The Riser as a Contract Document. Peter Sharp, RCDD
|
|
- Vernon Morton
- 5 years ago
- Views:
Transcription
1 The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1
2 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40 years Member of BICSI, RCDD Institute of Engineering and Technology (IET) (UK), and TIA engineering TR42 standards committees Senior Telecommunications Consultant with IBI Group, Member firm of the IBI Group, (HQ in Toronto) Multi-disciplinary engineering gand architectural consulting practice. (3000 persons world wide) Responsibilities include Design and specification of communications, life safety, security and building management systems Systems integration for Data Centers. Major clients include 2 Governments, Nuclear power generation authorities, International border crossing agencies, Chartered banks, Insurance underwriters, and Transit authorities.
3 Why are we here? To think about.. The Riser as a Contract Document Idea What Components of a structured cabling system can be fully described on one schematic riser diagram. CAD drawing Different from current drawing practice and focuses on the cabling, not conduit or pathways. CAD Library of graphic elements described in detail. Examples Illustrate how the symbols are used to define and specify a complete cabling system. Included are the type and pair count of different cables and cable types, termination types, termination locations, cross connections and 3 patch-cords
4 What will we learn? Objectives Context of a construction contract Legal nature of a contract Establish need for clarity and completeness Identify key documents for structured cabling Identify use of LAYOUT PLANS Identify proper use of SPECIFICATIONS Identify use of SCHEMATIC RISER How to prepare a RICH DETAIL FORMAT (RDF) RISER SCHEMATIC 4
5 5 Part 2 CONTRACT DOCUMENTS
6 Context Owner, designer and contractor operate together in a world of contract law Owner + $$ + idea + designer = Contract Documents Contract Documents+ Contractor + materials = work results 6
7 Contract Documents General terms and conditions Technical specifications Drawings 7
8 Purpose and Proper Use of Contract Documents General terms and conditions 8 Establishes relationship between the Contractor and the Owner Details the do s and don ts of the work Sets up contract as Construction Management (CM) or General Contract (GC) CM or GC can affect way Data cabling is subcontracted
9 Purpose and Proper Use of Contract Documents Specifications Legally reinforces what is on the drawings Defines scope of work Defines material components Designer will use specifications to 9 Expand on scope of work Detail desired components Describes special execution of work
10 Purpose and Proper Use of Contract Documents Specification split by description of Work Does NOT separate work by trade Specific areas of interest to this subject 10 Division 26 Electrical rough in Communications pathways; supports cabling Division 27 Communications Structured cabling Division 28 Security/Safety Uses structured cabling
11 Division 27 - Communications General description of work What is included and excluded Look for Provide or Install or Furnish. Definitions of 11 Cable type and performance Connector type and performance Standards for execution/installation Testing and test reporting
12 Correct Use of Drawings - Layouts Communications layout drawings Outside plant shows conduits and site routing Inside plant Outlets positions and jack count Telecommunications rooms Conduit and tray (sometimes) Contractor responsible for 12 Take off - quantity
13 Correct Use of Drawings - Elevations Communications elevation drawings Communications rooms Identifies racking Identifies wall layouts Identifies cable routing 13
14 Correct Use of Drawings - Riser Communications Riser drawings 14 Describes the fixed link Details outside and inside cabling Details connector types Copper Optical fibre Details mounting locations Rack Wall
