Distribu(on System Coordina(on Using. Jim Cross, PE Planning Engineer Homer Electric Associa(on, Inc. Kenai, AK. WindMil / Light Table

Size: px
Start display at page:

Download "Distribu(on System Coordina(on Using. Jim Cross, PE Planning Engineer Homer Electric Associa(on, Inc. Kenai, AK. WindMil / Light Table"

Transcription

1 Distribu(on System Coordina(on Using Jim Cross, PE Planning Engineer Homer Electric Associa(on, Inc. Kenai, AK WindMil / Light Table

2 Outline Define topic What can WindMil do? What can LightTable do? What can WindMil + LightTable do? Case Study

3 Topic Designing or improving a scheme of over- current devices to protect your power system from the majority of expected fault condi(ons. Available technology versus u(lity preferences versus economics. Realize there is as much art to this as science. There is no such thing as perfect, and there are likely to be mul(ple schemes that will work.

4 System Coordina(on Guidelines Have a living document that outlines philosophy and goals of your distribu(on system protec(on. Make sure all affected departments (Engineering, Opera(ons, etc.) buy in on the guidelines. Remember the art versus science aspect. It s a guideline expect cases where you will have to make excep(ons.

5 Outline Define topic What can WindMil do? What can LightTable do? What can WindMil + LightTable do? Case Study

6 Terminology Device pair two protec(ve devices that are in series with each other. The upstream device, or the one closer to the sub is o]en referred to as the protected device. The downstream device, or the one farther from the sub is o]en referred to as the protec(ng device.

7 Terminology Coordina(on point intersec(on of two TCC curves that determines the limit of coordina(on between two protec(ve devices. If you are using fuses from a single vendor & family, vendors can o]en provide.

8 Limit of Coordina(on Chart PROTECTING DEVICE 65T 65E- vs 40T 40E- s 25T 25E- std 10T 10E- std 65T * * E- vs * * PROTEC TED DEVICE 40T * * * * E- s * * * * * * T * * * * * * E- std * * * * * * T * * * * * * * * 10E- std * * * * * * * * NOTES All fuses are S&C All values are available fault current in amps "75% Rule" states protected fuse minimum melt curve mul(plied by 0.75 (me factor

9 WindMil Tools Fault Current Calcula(ons Determine the levels of fault current that are available on various parts of your system. Model different fault types Maximum and minimum fault levels. One needs to set- up informa(on in the SOURCE elements for this to work properly. Good Z data for lines, XFMRs, etc. Calculate faults for each element down- line of the SOURCE element.

10 Seqng Up a SOURCE element Obtain fault data from your transmission provider.

11 Seqng Up a SOURCE element Since we have modeled the source at the transmission level, we can simply enter the fault data here.

12 Seqng Up a SOURCE element In the case where you do not have the substa(on XFMR modeled, you can enter it here. This will shi] the fault reference data to the XFMR low side.

13 Running Fault Current Analysis Turn on circuit(s) you want to analyze Select Fault Current and run. Radial analysis goes quickly, looped analysis can take a few minutes.

14 Fault Current Seqngs This is the less controversial set of op(ons. What to include, voltage op(ons, etc.

15 Fault Current Seqngs Minimum fault current method may be one of the most controversial discussed topics in our industry.

16 Minimum Fault Methods Two generally accepted methods: Constant Ohm Z (a.k.a. the 40 Ohm Rule) Percent (some reasonable % of the bolted fault (max) current Which one do I use, and what numbers???

17 Minimum Fault Methods This ques(on alone merits having a company- accepted set of coordina(on standards. Don t blindly follow 40 Ω Rule. Do what is best for your u(lity s unique situa(on.

18 Fault Current Calcula(ons Bench- marking With all of the new relays and meters that are capable of event / waveform capture, it s very easy to bench- mark model calcula(ons against real system faults. A single fault on a quiet day is bever than trying to correlate events and loca(ons from a storm event. Obtain addi(onal info from Opera(ons / crews (loca(on, cause, etc.)

19 Coordina(on Analysis This analysis will systema(cally go thru selected protec(ve devices and checks seqngs against a set of rules. There are some default industry standards built- in, but most are user configurable.

