Einstein User Guide Rev 1.12 April Einstein User Guide. CPC (UK) Ltd. Tel: Fax:

Size: px
Start display at page:

Download "Einstein User Guide Rev 1.12 April Einstein User Guide. CPC (UK) Ltd. Tel: Fax:"

Transcription

1 Einstein User Guide CPC (UK) Ltd. Tel: Fax: Unit 7&8 Heathrow Causeway Est. Ariel Way, Hounslow, Middlesex. TW4 6JW 1 of 75

2 Contents SECTION ONE...5 BEFORE SWITCHING ON THE EINSTEIN....5 CLEARING THE UNIT ON POWER UP....6 IMPORTANT NOTE ABOUT NAVIGATION...6 SETTING UP THE UNIT FROM A CLEAROUT/BLANK UNIT....7 SETTING UP GLOBAL INFORMATION....7 General Controller Information...7 General. [Shortcut:*Y1]... 7 Eng Units. [Shortcut: *Y1@]... 8 Modem. [Shortcut:*Y1s+#]... 8 TCP/IP. [Shortcut: * Y1s+$]... 8 System. [Shortcut: * Y1s+*]... 8 User Access Setup...8 Time and Date....9 Network Status/Setup....9 Connected I/O Boards & Controllers... 9 Controller Setup Default Logging Setup...10 SECTION TWO...11 DFMC SETUP...11 Setup [Shortcut: Select DFMC to program then n *B] Setpoints [Shortcut: Select DFMC to program then n*b@] Inputs [Shortcut: Select DFMC to program then n*bs+#] Sensors [Shortcut: Select DFMC to program then n*bs+$] Status [Shortcut: Select DFMC to program then n*bs+%] WCC SETUP...13 Setup [Shortcut: % 5 Enter Select WCC to program then n *B] Inputs [Shortcut: %5 Enter Select WCC to program then n *Bs+#] SECTION THREE...15 SET UP A CONTROL APPLICATION...15 Add Control Application...15 Edit Existing Application...15 Delete Existing Application...15 DFMC LIGHTING SCHEDULE...16 General [Shortcut: %J*B] Std Events [Shortcut: %J*Bs+$] PACK FAULTS (DIGITAL SIGNALS)...17 General [Shortcut: $ Select Digital Sensor n *B] Inputs [Shortcut: $ Select Digital Sensor n 17 Outputs [Shortcut: $ Select Digital Sensor n*bs+^] SECTION FOUR...18 MULTIFLEX PAK COMPRESSOR/CONDENSER CONTROL BOARD...18 Network ID Numbers...18 Numbering the MultiFlex PAK...18 Setting the Baud Rate...18 Setting the Terminating Resistance Jumpers of 75

3 I/O BOARD INPUT AND OUTPUT SETUP...19 The Inputs...19 Wiring...19 Input Type Dip Switches...19 Power Connection...19 Current Ratings for On-Board Power Sources...19 The Relay Outputs...20 Wiring...20 Output Fail-Safe Dip Switches...20 Relay Output Ratings and Fuse Protection...20 The Analog Outputs...20 BOARD STATUS LEDS...21 Status LED...21 Tx and Rx LEDs...21 Code A and Code B LEDs...21 Code A Failure Conditions Code B Failure Conditions Relay Output LEDs...22 PAK SOFTWARE OVERVIEW...22 Maximum # of Groups...22 SAFETY FEATURES...22 Condenser Control...22 Discharge Pressure Min...22 Discharge Pressure Max...22 Condenser Spray...23 Discharge Trip...23 Alarms...23 MULTIFLEX PAK EINSTEIN...23 Interface...23 Viewing the PAK Status Screen...23 Inputs and Set Points...24 Suct TD Suction Temp Liquid Level Comp Amps Cond Temp Amb Temp 1 and Disch Cond Amps Compressor Groups COMP Mode Comp Strategy Condenser Fans Cond Mode PAK State MULTIFLEX PAK HAND- HELD TERMINAL INTERFACE...26 Plugging In the Hand-Held Terminal...26 CPC PAK PACK CONTROLLER SETUP...27 Setup [Shortcut: %D Select Pack Controller n *B] THIRD PARTY PACK CONTROLLER SETUP...31 Setup [Shortcut: %Xt Select Pack Controller n *B] For TX Pack Controllers (WTPK) For Woodley Pack Controllers (WPK) of 75

4 SECTION FIVE...33 SETTING UP AN IRLDS...33 General [Shortcut: %L*B] Outputs [Shortcut: 33 Zone Names [Shortcut: %L*Bs+#] Setting Up an Analogue Sensor Control as part of the IRLDS Setup...34 General [Shortcut: $ Select the Analog Sensor n*b] Inputs [Shortcut: $ Select the Analog Sensor n*b@] Setpoints [Shortcut: $ Select the Analog Sensor n*b s+$] Outputs [Shortcut: $ Select the Analog Sensor n*b s+%] Alarms [Shortcut: $ Select the Analog Sensor n *Bs+^] Notices [Shortcut: $ Select the Analog Sensor n *B s+&] SETTING UP A DIGITAL COMBINER...36 General [Shortcut: *Z2] Comb Ins [Shortcut: *Z2@] Outputs [Shortcut: *Z2s+$] SECTION SIX...37 SETTING UP POWER MONITORING...37 General [Shortcut: *Z2&Highlight Pow Mon nnhighlight Mon Point n] Inputs [Shortcut: *Z2&Highlight Pow Mon nnhighlight Mon Point n@@] SECTION SEVEN...38 HARDWARE SETUP...38 Gateway Setup...38 DFMC Gateway...39 Woodley Gateway (Combo)...39 Combo Gateway Protocol AI Setup RO Board Setup...41 Network Configuration...41 SECTION EIGHT...42 TESCO TERMINOLOGY...42 APPENDICES...43 USING THE EINSTEIN SHORT FORM...44 PACK WIRING INFORMATION...46 Linde TX Pack Controller Format...46 Hussmann TX Pack Controller Format...46 Space TX Pack Controller Format...46 GENERAL DRAWINGS MULTIFLEX PAK CONTROLLER HAND HELD TERMINAL OPERATION...66 Table of contents:...67 Overview...68 Communication Settings...69 Scrolling information screens...70 Configuration Screens...72 General Options...72 Compressor Set Points...72 Compressor Set Points...73 Parameter Listings: of 75

