1 With Great Power Over Ethernet Comes Great Responsibility PRESENTED BY Bob Crain
2 Pathways and Spaces Planning for a PoE Environment IEC 2018 Bob Crain
3 With Great Power Over Ethernet Comes Great Responsibility Agenda Data Cabling Current TIA Standards NEC 2017 PoE Data cabling Ampacity Fill and Bundling Standards Evolution
4 Requirements are Changing! Systems are Integrating!
5 TIA-569-Open Pathways (Current Standard) ülimit Conduit Use Use of conduit The use of conduit as a horizontal raceway system for telecommunications cabling is considered when: it is required by code, outlet locations are permanent, device densities are low, special mechanical protection is required, or flexibility is not required. In-floor conduit systems are especially inflexible as they are usually buried in concrete. üj Hook 5 Spacing Max 9.8 Non-continuous support Non-continuous supports shall be located at intervals not to exceed 1.5 m (5 ft).
6 TIA-569-Open Pathways (Current Standard) üaccess Requirements and Power and Data Separation Trays may be divided with a barrier to allow for physical separation between power and conductive telecommunications cables. Power and telecommunications cables shall be installed per electrical code. A minimum of 200 mm (8 in) access headroom shall be provided and maintained above a cable tray system or cable runway. The recommended access headroom above cable trays and runways is 300 mm (12 in). Care shall be taken to ensure that other building components (e.g., air conditioning ducts) do not restrict access. üreference NEMA VE2 NOTE NEMA VE2 contains useful information regarding additional cable tray support and installation. ücable Tray Fill 25-50% Cable trays Cable trays shall be planned for an initial maximum calculated fill of 25% (see example 1). The maximum fill of any cable tray shall be 50%. The maximum fill depth of any cable tray shall be 150 mm (6 in). NOTE A calculated fill of 50% for four-pair and similar diameter cables will physically fill the entire tray due to spaces between cables, and random placement.
7 TIA-569-Open Pathways (Current Stds for Data only) 50% Fill is Full! ünec or TIA - 50% Max Fill Let s Do the Math Example: ü2 x 6 Cablofil Wire Mesh = 12 sq in of area üper NEC 50% rule 12/2 = 6 sq in space for cables ücat 5e Cable =.21 in (DIA) = 3.14(.21)2/4= 0.4 sq in ü6 sq in /.04 sq in = 150 cables So what does 150 cat 5e cables look like in a 2x6 wire mesh tray? Cable bundling is very common for data cables No size rules for cable bundles for data cables
8 Current Power is limited Watts and Amps TIA focused on Watts NEC focused on Amps POE standards 1993 IEEE 802.3af - 13W (350 ma) 2009 IEEE 802.3at W (600mA) 2017 NEC Greater than 60W requires limitations
9 NEC 2017 PoE (Section 725) Cable Bundles ücable Type Separation ü Class 2 or 3 circuits require barrier from Power, Class 1, Lighting ü No strapping cables to conduit ücable Ampacity and Bundle Sizes ü Limited to capacity of cable gage & connectors ü No derate for Loose Fill
10 NEC 2017 PoE (Section 725) vs 392 (Data non PoE Cat 6 cables) üspace requirement Class 2 or 3 circuits ü DATA ONLY (.22 dia -24 AWG) ü 2x24 space 636 cables ü Limited by physical space available ü POE ONLY (.22 dia -24 AWG) ü 2x24 space 636 cables ü Limited Ampacity based on bundle size ü ½ POE + ½ Data (.22 dia -24 AWG) ü 2x24 space 636 cables loose fill only
11 Why the focus on amps? Safety Cable overheating Items to address % of PoE deployment How many cables are PoE? How many are data only? Cable Management Techniques Loose fill vs cable bundle conflict Loose Fill = Sloppy = cables run cooler Cable Bundles = Neat and Workman like = derating
12 Why the focus on amps? Safety Cable overheating Items to address Cable type matters Twist Insulation thickness = larger diameter cooler Construction type (Foil wrapped = best at heat dissipation) Pathway system matters Closed systems vs Open systems No suprize open systems run cooler Steel conduit most heat rise (not a thermal sink)
13 Why the focus on amps? Safety Connectors RJ45 Current Limitations Redesigns and testing Alternate Connector designs Disconnection under load
14 Why the focus on amps? Safety End User Concerns Faceplate designations PoE connection Non-PoE connection Patch cord specification Marking Voltage drop Power at device Power at source
15 New Addendum to TIA-569 (Pathway & Spaces Standard) Additional considerations for supporting remote power over balanced twisted pair cabling ütia TR-42.3 subcommittee is working hard on a 2 nd addendum to the 569 Pathway and Spaces standard ü40% fill max üfocus on Bundled and Un-Bundled state (24 cable bundle max) ütable for guidance on heat dissipation depending on cable quantity and bundles. ürj45 rated for 2.0 amp (new connection designs in review to allow greater ampacity) üno Disconnecting under load