20 Coordina(on Analysis Seqngs Unbalanced or balanced voltage drop? Coordina(on points? (next slide) Recalculate coordina(on points for each itera(on of Coordina(on Analysis? Default is all device pairs. If using manually set coordina(on points, pick the lower op(on.

21 Seqng Coordina(on Points Manually This is where one defines the upline (protected) devices for each device in your Equipment List. If using Light Table devices, this is done automa(cally.

22 Coordina(on Analysis Results from voltage drop analysis are compared to the Con(nuous Current Seqngs for each protec(ve device. The Con(nuous Current Seqngs compare the current ra(ng of a device to the normal load current going through it. The mul(pliers are used to change the amount of load each device compares to. A lower mul(plier can be used to cushion for future load growth.

23 Coordina(on Analysis The Maximum Fault Test will compare the calculated maximum fault current at each device loca(on to the manufacturer s recommended maximum fault current ra(ng (as defined in LightTable) at that loca(on (mes a mul(plying factor. The Maximum Fault Test will fail if the calculated fault is greater than the fault ra(ng (mes the mul(plying factor.

24 Coordina(on Analysis The Minimum Pickup Test, performed during Coordina(on Analysis, will compare the calculated minimum fault current down- line from each device loca(on to the manufacturer s recommended minimum pickup ra(ng of the device (defined in LightTable) (mes a mul(plying factor. The Minimum Pickup Test will fail if the calculated minimum fault is less than the ra(ng (mes the mul(plying factor.

25 Coordina(on Analysis Seqngs The Coordina(on Test will check for correct coordina(on between each device and its upline device. The test method and required data are dependent on the type of device and the type of the protected (upline) device.

26 Outline Define topic What can WindMil do? What can LightTable do? What can WindMil + LightTable do? Case Study

27 Light Table A stand- alone product that allows engineers to look at the (me- current- characteris(c curves (TCC) for protec(ve devices w.r.t. each other, along with faults and device damage curves.

28 Light Table Overview This is the new look for Light Table. One- line TCC curves Curve Controls Dialog box

29 Light Table Overview This is where you set- up your Light Table devices: Device Seqngs Curve Characteris(cs Appearance in LT

30 Outline Define topic What can WindMil do? What can LightTable do? What can WindMil + LightTable do? Case Study

31 WindMil + Light Table Ability to move data between Fault Calcula(on Analysis in WindMil and TCC data in Light Table. Tie LightTable device data directly to devices as shown in WindMil.

32 WindMil + LightTable This is the dialog box for moving WindMil data into LightTable.

33 Outline Define topic What can WindMil do? What can LightTable do? What can WindMil + LightTable do? Case Study

34 Case Study - Considera(ons New technology / equipment Crew accessibility / (me to troubleshoot What types of faults does your system experience?

35 Case Study Verify new substa(on feeder relay seqng with exis(ng fusing scheme Verify fuse selec(on for new UG tap

36 Case Study Tasks Model the new feeder relay configura(on. Determine new fault currents Add new fuse for UG Modify exis(ng protec(ve devices? Test coordina(on to see if it works

37 Other Helpful Tasks Run a LUA script that will save the exis(ng device equipment off to the user tag field. One can then create a custom report that shows exis(ng equipment and proposed equipment. Create a custom toolbar for the fuse links. Create a color by custom mode to delineate OH from UG. Create a user- defined databox that shows available fault currents and the upstream or protected device. Record all changes into a project.

38 New Feeder Relay For fast & slow, phase and ground curves Don t forget to set up the general seqngs on the 1 st tab fault ra(ngs and reclose intervals

39 Case Study - Overview LUA script run before any changes are made. Project to record changes. UG colored ORANGE, OH is BLACK. Toolbar allows user to easily change devices. Max and min faults are visible, along w/ the upstream or protected device.

40 Coordina(on Analysis Report indicates some errors seqng up recloser & hi- side protec(on curves. Fuse fuse coordina(on looks fine!

41 LightTable Coordina(on Data exported from WindMil a]er running Fault Current Analysis.

42 Summary Individually, WindMil and LightTable offer several features and analysis tools to aide protec(on engineers w/ coordina(on of overcurrent protec(ve devices on a power system. The combina(on of the two products can provide even more features that make the task easier and faster.

