BICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD
|
|
- Mercy Cameron
- 5 years ago
- Views:
Transcription
1 BICSI Northeast Regional Meeting June 17, Storrs CT Considerations in Data Center Design Thomas McNamara, RCDD
2 AGENDA Purpose is to allow the ITS professional to be aware of the issues and therefore pose the right questions and seek the answers from the owner (I.T) during the design process. Participants are encouraged to share ideas on specific codes and standards that apply/don t apply and what their experiences have proven to work.
3 Codes and Standards There are specific Codes (NEC 250/392/645/800), Standards (ANSI/TIA/EIA-942) requirements and practices (BICSI and The Uptime Institute) that can apply. All of these factors will determine the ultimate costs and functionality of the Data Center ITS. Some of the design choices that need to be made are: Overhead vs. under-floor cable tray? Plenum vs. non-plenum cabling? Shielded vs. non-shielded cabling? Single-mode vs. multimode fiber Optic cabling and termination methods? Information Transport System (ITS) grounding (TMGB)?
4 ITS Infrastructure and Cabling Choices Overhead Tray vs. Under-floor?
5 Cable Tray Options
6 Underfloor Tray
7 Overhead Single-Tier
8 Overhead Multi-Tier
9 ITS Infrastructure and Cabling Choices Backbone cable distribution for ER, MDA, HDA and NOC?
10 ITS Infrastructure and Cabling Choices Server/Host/SAN Cabling Media (i.e. Copper Cat.5E and Lazer Optimized Fiber)
11 Main Distribution Frame Fiber Optic Distribution (Backbone) versus Copper UTP (Horizontal)
12 Data Center Room Adjacencies TR/Cabling for Offices, Labs and other Soft Support Areas
13 Cabling for Offices, Labs and Other Soft Support Areas Medium Data Center
14 Redundancy Requirements Early agreement on the Tier Level (TI,TII,TIII,TIV) is the most important factor in designing the facility Tier I - composed of a single path for power and cooling distribution, without redundant components, providing % availability. Tier II - composed of a single path for power and cooling distribution, with redundant components, providing % availability. Tier III - composed of multiple active power and cooling distribution paths, but only one path active, has redundant components, and is concurrently maintainable, providing % availability. Tier IV - composed of multiple active power and cooling distribution paths, has redundant components, and is fault tolerant, providing % availability.
15 Redundancy Requirements Decision will dictate the level of redundancy required, including Information Transport System Start at the beginning (ER) if redundancy is a requirement (typical today is Tier III/Tier IV Combination)
16 Entrance Room Separate ER for Multiple Carrier s Demarcation OK to combine ER and MDA if environment is more suitable If the system must be designed to T-IV, all services should be fed from multiple (redundant) network carrier components
17 Cabling Type Requirements per NEC Non-Plenum (PVC) versus Plenum-Rated (CMP) Cabling NEC Article 645 (NFPA) Computer Room Cabling The NEC is the governing document for the installation of electrical cable in all situations. Code permits non-plenum cable under a raised floor that meets certain conditions per Article of the NEC. This supersedes Article 800 which requires the use of Plenum-Rated cables in air handling spaces. In summary, Article describes certain HVAC and disconnect features that must be included in your computer room design in order for the Article to apply. Using Non-Plenum Cable Under a Raised Floor and Meeting Code There are provisions in the National Electric Code that clearly permit the installation of non-plenum cable under a raised floor. Even though the National Electric Code permits non-plenum cable under a raised floor under certain circumstances, the final decision on which cable can be used is up to the Authority Having Jurisdiction (AHJ) which should be contacted prior to writing a cabling RFP and seek written permission to use non-plenum communications cable under the raised floor.
18 ITS grounding per NEC/TIA Grounding requirements with regards to the Data Center Grid: Reference BICSI TDDM Chapter 8 Version11 (Grounding, Bonding and Protection ANSI J-STD-607-A (Commercial Building Grounding and Bonding) IEEE 1100 (Power and Grounding Sensitive Electronic Equipment) TIA 942 (Telecommunications Infrastructure Standard for Data Centers) NEC Article 250 / Parts A-G (System Grounding) Fundamental concept of grounding: The prevention of "objectionable current flow over the grounding conductors or grounding paths."
