1 Configuration Questions: 1 What equipment will be protected? Calculate using Table 1 What do I want the UPS to do? Shutdown server(s) interface? Provide extended battery (autonomy) runtime? 3 Where do I want the UPS installed? Desk side or rack mount? 4 Power quality at the site Office (series 5 9) or industrial (series 9) grade protection? 5 Determine power available on site Voltage, is it 08 40V or 10V? If 10V needs to be less than 1400 Watts and desk side UPS Limited amperage? 15A, 0A, 30A or 60A? p5 Flow Chart v14ppt Page 1 of 10 May, 007

2 All devices and UPS in One rack? es One to Two* or Two or Four** PDUs? es es If LPAR s or Web/SNMP connectivity (interface) required, select FC 934 If no LPAR s ensure p5 has #573 for serial communications P30 (No PDU) Fig 5,100W U IEC power cord kit /61 (L6-0) power cord or: (L6-30) power cord P30 Options: U Battery module P33 (One*Fig or two** Fig 4 9/7188 PDUs),700W U ; or, (if S11 or S5 rack) IEC power cord kit PDU to UPS power cord (L6-30) UPS input power cord P33 Options: U Battery module Toll-free IBM pre-sales support & application (US) option 1 No Calculate power draw, select UPS with watt rating higher than power draw P33 (No PDU) Fig 5,700W U IEC power cord kit /61 (L6-0) power cord or: (L6-30) power cord P33 Options: U Battery module Figures on Following Pages No One 9176 PDU? (Figure 3) Select from P30, P33, P64 or UPS The following texts describes various UPSs and the configuration (eg No PDU ) and features necessary for a proper configuration *Non-redundant ** Dual-Redundant P30 (One*Fig or two** Fig 4 9/7188 PDUs),100W U IEC power cord kit /61 (L6-0) power cord or: (L6-30) power cord PDU to UPS power cord P30 Options: U Battery module p5 Flow Chart v14ppt Page of 10 May, UPS Chart Updated May 07 No Go to Tower UPS Charts or Contact Eaton (Powerware) Opt 1 (US) P64 (One*Fig 6 or two** Fig 7 9/7188 PDUs) 4,00W 5U rail kit /1 (L6-30) power cord or 973 PDU to UPS power cord P64 Options: U Battery module rail kit 9188 & 7188 PDU NOTES: P30 & P33 ou will not use the 9/7188 PDU #66xx power cord, store for future use p5 Model Watts Qty , A A 4-way , , 55A core active mode & : #031, -4core Base CEC 1400 #03 & 060, 5-8core nd CEC 800 #041, 9-1 core 3rd CEC 400 #041 or 04, 13-16core 4th CEC p5 575 Max 41, p5 590 Max, p5 595 Max, A50, A50 -way U U , EX B H DS L L3, 3581-F L All D , CR D11, D TF3 0 Other Table 1 (One* Fig 6, two* Fig 7 or 8 or four** Fig 9 or 10 9/7188 PDUs) 4,500W 3U rail kit /1 (L6-30) power cord or 973 PDU to UPS power cord NOTE: The can support one (1) additional PDU Select one PDU to UPS power cord for second PDU Options: U Battery module rail kit TTL Watts

3 Table Attribute P30 P33 P64 Level of protection (Type/Series) 9 = Double conversion, 5 = line interactive Hot Swap Batteries Hot Swap Electronics - - Load Segments - No PDU supported, non-redundant No PDU supported, dual-redundant 4 Height U 5 3 Output Watts,100,700 4,00 4,500 Watts per U 1,050 1, ,500 Optional Extended Battery Modules (EBM) (#6640) Max: 4 (#6607) Max: 4 (#6641) Max: 4 (#6641) Max: 4 Optional X-Slot Web/SNMP Card for LPARs (934) Optional Env Monitoring Probe (1) (938) Optional 10V Convenience PDU (916) () (1) Requires FC 934 () Requires 9188, 7188 or 9176 to power 10V Convenience PDU p5 Flow Chart v14ppt Page 3 of 10 May, 007

4 Step 1: Determine your rack model: 7014-T4 = 4U 7014-S5 = 5U 7014-S11 = 11U PDUs can be installed in side pockets (4U only) or EIA space (all) The 5U and 11U racks support 9910-P33 UPS A minimum of one PDU will be included with each rack Choose the figure closest to your application PDU (side pocket) 4U (T4) PDU (side pocket) Model UPS Support by racks: T4 supports P30, P33, P64 and (Figure 1A) S5 supports P33 (Figure 1B) S11 supports P33 (Figure 1C) 5U (S5) PDU (side pocket) Device PDU (side pocket) 11U (S11) Device Device PDU (EIA space) PDU (EIA space) PDU (EIA space) UPS (varies) UPS (P33) UPS (P33) Figure 1A Figure 1B Figure 1C p5 Flow Chart v14ppt Page 4 of 10 May, 007

