1 1 Optical Fiber Premises Standards News & Trends Herb Congdon Tyco Electronics Updated: October 2005

2 2 IEEE Ten Gigabit Ethernet (10GBASE-F) Published as IEEE802.3ae in June 2002 Ten Gigabit Ethernet (10GBASE-LRM) 10GBASE-LRM (802.3aq) 10G using one SM laser source Objective is a less-expensive solution for legacy MM fiber Reach is an issue 220m, not 300m

3 3 TIA TR-42 UPTI Nine Subcommittees 42.1 Commercial Building Cabling 42.2 Residential 42.3 Pathways & Spaces 42.4 Outside Plant 42.5 Terms, Definitions and Abbreviations 42.6 Administration 42.7 Copper Components 42.8 Optical Fiber Components 42.9 Industrial Most recent meetings held Oct 2-7, 2005

4 4 TR-42.1 Commercial Building Cabling Completed Work for 568-B.1 Addendum 3 (Supportable Distances and Channel Attenuation for Optical Fiber Applications by Fiber Type) published 2/03 100BASE-SX and 10GBASE-F included Addendum 4 (Recognition of Category 6 and 850nm Laser-Optimized 50/125 µm Multimode Optical Fiber Cabling) published 2/03 Allows the 850nm Laser-Optimized 50/125 µm

5 5 TR-42.1 Commercial Building Cabling Completed Work on 568-B.1 Addendum 5 (Telecommunications Enclosures) is released for publication This addendum says how a TE can be used in a 568-B.1-compliant manner Allows fiber further into the network

6 6 TE - Traditional Horizontal Cabling HC in the TR Optical Fiber Backbone Horizontal cabling 4-pr. UTP cables TO Offices Cubicles

7 7 TE - Concept Implementation HC in the TR Optical Fiber Backbone Optical Fiber Backbones e.g. TE TE TO Cubicles Horizontal cabling Offices

8 8 TR-42.1 Commercial Building Cabling TIA-942, Telecommunications Infrastructure Standard for Data Centers Network Distribution Nodes More commonly referred to as the Data Center & SAN Standard Available for purchase since April 1, 2005 ($250) Important Fiber Issues Single-mode, 62.5-micron, 50-micron and 850nm Laser-optimized fiber allowed (latter is recommended) 300 meter pull-through allowed for centralized fiber networks (not 90m as in 568B)

9 9 TR-42.3 Pathways and Spaces Work Completed in February 569-B is now published & available ($163) Final editorial change approved in June 2004 Published as a TIA Standard TIA-569-B (Pathways and Spaces) defined telecommunications enclosures (TEs)

10 1 0 TR-42.7 Copper Cabling Components Recently Completed Work TIA-568-B.2-11 Maximum Diameter Of SCTP Cable To.354 Inches was sent to publish in the October meeting 2-fiber zipcord: 0.11 x 0.22 inches 2-fiber mini-zipcord: 0.08 x 0.16 inches 2-fiber DUAL: 0.19 inches 2-fiber QUAD: 0.19 inches

11 1 1 TR-42.8 Optical Fiber Cabling Components Recently Completed Work for 568-B B.1-7 Guidelines For Maintaining Optical Fiber Polarity with Systems Utilizing Array Connectors Supports use of array connectors (MPO) Started in support of Data Center Standard

12 1 2 TR-42.8 Optical Fiber Cabling Components New Project 568-C.3 revision project started

13 C?!?! Just what do you think you re doing? TIA mandates that Standards be revised, withdrawn or reaffirmed every 5 years The revision process takes about two years or so TIA-568B was published in May of 2001 (over four years ago) so...better get started! Projects opened for 568C.0 568C.1 568C.2 568C.3

14 1 4 What s this about 568-C.0? A better way to do things in TR-42? Types of Premises Standards Commercial, Residential, Outside Plant, Industrial (eventually), Data Centers Components Standards Copper UTP, Coaxial Cable, Optical Fiber, Connectors, etc. Practice Standards Pathways & Spaces, Administration TR-42 Subcommittee Chairs looked at what we were doing things and wondered how to do them better

15 1 5 What s this about 568-C.0? One thing we re doing is repeating information Can generate inconsistencies Requirements and documents that may not reflect the most recent information Document cycles complicate adoption of consistent information and revisions

