an advanced access control panel capable of providing

More information

Metasys Integrator Multistack Application

Metasys Integrator Multistack Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details

More information

NetworX Series NX-1710E Single Door Control. Installation and Startup Manual

NetworX Series NX-1710E Single Door Control. Installation and Startup Manual NetworX Series NX-1710E Single Door Control Installation and Startup Manual 2005 GE Security All rights reserved. NetworX is a trademark of the GE companies. Printed in the USA. These instructions do not

More information

Latin America, and the UK. Johnson Controls N2 Master Driver Product Update. Development Status

Latin America, and the UK. Johnson Controls N2 Master Driver Product Update. Development Status Building Technologies CPS Products Product Update Restricted! Product Line: Other BAS Product Manager: John Nicolson Distribution: USA, Canada, Asia Pacific, Latin America, and the UK 127-0502T Date: July

More information

Product Manual SZ2141

Product Manual SZ2141 Product Manual SZ11 Refrigeration Controller Communicating Controls Description The SZ11 is a microprocessor-based refrigeration controller and alarm interface designed to control three coolers or freezers

More information

Downloading Metasys Integrator 300 Series Code

Downloading Metasys Integrator 300 Series Code M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key

More information

N2 Multistate Output/ BACnet Multistate Output

N2 Multistate Output/ BACnet Multistate Output Object Dictionary 1 N2 Multistate Output/ BACnet Multistate Output Introduction Note: The Johnson Controls N2 Multistate Output object is considered a BACnet Multistate Output object because it supports

More information

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up USB-Link 2 Technical Guide USB-Link 2 Code: SS0073 Version 4.11 and up TABLE OF CONTENTS GENERAL INFORMATION... 3 USB-Link 2 Overview... 3 System Requirements... 3 QUICK GUIDE...4 USB-LINK 2 DRIVER INSTALLATION

More information

UNIVERSAL EXPANDER FOR CARD / CHIP READERS INT-R. 1. Features. 2. Installation and start-up

UNIVERSAL EXPANDER FOR CARD / CHIP READERS INT-R. 1. Features. 2. Installation and start-up UNIVERSAL EXPANDER FOR CARD / CHIP READERS INT-R int-r_en 09/11 The INT-R expander interfaces with the INTEGRA and CA-64 alarm control panels, replacing the previously offered CA-64 SR and CA-64 DR expanders.

More information

ID UM.L User Manual. LX-M10 MultiController. SW type A

ID UM.L User Manual. LX-M10 MultiController. SW type A ID UM.L82341.2012 User Manual LX- SW type A LONIX LTD www.lonix.com Teollisuuskatu 33 FI-00510 Helsinki, Finland Tel. +358 9 349 9853 Fax +358 9 349 9863 VAT 1043054-9 Trade Reg.No. 678.356 User Manual

More information

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options. TUC03 Configurable Terminal Unit Controller Product Bulletin The TUC03 Configurable Terminal Unit Controller is designed specifically to provide direct digital control of terminal unit applications with

More information

Using Loop Tuning for ASC Devices

Using Loop Tuning for ASC Devices HVAC PRO User s Guide 13-1 Chapter 13 Using Loop Tuning for ASC Devices Introduction Use Loop Tuning to monitor and/or tune Proportional plus Integral (PI) process control loops for ASC devices. This chapter

More information

FX Input/Output (I/O) Modules XM07 and XM14

FX Input/Output (I/O) Modules XM07 and XM14 Product Bulletin FX I/O Modules Issue Date July 6, 2009 FX Input/Output (I/O) Modules XM07 and XM14 The FX Input/Output (I/O) Modules provide additional physical input and output points for FX field controllers

More information

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads...

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads... HWZRU;;( Control/Communicator Installation Manual Table of Contents General Description... Ordering Information... Feature Definitions... Programming the LED Keypads... Programming the NX-E...9 Types of

More information

PRO3200 Professional Modular Access Control Hardware

PRO3200 Professional Modular Access Control Hardware PRO3200 Access Control Hardware As a part of the WIN-PAK software controlled hardware family the PRO3200 professional modular access control hardware is an advanced access control panel capable of providing

More information

AirTest Model CN9000 Series Sensor Controller

AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller THEORY OF OPERATION A basic CN9000 configuration consists of Input/Process/Display combination modules, a 3 relay

More information

Synergis Master Controller 2.2 Integration Guide for Axis Interface Modules

Synergis Master Controller 2.2 Integration Guide for Axis Interface Modules Synergis Master Controller 2.2 Integration Guide for Axis Interface Modules This guide supplements the Synergis Master Controller Configuration Guide and explains how to configure Axis interface modules

More information

NU2 UIB 842 Manual GENERAL

NU2 UIB 842 Manual GENERAL GENERAL The Universal Interface Board 842 (UIB 842) is an Access Control Power Distribution Manager (aka ACM) designed to support access control system with eight wet or powered outputs, delivering 12V

More information

XT-9100 Configuration Guide

XT-9100 Configuration Guide System 9100 Technical Manual 636.4 Configuration Guides Section Configuration Guide Issue Date 0896 XT-9100 Configuration Guide XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3

More information

DG-800 Stand-Alone Proximity Reader Instruction Manual

DG-800 Stand-Alone Proximity Reader Instruction Manual DG-800 Stand-Alone Proximity Reader Instruction Manual I. Features 1. Memory volume up to 1000+10 proximity cards/tokens and PINs with the programming time up to 0.5 seconds. 2. Access modes: a. Only Proximity

More information

VISTA-128BP/VISTA-250BP Programming Form

VISTA-128BP/VISTA-250BP Programming Form VISTA-128BP/VISTA-250BP Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section

