Optical Time Domain Reflectrometry The Smart Way

Size: px
Start display at page:

Download "Optical Time Domain Reflectrometry The Smart Way"

Transcription

1 Optical Time Domain Reflectrometry The Smart Way Christian Schillab Product Manager Media Test Fluke Networks Europe Member British Standards Institute Working Group TCT 7/-/1 & CENELEC TC215 WG1 PTH und PTT

2 Optical Time Domain Recflectrometry The Smart Way The discussion on whether OTDRs are the right tools to test new installations for compliance is fueled by common practices which try to balance simplicity with achieving relevant test results. In This presentation, we describe new methods and procedures which deliver highly accurate and repeatable results and, at the same time, significantly reduce the overall testing time.

3 Agenda OTDRs have a point of view Normative requirements Comparison of methods Using a loop to accelerate the test Smart support for loop testing Cost comparisons for the different methods

4 Fiber Optic Test Methods Standard Tier-1 Methods TIA-568-C Tier-2 ISO AMD.1 / ISO/IEC BASIC Test Regime LSPM: Light Source & Power Meter EXTENDED Test Regime OTDR: Optical Time Domain Reflectometer The two methods are complimentary! OTDR based method does not replace the LSPM based solution Both methods have advantages and limitations

5 From The Archive. BICSI 2012 The next 6 slides are from a 2012 presentation

6 OTDR s Have Multiple Points of View db db 0.33 db 0.32 db db db

7 Causes for Directivity Potential causes for different results depending on the direction 1. Two fibers are different Diameter Back Scatter Index NA. Numerical Aperture Major difference in IR Index of Refraction 2. Damaged fiber end faces Glass is chipped off

8 Bi Directional Averaging The averaging can be performed manually or by an advanced results management software

9 Can We Quantify Directivity? No standard defines how to calculate it but it is simple ISO/IEC defines no maximum allowed directivity

10 How to Quantify Directivity Delta of measured loss from End-1 and End-2 divided by Δ (-0.23 and 0.41) / 2 = 0.64 / 2 = 0.3dB Δ (0.44 and ) / 2 = 0.64 / 2 = 0.3dB In this example: Prior to averaging the result will be over stated by 0.30dB in one and understated by 0.3dB in the other directions NOTE: The overall loss is not suffering from directivity Only if launch and receive fiber exhibit no directivity if tested without a link

11 Common Practices Voice of the Customer... In EMEA a majority of text in SOWs (Standards Of Work) specify a bi-directional test but not the use of a tail fiber If use of a tail fiber is specified a match with the launch fiber is typically not mentioned as a requirement

12 Bi-Directional OTDR Tests Without a Tail Fiber 0.15 db 0.28 db 0.20 db Question: Can we trust the results? Is the total loss = 0.48dB? Answer: A bi-directional test without the use of a tail fiber test is the best way. to PASS non compliant or to FAIL compliant links

13 we re-measure the link the correct way A. We retest the link using a launch fiber plus a tail fiber Can we trust the results? Is the total loss = 0.48dB? B. We use Bi-Directional averaging to get the ultimate information and we observe.. End 1 End 2 1. The result should have been a FAIL 2. Overall loss was wrong by 43% We observe 3. Connector loss was wrong by 62% and 87%

14 First Embedded Last Overall Loss Technicians Required Testing Time Accuracy of Methods Compared Launch Fiber Tail Fiber Connections Launch n/ 1 x Launch & Tail Uni- Directional a / 2 x Launch n/ 1 2x Bi- a Excellent / Hi Relevane Directional Launch & Tail 2 2x Poor / Hi Uncertainty n/a not available

15 Alternative Methode using a Loop Launch A Loopback Tail B 1. Tests A and B fiber simultaneously 2. In a second step from the other direction 3. The individual segments need to be identified in the trace

16 Alternative Method Using a Loop A B Launc h Loopback Tail A B Nn,mn,m

17 Pros & Cons of Loop Testing A B PROs Total time for trace acquisition time is halved For Launch & Tail Fiber the number of mating's is halved Use of multiple Loop Fibers allow a single technician to walk less often to the other end CONs Each trace needs to be saved two times after identifying Fiber A and then Fiber B Extensive cursor setting and saving results multiple times is a common source of error Fiber A from End1 Fiber B from End1 Fiber A from End2 Fiber B from End2

18 Concept of Smart Loop Testing The OTDR automatically identifies Fiber A and B for both both test From End 1 From End 2 The OTDR saves 4 test results in one pass The OTDR automatically learns the correct lengths of Launch / Loop / Tail Fibers

19 Test Results Navigation Tap to toggle between fibers A and B Tap to toggle between Ends 1 and 2 The loopback fiber is always End 2

