N2 Binary Input/ BACnet Binary Input
|
|
- Loraine Cori Scott
- 6 years ago
- Views:
Transcription
1 Object Dictionary 1 N2 Binary Input/ BACnet Binary Input Introduction Note: The Johnson Controls Binary Input object is considered a BACnet Binary Input object, because it supports BACnet functionality. In addition, this object has Johnson Controls proprietary attributes. The N2 Binary Input object s attributes represent the external, visible characteristics of a binary input. As a binary input, this object can be in either an Active or Inactive state. The Polarity attribute allows for normally open relays that are Active when energized and normally closed relays that are Inactive when energized. The N2 Binary Input object integrates N2 controllers into supervisory controllers, resulting in: a consistent interface to N2 point objects for all controller types, so they appear as a homogenous set to the user interface flexibility in point mapping support for all Metasys and Facilitator controllers. Refer to Table 1 in the Controller chapter (LIT ) of the Object Dictionary. For example, this object allows you to map a fan status into a supervisory controller. See the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE) Standard for information on this object and the BACnet communication standard. May 1, 2002 Johnson Controls, Inc. Code No. LIT Software Release 5.1
2 2 N2 Binary Input/BACnet Binary Input Key Concepts BACnet Polarity Relationships The relationship between the Present Value of an object and the physical state of the object is determined by the Polarity attribute. Note: Table 1 describes this relationship as defined by BACnet standards. Johnson Controls Polarity is always Normal. Johnson Controls does not support changes to the Polarity attribute. Table 1: Polarity Relationships Present Value Polarity Physical State of the Hardware Input Inactive Normal Off or Inactive not running Active Normal On or Active running Inactive Reverse On or Active not running Active Reverse Off or Inactive running Physical State of the Monitored Device
3 Object Dictionary 3 Attributes Specific Attributes Table 2: Attribute Properties Table 2 lists the attributes specific to the N2 Binary Input object. The N2 Binary Input object also has the attributes of the Metasys Common object. Refer to Table 1 in the Metasys Common Object chapter (LIT ) for details. Attribute Name Data Type N30 M-Series N30 Default Value Options/Range Metasys Common Attributes See Table 1 in the Metasys Common Object chapter (LIT ). BACnet Required Attributes Event State Enumeration Normal Normal, Fault, Offnormal Object Identifier BACnet Object ID C Out of Service Boolean False False Polarity Enumeration W Normal Normal, Reverse See Normal Reverse Present Enumeration DNRW States Text attribute identifies Value 1 the enumeration set for this attribute. Status Flags Bit String False, False, False, False In Alarm, Fault, Overridden, Out of Service See BAC Status Flags * C - Configurable, D - Default Attribute, N - Value Not Required, R - Association to Reliability, W - Writable 1 If Out of Service is, this attribute is writable.
4 4 N2 Binary Input/BACnet Binary Input Attribute Name Data Type N30 M-Series N30 Default Value BACnet Optional Attributes Acked Bit String,, Transitions 2 Options/Range To-Offnormal, To-Fault, To-Normal See BAC Event Bits Active Text 3 String W Limit: 20 characters Alarm Value 2 Enumeration CW W Active Inactive, Active States Text attribute identifies the enumeration set for this attribute. Change of Unsigned W or greater State Count 4 Change of Date/Time W NONE_FFFF State Time 4 Device Type String CW W Null Limit: 20 characters Elapsed Active Time Unsigned Long W Null Units = seconds Event Enable 2 Bit String CW W,, To-Offnormal, To-Fault, To-Normal See BAC Event Bits Event Time Stamps 2 Array NONE_FFFF BACnetArray[3] of BACnet Time Stamp Inactive Text 3 String W Limit: 20 characters Notification Class 2 Unsigned Long CW W The BACnet Object Identifier of the Notification Class object used for routing Notify Type 2 Enumeration CW W Alarm Alarm, Event See BAC Notify Type Profile Name This BACnet optional attribute is not supported. * C - Configurable, W - Writable 2 These attributes are required if the object supports intrinsic reporting. 3 If either Inactive Text or Active Text is present, both are present. 4 If Change of State Time, Change of State Count, or Time of State Count Reset is present, all are present.
