SPECIAL SPECIFICATION 6027 Lane Control Signal Equipment

Size: px
Start display at page:

Download "SPECIAL SPECIFICATION 6027 Lane Control Signal Equipment"

Transcription

1 2004 Specifications SPECIAL SPECIFICATION 6027 Lane Control Signal Equipment 1. Description. Furnish and install Lane Control Signal (LCS) equipment. 2. Material. Provide new, corrosion resistant materials in accordance with the details shown on the plans. Provide LCS Control Panels, load switches, and all pertinent hardware, cabling, and wiring. Provide LCS heads, hardware, brackets, rigid and flexible conduit, electrical wire and cable. A. Lane Control Signal Head. Provide fiber optic LCS heads with dot matrix indications on a flat, black, non-reflective, rectangular face. Provide glass optic fibers, i.e. Corning, AT&T, or equivalent. 1. Signal Indications. Form the signal indications by forming a group of dots to which light is transmitted from a central light source through glass fiber bundles. Fit individual lenses over the end of each fiber optic bundle for increased intensity and improved view angle in the forward direction. Use color filters to obtain the color of any indication. Provide color filters that are changeable in the field without requiring removal of the signal from the case. Illuminate each indication with 2 Quartz Halogen lamps (40 watts nominal). Provide lamps that have at least an average life of 8,000 hr. at the operating voltage. 2. Dimming Provision. For each signal indication, provide a light source designed for operation with both lamps on during bright ambient light and with one lamp on during dim ambient light. Provide burnout protection for the dimming mode so as not to turn off the bulb when the other 1 is burned out. 3. Fiber Randomization. Arrange fiber optic bundles in each signal with alternate bundles leading to the same lamp so that in the event of failure of one of the lamps, the other will continue to display a discernible indication. 4. Extra Fiber Bundles. Provide a minimum of 6 extra bundles of fibers, properly protected within chaff resistant casing for insertion in lenses, for each LCS head. 5. Fiber Protection. Protect fiber optics bundles to avoid damage when installing, or during maintenance on other components in the signal head. 6. Visibility. Provide LCS heads with indications that are clearly visible and legible for 1/4 mi. distance within a 20 cone centered about the optical axis under

2 normal atmospheric conditions and under any lighting conditions. Visors or hoods will not be permitted or required. B. LCS Controller. Provide LCS Control Panels capable of controlling up to 6 independent LCS heads in each cabinet. Provide LCS Control Panels that are each 1 integral unit, with power supplies located on the unit. Install LCS Control Panels as shown on the plans, or as directed. Provide LCS Control Panels that are capable of displaying all indications on the LCS in either of the 2 selectable modes of operation. Provide LCS Control Panels that provide both the manual selection of the LCS indications via the mechanical switches, and the remote selection of LCS indications by passing through a signal from the Local Control Unit. 1. Local Mode. When in local mode, the LCS responds to the signal select switches located on the LCS Control Panel. The signal indication selected on the signal select switches remains until another signal is selected, or the mode is changed. 2. Remote Mode. When in remote mode, the Local Control Unit controls the Lane Control Signal. 3. LCS Control Panel and Indicators. Provide LCS Control Panels with the following clearly labeled switches and indicators. On/Off Switch. This switch controls the power to the LCS and the LCS Control Panel. This switch may be located elsewhere in the cabinet. Control Panel Mode Switch. This switch controls the mode of operation of the LCS Control Panel. The positions of the switch are Local and Remote. Only 1 position can be selected at a time. LCS Head Switch/Indicators. Provide LCS Control Panels with fitted front panels with a 6 position interlocking pushbutton mechanical switch, with lock-out feature, for each LCS head (6 per control panel). The first 5 positions correspond to the required indications and the sixth position turns off power to the head. Furnish each sixth position switch with 6 corresponding light emitting diodes (LED) that are colored to match the indication selected by the associated switch. Clearly silkscreen label each switch position, and corresponding LED, with the indication that switch activates on the LCS head. Equip LCS Control Panels with a lamp test switch to check all panel indicators

3 4. Load Switches. Include the load switches required to operate the lane control signals. Provide solid state load switches with no moving parts. Provide load switches that comply with Section 5 of NEMA Standard TS2, latest revision. Provide load switches that are capable of controlling all 3 lamp sets in a LCS head. Use a pair of 3 circuit load switches to control the 5 lamp sets. Provide an indicator light for each circuit on each load switch. The indicator light turns on when a true input to the load switch is present. Provide load switches capable of operation at 10 amps of tungsten lamp load over the specified temperature range. Mount and connect the load switches and field wiring to the Cabinet Back Panel. C. Functional Requirements. Furnish and install LCS on bridge beams, existing sign bridges, or overhead structures as shown on the plans. Each LCS head will be independently controlled to indicate the status of each lane. Provide LCS heads that display the following indications: Red X, Yellow X, Yellow Down Arrow (slanted at 45 deg. right), Yellow Down Arrow (slanted at 45 deg. left), Green Down Arrow. The LCS Control Panel drives the LCS heads via the Cabinet Back Panel. Commands to the LCS Control Panel will be from the following sources: Manual Control switches mounted on the front of the LCS Control Panel, Remote Control Mode via the communications network from the Traffic Management Center. Provide identical and interchangeable LCS equipment at each field location. LCS equipment includes the following: Up to 6 lane control signal heads at each location as shown on the plans, One LCS Control Panel for up to 6 lane control signal heads, Load switches mounted on the Cabinet Back Panel, or on the remote field equipment load switch panel, Control switches, indicators, cabling, supporting hardware, and mounting hardware required to functionally complete, test, and operate LCS installation