20 Pros & Cons of Smart Loop Testing A B PROs Total time for trace acquisition time is halved For Launch & Tail Fiber the number of mating's is halved Use of multiple Loop Fibers allow a single technician to walk less often to the other end CONs Each trace needs to be saved two times after identifying Fiber A and then Fiber B Extensive cursor setting and saving results multiple times is a common source of error Fiber A from End1 Fiber B from End1 Fiber A from End2 Fiber B from End2

21 Smart Loop Testing / 2 Technicians Comparing testing for 6 links (12 fibers) The time saving is a minimum of 50%

22 Smart Loop Testing / 1 Technician 3 remote loop are used to reduce the number of walks to the other end The time saving is typically > 33%

23 Cost Saving Calculation Find copy at danahertm.box.com/slcal

24 Cost Saving Calculation / Example 1 Smart Loop versus no loop 2 Technicians Cost Saving 50% Find copy at danahertm.box.com/slcal

25 Cost Saving Calculation / Example 2 Smart Loop versus Dumb loop 1 Technician 6 loop fibers are used Cost Saving 39% Find copy at danahertm.box.com/slcal

26 Conclusions

27 Thank You! for Your Attention I would be happy to answer an further question christian.schillab@flukenetworks.com

Skew and Strain measurements using the Optical Backscatter Reflectometer to Support TIA FOTP Application Note

Skew and Strain measurements using the Optical Backscatter Reflectometer to Support TIA FOTP Application Note Skew and Strain measurements using the Optical Backscatter Reflectometer to Support TIA FOTP 455038 Application Note 1 Introduction Luna s Optical Backscatter Reflectometer Series 4400 and PR, (herein

More information

White Paper: Installing Data Networks Using LinkWare Live SaaS

White Paper: Installing Data Networks Using LinkWare Live SaaS White Paper: Installing Data Networks Using LinkWare Live SaaS White Paper: Installing Data Networks Using LinkWare Live SaaS Software as a Service (SaaS) continues to grow in popularity across a wide

More information

Common Mistakes Made in Certification Specifications and Testing. Jim Davis Regional Marketing Engineer Fluke Networks

Common Mistakes Made in Certification Specifications and Testing. Jim Davis Regional Marketing Engineer Fluke Networks Common Mistakes Made in Certification Specifications and Testing Jim Davis Regional Marketing Engineer Fluke Networks Common Mistake #1 Failing to specify a Permanent Link test #1 Permanent Link or Channel?

More information

Advances in Fiber Tier 2 Enterprise & Data Center Testing

Advances in Fiber Tier 2 Enterprise & Data Center Testing Advances in Fiber Tier 2 Enterprise & Data Center Testing As the volume of fibers deployed into enterprise increases significantly, fiber cabling advances like multi-fiber (MPO) connectors and interfaces

More information

FlexScan FS200 OTDR With SmartAuto, FleXpress and LinkMap Quick Reference Guide

FlexScan FS200 OTDR With SmartAuto, FleXpress and LinkMap Quick Reference Guide Test & Inspection FlexScan FS200 OTDR With SmartAuto, FleXpress and LinkMap Quick Reference Guide www.aflglobal.com or (800) 321-5298, (603) 528-7780 Controls, Display, Interfaces 1 2 4 8 1. Power button

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

OFL250 OTDR. Quick Reference Guide. or +1 (800) , +1 (603)

OFL250 OTDR. Quick Reference Guide.  or +1 (800) , +1 (603) OFL250 OTDR Quick Reference Guide www.aflglobal.com or +1 (800) 321-5298, +1 (603) 528-7780 Functional Keys Functional Keys KEY NAME KEY FUNCTION Power Press and hold (approx. 2 sec.) to turn the OFL250

More information

SUMITOMO SPECIFICATION. FutureFLEX. Multimode 62.5 µm Core Optical Fiber (OM1) Gigabit Grade

SUMITOMO SPECIFICATION. FutureFLEX. Multimode 62.5 µm Core Optical Fiber (OM1) Gigabit Grade SUMITOMO SPECIFICATION FutureFLEX Multimode 62.5 µm Core Optical Fiber (OM1) Gigabit Grade SUMITOMO ELECTRIC LIGHTWAVE CORP. 201 South Rogers Lane, Suite 100, Raleigh, NC 27610 (919) 541-8100 or 1-800-358-7378

More information

FlexScan OTDR With SmartAuto and LinkMap

FlexScan OTDR With SmartAuto and LinkMap Test & Inspection FlexScan OTDR With SmartAuto and LinkMap Quick Reference Guide www.aflglobal.com or (800) 321-5298, (603) 528-7780 Controls, Display, Interfaces 1 2 4 8 1. Power button 2. Power jack

More information

TESTING HIGH SPEED FIBER LINKS

TESTING HIGH SPEED FIBER LINKS TESTING HIGH SPEED FIBER LINKS Rodney Casteel, RCDD, DCDC, NTS, OSP - CommScope, Chair TIA FOTC Tyler Vander Ploeg, RCDD - Viavi Solutions Jamie Humphreys - EXFO Rob Gilberti - AFL Jim Davis - Fluke Networks