5 Object Dictionary 5 Attribute Name Data Type N30 M-Series N30 Default Value BACnet Optional Attributes Options/Range Reliability Enumeration Reliable No Fault Detected (Reliable), No Sensor, Open Loop, Shorted Loop, Unreliable Other See Reliability Enumeration Set in Time Delay 2 Unsigned Short CW W 0 Units = seconds Time of Date/Time W NONE_FFFF Active Time Reset 5 Time of State Count Reset 4 Date/Time W NONE_FFFF Intrinsic Alarming Net N2 Address Net Point Address Net Point Type Johnson Controls Proprietary Attributes Boolean C False False Byte C 0 Range: Unsigned Short C 0 Range: Enumeration C 0 See Network Point Type Offline Boolean False False Overridden Boolean R R False False States Text Enumeration CW W Off On See States Text in Trouble Boolean R R False False * C - Configurable, R - Association to Reliability, W - Writable 2 These attributes are required if the object supports intrinsic reporting. 4 If Change of State Time, Change of State Count, or Time of State Count Reset is present, all are present. 5 If either Elapsed Active Time or Time of Active Time Reset is present, both are present.
6 6 N2 Binary Input/BACnet Binary Input Attribute Definitions Table 3: Attribute Definitions Attribute Name Event State Object Identifier Out of Service Polarity Present Value Table 3 lists the definitions of the attributes specific to the N2 Binary Input object. Definition BACnet Required Attributes Indicates if an active event state associated with the object. If the object supports intrinsic reporting, this attribute indicates the event state of the object. If not, the attribute is Normal. Identifies the object with a unique numeric code. Indicates the offline/online state of the connected hardware. This attribute exists for compatibility with BACnet protocol and indicates whether the physical input that the object represents is in service. When out of service, the Present Value is not taken from the hardware. Indicates the relationship between the physical state of the input and the logical state represented by Present Value. If the Polarity attribute is Normal, then the Active state of the Present Value attribute is also the Active or On state of the physical input as long as Out of Service is False. If the Polarity attribute is Reverse, then the Active state of the Present Value attribute is in the Inactive or Off state of the physical input as long as Out of Service is False. If Out of Service is False for a constant physical input state, a change in the Polarity attribute produces a change in Present Value. If Out of Service is, the Polarity attribute has no effect on Present Value. The Johnson Controls Polarity attribute is always Normal. Indicates the current value of the binary input. Polarity determines the relationship between Present Value and the state of the input. When Out of Service is, Present Value is writable. Status Flags Contains four Boolean flags that indicate the general health of the object. Three of the four flags are associated with the values of other attributes within the same object. By reading these attributes, you can achieve a clearer picture of the object status. The four flags are: In Alarm - In Alarm flag is False (0) if the Event State property value is Normal; otherwise, the In Alarm flag is (1). Fault - Fault flag is (1) if the Reliability attribute is not reliable; otherwise, the Fault flag is False (0). Overridden - Overridden flag is Logical 1 if the Present Value is decoupled from the hardware output, because operator intervention provided a different value or local override is active. Out of Service - Out of Service flag is if the Out of Service attribute value is ; otherwise, the Out of Service flag is False.
7 Object Dictionary 7 Attribute Name Acked Transitions Active Text Alarm Value Change of State Count Change of State Time Device Type Description BACnet Optional Attributes Conveys three flags that separately indicate the receipt of acknowledgements for To-Offnormal, To-Fault, and To-Normal events. In Binary Input objects, transitions to High Limit and Low Limit Event States are considered to be Offnormal events. These flags clear upon the occurrence of the corresponding event and set under any of these conditions: upon receipt of the corresponding acknowledgement upon the occurrence of the event if the corresponding flag is not set in the Event Enable attribute (meaning event notifications are not generated for this condition and, thus, no acknowledgement is expected) upon the occurrence of the event if the corresponding flag is set in the Event Enable attribute and the corresponding flag in the Ack Required attribute of the Notification Class object implicitly referenced by the Notification Class attribute of this object is not set (meaning no acknowledgement is expected) This attribute is required if intrinsic reporting is supported by this object. Characterizes the intended effect of the Active state of Present Value from the viewpoint of the operator. The content of this string is a local matter but is intended to represent a readable description of the Active state. For example, if the physical input is a switch contact, then the Active Text attribute is assigned a value such as Fan 1 On. If either the Active Text or the Inactive Text attribute is present, both of them are present. Specifies the value that Present Value must reach before an event generates. If the object supports intrinsic reporting, this attribute is required. A To-Offnormal event generates under these conditions: The Present Value maintains the value specified by Alarm Value for a minimum period of time, specified in the Time Delay attribute. The To-Offnormal flag is enabled in the Event Enable attribute. Once equal to the Alarm Value, the Present Value must become not equal to Alarm Value before a To-Normal event is generated under these conditions: The Present Value remains not equal to the Alarm Value for a minimum period of time, specified by the Time Delay attribute. The To-Normal flag is enabled in the Event Enable attribute. Represents the number of times the Present Value attribute changes state since the Change of State Count attribute was most recently set to zero. A change of state is any event that alters Present Value. When Out of Service is False, a change to the Polarity attribute alters Present Value and is considered a change of state. When Out of Service is, changes to Polarity do not cause changes of state. If Change of State Time, Change of State Count, or Time of State Count Reset is present, all are present. Represents the date and time at which the most recent change of state occurred. A change of state is any event that alters the Present Value attribute. When Out of Service is False, a change to the Polarity attribute alters Present Value and is considered a change of state. When Out of Service is, changes to Polarity do not cause changes of state. If Change of State Time, Change of State Count, or Time Of State Count Reset is present, all are present. Contains a text description of the physical device connected to the binary input, usually describing the type of sensor. Elapsed Active Time Represents the accumulated number of seconds Present Value is Active since the Elapsed Active Time attribute was most recently set to zero. If either Elapsed Active Time or Time of Active Time Reset are present, all are present.