4 D. Electrical Requirements. 1. LCS Control Panel Interface. Provide LCS Control Panels with inputs and outputs that comply with Section 13 of NEMA Standard TS2, latest revision. Provide LCS Control Panels with LCS Commands and Confirms as shown in Table 1 for each head: Table 1 LCS Commands and Confirms Commands Confirms Red-X Red-X Yellow Down Arrow Yellow Down Arrow Yellow Arrow (slanted 45 deg right) Yellow Arrow (slanted 45 deg right) Yellow Down Arrow (slanted 45 deg left) Yellow Down Arrow (slanted 45 deg left) Green Arrow Green Arrow One Online Command One Online Confirm One Local Control Confirm Blank Command Blank Confirm The confirm signals described above are true confirmed. These signals originate from the control lines, between the back panel and the LCS head, and place a 0 VDC (true ground) signal on the appropriate connector pin. A true command causes the corresponding indication to be displayed or action taken. A true confirm indicates illumination of the signal head or LCS Control Panel in a particular mode. 2. Signal Confirms. Provide wiring to generate a signal confirm for each green, red, and yellow signal display. These confirms are generated based on the current load of the 115 VAC signals between the load switch and the LCS head lamp transformer. The signal confirms are set true when the signal is illuminated and are fully compatible with the Local Control Unit (LCU) back panel signal interfaces. Provide plug-in current sensing devices, each with a visual indication when the device senses current flow. No toroid will be acceptable. 3. Power Requirements. Provide LCS equipment that meets all specified requirements when the input power is 115 VAC ± 10%, 60 Hz ± 3 Hz single phase. Do not exceed a maximum power requirement of 200 watts. Provide LCS equipment that operates unaffected by transient voltages, surges, and sags normally expected on commercial power lines. Check the local power service to determine if special design is needed for the equipment on the LCS cables. 4. Primary Input Power Interruption. Provide equipment that complies with Section Power Interruption of the National Electrical Manufacturers Association (NEMA) Standard TS2, latest revision

5 5. Power Service Transients. Provide equipment that complies with Section Transients, Power Service of the NEMA Standard TS2, latest revision. 6. Wiring. Provide wiring that complies with the NEC. Cut wires to proper length before assembly. Do not double back wire to take up slack. Neatly lace wires into cables with nylon lacing or plastic straps and secure with clamps where necessary. Do not use adhesive backed cable guides. Supply and install wiring to interconnect the LCS load switches in the Cabinet and the LCS heads. Use signal cables, as shown on the plans, for each of the LCS heads. If additional wires are required, install them at no cost to the Department. Provide wiring and interface equipment for interconnecting the multiplexers by means of NEMA-type inputs and outputs. 7. Grounding. Ground the LCS support bracket and field Cabinet as shown on the plans. 8. Transient Suppression. Provide diodes across the coils for transient suppression on all DC relays, solenoids, and holding coils. 9. Power Service Protection. Provide equipment that contains readily accessible manually resettable or replaceable circuit protection devices (such as circuit breakers or fuses) for equipment and power source protection. 10. Fail Safe. Design equipment such that the failure of the equipment does not cause the failure of any other unit of equipment. 11. Lane Control Signal Field Equipment. Install a 25 PR, 19 AWG, twisted pair cable to control the interface cabinet load switches, so the lane control signal field equipment for all remote interface cabinets require the LCU, through the interface backpanel, to drive all of the remotes. The Signal Confirms, Section 2.D.2., provide the LCU and the data system with the status of which LCS head is present, or true. The remote signal field equipment consists of the following: Load switch panel, 19 in. rack mounted, LCS head panel for Remote/Local controls, Voltage and current interface converters for the load switch confirms that interface to the LCU back panel, Standard cabinet power and signal electrical suppression equipment panels, Conduit as shown on the plans, Ground boxes as shown on the plans, 25 pair, 19 AWG, twisted pair communication cable, and 7 conductor, 12 AWG electrical cable