43 References Cooper s Blue Book is the source of several of the Milso] default seqngs. All sorts of texts out there. For an interes(ng read on 40Ω Rule: hvp://tdworld.com/substa(ons/im- expec(ng- resistance

44 Ques(ons??? Jim Cross, PE Homer Electric Associa(on, Inc. (907)

External Tables How They Benefit YOU! Eric Jung

External Tables How They Benefit YOU! Eric Jung External Tables How They Benefit YOU! Eric Jung What are the External Tables? A database(s), outside of WindMil, but connected to WindMil Data Multiple database types allowed in 8.2 Oracle MS SQL Server

More information

Ten Things I Wish Someone Had Told Me Bryan Hill. Director of Opera9ons

Ten Things I Wish Someone Had Told Me Bryan Hill. Director of Opera9ons Ten Things I Wish Someone Had Told Me Bryan Hill Director of Opera9ons The 10 things- in no par9cular order 1 Try complex things in a simple model 2 Save oden- but only if you mean it! 3 The equipment

More information

Modelling of Rail Traction and Power Distribution Systems

Modelling of Rail Traction and Power Distribution Systems Modelling of Rail Traction and Power Distribution Systems Derek Smith Business Development Director Daniel Ting Senior Power Engineer ETAP Automation No. etrax TM Modelling of Rail Trac0on & Power Distribu0on

More information

Maximizing protection coordination with self-healing technology

Maximizing protection coordination with self-healing technology Supersedes December 2011 Daniel P. Roth, Distribution Automation Technical Manager, Eaton s Cooper Power Systems Abstract Much of the Smart Grid initiative includes the installation of new recloser and

More information

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric

More information

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation

More information

Power System Protection Training

Power System Protection Training Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of

More information

Cyber Security and Power System Communica4ons Essen4al Parts of a Smart Grid Infrastructure. Talal El Awar

Cyber Security and Power System Communica4ons Essen4al Parts of a Smart Grid Infrastructure. Talal El Awar Cyber Security and Power System Communica4ons Essen4al Parts of a Smart Grid Infrastructure Author: Goran N. Ericsson, Senior Member, IEEE Talal El Awar Submi.ed in Par3al Fulfillment of the Course Requirements

More information

RELT Reduced Energy Let Thru 2018

RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels

More information

Objec0ves. Gain understanding of what IDA Pro is and what it can do. Expose students to the tool GUI

Objec0ves. Gain understanding of what IDA Pro is and what it can do. Expose students to the tool GUI Intro to IDA Pro 31/15 Objec0ves Gain understanding of what IDA Pro is and what it can do Expose students to the tool GUI Discuss some of the important func

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

ASPEN Software - Introduction

ASPEN Software - Introduction ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical

More information

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50)

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50) Fusing Equipment Catalog Data CA132064EN Supersedes January 2014 (240-50) COOPER POWER SERIES Table of contents Attention....3 Eaton is in the process of updating part numbers and technical data due to

More information

Monitoring IPv6 Content Accessibility and Reachability. Contact: R. Guerin University of Pennsylvania

Monitoring IPv6 Content Accessibility and Reachability. Contact: R. Guerin University of Pennsylvania Monitoring IPv6 Content Accessibility and Reachability Contact: R. Guerin (guerin@ee.upenn.edu) University of Pennsylvania Outline Goals and scope So=ware overview Func@onality, performance, and requirements

More information

30-Cycle Rated Switchboards - Selectivity Tradeoffs

30-Cycle Rated Switchboards - Selectivity Tradeoffs 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted

More information

ThinManager and FactoryTalk View SE. John Ter8n; ESE, Inc.

ThinManager and FactoryTalk View SE. John Ter8n; ESE, Inc. ThinManager and FactoryTalk View SE John Ter8n; ESE, Inc. Who Am I John Ter8n Director of Manufacturing Informa8on Systems Who We Are Founded in 1981 Headquartered in Marshfield, Wisconsin 100% Employee-

More information

We will discuss two types of loss-of-potential (LOP) logic during this presentation:

We will discuss two types of loss-of-potential (LOP) logic during this presentation: 1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Supersedes May 2018 COOPER POWER SERIES General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series with low current primary protection devices such as a Bay-O-Net