5 Before Switching on the Einstein. Section One Before powering up the Einstein, disconnect the power plugs on the Einstein and Gateways and confirm the DFMC networks using the DB9 connectors on the side of the Einstein enclosure. Remove the plastic battery shield on the rear of the unit. The unit should also be shipped with an Ethernet card fitted which is piggy backed on the Einstein processor board (Rear). Please check the jumpers to the right of the Ethernet card they should be in the positions listed. J7 should be set across pins 5. J8 should be set across the far RHS pins J21 should be set across pins of 75

6 Clearing the Unit on Power up. Einstein User Guide Rev 1.12 April 2006 At this time only connect the power source onto the Einstein. Leave the comms disconnected for the moment. When plugging in, hold the Cleanout and Reset buttons together (These are small buttons located next to the battery on the rear of the unit). After approximately 5 seconds let go of the reset button but still hold onto the cleanout button. Wait until the front screen shows Cleanout Process Initiated then release the Cleanout button and leave it to boot up. The unit will go through 3 boot up sequences before finally being ready with the first screen. On power up it would be wise to make a note of the software revision which will be shown in a band at the top of the screen towards the end of the boot up sequence. It should be written for example 1.82B06. It can also be checked once the Einstein has fully booted up, this is done by logging on to the unit and pressing *L. Important Note about Navigation. The bottom of the screen gives a description of what the Function Keys do at any one point. These Descriptions change as you progress through the menus. The Function keys give you access to sub menus which navigate the Einstein to enable you to set up and program the unit. The * key is the most common key we use for setting up the unit. % More shows another menu where selections can be made from. 6 of 75

7 k Page Down j Page Up To Use the letter X press s+z At any point you can get back to the Home Screen by either pressing ( Home or if this option is not available press ) Back multiple times to backtrack through the screens. The shortcuts that are in this manual all start from the main Home Screen. It is very important to make sure you have FULL TOGGLE on when setting up the unit as this will show all options during navigation. Full Toggle can be switched On/Off by pressing *Q. Indication of whether it is switched on is that the highlighted word FULL will show in the top right hand corner of the screen. Setting up the Unit from a Clearout/Blank Unit. The first screen that shows after a clearout and boot up is a user login box. Please enter USER in the username press / and then PASS in the password. Now press n. The next screen will show the Network Setup Page. This page is asking for the type and amount of devices which are attached to the network. For now just make sure that the Unit number is set at 1 and using / highlight the number of 16AI boards and input just 1. Now press n. To continue press ) (next). The next screen is the Application setup screen Enter 1 condenser and press ). You are now on the unit s Default Home Screen from here we can setup the unit and network. Setting up Global Information. Begin by setting up basic information on the unit like the date, time, engineering units and most important giving the Einstein a unique TCP/IP address. From the home screen press * then Y system Setup. This brings up the System Configuration Menu. General Controller Information Press 1. At the top of the screen you will see the titles of each of the pages in General Controller Information. You can navigate these pages by using the! Previous Tab Next Tab Keys. General. [Shortcut:*Y1] Under General the main information to be input is the site name and change the RX (Einstein) home screen to DFMC/Microm depending on the type of controllers on site. 7 of 75

8 To Input the Site name just highlight the box and type the name in. To change the Einstein home screen highlight then press & Lookup. This brings up a selection list of what the default screen can be set too, highlight the appropriate one then press n. Next Tab If you have set the home screen to something other than the default it still may not be showing. You should log off and log back on to update to the new selection. Eng Units. [Shortcut: *Y1@] Change the top 3 engineering units. By highlighting and pressing & for the selection list. EU Temp to Celsius, EU TempChg to DDC EU TempRateChg to degrees C/hour (DHC). The fourth Engineering units down should have the correct pressure units selected depending on what the packs are set for. PSI or BAR. Next Tab Modem. [Shortcut:*Y1s+#] No changes here Next Tab TCP/IP. [Shortcut: * Y1s+$] Here a unique TCP/IP address is put in which is issued by the SIIMS desk. The subnet mask should always be A primary gateway number should always be input. The primary gateway is always one less than the IP Address. e.g. IP Address Primary Gateway Next Tab System. [Shortcut: * Y1s+*] No changes here. Press ) Back User Access Setup. Press 2. [Shortcut: * Y2] 8 of 75

9 On this screen you can setup passwords and set levels at which those passwords can gain. By using the arrow keys you can move round the screen highlighting different settings. The numbers under set point, bypass, override, config and alarm ack indicate the level required to access these areas/facilities. The Enable Detailed Transaction Logging should be set to NO. Enable Global Log-on should be left YES. Using the arrow keys move into the Users box. From here you can add and delete users from the unit using the function keys. Once the users have been created you can give them a username and password and set their level of access. Suggested level of access is 3 for all. Press ) Back Time and Date. Press 3. [Shortcut: *Y3] Here you can change the date and time by scrolling down and either entering manually or using the & lookup option when available. The Date format should be set to English DD-MM-YY the default is for the US. Highlight Daylight saving Dates and press &, then select the User Defined DLT Dates. Press n. This will now automatically change for British Daylight saving dates. DLT start is the fourth week of March and DLT end is the fourth week of October. Press ) Back Network Status/Setup. Press 4. [Shortcut: *Y4] This takes you to a sub menu and we can add controllers and input boards etc. from selection 2. Connected I/O Boards & Controllers Press 2. [Shortcut: *Y42] Using the arrow keys scroll down and highlight the Unit name. Input the store name here abbreviating if necessary. By highlighting either the boards or controllers you can add controllers by increasing the total number in the box. Note: when adding boards/controllers. If there are some already on the system and you want to add extra just increase the number in the box by the amount you want to add. e.g. if there are 19 already on the system and you want to add a further 5 you need to increase the total number of controllers to of 75