5 Battery (autonomy) runtimes Battery (Autonomy) Watt load Std Internal Batts +1 EBM + EBMs +3 EBMs +4 EBMs P30 (EBM #6640) 875 Watts 16 min W W W P33 (EBM #6607) 1350 W W P64 (EBM #6641) 1400 W W W W W (EBM #6641) 900 W W W W W W Sample Power draw (load) Runtime desired Watts Minutes = = UPS and EBM configuration: Sample Power draw (load) Runtime desired Watts Minutes = = UPS and EBM configuration: p5 Flow Chart v14ppt Page 5 of 10 May, 007

6 Each Figure shows a rack with a different quantity of PDUs (zero to four) and with various input power cord types for the P30 & P33 The Figures showing two PDUs are show in *Non- & **Dual-Redundant (two separate power sources) configurations The figures showing four PDUs are shown in Dual-Redundant configurations only Choose the figure closest to your application Figure One 9188 PDU: P30/P33 with one PDU *NON-REDUNDANT (not to scale) PDU 9188/ 7188 Connector Type: UTG (Burndy) connections) to 9188 C19/C0 PDU to UPS power cord 6, P30 or P33 30A UPS input power cord 975 L6-30P 8 0A UPS input power cord #9860 L6-0P 14 #9861 L6-0P 6 Or P30 or P33 Figure 3 One 9176 PDU: P30/P33 with 9851 with one PDU *NON-REDUNDANT (not to scale) Up to 6 Devices (power connections) to 5160 NOTE: If you want a 30A power cord, you must delete the 98xx from the UPS configuration, then select #9851 Then you must order #140 (14ft) or #141 (6ft) PDU 9176 L6-30P 53P1967 L6-30R #9851 consists of two parts and connects: 1) PDU to UPS (PN 53P1966) ) UPS input to PDU line cord (PN 53P1967) C19/C0 53P1966 P30 or P33 L6-30R L6-30P P30 or P33 p5 Flow Chart v14ppt Page 6 of 10 May, 007

7 Figure 4 Two 9/7188 PDUs: P30/P33 Figure 5 No PDU: P30/P33 with two PDU **DUAL-REDUNDANT (not to scale) with No PDU *NON-REDUNDANT (not to scale) connections) to 9/7188 PDU line cord C13 to C14 power cord Up to 9 Devices (power connections) to P33 Up to 4 power connections to P P30 or P33 P30 or P33 Figure 6 One 9188 PDU: P64 or Figure 7 Two 9/7188 PDUs: P64 or UPS input line cord types: #140 L6-30P #141 L6-30P #14 RS3750 #143 RS3750 #144 IEC309 P+N+G 3A #145 PDL #146 KP #147 PDL NZ with one PDU *NON-REDUNDANT connections) w/ 7188 See UPS input line cord types with two PDUs **DUAL-REDUNDANT PDU #1 powered by UPS PDU powered from utility (mains) connections) w/ 7188 PDU line cord 97/3 cord 97/3 cord P64 or P64 or p5 Flow Chart v14ppt Page 7 of 10 May, 007

8 Figure 8 Two 9/7188 PDUs: Figure 9 Four 9/7188 PDUs: with two PDUs *NON-REDUNDANT PDU #1 & powered by UPS 974 PDU #3 to UPS cord with four PDUs **DUAL-REDUNDANT PDUs #1 & #3 powered by UPS PDUs # & 4 powered by utility (mains) PDU #4 line cord See UPS input line cord types connections) to each PDU to UPS cord See UPS input line cord types connections) to each 7188 PDU line cord 97/3 cord 97/ 3 cord Figure 10 Two s: (requires 1x 97 or #6654 and 1x 974) #1 with two PDUs *REDUNDANT PDU powered by UPS with two PDUs *REDUNDANT PDU #1 powered by UPS See PDU input line cord types connections) to each 7188 See UPS input line cord types connections) to each 7188 PDU line cord 974 cord 97 or #6654 PDU to UPS cord p5 Flow Chart v14ppt Page 8 of 10 May, 007

9 Figure 11 NEMA L6-30 (P+G) 30A, 08V used with UPS input power cord 975, PDU to UPS power cord 97, 973, input power cable (15ft) and P64/ outlet; and, 9188 or 7188 rack PDUs NEMA L6-0 (P+G) 0A, 08V used with UPS input power cord #9860 and #9861 C13 connector- 10A rated (female) PDU, P30/P33/ UPS outlets Mating connector to server C14 connector- 10A rated (male) The inlet on most servers & options jumper cords C19 connector- 16A rated (female) P30/P33/ UPS outlet and UPS input power cord (975, 976) C0 connector- 16A rated (male) BladeCenter, some i5 devices and P30/P33 inlets Figure 1 FC 97, 973 & 6654 PDU to UPS power cord 14ft/4m, 4ft/1m Burndy to L6-30P Figure 13 FC 975 UPS input (mains) power cord 8ft L6-30P to IEC-30-C19 C19 Figure 14 FC 974 PDU to UPS power cord 6ft/18m Burndy to IEC-30-C0 C0 Figure 15 Table 4 Mains (input) Power Cord Plug & Receptacle Descriptions FC 976 UPS input (mains) power cord 4m IEC309 (P+N+G) 3A to IEC-30-C19 C19 Type 11 FC 9860, 9861 (NEMA L6-0) Type 1 FC 140, 141, 144, 146, 970, 971, , 6654 (NEMA L6-30) Type 40 FC 14, , R&S 3750 Type 46 (16A) FC 9871, 141 IEC309 P+N+G Type 46 (3A) FC 144, 1449, , IEC309 P+N+G Type 64 FC 9875 inmetro p5 Flow Chart v14ppt Page 9 of 10 May, 007