More information

Documen$ng Mul$beam System Parameters in SIS

Documen$ng Mul$beam System Parameters in SIS Documen$ng Mul$beam System Parameters in SIS Mul$beam Advisory Commi3ee 2012-03- 21 SIS 3.8.3 Mul$beam Advisory Commi3ee March 21, 2012 1 Outline Expor$ng system configura$on parameters Screen grabs Installa$on

More information

GUJARAT TECHNOLOGICAL UNIVERSITY

GUJARAT TECHNOLOGICAL UNIVERSITY GUJARAT TECHNOLOGICAL UNIVERSITY Type of course: Engineering SUBJECT NAME: Switch Gear and Protection SUBJECT CODE: 2170908 Prerequisite: Electrical Power Systems II B.E. 7 th SEMESTER Rationale: This

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

Importing/Exporting Data in AdBase

Importing/Exporting Data in AdBase Importing/Exporting Data in AdBase Purpose of Presentation Provide an Overview of AdBase Utilities Which Allow:! Importing of Order Data or! Exporting of Order Data To or From the AdBase Core Database.

More information

Use JSL to Scrape Data from the Web and Predict Football Wins! William Baum Graduate Sta/s/cs Student University of New Hampshire

Use JSL to Scrape Data from the Web and Predict Football Wins! William Baum Graduate Sta/s/cs Student University of New Hampshire Use JSL to Scrape Data from the Web and Predict Football Wins! William Baum Graduate Sta/s/cs Student University of New Hampshire Just for Fun! I m an avid American football fan Sports sta/s/cs are easily

More information

CIGRE U.S. National Committee

CIGRE U.S. National Committee CIGRE U.S. National Committee 2014 Grid of the Future Symposium October 20, 2014 Houston, TX New Tools for Managing Smart Switching Devices Chris McCarthy, Jason Lombardo S&C Electric Company CWG/9416P

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Catalog Data CA132013EN Supersedes TD132002EN October 2014 COOPER POWER SERIES current-limiting backup fuse General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series

More information

DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT

DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT SCADA TO DG SITES DIGESTER MW AND MVAR INSTANTANEOUS READINGS FROM SEL 751 RELAY TRASK SUBSTATION LOADING DO NOT WANT TO FEED INTO

More information

New Tools for Managing Smart Switching Devices. C.A. MCCARTHY S&C Electric Company USA

New Tools for Managing Smart Switching Devices. C.A. MCCARTHY S&C Electric Company USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium New Tools for Managing Smart Switching Devices C.A. MCCARTHY S&C Electric Company USA

More information

What s New in Version 14 of ASPEN OneLiner/ Power Flow

What s New in Version 14 of ASPEN OneLiner/ Power Flow What s New in Version 14 of ASPEN OneLiner/ Power Flow The following are the new features in version 14 of ASPEN OneLiner/Power Flow. 1. Sharper and more vivid graphics on Windows 10. 2. New command to

More information

MAHR Webstore Tutorial POWERED BY

MAHR Webstore Tutorial POWERED BY MAHR Webstore Tutorial POWERED BY Sign In! Open a new browser window and go to the following link:! h3ps://marcomcentral.app.p;.com/lavigne/mahr/login.aspx?company_id=21708 If you have not registered,

More information

CORE STATES GROUP TRAINING SERIES BLUEBEAM EXPORTING CREATED BY: CSG IT CORE STATES GROUP

CORE STATES GROUP TRAINING SERIES BLUEBEAM EXPORTING CREATED BY: CSG IT CORE STATES GROUP CORE STATES GROUP TRAINING SERIES BLUEBEAM EXPORTING CREATED BY: CSG IT CORE STATES GROUP BLUEBEAM EXPORTING When working with PDF s there are a lot of +mes that you need to do something with that PDF

More information

ASPEN Software - Introduction

ASPEN Software - Introduction ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical

More information

Storwize in IT Environments Market Overview

Storwize in IT Environments Market Overview Storwize in IT Environments Market Overview Topic Challenges in Tradi,onal IT Environment Types of informa,on Storage systems required Storage for private clouds where tradi,onal IT is involved Storwize

More information

Mul$ple Upstream Interface Support for IGMP/MLD Proxy

Mul$ple Upstream Interface Support for IGMP/MLD Proxy 93 rd IETF, July 2015, Prague, Czech Republic Mul$ple Upstream Interface Support for dra