10 Important Note: If you have 19 controllers on the system and you want to add just controller 24 do not add 1 more controller and call it 24 you must add a further 5 controllers. Label the 24 th controller then delete the other 4. Press ) Back Controller Setup Press 1. [Shortcut: *Y41] In this page you can label the controllers. Highlight the Name of the controller then type in the details. The protocol for labelling DFMC s is 000SYS000 the first three numbers are the controller address number followed SYS then the system number. This protocol can vary when limited on the number of characters. Other designations have been 000S0.00 Press ) Back twice Default Logging Setup Press 7. [Shortcut: *Y7] The Base Logs should be setup with 1500 Samples at a logging interval of 5 minutes (0:05:00) Press ( Home Putting Controllers Online You should now connect the comms onto the Einstein. Assuming that the gateways are setup and the networks are correctly wired (See section 6) the controllers should come online after a few seconds of plugging in the comms network. 10 of 75

11 Section Two DFMC Setup The home screen should be showing a number of DFMC s which you have added using the section one. Highlight the DFMC to be programmed and press n. This brings up the controller information. Now press *B Setup. At the top of the screen you will see the titles of each of the pages in DFMC Controller Information. You can navigate these pages by using the!&@ Keys Previous and Next Tab. Make sure that FULL is showing in the top RHS of the screen. If not, switch Full Options on by pressing *Q Setup [Shortcut: Select DFMC to program then n *B] The name should follow Tesco terminology. Pack number first followed by the system number and then the description. Examples, HT1 S106 DAI (HT1 Pack, system 106, Dairy) HT3 S084 RIM (HT3 Pack, system 84, roll in milk) LT1 S023 FFF (LT1 Pack, system 23, Frozen food freezer) Full Tesco terminology is listed in the rear of this manual You can input a long name but the only place this will be seen is within this setup page. Next Tab Use the connected function YES/NO to switch the case controller on or off within the software. The default is set to off (Connected - No). While the controller is set to off no alarms will be created if the physical controller is not present on the network. This facility enables the total addition of all controllers which can then be switched on individually when they are physically present on the network. Setpoints [Shortcut: Select DFMC to program then n*b@] On this page you should enter the case set points that are required. Stat CutOut Case Temperature Setpoint TStat K Case Temperature Deadband Alarm Lo limit Not used. Set it low at -40 Alarm Hi limit Case Temperature Alarm Setpoint Hi Alm Delay 1 Defrost Alarm Lockout (From start of defrost) Hi Alm Delay 2 Case Alarm Delay Day Alarm Ratio Set at 100% Air off 11 of 75

12 Night Alm Ratio S5 Alarm Dest S6 Alarm Dest Set at 100% Air Off Set to Type 2 if a fifth probe is fitted, Disable if not. Disable Leave all other settings on this page at their defaults. Next Tab Inputs [Shortcut: Select DFMC to program then n*bs+#] This page is used to connect this controller to a lighting schedule and a leak detection output from an Infrared Leak Detection System (IRLDS). These inputs can be setup by reading the relevant section in this manual. Next Tab Sensors [Shortcut: Select DFMC to program then n*bs+$] This page can set the individual sensors to log. The logs are used to store information that is used to graph. Sensors that we should log include: COIL IN COIL OUT AIR ON AIR OFF DEFR TERM TEMP (Only if S5 probe is fitted) Highlight the sensor to be logged then press *7 Logging Setup. The box Logging Group Cell is automatically highlighted press & select Base Log and press n. Base Log should then appear in the Logging Group Cell box. Press ). The suffix L indicates whether this sensor is now logging but you will have to refresh the sensor page before it shows. Complete setting up the logs on each of the sensors by repeating this paragraph then press )*B s+$ to refresh page and check whether the suffixes appear to prove they are logging. To enhance the performance of the Einstein it is advisable that unused logging points are deleted. To switch off logging on points that are not needed refer to the next section. Next Tab Status [Shortcut: Select DFMC to program then n*bs+%] Deleting Unused Logging Points Highlight Alarm Air press *7 Logging Setup. The Logging Group Cell is highlighted and contains Base Log. Press d (Delete) ). Press k Page Down Repeat the delete sequence for Defrost All other pages in the DFMC Controller setup are not used. ( Home 12 of 75