16 1 6 What s this about 568-C.0? Several proposals considered Best Solution: Create a Generic Cabling Standard To serve as an umbrella document for all the types of premises standards Types of Premises standards would then list requirements specific to the type of premise

17 568-C.0: Generic Cabling 1 7 Since all the types of premises standards are based on the hierarchal star architecture, this document would outline the connection points and links Connection Points instead of spaces A (ex: Main Cross-connect) B (ex: Intermediate Cross-connect) C (ex: Telecommunications Room) D (ex: Consolidation Point) Links between connection points Level 1 (ex: intrabuilding cable) Level 2 (ex: interbuilding cable) Level 3 (ex: horizontal cable)

18 C.0: Generic Cabling Would also include other information common to several documents Choosing media Bonding and grounding Field testing Polarity etc.

19 1 9 So, the 568 Series would potentially be C.0: Generic Cabling 568-C.1: Commercial Building Cabling 568-C.2: Copper Cabling Components 568-C.3: Optical Fiber Cabling Components

20 C.0 Drawbacks Concerns about yet another Standard to purchase May be difficult to get finished in a timely manner May have a 4 to 5 year period before all other documents can be revised with recognition of this 568-C.0 What to do with Pathways & Spaces and Administration Standards?

21 C.0 Advantages Becomes a clearing house for common aspects of structured cabling Serves as springboard for new types of premises standards ex: Healthcare Facility Cabling Simplifies additions, deletions and revisions due to advances in technology

22 C.0 Today Still just a project proposed and approved Discussions are continuing on how to divide up the existing documents First draft may be released before October meetings Probably a cut-and-paste of existing documents

23 How could it look? 2 3 Existing documents (Standards, Addenda, etc.) will have to be parsed out into one of the new documents or left behind for the next revision

24 2 4 Examples - Addenda Addenda to 568-B.1 could roll into 568-C Seven approved or in ballot 1: Patch Cable Bend Radius C.0 (use) and C.2 (manufacture) 2: B&G for Screened TWP C.0 3: Annex E Revision (Fiber Design Param s) C.0 4: Cat 6 and 850nm LO 50-micron C.0 (use) and C.2/C.3 (mfg) 5: Telecommunications Enclosures C.1 6: DC Power (DTE) C.0 7: Array Connector Polarity C.0 (use) & C.3 (manufacture)

25 2 5 Examples - TSBs TSBs can be rolled into 568-C TSB-125 Reverse Pair Positioning Polarity C.0 & C.3 TSB-140 on fiber certification testing C.0 TSB on cabling bundles and loops C.0 & C.2

26 2 6 What happens with 568-C.1? Retains those requirements and guidelines specific to commercial building cabling Nomenclature (tends to be different across types of premises) Outlet number and location Allowable media (subset of all media)

27 2 7 How about 568-C.2? Retains content of 568-B.2 and related documents specific to the components and link performance May need to add coaxial cable (Data Centers, Residential, etc.)

28 How about 568-C.3? 2 8 Retains content of 568-B.3 and related documents specific to the components and link performance Already some agreements on changes to make Add in an indoor/outdoor cable reference (ICEA S ) and a drop cable reference (ICEA S ) Use when color is used to identify the fiber type... (color) should indicate (fiber type)... Separate out 50µm connectors and adapters so that the color black indicates 50µm, beige indicates 62.5µm, aqua indicates 850nm laser optimized 50µm mmf, blue indicates single-mode, and green for angled single-mode

29 2 9 What About the Other Documents? Although incongruous at first, the other standards documents will be revised to fit under the umbrella of 568-C C.0 will reference the components defined in C.2 and C-3 Practice Standards (Admin, Pathways and Spaces) may get rolled into Generic or remain as standalone

30 3 0 What s Next? Chairs group has matrix of all documents Table of contents with proposals for retaining or moving to another document Once satisfied, drafts for 568-C.0, 568-C.1, 568- C.2 and 568-C.3 will be created THEN the real fun can begin Proposed Schedule Drafts in December 2005 Ballots in 2006 Publish???