More information

ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng. Prof. Natalie Enright Jerger

ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng. Prof. Natalie Enright Jerger ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng Prof. Natalie Enright Jerger Announcements Feedback on your project proposals This week Scheduled extended 1 week Next week:

More information

DISTRIBUTION PROTECTION OVERVIEW

DISTRIBUTION PROTECTION OVERVIEW DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Mike Diedesch Avista Utilities Presented March th, 0 At the st Annual Hands-On Relay School Washington State University Pullman, Washington Table of Contents

More information

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY Fahrudin Mekic Ken Alloway Cleber Angelo Robert Goodin ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com.ken.alloway@us.abb.com

More information

WiAutoLink Frequently Asked Questions

WiAutoLink Frequently Asked Questions Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic

More information

PaintManager XI Quick Reference Guides for LIC

PaintManager XI Quick Reference Guides for LIC PaintManager XI Quick Reference Guides for LIC Quick Reference Guide Page Color Search. 2 Custom Formula from Scratch. 3 Custom Formula from Existing Color.. 4 Wildcard Search from the Dashboard.. 5 Wildcard

More information

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy Patrick Robinson Altelec Engineering Captured Arcing Fault Event Arc begins as phase A-C, 8ka peak, dies out then

More information

COSC 111: Computer Programming I. Dr. Bowen Hui University of Bri>sh Columbia Okanagan

COSC 111: Computer Programming I. Dr. Bowen Hui University of Bri>sh Columbia Okanagan COSC 111: Computer Programming I Dr. Bowen Hui University of Bri>sh Columbia Okanagan 1 First half of course SoEware examples From English to Java Template for building small programs Exposure to Java

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

Distribution Management System Open++ Opera v.3.3. User Manual

Distribution Management System Open++ Opera v.3.3. User Manual Distribution Management System Open++ Opera v.3.3 User Manual 1MRS 751464-MUM Issued: 31.12.1999 Version: D/29.8.2003 Program Revision: 3.3D We reserve the right to change data without prior notice. User

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION Fahrudin Mekic Zhenyuan Wang Vaibhav Donde Fang Yang James Stoupis ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com

More information

Document Databases: MongoDB

Document Databases: MongoDB NDBI040: Big Data Management and NoSQL Databases hp://www.ksi.mff.cuni.cz/~svoboda/courses/171-ndbi040/ Lecture 9 Document Databases: MongoDB Marn Svoboda svoboda@ksi.mff.cuni.cz 28. 11. 2017 Charles University

More information

Elas%c Load Balancing, Amazon CloudWatch, and Auto Scaling Sco) Linder

Elas%c Load Balancing, Amazon CloudWatch, and Auto Scaling Sco) Linder Elas%c Load Balancing, Amazon, and Auto Scaling Sco) Linder Overview Elas4c Load Balancing Features/Restric4ons Connec4on Types Listeners Configura4on Op4ons Auto Scaling Launch Configura4ons Scaling Types

More information

Transla'on, Protec'on, and Virtual Memory. 2/25/16 CS 152 Sec'on 6 Colin Schmidt

Transla'on, Protec'on, and Virtual Memory. 2/25/16 CS 152 Sec'on 6 Colin Schmidt Transla'on, Protec'on, and Virtual Memory 2/25/16 CS 152 Sec'on 6 Colin Schmidt Agenda Protec'on Transla'on Virtual Memory Lab 1 Feedback Ques'ons/Open-ended discussion Hand back Lab 1 Protec'on Why? Supervisor

More information

Developing an IDE4L Grid

Developing an IDE4L Grid Developing an IDE4L Grid Presenter: Antonino Riccobono, Ph.D. RWTH Aachen University Project Coordinator: Prof. Sami Repo Tampere University of Technology 5 th November 2014 SLIDE 2 Contents Overview of

More information

Spa$al Analysis and Modeling (GIST 4302/5302) Guofeng Cao Department of Geosciences Texas Tech University

Spa$al Analysis and Modeling (GIST 4302/5302) Guofeng Cao Department of Geosciences Texas Tech University Spa$al Analysis and Modeling (GIST 432/532) Guofeng Cao Department of Geosciences Texas Tech University Representa$on of Spa$al Data Representa$on of Spa$al Data Models Object- based model: treats the

More information

Con$nuous Integra$on Development Environment. Kovács Gábor

Con$nuous Integra$on Development Environment. Kovács Gábor Con$nuous Integra$on Development Environment Kovács Gábor kovacsg@tmit.bme.hu Before we start anything Select a language Set up conven$ons Select development tools Set up development environment Set up

More information

Component diagrams. Components Components are model elements that represent independent, interchangeable parts of a system.