13 WCC Setup WCC stands for Woodley Case Controller. These case controllers include Microm, Guardian and CDK which all sit on a Woodley 3 rd party network. See Network Status Setup in the previous section to add WCC s. The DFMC page is usually the set as the Home screen. To See the WCC screen press % More and 5 for WCC. (The WCC menu will not be there if you have not added any controllers under Network Status Setup ). Highlight See Summary and press n. This now shows you the WCC summary page which is the same as the DFMC summary page. Highlight the WCC to be programmed and press n. This brings up the controller information. Now press *B Setup. At the top of the screen you will see the titles of each of the pages in WCC Controller Information. You can navigate these pages by using the!&@ Keys Previous and Next Tab. Make sure that FULL is showing in the top RHS of the screen. If not, switch Full Options on by pressing *Q Setup [Shortcut: % 5 Enter Select WCC to program then n *B] On this page you should enter the case set points that are required. The name should follow Tesco terminology. Pack number first followed by the system number and then the description. Examples, HT1 S106 DAI (HT1 Pack, system 106, Dairy) HT3 S084 RIM (HT3 Pack, system 84, roll in milk) LT1 S023 FFF (LT1 Pack, system 23, Frozen food freezer) Full Tesco terminology is listed in the rear of this manual You can input a long name but the only place this will be seen is within this setup page. TEMP HI LIMIT Case Temperature Alarm Setpoint Recovery Time Defrost Alarm Lockout (From start of defrost) Temp Alarm Dly Case Alarm Delay Device Type Press F7 Select the Type of WCC. (See Note) Note: Generic TX Controller. Guardian Microm Controller. Extended CDK Controller. Leave all other settings on this page at their defaults. Inputs [Shortcut: %5 Enter Select WCC to program then n *Bs+#] This page can set the individual sensors to log. The logs are used to store information that is used to graph. Sensors that we should log include: 13 of 75

14 COIL IN COIL OUT AIR ON AIR OFF Highlight the sensor to be logged then press *7 Logging Setup. The box Logging Group Cell is automatically highlighted press & select Base Log and press n. Base Log should then appear in the Logging Group Cell box. Press ). The suffix L indicates whether this sensor is now logging but you will have to refresh the sensor page before it shows. Complete setting up the logs on each of the sensors by repeating this paragraph then press )*B s+$ to refresh page and check whether the suffixes appear to prove they are logging. All other pages in the WCC Controller setup are not used. ( Home 14 of 75

15 Section Three Set up a control application The following shows you how to setup a control application. Control Applications are software tools which perform different tasks. There are many different types of control application the following few paragraphs show how to select the ones you want and then program them for there particular tasks. From the Home screen press *Z Control Application Setup this leads you into the Application Configuration Menu. Typical Control applications that need to be setup would normally include Time Schedules (E.g. For Lighting), Analogue Sensor Ctrl s (Analogue input/switch), Digital Sensor Ctrl (Digital input/switch) and Standard Circuits (For case monitoring/controlling) Add Control Application Press 1. [Shortcut:*Z1] The control application screen just asks what type do you want to add and how many. The type of application is already highlighted and defaults to condenser. If you press & Look Up a list appears of the different applications. Select the application you require and press n, scroll down using the / key and select how many you require then press ny. Press ) Back Edit Existing Application Press 2. [Shortcut:*Z2] This takes you into the Edit Control Application screen press & Lookup and scroll to the application you want to edit press n and n again. If there is only one of these applications created you will be taken immediately to that screen but if there are multiple applications you will given a list of the applications asking you which one you want to edit. Each Application differs in its setup. Please refer to the relevant section on how to setup the individual applications. Press ) Back (Twice if multiple applications) Delete Existing Application Press 3. [Shortcut: *Z3] This takes you into the Delete Control Application screen press & Lookup and scroll to the application you want to delete press n and n again. If there is only one of these applications created you will be given the option to immediately delete the application but if there are multiple 15 of 75

16 applications you will given a list of the applications asking you which one you want to delete. Select the application to delete press n then Y. Press ) Back (Twice if multiple applications) DFMC Lighting Schedule Create a Time Schedule by adding a control application. From the home screen Press % More. This brings up the Existing Applications menu. Time Schedules should appear under J. Press J. If there is only 1 time schedule it will take you directly into it. If there are multiple time schedules the Einstein will bring up a list of the time schedules from which you need to select the one you require. To setup the time schedule press *B. At the top of the screen you will see the titles of each of the pages in Time Schedules. You can navigate these pages by using the!?&@ Keys Previous and Next Tab. General [Shortcut: %J*B] Change the name to Case Lighting Press s+$ Std Events [Shortcut: %J*Bs+$] This gives you a list of events which you can program to be On or Off on certain days. Under Event 1 the first box requires an On command (just type the word in) then moving across the boxes an On time needs to be input. Event 2 requires an Off command followed by an Off time. The following selection is asking which days of the week you want this schedule to be activated on. Highlight the day of the week and press. Next & : Prev to toggle that day. Press ( Home This time schedule now needs to be linked to the individual DFMC s. From the Home Screen select the DFMC that needs to have the lighting schedule attached and press n. Press *B setup twice until you tab to the Inputs page. Scroll down to the lights input and under Controller press & lookup. There will be only one selection so just press n. Scroll to the next box Application press & and select the lighting schedule that you have created in the list that appears. Scroll to the next box Output press & and select output, press n. Press ( Home Note: The physical DFMC has to be changed to Remote for the lighting to switch via the Einstein. Do this using the Danfoss Handheld Unit. 16 of 75

17 Pack Faults (Digital Signals) Einstein User Guide Rev 1.12 April 2006 For simple pack faults a digital signal input is setup to receive an NO/NC signal from a pack. Create the amount of pack faults you require by adding Digital Sensor Ctrl under Add Control Application. Then setup the pack fault by Edit Existing Application [Shortcut: *Z2&] Scroll to Digital Sensor Ctrl press n then select the digital sensor that you want to edit press n. At the top of the screen you will see the titles of each of the pages in Sensor Control DV. You can navigate these pages by using the! Keys Previous and Next Tab. General [Shortcut: $ Select Digital Sensor n *B] Name the pack fault using the correct protocol. The Invert Ctrl Val defaults at NO (Close on fault). It is recommended that this is changed to NC (Open on Fault). Do this by highlighting Invert Ctrl Val then press & and select Yes, press n. This is recommended so if the cable is cut or disconnected it would show as a fault and should be rectified as a priority. Inputs [Shortcut: $ Select Digital Sensor n Input the Board and Point number. The board number relates to a 16AI address number which the pack inputs have been wired to. The point number relates to the individual input on the 16AI which a particular pack has been wired to. Press s+^ Outputs [Shortcut: $ Select Digital Sensor n*bs+^] We have to make this input alarm when a signal is given. Press *6 Generic Alarm Setup. This gives you the Digital Advisory Configuration Setup page for this input. It defaults to No Alarming. Press & and scroll to Select Methods n. Press /, which then shows up the setup box. The Report Delay Notice and Alarm levels should be set for 2 minutes 0:02. The Report Priority Notice and Alarm level should be set for 20. The Alarm On an should be set at Yes by highlighting and pressing Y. Press ) (. Repeat this action for each of the Digital inputs for the pack faults. 17 of 75