15 Three Parts to the Contract Documents Layout Describes placement/quantity of outlets Shows pathways Specifications Defines products and designer swants s Riser Describes the cabling infrastructure 15
16 Which Document is the Most Valuable Resource? 16
17 17 Part 3 THE RISER SCHEMATIC
18 Start with TIA 568.C.0 DISTRIBUTOR A (DA) HORIZONTAL CROSS-CONNECT FLOOR DISTRIBUTOR DISTRIBUTOR B (DB) INTERMEDIATE CROSS- CONNECT DISTRIBUTOR C (DC) MAIN CROSS-CONNECT 18
19 Traditional Riser Scheme Simple representation of cross connect Works for copper voice cabling Works for optical fibre Cannot mix cable types Does not show equipment Not good for detailing 19
20 Cross-Connect + Equipment New symbol needed to separate Backbone Equipment Distribution What kind of terminations? IDC? Patch panel? What kind of connections? Cross-connect? Interconnect? 20
21 Traditional + Equipment Drawing becomes crowded No space to add detail Suitable only for one cable type. Better approach needed 21
22 Part 4 DEVELOPING A NEW RISER SCHEMATIC 22
23 23 DISTRIBUTOR A: THE CROSS-CONNECT
24 1. Refine the Symbol Vertical lines become generic termination strips Identify with B Backbone E Equipment D Distribution Cross lines eliminated Horizontal lines represent cables 24
25 2. Show Cabling Back bone cables Distribution cables Indicate outlet jack 25
26 3. Add Cabling Terminations Open symbols represent RJ45 jacks 26
27 4. Add Patch Cords Solid symbols represent RJ45 plugs 27
28 5. Add Fibre Round symbols represent tfibre Open symbol = jack Solid symbol = plug 28
29 So far.. Horizontal copper cable terminated on RJ45 patch panel Backbone copper terminated on RJ45 patch panel Backbone fibre terminated on patch panel Copper patch cords between horizontal and backbone Copper equipment cords between horizontal and equipment Fibre equipment cords between equipment and backbone 29
30 6. Copper Terminations at 110/BIX ARROW symbol for 110/BIX punch-down Terminate TELEPHONE at 110/BIX IDC strip Terminate TELEPHONE backbone on 110/BIX IDC strip Show cross-connect connect between 110/BIX IDC strips 30
31 7. Separating Termination Locations Separate WALL and RACK terminations ti BW=Backbone/Wall BR=Backbone/Rack DW=Distribution/Wall DR=Distribution/Rack 31
32 8. Converged Services Crossover copper connection Link between RACK and WALL for backbone copper 32
33 9. Common Outlet ONE outlet for two services RED path for voice BLUE path for data 33
34 Summary: In the Telecom Room Symbolic representation for Copper cabling and terminations 110/BIX AND patch panel Optical fibre cabling and terminations Wall and rack mounting Equipment Patch/cross-connect cords Next up 34 Backbone cabling
35 35 BACKBONE CONNECTIONS
36 Revisit TIA 568.C.0 Note the Backbone connections between distributors 36
37 Distributor Connections Return to the same new starting ti point 37
38 Distributor Connections Expand the bubble 38
39 Distributors B and A 39
40 Backbone Cables Between Distributors 40
41 Step 1: Replace OLD symbol with NEW Compare OLD style with NEW style 41
42 Step 1: Replace OLD Symbol with NEW Note: Distributor B has Equipment but no Horizontal Distribution 42
43 Step 2: Extend the Backbone Between Distributor A and Distributor B 43
44 Cable Terminations are Detailed: Not Possible Using the Old Style 44
45 Better Organize the Diagram: Shift Elements to Prevent Symbol Interference 45
46 Clean Up: Tighten Symbols Group Backbone Cables Together; Apply Labels 46
47 Add Fibre to Backbone and Equipment (Symbols are Exaggerated for Clarity) 47
48 Add Legend: Component Details and Room Locations 48
49 Relating the Diagram to a Contract Document Cable: Types: defined Quantity: defined Termination: Types: defined Locations: defined Quantities and formats defined 49
50 Special Conditions: Overvoltage Protection 50
51 Special Conditions: Equipment Plug In (PBX) 51
52 Special Conditions: Equipment Plug In (PBX) 52
53 Symbols Used 53
54 Part 5 EXAMPLES 54
55 Sample: Full Riser Schematic 55