6 12. Surge Protection. Provide LCS cabinets that incorporate surge protection as detailed in Special Specification, ITS Field Equipment Cabinets. E. Mechanical Requirements. 1. LCS Head. Provide LCS heads with lane control signal faces 18 in. in width and height, in a minimum in. thickness sheet aluminum case that is primed with epoxy type paint. Degrease and prime the interior and exterior of each LCS head with 1 coat of vinyl butyral primer, between 0.1 mil and 1 mil in thickness. Cover the primer coat with 2 coats of aliphatic urethane flat black, to a thickness of 3 mil. If the bracket anchor bolts and conduit runs are attached to the surface of a concrete bridge beam, paint the bracket anchor bolts and conduit the same color as the bridge beam. Paint in accordance with Item 446, Cleaning and Painting Steel. Provide galvanized brackets, anchor bolts, and conduit runs for corrosion resistance when attached to steel truss overhead sign bridges. To minimize legibility when the signal is not illuminated, provide LCS heads with black-colored front panels of the signal and lens mount. No color appears in the lens when not illuminated, regardless of sunlight intensity. Provide a barrier type terminal strip in each signal for the connection of field wires. Clearly mark the function of each terminal. Mount all fiber optics and lamps on a hinged door. All components are readily accessible when the door is opened. The only tool required for maintenance or replacement of components is a standard screwdriver. The signal housing case, together with door and mounting attachments, comprise a dust and moisture proof housing for the optical unit, connecting wiring, and terminal block. The signal housing and door, fittings, and accessories are made of non-corrosive, rust resistant materials capable of withstanding constant exposure to sunlight and corrosive atmospheres, and provide adequate strength for its intended purpose. Provide a lamp socket designed to prevent the formation of corrosion on either the lamp or socket contacts. Provide lamp sockets that do not allow the lamps to work loose from the socket when vibrated. Provide LCS heads capable of withstanding 100 mph wind loading. Provide LCS heads with MS type connectors so that each head can be electrically disconnected and replaced without having to remove wire from the terminal box. 2. LCS Control Panel. Fabricate LCS Control Panels from durably finished sheet metal with indicators, switches, capable of selecting and displaying the status of the signal indications. All connections for the LCS Control Panel are made by type MS connectors (metal casing) locating on the LCS Control Panel. Provide LCS Control Panels no larger than 11 in. wide X 12 in. high X 11 in. deep. All local selection switches are multiple push button switches with an interlocking lock-out feature

7 3. Construction. 3. Modular Design. Design the equipment to be modular for ease of replacement. Key modules of unlike function to prevent insertion into the wrong socket or connector. Identify modules and assemblies with name, model number, serial number, and any other pertinent information required to facilitate equipment maintenance. 4. Connectors and Harness. Make all external connections by means of keyed connectors to prevent improper hookups. Color code or appropriately mark wires between the connectors. 5. Environmental Design Requirements. Provide LCS equipment that meets the specified requirements during and after subjection to any combination of the following: Ambient temperature range of -40ºF to +140ºF, Temperature shock not exceeding 30ºF per hour, during which the relative humidity does not exceed 95%, Relative humidity range not exceeding 95% over the temperature range of 41ºF to 111ºF, and Moisture condensation on all surfaces caused by temperature changes. a. Primary Power Variation. Provide equipment that meets the specified performance requirements when the input voltage is ±10% from the nominal value of 115 V. b. Relative Humidity. Provide equipment that meets the specified performance requirements when subjected to a temperature and relative humidity of 60ºC and 22% respectively for 48 hr. c. Vibration. Provide equipment that shows no degradation of mechanical structure, solder components, plug in components, or satisfactory operation in conformance with the manufacturer s equipment specifications after being subjected to the vibration test as described in Section Vibration Test of the NEMA standard TS2 latest revision. A. General. Utilize the latest available techniques to minimize the number of different parts, subassemblies, circuits, cards, and modules to maximize standardization and commonality. Provide components that are standard off-the-shelf models. Design equipment for ease of maintenance. Provide component parts that are readily accessible for inspection and maintenance. Provide equipment that requires only simple hand held tools, basic meters, and oscilloscopes for maintenance. Provide test points for checking voltages and wave forms

8 Silk screen all text, markings, diagrams, and labels on housings and panels. Chemically etch in place all text, markings, diagrams, and labels on circuit boards. B. Electronic Components. Provide electronic components that comply with the Special Specification Electronic Components. Provide LCS Control Panels of solid state construction. Mechanical relays will not be accepted. C. Mechanical Components. Furnish stainless steel external screws, nuts, and locking washers. Do not use self-tapping screws unless otherwise directed. Provide corrosion resistant materials and materials resistant to fungus growth and moisture deterioration. Separate dissimilar metals with an inert dielectric material. D. Testing. Perform testing in accordance with Article 2, Special Specification, Testing, Training, Documentation, Final Acceptance, and Warranty. E. Training. Provide training in accordance with Article 3, Special Specification, Testing, Training, Documentation, Final Acceptance, and Warranty. F. Documentation. Provide documentation in accordance with Article 4, Special Specification, Testing, Training, Documentation, Final Acceptance, and Warranty. G. Warranty. Provide a warranty in accordance with Article 6, Special Specification, Testing, Training, Documentation, Final Acceptance, and Warranty. 4. Measurement. This Item will be measured as each unit. 5. Payment. The work performed and materials furnished in accordance with this Item and measured as provided under Measurement will be paid for at the unit price bid for Lane Control Signal Equipment or Lane Control Signal Equipment (Remote). This price is full compensation for all equipment furnished, installed, and fully operational and testing including all cables and connectors, documentation, warranty, labor, hardware, materials, training, tools, and incidentals. New conduit will be paid under Item 618, Conduit. New ground boxes will be paid under Item 624, Ground Boxes. New traffic signal cables will be paid under Item 684, Traffic Signal Cables. New electrical conductors will be paid under Item 620, Electrical Conductors

SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem

SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem 2004 Specifications CSJ s 0508-07-027, 0177-06-064, 0271-04-067, 0389-13-049 SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem 1. Description. Furnish and install Fiber Optic RS-232 Data Modem (FO-MODEM)

More information

SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem

SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem 2004 Specifications CSJ 0924-06-258 SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic RS- 232 Data Modem

More information

SPECIAL SPECIFICATION 6274 Microwave Vehicle Detection System

SPECIAL SPECIFICATION 6274 Microwave Vehicle Detection System 2004 Specifications CSJ 2374-01-153, etc. SPECIAL SPECIFICATION 6274 Microwave Vehicle Detection System 1. Description. Furnish and install the microwave vehicle detection (MVD) system as shown in the

More information

SPECIAL SPECIFICATION 1861 Premium Subrate Data Multiplexer and Distribution Panel

SPECIAL SPECIFICATION 1861 Premium Subrate Data Multiplexer and Distribution Panel 1993 Specifications CSJ s 0924-06-221, etc. & 0924-06-223 SPECIAL SPECIFICATION 1861 Premium Subrate Data Multiplexer and Distribution Panel 1. Description. This Item shall govern for the furnishing and

More information

SPECIAL SPECIFICATION 6518 IP Video Codec

SPECIAL SPECIFICATION 6518 IP Video Codec 2004 Specifications CSJ 0922-33-098 SPECIAL SPECIFICATION 6518 IP Video Codec 1. Description. A. This Item governs the furnishing and installation of IP Video Codec in field location(s) as shown on the

More information

SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link

SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link 2004 Specifications CSJ 0016-06-046, etc. SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link 1. Description. Furnish and install Wireless Ethernet Radio (WER) (Backhaul) Link in the 5.8

More information

SPECIAL SPECIFICATION 6192 Hardened Ethernet Switch

SPECIAL SPECIFICATION 6192 Hardened Ethernet Switch 2004 Specifications CSJ 2150-04-034 SPECIAL SPECIFICATION 6192 Hardened Ethernet Switch 1. Description. This Item governs the furnishing and installation of Hardened Ethernet Switch (HES) at designated

More information

SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System

SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System 2004 Specifications CSJ 0902-48-433 SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System 1. Description. Furnish and install Digital Video Encoder/Decoder (Ethernet) System (DVE/DES)

More information

SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System

SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System 2004 Specifications CSJ 0002-01-080 SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System 1. Description. Furnish and install Wireless Ethernet Radio System (WERS) links for pointto-point applications,

More information

SPECIAL SPECIFICATION 6475 CCTV Field Equipment

SPECIAL SPECIFICATION 6475 CCTV Field Equipment 2004 Specifications CSJ 0720-03-095 SPECIAL SPECIFICATION 6475 CCTV Field Equipment 1. Description. Furnish and install Closed Circuit Television (CCTV) field equipment in designated field locations and

More information

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof

More information

SPECIAL SPECIFICATION 1606 ISDN Compressed Video Equipment

SPECIAL SPECIFICATION 1606 ISDN Compressed Video Equipment 1993 Specifications CSJ 0043-09-104, etc. SPECIAL SPECIFICATION 1606 ISDN Compressed Video Equipment 1. Description. This Item shall govern for the furnishing and installation of Integrated Services Digital

More information

SPECIAL SPECIFICATION 6025 CCTV Field Equipment

SPECIAL SPECIFICATION 6025 CCTV Field Equipment 2004 Specifications SPECIAL SPECIFICATION 6025 CCTV Field Equipment 1. Description. Furnish and install closed circuit television (CCTV) field equipment. 2. Materials. Provide new, corrosion resistant

More information

SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio

SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio 2004 Specifications CSJ 1068-02-124 SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio 1. Description. Furnish and install Wireless Ethernet Microwave Radio (WEMR) as shown on the plans, as detailed

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM 6392 CCTV FIELD EQUIPMENT

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM 6392 CCTV FIELD EQUIPMENT 1993 Specifications CSJ 0364-01-095 SPECIAL SPECIFICATION ITEM 6392 CCTV FIELD EQUIPMENT 1.0 Description. This Item shall govern for the furnishing and installation of closed circuit television (CCTV)

More information

SPECIAL SPECIFICATION 1672 ISDN Compressed Video Equipment

SPECIAL SPECIFICATION 1672 ISDN Compressed Video Equipment 1993 Specifications CSJ s 0912-34-101 & 0027-08-108, etc. SPECIAL SPECIFICATION 1672 ISDN Compressed Video Equipment 1. Description. Furnish and install Integrated Services Digital Network (ISDN) Compressed

More information

SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED

SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED 2004 Specifications CSJ 0025-02-194, 0017-10-261, 0017-10-268 & 0017-10-271 SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED 1. Description. Retrofit existing