19 Horizontal Distribution Area IS Strategy: Are the network (Core & Distribution) electronics going to be centralized (MDA only)?
20 Horizontal Distribution Area Core (MDA) versus Distribution Switching: Edge Switch placed at each Row (HDA) Fiber Optic Backbone to MDA
21 Horizontal Distribution Area Horizontal (Edge) Server cabinet electronics: Edge Switch placed in each cabinet Fiber Optic Backbone to MDA
22 Horizontal Distribution Area So how does this effect the Horizontal Distribution Area (HDA)? Cable tray, cabling and wire-management will vary by degree (size & quantity) based on the strategy chosen by the IS designer.
23 Server Cabinet Distribution Fiber Optic versus Copper or combination? Decision based on server interface (1Gb) and future deployments (10G)? If the system must be designed to T-IV, should all servers be fed from multiple (redundant) network components? How does this effect the ITS cabling?
24 SAN/Hosts Connectivity SAN Protocol cabling requirements: SAN Area Fiber Optics (Cabinet-to-Cabinet Patching) vs. MDA Distribution? 50-Micron Multi-Mode Laser Optimized Fiber (LOF)?YES!! Category 6(A) / CAT 7 (STP) for 10G IP YES!! Connectivity for: iscsi; a protocol that allows clients (called initiators ) to send SCSI commands ( CDBs ) to SCSI storage devices ( targets ) on remote servers. It is a popular Storage Area Network (SAN) protocol, allowing organizations to consolidate storage into data center storage arrays while providing hosts (such as database and web servers) with the illusion of locally-attached disks.
25 Sample SAN Equipment Positioning Tool SSR Data Center - SAMPLE Link Loss Budget Calculations End-Point shown above has an estimated (MAX) db Link-Loss as follows: = SAN A 2 = LAN B 3 = SAN C 4 = SAN D = LAN E ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### R4 ### ### ### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### R4 6 = SAN F ### ### ### ### ### ### ### ### 7 = SAN G ### ### ### ### ### ### ### ### ### #### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 8 = LAN H 38 ### ### ### ### 19 9 = SAN I ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### R3 ### ### ### ### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### R3 10 = SAN J ### ### ### ### ### ### ### ### ### 11 = LAN K ### ### ### ### ### ### ### ### ### #### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 12 = SAN L 39 ### ### ### ### = SAN M ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### R2 ### ### ### ### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### R2 14 = LAN N ### ### ### ### ### ### ### ### ### 15 = SAN O ### ### ### ### ### ### ### ### ### #### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 16 = SAN P 40 ### ### ### ### 1 17 = LAN Q ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### R1 ### ### ### ### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### R1 18 = SAN R ### ### ### ### ### ### ### ### ### 19 = SAN S ### ### ### ### ### ### ### ### ### #### ### ### ### #### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 20 = LAN T ### ### ### ### 21 = SAN U ### ### ### ### 22 = SAN V ### ### ### ### 23 = LAN W ### ### ##### #### ### ### ### ### ### ### ### ### ### ### #### ### ### ### ### ### #### ### ### #### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 24 = SAN X ### ### 25 = SAN Y ### ### 26 = LAN Z KEY: ACTIVE SERVER CABINET ### ### ### ### ### ### ### ### ### ### ### ### ### 27 = SAN AA MDF 28 = SAN BB FUTURE SERVER CABINET 29 = LAN CC 30 = SAN HOST/TAPE/ETC General, Notes are as follows: 31 = SAN 32 = LAN SAN AREA (Brocade M6140 / 48000) Overall 10G Ethernet/SAN Spec allows for total 2.6dB using Laser Optimized (LO) 50um/125 cable ( nm VCSel). 33 = SAN 34 = SAN DCN CABINET 35 = LAN BC will require to goto ELO due to the number of connections and patch cables and BC must locate the SAN in the MDF (TBD). 36 = SAN ### FIBER - MTP/LC CASSETTE 37 = SAN (AREA) Each Cassette (MPO/LC) consumes.75db +.5 MPO: 1.25 db 38 = SAN (AREA) ### FIBER - MPO/MPO ADAPTERS Each Adapter Panel (MPO/MPO) in SAN area and MDF consumes.75db (MPO Mated Pai0.75 db 39 = SAN (AREA) The 12-Fiber Ribbon cable consumes.0011db per foot 850nm) Note: Based on EL0.001 db per foot 40 = SAN (AREA) ### LC - CONNECTOR (PATCHCORD) ### 50um ENHANCED LASER-OPTIMIZED (ELO) RIBBON CABLE NOTE: If BC does not locate SAN in MDF, to determine total channel (patch-thru), pick any two (2) SAN End-Points and add together NOTE: These calculations do not include Patch Cord Loss (Length), or equipment Gain
26 Sample Fiber Calculators SSR Example SSR FO Link Loss (TFM ).xls Siemon Company Online Tool Siemon Company - Fiber Loss Calculator ( ).xls