More information

User Manual Fiber Certification Testing

User Manual Fiber Certification Testing User Manual Fiber Certification Testing User Manual Fiber Certification, WireXpert v7.1.0, build #276 WireXpert4500_Fiber_IT_EN_U_201511_102S Copyrights 2015 Softing Inc. http://itnetworks.softing.com/

More information

Introduction to Key Principles of Telecommunications Cabling

Introduction to Key Principles of Telecommunications Cabling Introduction to Key Principles of Telecommunications Cabling Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of

More information

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices

More information

Multimode Measurement Cords Recommendations for Multimode Link Field Certification

Multimode Measurement Cords Recommendations for Multimode Link Field Certification Multimode Measurement Cords Recommendations for Multimode Link Field Certification FiberXpert OTDR 1 BACKGROUND Different Multimode Cable Categories Multimode cables are at current categorised into 4 different

More information

Optical Certifier I. Tier-1 Fibre Certifier for Multimode and Single-mode Fibre Cabling. Proof of Performance

Optical Certifier I. Tier-1 Fibre Certifier for Multimode and Single-mode Fibre Cabling. Proof of Performance Optical Certifier I Tier-1 Fibre Certifier for Multimode and Single-mode Fibre Cabling Proof of Performance Optical Certifier I Tier-1 Fibre Certifier for Multimode and Single-mode fibre cabling The Optical

More information

Advanced Fiber Optic Connector Installation

Advanced Fiber Optic Connector Installation Advanced Fiber Optic Connector Installation QUICK SUMMARY Length: 48 hours, 52 hours with Fiber Optic Association CFOT certification Hands-on Activities: activities, 70-75 % Text/Field Reference: Professional

More information

White Paper: Choosing the RIght OTDR for your Datacenter

White Paper: Choosing the RIght OTDR for your Datacenter White Paper: Choosing the RIght OTDR for your Datacenter To ensure that fiber in datacenters is reliable, network professionals need a more accurate, easier, and faster methodology for assessing the integrity

More information

CS260 Contractor Series OTDR

CS260 Contractor Series OTDR CS260 Contractor Series OTDR Quick Reference Guide www.aflglobal.com or (800) 321-5298, (603) 528-7780 Functional Keys KEY NAME KEY FUNCTION Power Press and hold (~1 second) to turn the CS260 on or off.

More information

Data Center: First-Time Right Acceptance Testing Steps for Certification and Troubleshooting - Intra & Inter-connect. Nicholas Gagnon EXFO

Data Center: First-Time Right Acceptance Testing Steps for Certification and Troubleshooting - Intra & Inter-connect. Nicholas Gagnon EXFO Data Center: First-Time Right Acceptance Testing Steps for Certification and Troubleshooting - Intra & Inter-connect Nicholas Gagnon EXFO Data Center today Source: EXFO Global Data Center Traffic by Destination

More information

How new testing standards affect you Singapore, Nov 2009

How new testing standards affect you Singapore, Nov 2009 How new testing standards affect you Singapore, Nov 2009 Adrian Young Sr. Customer Support Engineer In this presentation, we will cover How ANSI/TIA-568-C.2 has consolidated all the different test plugs

More information

Sumitomo Fiber Specification SE-5** PureBand Single-Mode Fiber. Zero Water Peak (ZWP) Attenuation Optical Fiber, ITU G.

Sumitomo Fiber Specification SE-5** PureBand Single-Mode Fiber. Zero Water Peak (ZWP) Attenuation Optical Fiber, ITU G. Sumitomo Fiber Specification SE-5** PureBand Single-Mode Fiber Zero Water Peak (ZWP) Attenuation Optical Fiber, ITU G.652D TIA Type IVa Issued: March 2009 78 Alexander Drive, Research Triangle Park, NC

More information

Presenter: Roland Schlehuber. Fluke Networks

Presenter: Roland Schlehuber. Fluke Networks Fiber optic theory and testing Presenter: Roland Schlehuber NE Distribution Sales Manager Fluke Networks Agenda Trends and Performance Requirements in Fiber optics Fiber Inspection and Cleaning Tier 1

More information

Datasheet: Fiber OneShot PRO Singlemode Fiber Distance and Fault Locator; Fiber QuickMap Multimode Fiber Distance and Fault Locator

Datasheet: Fiber OneShot PRO Singlemode Fiber Distance and Fault Locator; Fiber QuickMap Multimode Fiber Distance and Fault Locator Datasheet: Fiber OneShot PRO Singlemode Fiber Distance and Fault Locator; Fiber QuickMap Multimode Fiber Distance and Fault Locator Datasheet: Fiber OneShot PRO Singlemode Fiber Distance and Fault Locator;

