1 Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12 Springfield Public Schools R12 Springfield Public Schools R12

2 TABLE OF CONTENTS PREFACE DOCUMENT INTENT SPECIFICATION SECTIONS... 3 SECTION 1 GENERAL CONSTRUCTION 3 SECTION 2 SITE CABLING. 4 SECTION 3 GROUNDING AND BONDING FOR NETWORKS. 6 SECTION 4 TESTING. 7 SECTION 5 PART SPECIFICATIONS PREFACE The Network Construction Guide Specification is written for designers of R12 Network systems. It is intended to assist designers in developing project specifications that communicate R12 s requirements for the construction of Network, IP Cameras, and Phone systems at their facilities. The NCGS was developed from R12 s previous version of its telecommunications infrastructure standard specifications in use at that time. It has been updated to reflect the changes that have occurred since the previous version was published. This document will supersede any other document in the event of a conflict including construction documents and specs. 1.1 DOCUMENT INTENT R12 has developed the NCGS with the intent that its standards and practices are followed during the design and construction of Network, IP Camera, and Phone infrastructure. Each NCGS specification section has references, products, procedures, processes, and work descriptions/summaries that are common to all R12 cabling projects. This information is provided in specification format to serve as a guide to the Engineer/Designer in producing a BICSI-compliant specification that will meet the unique requirements of R12 cabling projects. The NCGS is intended to be a Master Specification. The products listed and other information included in each section is intended to be all-inclusive for any given project. 2

3 Unless otherwise stated, the information in the NCGS applies to both new construction and remodel projects. 1.2 SPECIFICATION SECTIONS The NCGS contains the following 5 specification sections: 1 General Construction of MDF/IDF Rooms 2 Plant Cabling 3 Grounding and Bonding for Networks 4 Testing 5 Part Specifications SECTION 1 GENERAL CONSTRUCTION OF MDF/IDF ROOMS REQUIREMENTS SPS Networking Dept will layout all MDF/IDF rooms for Data/Phone equipment and provide detailed drawings to Contractors. Contractors will install ladder tray, racks, wire management, patch panels, and fiber enclosures all provided by SPS. SPS Networking Dept will provide and install all networked switches and patch cables. A preconstruction trade meeting must be performed before any Data/Phone work is started with a representative from the SPS Networking Dept present. All Mdf/Idf room walls shall have an added layer of 3/4 plywood, B-C ext. grade 5. Plywood must be fire-retardant. Install the plywood horizontally on walls from 2-0 to 6-0 AFF from corner to corner. All walls shall be painted with a light-colored paint. All MDF and IDF telecommunication rooms shall have ladder type cable tray installed around the perimeter of the room and over Data/Phone racks designated by SPS Networking Dept. Suspended ceilings are not expected in Telecommunications rooms. Minimum ceiling height shall be 8-6. Doors shall be lockable, opening 90 or greater and 36 wide x 80 min height. Hinge doors to open outward unless corridor width will not accommodate out-swing without reducing egress. If door must swing in, then assure that MDF room size is increased to accommodate in-swinging door. Fire rating of doors and sprinkling of room shall be as required by code. Hardware: hinges, lockset, stop, kick plate and closer per R12 General Service Center Standards. Locking: Cylinder shall be General Service Center standard for MDF/IDF rooms. Structural Requirements of Telecommunications Rooms: The floor rating under distributed loading shall be greater than 100lbf/ft². 3

4 Mechanical Construction Requirements of telecommunication rooms: Provide ventilation and air conditioning that will maintain a temperature range of Fahrenheit Per BICSI Telecommunications Distributions Methods Manual. Relative humidity range should be 30% to 55% relative humidity Per BICSI Telecommunications Distributions Methods Manual. No mechanical equipment shall be installed on the plywood or impair the routing of telecommunication cables. It is not permissible to route any mechanical systems through the room, including HVAC ducts, plumbing, gas lines, air lines, clean outs, etc. that do not directly serve the telecommunications room. Mechanical designers shall work with telecommunications designers to ensure that space is available for access to cable tray or cable pathway in hallways Electrical Construction Requirements of MDF/IDF rooms: Provide a minimum lighting level of 50 foot-candles measured 1 meter above the finished floor level. Provide a minimum of two dedicated, isolated ground, 110V, 20A quad electrical outlets which are on separate circuits on each wall. One of these outlets shall be installed on the wall near the equipment frames. SECTION 2 SITE CABLING CROSS-CONNECT SYSTEM All horizontal cabling will be terminated on Category 6 patch panels (see parts list end of document). This allows any cable to be used for voice, data or other purpose. Cross-connects will be done by using patch cords in the MDF/IDF rooms to connect a jack on the horizontal cabling system Category 6 patch panel to either network equipment or a patch panel designated for voice or other use in the equipment racks. All patch cords other than voice or data must be clearly labeled and identified by the installer BACKBONE CABLE Data backbone cabling installed between each Mdf/Idf room will consist of one 12 strand Interlocking Armored 50/125um OM4 multimode optical fiber cable (see parts list end of document). Phone backbone cabling installed between MDF/IDF will consist on one 50 pair copper cable. Phone backbone cabling installed between MDF/DMARK will consist on one 25 pair copper cable BACKBONE CABLE INSTALLATION 4