31 3 1 A respectful request... Your input is valuable to the process Please submit your comments, criticisms, gripes and other observations for consideration Next meeting is in late January

32 3 2 For More Information & Updates Fiber Optic LAN Section Cost Models White Papers Standards Updates

33 3 Thank You Herb Congdon

LAN Standards, News & Trends. Herbert V. Congdon II, PE Tyco Electronics Updated: October 10, 2008

LAN Standards, News & Trends. Herbert V. Congdon II, PE Tyco Electronics Updated: October 10, 2008 LAN Standards, News & Trends Herbert V. Congdon II, PE Tyco Electronics Updated: October 10, 2008 October 16, 2008 Objectives Review the recent events and activities of the TIA TR-42 Subcommittees Review

More information

Optical Fiber Networks: Industry. and New Options for Networks

Optical Fiber Networks: Industry. and New Options for Networks Optical Fiber Networks: Industry Trends, Application Influences and New Options for Networks Herbert V Congdon II, PE Manager, Standards & Technology Tyco Electronics AMP NETCONNECT Solutions Preview Deciding

More information

IEEE Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3

IEEE Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3 IEEE 802.3 Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire The Siemon Company Dallas, TX November 9, 2015 Page 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org

More information

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic

More information

Optical Fiber for Today s Premises Applications

Optical Fiber for Today s Premises Applications Optical Fiber for Today s Premises Applications Tony Irujo Customer Technical Support Mgr. OFS Optical Fiber Division 508-347-8582 tirujo@ofsoptics.com 1 Copyright 2006 Fitel USA Corp., All rights reserved.

More information

Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications

Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications Author: David Kozischek Marketing Manager, Data Center Applications Corning Optical Communications Systems engineers at Corning are

More information

Anixter Standards Reference Guide

Anixter Standards Reference Guide Anixter: The Cabling System Experts Anixter is a leading global supplier of communications and security products, electrical and electronic wire and cable, fasteners and other small components. We help

More information

November 2010 IEEE 802.3

November 2010 IEEE 802.3 TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire Vice Chair, TIA TR-42 Vice Chair, TIA TR-42.7 November, 2010 Dallas, TX 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org TR-42:

More information

LAN Standards, News & Trends Update 2017 June 15, 2017

LAN Standards, News & Trends Update 2017 June 15, 2017 LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE

More information

1 of 5 12/31/2008 8:41 AM

1 of 5 12/31/2008 8:41 AM 1 of 5 12/31/2008 8:41 AM SAVE THIS EMAIL THIS Close All multimode fiber is not created equal By Robert Reid Bandwidth, reach, and cost are among the key factors you ll need to weigh. Multimode fiber cabling

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

Industry Standards Activity Overview

Industry Standards Activity Overview Industry Standards Activity Overview Most Recent Plenary Meeting: June 12-16, 2017 in Quebec City, QC, CAN Updated: July 7, 2017 TR-42.1 Commercial Building Cabling: TIA TSB-185 Environmental Classification

More information

Atras Network Communications

Atras Network Communications Atras Network Communications Guide to Information and Communications Technology (ICT) Standards developed and published by the Telecommunications Industry Association (TIA) The Telecommunications Industry

More information

November 2013 IEEE 802.3

November 2013 IEEE 802.3 TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire Vice Chair, TIA TR-42 Telecommunications Cabling Systems Engineering Committee November, 2013 Dallas, TX 1 Introduction to TIA Telecommunications Industry

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

FTTE Revisited for New Technologies

FTTE Revisited for New Technologies FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern

More information

Certification for 10G copper cabling

Certification for 10G copper cabling Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards

More information

Fiber Backbone Cabling in Buildings

Fiber Backbone Cabling in Buildings White Paper Fiber Backbone Cabling in Buildings www.commscope.com Contents Introduction 3 Backbone Cabling Speeds 3 Optical Fiber in the Backbone 4 b/s Optical Fiber Backbone 4 Migrating to 40 Gbps and

More information

Standards Update. by Paul Kish NORDX/CDT

Standards Update. by Paul Kish NORDX/CDT Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline

More information

Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"

Industry Standards in ICT Enabled Projects Reading and Applying the Fine Print Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland

More information

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on

More information

Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only

Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only 1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda

More information

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications

More information

Insuring 40/100G Performance Multimode Fiber Bandwidth Testing & Array Solutions. Kevin Paschal Sr. Product Manager Enterprise Fiber Solutions

Insuring 40/100G Performance Multimode Fiber Bandwidth Testing & Array Solutions. Kevin Paschal Sr. Product Manager Enterprise Fiber Solutions Insuring 40/100G Performance Multimode Fiber Bandwidth Testing & Array Solutions Kevin Paschal Sr. Product Manager Enterprise Fiber Solutions Fiber Optics LAN Section Part of the Telecommunications Industry

More information

Structured Cabling Organizations and Standards

Structured Cabling Organizations and Standards since 1976 Structured Cabling Organizations and Standards Key cabling infrastructure standards ANSI/TIA ISO/IEC 724-746-5500 blackbox.com IEEE Introduction Table of Contents The importance of standards...

