1 Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden)
2 Motivation Background Our Research Agenda Modeling Thermal Behavior Static Workload Provisioning Dynamic Workload Provisioning Improving Data Center Efficiency by Fixing Existing inefficiencies/hotspots Layout Planning Current Status
3 Total US Data Center Power Consumption is about 1.5% of US total electricity consumption Total Cost for Data Center Electricity consumption ~ $5B in 2007 ($7.5B by 2011) Issue: Though it accounts for a very small percentage of overall consumption, the concentrated nature/density leads to supply issues (concentrated demand on power grids)
4 Data Center Power Consumption 50% Heating Ventilation & Air Conditioning (HVAC) 20-35% Servers 10-25% Storage 5% Networking Different Types of data centers Compute Centric (Ex: HPC) 35% Servers,10% Storage, 5% Networking Data Centric (Ex: Enterprise) 20% Servers, 25% Storage, 5% Networking Average Case 25% Servers, 20% Storage, 5% Networking
5 Almost all Energy consumed by all IT equipment is released as Heat Heat Extraction Process Fans suck in Cold Air from the vents at front of servers (inlets) As the cold air passes through the server, heat is extracted/absorbed and air exits the system at a higher temperature Q: Heat generated is a function of System Load Inlet temperatures should be kept below 25 0 C for safe operation (Thermal Redlining) : Failure rates increase non linearly above this threshold
6 Computer Room Air Conditioning Units (CRACs) extract out the heat generated by devices and supply cold air to the data center Higher the Supply Temperature -> Higher the CRAC Efficiency (Coefficient Of Performance) Q: Amount of Heat W: Work done is removing/extracting Q units of heat [HP Usenix 07] Device Inlet temperatures are a function of Supply temperature 25 0 C Supply temperature!= 25 0 C Server Inlet temperature Higher Supply Temp -> Higher Inlet Temp (Ideal setting: Highest Supply temp that leads to Max Inlet Temp < 25 0 C)
7 Heat Recirculation or Hot gas bypass Hot air generated by servers/storages does not completely travel across and reach the CRAC for extraction, a portion of it recirculates into cold isle. Cause Natural recirculation around the end of isles and top of racks or unused open spaces in racks in combination with flow rates of supplied cold air Effect With Supply temperature set to a given point, the Inlet temperatures at various servers tends to be higher that the supply temperature Factors that affect HR Data Center Layout/dimensions Workload distribution
8 Top View Profile View Typical Raised Floor Based Layout
9 Height:3ft Height:6ft Impact of Heat Recirculation Increases with height Temperatures at rack tops are higher than at rack bottom
10 Difference???? Difference???? Row Ends Row Middle Impact of Heat Recirculation Lesser at middle of rows/isles Increases towards row/isle ends
11
12 Objective Predict Temperatures Profile of Data Center Inlet temperatures of all Server & Storages as a function of Workload on all systems for a fixed layout and cooling system Given Power Usage of all equipment Physical Location of all equipment Physical Dimensions and Layout of the Data Center(fixed) Our Proposed Solution Use Supervised Machine learning techniques to build regression based predictors Support Vector Machines
13 Limitations of Related work (ASU) Modeling based approach & (HPLabs) Neural Net based approach Does not account for On/Off nature of server/fans (ASU) Does not provide any means of understanding/ verifying learnt functions (HPLabs) Parameter space has to be reduced for reasonable learning time (HPLabs) Assumes homogenous equipment (flow to power ratio) Our approach uses SVM based predictors Incorporates both Flows and Power profiles of servers Scalable & Verifiable Support Vectors Provides a means for understanding HR characteristics
14 Objective Determine relationship between Supply temperatures of Cooling Units and Server Inlet temperatures Given Power Usage of all equipment Physical Location of all equipment Physical Dimensions and Layout of the Data Center(fixed) Our Proposed Solution Profiling based approach to determine Zone Ownership Vary Supply temperature of each of the CRACs one by one and observe the corresponding change in Server Inlets Difficult to Model: Highly Dependent/Coupled with Server Workloads Zones of ownership more easier to determine and often adequate
15 Objective Minimize Data Center Power Consumption for a given Workload Set Assumptions Provisioning from scratch No deadlines all at once Constraints Server Inlet Temperatures < Threshold (25 0 C) CRAC loads < Maximum Capacity (100kW each) Given Physical Layout Information
16 Our Proposed Solution: Discrete non-linear optimization Objective function: Minimize overall Power Consumption Minimize Power consumption of Servers + Storages Minimize Peak Inlet temperature of devices (Zones) Basic Constraint: Inlet Temp < threshold Advanced Constraint: Connectivity + Policy based Solution Technique: Genetic Algorithms Workload distribution as the population string Challenges Trade off between Workload/platform efficiency and Cooling system efficiency Impact of Modeling accuracy on optimization process Incorporating Constraints
17 Objective Minimize Data Center Power Consumption for a given Workload on an running system/reprovisioning existing system to minimize inefficienies Assumptions System with pre running workloads and pre specified system state Constraints Server Inlet Temperatures < Threshold (25 0 C) CRAC loads < Maximum Capacity (100kW each) Given Physical Layout Information
18 Challenges Minimizing impact of reprovisioning on real time performance Trade off between repositioning one or more existing workloads vs performance/power gain by reprovisioning in the long run Accounting for power cost of reprovisioning Accounting for constraints
19 Objective Derive best practices for Floor Planning using the system models Temperature Profile as function of Data Center Dimensions Raised Floor Depth Ceiling Height Row Width CRAC placement Constraints Prevent thermal redlining Given Thermal Characteristics of devices Performance characteristics of devices
20 Layout Planning Designed simulations in Flovent CFD simulator Impact of Datacenter Characteristics on Thermal Profile Thermal Modeling as a function of Workload Collected Training Data for Supervised Learning Implement SVM based regression learners Thermal Modeling as a function of Variable Cooling Units Designed simulations in Flovent Impact of Cooling System variation on Thermal Profile Determined Zone based ownership
21 Raised Floor Depth 0.15m 0.3m 0.45m 0.6m # of Servers > 25C
22 Ceiling Height # of Servers >25C
23 Layout EEWW NSEW NNSS # of Servers > 25C
24 Size 4ft 6ft 8ft # of Servers > 25C *Room Size: 4ft = 2 floor tiles at any point between racks and walls
25 C R A C A Effect of 1 0 Change on CRAC Supply Temperature C R A C B Rack Bottom Rack Top
26 C R A C C Effect of 1 0 Change on CRAC Supply Temperature C R A C D Rack Bottom Rack Top
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationEstimating Data Center Thermal Correlation Indices from Historical Data
Estimating Data Center Thermal Correlation Indices from Historical Data Manish Marwah, Cullen Bash, Rongliang Zhou, Carlos Felix, Rocky Shih, Tom Christian HP Labs Palo Alto, CA 94304 Email: firstname.lastname@hp.com
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationAvoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationCoordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization
Coordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization Li Li, Wenli Zheng, Xiaodong Wang, and Xiaorui Wang Dept. of Electrical and Computer Engineering The
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationTemperature monitoring and CFD Analysis of Data Centre
Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationEnergy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering
Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationA LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER
A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.