5 All backbone cables shall be installed in the following manner: Where cables are housed in conduits, the backbone and horizontal cables shall be installed in separate conduits. Backbone cabling not installed in cable tray must be properly installed in J hooks or Bridal rings at a maximum of 5 apart. Pathways for Backbone cabling must be self supporting and not run through any building structure unless authorized by the SPS Networking Dept. For optical fiber backbone cables: Do not exceed the cable s minimum bend radius. Bending cable tighter than the minimum bend Radius may result in increased optical fiber attenuation or fiber breakage. Fiber backbone cable must be fastened to fiber boxes at each end with a 3/8 flex connector. Do not exceed the cables maximum compression, tensile loading, or minimum bend radius (See manufacture specifications for more info). NOTE: Do not locate backbone cable pathways in elevator shafts. Do not over fill conduits, ducts or sleeves. Refer to the BICSI Telecommunications Distributions Methods Manual, latest edition for more information CABLING Copper Data/Phone cabling: Any Contractor installing Data/Phone/IP Camera cabling must have a BICSI level II installer on staff. Contractors must be certified by the manufacturer and provide a minimum 25 year warranty on cabling and connectivity. Contractors installing Data/Phone/IP Camera cabling must provide the proper credentials at the bid opening. SPS utilizes a controller based Wireless system that is part of the Network infrastructure. It requires 2 drops per wireless access point. One location in the center of every classroom, two in every Learning Lab, cafeteria, all purpose room, library, gym, commons area, any other large multipurpose room and coverage for all other areas designated by the SPS Networking department. All wireless access point locations not in drop ceiling must have a 4s box, shallow mud ring, and conduit to the nearest cabling pathway. All cabling for Wireless Access Points in drop ceiling must have a 15 loop at the access point. Pathways for horizontal cabling must be self supporting and not run through any building structure unless authorized by the SPS Networking Dept. All cabling terminating in the Telecommunications room (MDF/IDF) must have 10 (3m) of slack and be installed in an extended loop meeting all BICSI requirements and best practices. All cabling terminating at a Communications outlet (Jack) must have 3.28 (1m) of slack. All Data/Phone locations must use a 2 gang box with mud ring. Any Data/Phone locations with more than 4 ports must use a 2 gang faceplate. The maximum distance of any cable shall not exceed 295 including slack loops. Cabling not installed in cable tray or conduit must be installed in J hooks or Bridal rings at a maximum of 5 apart. 5

6 Certified to Category 6 standard for Data/Phone/IP Camera. All four pairs terminated on each end with RJ-45 EIA/Tia 568-B. Data cables and jacks must be blue in color (see parts list end of document). Phone cables and jacks must be white in color (see parts list end of document). IP Camera cables and jacks must be green in color (see parts list end of document) Phone locations for all Secretaries must have two phone drops. Phone cabling for class rooms must be wall mounted by the door to meet SPS safety requirements. All rooms must have phone cabling installed including the gym, stage, kitchen, cafeteria, and commons areas to meet SPS safety requirements. Flush mount faceplate to match electrical (see parts list end of document). All cable outlets labeled and Category 6 twisted pair (UTP) certified. Data station distribution cables constructed with Category 6 data grade media and shall originate on a Category modular patch panel located in the Main Distribution Frame (MDF) or Intermediate Distribution Frame (IDF) location (see parts list end of document). Testing and certification documentation shall be returned to the SPS Networking Group upon completion of the job. Any wall or floor penetration must have a sleeve installed sized for 25% growth. All conduit stub-ups and sleeves must have protective bushings installed. Do not daisy chain conduits. Conduit fill Ratio for any combination of Data and Phone cabling: 1-4 Cables ¾ 5-8 Cables Cables 1 ¼ Cables 1 ½ NOTE: Do not over fill conduits, ducts or sleeves. Refer to the BICSI Telecommunications Distributions Methods Manual, latest edition for more information CABLING Fiber optic cabling: Fiber connectors must be fusion spiced using pre-polished pigtails or pre-polished connectors. Fiber connector type must be (LC). Fiber Optic cable meets EIA crush resistance, EIA impact resistance, and EIA flexure specifications and shall not have greater than eight (8) inch bend radius. Fiber optic cables are terminated in rack Fiber Optic Termination Boxes (see parts list end of document). Adapter plates that accommodate LC type connectors are specified for all available spaces within each Fiber Optic Termination Box (see parts list end of 6