More information

Why you need Fiber and Copper Certification. Presenter: Wayne Allen Role: Technical Manager Fluke Networks

Why you need Fiber and Copper Certification. Presenter: Wayne Allen Role: Technical Manager Fluke Networks Why you need Fiber and Copper Certification Presenter: Wayne Allen Role: Technical Manager Fluke Networks What is driving IT today? IT is Changing The IT industry is full of Buzz words! Cloud, SDN, SAN,

More information

Psiber Data WireXpert P R O F E S S I O N A L N E T W O R K T E S T I N G & P R O T O C O L A N A L Y S I S

Psiber Data WireXpert P R O F E S S I O N A L N E T W O R K T E S T I N G & P R O T O C O L A N A L Y S I S Psiber Data WireXpert Agenda Psiber Data WireXpert Introduction Company Presentation Why Cable Certification? Universal Structured Cabling or The Network Standards The WireXpert Page 2 Psiber Data Company

More information

The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures. Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress

The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures. Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress 36 Years of Experience CABLExpress is a manufacturer of

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

WIREXPERT FIBER LOSS TEST KIT TECHNICAL REFERENCE MANUAL. WireXpert Fiber Loss Test Kit Technical Reference Manual

WIREXPERT FIBER LOSS TEST KIT TECHNICAL REFERENCE MANUAL. WireXpert Fiber Loss Test Kit Technical Reference Manual WireXpert Fiber Loss Test Kit Technical Reference Manual i Table of Contents Introduction... 1 Package Contents... 1 Single-mode Certification Kit... 1 Multi-mode Certification Kit... 1 Features and Benefits...

More information

Optical Fiber Test and Troubleshooting Solutions

Optical Fiber Test and Troubleshooting Solutions Optical Fiber Test and Troubleshooting Solutions I look for rugged, long-lasting tools that can stand up to the wear and tear of being used daily Installation Contractor Sacramento, CA During my day, I

More information

CERTIFICATION PLUS SM

CERTIFICATION PLUS SM CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation

More information

HUBER+SUHNER DCCT Training

HUBER+SUHNER DCCT Training HUBER+SUHNER DCCT Training DCCT training The following topics are covered throughout the 2 course: Fiber optic fundamentals This is an optional section of the training which covers the basics about fiber

More information

PARKING. JDSU Solutions for Enterprise Structured Cabling

PARKING. JDSU Solutions for Enterprise Structured Cabling COMMUNICATIONS TEST AND MEASUREMENT SOLUTIONS JDSU Solutions for Enterprise Structured Cabling JDSU offers a complete range of communications test and measurement solutions to address the needs of cabling

More information

Innovative Design, Proven Performance

Innovative Design, Proven Performance White Paper LaserWave FLEX Bend-Optimized Fiber: Innovative Design, Proven Performance Multimode fiber using a graded-index waveguide has been deployed in communications networks for more than 30 years.

More information

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India Enterprise Network Test Strategies for Network Availability and Performance A Sitaramaiah Director Fluke Networks India 1 Why is Enterprise Network Testing becoming increasingly important? IT is increasingly

More information

Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS)

Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS) Application Note Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS) MT9090A/MU909011A Network Master Optical Fault Locator (OTDR) By Stephen Colangelo

More information

Nicotra Sistemi RTU 2012 REMOTE TEST UNIT KEY FEATURES

Nicotra Sistemi RTU 2012 REMOTE TEST UNIT KEY FEATURES RTU 2012 REMOTE TEST UNIT KEY FEATURES 1 * Developed for long haul and FTTx point-to-point network * Small size (3U) * Low power consumption * Improved OTDR performances * Improved fast fiber scan mode

More information

Complimentary Reference Material

Complimentary Reference Material Complimentary Reference Material This PDF has been made available as a complimentary service for you to assist in evaluating this model for your testing requirements. TMG offers a wide range of test equipment

More information

Siemon Interconnect Solutions

Siemon Interconnect Solutions Siemon Interconnect Solutions W W W. S I E M O N. C O M / S I S technology at work for you DESIGN ENGINEERING Our Product Development Engineers and R&D Lab combine state of the art tools and capabilities

More information

Appendix 1 to the R&Mfreenet Warranty Program

Appendix 1 to the R&Mfreenet Warranty Program Appendix 1 to the R&Mfreenet Warranty Program 1 R&M Certification Process The R&Mfreenet certification process is three pillars: a) Adherence to applicable standards, both for products and installations;

More information

Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only

Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only 1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda

More information

PEEK. Coated Fiber Evaluation. TEST REPORT Test Date: March 8-9, 2016 PREPARED BY: Matt Davis Lead Research Engineer LUNA Blacksburg, VA