10 UPS Rear Panels P30 Figure 16 P33 Figure 17 P64 Figure 18 Figure 19 p5 Flow Chart v14ppt Page 10 of 10 May, 007

9910-UPS Rack Chart Updated Oct 05

9910-UPS Rack Chart Updated Oct 05 All devices and UPS in One rack? es One to Two* or Two or Four** 9188-7188 PDUs? es es If LPAR s or Web/SNMP connectivity (interface) required, select FC 934 If no LPAR s ensure p5 has #573 for serial

More information

Configuration Questions:

Configuration Questions: Configuration Questions: 1 What equipment will be protected? Calculate using Table 1 What do I want the UPS to do? Shutdown server(s) interface? Provide extended battery (autonomy) runtime? 3 Where do

More information

9910-UPS Rack Chart Updated March 08

9910-UPS Rack Chart Updated March 08 All devices and UPS in One rack? 7188 or 5889 PDUs? Qty: Zero to Ten es es E30 (No PDU, Fig 6) 2,100W 2U 9910-0243 rack specify code 9910-9860/61 (L6-20) or: 9910-2975 (L6-30) E30 Options: 9910-6644 2U

More information

9910-UPS Rack Chart (IEC309 16A) power cord

9910-UPS Rack Chart (IEC309 16A) power cord All devices and UPS in One rack? Zero to Two* or Two or Four** 7188 PDUs? Yes No No One 5161 PDU? (Figure 2) 9910-UPS Chart No Go to Tower UPS Charts or Contact Eaton (Powerware) +44 add number here i5

More information

Powerware P60/61

Powerware P60/61 ware 51405 9910 P60/61 Runtime and Rack Connections P60 & P61 Runtime and Rack Connections v5.ppt Battery Runtime Matrix Battery Runtime (in minutes)* Standard (Std) Watts Internal Batteries 1 EBM 2 EBMs

More information

eserver Integration

eserver Integration 9125 - eserver TOPICS Installation Startup Optional Features Help/Resources 9125 Prep - eserver rev April 01 Page 1 Obtain a copy of Powerware 9125 9910 Installation Guide for IBM Applications and Powerware

More information

Powerware 9125 (9910-E64) UPS Installation Guide for IBM Applications

Powerware 9125 (9910-E64) UPS Installation Guide for IBM Applications Powerware 9125 (9910-E64) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF

More information

Prestige - eserver Integration

Prestige - eserver Integration Prestige - eserver TOPICS Installation Startup Optional Features Help/Resources PrestPrep - eserver rev Apr 01 Page 1 Obtain a copy of Powerware Prestige User s Guide from URL noted: EP5 (21H1572) U33

More information

IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units. 10/9/ IBM Corporation

IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units. 10/9/ IBM Corporation IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units 10/9/2007 Agenda System x Options Program and PDU market overview What is a PDU? Why do you need an IBM DPI PDU? IBM DPI PDU offering

More information

Powerware 5125 (9910-P33) UPS Installation Guide for IBM Applications

Powerware 5125 (9910-P33) UPS Installation Guide for IBM Applications Powerware 5125 (9910-P33) UPS Installation Guide for IBM Applications IBM, pseries, AIX, xseries, AS/400, OS/400, and RS/6000 are registered trademarks and iseries, OpenPower, and i5/os are trademarks

More information

Powerware 5125 (9910-E33) UPS Installation Guide for IBM Applications

Powerware 5125 (9910-E33) UPS Installation Guide for IBM Applications Powerware 5125 (9910-E33) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF

More information

Axxium Pro - iseries (AS/400) Integration

Axxium Pro - iseries (AS/400) Integration Axxium Pro - iseries () TOPICS Preparation Installation Optional Features Help/Resources www.invensys-power.com/ibm-ups/9910solutions.html, ProStart - iseries Dec, 2000 Page 1 Step 1 - Turn Off Server

More information

Axxium Pro - iseries (AS/400) Integration

Axxium Pro - iseries (AS/400) Integration Axxium Pro - iseries (AS/400) TOPICS Installation Startup Optional Features Help/Resources www.invensys-power.com/ibm-ups/9910solutions.html, ProPrep - iseries Dec, 2000 Page 1 Obtain a copy of Axxium

More information

IBM 9910 UPSs for IBM iseries and pseries safeguard your equipment and data from power problems

IBM 9910 UPSs for IBM iseries and pseries safeguard your equipment and data from power problems Hardware Announcement April 20, 2004 IBM 9910 UPSs for IBM iseries and pseries safeguard your equipment and data from power problems Overview To meet the changing power protection needs of IBM servers,

More information

Powerware 9910-P11 and 9910-P16

Powerware 9910-P11 and 9910-P16 Powerware 9910-P11 and 9910-P16 High Performance High Reliability & Availability Flexible & Configurable Advanced Communications 2002 Eaton Corporation. All rights reserved. P11 and P16 Features Fourth-Generation

More information

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems IBM United States Announcement 108-068, dated January 29, 2008 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Key prerequisites...2 Description...2 Publications...