56 Focus Area: Entrance and Backbones 56
57 Building Entrance Copper Backbone 110 Terminations - Diverse Routing Building entrance Diverse backbone pathways 57
58 Focus: Distribution Terminations 58
59 Focus: Distribution Terminations Outlets in two work areas to common patch panel Pay phones run back to 110 in entrance room 59
60 EXAMPLE: Data Centre: Sample: 2 rows x 6 racks + 2 core Copper: Ethernet Cat 6A Rack to end of row End of row to core End of row to core Rack to end of row Admin point 1 60 Admin point 2
61 Data Centre: Sample: 2 rows x 6 racks + 2 core Fibre Channel + Ethernet Two more administration points Different End of row to Different core End of row to core Admin point 3 61 Admin point 4
62 Data centre: All cables + terminations: One diagram 62
63 Data centre: All cables + terminations: One diagram
64 Data Centre: Context 64
65 Data Centre: 4000 sf One drawing 100 Cabinets 3 levels of hierarchy Core Distribution Edge Parallel redundant backbone Ethernet fibre and Cat 6A distribution Fibre channel Two FC administration points 65
66 Part 6 CONCLUSION 66
67 Conclusion One drawing CAN represent entire system Cables AND terminations Rooms and enclosures Cross-connections and patch cords Equipment connections No duplications, no ambiguity Essential member of contract documents 67
68 The Riser as a Contract Document Peter Sharp, RCDD IBI Group peter.sharp@ibigroup.com 68
Peter Sharp RCDD IBI Group
Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationOffice of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO
Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationCabling Infrastructure
Presented by: Jim McGlynn PE RCDD/LAN Specialist O Neal/Gaj A telecommunications and technology consulting firm that specializes in the hospitality industry. Program Discussion: Goals Technology Definitions
More informationCopper Riser And Intrabuilding Cabling
Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationFTTE Revisited for New Technologies
FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern
More informationv2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.
Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations
More informationE. Numbering and Labeling Pathway components. In general, pathway components are not labeled.
27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part
More informationHow to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect
How to Decide on Optical Fibre Termination Options Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect Termination Choices Optical Fiber Cabling in Data Center Options available Traditional
More informationFiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications
Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications Author: David Kozischek Marketing Manager, Data Center Applications Corning Optical Communications Systems engineers at Corning are
More informationDesign Guidelines for Facilities Construction:
Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More informationThe advantages of the 6-connector channel
APRIL 2007 The advantages of the 6-connector channel The advantage of sticking to standardised rules such as ISO11801 (that define the performance of the components, the performance of the whole cable
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationSECTION COMMUNICATIONS BACKBONE CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED
More informationSECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION
SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationInstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 InstaPATCH Cu Solution Specification 2 Harness Assembly Design 3
More informationDIVISION 27 COMMUNICATIONS
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS 27 01 00 Operation and Maintenance of Communications Systems 27 01 10 Operation and Maintenance of Structured Cabling and Enclosures 27 01 20 Operation
More informationBACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.