More information

How to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect

How to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect How to Decide on Optical Fibre Termination Options Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect Termination Choices Optical Fiber Cabling in Data Center Options available Traditional

More information

Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution

Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution 1 2 Agenda 1. Wirewerks introduction 2. Wirewerks products overview Data Center: Next Step TM Confidential Information Wirewerks

More information

STANDARDS REFERENCE GUIDE ANIXTER anixter.com. Products. Technology. Services. Delivered Globally.

STANDARDS REFERENCE GUIDE ANIXTER anixter.com. Products. Technology. Services. Delivered Globally. ANSI/TIA-568-C.0 ANSI/TIA-568-C.1 ANSI/TIA-568-C.2 ANSI/TIA-568-C.3 ANSI/TIA-569-D ANSI/TIA-606-B ANSI/TIA-607-C ANSI/TIA-862-A ANSI/TIA-942-A ANSI/TIA-1005-A ANSI/TIA-1179 ISO/IEC 11801 IEEE 802.3af IEEE

More information

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

History of Standards

History of Standards History of Standards From 10Mbps to 100Gbps Ethernet 12 th May 2014 Gautier Humbert, RCDD Business Development Manager Legrand East and Central Europe Agenda 1- Current standards and their structures

More information

Fiber or Copper Which Costs More? Daniel Harman Aug 2006

Fiber or Copper Which Costs More? Daniel Harman Aug 2006 Fiber or Copper Which Costs More? Daniel Harman Aug 2006 LAN Infrastructure Choices Hierarchical Star (Traditional) Centralized Fiber (Fiber to the Desk) FTTE (Fiber to the Telecom Enclosure) Why Compare

More information

Fiber to the Desk. Where Is It Cost-Effective Today? John Struhar, Chair TIA Fiber Optics LAN Section

Fiber to the Desk. Where Is It Cost-Effective Today? John Struhar, Chair TIA Fiber Optics LAN Section Fiber to the Desk Where Is It Cost-Effective Today? John Struhar, Chair TIA Fiber Optics LAN Section jmsjr1@att.net BICSI Fall Conference Nashville, Tennessee 20 August 2003 Fiber to the Desk JS Copyright

More information

Fiber in Data Centers What s Next? Srinivasan B, RCDD

Fiber in Data Centers What s Next? Srinivasan B, RCDD Fiber in Data Centers What s Next? Srinivasan B, RCDD Hubbell Fiber Systems 10G / 40G / 100G / 400G Standards, Applications and Practices Agenda Part 1: Current Technologies Standards Review IEEE 802.3:

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications

Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications David Kozischek, Market Manager Enterprise Networks, Corning Optical Communications Systems engineers at Corning

More information

Data Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems

Data Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems Data Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems John Struhar, Director Fiber Structured Cabling System Solutions, Ortronics Chairman, TIA Fiber Optics LAN Section (fols.org)

More information

The following pages contain a guide for the installation

The following pages contain a guide for the installation INDEX The goal of this section is to illustrate how Siemon Company products can be used to support some of the most popular and emerging networks on the market. Section Contents 100Base-T....................................

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India Enterprise Network Test Strategies for Network Availability and Performance A Sitaramaiah Director Fluke Networks India 1 Why is Enterprise Network Testing becoming increasingly important? IT is increasingly

More information

Everything you wanted to know about cabling, but were afraid to ask

Everything you wanted to know about cabling, but were afraid to ask Everything you wanted to know about cabling, but were afraid to ask Join the teleconference To receive a call back, click Communicate/Teleconference/Join Teleconference. In the pop-up window, enter your

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek-etlsemko.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton 2222 222nd St. SE Bothell,