More information

Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications

Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF

More information

Powerware P64

Powerware P64 Powerware 91259 9910 - P64 High Performance High Reliability & Availability Flexible & Configurable Advanced Communications p64pres.ppt rev 4.16.04 1 P64 Features Double-conversion online High-power density

More information

eserver Integration

eserver Integration 9125 - eserver TOPICS Preparation Startup Optional Features Help/Resources 9125Install - iseries Dec, 2000 Page 1 Step 1 - Remove UPS equipment from Cartons UPS must be placed near the installation site

More information

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems IBM United States Hardware Announcement 111-139, dated July 26, 2011 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 3 Publications

More information

7014-T V, 30 or 60Amp, 3-Ph or 1-Ph

7014-T V, 30 or 60Amp, 3-Ph or 1-Ph 7311-D10: p570 I/O Drawer 200-240V Holds (1) or (2) D10 Drawers Max Drwr =.21KVA,.2KW,.683KBtu Drawer = 8.6Wx28Dx6.6H @37lbs. F/C 7311 = 2 Position Drawer Enclosure Enclosure = 4U 17.5Wx28Dx6.9H @86lbs.

More information

9910 P18. Advanced power protection for mission-critical System p, System x, Storage and Networking rack products and applications. P18.

9910 P18. Advanced power protection for mission-critical System p, System x, Storage and Networking rack products and applications. P18. 9910 P18 Advanced power protection for mission-critical System p, System x, Storage and Networking rack products and applications 2002 Eaton Corporation. All rights reserved. P18.ppt P18 snapshot High

More information

IBM 1U Switched and Monitored Power Distribution Units IBM System x at-a-glance guide

IBM 1U Switched and Monitored Power Distribution Units IBM System x at-a-glance guide IBM 1U Switched and Monitored Power Distribution Units IBM System x at-a-glance guide The IBM 1U Switched and Monitored Power Distribution Units (PDUs) make it quick and simple to deploy, protect, and

More information

Prestige - eserver Integration

Prestige - eserver Integration Prestige - eserver TOPICS Preparation Startup Optional Features Help/Resources PrestInstall - eserver rev Apr 01 Page 1 Step 1 - Remove UPS equipment from Cartons UPS must be placed near the installation

More information

QuickSpecs. HP Remote Monitoring Power Distribution Units. Overview

QuickSpecs. HP Remote Monitoring Power Distribution Units. Overview QuickSpecs Overview (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to make the most of circuit capacity

More information

IBM UPS5000 HV Uninterruptible Power Supply for IBM System x Product Guide

IBM UPS5000 HV Uninterruptible Power Supply for IBM System x Product Guide IBM UPS5000 HV Uninterruptible Power Supply for IBM System x Product Guide The IBM UPS5000 HV is a 5 KVA rack-mountable uninterruptible power supply (UPS) that utilizes advanced backup power technology

More information

Powerware P95

Powerware P95 Powerware 93059 9910 - P95 Reliable power with proven double conversion online technology p95pres.ppt Rev 15.04.04 1 P95 Features Double-conversion, online technology protects against the 9 power problems

More information

EATON Transformer Module

EATON Transformer Module www.eaton.com EATON Module Quick Start Standard Features When used with standard system, EATON Module provides isolated and Step-down 0/08/0 V AC outputs. Multiple Output receptacles: 0/08/0 V AC. 86-86000-0

More information

Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments

Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments Powerware 9140 Uninterruptible Power System Product Focus Superior de-centralized power protection for medium- and high-density rack environments Product Snapshot Features Protects mission-critical rackmount

More information

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview Overview You cannot control what you cannot monitor. The new brings state of the art management and control to rack mounted power distribution units (PDU) to prevent over provisioning of power from restricting

More information

Product Snapshot. The Powerware Uninterruptible Power System. Product Focus

Product Snapshot. The Powerware Uninterruptible Power System. Product Focus Powerware 9120 Uninterruptible Power System Product Focus Product Snapshot Power Rating: 700-3000VA Voltage: 120 and 230 Vac Frequency: 50/60 Hz (auto-sensing) Configuration: tower Features True double-conversion

More information

HP Rackmountable 3 Phase Uninterruptible Power Systems Overview

HP Rackmountable 3 Phase Uninterruptible Power Systems Overview Overview Crowded data centers and racks filled to capacity with storage devices, monitors, servers communications devices, and other equipment are driving the need for uninterruptible power with increased

More information

Product comparison. 700 VA 120V tower

Product comparison. 700 VA 120V tower Product comparison Eaton 9SX vs 9130 UPS comparison Combining reliable double-conversion topology, internal static bypass and an easy-to-read LCD menu display, the Eaton 9SX UPS provides the highly efficient

More information

Powerware Software Connectivity Service. > Powerware Software Suite ensures data integrity; free updates on

Powerware Software Connectivity Service. > Powerware Software Suite ensures data integrity; free updates on Powerware 9120 Features True double conversion online technology give you protection from all nine power problems Simple installation and operation Intuitive LCD screen provides realtime updates of UPS