PEEK. Coated Fiber Evaluation. TEST REPORT Test Date: March 8-9, 2016 PREPARED BY: Matt Davis Lead Research Engineer LUNA Blacksburg, VA PEEK TEST REPORT Test Date: March 8-9, 2016 Coated Fiber Evaluation PREPARED BY: Matt Davis Lead Research Engineer LUNA Blacksburg, VA Jason Fant Global Market Manager, Fiber Optics Zeus Industrial Products,

More information

Field Testing Installed Optical Fiber Cabling. Field Testing Installed Optical Fiber Cabling JUNE 2010 WHITE PAPER JUNE 2010

Field Testing Installed Optical Fiber Cabling. Field Testing Installed Optical Fiber Cabling JUNE 2010 WHITE PAPER JUNE 2010 JUNE 2010 Field Testing Installed Optical Fiber Cabling 1 BY: JAY PAUL MYERS, RCDD TECHNICAL TRAINING SPECIALIST LEGRAND ORTRONICS BY: JASON TARN PRODUCT MARKETING MANAGER FLUKE NETWORKS 2 This joint white

More information

OTDR Testing Quick Reference Guide

OTDR Testing Quick Reference Guide Keys OTDR Testing Quick Reference Guide Key Name Key Function Power Press and hold (approx. 1 sec.) to turn the OTDR on or off or VFL Menu L and R Tab keys Arrow keys Enter Back Test Save ON 2 Hz - Press

More information

2DXX Optical Modules with Diagnostic Analog Output

2DXX Optical Modules with Diagnostic Analog Output 2DXX Optical Modules with Diagnostic Analog Output The diagnostic analog output is used to indicate the strength of an incoming light signal to the receiver (RX) input on the optical module. The sensitivity

More information

JDSU REFERENCE GUIDE TO FIBER OPTIC TESTING PDF

JDSU REFERENCE GUIDE TO FIBER OPTIC TESTING PDF JDSU REFERENCE GUIDE TO FIBER OPTIC TESTING PDF ==> Download: JDSU REFERENCE GUIDE TO FIBER OPTIC TESTING PDF JDSU REFERENCE GUIDE TO FIBER OPTIC TESTING PDF - Are you searching for Jdsu Reference Guide

More information

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents

More information

Test Report: PEEK Coated Optical Fiber Evaluation

Test Report: PEEK Coated Optical Fiber Evaluation prepared by: Matt Davis Applications Engineer LUNA Blacksburg, VA and Jason Fant Global Market Mgr, Fiber Optics Zeus Industrial Products, Inc. Orangeburg, SC Edited by: Kevin J. Bigham, PhD. Technical

More information

Certification Testing Quick Reference Guide

Certification Testing Quick Reference Guide Keys Certification Testing Quick Reference Guide Key Name Key Function Power Press and hold (approx. 1 sec.) to turn the OTDR on or off VFL Menu ON 2Hz - Press and hold (approx. 2 sec.) LED will flash

More information

History of Standards

History of Standards History of Standards From 10Mbps to 100Gbps Ethernet 12 th May 2014 Gautier Humbert, RCDD Business Development Manager Legrand East and Central Europe Agenda 1- Current standards and their structures

More information

Release Notes. WireXpert / export. Version 7.3 Build 854

Release Notes. WireXpert / export. Version 7.3 Build 854 Release Notes WireXpert / export Version 7.3 Build 854 June 1, 2017 Version: 1.0 Page 1 of 6 1 New or enhanced features: WireXpert / Certifier Copper cable database updated Link / Berk-Tek / Leviton /Giga

More information

SCT-MMA / SCT-SMA Fiber Optic Adapters

SCT-MMA / SCT-SMA Fiber Optic Adapters SCT-MMA / SCT-SMA Fiber Optic Adapters USER MANUAL ENGLISH i SAFETY WARNINGS Read First: Safety and Operational Information The international electrical symbols used on the instrument or in this manual

More information

Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"

Industry Standards in ICT Enabled Projects Reading and Applying the Fine Print Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland

More information

Sumitomo Fiber Specification SE-7** Non-Zero Dispersion Shifted Single-Mode Fiber. PureMetro SM Optical Fiber, TIA Type Ivd, ITU-T G.

Sumitomo Fiber Specification SE-7** Non-Zero Dispersion Shifted Single-Mode Fiber. PureMetro SM Optical Fiber, TIA Type Ivd, ITU-T G. Sumitomo Fiber Specification SE-7** Non-Zero Dispersion Shifted Single-Mode Fiber PureMetro SM Optical Fiber, TIA Type Ivd, ITU-T G.655 Issued: January 2006 CONTENTS 78 Alexander Drive, Research Triangle

More information

Highlights: ISO/IEC SC25/WG3 Meeting Madrid: 27 Feb - 01 Mar Customer Premises Cabling -

Highlights: ISO/IEC SC25/WG3 Meeting Madrid: 27 Feb - 01 Mar Customer Premises Cabling - 1 ISO/IEC SC25/WG3 Meeting Madrid: 27 Feb - 01 Mar 2012 - Customer Premises Cabling - Highlights: 1. ISO/IEC 14763-2 Planning/Installation published 2. ISO/IEC 14763-3 OF Testing Ed.2 CD April 2012 3.