More information

Appendix 1 to the R&Mfreenet Warranty Program

Appendix 1 to the R&Mfreenet Warranty Program Appendix 1 to the R&Mfreenet Warranty Program 1 R&M Certification Process The R&Mfreenet certification process is three pillars: a) Adherence to applicable standards, both for products and installations;

More information

DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005

DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005 DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005 Mike Gilmore Managing Director, e-ready Building Convenor CENELEC TC215 WG1 Mike Gilmore Standards Activities Member JTC1 SC25 WG3: Generic

More information

Cabling a Data Center to TIA-942 Standard

Cabling a Data Center to TIA-942 Standard Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center

More information

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS

More information

Copper Cabling Standards

Copper Cabling Standards Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

Panduit Certified Installer. Fiber Certification Review

Panduit Certified Installer. Fiber Certification Review Panduit Certified Installer Fiber Certification Review 2 What does the cleave tool do? A. Breaks the glass cleanly B. Cuts the glass cleanly C. Scores the glass cleanly D. Shatters the glass cleanly Breaks

More information

NGBASE-T Cabling Requirements

NGBASE-T Cabling Requirements NGBASE-T Cabling Requirements Dr. T. C. Tan, DMTS, CommScope Labs B.Sc (Eng), DIC, PhD, CEng, FIET White paper www.commscope.com Contents Contents Contents 2 1.0 Introduction 3 2.0 IEEE 802.3 NGBASE-T

More information

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit NGEAB-T Use Cases Berlin, Germany February 2015 Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Scope Next Generation Enterprise Access BASE-T PHY Study Group to define use cases and deployment

More information

Siemon PON Fiber Cabling Solutions

Siemon PON Fiber Cabling Solutions Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility

More information

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Testing and deployment of direct attach and the impact of category 8 Thursday, 10 August 2017, 3:50-4:40 P.M. Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Overview Traditional

More information

HIGH DENSITY DATA CENTER CABLING GUIDE. Optics DACs Cables Cable Management Fiber TAPs Media Converters

HIGH DENSITY DATA CENTER CABLING GUIDE. Optics DACs Cables Cable Management Fiber TAPs Media Converters HIGH DENSITY DATA CENTER CABLING GUIDE Optics DACs Cables Cable Management Fiber TAPs Media Converters PROVIDING MTP CABLING SOLUTIONS FOR THE SMART DATA CENTER. APPROVED NETWORKS SETS THE STANDARD The

More information

MTP Outdoor Cabling System

MTP Outdoor Cabling System The AFL MTPE (MTP Elite) Low Loss outdoor cabling system offers a market leading, low loss, fast and efficient connection system for underground (UG) and outside plant applications. These assemblies offer

More information

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com A The urpose: stablish a generic telecommunications cabling standard that will support a multivendor environment nable the planning and installation of a structured cabling system for commercial buildings

More information

LC Connector. A High Density Fiber Optic Network Solution. Paul Kolesar Lucent Technologies, Bell Laboratories

LC Connector. A High Density Fiber Optic Network Solution. Paul Kolesar Lucent Technologies, Bell Laboratories A High Density Fiber Optic Network Solution Paul Kolesar Lucent Technologies, Bell Laboratories IEEE 802.3z Gigabit Ethernet March, 1997 Outline Design Background and Goals Product Family Overview Features

More information

Frequently Asked Questions (FAQs) Siemon 10G ip Solutions

Frequently Asked Questions (FAQs) Siemon 10G ip Solutions Frequently Asked Questions (FAQs) Siemon 10G ip Solutions The world of enterprise cabling is evolving rapidly. Emerging, high-bandwidth services and the adoption of higher speed Ethernet standards, like

More information

CODES, STANDARDS AND PUBLICATIONS UPDATE March 2015

CODES, STANDARDS AND PUBLICATIONS UPDATE March 2015 CODES, STANDARDS AND PUBLICATIONS UPDATE March 2015 Bob Hertling Supervising Communications Engineer RCDD, OSP RI Telecommunications Systems Contractor License #4848 PARSONS Rail and Transit Systems Division

More information

Trends in Testing Data Center Infrastructure. Ed Gastle VIAVI Solutions

Trends in Testing Data Center Infrastructure. Ed Gastle VIAVI Solutions Trends in Testing Data Center Infrastructure Ed Gastle VIAVI Solutions Agenda INTRODUCTION Modern Data Center Architecture Historically Enterprise has been a 3 tier topology Core, Aggregation, Access Cloud