18 Section Four MultiFlex PAK Compressor/Condenser Control Board Network ID Numbers Each device on an RS485 network has a dip switch that must be used to assign the board a unique network ID number. The network ID number makes a board unique from other boards on the network of the same type. This allows the site controller to find it and communicate with it. Boards of the same type should be numbered in sequence, starting with one and continuing with two, three, and so forth. Numbering the MultiFlex PAK The network ID on the MultiFlex PAK is set using the first five dip switches on dip switch bank S3. Setting the Baud Rate All I/O boards have dip switches that determine the baud rate at which they communicate. Currently, the baud rate dip switch in network components should be set at 9600 baud. On all MultiFlex boards, switches 6 and 7 on S3 are used to set the baud rate. To communicate at 9600 baud, set switch #6 UP and #7 DOWN. Setting the Terminating Resistance Jumpers All MultiFlex boards and other RS485 devices have a set of terminating resistance jumpers (one jumper for each wire lead). These jumpers are labeled JP2, JP3, and JP4 on the MultiFlex board. The purpose of the jumpers is to indicate the two ends, or termination points, of the network. On a daisy chain, one device at the beginning and one device on the end must be terminated. On the MultiFlex, this is done by placing all three termination jumpers in the OUT (toward the left edge of the board) 18 of 75

19 position. To unterminate a MultiFlex, these jumpers must be set to the IN (toward the center of the board) position. I/O Board Input and Output Setup The Inputs The inputs on a MultiFlex board are compatible with a wide range of analog and digital sensors and transducers. In general, the inputs are capable of reading analog voltage signals in the range of 0V to +7VDC and dry-contact (no outside voltage) digital sensors and switches. Connecting Sensors to Input Boards Wiring a sensor to the input points on a MultiFlex board requires three steps: 1. Connect the sensor s signal wires to the two terminals of an input point. 2. Set the input type dip switch that corresponds to the point being connected. 3. If necessary, connect the sensor to one of the 5V or 12V power terminals. Wiring An input point on a MultiFlex board consists of two terminals. One of these terminals, labeled SIG, reads the signal from the sensor, while the other, labeled 0v is where the sensor s ground and/or cable shield wire is connected. Input Type Dip Switches Each MultiFlex input point has an input type dip switch that must be set. Input type dip switches are located in the switch banks labelled S1 and S2. The input type dip switch tells the input board whether or not the sensor connected to the point is a resistive type sensor. Generally, if the sensor or transducer supplies its own voltage signal to the point, the dip switch should be set to the LEFT (OFF) position. If the sensor uses variable resistance and requires voltage to be supplied to it from the input point, set the dip switch to the RIGHT (ON) position. Dip switches for unused points should be set to the RIGHT (ON) position. The exception to this rule is for CPC s 5VDC pressure transducers -- though they supply their own voltage signal, the dip switch MUST be set to the RIGHT (ON) position. Power Connection If power is needed to operate the sensor, four points are provided on the MultiFlex board that supply DC power: one +12VDC point, and three +5VDC points. See picture for the location of these points. Current Ratings for On-Board Power Sources The maximum current that may be drawn from the +12VDC terminal is 100 milliamps. The maximum current that can be drawn from all three +5VDC terminals COMBINED is 50 milliamps. 19 of 75

20 The Relay Outputs Wiring The MultiFlex PAK boards have Form C relay contacts. One wire of the two-wire connection should always be connected to the middle terminal. The second wire must either be connected to the N.C. terminal (if you want the path to be closed when the relay is de-energized) or the N.O. terminal (if you want the path to be open during power failure). The contacts you choose also affect what the board s fail-safe dip switch will need to be set to for proper operation. Output Fail-Safe Dip Switches When a controller calls for a MultiFlex relay output to be ON, it sends a command to the MultiFlex to turn the output to the ON state (signified by the output LED being ON). The behaviour of the relay when it is ON is determined by the position of the fail-safe switch. The fail-safe switches for the outputs are on a switch bank at the bottom right corner the plug-in output module. Each switch corresponds to an output on the board (switch #1 = output #1, etc Relay Output Ratings and Fuse Protection Each relay output on the MultiFlex Combination I/O boards is rated for up to 240 VAC with a maximum current of 2 amps. Each relay is fused with a 2A fast-blow 5mm x 20mm fuse, Bussman GMA-2 or equivalent. The Analog Outputs The MultiFlex PAK board has four analog outputs that pulse a +8VDC signal. Each output is rated up to 10 milliamps. These outputs can be set to drive solid-state relays for condenser fan control, liquid injection, and spray cooling. The MultiFlex PAK may be configured in the software to define 0/8V as ON/OFF or as OFF/ON. 20 of 75