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

HP Uninterruptible Power Supplies Overview

HP Uninterruptible Power Supplies Overview NOTE: Additional information on these and additional HP UPS products at: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html Description HP rack mountable UPSs, designed

More information

IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x Product Guide

IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x Product Guide IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x Product Guide The IBM 3000VA LCD 3U Rack uninterruptible power supply (UPS) delivers 2700 watts of power in only 3U of rack space, providing

More information

Rack- and Panel-Mount Power Distribution Units (PDUs)

Rack- and Panel-Mount Power Distribution Units (PDUs) Spec-00193 Cable and Power Management Power Distribution Units (PDUs) Rack- and Panel-Mount Power Distribution Units (PDUs) FEATURES Power on/off LED indicates whether power is available at the PDU External

More information

Retired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)

Retired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks) Overview The HP Monitored PDUs allow administrators and facility personnel to monitor current draw directly at the rack and per PDU. HP Monitored PDUs are available in both 1 phase and 3 phase and in single

More information

5125 Family Uninterruptible Power System

5125 Family Uninterruptible Power System Powerware series 5125 Family Uninterruptible Power System 5125 rackmount 5000 to 6000 VA Features Protects connected from common power anomalies including surges, sags, brownouts, and over-voltage Provides

More information

P/N Operation & Installation Manual Serial Control Transfer Switch Model TM-STS

P/N Operation & Installation Manual Serial Control Transfer Switch Model TM-STS P/N 92 53626 000-11 Operation & Installation Manual Serial Control Transfer Switch Model TM-STS 92 53626 000 Table of Contents 1.0 SCOPE 1 2.0 INTRODUCTION 1 3.0 SPECIFICATIONS 2 4.0 EQUIPMENT DESCRIPTION

More information

SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 14U Rack/Tower, 208/120V or 240/120V NEMA & C19 outlets

SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 14U Rack/Tower, 208/120V or 240/120V NEMA & C19 outlets SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 14U Rack/Tower, 208/120V or 240/120V NEMA & C19 outlets MODEL NUMBER: SU20KRT-1TF Description Tripp Lite SU20KRT-1TF 20,000VA / 20kVA / 18,000 watt

More information

HP PDU Best Practices

HP PDU Best Practices HP PDU Best Practices Abstract... 2 Introduction... 2 Product Highlights... 2 HP PDU Models Available... 2 Modular PDUs... 2 Modular PDUs... 3 Monitored PDUs... 3 HP Modular PDU Advantages... 4 HP Monitored

More information

BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets

BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets MODEL NUMBER: BCPRO1400 Highlights 1400VA / 1.4kVA tower 120V standby UPS Maintains AC output during power failures USB port, Front panel

More information

Product Snapshot. the Powerware Uninterruptible Power System. Double-conversion, online design offers superior reliability and protection

Product Snapshot. the Powerware Uninterruptible Power System. Double-conversion, online design offers superior reliability and protection Powerware 9125 Uninterruptible Power System Product Focus 700-6000 VA Powerware 9125 6000 VA Features Protects mission-critical applications from downtime, data loss and corruption, and process interruption

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

Powerware 9120 UPS. Product Snapshot. Features

Powerware 9120 UPS. Product Snapshot. Features Powerware 9120 UPS Features True double conversion online technology give you protection from all nine power problems Simple installation and operation Intuitive LCD screen provides realtime updates of

More information

Rack- and Panel-Mount Power Distribution Units (PDUs)

Rack- and Panel-Mount Power Distribution Units (PDUs) Spec-00193 Cable and Power Management Power Distribution Units (PDUs) Rack- and Panel-Mount Power Distribution Units (PDUs) FEATURES INDUSTRY STANDARDS UL/cUL 60950 listed UL 1449 (Surge protector models

More information

QuickSpecs. HP Basic Power Distribution Units (bpdu) Overview

QuickSpecs. HP Basic Power Distribution Units (bpdu) Overview Overview HP Basic PDUs are designed to provide reliable and cost effective power distribution for your HP and non-hp IT racks. Offering simple 0U and 1U installation options, HP Basic PDUs are available

More information

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview Overview You cannot control what you cannot monitor. The new brings state of the art management and control to rack mounted power distribution units (PDU) to prevent over provisioning of power from restricting

More information

BC Personal 120V 450VA 280W Standby UPS, Tower, USB port, 3 Outlets

BC Personal 120V 450VA 280W Standby UPS, Tower, USB port, 3 Outlets BC Personal 120V 450VA 280W Standby UPS, Tower, USB port, 3 Outlets MODEL NUMBER: BCPERS450 Highlights 450VA tower 120V standby UPS Maintains AC output during power failures USB port, Status LEDs NEMA

More information

SmartOnline V 6kVA 5.4kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial, Bypass Switch

SmartOnline V 6kVA 5.4kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial, Bypass Switch SmartOnline 200-240V 6kVA 5.4kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial, Bypass Switch MODEL NUMBER: SU6000RT4UHVG Highlights 6kVA / 6000VA / 5400W on-line