More information

A New Standards-Based Structured Cabling System Architecture

A New Standards-Based Structured Cabling System Architecture A New Standards-Based Structured Cabling System Architecture Bringing High Performance Closer to the User TIA Fiber Optics LAN Section 2:00-3:30 PM EST 13 November 2006 John M. Struhar Marketing Manager

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

Traverse System Documentation. Installation and Commissioning Guide

Traverse System Documentation. Installation and Commissioning Guide Force10 Networks Inc. Traverse System Documentation Installation and Commissioning Guide Release TR3.2.2 Publication Date: April 2009 Document Number: 800-0002-TR322 Rev. A Copyright 2009 Force10 Networks,

More information

Fiber backbone cabling in buildings

Fiber backbone cabling in buildings White paper Fiber backbone cabling in buildings www.commscope.com 1 Contents Introduction 3 Backbone cabling speeds 3 Optical fiber in the backbone 3 10 Gbps optical fiber backbone 3 Migrating to 40 Gbps

More information

REFERENCE T3 R3 T2 R1 T1 R2 T4 R4 WHT GRN T2 R2 T3 R1 T1 R3 T4 R4 WHT

REFERENCE T3 R3 T2 R1 T1 R2 T4 R4 WHT GRN T2 R2 T3 R1 T1 R3 T4 R4 WHT P O L A R I Z A T I O N G L O S S A R Y & A L P H A N U M E R I C REFERENCE S Y S T E M A P P L I C A T I O N S C A B L I N G S T A N D A R D S 1 2 3 4 5 6 7 8 T3 R3 T2 R1 T1 R2 T4 R4 WHT GRN GRN WHT ORG

More information

10 Gigabit Ethernet and Future Cabling for Offices + Data Centres

10 Gigabit Ethernet and Future Cabling for Offices + Data Centres 10 Gigabit Ethernet and Future Cabling for Offices + Data Centres Presentation at Nexans Seminar Scandinavia, May 2006 Dr Alan Flatman Principal Consultant LAN Technologies Topics 1. 10 Gig over optical

More information

Trends in Data Centre

Trends in Data Centre Trends in Data Centre The impact on the IT infrastructure Thomas Ko Product Manager Market Situation Standards Update and Topology 40G and 100G Ethernet - Impact on IT Cabling Migration Options with Fiber

More information

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled. 27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

Telecommunications Structured Cabling Systems

Telecommunications Structured Cabling Systems Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

Passive Optical Networking

Passive Optical Networking Passive Optical Networking Greg Dawes Zhone Technologies Sr. Sales Engineer Fiber to the Room Workgroup Chair Fiber to the Room Workgroup Passive Optical Networking 101 Agenda What is Passive Optical Networking

More information

PANGEN SYSTEM WARRANTY. Warranty Guide

PANGEN SYSTEM WARRANTY. Warranty Guide PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &

More information

3 Chapter Introduction. 3.2 Copper Cable

3 Chapter Introduction. 3.2 Copper Cable 3 Chapter 3 3.1 Introduction The Network Media is the device that physically carries the data from computer to computer. The three major types of network media are: Copper Cable Fiber-Optic Cable Wireless

More information

Data Center Design and the ANSI/TIA-942 Standard

Data Center Design and the ANSI/TIA-942 Standard Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications

More information

BICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD

BICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD BICSI Northeast Regional Meeting June 17, Storrs CT Considerations in Data Center Design Thomas McNamara, RCDD AGENDA Purpose is to allow the ITS professional to be aware of the issues and therefore pose

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: Leviton Manufacturing Co. 417 Stone Drive St. Charles,

More information

MTP Cabling Overview. MTP Cabling System

MTP Cabling Overview. MTP Cabling System MTP cabling architectures utilise varying cable and patchcord configurations as defined in TIA-568-C.0-2. These cables vary by gender, fibre orientation and pair management. AFL manufactures a large and

More information

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels

More information

Design of the Physical Layer

Design of the Physical Layer Design of the Physical Layer Critical Choices for Today's Data Centres The Siemon Company: The partner of choice for your Global Data Centers Alberto Zucchinali RCDD Senior Technical Manager EMEA DC Solutions

More information

or go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS

or go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS GO SMALL or go home STANDARDS PAGE 17 WBMMF on the fast track NETWORK MANAGEMENT PAGE 31 Quicken