More information

SPECIAL SPECIFICATION 8167 Ethernet Switch

SPECIAL SPECIFICATION 8167 Ethernet Switch 2004 Specifications CSJ 0912-72-111 SPECIAL SPECIFICATION 8167 Ethernet Switch 1. Description. Furnish, install, integrate, and test Ethernet Switches (ES) and Hardened Ethernet Switches (HES) at designated

More information

SPECIAL SPECIFICATION 1986 CCTV Field Equipment

SPECIAL SPECIFICATION 1986 CCTV Field Equipment 1993 Specifications CSJ 0027-12-086, etc. SPECIAL SPECIFICATION 1986 CCTV Field Equipment 1. Description. This Item shall govern for the furnishing and installation of Closed Circuit Television (CCTV)

More information

SPECIAL SPECIFICATION 6287 CCTV Field Equipment

SPECIAL SPECIFICATION 6287 CCTV Field Equipment 2004 Specifications CSJ 0110-04-166 SPECIAL SPECIFICATION 6287 CCTV Field Equipment 1. Description. Furnish and install Closed Circuit Television (CCTV) field equipment in designated field locations and

More information

1995 Metric CSJ's & SPECIAL SPECIFICATION ITEM CCTV Field Equipment

1995 Metric CSJ's & SPECIAL SPECIFICATION ITEM CCTV Field Equipment 1995 Metric CSJ's 0177-07-098 & 0720-03-095 SPECIAL SPECIFICATION ITEM 6162 CCTV Field Equipment 1.0 Description. This Item shall govern for the furnishing and installation of Closed Circuit Television

More information

SPECIAL SPECIFICATION 6325 Wireless Ethernet Microwave Radio

SPECIAL SPECIFICATION 6325 Wireless Ethernet Microwave Radio 2004 Specifications CSJ 0902-48-433 SPECIAL SPECIFICATION 6325 Wireless Ethernet Microwave Radio 1. Description. Furnish and install Wireless Ethernet Microwave Radio (WEMR) as shown on the plans, as detailed

More information

Special Specification 6082 LED Lane Control System

Special Specification 6082 LED Lane Control System Special Specification LED Lane Control System 1. DESCRIPTION 2. MATERIALS Furnish and install FTM (Freeway Traffic Management) LED Lane Control Signal (LCS) Field Equipment and all necessary associated

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console 1993 Specifications CSJ 0598-01-057 1.0 Description SPECIAL SPECIFICATION ITEM 6398 Transportation Management Console This Item shall govern for the furnishing and installation of Transportation Management

More information

SPECIAL SPECIFICATION 6900 LED Lane Control System

SPECIAL SPECIFICATION 6900 LED Lane Control System 2004 Specifications CSJ 0073-08-162, 0017-10-269, 0017-10-268 & 0017-10-271 SPECIAL SPECIFICATION 6900 LED Lane Control System 1. Description. Furnish and install FTM (Freeway Traffic Management) LED Lane

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR TRAVEL TIME SYSTEM. UNIV:SRP 1 of 6 ITS:APPR:CLC:DBP:

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR TRAVEL TIME SYSTEM. UNIV:SRP 1 of 6 ITS:APPR:CLC:DBP: MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR TRAVEL TIME SYSTEM UNIV:SRP 1 of 6 ITS:APPR:CLC:DBP:02-02-12 a. Description. This work consists of furnishing, installing, integrating, and testing

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM ITS:CLC 1 of 6 APPR:LWB:DBP:07-31-13 FHWA:APPR:09-23-13 a. Description. This work consists of one or more

More information

SPECIAL SPECIFICATION 1528 Add/Drop Multiplexor/Demultiplexor

SPECIAL SPECIFICATION 1528 Add/Drop Multiplexor/Demultiplexor 1993 Specifications CSJ 3136-01-096 SPECIAL SPECIFICATION 1528 Add/Drop Multiplexor/Demultiplexor 1. Description. This Item shall govern for the furnishing and installation of a SONET Add/Drop Multiplexor/Demultiplexor

More information

SPECIAL SPECIFICATION 1826 Field Ethernet Switch

SPECIAL SPECIFICATION 1826 Field Ethernet Switch 1993 Specifications CSJ 0521-04-223 SPECIAL SPECIFICATION 1826 Field Ethernet Switch 1. Description. Furnish, install, and make fully operational a Field Ethernet Switch at designated locations as shown

More information

Special Specification 2342 Environmentally Controlled Radio Tower Cabinet

Special Specification 2342 Environmentally Controlled Radio Tower Cabinet 2004 Specifications CSJ 0912-00-488 Special Specification 2342 Environmentally Controlled Radio Tower Cabinet 1. Description. Furnish, install, and test Environmentally Controlled Radio Tower Cabinet.