More information

USB-Link 2 Technical Guide

USB-Link 2 Technical Guide www.wattmaster.com USB-Link 2 Technical Guide USB-Link 2 Code: SS0073 Version 4.11 and up TABLE OF CONTENTS GENERAL INFORMATION... 3 USB-Link 2 Overview... 3 System Requirements... 3 QUICK GUIDE...4 USB-LINK

More information

FXVMA Variable Air Volume (VAV) Box Controller

FXVMA Variable Air Volume (VAV) Box Controller FXVMA Product Bulletin FXVMA Issue Date November 21, 2008 FXVMA Variable Air Volume (VAV) Box Controller The FXVMA is an integrated assembly used to control Variable Air Volume (VAV) boxes. The FXVMA consists

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

S300-DIN-RDR2SA Address Mode Configuration

S300-DIN-RDR2SA Address Mode Configuration Technical Bulletin Issue Date August 17, 2010 S300-DIN-RDR2SA Address Mode Configuration The S300-DIN-RDR2SA (also referred to as ) can be addressed in two ways: legacy mode and physical address mode.

More information

Using Sideloops. Introduction

Using Sideloops. Introduction HVAC PRO User s Guide 11-1 Chapter 11 Using Sideloops Introduction The Sideloops list box, accessed by clicking the Sideloop button, provides the means to define new sideloops and view and modify existing

More information

Control Panel D9124. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6.

Control Panel D9124. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6. Control Panel Release for Version 7.00 March 2007 1.0 Introduction Firmware Update Kits (P/N: D9499-0700) are available for this product. Refer to the D9412G/D7412G Program Entry Guide (P/N: 47775D or

More information

QUICK START. Installation & Programming Guide

QUICK START. Installation & Programming Guide QUICK START Installation & Programming Guide PRECAUTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit breaker

More information

T8800 series BACnet MS/TP Networked Thermostat Controller

T8800 series BACnet MS/TP Networked Thermostat Controller T8800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin Contents Revision... 2 1. Introduction... 3 2 Configuring MS/TP... 3 2.1 Wiring the network... 3 2.2 End-of-Line termination...

More information

BCPro System Product Bulletin

BCPro System Product Bulletin CH-BCM100-0, CH-BCM200-0 Introduction The BCPro system from Johnson Controls is ideally suited to automating the environmental control and energy usage functions of conventional buildings. Not only does

More information

KarizmaPlus Intruder alarm system Operating instructions

KarizmaPlus Intruder alarm system Operating instructions KarizmaPlus Intruder alarm system Operating instructions Introduction The purpose of this user guide is to describe how to operate Karizma plus system. Some of the features described in this guide may

More information

2000 Series e/em Style Keypad Installation and Programming Manual

2000 Series e/em Style Keypad Installation and Programming Manual 2000 Series e/em Style Keypad Installation and Programming Manual Document Number: 6054022 Revision: 0 Date: 12/21/06 Table of Contents Table of Contents Section 1: Introduction... 6 1 Product Description...6

More information

Metasys Integrator Graham Application

Metasys Integrator Graham Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3

More information

Security System. Owner s Manual

Security System. Owner s Manual Security System Owner s Manual What You Need to Know Before using this manual, you should become familiar with the Security System User s Guide. The User s Guide provides step by step instructions for

More information

SL2000E. Status Output. Electronic Code Lock. Features. Input. Exit Button Input. Introduction. Door Contact Input. Functional Description.

SL2000E. Status Output. Electronic Code Lock. Features. Input. Exit Button Input. Introduction. Door Contact Input. Functional Description. SL2000E Electronic Code Lock Features Door Relay output Status transistor output Aux transistor output Door Contact input Exit Button input INSTALLER code for programming MASTER code for arming/disarming

More information

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO D ISSUED NOVEMBER 2002 VERSION 2.

IDS.  Users Guide to Keypad Functions S E C U R I T Y MANUAL NO D ISSUED NOVEMBER 2002 VERSION 2. INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-146-01D ISSUED NOVEMBER 2002 VERSION 2.17 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm

More information

Creating, Saving, and Printing Configurations

Creating, Saving, and Printing Configurations HVAC PRO User s Guide 2-1 Chapter 2 Creating, Saving, and Printing Configurations Introduction HVAC PRO software provides a Question/Answer session to set up specific configurations for the mechanical

More information

Wireless Expansion Module V2.0 OMN-RCV3. Reference & Installation Manual. Stand-Alone System

Wireless Expansion Module V2.0 OMN-RCV3. Reference & Installation Manual. Stand-Alone System Wireless Expansion Module V2.0 OMN-RCV3 Reference & Installation Manual Stand-Alone System Table of Contents Introduction...3 What s New with Version 2.0... 3 Technical Specifications... 3 System Features...

More information

Defining Inputs, Outputs, and Programmable Modules

Defining Inputs, Outputs, and Programmable Modules GX-9100 Software Configuration Tool User s Guide 4-1 Chapter 4 Defining Inputs, Outputs, and Programmable Modules Introduction The GX Tool configures the DX controller using 12 multi-purpose programmable

More information

SOFTWARE VERSION 3.10

SOFTWARE VERSION 3.10 738PEP-03 SOFTWARE VERSION 3.10 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

Operator Workstation

Operator Workstation Technical Bulletin Issue Date June 18, 2004 Operator Workstation Operator Workstation...3 Introduction... 3 Key Concepts... 5 Operator Workstation... 5 Theory of Operation... 5 Multiple Direct Connects...

More information

IRfast Comms Task Format

IRfast Comms Task Format IRfast Comms-4-1 IRfast Comms Task Format Dialer Operation - IRfast The Model 3000 and Access 4000 panels can communicate in IRfast dialer format to a suitably equipped Central Station. IRfast can be used

More information