7 document). Testing and certification documentation shall be returned to the SPS Networking Group upon completion of the job. NOTE: Do not over fill conduits, ducts or sleeves. Refer to the BICSI Telecommunications Distributions Methods Manual, latest edition for more information. SECTION 3 GROUNDING AND BONDING FOR NETWORKS Grounding Grounding and bonding shall comply with EIA/TIA 607. Each MDF/IDF closet shall be equipped with a grounding bar. Multiple grounding bars within a closet shall be bonded together with a conductor sized appropriately. All cross connect frames, patch panels, racks, and ladder tray shall be grounded per standard practice. Telecommunications grounds in each closet shall be tied to the main grounding bar located at the MDF with a minimum #6 AWG copper ground cable. This ground shall be connected to the building s main power grounding electrode, or alternate approved grounding location. The vendor will insure that no ground loops or extraneous voltages exist within the grounding system, or that no DC resistance greater than 5 ohms exists between any ground bar and the main building electrical grounding electrode. SECTION 4- TESTING Testing All cables and termination hardware shall be 100% tested for defects in installation and to verify cable performance under installed conditions. The contractor prior to system acceptance shall verify all conductors of each installed cable useable. Any defect in the cabling system installation including but not limited to cable, connectors, feed through couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% useable conductors in all cables installed. All cables shall be tested in accordance to best industry practices. If any of these are in conflict, the Contractor shall be responsible to bring any discrepancies to the attention of the project manager for clarification and/or resolution. 7

8 4.0.2 Performance COPPER Category 6 Data/Phone cable shall be performance verified using an automated test set. Test results shall be automatically evaluated by the equipment, using the most up-to-date criteria from the TIA/EIA and the result shown as pass/fail. Test results shall be printed directly from the test unit or from a downloaded file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved. FIBER Test results shall be automatically evaluated by the equipment, using the most upto-date criteria from the TIA/EIA Standard and the results shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved. 8

9 Product Manufacture Part # 48 Port Cat 6 Patch Panel Hubbell P6E48U 7'x19" 2 Post Rack (Black) Hoffman EDR19FM45U Horizontal Wire Management (2U) Panduit WMP1E Vertical Wire Management Panduit WMPVHC45E Wire Management Center Mount Kit Panduit WMPVCBE Fiber Enclosure (Rack Mount) Panduit FMT1 Fiber Enclosure (Wall Mount) Panduit FWME2 Fiber Adapter Patch Panel Panduit CFAPPBL1 Fiber Adapter Panel Panduit FAP6WAQDLCZ Fiber Filler Panels Panduit FAPB Fiber Patch Cable 2 Meter (LC-LC) CP Technologies LC G Fiber Patch Cable 3 Meter (LC-LC) CP Technologies LC G Cat 6 Patch Cables 5' (Blue) CP Technologies C6-BLUE-05-M Cat 6 Patch Cables 10' (Blue) CP Technologies C6-BLUE-10-M Cat 6 Patch Cables 14 (Blue) CP Technologies C6-BLUE-14-M Cat 6 Patch Cables 5' (White) CP Technologies C6-WHITE-05-M Cat 6 Patch Cables 3' (Green) CP Technologies C6-GREEN-03-M Cat 6 Patch Cables 5' (Green) CP Technologies C6-GREEN-05-M Cat 6 Patch Cables 7' (Green) CP Technologies C6-GREEN-07-M Cat 6 Plenum Cable (Blue) Berk-Tek Cat 6 Plenum Cable (White) Berk-Tek Cat 6 Plenum Cable (Green) Berk-Tek Pair Cable (White) Superior Essex Pair Cable (Gray) Superior Essex Strand 50 Micron Interlocking Superior Essex L4012F401 Armored OM4 Fiber Optic Cable Data Jacks (Blue) Hubbell HXJ6B Phone Jacks (White) Hubbell HXJ6W IP Camera Jacks (Green) Hubbell HXJ6GN Wall Mount Faceplate (Stainless) Hubbell P630S1GC6 1 Port Faceplate (Stainless) Hubbell SSF11 2 Port Faceplate (Stainless) Hubbell SSF12 3 Port Faceplate (Stainless) Hubbell SSF13 4 Port Faceplate (Stainless) Hubbell SSF14 4 Port Faceplate (Stainless) 2 Gang Hubbell SSF204 6 Port Faceplate (Stainless) 2 Gang Hubbell SSF206 9