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton Manufacturing Co. 417 Stone Drive

More information

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant Is Cable Balancing Efficient i Enough for EMI Mitigation in Data Centers? Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant What are You going to Learn? What are the potential sources

More information

Fiber USER MANUAL.

Fiber USER MANUAL. Fiber USER MANUAL http://itnetworks.softing.com ENGLISH TABLE OF CONTENTS 1 Introduction... 4 1.1 About product... 4 1.2 Safety precautions... 4 1.3 Intended use... 5 1.4 About this document... 5 1.5 Before

More information

Performance specification for the Fluke DSP Fluke Corporation

Performance specification for the Fluke DSP Fluke Corporation Performance specification for the Fluke Fluke Corporation 1. Summary This document contains the performance specifications in terms of requirements per draft TIA and IEC specifications. Since requirements

More information

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic

More information

Clean or not clean? itnetworks.softing.com

Clean or not clean? itnetworks.softing.com Clean or not Figure 1: Microscopic images of fiber end s in various conditions OK Dirt/ Particles Oil/Finger print Scratches/ Grooves Cleaning agent residues Adhesive residues Singlemode Multimode What

More information

e-ready Building Next Generation IT infrastructures ϕ The Cabling Partnership Mike Gilmore Managing Director, e-ready Building The Cabling Partnership

e-ready Building Next Generation IT infrastructures ϕ The Cabling Partnership Mike Gilmore Managing Director, e-ready Building The Cabling Partnership eready Building THE ONESTOP SHOP Telecommunications equipment and telecommunications cabling Specification for installation, operation and maintenance THE ONESTOPSHOP FOR INSTALLATION Q.A. Mike Gilmore

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek-etlsemko.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton 2222 222nd St. SE Bothell,

More information

Trends in Testing Data Center Infrastructure. Ed Gastle VIAVI Solutions

Trends in Testing Data Center Infrastructure. Ed Gastle VIAVI Solutions Trends in Testing Data Center Infrastructure Ed Gastle VIAVI Solutions Agenda INTRODUCTION Modern Data Center Architecture Historically Enterprise has been a 3 tier topology Core, Aggregation, Access Cloud

More information

FTTE Revisited for New Technologies

FTTE Revisited for New Technologies FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern

More information

FTBx-1750/OHS-1700 KEY FEATURES RELATED PRODUCTS AND ACCESSORIES SPEC SHEET HIGH-PERFORMANCE POWER METER AND OPTICAL HEAD SERIES

FTBx-1750/OHS-1700 KEY FEATURES RELATED PRODUCTS AND ACCESSORIES SPEC SHEET HIGH-PERFORMANCE POWER METER AND OPTICAL HEAD SERIES HIGH-PERFORMANCE POWER METER AND OPTICAL HEAD SERIES Fast, accurate, flexible power measurement in a platform-based solution. SPEC SHEET KEY FEATURES One, two or four detectors on a single module Ultra-High-Power

More information

The Mini-OTDR Modes. Connecting a Fiber. Cleaning Connectors

The Mini-OTDR Modes. Connecting a Fiber. Cleaning Connectors The Mini-OTDR Modes OTDR Mode: make, view and analyze traces Fiber Break Locator: simplified trace setting to locate fiber breaks quickly. Source Mode: enable the stabilized laser source for loss. If a

More information

European Data Centre Infrastructure Standards EN series. Rob Cardigan, Senior Product Manager Nexans Cabling Solutions

European Data Centre Infrastructure Standards EN series. Rob Cardigan, Senior Product Manager Nexans Cabling Solutions European Data Centre Infrastructure Standards EN 50600 series Rob Cardigan, Senior Product Manager Nexans Cabling Solutions Scope Presentation Nexans explains the recent standardization process for data

More information

TO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled:

TO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled: ADDENDUM NO. 2 TO THE BID PACKAGE FOR February 6, 2006 This addendum is being issued to modify portions of the Bid Package for the Project entitled: Receipt of this Addendum should be acknowledged by inserting

More information

Development of Cleanliness Specification for Expanded Beam Connectors Project. End of Project Brief. July 20, 2016

Development of Cleanliness Specification for Expanded Beam Connectors Project. End of Project Brief. July 20, 2016 Development of Cleanliness Specification for Expanded Beam Connectors Project End of Project Brief July 20, 2016 Project Members Tatiana Berdinskikh Tom Coughlin Michael Kadar-Kallen, Mike Gurreri Christine

More information

White paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com

White paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com The dramatic growth of high-bandwidth wireless access points and other IP-enabled devices, such as surveillance cameras and building automation equipment has resulted in the practice of installing direct