16 ALL About Power Watts vs Amps TIA focused on Watts NEC focused on Amps POE standards Evolution 1993 IEEE 802.3af - 13W (350 ma) 2009 IEEE 802.3at W (600mA) 20xx IEEE 802.3bt - 9 Power classifications
17 ALL About Power
18 Future Power over balanced twisted pair cabling üpoe will continue to grow üpoe is a dramatic technology shift üpoe Connectivity is critical (Life safety not just performance) üadditional coordination of NEC/TIA required ücable installation techniques will need to be reviewed & revised ümust plan! Can no longer pull cables until its full üpower cable rules will apply to data cables! ü Data cable voltage drop calculations (length * twist rate factor) ü Data cable ampacity calculations ü Data cable connection fill calculations ü Data cable splice/connection heating tests ü Must mark/label/inform users ü Must mark/label/inform users
19 19 Questions? For more Information: Visit us in Booth #
20
Implementation considerations for cabling supporting remote powering
Implementation considerations for cabling supporting remote powering Table of contents Background...3 Advantages of remote powering using communications cabling...4 CommScope implementation considerations
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Increasing usage of Power over Ethernet (PoE) represents
More informationThe Power of PoE: Converging Power and Control of Intelligent Devices
The Power of PoE: Converging Power and Control of Intelligent Devices Amir Sekhavat Global Director, Copper Product Management and Enterprise Market Development Superior Essex Objectives What drives the
More informationThe Real Impact of High Power PoE on Your IP Network
The Real Impact of High Power PoE on Your IP Network Jason Finnegan, Product Manager Copper Solutions, Legrand Cindy Montstream, Director of Technical Support & Training, Legrand Amir Sekhavat, Global
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationCabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring
Cabling to support 802.11ac and beyond Nate Herring Sr. Product Manager Hubbell Premise Wiring IP Traffic Continues to Increase Globally, IP traffic will grow 3-fold from 2014 to 2019, a compound annual
More informationIEEE P802.3bt Guidelines For Field Deployment
IEEE P802.3bt Guidelines For Field Deployment Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Background Power delivery over BASE-T PHYS with specified operation over TIA/ISO cabling 802.3af,
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Power over Ethernet (PoE) represents one of the most meaningful
More informationThe Real Impact of High-Power PoE on Your IP Network
The Real Impact of High-Power PoE on Your IP Network Jason Finnegan, Product Manager Copper Solutions - Legrand Cindy Montstream, RCDD, NTS - Director of Technical Support & Training - Legrand Brian Ensign,
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationNew Standardized Cabling Options for NBASE-T Devices
New Standardized Cabling Options for NBASE-T Devices Webinar Speakers Tom Baum Sr. Product Manager, Panduit tmba@panduit.com Peter Jones Chairman, NBASE-T Alliance Distinguished Engineer, Cisco chairman@nbaset.org
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationTelecommunication Cabling Standards to address IoT and power delivery. 5 October
Telecommunication Cabling Standards to address IoT and power delivery 1 5 October 2018 www.vti.net.au In a nut shell Out for comment NOW AS/NZS 11801.1 (General requirements) AS 11801.2 (Office) AS 11801.3
More informationR&Mfreenet Advanced Cat 6 A Unshielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions
More information[0.057] 5.8 [0.23]
Product Specification 7 June 13 Rev B SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used
More informationR&Mfreenet Advanced Cat 6A Shielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6A Connection Module The R&Mfreenet Cat 6A shielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions and
More informationor go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS
SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS GO SMALL or go home STANDARDS PAGE 17 WBMMF on the fast track NETWORK MANAGEMENT PAGE 31 Quicken
More information[0.057] 5.8 [0.23]
Product Specification 7 March 13 Rev A1 SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationLaying the groundwork for a new level of Power over Ethernet
White paper Laying the groundwork for a new level of Power over Ethernet April 2017 Contents Laying the groundwork for a new level of Power over Ethernet 3 PoE basics 3 PoE standards development 4 Four-pair
More informationCable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.
Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications Broadband High-Speed LAN Voice Robert Y. Faber Jr., RCDD/NTS Minimum Port Recommendations TIA/EIA-568-B.1 2 outlets
More informationCopper Riser And Intrabuilding Cabling
Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable
More informationLaying the groundwork for a new level of Power over Ethernet
Laying the groundwork for a new level of Power over Ethernet October 2018 Table of contents Laying the groundwork for a new level of Power over Ethernet...3 PoE basics...4 PoE standards development...5
More informationThe Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling in Modern Building Design
The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling in Modern Building Design Agenda Introduction What is it & What is coming? The Impact Why is it important? Recommendations & Summary
More informationBonding and grounding NETCONNECT copper cabling systems
White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding
More informationOffice of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO
Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note
More informationConsiderations for the Design & Field Testing of an Optimized High-Power PoE Cabling System
WHITE PAPER Considerations for the Design & Field Testing of an Optimized High-Power PoE Cabling System Why Comprehensive Testing for DCR Unbalance is Critical As Power-over-Ethernet (PoE) becomes the
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationBest Practices to realise the full potential of Remote Powering. Paul Cave Technical Manager Excel Networking
Best Practices to realise the full potential of Remote Powering Paul Cave Technical Manager Excel Networking Benefits of Power over Ethernet (PoE) Remote Powering No requirement for local power outlets
More informationv2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.
Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations
More informationHigh Power PoE. Updating Power over Ethernet Standards for More Power, Speed, and Efficiency
P E R F O R M B E YO N D E X P E C TAT I O N S A B E R K -T E K W H I T E P A P E R High Power PoE Updating Power over Ethernet Standards for More Power, Speed, and Efficiency W W W. B E R K T E K.COM
More informationCopper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only
1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda
More informationMosaic TM LCS2 Cat. 6 RJ 45 socket
870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics....1 2. Presentation...2 3. Installation...2 4.
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationLight over PoE. Emanuele Colombo Country Manager R&M Italia October 2017
Light over PoE Emanuele Colombo Country Manager R&M Italia October 2017 Content Introduction Development of PoE Zone cabling according EN50173-6 Digital Ceiling Solution R&M proposals for Digital Ceiling
More informationStandards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee
Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic
More informationStandards Update. by Paul Kish NORDX/CDT
Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline
More informationTIA/EIA 568A Sub-system HORIZONTAL CABLING
TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,
More informationTarget Interface / Construction Compliance Inspection Checklist
TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationKnow Your Limitations Power over Ethernet (PoE) Loredana Coscotin, Product Manager Belden Peter Kauwenberg, Product Manager Belden
Know Your Limitations Power over Ethernet (PoE) Loredana Coscotin, Product Manager Belden Peter Kauwenberg, Product Manager Belden Power over Ethernet Power over Ethernet or PoE technology describes a
More informationAMP-TWIST* Modular Jack, UTP, Category 6A
Product Specification 5 July 13 Rev A AMP-TWIST* Modular Jack, UTP, Category 6A 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for TE Connectivity*, 6A UTP AMP-
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationMosaic TM LCS2 Cat. 6 RJ 45 socket
870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics...1 2. Presentation...2 3. Installation....2 4.