Component diagrams. Components Components are model elements that represent independent, interchangeable parts of a system. Component diagrams Components Components are model elements that represent independent, interchangeable parts of a system. Components are more abstract than classes and can be considered to be stand- alone

More information

Best practices for making switchgear safer.

Best practices for making switchgear safer. Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

Object Oriented Design (OOD): The Concept

Object Oriented Design (OOD): The Concept Object Oriented Design (OOD): The Concept Objec,ves To explain how a so8ware design may be represented as a set of interac;ng objects that manage their own state and opera;ons 1 Topics covered Object Oriented

More information

DHCPv6 Failover Update

DHCPv6 Failover Update DHCPv6 Failover Update dhcp-ietf-dhc-dhcpv6-failover-design-04.txt Kim Kinnear kkinnear@cisco.com 2014-07- 23 (Former) DHCPv6 Failover Grand Plan Step 0: Redundancy considera6ons Published as RFC6853 Step

More information

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

UL 508A Industrial Control Panels Eaton. All Rights Reserved. UL 508A Industrial Control Panels Objectives Who is UL? UL508A Origin Current emphasis on UL508A What is the UL 508A Standard? Implementation of the Standard Component Selection Short Circuit Current Ratings

More information

Ge#ng Started with L Edit

Ge#ng Started with L Edit Ge#ng Started with L Edit L edit is a Layout Editor. It is a product of EDA stands for Electronic Design and Automa@on hbp://www.tanner.com/eda/ Layout Layout is essen@ally a drawing process. You are drawing

More information

Distribution Management System Open++ Opera v.3.2. User Manual

Distribution Management System Open++ Opera v.3.2. User Manual Distribution Management System Open++ Opera v.3.2 1MRS 751464-MUM Issued: 31.12.1999 Version: B/21.2.2001 Checked: MK Approved: PV Open++ Opera v.3.2 We reserve the right to change data without prior

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Common requirements for all ISPs

Common requirements for all ISPs Introduc)on Introduc)on In the transi)on state from IPv4 to IPv6, we should consider We cannot assign new global IPv4 addresses for new subscribers The network (par)cularly access NW) may have only IPv4

More information

Computer Projection Presentation Guide

Computer Projection Presentation Guide Computer Projection Presentation Guide 2007 HPS Midyear Topical Meeting Knoxville, TN 05/02/05 This Presentation Provides: Information about the computers used at the HPS meeting. Guidelines for developing

More information

Volume Rendering, pt 1. Hank Childs, University of Oregon

Volume Rendering, pt 1. Hank Childs, University of Oregon Volume Rendering, pt 1 Hank Childs, University of Oregon Announcements No class Friday Grad students: No project 8G s8ll need to do short presenta8ons Come to OH and let s chat Plo$ng Techniques X- rays

More information

Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications

Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications The 2Pro AC family of devices provide integrated overcurrent/ overvoltage/overtemperature

More information

Spectra RMS Circuit Breakers with microentelliguard Trip Units

Spectra RMS Circuit Breakers with microentelliguard Trip Units GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

TSC Schneider-PDI Agenda

TSC Schneider-PDI Agenda TSC Schneider-PDI Agenda General Electrical Power Layouts and Equipment Single Phase UPS s Three Phase UPS s Trends In Data Center Power Distribution Data Center Cooling Trends and Products Jim Tubbesing

More information

Instruction Manual for BE-SP3 Circuit. 10/21/07

Instruction Manual for BE-SP3 Circuit. 10/21/07 Page 1 of 54 Instruction Manual for BE-SP3 Circuit. 10/21/07 Page 1 Index: Page 2 BE-SP3 Circuit Specifications. Page 3-4 Intro to the BE-SP3. Page 5 Basics of serial to parallel. Page 6-7 ASCII Code.