More information

XTREME POWER CONVERSION THE VALUE LEADER IN POWER PROTECTION

XTREME POWER CONVERSION THE VALUE LEADER IN POWER PROTECTION CONVERSION THE VALUE LEADER IN POWER PROTECTION Xtreme Power is a global manufacturer of power quality and data center solutions Xtreme Power manufactures UPS from 400VA to 40kVA Designs, engineers, and

More information

OmniSmart 230V 350VA 225W CE/IEC Medical Grade Line-Interactive UPS with Built-In Isolation Transformer

OmniSmart 230V 350VA 225W CE/IEC Medical Grade Line-Interactive UPS with Built-In Isolation Transformer OmniSmart 230V 350VA 225W CE/IEC 60601-1 Medical Grade Line-Interactive UPS with Built-In Isolation Transformer MODEL NUMBER: OMNIX350HG Highlights 350VA line interactive tower UPS Professional features

More information

QuickSpecs HP T750 UPS. Overview

QuickSpecs HP T750 UPS. Overview Overview Rated at 750 VA/500 Watts, the features a unique design and easy-to-configure front panel display. Ideal for desktop, workstation, or entry-level server environments, this Uninterruptible Power

More information

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview Overview You cannot control what you cannot monitor. The new brings state of the art management and control to rack mounted power distribution units (PDU) to prevent over provisioning of power from restricting

More information

SmartPro 120V 700VA 450W Line-Interactive Sine Wave UPS, Tower, 120 or 230V input, Network Card Options, USB, DB9

SmartPro 120V 700VA 450W Line-Interactive Sine Wave UPS, Tower, 120 or 230V input, Network Card Options, USB, DB9 SmartPro 120V 700VA 450W Line-Interactive Sine Wave UPS, Tower, 120 or 230V input, Network Card Options, USB, DB9 MODEL NUMBER: SMART700DV Highlights 700VA tower line interactive UPS Maintains 120V output

More information

Family Uninterruptible Power System (UPS) for RS/6000/pSeries IBM U.S. Sales Manual Revised: October 10, 2005.

Family Uninterruptible Power System (UPS) for RS/6000/pSeries IBM U.S. Sales Manual Revised: October 10, 2005. Page 1 of 39 Family 9910+01 Uninterruptible Power System (UPS) for RS/6000/pSeries IBM U.S. Sales Manual Revised: October 10, 2005. Table of contents Document options IBM U.S. Product Life Cycle Dates

More information

Eaton BladeUPS 12 60kW

Eaton BladeUPS 12 60kW Power Quality Solution for Data Centres Eaton BladeUPS 12 60kW The power quality solution that simply grows with your needs Delivering power reducing costs Two key trends have emerged in the data centre:

More information

SmartOnline 208 & 120V 5kVA 4.5kW Double- Conversion UPS, 6U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial

SmartOnline 208 & 120V 5kVA 4.5kW Double- Conversion UPS, 6U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial SmartOnline 208 & 120V 5kVA 4.5kW Double- Conversion UPS, 6U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial MODEL NUMBER: SU5000RT4UTF Highlights 5kVA / 5000VA / 4500 watt online double-conversion

More information

Tripp Lite PDUs POWER DISTRIBUTION UNITS. Reliable rack power distribution for high-density IT environments. Introduction 2-3.

Tripp Lite PDUs POWER DISTRIBUTION UNITS. Reliable rack power distribution for high-density IT environments. Introduction 2-3. POWER DISTRIBUTION UNITS Tripp Lite rack power distribution for high-density IT environments. Introduction 2-3 Basic 4 Metered 5 Monitored 6 Switched 7 ATS 8 Hot-Swap 8 INTRODUCTION Tripp Lite Rack increase

More information

SmartPro 230V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

SmartPro 230V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial SmartPro 230V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX500RT1U Highlights 500VA line interactive 1U rack/tower UPS 230V nominal output during brownouts

More information

Netfinity White Paper Netfinity Technology Center

Netfinity White Paper Netfinity Technology Center Netfinity White Paper Netfinity Technology Center Rack Storage Expansion Enclosure Planning Guide Abstract This paper is designed for use by Pre-Sales technical marketing representatives. This includes

More information

Powerstar PS3204rm2u True online 2KVA /1800W (19.7 deep)

Powerstar PS3204rm2u True online 2KVA /1800W (19.7 deep) Powerstar PS3204rm2u PS3204 tower (120V) 3.4 H x16.9 W x19.7 D 85 x 430 x 497mm Model upgrade from PS3200 (GXT2) and PS3203 (GXT3)- now using Liebert GXT4 electronics Double Conversion true online type

More information

UPS Systems With functionality, flexibility, and ease of installation at top of mind, V7 UPS systems are designed with high grade durable components

UPS Systems With functionality, flexibility, and ease of installation at top of mind, V7 UPS systems are designed with high grade durable components UPS Systems With functionality, flexibility, and ease of installation at top of mind, V7 UPS systems are designed with high grade durable components and materials. Rigorous load and performance testing

More information

Metered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord

Metered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord Metered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord APC Metered Rack PDU, Input: 208V 3PH, Input Connections: NEMA L21-20P, Cord Length: 10 feet ( 3.05 meters ), Output: 208V,