More information

DATA CENTER SYMPOSIUM

DATA CENTER SYMPOSIUM DATA CENTER SYMPOSIUM Dynamic Changes in Data Center Optic Transmissions & The Impact to Structured Fiber Cabling Rick Dallmann CABLExpress Years of Experience CABLExpress is a manufacturer of custom built

More information

MT-7610 Optical Time Domain Reflectometer USER'S GUIDE

MT-7610 Optical Time Domain Reflectometer USER'S GUIDE MT-7610 Optical Time Domain Reflectometer USER'S GUIDE English Test Equipment Depot - 800.517.8431-99 Washington Street - Melrose, MA 02176 TestEquipmentDepot.com AVOD EYE OR SKIN EXPOSURE TO DIRECT OR

More information

THE NEW OPTICAL FIBRE CATEGORIES What do they promise?

THE NEW OPTICAL FIBRE CATEGORIES What do they promise? THE NEW OPTICAL FIBRE CATEGORIES What do they promise? prepared and delivered by ϕ Breakfast Seminar 13th March 2001 Fibreoptic Industry Association PO Box MT65 LEEDS LS17 8YD UK Tel: +44 (0) 113 232 3721

More information

Bend, Bandwidth or Both: enterprise networks. Ravi Yekula

Bend, Bandwidth or Both: enterprise networks. Ravi Yekula Bend, Bandwidth or Both: Making the right choice for enterprise networks Ravi Yekula Corning Optical Fiber Agenda Multimode fiber remains the most cost-effective choice for enterprise networks Multimode

More information

TK1-V2 OLTS (TIER 1) AND OTDR (TIER 2) FIBER CERTIFICATION KIT FOR THE FTB-1 PLATFORM

TK1-V2 OLTS (TIER 1) AND OTDR (TIER 2) FIBER CERTIFICATION KIT FOR THE FTB-1 PLATFORM OLTS (TIER 1) AND OTDR (TIER 2) FIBER CERTIFICATION KIT FOR THE FTB-1 PLATFORM KEY FEATURES Lightweight and portable solution designed for field engineers or cell technicians who install, troubleshoot

More information

Qualification of the optical links for the data readout in LHCb

Qualification of the optical links for the data readout in LHCb Qualification of the optical links for the data readout in LHCb LHCB Technical Note Issue: Draft Revision: 1 Reference: LHCB xxxxx Created: 28 th Jan 2005 Last modified: 11 th Dec 1997 Prepared By: V.

More information

Qualified Partner Programme QPP. Fiber Optic Gigabit Ethernet Theory Felice Guarna

Qualified Partner Programme QPP. Fiber Optic Gigabit Ethernet Theory Felice Guarna Qualified Partner Programme QPP Fiber Optic Gigabit Ethernet Theory Felice Guarna Applications The protocols used in LAN mostly base on Ethernet technology. In 1998 the IEEE 802.3z was passed (Gigabit

More information

7.3 Refractive Index Profiling of Fibers and Fusion Splices

7.3 Refractive Index Profiling of Fibers and Fusion Splices 7.3 Refractive Index Profiling of Fibers and Fusion Splices 199 necessary for measuring the reflectance of optical fiber fusion splices. Fig. 7.10 schematically depicts an OFDR containing a Michelson interferometer

More information

Machine Layout Basics

Machine Layout Basics QUICK REFERENCE GUIDE KI7347C Series Optical Two Way Loss Test Set with ORL Machine Layout Basics Save Test Data Power Hard Key Functions Wavelength Tested Light Source ORL Meter Power Meter Auto Test

More information

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com. FiberTEK III

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com. FiberTEK III Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com FiberTEK III User Manual Page 1 COPYRIGHT NOTICE The information contained in this document is the property

More information

Autofocus Video Inspection Probe G0382A. Product Introduction

Autofocus Video Inspection Probe G0382A. Product Introduction focus Video Inspection Probe G0382A Product Introduction What is Video Inspection Probe? Scratches and stains to optic fiber ferrule endfaces are often said to have a negative impact on transmission quality.

More information

IO Ninja Hardware Manual

IO Ninja Hardware Manual IO Ninja Hardware Manual Copyright Tibbo Technology 2000-2018 I IO Ninja Hardware Manual (NHM) Table of Contents Introduction 1 Serial Tap 1 Block Diagram... 4 Using the Serial... Tap 4 Wedge RS232 monitoring...

More information

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3)

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3) Pretium EDGE 133 Pretium EDGE Solutions Trunk Cable, 50 Pretium EDGE Solutions trunk cables utilize the MTP Connector, a 12 -fiber push/pull optical connector with a footprint similar to the SC simplex

More information

Optical Loss Budgets

Optical Loss Budgets CHAPTER 4 The optical loss budget is an important aspect in designing networks with the Cisco ONS 15540. The optical loss budget is the ultimate limiting factor in distances between nodes in a topology.