More informationCabling a Data Center to TIA-942 Standard
Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center
More informationLAN Standards, News & Trends Update 2017 June 15, 2017
LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE
More informationThe Internet of Everything (IoE)
The Internet of Everything (IoE) Agenda The Internet of Everything is coming, In 2018, How do I Prepare? Why Cable Matters Conclusions Here s what I know about the future: it happens as a result of what
More informationInstruction Manual HPH-8
Specifications HPH-8 Trigger cable 120-volt, Nema 1-15 Main Power 50-amps @ 240-volt AC Power receptacles (4) Nema 5-15 or 6-15 Maximum HID wattage 8000 watts (on 240-volt) 4800 watts (on 120-volt) Maximum
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationSpring Test 17 due 06/14/2013
Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered
More informationPower over Ethernet: A Consumer Centric Development Perspective
POWER OVER ETHERNET Power over Ethernet: A Consumer Centric Development Perspective Written by: Roy Kusuma, Engineer, Communications Products Matt Gentile, Product Manager, Communications Products TABLE
More informationConnected & Efficient Building. Field Application Engineer - Kutlugün Sürmeli CommScope
Connected & Efficient Building Field Application Engineer - Kutlugün Sürmeli CommScope Low Voltage Over Twisted Pair Revolution Desktop Voice and Data WiFi Access Control Security Cameras Occupancy Sensors
More information4Cu-LSA Connection technology
4Cu-LSA technology LSA- technology: Patch panels, Telephone Patch Panels, RJ45, Tera, Office-Patch Panels, Data outlets, surface mounting, flush mount, underfloor, 60 Table of Contents Office DC FTTX Patch
More information3M ID 3000 System. ID 3128 block. Disconnection module. ID 3100 block Wire guide housing
3M ID 3000 System ID 3128 block Disconnection module ID 3100 block Wire guide housing 71 Disconnection element 72 The ID 3000 connection system is the latest generation of insulation displacement connector
More informationLeveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions
Leveraging the Structured Cabling System for Security Applications Mark Dearing, RCDD Leviton Network Solutions Trends - Cable Category Mix Source: Leviton projections based on market growth rates Over
More informationIEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and
IEC 60309 H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and amperage to prevent interchangeability of voltages Watertight
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationIEEE 802.3at PoE Plus Operating Efficiency:
IEEE 802.3at PoE Plus Operating Efficiency: How to Keep a Hot Application Running Cool The development of the pending PoE Plus standards brings to light a significant new challenge in delivering power
More informationWhite Paper. Cabling and Connectivity for Power over Ethernet. Kirk Krahn Senior Product Manager for Leviton Network Solutions
White Paper Cabling and Connectivity for Power over Ethernet Kirk Krahn Senior Product Manager for Leviton Network Solutions Table of Contents Introduction 3 Standards 3 Equipment for Delivering PoE 5
More informationPanduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA
Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Figure 1: Industrial Distribution Frame (IDF) Equipment Elevation
More informationPoE Lighting: Unleashing IoT and Opportunity in the ICT Industry
PoE Lighting: Unleashing IoT and Opportunity in the ICT Industry Bob Allan, MBA, LEED GA Global Business Development Manager Intelligent Buildings and Strategic Alliances @ballan32 There s a Revolution
More informationAMP-TWIST* 6S Series SL Jack
Product Specification 108-93003 16/Mar/2011 Rev E AMP-TWIST* 6S Series SL Jack 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, AMP- TWIST*
More informationMD3. Microstepping Motor Driver Page 1 of 7. Description. Software. Mechanical Drawing. Features
Page 1 of 7 The MD3 is a stepper motor driver with an integrated motion controller that is capable of driving size 14 to 42 stepper motors from 2 to 256 microsteps per step. Peak motor currents are selectable
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationSYSTIMAX GigaSPEED Xpress Solution Design Guidelines
Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO/IEC 18010 First edition 2002-05 Information technology Pathways and spaces for customer premises cabling ISO/IEC 2002 All rights reserved. Unless otherwise specified, no part
More informationWiring Best Practices
Form Number F-2825 Issue Date Jan 3, 2018 Revision Date Jun 5, 2018 Wiring Best Practices Selecting, planning, and routing wires. Waterous Company 125 Hardman Avenue South South Saint Paul, MN 55075 (651)
More informationINTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES
INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside
More informationINJ-24A Series Quick Installation Guide
INJ-24A Series Quick Installation Guide Moxa High-Power PoE+ Injector Edition 4.1, August 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777
More informationSpring Test 5 due 4/26/2013
Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationTHE CTB08D LIGHT CONTOLLER
THE CTB08D LIGHT CONTOLLER The CTB08D is a one of the components in the Hobbyist line of Light- O-Rama products. The CTB08D must be used in conjunction with the Light-O-Rama software package. This controller
More informationIndustrial Field-Bus Standards Update (Physical Layer)
Industrial Field-Bus Standards Update (Physical Layer) Bob Lounsbury Principal Engineer Rockwell Presented at the ODVA 2014 Industry Conference & 16 th Annual Meeting March 11-13, 2014 Phoenix, Arizona,
More informationLFWLP350 SERIES 350 Watt Open Frame Power Supply Measures: 5.00 x 3.00 x 1.00
Features 5 x 3 x 1 Inches Form factor 350 Watts with Forced Air Cooling & 200 Watts Convection Cooling Efficiencies upto 94% -40 to 70 degree operating temperature* 12V / 0.5A Fan Output, Thermal Shut-Down
More informationLos Angeles Community College District Design Standards
LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure
More informationProduct Specification. CLOUDSPLITTER Connector System
Product Specification 01NOV2013 Rev A CLOUDSPLITTER Connector System 1. SCOPE 1.1. Content This specification covers the performance, tests and quality requirements for the CLOUDSPLITTER connector system.