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM ITS:CLC 1 of 5 APPR:JVG:DBP:06-29-17 FHWA:APPR:08-02-17 a. Description. This work consists of one or more

More information

SPECIAL SPECIFICATION 8371 Field Terminal Server

SPECIAL SPECIFICATION 8371 Field Terminal Server 2004 Specifications CSJ 0914-00-280 SPECIAL SPECIFICATION 8371 Field Terminal Server 1. Description. Furnish, install, and make fully operational a Field Terminal Server at designated locations as shown

More information

SPECIAL SPECIFICATION 1252 System Control Unit Console

SPECIAL SPECIFICATION 1252 System Control Unit Console 1993 Specifications CSJ 0924-06-147, etc. SPECIAL SPECIFICATION 1252 System Control Unit Console 1. Description. This Item shall govern for the furnishing and installation of system control unit (SCU)

More information

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m. Built-in Amplifier (Medium Size) ES-A CSM_ES-A_DS_E Be sure to read Safety Precautions on page 0. Ordering Information Built-in Amplifier s Red light Infrared light Sensing method Appearance Connection

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Special Specification 6016 ITS Field Equipment Cabinet

Special Specification 6016 ITS Field Equipment Cabinet 2004 Specifications Special Specification 6016 ITS Field Equipment Cabinet 1. Description. Furnish, install, and test equipment cabinets. 2. Materials. Furnish new, corrosion resistant materials. Furnish,

More information

Mini Photoelectric Sensor

Mini Photoelectric Sensor Mini Photoelectric Sensor High cost-performance Mini Photoelectric Sensor Saves Installation Space and Wiring Effort and Detects Minute Sensing Objects Pin-point beam (1 to 2-mm dia.) makes it possible

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Special Specification 6017 Communications Hub Building

Special Specification 6017 Communications Hub Building Special Specification Communications Hub Building 1. DESCRIPTION Furnish and install Communications Hub Buildings as shown on the plans, as detailed in this Special Specification and as directed by the

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis. A21 DIMMER CABINET SPECIFICATION. GENERAL. A.) Overview. 1.) The dimmer cabinets shall be fully digital, designed specifically for architectural and entertainment lighting applications, and shall consist

More information

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM 1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL

More information

Model 720 Electromechanical Hour Meter

Model 720 Electromechanical Hour Meter Model 720 Electromechanical Hour Meter A 5 figure (reset) or 6 figure (non-reset), AC hour meter encased in a rugged steel housing and designed to mil-spec environmental requirements. The non-reset models

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR ACCESSIBLE PEDESTRIAN SIGNAL SYSTEM

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR ACCESSIBLE PEDESTRIAN SIGNAL SYSTEM MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR ACCESSIBLE PEDESTRIAN SIGNAL SYSTEM SIG:EMS 1 of 6 APPR:LWB:DBP:07-17-14 FHWA:APPR:07-30-14 a. Description. This work consists of either furnishing

More information

SPECIAL SPECIFICATION 1838 Computer Room VoIP Gateway/Gatekeeper

SPECIAL SPECIFICATION 1838 Computer Room VoIP Gateway/Gatekeeper 1993 Specifications CSJ 0521-04-223 SPECIAL SPECIFICATION 1838 Computer Room VoIP Gateway/Gatekeeper 1. Description. Furnish, install, and make fully operational a Computer Room Voice-over- Internet Protocol

More information

SPECIAL SPECIFICATION 6620 Add/Drop Multiplexor

SPECIAL SPECIFICATION 6620 Add/Drop Multiplexor 2004 Specifications CSJ 2121-04-067, etc. SPECIAL SPECIFICATION 6620 Add/Drop Multiplexor 1. Description. This Item shall govern for the furnishing and installation of an Add/Drop Multiplexor/Demultiplexor

More information

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 September 2011 STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 MATERIAL SPECIFICATIONS FOR WEIGH-IN-MOTION SYSTEM The

More information

Model NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by

Model NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by Naztec Operations Manual For Model NM512 TS1 Conflict Monitor Standard 12 Channel Unit Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 2407233 Fax: (281) 240-7238 Copyright

More information

60 Watt Portable LED Work Area Light - Waterproof - Aluminum Frame - Adjustable Light Head

60 Watt Portable LED Work Area Light - Waterproof - Aluminum Frame - Adjustable Light Head 60 Watt Portable LED Work Area Light - Waterproof - Aluminum Frame - Adjustable Light Head - 120-277 Part #: WAL-PM-WP60 Page: 1 Made in the USA The WAL-PM-WP60 Portable LED Work Light from Larson Electronics

More information

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7 User's Manual: Series 330I Model 330I DC-Powered Three-Way Isolator Table of Contents Page Introduction... 2 Description....2 Specifications....3 Installation.. 5 Calibration.. 6 General Maintenance...7

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 6 APPR:MDW:JVG:06-08-18

More information

RCL-50B PRODUCT SUPPORT MANUAL. Remote Control Searchlight Master Controller Point Pad. Y Rev. B

RCL-50B PRODUCT SUPPORT MANUAL. Remote Control Searchlight Master Controller Point Pad. Y Rev. B PRODUCT SUPPORT MANUAL Y1-03-0141 Rev. B RCL-50B Remote Control Searchlight Master Controller Point Pad ACR Electronics, Inc. 5757 Ravenswood Road Fort Lauderdale, Fl 33312 +1(954) 981-3333 Fax +1 (954)