8 8 N2 Binary Input/BACnet Binary Input Attribute Name Event Enable Event Time Stamps Inactive Text Notification Class Description BACnet Optional Attributes Conveys three flags that separately enable and disable reporting of To-Offnormal, To-Fault, and To-Normal events. An unreliable condition generates a Fault event. This attribute is required if the object supports intrinsic reporting. Conveys the times of the last To-Offnormal, To-Fault, and To-Normal event notifications, respectively. Time or Date time stamps have FF in each octet. Sequence time stamps are 0 if no event notification of that type has been generated. If intrinsic reporting is supported by the object, this attribute is required. Characterizes the intended effect of the Inactive state of Present Value attribute from the viewpoint of the operator. The content of this string is a local matter, but it is intended to represent a readable description of the Inactive state. For example, if the physical input is connected to a switch contact, then the Inactive Text attribute is assigned a value such as Fan 1 Off. If either the Inactive Text or Active Text attribute is present, both are present. Specifies the notification class used when handling and generating event notifications for the object. This attribute implicitly refers to the Notification Class object that has a Notification Class attribute of the same value. This attribute is required if the object supports intrinsic reporting. Notify Type Conveys whether the notifications generated by the object are Events or Alarms. This attribute is required if the object supports intrinsic reporting. Reliability Indicates if the Present Value is unreliable and why. Any value defined in the Metasys Common Object (LIT ) can be written directly to this attribute. Any value written to the Reliability attribute remains until the next time the Present Value is written. Time Delay Specifies the minimum number of seconds that the Present Value must remain: outside the range defined by the High Limit and Low Limit attributes before a To-Offnormal event generates within the range defined by the High Limit and Low Limit attributes, including the Deadband attribute, before a To-Normal event generates This attribute is required for intrinsic alarming. Time of Active Time Reset Time of State Count Reset Represents the last date and time Elapsed Active Time set to a zero value. If either Elapsed Active Time or Time of Active Time Reset is present, all are present. Represents the date and time the Change of State Count attribute was most recently set to a zero value. If Change of State Time, Change of State Count, or Time of State Count Reset is present, all are present.
9 Object Dictionary 9 Attribute Name Intrinsic Alarming Description Johnson Controls Proprietary Attributes Enables the definition of the intrinsic alarm related attributes. Net N2 Address Indicates the actual controller N2 Address (1-254) as defined by switch settings on the controller. Net Point Address Indicates the network point address of the specified type (1-256). Net Point Type Offline Overridden States Text Trouble Indicates the point type in the controller. Indicates whether the object is online or offline as determined by the controller s offline condition. Shows the override state of the hardware (if supported by the hardware). Indicates the displayed strings for the Present Value. Indicates the trouble state of the hardware (if supported by the hardware). Commands The N2 Binary Input object supports the commands listed in Table 4. The order of the commands in the table reflects how the commands appear on the user interface. Table 4: Supported Commands Command Name Override Number of Parameters The value to be written to the Present Value Access Level Supervise Description Updates the Present Value at Command Priority Operator Override. Override Release Supervise Releases Command Priority Operator Override from Present Value. Enable Modify Allows distribution of Changes-of-Value and commanding. Disable Modify Prevents distribution of Changes-of-Value and commanding. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A.