More information

Version Changes

Version Changes Version 8.7.7 Changes Copyright Notice Copyright @1985-2018 Milsoft Utility Solutions, Inc. All rights reserved. Version 8.7.7 January 8, 2018 Trademarks Milsoft TM, WindMil TM, WindMilMap TM, and DisSPatch

More information

Founda'ons of Game AI

Founda'ons of Game AI Founda'ons of Game AI Level 3 Basic Movement Prof Alexiei Dingli 2D Movement 2D Movement 2D Movement 2D Movement 2D Movement Movement Character considered as a point 3 Axis (x,y,z) Y (Up) Z X Character

More information

BREAKER FAILURE PROTECTION

BREAKER FAILURE PROTECTION 0 th Annual HANDS-ON RELAY SCHOOL March 11-15, 201 REAKER FAILURE PROTECTION brent.c@relayapplication.com OUTLINE Protection System Failures and reaker Failures Protection versus Relaying Relay Schemes

More information

LightTable Auto-Update. A New Feature

LightTable Auto-Update. A New Feature LightTable Auto-Update A New Feature Overview: What does it take to add a curve? I want to show you a glimpse of the process to update our curve database on the MilsoE end I will introduce a new feature

More information

Call Toll Free: Website:

Call Toll Free: Website: 1 2 Introducing Road Commander Intellitec is launching a new product family, named Road Commander that will allow you to control your RV systems via a touch screen, control center, or smart phone, whether

More information

Button Code Kit. Assembly Instructions and User Guide. Single Button Code Entry System

Button Code Kit. Assembly Instructions and User Guide. Single Button Code Entry System Button Code Kit Single Button Code Entry System Assembly Instructions and User Guide Rev 1.0 December 2009 www.alan-parekh.com Copyright 2009 Alan Electronic Projects Inc. 1. Introduction... 4 1.1 Concept

More information

EE 868: Digital Techniques for Power System Protection. Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination

EE 868: Digital Techniques for Power System Protection. Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination EE 868: Digital Techniques for Power System Protection 1 Objective Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination Rama Gokaraju Department of Electrical & Computer Engineering

More information

Guide to the Enterprise Catalogue

Guide to the Enterprise Catalogue Guide to the Enterprise Catalogue Welcome to the new Enterprise online catalogue at the Mississauga Library System. We hope that you will find the catalogue easy to use. This handout should get you started.

More information

Basic PowerPoint Guidelines. Tips for Creating Great Presentations

Basic PowerPoint Guidelines. Tips for Creating Great Presentations Basic PowerPoint Guidelines Tips for Creating Great Presentations Fonts No more than 2 fonts per slide Serif fonts- fonts with curves - Times New Roman Sans Serif fonts- clean, block fonts- Arial Script-

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

Lecture 4: Build Systems, Tar, Character Strings

Lecture 4: Build Systems, Tar, Character Strings CIS 330:! / / / / (_) / / / / _/_/ / / / / / \/ / /_/ / `/ \/ / / / _/_// / / / / /_ / /_/ / / / / /> < / /_/ / / / / /_/ / / / /_/ / / / / / \ /_/ /_/_/_/ _ \,_/_/ /_/\,_/ \ /_/ \ //_/ /_/ Lecture 4:

More information

Welcome to the SIHO itransact portal.

Welcome to the SIHO itransact portal. Provider and Vendor Access Portal One stop access for your guide to utilizing SIHO s new itransact platform. Welcome to the SIHO itransact portal. Primary access codes will be given to key contacts at

More information

GETTING STARTED WITH NUODB

GETTING STARTED WITH NUODB February 15, 2017 GETTING STARTED WITH NUODB The elastic SQL database for hybrid cloud applications LOGISTICS AND INTRODUCTIONS 2 + All a&endees are muted + Submit ques3ons in the Q&A box on the right

More information

Vector Drive - Troubleshooting Guide

Vector Drive - Troubleshooting Guide Haas Technical Documentation Vector Drive - Troubleshooting Guide Scan code to get the latest version of this document Translation Available The Haas Vector drive is the source of power for the spindle

More information

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly

More information

Jeff Gooding Southern California Edison. Innovation at Southern California Edison

Jeff Gooding Southern California Edison. Innovation at Southern California Edison Jeff Gooding Southern California Edison Innovation at Southern California Edison Understand Cultural Risk Aversion to Innova