More information

Oil-resistive, Long-range Photoelectric Sensor with Metal Housing

Oil-resistive, Long-range Photoelectric Sensor with Metal Housing Oil-resistive, Long-range with Metal Housing ES-C Water- and Oil-resistive with Metal Housing Used for Long-range Sensing Satisfies the water- and oil-resistive requirements and safe enough for use in

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

SPECIAL SPECIFICATION 6710 Fiber Optic Dynamic Message Sign System

SPECIAL SPECIFICATION 6710 Fiber Optic Dynamic Message Sign System 1995 Metric CSJ:0038-01-033, Etc. SPECIAL SPECIFICATION 6710 Fiber Optic Dynamic Message Sign System 1. Description. Furnish and install fiber optic dynamic message sign (DMS) systems with nominal 200

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Cabinet

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Cabinet 1993 Specifications CSJ 2552-03-023 1.0 Description. SPECIAL SPECIFICATION ITEM 6387 Cabinet This Item shall govern for the furnishing and installation of Type 3, Type 5 and Type P cabinets as shown on

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Click Desktop Kit. Click Desktop Kit

Click Desktop Kit. Click Desktop Kit Click Desktop Kit Click Desktop Kit The Click Desktop Kit is a desktop-mounted set that gives you the building blocks necessary to work with your Click modules at your computer, whether you re testing

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

Terminal Junction System (MIL-T and Commercial)

Terminal Junction System (MIL-T and Commercial) Introduction Product Facts The TJS connections are inherently more reliable than conventional threaded and solder terminations. The user s wiring is crimped to gold plated pin contacts, conforming the

More information

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm Long Distance Cylindrical. Extra long for increased protection and sensing performance triple proximity sensors for flush mounting requirements. designed and tested for extra long life. Ordering Information

More information

Addendum # 2. Bid # Scoreboards (Softball Baseball Soccer) Addition Specification on Softball and Baseball

Addendum # 2. Bid # Scoreboards (Softball Baseball Soccer) Addition Specification on Softball and Baseball Addendum # 2 Bid # 20170328 Scoreboards (Softball Baseball Soccer) Addition Specification on Softball and Baseball NEVCO, INC. MODEL 1608 SCOREBOARD PART 1 - GENERAL 1.1 SUMMARY 1.2 REFERENCES A. American

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer submodule N 528/41 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA)

SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA) TECHNICAL SPECIAL PROVISION FOR SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA) FINANCIAL PROJECT NO.: 428213-2-52-02 MARION COUNTY The official record of this Technical Special Provision is the

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

DIN Molded Cable Assemblies

DIN Molded Cable Assemblies DIN 43650 Telephone (973) 586-500 FAX (973) 596-590 DIN 43650 8mm For Solenoid Valve Applications Black PVC Cable & Connector DUAL JUMPED GROUND PINS Molded cable assemblies can be mounted with cable exiting

More information

Level-Lance Model 5400A

Level-Lance Model 5400A Sales Manual Section 100 PRODUCT SPECIFICATION 5400A GENERAL DESCRIPTION The ROBERTSHAW Level-Lance Model 5400A is a microprocessor based, multi-point On-Off capacitance type level detection system. Utilizing

More information

MLC. Semi Metal USB. Generation 5 / 5L HERCULES-PB Series. Product Specification MLC. Semi Metal USB Flash Disk Generation 5/5L

MLC. Semi Metal USB. Generation 5 / 5L HERCULES-PB Series. Product Specification MLC. Semi Metal USB Flash Disk Generation 5/5L MLC Semi Metal USB Generation 5 / 5L HERCULES-PB Series Product Specification MLC Semi Metal USB Flash Disk Generation 5/5L Version 01V0 Document No. 100-xMUFD-MPBTMB5 MAY 2016 APRO CO., LTD. Phone: +88628226-1539

More information

MLC. Semi-Metal USB. Generation 3L HERMIT-C Series. Product Specification MLC. Semi-Metal USB Flash Disk Generation 3L

MLC. Semi-Metal USB. Generation 3L HERMIT-C Series. Product Specification MLC. Semi-Metal USB Flash Disk Generation 3L MLC Semi-Metal USB Generation 3L HERMIT-C Series Product Specification MLC Semi-Metal USB Flash Disk Generation 3L Version 01V0 Document No. 100-xMUFD-HCTMB3L JUNE, 2016 APRO CO., LTD. Phone: +88628226-1539

More information

S8VE (60/90/120/180/240-W Models)

S8VE (60/90/120/180/240-W Models) Switch Mode Power Supply S8VE (60/90/120/180/240-W Models) CSM_S8VE_DS_E_1_1 60/90/120/180/240-W Models Improved Versions of Standard-type Power Supplies without Indication Monitor. Safety standards: UL508/60950-1,

More information

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m. Built-in Amplifier (Medium Size) ES-A Be sure to read Safety Precautions on page 0. Ordering Information Built-in Amplifier s Red light Infrared light Sensing method Appearance Connection method Sensing