21 Board Status LEDs When a MultiFlex board is powered up, you will be able to determine the operating status of the board by observing its status LEDs. Status LED The Status LED simply blinks GREEN once per second to show that the board is powered and operational. If this light is dark, the board has likely lost power. Tx and Rx LEDs The Tx and Rx LEDs indicate when the MultiFlex is sending or receiving messages on the RS485 network. The Tx LED blinks once every time the MultiFlex sends a response to the Einstein or REFLECS. The Rx LED blinks once when the MultiFlex receives a message. If the MultiFlex is connected to the network and set up to communicate with the controller, you should see these lights blinking regularly. If they do not, there may be a problem with the network. Code A and Code B LEDs The MultiFlex PAK has two LEDs labelled Code A and Code B. These LEDs indicate failure conditions. When these LEDs are OFF, there are no failures active. When one or both of these LEDs are blinking, there are failure conditions. The rate of blinking indicates the type of failure: Code A Failure Conditions 1. Blinking fast (4 times/second) - There is a problem with the flash memory or hardware clock on this board. This generally means the board is bad and must be replaced. 2. Blinking slow (1 time/second) - The board is not receiving any messages addressed to it. This means either the I/O network is down or it has not yet been commissioned in the Einstein or REFLECS Network Configuration screen. 21 of 75

22 Code B Failure Conditions 1. Blinking 2 times/second - This indicates the board has lost its configuration. If Code B blinks at this rate on an operational board, it means the board must be reprogrammed. This light does not blink if the board is new or is using the unmodified default configuration. Relay Output LEDs Each relay output point on a MultiFlex has an indicator LED that shows the status of the output. This LED is lit to show the output is ON, and unlit to show the output is OFF. The definition of ON and OFF in this case is determined by the position of the fail-safe dip switch. PAK Software Overview Maximum # of Groups The maximum number of compressor groups is eight. Each compressor group corresponds to a physical relay point on a MultiFlex board. PAK activates and deactivates compressor groups in order to control the suction pressure. The total maximum number of individual compressors that can be controlled by the PAK is sixteen, regardless of how many compressor groups these compressors are associated with. Compressors are only activated or deactivated as part of a compressor group; however, a PAK input may be set up to read the discharge temperature for any or all of the individual compressors. The number of compressors that may belong to a single compressor group is limited by the amperage rating on the MultiFlex output point (max. 2A up to 240VAC). Safety Features Condenser Control The MultiFlex PAK uses a temperature differential (TD) strategy identical to the current Condenser TD strategy implemented in Einstein s own Condenser Control cell. TD control in the MultiFlex PAK uses a control value that is calculated by subtracting the ambient air temperature near the condenser fans from the calculated discharge temperature (calculated by converting the discharge pressure to temperature based on the refrigerant type). This control value is compared to a fixed temperature differential set point, and condenser fans and/or sprays are activated or deactivated to attempt to keep the control value at or near the TD set point. Discharge Pressure Min To prevent overcooling, the MultiFlex PAK features a minimum pressure set point. If the value of the discharge/condensing pressure falls below this set point, regardless of the TD strategy, all fans will be staged OFF. Discharge Pressure Max The Disch Pres Max feature adds a second "line of defence" to TD control. If the value of the discharge/condensing pressure rises above the set point, all fans will immediately be staged ON regardless of the number of fans called for by TD control. 22 of 75

23 Condenser Spray If a condenser spray output is configured, the PAK can be programmed to activate a water spray to keep the discharge pressure from climbing above a user-defined pressure set point. The spray is activated when the discharge pressure rises above the condenser spray set point, and shuts off when the pressure falls below the set point. To prevent unnecessary activation of the spray when the ambient conditions make evaporative cooling less effective, the PAK can be programmed with an ambient temperature lock out, which prevents the spray from activating if the ambient temperature is below a user-defined ambient lockout set point. Discharge Trip Discharge trip is a safety feature that will shut down all compressor groups if the discharge pressure rises above a critical user-defined set point. Discharge trip occurs immediately the moment the pressure rises above the set point. All compressors shut off, and an alarm is generated and sent to Einstein notifying of the trip condition. The status screen will show the status of both the compressor groups and the condenser fans as "Disch Trip." The pack remains shut down for a minimum userdefined reset delay. Then this delay has passed, the PAK will automatically reset the discharge trip and resume operation if and only if the discharge pressure has fallen to an acceptable level determined by a user-defined reset pressure differential). Alarms The Multiflex PAK will communicate the following alarm conditions: 1. High Discharge Pressure Trip 2. If a defined physical analog input sensor reading is out of range 3. If the Multiflex PAK controller has a digital output as an Alarm Output, then the relay will close when any of the alarm conditions listed above are active. 4. If set to Yes, the Reset Alarm function will reset all alarms and restart the PAK. MultiFlex PAK Einstein Interface The MultiFlex PAK is capable of communicating with an Einstein RX refrigeration controller with software version 1.83 or above. Using MultiFlex PAK boards with a central Einstein controller offers several benefits over simple stand-alone PAK control, including: 1. Reporting of PAK-related alarms in the Alarm Advisory Log 2. The ability to log PAK inputs in an Einstein logging group 3. Remote access to PAK status and programming from the Einstein front panel or remote communication tools (InSite or UltraSite32). 4. Communication between Einstein and a PAK takes place over the RS485 I/O Network. Viewing the PAK Status Screen The PAK Status Screen shows the current status of all compressors and condensers. Though there is a large amount of information on a PAK status screen, status information is grouped on this screen in 23 of 75

24 several groups of related information in order to make the screen easier to read. These groups are described below. Inputs and Set Points The top four lines of the PAK Status Screen show the current values of all the important inputs and set points in the PAK controller. Suct The Suct field shows the current value of the suction pressure. The value shown in smaller type to the right of the suction pressure field (enclosed by brackets [ ]) is the suction pressure control set point, displayed here for reference purposes. TD The TD field shows the current calculated value of the temperature differential between the discharge temperature and the ambient temperature. The value shown in smaller type to the right of the TD field (enclosed by brackets [ ]) is the TD set point, displayed here for reference purposes. Suction Temp This field shows the value of the PAK s suction return gas temperature input. Liquid Level This field shows the value of the PAK s liquid level input. Comp Amps This field shows the value of the PAK s Compressor Amps input. Cond Temp This field shows the condenser temperaturecalculated by converting the discharge pressure to temperature based on the system refrigerant. Amb Temp 1 and 2 The Amb Temp 1 and 2 fields show the current values of the ambient temperature sensors on the condenser. These values are combined into a single ambient temperature, which is used in the TD calculation. Disch This field shows the current value of the discharge pressure transducer. 24 of 75