More information

QuickSpecs. Compaq Uninterruptible Power Systems M ODELS

QuickSpecs. Compaq Uninterruptible Power Systems M ODELS M ODELS Rack-Mountable UPS Models 242704-001 242705-001 h-na 242705-003 Tower UPS Models 295372-B21 242688-001 242688-003 242688-005 T2400h-NA 242688-007 OVERVIEW Compaq UPS Products Compaq has developed

More information

Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments

Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments Powerware 9140 Uninterruptible Power System Product Focus Superior de-centralized power protection for medium- and high-density rack environments Product Snapshot Power Rating: Nominal Input Voltage: Nominal

More information

SmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch

SmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch SmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch MODEL NUMBER: SU20KRT-1TF Highlights 20kVA / 20,000VA / 18,000W on-line double-conversion

More information

UPS series PROTECT C. / C.R. Double conversion UPS with true sine wave - output

UPS series PROTECT C. / C.R. Double conversion UPS with true sine wave - output UPS series PROTECT C. / C.R Double conversion UPS with true sine wave - output PROTECT C. / C.R 2 nd generation Double - Conversion UPS with True Sine Wave - Output 10000 VA 6000 VA 3000 VA 2000 VA 1000

More information

SmartPro 230V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

SmartPro 230V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial SmartPro 230V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1500XLRT2U Highlights 1.5kVA / 1500VA / 1350W line interactive 2U

More information

SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial

SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial MODEL NUMBER: SU3000RTXL3UHV Highlights 3000VA / 3kVA / 2400 watt on-line double-conversion

More information

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems IBM Latin America Hardware Announcement LG10-0100, dated May 18, 2010 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 2 Product

More information

StorNext M440 Site Planning Guide

StorNext M440 Site Planning Guide StorNext M440 Contents StorNext M440 Site Planning Guide Included with Your StorNext M440... 1 Professional Installation Requirements. 2 Site Requirements... 2 Shipping Information... 3 StorNext M440 System

More information

IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Product Guide

IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Product Guide IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Product Guide Did you know? Unlike other competing UPS topologies, the IBM 11000VA UPS features online double-conversion technology to fully protect

More information

T1000 G2 and T1500 G2 1. Battery Compartment 1. Battery Compartment 2. LED display 2. LED display HP T1500 UPS INTL HP T1500 UPS JPN/TWN

T1000 G2 and T1500 G2 1. Battery Compartment 1. Battery Compartment 2. LED display 2. LED display HP T1500 UPS INTL HP T1500 UPS JPN/TWN Overview The Tower UPS "G2" models are the next generation HP tower UPSs with USB support. The new models are the UPS T1000 G2, T1500 G2 and R/T2200 G2 respectively. These new UPSs are designed to provide

More information

SmartOnline V 3kVA 2.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

SmartOnline V 3kVA 2.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial SmartOnline 200-240V 3kVA 2.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SUINT3000RTXL2U Description 3000VA / 3kVA / 2500 watt on-line, double-conversion

More information

SmartOnline V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

SmartOnline V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial SmartOnline 100-120V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU1000RTXL2UA Highlights 1000VA / 1kVA / 800 watt on-line double-conversion

More information

Metered Rack PDU Rack PDU, Metered, Zero U, 10A, 230V, (16) C13

Metered Rack PDU Rack PDU, Metered, Zero U, 10A, 230V, (16) C13 Metered Rack PDU Rack PDU, Metered, Zero U, 10A, 230V, (16) C13 APC Metered Rack PDU, Input: 230V, Input Connections: IEC-320 C14, Cord Length: 10 feet ( 3.05 meters ), Output: 230V, Output Connections:

More information

SmartPro LCD 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD display, USB, DB9 Serial

SmartPro LCD 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD display, USB, DB9 Serial SmartPro LCD 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD display, USB, DB9 Serial MODEL NUMBER: SMX1500LCD Highlights 1500VA / 1.5kVA 2U rack/tower 230V line interactive UPS with LCD display

More information

Reference Data Eaton 9PX 6000i Rack/Tower 3U UPS

Reference Data Eaton 9PX 6000i Rack/Tower 3U UPS Eaton 9PX 6000i Rack/Tower 3U UPS Eaton 9PX 6000i Energy efficient Online Double conversion UPS (up to 94% efficiency in online mode), 6000VA/5400W, Versatile Rack/Tower 3U, Parallel operation (power extension

More information

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems

IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems IBM United States Hardware Announcement 110-077, dated May 18, 2010 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 2 Product number

More information

OmniSmart 120V 1400VA 940W Line-Interactive UPS, Tower, USB port

OmniSmart 120V 1400VA 940W Line-Interactive UPS, Tower, USB port OmniSmart 120V 1400VA 940W Line-Interactive UPS, Tower, USB port MODEL NUMBER: OMNISMART1400 Highlights 1400VA / 1.4kVA tower 120V line interactive UPS Corrects brownouts and overvoltages from 75V to 147V

More information

Solutions Guide for Cisco UCS B and C Series Servers

Solutions Guide for Cisco UCS B and C Series Servers Solutions Guide for Cisco UCS B and C Series Servers The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a