More information

Communication

Communication 27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and

More information

10 GB Ethernet: Copper or Fiber? Choosing the Right Media for the Application

10 GB Ethernet: Copper or Fiber? Choosing the Right Media for the Application 10 GB Ethernet: Copper or Fiber? Choosing the Right Media for the Application Outline Why 10 GB Ethernet? Current Standards Copper Choices Fiber Choices Comparison Summary Why 10 GB Ethernet? Aggregation

More information

Cisco 100GBASE QSFP-100G Modules

Cisco 100GBASE QSFP-100G Modules Data Sheet Cisco 100GBASE QSFP-100G Modules Product Overview The Cisco 100GBASE Quad Small Form-Factor Pluggable (QSFP) portfolio offers customers a wide variety of high-density and low-power 100 Gigabit

More information

Cisco 100GBASE QSFP-100G Modules

Cisco 100GBASE QSFP-100G Modules Data Sheet Cisco 100GBASE QSFP-100G Modules Product Overview The Cisco 100GBASE Quad Small Form-Factor Pluggable (QSFP) portfolio offers customers a wide variety of high-density and low-power 100 Gigabit

More information

PCS PATCH CORD SOLUTIONS PATCH CORD SOLUTIONS

PCS PATCH CORD SOLUTIONS PATCH CORD SOLUTIONS Structured Cabling Solutions PCS PATCH CORDS. HiPerlink 6 Colored Patch Cords- 35,36 HiPerlink 1000 Category 5e Colored Patch Cords- 35,36 Snap-in Icons 36 ScTP Category 5 Patch Cord 37 Category 5 Colored

More information

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett

Testing Considerations for Beyond 10Gigabit Ethernet. Erin Hallett Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices

More information

AMENDED FINAL REPORT FOR:

AMENDED FINAL REPORT FOR: 731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton Manufacturing Co. 417 Stone Drive

More information

How You Can Optimize Passive Optical LAN Through Structured Cabling

How You Can Optimize Passive Optical LAN Through Structured Cabling How You Can Optimize Passive Optical LAN Through Structured Cabling Author: Stephane Bourgeois Director Technology Strategy Table of Contents Overview 1 What is POLAN? 1, 2 Deploying a POLAN 2 The Benefits

More information

Introduction to Key Principles of Telecommunications Cabling

Introduction to Key Principles of Telecommunications Cabling Introduction to Key Principles of Telecommunications Cabling Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of

More information

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017. Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations

More information

Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks

Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Agenda New ISO/IEC 11801 Standard New Fibre standards and encoding methods Higher speeds,

More information

Power Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure

Power Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Increasing usage of Power over Ethernet (PoE) represents

More information

Leveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions

Leveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions Leveraging the Structured Cabling System for Security Applications Mark Dearing, RCDD Leviton Network Solutions Trends - Cable Category Mix Source: Leviton projections based on market growth rates Over

More information

Peter Sharp RCDD IBI Group

Peter Sharp RCDD IBI Group Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member

More information

AMP NETCONNECT XG FIBER SYSTEM

AMP NETCONNECT XG FIBER SYSTEM AMP NETCONNECT XG FIBER SYSTEM The Complete High-Performance, Cost-Effective Optical Fiber Premises Cabling Solution for Supporting the Emerging Ten Gigabit Networks von mit freundlicher Genehmigung von

More information

Structured Cabling Guidelines For The State Of Oregon

Structured Cabling Guidelines For The State Of Oregon Structured Cabling Guidelines For The State Of Oregon Compiled by; TABLE OF CONTENTS 1. INTRODUCTION 2 2. SPECIFICATIONS 4 3. SIX SUBSYSTEMS OF A STRUCTURED CABLING SYSTEM: 5 3.1. Building Entrance/Entrance

More information

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents

More information

Leaders in the Advancement of Multimode Fiber. Fiber Future and Beyond

Leaders in the Advancement of Multimode Fiber. Fiber Future and Beyond Leaders in the Advancement of Multimode Fiber Fiber Future and Beyond Major Milestones in the Advancement of Multimode Fiber (MMF) Transmission OM4 Signature Core Fiber Cabling TIA WBMMF ISO/IEC OM5 (WBMMF)

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

CERTIFICATION PLUS SM

CERTIFICATION PLUS SM CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation

More information