25 Cond Amps This field shows the current value of the PAK s Condenser Amps input. Compressor Groups The box left of the middle of the PAK Status Screen shows the current status of the compressor groups defined for the PAK. Compressor Group HP/AMPS and Status Each group from 1 through 8 has a field showing HP/AMPS, which displays the total amount of HP or AMPS of all compressors associated with the group, and a Status field, which shows whether the group is currently ON or OFF. COMP Mode The Compressor Group Mode field explains the current state of the fixed step control algorithm in the MultiFlex PAK. There are seven messages that may appear here: 1. OFF - No compressor groups are ON, and none are being called to be ON. 2. Off Delay - The MultiFlex PAK requires less compressor HP/AMPS, and is trying to cycle backward through the fixed steps, but PAK is currently waiting for the fixed step OFF delay to elapse before moving to the next lower step. 3. On Delay - The MultiFlex PAK requires more compressor HP/AMPS, and is trying to cycle forward through the fixed steps, but PAK is currently waiting for the fixed step ON delay to elapse before moving to the next higher step. 4. DeadBand - The suction pressure is within the set point dead band. The PAK will remain on the current fixed step and is not attempting to move up or down to a new step. 5. Max Cap - The PAK has cycled through the fixed steps all the way to the last step, but the set point is still out of range. In other words, the PAK would activate more HP/AMPS if more were available, but it is operating at maximum capacity. 6. XDucer Fail - The suction pressure transducer input has failed. 7. Disch Trip - The discharge pressure has exceeded the discharge trip setpoint, causing the compressor group to shut down. Comp Strategy This field shows the compressor strategy whether fixed steps or cyclic. Condenser Fans The box on the right of the PAK Status Screen shows the current status of the condenser fans. Each fan from 1 through 4 has a field showing the ON/OFF status of the fan. Cond Mode The Condenser Mode field explains the current state of the condenser fan control algorithm in the MultiFlex PAK. There are seven messages that may appear here: 1. OFF - All condenser fans are OFF, and thedischarge pressure/temperature is low enough to not require any fans to be activated. 25 of 75

26 2. OFF Delay - The PAK is calling for fan stages to deactivate, and PAK is waiting for the OFF Delay time period to elapse before deactivating the next fan stage. 3. ON Delay - The PAK is calling for fan stagesto activate, and PAK is waiting for the ON Delay time period to elapse before activating the next fan stage. 4. DeadBand - The discharge pressure is within the setpoint deadband, and therefore the PAK is neither activating nor deactivating any fan stages. 5. Max Cap - All condenser fans are ON, but the discharge pressure is still above set point. In other words, PAK would activate more fan stages if more were available, but it is operating at maximum capacity. 6. Cond Spray - The condenser spray output is currently ON, meaning the discharge pressure is currently higher than the condenser spray set point. PAK State At the very bottom of the PAK Status Screen, the "PAK State" field shows whether the Multi-Flex PAK is currently reading as Online or Offline. MultiFlex PAK Hand- Held Terminal Interface All MultiFlex boards have a Hand-Held Terminal interface, which can be used to view status for the board without having to use the site controller. Though different for each model of MultiFlex, the Hand-Held Terminal interface allows you to perform the same general functions: 1. View failure messages that relate to the MultiFlex 2. View the status of inputs (both in volts and in engineering units appropriate to the sensor type) 3. View the current state of relay outputs (ON or OFF) and analog outputs (both in volts and in percentage) 4. Override relay outputs to a fixed ON or OFF state, or override analog outputs to a fixed percentage 5. Configure set points Plugging In the Hand-Held Terminal The Hand-Held Terminal plugs into the RJ11 jack on the MultiFlex base board (located on the bottom left side of the board. Press the Hand-Held Terminal connector into the jack until it snaps into place. When the connector is correctly seated, the screen to the Hand- Held Terminal will display the message CPC Handheld Terminal and then the first screen of the MultiFlex interface. 26 of 75

27 CPC PAK Pack Controller Setup Add the required type and number of pack controllers under Connected I/O Boards & Controllers in Network Status Setup. [Shortcut: * Y42] Press ( Home. Press %D. If there is only one pack controller created, then this will take you directly into the pack controller page. If there are multiple controllers created, then this will take you to a pack controller selection list. Select the pack controller to be edited, and press n. Setup [Shortcut: %D Select Pack Controller n *B] At the top of the screen you will see the titles of each of the pages in controller setup. You can navigate these pages by using the! Keys Previous and Next Tab. Selections can be made by either using a lookup table & (highlight selection and press n) or the :. keys to cycle through the options. The following, lists all the inputs required to setup a PAK controller General Input 1. Name the pack controller using the correct protocol. Alphanumeric 2. Long name is not used. 3. Input refrigerant type R404a/R22/R408a 4. Select pressure units (Note, Bar x 10 = Kpa) Kpa/PSI 5. Select temperature units DegC/DegF 6. Select compressor strategy Cyclic/Fixed Steps 7. Comp proof fail Enable/Disable This enables the proof alarming within the Einstein 8. Condenser interlock On/Off Switches off all fans when no compressors are running 9. Input number of steps for fixed step strategy. Numeric Value Only appears when fixed steps is selected as the compressor Strategy. 10. Number of compressors Numeric Value 11. Condenser Type Staged/VSD/Seq Input type of condenser fan control 12. Number of condenser fans Numeric Value Comp Setpts 1. Suction pressure deadband Pressure Value 2. Step on delay HH:MM:SS 3. Step off delay HH:MM:SS 4. Suction pressure minimum Pressure Value The PAK will turn off all compressors if this limit is exceeded 5. Proof restart delay HH:MM:SS Wait this time before restarting after a proof failure 27 of 75