27 Questions and Follow-up Final Q&A Request for presentation attachments to
Cabling a Data Center to TIA-942 Standard
Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center
More informationData Center Design and the ANSI/TIA-942 Standard
Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationConflicts in Data Center Fiber Structured Cabling Standards
Conflicts in Data Center Fiber Structured Cabling Standards By Dave Fredricks, CABLExpress Data Center Infrastructure Architect Various telecommunications and data center (DC)-specific standards are commonly
More informationData Center Design and the ANSI/TIA-942 Standard
Data Center Design and the BICSI Regional Meeting Charleston, WV Rick Foster RCDD,TLT Communications Infrastructure Group April 20, 2006 Maurice Zetena Fiber Connect Standards TIA-942 NFPA-70 Article 645
More informationFTTE Revisited for New Technologies
FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationTrends in Data Centre
Trends in Data Centre The impact on the IT infrastructure Thomas Ko Product Manager Market Situation Standards Update and Topology 40G and 100G Ethernet - Impact on IT Cabling Migration Options with Fiber
More informationViable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ
Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationStandards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee
Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic
More informationOffice of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO
Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note
More informationApplication Note. Data Center Standards and Layouts
Application Note Data Center Standards and Layouts 1. Data Center Standards In earlier times, a room in which one or more servers, a telephone system and active network components were located was often
More informationWirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution
Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution 1 2 Agenda 1. Wirewerks introduction 2. Wirewerks products overview Data Center: Next Step TM Confidential Information Wirewerks
More informationThe Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures. Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress
The Impact of Emerging Data Rates on Layer One Fiber Cabling Infrastructures Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress 36 Years of Experience CABLExpress is a manufacturer of
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationCabling Infrastructure
Presented by: Jim McGlynn PE RCDD/LAN Specialist O Neal/Gaj A telecommunications and technology consulting firm that specializes in the hospitality industry. Program Discussion: Goals Technology Definitions
More informationCopper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only
1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda
More information(Data Center Networks & Cloud Computing Security)
BPSDC (Data Center Networks & Cloud Computing Security) Lecture 3 Data Center Standars Service Level Agreement 2 Building a Data Center is just a Start What is Service Level Agreement (SLA)? An official
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationFiber in Data Centers What s Next? Srinivasan B, RCDD
Fiber in Data Centers What s Next? Srinivasan B, RCDD Hubbell Fiber Systems 10G / 40G / 100G / 400G Standards, Applications and Practices Agenda Part 1: Current Technologies Standards Review IEEE 802.3:
More informationInstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 InstaPATCH Cu Solution Specification 2 Harness Assembly Design 3
More informationUsing Low DMD, Laser Optimized Multimode Fiber to Expand 10-Gigabit Network Design Options
Using Low DMD, Laser Optimized Multimode Fiber to Expand 10-Gigabit Network Design Options Lisa Huff Technical Manager, Advanced Design & Applications Berk-Tek, a Nexans Company Adam Murano Fiber Engineering
More informationData Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems
Data Centers & Storage Area Networks Trends in Fiber Optics & Cabling Systems John Struhar, Director Fiber Structured Cabling System Solutions, Ortronics Chairman, TIA Fiber Optics LAN Section (fols.org)
More informationDesign of the Physical Layer
Design of the Physical Layer Critical Choices for Today's Data Centres The Siemon Company: The partner of choice for your Global Data Centers Alberto Zucchinali RCDD Senior Technical Manager EMEA DC Solutions
More informationSECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION
SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction
More informationLAN Standards, News & Trends Update 2017 June 15, 2017
LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE
More informationHow to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect
How to Decide on Optical Fibre Termination Options Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect Termination Choices Optical Fiber Cabling in Data Center Options available Traditional
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationCables and Connectors
Module 2 Cables and Connectors Twisted Pair Two wires that carry the data signals (one conductor carries a positive signal; one carries a negative signal). Two wires are twisted to reduce the effects of
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationV-Built Custom Preconfigured Solutions
WWW.SIEMON.COM V-Built Custom Preconfigured Solutions 8 One Part Number, One Price Ready to Roll Available with any Siemon cabinet, rack or enclosure, Siemon s V-Built Custom Preconfigured Solutions are
More informationBICSI NxtGEN & Global Data Center Standards Update
BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee
More informationNZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers
Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on
More informationStructured Cabling Design for Large IT/Service Provider Data Centers
Structured Cabling Design for Large IT/Service Provider Data Centers Author: Dave Kozischek, Marketing Applications Manager, Data Center and In-Building Networks Introduction Structured cabling is defined
More informationTesting Considerations for Beyond 10Gigabit Ethernet. Erin Hallett
Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More informationOptical Fiber Premises Standards News & Trends
1 Optical Fiber Premises Standards News & Trends Herb Congdon Tyco Electronics Updated: October 2005 hvcongdon@tycoelectronics.com 2 IEEE Ten Gigabit Ethernet (10GBASE-F) Published as IEEE802.3ae in June
More informationOptical Fiber Networks: Industry. and New Options for Networks
Optical Fiber Networks: Industry Trends, Application Influences and New Options for Networks Herbert V Congdon II, PE Manager, Standards & Technology Tyco Electronics AMP NETCONNECT Solutions Preview Deciding
More informationBonding and grounding NETCONNECT copper cabling systems
White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding
More informationDATA CENTER SOLUTIONS TM. Fiber Flex
DATA CENTER SOLUTIONS TM Fiber Flex We help reach your mission-critical objectives!! Olabs develops superior products and solutions in close collaboration with our customers. Our fiber optic structured
More informationWHITE PAPER. The Three Principles of Data Center Infrastructure Design
WHITE PAPER The Three Principles of Data Center Infrastructure Design The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership
More informationDesign Guidelines for Facilities Construction:
Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,
More informationDivision 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationHistory of Standards
History of Standards From 10Mbps to 100Gbps Ethernet 12 th May 2014 Gautier Humbert, RCDD Business Development Manager Legrand East and Central Europe Agenda 1- Current standards and their structures
More informationCommunication
27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and
More informationE. Numbering and Labeling Pathway components. In general, pathway components are not labeled.
27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part
More informationStructured Cabling Design for Large IT/Service Provider Data Centres. Liang Dong Yuan, Technical Sales manager, CDCE
Structured Cabling Design for Large IT/Service Provider Data Centres Liang Dong Yuan, Technical Sales manager, CDCE Structured Cabling Design for Large IT/Service Provider DCs Outline Section Industry
More informationThe Riser as a Contract Document. Peter Sharp, RCDD
The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40
More informationDATA CENTER SYMPOSIUM
DATA CENTER SYMPOSIUM Dynamic Changes in Data Center Optic Transmissions & The Impact to Structured Fiber Cabling Rick Dallmann CABLExpress Years of Experience CABLExpress is a manufacturer of custom built
More informationBROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS
BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS
More informationWith the publication. Make the right connection: Bonding a shielded system. installation
Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being
More informationPhysical Layer V What does the physical layer provide?