More information

FlexScan OTDR With SmartAuto and LinkMap

FlexScan OTDR With SmartAuto and LinkMap FlexScan OTDR With SmartAuto and LinkMap User s Guide Test & Inspection Contents Safety Information...5 Hardware Overview...7 Controls, Display, Interfaces...7 Front Panel Buttons and Indicators...9 Battery

More information

LEAD Fiber Optics PRODUCT CATALOGUE

LEAD Fiber Optics PRODUCT CATALOGUE LEAD Fiber Optics PRODUCT CATALOGUE BARE FIBER ADAPTER TEL:+886-2-8672-2371 FAX:+886-2-8672-3275 Web:http://www.twfiberoptic.com Bare Fiber Adapter Bare fiber adapters are used as the medium to link the

More information

Fiber Optic Technician - Outside Plant (FOT-OSP) Course Description. Certification(s) Students Will Learn. Splicing Overview & Testing Outside Plant

Fiber Optic Technician - Outside Plant (FOT-OSP) Course Description. Certification(s) Students Will Learn. Splicing Overview & Testing Outside Plant Fiber Optic Technician - Outside Plant (FOT-OSP) Splicing Overview & Testing Outside Plant Course Description This 4-day Hands-On course is the Fiber Optic Technician OSP course. This course provides more

More information

M200 Handheld OTDR User s Guide

M200 Handheld OTDR User s Guide WWW.EXFIBER.COM M200 Handheld OTDR User s Guide Test & Inspection Limited Warranty One Year Limited Warranty All Noyes products are warranted against defective material and workmanship for a period of

More information

Application Note. Data Center Standards and Layouts

Application Note. Data Center Standards and Layouts Application Note Data Center Standards and Layouts 1. Data Center Standards In earlier times, a room in which one or more servers, a telephone system and active network components were located was often

More information

Are Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk?

Are Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk? Are Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk? Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress 36 Years of Experience CABLExpress

More information

Roambi Pulse Quick Start Guide V

Roambi Pulse Quick Start Guide V Roambi Pulse Quick Start Guide V4.4.0.0 Table of Contents ROAMBI PULSE OVERVIEW 3 FEATURES 3 DATA SOURCES 4 CREATING A ROAMBI PULSE 5 STEP 1: CHOOSE PULSE FROM THE CAROUSEL 5 STEP 2: IMPORT YOUR DATA 7

More information

LEEDS FORENSIC SYSTEMS Your Forensic Imaging Source

LEEDS FORENSIC SYSTEMS Your Forensic Imaging Source LEEDS FORENSIC SYSTEMS Your Forensic Imaging Source All Product Brochure LCF3 Discovery LCT LCF2 Discovery-Z Trace-Z Leeds Forensic Systems, Inc. is one of the world s premier innovators, manufacturers,

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: Leviton Manufacturing Co. 417 Stone Drive St. Charles,

More information

Embedded Polymer Waveguide to Optical Fiber Interconnects Creating the Optimal Link

Embedded Polymer Waveguide to Optical Fiber Interconnects Creating the Optimal Link Embedded Polymer Waveguide to Optical Fiber Interconnects Creating the Optimal Link Dr. Blanca Ruiz, Marika Immonen, Dr. Andres Ferrer, Christian Gsell, Dr. Peter Cristea CTI Corporate Technology & Innovation

More information

Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks

Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Agenda New ISO/IEC 11801 Standard New Fibre standards and encoding methods Higher speeds,

More information

Fiber Optic Communication Systems. Unit-03: Properties of Light. https://sites.google.com/a/faculty.muet.edu.pk/abdullatif

Fiber Optic Communication Systems. Unit-03: Properties of Light. https://sites.google.com/a/faculty.muet.edu.pk/abdullatif Unit-03: Properties of Light https://sites.google.com/a/faculty.muet.edu.pk/abdullatif Department of Telecommunication, MUET UET Jamshoro 1 Refractive index Department of Telecommunication, MUET UET Jamshoro

More information

Copper Certification Testing Best Practices Pocket Guide

Copper Certification Testing Best Practices Pocket Guide Copper Certification Testing Best Practices Pocket Guide Cabling certification is a best practice of world class installers because it shows the true quality of the installation and reduces the risk of

More information

Copper Cabling Standards

Copper Cabling Standards Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals

More information

Pin-in-Paste Process Webcast

Pin-in-Paste Process Webcast Pin-in-Paste Process Webcast March 22, 2001 Presented By: Surface Mount Technology Laboratory David Vicari Process Research Engineer Wilhelm Prinz von Hessen Manager, Customer Process Support Jim Adriance

More information

Signature Core Fiber Optic Cabling System

Signature Core Fiber Optic Cabling System White Paper June 2012 WP-17 Signature Core Fiber Optic Cabling System Multimode Fiber: Understanding Chromatic Dispersion Introduction The performance and reliability of networks within the Data Center

More information