More information

PW9170+ CTO Configuration Guide CTO Configuration Guide

PW9170+ CTO Configuration Guide CTO Configuration Guide CTO Configuration Guide Eaton 9170+ UPS 9170PCG January 1, 2018 Configuring Your PW9170+ UPS PW9170+ chassis s must be ordered using a Configure To Order (CTO) Number that reflects the cabinet style, isolation

More information

SmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial

SmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial SmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial MODEL NUMBER: SU2200RTXL2UA Highlights 2200VA / 2.2kVA / 1600 watt on-line double-conversion

More information

QuickSpecs. HPE Basic Power Distribution Units (PDU) Overview

QuickSpecs. HPE Basic Power Distribution Units (PDU) Overview Overview HPE Basic PDUs are designed to provide reliable and cost effective power distribution for your Hewlett Packard Enterprise and non-hewlett Packard Enterprise IT racks. Offering simple 0U and 1U

More information

Eaton 5125 UPS family

Eaton 5125 UPS family Powerware series Eaton 5125 UPS family 5125 tower model 1000 to 2200 VA 5125 rackmount 5000 to 6000 VA Features Protects connected equipment from common power anomalies including surges, sags, brownouts,

More information

OmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets

OmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets OmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets MODEL NUMBER: OMNIVSINT800 Highlights 800VA tower 230V line interactive UPS Corrects brownouts as low as 159V without using battery power

More information

SmartPro Dual Voltage Tower UPS System Maintains 120V nominal output with either 120V or 230V input power

SmartPro Dual Voltage Tower UPS System Maintains 120V nominal output with either 120V or 230V input power SmartPro Dual Voltage Tower UPS System Maintains 120V nominal output with either 120V or 230V input power Model #: SMART700DV 700VA line-interactive tower UPS system powers 120V devices from global power

More information

Making the switch: 9130 rackmount to 9PX

Making the switch: 9130 rackmount to 9PX Cross reference Making the switch: 9130 rackmount to 9PX The 9PX 700-3000 VA UPS models are here reliable, versatile, powerful, efficient power for IT equipment. If you re looking to upgrade your 9130

More information

Single phase UPS. Applications. Highlights. 1ph from 450 VA to 10 kva. Home Office Computers and peripherals Networks and servers Small data centers

Single phase UPS. Applications. Highlights. 1ph from 450 VA to 10 kva. Home Office Computers and peripherals Networks and servers Small data centers Single phase UPS 1ph from 450 VA to 10 kva Applications Home Office Computers and peripherals Networks and servers Small data centers Highlights User-friendly and Plug and Play Compact and noiseless Intuitive

More information

BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets

BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets MODEL NUMBER: BCPRO1400 Highlights 1400VA / 1.4kVA tower 120V standby UPS Maintains AC output during power failures USB port, Front panel

More information

Power distribution solutions for the ProLiant DL580 G2 server

Power distribution solutions for the ProLiant DL580 G2 server Power distribution solutions for the ProLiant DL580 G2 server Introduction... 2 Symbols in text... 2 Executive summary... 2 Glossary... 2 ProLiant DL580 G2 server power requirements... 3 Power distribution

More information

Intelligent-Remote Monitoring (3) Environmental Port (4) Power Outlet Level (5)

Intelligent-Remote Monitoring (3) Environmental Port (4) Power Outlet Level (5) Faster. Enclosure Power Distribution Units (PDUs) (continued) PDU Selection: Basic, with Local and Intelligent PDU mounted display option for local current or power monitoring, making phase balancing easier

More information

Powerware 5125 UPS. Features

Powerware 5125 UPS. Features Powerware 5125 UPS Features Advanced Battery Management Plus (ABM TM Plus) doubles battery service life Buck/Double Boost voltage regulation with pure sine wave output Load Segment control (separate receptacle

More information

Model #: SU6000RT4UHVG

Model #: SU6000RT4UHVG Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com Model #: SU6000RT4UHVG SmartOnline EZ-series UPS System - High efficiency, Hot-swappable,

More information

OmniVS 230V 1500VA 940W Line-Interactive UPS, Extended Run, Tower, USB port, C13 Outlets

OmniVS 230V 1500VA 940W Line-Interactive UPS, Extended Run, Tower, USB port, C13 Outlets OmniVS 230V 1500VA 940W Line-Interactive UPS, Extended Run, Tower, USB port, C13 Outlets MODEL NUMBER: OMNIVSINT1500XL Highlights 1500VA / 1.5kVA tower 230V line interactive extended-run UPS Corrects brownouts

More information

Acumentrics UPS Accessories List

Acumentrics UPS Accessories List Part Number ACG9010 ACG9012 ACG9013 ACG9019 ACG9021 ACG9022 ACG9200 ACG9201 ACG9202 ACG9203 ACG9205 ACG9206 ACG9208 ACG9209 ACG9210 ACG9211 ACG9214 ACG9215 ACG9216 ACG9217 ACG9218 Acumentrics UPS Accessories

More information

Eaton 5PX VA Rack-Tower Guide Specification

Eaton 5PX VA Rack-Tower Guide Specification Eaton 5PX 1000-3000VA Rack-Tower Guide Specification 1.1 Summary This specification shall define the electrical and mechanical characteristics and requirements for a line-interactive, single phase, uninterruptible

More information