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network

More information

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels

More information

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside

More information

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120 DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified

More information

LACCD IT Design Standards

LACCD IT Design Standards LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage

More information

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017. Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

TIA/EIA 568A Sub-system HORIZONTAL CABLING

TIA/EIA 568A Sub-system HORIZONTAL CABLING TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

SECTION TELEPHONE AND COMPUTER CABLING

SECTION TELEPHONE AND COMPUTER CABLING SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

Los Angeles Community College District Design Standards

Los Angeles Community College District Design Standards LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

Technology Standards

Technology Standards June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

Newark, Delaware Architectural Engineering Senior Thesis Portfolio

Newark, Delaware Architectural Engineering Senior Thesis Portfolio Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should

More information

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE

More information

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled. 27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Figure 1: Industrial Distribution Frame (IDF) Equipment Elevation

More information

Classroom WiFi Network Infrastructure Plan

Classroom WiFi Network Infrastructure Plan Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

SPECIFICATION STANDARD

SPECIFICATION STANDARD PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated

More information

Structured Cabling Guidelines

Structured Cabling Guidelines Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE

More information

Communications Updated April

Communications Updated April 27 00 00 Communication 27 05 00 Common Work Results for Communications 1. Purpose a. Coastal Carolina University facilities requiring cabling installation. This document provides the minimum performance

More information

COUNTY OF SAN JOAQUIN

COUNTY OF SAN JOAQUIN COUNTY OF SAN JOAQUIN General Services Department 44 North San Joaquin Street, Suite 590 Stockton, California 95202-2778 (209) 468-3357, Fax (209) 468-2186 GABRIEL E. KARAM Director Capital Projects Facilities

More information

SECURE NETWORK INFRASTRUCTURE POLICY

SECURE NETWORK INFRASTRUCTURE POLICY Responsible University Administrator: Vice Provost for Academic Affairs Responsible Officer: Chief Information Officer Origination Date: N/A Current Revision Date: 02/19/13 Next Review Date: 02/19/17 End

More information

UNIVERSITY OF CALICUT (Purchase Division)

UNIVERSITY OF CALICUT (Purchase Division) No. 12831/PURCHASE-ASST-A1/2013/CU UNIVERSITY OF CALICUT (Purchase Division) Calicut University. P.O., Dated, 07.06.2013. TENDER NOTICE Sealed and competitive tenders are invited for the installation of

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

ANSI/TIA/EIA-568-B Cabling Standard NOTE

ANSI/TIA/EIA-568-B Cabling Standard NOTE 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

Addendum No. 1 January 7, 2015

Addendum No. 1 January 7, 2015 Addendum No. 1 January 7, 2015 DISTRICT-WIDE WIRELESS UPGRADE AND CABLING: INTERNAL CONNECTIONS E-RATE YEAR 18 - RFP NO. 14-15-103 Below is the list of questions received and clarifications. The color

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

Element Z General Design Requirements Owner Standards and Other Requirements

Element Z General Design Requirements Owner Standards and Other Requirements Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases

More information

Huron School District Request for Proposal

Huron School District Request for Proposal Huron School District Request for Proposal Allowable Contract Date: January 25, 2017 Bids received after January 25, 2017 may not be considered 32044 Huron River Dr. New Boston, MI 48164 Contact person:

More information

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE The Omega MPP enclosure is based on a 19" frame, with 4 empty module slots for MPP modules. Highly flexible : any mix between twisted pair and optical fiber modules.