Structured Cabling Systems BACKBONE CABLING Bldg 3 Entrance Closet Telco Closet Bldg 2 Telco Closet Intermediate Cross Connect Main Cross Connect Backbone Cabling ER HC/FD UTP STP-A Optical Fiber HC/FD
More informationCabling Infrastructure
Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More information2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS
NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated
More informationBusiness Customer Demarcation Information
Business Customer Demarcation Information The intent of this document is to clearly define Communications terminology and deployment with reference to business data customers and services. 1. What is a
More information(Data Center Networks & Cloud Computing Security)
BPSDC (Data Center Networks & Cloud Computing Security) Lecture 3 Data Center Standars Service Level Agreement 2 Building a Data Center is just a Start What is Service Level Agreement (SLA)? An official
More informationCopper Cabling Standards
Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals
More informationData Center Design and the ANSI/TIA-942 Standard
Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications
More informationLACCD IT Design Standards
LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage
More informationCabling a Data Center to TIA-942 Standard
Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center
More informationConflicts in Data Center Fiber Structured Cabling Standards
Conflicts in Data Center Fiber Structured Cabling Standards By Dave Fredricks, CABLExpress Data Center Infrastructure Architect Various telecommunications and data center (DC)-specific standards are commonly
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationPIONEERS OF The Structured Cabling Systems
ems t s y gs F n O i l S b EER red Ca N O I P uctu r t S The w w w. n c c - k s a. n e t Network Code Company (Ncc) is one of the Well Known Establishments & Companies Under M/s AlMuhkam Contracting Group
More informationTroubleshooting Networking Problems. Understanding your school s network
Troubleshooting Networking Problems Understanding your school s network by Stu Hasic Feb 2013 Typical Networks All schools use Ethernet Networks There s networks Typical School Networks Almost all schools
More informationStructured Cabling Guidelines
Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationNetwork+ Guide to Networks 7 th Edition
Network+ Guide to Networks 7 th Edition Chapter 4 Structured Cabling and Networking Elements 2016 Cengage Learning. May not be scanned, copied or duplicated, or posted to a publicly accessible website,
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationStandards-based Labelling: The Key to Effective Network Cabling Plan. Lin Huanyu Market Development, Regional Manager Brother International Singapore
Standards-based Labelling: The Key to Effective Network Cabling Plan Lin Huanyu Market Development, Regional Manager Brother International Singapore DATA CENTRE LANDSCAPE Digital Economy Datadriven population
More informationCommercialNetworking: Training
17.1 Table of Contents CommercialNetworking: Training 17 Commercial Networking Training Page No. Overview: 17.2 / Course Number 17.3 17.6 Intro to Belden Belden IBDN 305 17.3 Project Management Belden
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationSTRUCTURED CABLING WORKS SCHEDULE 1: GROUND FLOOR ITEM DESCRIPTION QTY UNIT RATE KSH
STRUCTURED CABLING WORKS SCHEDULE 1: GROUND FLOOR ITEM DESCRIPTION QTY UNIT RATE KSH Supply, Install Test and Commission the following Items: HORIZONTAL CABLING 1.1.01 Cat 6 UTP 4-pair cable 9,000 LM 1.1.02
More informationFiber or Copper Which Costs More? Daniel Harman Aug 2006
Fiber or Copper Which Costs More? Daniel Harman Aug 2006 LAN Infrastructure Choices Hierarchical Star (Traditional) Centralized Fiber (Fiber to the Desk) FTTE (Fiber to the Telecom Enclosure) Why Compare
More informationBICSI NxtGEN & Global Data Center Standards Update
BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee
More informationStandards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee
Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic
More informationMayhew Technology Solutions
Mayhew Technology Solutions Business Overview MTS offers design, engineering, and installation services for fiber optic, telecommunications, ISP, OSP, physical security, low voltage, and audio-visual systems.
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationA. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationField-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.
FM45 Connector Cat. 6 A IP20, 4P, TIA 568-A/B, 10x R815651 966704105 10 Stk. 090.7437 / ähnliche Abbildung Instruction manual Field-terminated connector with housing. Color housing: gray (RAL 7042). Color
More informationBROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS
BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS
More informationANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions
ANSI/BICSI-001-2009, Information Transport Systems Design Standard for K-12 Educational Institutions Terry W. Hochbein RCDD/NTS/OSP ATSR Architects/Engineers Forward PURPOSE This Standard specifies minimum
More informationFIBER OPTIC HARDWARE STEVE PAULOV
C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.