N2 Binary Output/ BACnet Binary Output
Object Dictionary 1 N2 Binary Output/ BACnet Binary Output Introduction Note: The Johnson Controls Binary Output object is considered a BACnet Binary Output object because it supports BACnet functionality.
More informationN2 Analog Input/ BACnet Analog Input
Object Dictionary 1 N2 Analog Input/ BACnet Analog Input Introduction Note: The Johnson Controls N2 Analog Input object is considered a BACnet Analog Input object because it supports BACnet functionality.
More informationN2 Multistate Output/ BACnet Multistate Output
Object Dictionary 1 N2 Multistate Output/ BACnet Multistate Output Introduction Note: The Johnson Controls N2 Multistate Output object is considered a BACnet Multistate Output object because it supports
More informationMultistate Value/ BACnet Multistate Value
Object Dictionary 1 Multistate Value/ BACnet Multistate Value Introduction Note: The Johnson Controls Multistate Value object is considered a BACnet Multistate Value object because it supports BACnet functionality.
More informationTrend Log/BACnet Trend Log
Object Dictionary 1 Trend Log/BACnet Trend Log Introduction Notes: The Johnson Controls Trend Log object is considered a BACnet Trend Log object because it supports BACnet functionality. In addition, this
More informationDisplay. Introduction
Object Dictionary 1 Display Introduction The Display object configures the display of a Local Display Terminal (LDT) in an N30 supervisory controller. Use Project Builder to create a Display object for
More informationRuntime Totalization. Introduction
Object Dictionary 1 Runtime Totalization Introduction The Runtime Totalization object tracks the time that elapses while a designated input, such as a binary or multistate value, matches a specified state.
More informationObject Dictionary 1. Pager. Introduction
Object Dictionary 1 Pager Introduction The Pager object provides alarm notifications via pager to personnel at a remote location who would otherwise not be aware of the alarm coming into a workstation
More informationSchedule/BACnet Schedule
Object Dictionary 1 Schedule/BACnet Schedule Introduction Note: The Johnson Controls Schedule object is considered a BACnet Schedule object because it supports BACnet functionality. In addition, this object
More informationWorking with BACnet Group Objects
N30 Supervisory Controller User s Manual 33-1 Chapter 33 Working with BACnet Group Objects Introduction Note: Do not confuse the BACnet Group object with the Johnson Controls Group object. For information
More informationDevice Diagnostic. Introduction
Object Dictionary 1 Device Diagnostic Introduction The Device Diagnostic object supports various diagnostic functions of the device and monitors the device for an overload condition. This object allows
More informationEthernet IP Datalink. Introduction
Object Dictionary 1 Ethernet IP Datalink Introduction The Ethernet Internet Protocol (IP) Datalink object manages the Ethernet communications bus and the messages transmitted on it. This object allows
More informationWorking with Runtime Totalization Objects
N30 Supervisory Controller User s Manual 25-1 Chapter 25 Working with Runtime Totalization Objects Introduction The Runtime Totalization object tracks the number of one minute time intervals that elapse
More informationWonderware Operations Integration Supervisory BACnet/IP BACLITE Server (G-1.2 Series)
Wonderware Operations Integration Supervisory BACnet/IP BACLITE Server (G-1.2 Series) Contents Contents WONDERWARE OPERATIONS INTEGRATION - SUPERVISORY BACNET/IP BACLITE SERVER (G-1.2 SERIES)... 3 Legal
More informationDownloading Metasys Integrator 300 Series Code
M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key
More informationProposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks
BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2012 Public Review Draft Proposed Addendum bd to Standard 135-2012, BACnet - A Data Communication Protocol for Building Automation and Control (February
More informationMetasys System Extended Architecture Glossary
Technical Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture Glossary Key Concepts... 2 Metasys System Extended Architecture Component Acronyms... 2 Metasys System Extended Architecture
More informationAPPLICATION NOTE JC/85
Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software
More informationWhat a BACnet system looks like and how it can be used generally depends. By Roland Laird
This article was published in ASHRAE Journal, November 2009. Copyright 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
More informationFOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum.