More information

Siemon PON Fiber Cabling Solutions

Siemon PON Fiber Cabling Solutions Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

SECTION COMMUNICATIONS BACKBONE CABLING

SECTION COMMUNICATIONS BACKBONE CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS

PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS Version 14 November 19, 2014 Digital Realty Table of Contents INTRODUCTION... 3 ACCESS TO THE POP ROOMS, ISP & OSP... 3 PoP- MoP Forms... 3 Who must

More information

Design Guidelines for Facilities Construction:

Design Guidelines for Facilities Construction: Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,

More information

Peter Sharp RCDD IBI Group

Peter Sharp RCDD IBI Group Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member

More information

Cabling Infrastructure

Cabling Infrastructure Presented by: Jim McGlynn PE RCDD/LAN Specialist O Neal/Gaj A telecommunications and technology consulting firm that specializes in the hospitality industry. Program Discussion: Goals Technology Definitions

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

9/27/04 cci Cablecom Inc. 1

9/27/04 cci Cablecom Inc. 1 cci Cablecom Inc. 1 CCI Cablecom Inc. is a privately held, women owned corporation headquartered in Aurora, CO. We manufacture a variety of voice and datacom products. Cable applications Include: Local

More information

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY Introduction A classroom is measured by its effectiveness in facilitating the exchange of information. The following general guidelines have been developed

More information

Huron School District Request for Proposal

Huron School District Request for Proposal Huron School District Request for Proposal Allowable Contract Date: February 27th, 2017 Bids received after February 27th, 2017 may not be considered 32044 Huron River Dr. New Boston, MI 48164 Contact

More information

Information Transport Systems and Spaces

Information Transport Systems and Spaces Division 27 Master Specification for Information Transport Systems and Spaces 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor 1.3 Submittals

More information

Network+ Guide to Networks 7 th Edition

Network+ Guide to Networks 7 th Edition Network+ Guide to Networks 7 th Edition Chapter 4 Structured Cabling and Networking Elements 2016 Cengage Learning. May not be scanned, copied or duplicated, or posted to a publicly accessible website,

More information

PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS)

PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS) PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS) This is an RFP for Internal Connections (Cabling) for Prairie-Hills Elementary

More information

CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program

CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program F.A.R.B Case Study F.A.R.B Software Development, LTD.: Network Design and Implementation CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program Overview Students completing this case study should

More information

Field-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.

Field-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red. FM45 Connector Cat. 6 A IP20, 4P, TIA 568-A/B, 10x R815651 966704105 10 Stk. 090.7437 / ähnliche Abbildung Instruction manual Field-terminated connector with housing. Color housing: gray (RAL 7042). Color

More information

The Riser as a Contract Document. Peter Sharp, RCDD

The Riser as a Contract Document. Peter Sharp, RCDD The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40

More information

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT CAPACITY WITH OPTION TO SEGMENT CHANNELS FIBER CABLE TO UPGRADE CURRENT BUILDING NETWORK

More information

FLORIDA A&M UNIVERSITY S

FLORIDA A&M UNIVERSITY S FLORIDA A&M UNIVERSITY S INFORMATION TECHNOLOGY SYSTEMS GUIDELINES TABLE OF CONTENT Page 1 INTRODUCTION 3 APPROVED VENDOR QUALIFICATIONS 4 SPECIFICATIONS 4 SCOPE OF WORK 8 APPROVED PRODUCTS 11 TESTING

More information

Communication

Communication 27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and

More information

Panduit Certified Installer. Fiber Certification Review

Panduit Certified Installer. Fiber Certification Review Panduit Certified Installer Fiber Certification Review 2 What does the cleave tool do? A. Breaks the glass cleanly B. Cuts the glass cleanly C. Scores the glass cleanly D. Shatters the glass cleanly Breaks

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Date: Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of stations meets DD 9, applicable

More information

BSD Technical Standard. Division 27: Communications & Technology

BSD Technical Standard. Division 27: Communications & Technology Division 27: Communications & Technology I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for telecommunication infrastructure standards.