More information1 of 5 12/31/2008 8:41 AM
1 of 5 12/31/2008 8:41 AM SAVE THIS EMAIL THIS Close All multimode fiber is not created equal By Robert Reid Bandwidth, reach, and cost are among the key factors you ll need to weigh. Multimode fiber cabling
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationNetwork Construction Guide Specification Telecommunications Infrastructure Standards V 2.6
Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12
More informationSECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations
SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology
More informationQualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001
Qualified Partner Programme QPP Installation Practice Felice Guarna Wetzikon, Why installation quality Product performance must be preserved by an accurate installation Long term warranty requires design
More informationHow You Can Optimize Passive Optical LAN Through Structured Cabling
How You Can Optimize Passive Optical LAN Through Structured Cabling Author: Stephane Bourgeois Director Technology Strategy Table of Contents Overview 1 What is POLAN? 1, 2 Deploying a POLAN 2 The Benefits
More informationStandards Update. by Paul Kish NORDX/CDT
Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline
More information2G Engine Installation
Issue 3, April 2015 2G Engine Installation General The Redwood engine powers and communicates with Redwood gateways, sensors, and wall switches. The engine offers sophisticated controls that significantly
More informationJamey Calloway, RCDD Product Management Specialist Optical Cable Corporation
Testing and deployment of direct attach and the impact of category 8 Thursday, 10 August 2017, 3:50-4:40 P.M. Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Overview Traditional
More informationDesign of the Physical Layer
Design of the Physical Layer Critical Choices for Today's Data Centres The Siemon Company: The partner of choice for your Global Data Centers Alberto Zucchinali RCDD Senior Technical Manager EMEA DC Solutions
More informationDistributed ConvergeIT Systems. Lee Funnell EMEA Technical Manager
Distributed ConvergeIT Systems Lee Funnell EMEA Technical Manager Introduction Lee Funnell CTP, CDCDP EMEA Technical Manager British Standards Institute - Premises Cabling Experts Panel Data Centre Alliance
More informationLeveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions
Leveraging the Structured Cabling System for Security Applications Mark Dearing, RCDD Leviton Network Solutions Trends - Cable Category Mix Source: Leviton projections based on market growth rates Over
More informationCable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.
Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications Broadband High-Speed LAN Voice Robert Y. Faber Jr., RCDD/NTS Minimum Port Recommendations TIA/EIA-568-B.1 2 outlets
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationThe Quality Connection. LEONI QuickLine Class E Cabling Solution
The Quality Connection LEONI QuickLine Class E Cabling Solution QuickLine 2 Content Infrastructure & Datacom Solutions from a single source Shielded solution, keystone 4 Shielded solution, punch-down 5
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationPRODUCT CATALOGUE. Rev A HEXATRONIC.SE
PRODUCT CATALOGUE Rev. 2017-A HEXATRONIC.SE 1 Contents THE FLEXFIELD CONCEPT...4 RACKS AND SUBRACKS...6 DDF MODULES AND ACCESSORIES...8 ETHERNET MODULES AND ACCESSORIES... 16 ODF MODULES AND ACCESSORIES...
More informationA New Standards-Based Structured Cabling System Architecture
A New Standards-Based Structured Cabling System Architecture Bringing High Performance Closer to the User TIA Fiber Optics LAN Section 2:00-3:30 PM EST 13 November 2006 John M. Struhar Marketing Manager
More informationCertification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More informationWirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution
Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution 1 2 Agenda 1. Wirewerks introduction 2. Wirewerks products overview Data Center: Next Step TM Confidential Information Wirewerks
More informationData Center Consultants for the upcoming IIT Bombay HPC+BYOH Data Center
Data Center Consultants for the upcoming IIT Bombay HPC+BYOH Data Center IIT Bombay Computer Center invites Data Center Consultants to submit their bids for the contract for the design and project management
More informationa. Common Data Cabling 1) Structured cabling network - Schematic Diagram