[This foreword and the Overview on the following pages are not part of this Test Package. They are merely informative and do not contain requirements necessary for conformance to the Test Package.] FOREWORD
More informationIntroduction to the N30 Supervisory Controller
N30 Supervisory Controller User s Manual 2-1 Chapter 2 Introduction to the N30 Supervisory Controller Introduction This chapter describes the basic functions and operation of an N30 Supervisory Controller
More informationWT-BAC-IP Gateway Protocol Implementation Conformance Statement
WT-BAC-IP Gateway Protocol Implementation Conformance Statement Technical Bulletin WT-BAC-IP Code No. LIT-12011936 Issued June 2017 Refer to the QuickLIT Web site for the most up-to-date version of this
More informationBACnet: A Data Communication Protocol for Building Automation and Control Networks
. BACnet: A Data Communication Protocol for Building Automation and Control Networks.......... CS495 Computer Networking Research Project Submitted By: Eric Durant Submitted To: Dr. Henry Welch Date: Wednesday
More informationNS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement
NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS-BCN7004-0, NS-BCN7004-2 Code No. LIT-12011581 Issued November 9, 2011 Supersedes April 12, 2011 Refer to the QuickLIT
More informationASHRAE STANDARD. BACnet - A Data Communication Protocol for Building Automation and Control Networks
BSR/ASHRAE Addendum c to ANSI/ASHRAE Standard 135-2001 This supplement will be submitted to the American National Standards Institute Board of Standards Review (BSR) for approval. ASHRAE STANDARD BACnet
More informationBACnet Protocol Guide for 2X Series Control Panels
BACnet Protocol Guide for 2X Series Control Panels P/N 00-3243-505-0503-01 ISS 02DEC15 Copyright Trademarks and patents Manufacturer Version REV 01 Certification 2015 UTC Fire & Security. All rights reserved.
More informationAppendix C: HVAC PRO Modules
FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix C: HVAC PRO Modules HVAC PRO Modules...3 Introduction...*3 Key Concepts...*4 ABS VALUE... 6 ADD... 6 ANALOG OUTPUT... 6 AND...
More informationMetasys System Configuration Tool (SCT)
Product Bulletin Issue Date March 31, 2003 Metasys System Configuration Tool (SCT) As an integral part of the Metasys system extended architecture, the System Configuration Tool (SCT) supports the engineering,
More informationP2000 Commend Intercom Interface Option
P2000 Commend Interface Option Product Bulletin Code No. LIT-12012142 Software Release 3.14 Issued November 30, 2015 Johnson Controls offers a purchase option that enables the P2000 Security Management
More informationProposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks
BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2016 Public Review Draft Proposed Addendum bd to Standard 135-2016, BACnet - A Data Communication Protocol for Building Automation and Control Networks
More informationSite Book User s Guide
Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6
More informationSAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement
BACnet Protocol Implementation Conformance Statement D100275255-05 Content Note: This statement corresponds to the ANSI/ASHRAE 135-2012 release. Changes are taking place constantly, without prior notification.
More informationIntroduction to DX LCD Display
DX LCD Display User s Guide 2-1 Chapter 2 Introduction to DX LCD Display Introduction The DX LCD Display unit is a person/controller interface used with the DX-9100 series of controllers. The display can
More informationMetasys BACnet System Integrator (BSI) Monitoring
Metasys Connectivity Technical Manual 629.5 Metasys BACnet System Integrator Section Issue Date 73 TECHNICAL BULLETIN Metasys BACnet System Integrator (BSI) Monitoring Monitoring the BSI Communicator...2
More informationZoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement
Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement Technical Bulletin TEC2647Z-2 and TEC2647Z-2+PIR Code No. LIT-12011399 Issued March 9, 2009 Supersedes
More informationMetasys Integrator Allen-Bradley Custom Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Allen-Bradley Custom Application Introduction Page 3 Application
More informationProposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks
BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2016 Public Review Draft Proposed Addendum bd to Standard 135-2016, BACnet - A Data Communication Protocol for Building Automation and Control Networks
More informationNS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement
NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement Technical Bulletin NS-AHx7x0x-x, NS-APx7x0x-0, NS-ATx700x-x, NS-BHx7x0x-0, NS-BPx700x-0,
More informationOWNER S MANUAL. Building Gateways MD-CCM08/E (K01-BACNET)
OWNER S MANUAL Building Gateways MD-CCM08/E (K01-BACNET) Thank you very much for purchasing our air conditioner, please read this owner's manual carefully before using your air conditioner. CATALOGUE 1.
More informationMetasys System Extended Architecture Overview
Technical Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture Overview Metasys System Extended Architecture Overview...2 Introduction... 2 Key Concepts... 4 Metasys System Extended
More informationMetasys Integrator Northern Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details
More informationCENTRALINE NX BACNET UTILITIES DRIVER
CENTRALINE NX BACNET UTILITIES DRIVER User Guide Copyright 2017 Honeywell GmbH! All Rights Reserved EN2Z-1020GE51 R0217 CENTRALINE NX - BACNET UTILITIES DRIVER USER GUIDE EN2Z-1020GE51 R0217 USER GUIDE
More informationDirect Connect and Dial-Up Connection on Windows 2000 Operating Systems
Application Note Issue Date March 6, 2003 Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems...2 Introduction...