More information

Cabling Infrastructure

Cabling Infrastructure Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements

More information

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents

More information

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits SYSTIMAX Structured Cabling Systems Family of Cords Quality Stranded and Solid Cords That Connect Data and Voice Circuits Lucent Technologies Family of Stranded Cords includes 110 patch, modular and adapter

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

York Region Information Technology Services. Standards and Guidelines. Cabling and Wiring for Voice and Data Communications

York Region Information Technology Services. Standards and Guidelines. Cabling and Wiring for Voice and Data Communications York Region Information Technology Services Standards and Guidelines Cabling and Wiring for Voice and Data Communications Current Published Version May 9, 2018 Table of Contents Document History... 4 Revision

More information

or

or Infinite possibilities for your data center The F-Series TeraFrame T M Cabinet System The F-Series TeraFrame Cabinet System from Chatsworth Products, Inc. (CPI) provides configurable thermal management

More information

Telecommunications Structured Cabling Systems

Telecommunications Structured Cabling Systems Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T

More information

Power/Data Instructions. Genius. Movable Walls. September

Power/Data Instructions. Genius. Movable Walls. September Power/Data Genius Movable Walls September 2011 Genius Movable Walls Power and Data in Shell Level 1 Conventional Boxes in Panel (conventional box and conduit) Choose 2x4 box or 4x4 box (shown). Separate

More information

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications

More information

PANGEN SYSTEM WARRANTY. Warranty Guide

PANGEN SYSTEM WARRANTY. Warranty Guide PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &

More information

University of Arkansas at Little Rock

University of Arkansas at Little Rock University of Arkansas at Little Rock Policy Name: Infrastructure Cabling and Wiring Standards Policy Number: 702.1 Effective Date: September 24, 2008 Policy: University of Arkansas at Little Rock (UALR)

More information

BEJED DISTRIBUTION PRODUCTS FAX:

BEJED DISTRIBUTION PRODUCTS FAX: 1 BEJED DISTRIBUTION PRODUCTS 503.281.8153 800.232.3533 FAX: 503.281.3339 www.bejed.com Profile BEJED, Inc. s engineering designs have been supporting the telecommunications industry for over 30 years.

More information

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS

More information

The 5500 Series from The Wiremold Company

The 5500 Series from The Wiremold Company 5500 Nonmetallic Raceway Multi-Channel Surface Nonmetallic Raceway Available Factory Prewired. The 5500 Series from The Wiremold Company provides wire and cable management for data, voice, video, and power

More information

Bonding and grounding NETCONNECT copper cabling systems

Bonding and grounding NETCONNECT copper cabling systems White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding

More information

DESIGN GUIDELINES. Building Circulation

DESIGN GUIDELINES. Building Circulation DESIGN GUIDELINES Building Circulation Conceptual Plan FUNCTIONAL AREA DESCRIPTION Building circulation includes all the elements which enable people (including those with disability restrictions) to circulate

More information

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide This guide is designed to assist local on-site contacts to understand what you will need to

More information

General. Exterior Cameras. Camera Towers

General. Exterior Cameras. Camera Towers CAMERAS General This section explains the requirements for interior and exterior cameras. Two basic types of training ranges have cameras: Urban Ranges and Instrumented Training Ranges. Refer to the standard

More information

Powered Fiber Cable System

Powered Fiber Cable System CommScope Powered Fiber Cable System Template Rev. 3/2/2016 CommScope provides this information as a courtesy to its customers and potential customers. Customers should review the information to ensure

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

BUILDING NETWORK SOLUTIONS GUIDE

BUILDING NETWORK SOLUTIONS GUIDE BUILDING NETWORK SOLUTIONS GUIDE designed to be better. INTEGRATED SOLUTIONS BUILDING NETWORK CHALLENGES Constantly evolving technologies are driving connectivity expectations and moving interactions to

More information

Cabling a Data Center to TIA-942 Standard

Cabling a Data Center to TIA-942 Standard Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center

More information

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect. Structured Cabling Systems BACKBONE CABLING Bldg 3 Entrance Closet Telco Closet Bldg 2 Telco Closet Intermediate Cross Connect Main Cross Connect Backbone Cabling ER HC/FD UTP STP-A Optical Fiber HC/FD

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

AXXESS INDUSTRIES INC.

AXXESS INDUSTRIES INC. AXXESS INDUSTRIES INC. PRIVACYSERVICE Guest Room Management System INSTALLATION INSTRUCTIONS Rev. Aug 2012 The Axxess PrivacyService System consists of 2 main components, the Guest Room Switch ( GRM )

More information