More information

3D Digital Design. SketchUp

3D Digital Design. SketchUp 3D Digital Design SketchUp 1 Overview of 3D Digital Design Skills A few basic skills in a design program will go a long way: 1. Orien

More information

AMP-TRAP Form 101 A15QS

AMP-TRAP Form 101 A15QS AMP-TRAP Form 0 AQS SEMICONUCTOR PROTECTION FUSES AQS Amp-trap Form 0 Semiconductor Protection fuses were designed for the specific protection of diodes and other semiconductor devices rated VAC/C. The

More information

Joint Radio Company: Making the spectrum and technology work for your business

Joint Radio Company: Making the spectrum and technology work for your business Adrian Grilli Secretary, Radio Spectrum Group, European U5lity Telecom Council Director, Federa5on of Communica5ons Services Managing Director, Joint Radio Company Ltd Cable Test.MPG JRC Spectrum.mp4 500Kv_switch.mpg

More information

Mobile speed enforcement and video surveillance

Mobile speed enforcement and video surveillance Mobile speed enforcement and video surveillance Market leading innovaon ProVida combines high quality digital surveillance with the Police approved speed measurement tool. For over 20 years the ProVida

More information

STA 4273H: Sta-s-cal Machine Learning

STA 4273H: Sta-s-cal Machine Learning STA 4273H: Sta-s-cal Machine Learning Russ Salakhutdinov Department of Statistics! rsalakhu@utstat.toronto.edu! h0p://www.cs.toronto.edu/~rsalakhu/ Lecture 3 Parametric Distribu>ons We want model the probability

More information

Explore commands on the ribbon Each ribbon tab has groups, and each group has a set of related commands.

Explore commands on the ribbon Each ribbon tab has groups, and each group has a set of related commands. Quick Start Guide Microsoft Excel 2013 looks different from previous versions, so we created this guide to help you minimize the learning curve. Add commands to the Quick Access Toolbar Keep favorite commands

More information

IntelliTeam II Automatic Restoration System

IntelliTeam II Automatic Restoration System No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer

More information

Memshield Overcurrent Protection Relay (AOR1B)

Memshield Overcurrent Protection Relay (AOR1B) (AOB) Multi-function Protection Device Local and remote trip indication AO-B type OCs are available with trip indications. Two types of trip indication function are available: single contact type and individual

More information

Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids

Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids Enrico Ragaini (ABB Low Voltage Products), Alexandre Oudalov (ABB Corporate Research), ISGT Europe 2012, Berlin Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids

More information

ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng. Prof. Natalie Enright Jerger

ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng. Prof. Natalie Enright Jerger ECE 1749H: Interconnec1on Networks for Parallel Computer Architectures: Rou1ng Prof. Natalie Enright Jerger Rou1ng Overview Discussion of topologies assumed ideal rou1ng In prac1ce Rou1ng algorithms are

More information

Digital Speed Controller User Manual

Digital Speed Controller User Manual Diesel Engine for Generators Digital Speed Controller User Manual (DSC-1000) Ver_1.0 Doosan Infracore 페이지 1 / 36 Contents 1. Product Overview and General Specification 1.1 Product Information 1.2 Product

More information

Smart Distribution Technology

Smart Distribution Technology Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications

More information

Version Changes

Version Changes Version 8.7.15 Changes Copyright Notice Copyright @1985-2018 Milsoft Utility Solutions, Inc. All rights reserved. Version 8.7.15 July 25, 2018 Trademarks Milsoft TM, WindMil TM, WindMilMap TM, and DisSPatch

More information

Oracle Report Manager - What are the Leading Prac6ces for It's Configura6on and U6liza6on? Session ID#: 14984

Oracle Report Manager - What are the Leading Prac6ces for It's Configura6on and U6liza6on? Session ID#: 14984 Oracle Report Manager - What are the Leading Prac6ces for It's Configura6on and U6liza6on? Session ID#: 14984 Prepared by: Lee Briggs Prac1ce Director, Financials Management REMINDER Check in on the COLLABORATE

More information

TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS

TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS Minimize Energy Let-Through. Maximize Equipment Protection. Commonly used on 34.5kV and lower systems to enhance protection, external -Limiting

More information