More informationMetasys Integrator GE Lighting Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details
More informationBACstac/Win v6.8. User s Guide. Document Version: 1.0. Cimetrics, Inc.
BACstac/Win v6.8 User s Guide Document Version: 1.0 Cimetrics, Inc. 141 Tremont Street, Floor 11 BOSTON, MASSACHUSETTS 02111 USA TELEPHONE: +1 (617) 350-7550 FAX: +1 (617) 350-7552 E-MAIL: products@cimetrics.com
More informationExtended Digital Controller
The Metasys Extended Digital Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1093 Extended Digital Controller (DX-9100) is the
More informationFX Server BACNET AWS Protocol Implementation Conformance Statement
FX Server BACNET AWS Protocol Implementation Conformance Statement Document Introduction. 2 Annex A- Protocol Implementation Conformance Statement (Normative) 3 Product Description. 3 BACnet Standardized
More informationBACnet MS/TP Protocol for LabVIEW. User Manual
BACnet MS/TP Protocol for LabVIEW User Manual Ovak Technologies 2015 Contents 1 Introduction... 3 1.1 Definitions and Acronyms... 3 1.2 Purpose... 3 1.3 Overview... 3 2 BACnet Background... 4 3 BACnet
More informationN30 Device. Introduction
Object Dictionary 1 Introduction Note: The Johnson Controls object functions differently than the BACnet Device object. For information on the BACnet Device object, refer to the BACnet Device chapter (LIT-694150)
More informationINTERIM TEST SPECIFICATION
BACnet TESTING LABORATORIES INTERIM TEST SPECIFICATION To Be Used with Test Package 15.1 Version 10 July 19, 2018 Approved by the BTL Working Group on July 12, 2018 Approved by the BTL Working Group Voting
More informationUsing M-Collector. Using M-Collector...2. Introduction Key Concepts... 3
Technical Bulletin Issue Date October 3, 2003 Using M-Collector Using M-Collector...2 Introduction... 2 Key Concepts... 3 M-Collector... 3 Configuration... 3 Runtime Display...4 Maximum Capacity... 6 Collection
More informationPolling the N2 Network or Zone Bus for Devices
Metasys Checkout Tool User s Guide 3-1 Chapter 3 Polling the N2 Network or Zone Bus for Devices Introduction The first step in the checkout process is using the Metasys Checkout Tool to find and display
More informationMetasys Integrator Graham Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3
More informationFX Input/Output (I/O) Modules XM07 and XM14
Product Bulletin FX I/O Modules Issue Date July 6, 2009 FX Input/Output (I/O) Modules XM07 and XM14 The FX Input/Output (I/O) Modules provide additional physical input and output points for FX field controllers
More informationWorking with Objects and the M-View Screen
Project Builder User s Guide 6-1 Chapter 6 Working with Objects and the M-View Screen Introduction The Project Builder uses a variety of objects to configure controllers and perform tasks. This chapter
More informationCENTRALINE NX BACNET UTILITIES DRIVER
CENTRALINE NX BACNET UTILITIES DRIVER User Guide Copyright 2017 Honeywell GmbH All Rights Reserved EN2Z-1020GE51 R0917 CENTRALINE NX - BACNET UTILITIES DRIVER USER GUIDE EN2Z-1020GE51 R0917 2 USER GUIDE
More informationMetasys Integrator Caterpillar Application
Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations
More informationGuidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks
M-Graphics User s Manual G-1 Appendix G Guidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks Introduction This chapter discusses guidelines and recommendations for
More informationAPPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4
FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in
More informationFX Tools Express Software Package
Product Bulletin FX Tools Express Issue Date October 31, 2005 FX Tools Express Software Package FX Tools Express is a Windows based software package for configuring, downloading and commissioning of predefined
More informationCommunication Module BAC-06 for DGC-06 System
Page 1 Mar. 2017 The module is designed for transmitting values from gas measuring systems or gas sensors to BMS or PLC systems that can be connected via Ethernet to a BACnet/IP-network. APPLICATION The
More informationNB-VAV Family Protocol Implementation Conformance Statement (PICS)
Vendor Name: American Auto-Matrix Product Name: NB-VAV Family Product Model Number: NB-VAVta, NB-VAVtf, NB-VAVra, NB-VAVrf, NB-VAVr, NB-VAVta-IAQ, NB-VAVtf-IAQ Firmware Revision: 6.03 BACnet Protocol Revision:
More informationLab and Central Plant Controller
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is
More informationM-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems
Product Bulletin Issue Date July 6, 2006 Supersedes June 30, 2004 M-Tool M-Tool transforms the way you create control strategies by providing a suite of tools with an intuitive and efficient work environment.
More informationHoneywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)
July 2017 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 13 st September 2017
More informationCommunication Module BAC-06 for DGC6 System
Communication Module BAC-06 for DGC6 System Communication Module BAC-06 for DGC6 System The module is designed for transmitting values from gas measuring systems or gas sensors to BMS or PLC systems that
More informationNB-ASC Family Protocol Implementation Conformance Statement (PICS)
Vendor Name: American Auto-Matrix Product Name: NB-ASC Family Product l Number: NB-ASC, NB-ASCe, NB-Rooftop, NB-Heat Pump, NB-Fancoil Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description:
More informationICC. BACnet MS/TP Server Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.
INDUSTRIAL CONTROL COMMUNICATIONS, INC. BACnet MS/TP Server Driver Manual August 17, 2017 2017 Industrial Control Communications, Inc. TABLE OF CONTENTS 1 BACnet MS/TP Server... 2 1.1 Overview... 2 1.2
More informationDefining Points. Introduction
M-Series Workstation with Companion/Facilitator Manual 9-1 Chapter 9 Defining Points Introduction This chapter explains how to define software points. Points are software representations of input and output
More informationBACnet Controller Integration with NAE/NCE/ODS Technical Bulletin
BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin Code No. LIT-1201531 Software Release 9.0 Issued August 2017 Refer to the QuickLIT website for the most up-to-date version of this document.
More informationMetasys Integrator United Power Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator United Power Application lntroduction Page 3 Application Details
More informationPolyGard Communication Module BacNET-05 for DGC-05 System
PolyGard Communication Module BacNET-05 for DGC-05 System DESCRIPTION This Module is used to transport values from Gas measuring systems or gas Sensors to BMS or PLC systems, which are able to be connected
More informationNB-GPC Family Protocol Implementation Conformance Statement (PICS)
Vendor Name: American Auto-Matrix Product Name: NB-GPC Family Product Model Number: NB-GPC1, NB-GPC2, NB-GPC3, NB-GPC4 Firmware Revision: 2.00 BACnet Protocol Revision: 4 Product Description: NB-GPC controllers
More informationMatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile:
Vendor Name: American Auto Matrix Product Name: BACnet Building Controller Product Model Number: x BBC y (x indicating target model; y feature) Firmware Revision: Target using BBC module v1.1.56 or later
More informationFacility Explorer for Validated Environments
Facility Explorer for Validated Environments User s Guide 1 Facility Explorer for Validated Environments Introduction Facility Explorer for Validated Environments is an information-based software application
More informationWorking with Demand Limiting/Load Rolling (DLLR) Objects
N30 Supervisory Controller User s Manual 19-1 Chapter 19 Working with Demand Limiting/Load Rolling (DLLR) Objects Introduction The Demand Limiting/Load Rolling (DLLR) object selectively sheds loads to
More informationM-Password Application Actions
Issue Date 11/01/01 TECHNICAL BULLETIN M-Password s M-Password s...3 Introduction... 3 Key Concepts... 4 M-Password s...4 Analog Profile s...5 AWX Container (M-Alarm View) s...5 AWXInd32 (M-Alarm Indicator)
More informationMetasys Integrator Multistack Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details
More informationSuitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.
TUC03 Configurable Terminal Unit Controller Product Bulletin The TUC03 Configurable Terminal Unit Controller is designed specifically to provide direct digital control of terminal unit applications with
More informationGLAS Smart Thermostat
GLAS Smart Thermostat Product Bulletin SIO-00000, SIO-0000 Code No. LIT-098 Issued August 08 Refer to the QuickLIT website for the most up-to-date version of this document. The GLAS Smart Thermostat is
More informationProposed Addendum aq to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks
BSR/ASHRAE Addendum aq to ANSI/ASHRAE Standard 135-2012 Public Review Draft Proposed Addendum aq to Standard 135-2012, BACnet - A Data Communication Protocol for Building Automation Fourth Public Review
More informationBACnet Errata ANSI/ASHRAE STANDARD A Data Communication Protocol for Building Automation and Control Networks.