More informationGreat Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch
Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents
More informationData Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala
Data Centre Energy & Cost Efficiency Simulation Software Zahl Limbuwala BCS Data Centre Simulator Overview of Tools Structure of the BCS Simulator Input Data Sample Output Development Path Overview of
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationTen Cooling Solutions to Support High- Density Server Deployment
Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,
More informationMaking Scheduling Cool : Temperature-Aware Workload Placement in Data Centers
Making Scheduling Cool : Temperature-Aware Workload Placement in Data Centers Justin Moore Jeff Chase Parthasarathy Ranganathan Ratnesh Sharma Department of Computer Science Duke University {justin,chase}@duke.edu
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD
R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationExploiting a Thermal Side Channel for Power Attacks in Multi-Tenant Data Centers
Exploiting a Thermal Side Channel for Power Attacks in Multi-Tenant Data Centers Mohammad A. Islam, Shaolei Ren, and Adam Wierman Acknowledgement: NSF under grants CNS-1551661, CNS-1565474, and ECCS-1610471,
More informationCapacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.
Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationOne Stop Cooling Solution. Ben Tam Business Development Manager
One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One
More informationEnergy Efficient Cloud Computing: Challenges and Solutions
Energy Efficient Cloud Computing: Challenges and Solutions Burak Kantarci and Hussein T. Mouftah School of Electrical Engineering and Computer Science University of Ottawa Ottawa, ON, Canada Outline PART-I:
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationOptimizing data centers for high-density computing
Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for
More informationPower consumption and efficiency of cooling in a Data Center
Power consumption and efficiency of cooling in a Data Center Satoshi Itoh, Yuetsu Kodama, Toshiyuki Shimizu and Satoshi Sekiguchi (AIST), Hiroshi Nakamura (The University of Tokyo), Naohiko Mori (NTT Communications
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationHigh Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach
High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,
More informationMeasurement and Management Technologies (MMT)
IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationCost Model Energy Benefits DirectAire & SmartAire Overview & Explanation
Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation A cost model (See figure 1) has been created to provide the user a simplified method for directly comparing the energy cost of a
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationDesign and Installation Challenges: Aisle Containment Systems
Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and
More informationCRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS
CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical
More informationTo Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels
To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More information) ) page 04. page 07. page 10. page 10. page 12. page 14. page 14. page 16. page 18. page 19. page 19. page 20. page 21. page 22
english version SAIFOR ADVANCED COOLING SOLUTIONS HDC AISLE HIGH DENSITY COOLING MDC AISLE HDC RACK MDC RACK CUBO KEEP-COOL HTRD CADU MAIN FEATURES CONFIGURATIONS & ACCESSORIES CUBO ACCESSORIES ) ) MEDIUM
More informationHIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation
More informationPrecision Cooling. Precision Cooling Advantages
Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing
More informationReview on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management
Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management Alfonso Capozzoli 1, Marta Chinnici 2,, Marco Perino 1, Gianluca Serale 1 1 Politecnico di Torino, Corso
More informationInnovative Data Center Energy Efficiency Solutions
Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal
More informationHigh Density Cooling Solutions that work from Knurr Kris Holla
High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationImproving Rack Cooling Performance Using Blanking Panels
Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationCFD Modeling of an Existing Raised-Floor Data Center
CFD Modeling of an Existing Raised-Floor Data Center Amir Radmehr 1, Brendan Noll 2, John Fitzpatrick 2, Kailash Karki 1 1. Innovative Research, Inc. 3025 Harbor Lane N, Suite 300, Plymouth, MN 2. University
More informationRethinking Datacenter Cooling
Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationPartner Introduction
P R E S E N T S Partner Introduction September 16, 2013 Today s Agenda The Market Opportunity The Cooling Capacity Factor (CCF) New service Benefits to Upsite Partners How to Sell Launch Plan & Support
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationTRACE 700 Learning Series Module 2: Navigation
Module 2: Navigation Project Information, Weather & Templates Create Rooms Create Systems Assigning Rooms to Systems, Zoning, Calculate and View Results Output Overview Module 2 Exercise Module 1: Objectives
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationAPC APPLICATION NOTE #126
#16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson
More informationABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends
ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More information