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK Instruction Sheet PN 51A-54epH/rev J October 2010 ph/orp HART Model 54e ph/orp Analyzer/Controller For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. ESSENTIAL

More information

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR AUGUST 14, 2001 REVISION 1 Publication: SE-135-M Document: S95-C135-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

E105 1/2-ATR Short Fan cooled VME Enclosure

E105 1/2-ATR Short Fan cooled VME Enclosure E105 1/2-ATR Short Fan cooled VME Enclosure Rugged Chassis for Mobile Military Applications Designed for Harsh Mechanical, Climatic, Chemical and Electrical Stresses Environmentally Sealed Compact and

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings Siemens AG 200 ALPHA SIMBOX Small Distribution Boards /2 Introduction /2 Introduction /3 Flush-mounting and hollow-wall distribution boards /4 Hood-type distribution boards /5 Accessories /6 Dimensional

More information

Tempco Instruction Manual

Tempco Instruction Manual Tempco Instruction Manual 1/16 DIN Solid State Temperature Controller Relay Output Solid State Output For Heating Model Numbers: TEC-901, TEC-902, TEC-905 Temperature controls in this series are designed

More information

BGS (at min. setting) BGS (at max. setting)

BGS (at min. setting) BGS (at max. setting) Compact Photoelectric Sensor with Built-in Amplifier EZ-LS CSM_EZ-LS_DS_E_7_ Distance-settable Sensor Unaffected by Workpiece Color and Background Distance-settable triangulation model unaffected by color.

More information

Diffuse reflection light scanner with background suppression. Dimensioned drawing

Diffuse reflection light scanner with background suppression. Dimensioned drawing Specifications and description HRTR 55 Ex Diffuse reflection light scanner with background suppression Dimensioned drawing en 01-2011/05 50113748 1 khz 5 400mm 200mm with black-white error < 10% 10-30

More information

Industrial Semi-Metal USB

Industrial Semi-Metal USB Industrial Semi-Metal USB Generation 3L HERMIT-C Series Product Specification INDUSTRIAL Semi-Metal USB Flash Disk Generation 3L Version 01V0 Document No. 100-xMUFD-HCT3L December, 2015 APRO CO., LTD.

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES SECTION 16141 WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

APS4 Inductive Proximity Sensors

APS4 Inductive Proximity Sensors APS4 Inductive APS4-S-E-D APS4-S-E2-D APS4-M-E-D APS4-M-E2-D Compact x27 mm plastic DC 4 models available Compact polycarbonate housing; comes with mounting plate High-frequency oscillation type DC 3-wire,

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

TRUCK-MOUNT ARROW BOARDS

TRUCK-MOUNT ARROW BOARDS WSD-1015 10 2014 TRUCK-MOUNT ARROW BOARDS MODELS WB, WFB, WFP, WLP & WVGB PRODUCT SPECIFICATIONS OCTOBER 2014 Truck- Mount Arrow Boards Page 2 of 15 1. DESCRIPTION 1.1. Description Arrow boards direct

More information

Cabinet Interface Device

Cabinet Interface Device Cabinet Interface Device Click 650 The Click 650 provides streamlined communication for SmartSensor Matrix and Advance to traffic controllers in one compact case. This module communicates directly to the

More information

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount. This Datasheet for the IC697CHS790 Rack, 9 Slots, Rear Mount. http://www.cimtecautomation.com/parts/p-14771-ic697chs790.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

User's Manual: Series 250T Potentiometer/Slidewire Input, Two-Wire Transmitters

User's Manual: Series 250T Potentiometer/Slidewire Input, Two-Wire Transmitters User's Manual: Series 250T Potentiometer/Slidewire Input, Two-Wire Transmitters INTRODUCTION: Table of Contents Page Introduction 1 Description 1 Specifications 2 Specifications (Display Option) 3 Installation

More information

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations Slim Relay G2RV The World's First Industrial Slim Relay Large plug-in terminals for reliable connection. LED indicator and mechanical flag to check operation. Transparent housing enables checking relay

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS Installation Manual 1180 METRIX Experience Value 8824 Fallbrook Dr. Houston, TX 77064, USA Tel: 1-281-940-1802 After Hours Technical Assistance: 1-713-702-8805

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

IVR15-SPI 1.5 Solid State Illuminated Rail 2 Post Integral Power Supply

IVR15-SPI 1.5 Solid State Illuminated Rail 2 Post Integral Power Supply 1.5 Solid State Illuminated Rail 2 Post Integral Power Supply 1.50 RECOGNIZED 0.3 90 APERTURE Ends of Illuminated rail field cuttable to a minimum of 2 1/8 in length. Illuminated rail is available with

More information

APL/UPL, 205/295 Series Magnetic Circuit Protectors

APL/UPL, 205/295 Series Magnetic Circuit Protectors APL/UPL, 205/295 APL/UPL, 205/295 Series Magnetic Circuit Protectors Introduction 68 Single & Multi-Pole 69 Barriers 7 Configurations 72 Operating Characteristics 74 Delay Curves 75 Specifications 80 Decision

More information