BACnet Errata ANSI/ASHRAE STANDARD 135-2012 A Data Communication Protocol for Building Automation and Control Networks July 2, 2014 This document lists all known errata to ANSI/ASHRAE 135-2012 as of the
More informationWhat's New for Metasys Release 8.0 Code No. LIT Software Release 8.0 Issued July 2016
Code No. LIT-12012163 Software Release 8.0 Issued July 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Introduction...2 Summary of Changes...2 Features and s...2 Metasys
More informationMetasys System Extended Architecture
Product Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture The architecture of the Metasys building automation and facilities management system has been extended to be fully compatible
More informationMetasys Web Access System Overview
Technical Bulletin Issue Date February 18, 2003 Metasys Web Access System Overview Metasys Web Access System Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Hardware and Software
More informationField selectable application type and room module series, via dip-switches on controller
TUC03 Plus Configurable Terminal Unit Controller Product bulletin The TUC03 Plus configurable Terminal Unit Controller is specifically designed to provide an improved BACnet integration. It allows the
More informationBACnet MS/TP Interface User s Guide
PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak
More informationP216 Series Condenser Fan Speed Controller
P216 Series Condenser Fan Speed Controller Installation Instructions P216xxx-x Part No. 24-85895-18, Rev. D Issued 27 August 2015 Applications Refer to the QuickLIT website for the most up-to-date version
More informationBACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000
Date: 9/18/2008 Vendor Name: Automated Logic Corporation Product Name: LGR Product Model Number: LGR25, LGR250, LGR1000 Applications Software Version: ExecB ME-LGR-melgr Firmware Revision: 2.18 BACnet
More informationWT-4000 Wireless System
WT-4000 Wireless System Best Practices WT-BAC-IP Code No. LIT-12012551 Issued July 2017 Background and Wireless Network Components Refer to the QuickLIT website for the most up-to-date version of this
More informationCF Terminal User s Guide
Table of Contents CF Terminal User s Guide Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 Chapter Organization...1-2 Questions or Comments...1-2 Chapter 2 Getting Started...2-1
More informationDirect Connect and Dial-Up on Windows 98
N30 Supervisory Controller System Communications Manual 689.3 Application Notes Section Issue Date 0101 APPLICATION NOTE Direct Connect and Dial-Up on Windows 98 Direct Connect and Dial-Up on Windows 98...3
More informationMetasys Web Access. Provides full access to M-Alarm for monitoring and acknowledging alarm messages and generating alarm reports
Product Bulletin Issue Date March 17, 2003 Metasys Web Access Comprehensive information access at anytime and from any location: that is how the Metasys Web Access (MWA) software assists you in managing
More informationBCPro System Product Bulletin
CH-BCM100-0, CH-BCM200-0 Introduction The BCPro system from Johnson Controls is ideally suited to automating the environmental control and energy usage functions of conventional buildings. Not only does
More informationN30 Supervisory Controller Quick Start
Issue Date June 30, 2004 TECHNICAL BULLETIN N30 Supervisory Controller Quick Start N30 Supervisory Controller Quick Start...2 Introduction... 2 Key Concepts... 3 Using This Document... 3 Related Information...
More informationCOMPASS1.5 WORKSTATION DEALER GUIDE
COMPASS1.5 WORKSTATION DEALER GUIDE Before you begin COMPASS 1.5 DEALER GUIDE ABOUT COMPASS About Compass Compass is an operator workstation software package for BACnet-compliant systems. Compass, which
More informationBACnet Protocol Implementation Conformance Statement OEMPrtl Pro
Date: 12/13/2011 Vendor Name: OEMCtrl Product Name: Product Model Number: Applications Software Version: Firmware Revision: 4.02 BACnet Protocol Revision: 9 Product Description: The is
More informationSpreadsheet Applications
Metasys Network Technical Manual 3 App. Notes: Network Communications Technical Bulletin Issue Date 9 Spreadsheet Applications lntroduction Page 3 Metasys and Spreadsheet Applications 5 Locating and Opening.DBF
More informationBACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)
Date: 10/05/2016 Vendor Name: OEMCtrl Product Name: Unitary Protocol Converter Product Model Number: UPC Applications Software Version: Firmware Revision: 6.00a BACnet Protocol
More informationNB-V3Tb Protocol Implementation Conformance Statement (PICS)
NB-V3Tb Vendor Name: American Auto-Matrix Product Name: NB-V3Tb Product Model Number: NB-V3Tb Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description: NB-V3Tb is a full-featured VVT system
More information