SEMESTER 1 Chapter 8 Physical Layer V 4.0 90 Points 8.1.1 What does the physical layer provide? What are the four elements of delivering frames across the media? 8.1.2 What are the three basic forms of
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationBACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.
Structured Cabling Systems BACKBONE CABLING Bldg 3 Entrance Closet Telco Closet Bldg 2 Telco Closet Intermediate Cross Connect Main Cross Connect Backbone Cabling ER HC/FD UTP STP-A Optical Fiber HC/FD
More informationDr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant
Is Cable Balancing Efficient i Enough for EMI Mitigation in Data Centers? Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant What are You going to Learn? What are the potential sources
More informationThe following pages contain a guide for the installation
INDEX The goal of this section is to illustrate how Siemon Company products can be used to support some of the most popular and emerging networks on the market. Section Contents 100Base-T....................................
More informationPeter Sharp RCDD IBI Group
Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationPlug & Play Universal Low-Loss Systems A LANscape Pretium Solutions Product
Applications Data Center LAN/SAN Enterprise Building Backbone -to-the-desk Description Plug & Play Universal Systems are preterminated optical fiber cabling systems designed to dramatically improve performance
More informationA. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationFiber Backbone Cabling in Buildings
White Paper Fiber Backbone Cabling in Buildings www.commscope.com Contents Introduction 3 Backbone Cabling Speeds 3 Optical Fiber in the Backbone 4 b/s Optical Fiber Backbone 4 Migrating to 40 Gbps and
More informationInterconnection to MIX - Technical specifications
Interconnection to MIX - Technical specifications Pag. 1 di 9 DOCUMENT CODE : MIX-302E VERSION : 3.1 DEPARTMENT : TECHNICAL OFFICE STATUS : DEFINITIVE DOCUMENT DATE : 03/03/11 NUMBER OF PAGES : 9 RELEASED
More informationANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions
ANSI/BICSI-001-2009, Information Transport Systems Design Standard for K-12 Educational Institutions Terry W. Hochbein RCDD/NTS/OSP ATSR Architects/Engineers Forward PURPOSE This Standard specifies minimum
More information1 of 5 12/31/2008 8:41 AM
1 of 5 12/31/2008 8:41 AM SAVE THIS EMAIL THIS Close All multimode fiber is not created equal By Robert Reid Bandwidth, reach, and cost are among the key factors you ll need to weigh. Multimode fiber cabling
More informationOptical Fiber for Today s Premises Applications
Optical Fiber for Today s Premises Applications Tony Irujo Customer Technical Support Mgr. OFS Optical Fiber Division 508-347-8582 tirujo@ofsoptics.com 1 Copyright 2006 Fitel USA Corp., All rights reserved.