SECTION 16740 STRUCTURED CABLING NETWORK (Fibre to the Office/Outlet) FTTO PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Contract 1. Drawings and general provisions of the Contract, including Conditions of Contract
More informationConnectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture
Connectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture Issue Document Status Date: Prepared: Checked: 6 Cat 6 U/UTP, Optical Fibre and MER/SER Guidelines 29/03/2018
More informationANSI/TIA-568-C Cat 6 Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability
More informationComputer Network Design Guide Existing Systems 1 / 6
COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should
More informationSYSTIMAX GigaSPEED Xpress Solution Design Guidelines
Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien
More informationWORLDSKILLS STANDARD SPECIFICATION
WORLDSKILLS STANDARD SPECIFICATION Skill 02 Information Network Cabling WSC2015_WSSS02 THE WORLDSKILLS STANDARDS SPECIFICATION (WSSS) GENERAL NOTES ON THE WSSS The WSSS specifies the knowledge, understanding
More informationHUBER+SUHNER DCCT Training
HUBER+SUHNER DCCT Training DCCT training The following topics are covered throughout the 2 course: Fiber optic fundamentals This is an optional section of the training which covers the basics about fiber
More informationStructured Cabling Design for Large IT/Service Provider Data Centers
Structured Cabling Design for Large IT/Service Provider Data Centers Author: Dave Kozischek, Marketing Applications Manager, Data Center and In-Building Networks Introduction Structured cabling is defined
More informationISO/IEC SC25 WG3. Who are they & what can they do for 802.3cg? Alan Flatman. Principal Consultant LAN Technologies.
1 ISO/IEC SC25 WG3 Who are they & what can they do for 802.3cg? Alan Flatman Principal Consultant LAN Technologies Email: a_flatman@tiscali.co.uk 2 Who are ISO/IEC SC25 WG3? Ø International systems group
More informationBonding and grounding NETCONNECT copper cabling systems
White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding
More informationWelcome. BICSI And BICSI Standards, An Overview. Presented by: Greg Sherry RCDD/NTS/WD BICSI European Region Director
Welcome BICSI And BICSI Standards, An Overview July 12 th 2007 Presented by: Greg Sherry RCDD/NTS/WD BICSI European Region Director Greg Sherry, Qualitas Ltd 1976 - Started in the IT industry Various roles
More informationQualified Partner Programme QPP. Voice Integration Felice Guarna
Qualified Partner Programme QPP Voice Integration Felice Guarna Easiest voice integration - with "R&Mfreenet" The worlds of voice and data transmission are increasingly growing together. Modern private
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More information19" TiRAX cabinet system. from page 3. 19" NETcell cabinet system from page 31. Open 19" racks from page 43
9" TiRAX cabinet system from page 9" NETcell cabinet system from page Open 9" racks from page Wall-mounting/stand-alone distribution systems from page 5 Wall-mounting enclosure systems from page 6 Air
More informationPANGEN SYSTEM WARRANTY. Warranty Guide
PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &
More informationAT&T Switched Ethernet Service SM
Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks
More informationCabling Solutions Data Center & Local Area Networks
Cabling Solutions Data Center & Local Area Networks R&M About us. «R&M is a leading provider of cabling solutions for high quality communication networks.» R&M (Reichle & De-Massari AG) has developed and
More informationHITEC 2003 Produced by Hospitality Financial and Technology Professionals
Infrastructure of a Hotel Dan Phillips Bob Stoutenburgh David Hostetter Presenters Dan Phillips Founding partner and COO of ITS Inc., Dan manages and organizes telecommunications and data projects for
More informationBICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD
BICSI Northeast Regional Meeting June 17, Storrs CT Considerations in Data Center Design Thomas McNamara, RCDD AGENDA Purpose is to allow the ITS professional to be aware of the issues and therefore pose
More informationDon t Get Left Behind: Cabling Designs You Can Trust to Support Speeds of 32G to 400G
Don t Get Left Behind: Cabling Designs You Can Trust to Support Speeds of G to 00G Dave Fredricks Data Center Infrastructure Architect #DATACENTERWORLD #CPEXPO CHANNELPARTNERSCONFERENCE.COM DATACENTERWORLD.COM
More informationData Cabling / Low Voltage Technology Specifications
P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall
More information