More informationMosaic TM LCS2 Cat. 6A STP RJ 45 socket
870 LIMOGES Cedex Telephone: + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Page 765 73 794 76 1. General characteristics...1 2. Presentation...1 3. Installation....1 4. Technical characteristics....2
More informationElectrical Integration of PV Systems. Ridha Hamidi, Ph.D.
Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various
More informationEthernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement
Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement Overview SPE is poised to enable a new class of low power devices that
More informationComputer Network Design Guide Existing Systems 1 / 6
COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should
More informationCertification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More informationClient Utility Package
Client Utility Package Attached are the order forms for the services we offer at the DCU Center in Worcester, Massachusetts. Things to know > The electrical charge is a one-time charge that will cover
More informationWireless LANs - PoE s Killer App
Wireless LANs - PoE s Killer App Wireless LANs - PoE s Killer App The Internet of Things New LAN on the Rise Synergy in the LAN Power is the New Signal Wireless Means Better Wire Readying for the Future
More informationSynJet PAR25 LED Cooler with Heat Sink
PRODUCT SynJet PAR25 LED Cooler with Heat Sink Assembly Guide Version 1.0 June 2009 Version History Document Name: SynJet PAR25 LED Cooler with Heat Sink Assembly Guide Document Number: MKTG-DOC-00048.
More informationInstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 InstaPATCH Cu Solution Specification 2 Harness Assembly Design 3
More informationWith the publication. Make the right connection: Bonding a shielded system. installation
Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being
More informationPowered Fiber Cable System
CommScope Powered Fiber Cable System Template Rev. 3/2/2016 CommScope provides this information as a courtesy to its customers and potential customers. Customers should review the information to ensure
More informationThis Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.
This Datasheet for the IC697CHS790 Rack, 9 Slots, Rear Mount. http://www.cimtecautomation.com/parts/p-14771-ic697chs790.aspx Provides the wiring diagrams and installation guidelines for this GE Series
More informationDigital Lighting Systems, Inc.
, Inc. PD402-DMX Four Channel Dimmer and Switch Packs 4 x 2.5 Amps @ 6VDC to 24 VDC DMX52 compatible DMX52 4 x 2.5 Amps Dimmer Pack C UL US LISTED Digital Lighting Systems, Inc. USER'S MANUAL User's Manual
More informationHigh Power PoE Updating Power over Ethernet Standards for More Power, Speed and Efficiency. White Paper January 2017
High Power PoE Updating Power over Ethernet Standards for More Power, Speed and Efficiency White Paper January 2017 High Power PoE For the last ten years, Power over Ethernet (PoE) and PoE+ have provided
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea,
More informationIndustrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide
Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-HP Installation Guide DOC.141201-1- (C) 2014 KTI Networks Inc. All rights reserved.
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationCOMPUTER NETWORK WIRING SYSTEMS FOR PLCs
SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network
More informationNTS-protect. Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/
NTS-protect Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/ SAFETY INSTRUCTIONS! This are the important Safety Instructions
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationSaving Critical Space. Cable Management Solutions
Saving Critical Space Cable Management Solutions Cable Management Innovation that Saves Space where You Need It Most Enterprise telecom rooms have traditionally housed telecommunications equipment, cable
More information