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationRequest for Proposal George West Independent School District ERate
Request for Proposal ERate 2015-2016 Infrastructure for New Wings at George West High School and George West Elementary School Due: March 9, 2015 2:00 PM Superintendent: Ty Sparks ERate 2015 RFP:, George
More informationNetwork Construction Guide Specification Telecommunications Infrastructure Standards V 2.6
Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12
More informationCOURSE CATALOG. anixter.com/au
2010 COURSE CATALOG Products. Technology. Services. Delivered Globally. anixter.com/au Anixter University Introduction...3 Colleges...4 12 Data Center College...4 7 Automation College...8 10 School of
More informationA Review of the National Electrical Code Articles that Affect Data Center Design By Leo Marsh, PE, RCDD JACOBS (CH2M)
A Review of the National Electrical Code Articles that Affect Data Center Design By Leo Marsh, PE, RCDD JACOBS (CH2M) Safety Moment Here are five quick tips to remember before leaving your house and while
More informationPassive Optical Networking
Passive Optical Networking Greg Dawes Zhone Technologies Sr. Sales Engineer Fiber to the Room Workgroup Chair Fiber to the Room Workgroup Passive Optical Networking 101 Agenda What is Passive Optical Networking
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More informationTarget Interface / Construction Compliance Inspection Checklist
TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data
More informationSYSTIMAX GigaSPEED Xpress Solution Design Guidelines
Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien
More informationSECTION COMMON WORK RESULTS FOR COMMUNICATIONS
PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationPN Telecommunications Infrastructure Standard for Data Centers Draft 2.0 July 9, 2003
0 NOTICE: PN--00 Telecommunications Infrastructure Standard for Data Centers Draft.0 July, 00 0 This contribution has been prepared to assist the TR- Standards Committee. It is offered to the Committee
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationSection 1.1: Networking Overview
Section 1.1: Networking Overview This section provides an introduction to networking. Students will become familiar with the following aspects of a network: Components of a network o Computers o Transmission
More informationDon t Get Left Behind: Cabling Designs You Can Trust to Support Speeds of 32G to 400G
Don t Get Left Behind: Cabling Designs You Can Trust to Support Speeds of G to 00G Dave Fredricks Data Center Infrastructure Architect #DATACENTERWORLD #CPEXPO CHANNELPARTNERSCONFERENCE.COM DATACENTERWORLD.COM
More informationCOMMON WORK RESULTS FOR COMMUNICATIONS
SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More informationData Center Cabling Guide
Data Center Cabling Guide Planning Your Data Center Version T A B L E O F C O N T E N T S P A G E Introduction Data Center Horizontal Cabling Topology Topology Number : Centralized with Cross-connect Topology
More informationDATA CENTER CABLING DESIGN FUNDAMENTALS
White Paper DATA CENTER CABLING DESIGN FUNDAMENTALS Telecommunications Cabling Infrastructure Requirements according the Availability Classes I-IV of Introduction With the completion by end of Q1 2016,
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationHow You Can Optimize Passive Optical LAN Through Structured Cabling
How You Can Optimize Passive Optical LAN Through Structured Cabling Author: Stephane Bourgeois Director Technology Strategy Table of Contents Overview 1 What is POLAN? 1, 2 Deploying a POLAN 2 The Benefits
More informationCabling for Data Centres. Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari
Cabling for Data Centres Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari Data Center Definition is a facility used to house computer systems and associated components, such as telecommunications
More information10G the Next Generation Structured Cabling. Technology Paper 002
Technology Paper 002 10G the Next Generation Structured Cabling Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationThe advantages of the 6-connector channel
APRIL 2007 The advantages of the 6-connector channel The advantage of sticking to standardised rules such as ISO11801 (that define the performance of the components, the performance of the whole cable
More informationAre Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk?
Are Conflicts in Data Center Fiber Optic Structured Cabling Standards Putting Your Organization at Risk? Rick Dallmann Senior Data Center Infrastructure Architect CABLExpress 36 Years of Experience CABLExpress
More informationAdvances in Fiber Tier 2 Enterprise & Data Center Testing
Advances in Fiber Tier 2 Enterprise & Data Center Testing As the volume of fibers deployed into enterprise increases significantly, fiber cabling advances like multi-fiber (MPO) connectors and interfaces
More informationOvercoming the Testing Challenges of 40G and Beyond. Eric Farst Channel Sales Manager
Overcoming the Testing Challenges of 40G and Beyond Eric Farst Channel Sales Manager Agenda Introduction Increased demand for speed & capacity in the Enterprise/Data Center How Enterprises/Data Centers
More informationUsing Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications
Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications David Kozischek, Market Manager Enterprise Networks, Corning Optical Communications Systems engineers at Corning
More informationFiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications
Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications Author: David Kozischek Marketing Manager, Data Center Applications Corning Optical Communications Systems engineers at Corning are
More information