28 6. Proof restart PH Numeric Value Max number of restarts per hour then hold off until next hour 7. Groups Assigns every compressor to a group. 8. Amps per comp1-10 Value in Amps Value used for display only Cond Setpts 1. Condenser TD deadband Pressure Value The PAK controls on this setpoint 2. Fan on delay HH:MM:SS 3. Fan off delay HH:MM:SS 4. Discharge pressure max Pressure Value Fast recovery value Brings in each remaining fan stage with appropriate delay. 5. Discharge pressure min Pressure Value Inverse of the above 6. Discharge pressure setpoint Pressure Value Only used if the ambient temperature sensors fail 7. Discharge pressure deadband Pressure Value Only used if the ambient temperature sensors fail 8. Ambient temperature minimum setpoint Temperature Value The condenser TD calculation uses this minimum if the ambient temperature falls below this limit 9. Interlock Dis Pressure Value Cond and compressor interlock will cause the condenser fans to stage off using Fan off Delay if all the compressors are called to be off. This feature is disabled if the Disch Presssure is above the setpoint DischPresInterlockDisable. This feature can also be disabled (under General tab) by setting the field code Interlock to OFF. 10. Condenser spray setpoint Pressure Value Discharge pressure setpoint at which the adiabatic cooling spray Commences (Mr. Squirty) 11. Ambient spray lockout Temperature Value Ambient temperature at which the adiabatic cooling spray locks out 12. Rtn2Nml Pressure Value Adiabatic cooling switches off 13. Rtn2NmlTm HH/MM Adiabatic cooling off delay 14. Fan Max Volts Value in Volts Fan Sequencer setup or Variable Speed 15. Fan Min On Volts Value in Volts Fan Sequencer setup or Variable Speed 16. VS Min on Percentage Value in Percent Variable speed minimum on percentage 17. VS Inc VPM Rate Value in Volts Rate at which the variable speed increases when pressure is above the TD Deadband. 28 of 75

29 18. VS Dec VPM Rate. Value in Volts Rate at which the variable speed decreases when pressure is below the TD Deadband. 19. Seq Step Volts Value in volts Incremental output voltage for Fan Seq mode. 20. VS Inv Reset PH Numeric Value Number of variable speed inverter resets per hour after a failure. 21. VS InvRst Delay HH/MM/SS Variable speed inverter reset delay 22. VS Fault ActLvl Open/Closed/NA Defines input state for fault condition. 23. Fan Output Num1-8 Output 1-4/NDF Relevant to the number of fans input on General screen. Assigns output stage number to each condenser stage. 24. Fan HP or Amps1-8 Numeric Value Value used for display only Inputs 1. Suction Pressure setpoint Pressure Value 2. Condenser TD setpoint Pressure Value PAK Inputs 1. Liquid Level Min Value in Percent The min level of the receiver range which the level indicator covers 2. Liquid Level Max Value in Percent The max level of the receiver range which the level indicator covers 3. Liquid Level Min V Value in Volts Voltage at which the level indicator is at its minimum 4. Liquid Level Max V Value in Volts Voltage at which the level indicator is at its maximum 5. Use high temp discharge ON/OFF/NOTACT Selects special high temperature sensor configuration, as opposed to standard or none. 6. Suction Transduser size 100lb/200lb 7. Condenser CT amp size Value in amps 8. Compressor CT amp size Value in Amps 9. Suction Pressure offset Pressure Value Calibration purposes 10. Discharge Pressure offset Pressure Value Calibration purposes 11. Ambient Temp offset Temperature Value Only applies to ambient sensor Input Type1-16 User Defined 16 user definable inputs on the PAK. Use & Lookup highlight selection and press n 29 of 75

30 Outputs Not used except for logging. PAK Outputs 1. Output Type1-8 User Defined 8 user definable digital outputs on the PAK. Use & Lookup highlight selection and press n 2. Analog Type1-4 User Defined 4 user definable analog outputs on the PAK. Use & Lookup highlight selection and press n 3. Act level 1-4 ON/OFF/NOTACT Invert control output voltage. (0-5v off 5-0v on) Fixed Steps Menu appears if compressor strategy is set to fixed steps. This assigns the compressor groups to stages. Safety 1. Disch Trip Setpoint Pressure Value Shutsdown all compressors if this limit is exceeded 2. Reset Diff Pressure Value Discharge trip reset differential 3. Disch Reset Delay HH:MM:SS Pack resets after this delay has timed out if the discharge pressure falls below trip setpoint less differential level. 4. Disch Auto Rst Numeric Value Number of times it will automatically reset a discharge trip before it locks out. Then requiring a manual reset. 30 of 75

31 Third Party Pack Controller Setup Add the required type and number of pack controllers under Connected I/O Boards & Controllers in Network Status Setup. [Shortcut: * Y42] There are 3 types of pack controller that are listed on this page. WTPK are TX pack controllers, WPK are Microm pack controllers and PAK are CPC pack controllers. Press ( Home. Press %Xt. If there is only one pack controller created, then this will take you directly into the pack controller page. If there are multiple controllers created, then this will take you to a pack controller selection list. Select the pack controller to be edited, and press n. Setup [Shortcut: %Xt Select Pack Controller n *B] At the top of the screen you will see the titles of each of the pages in controller setup. You can navigate these pages by using the! Keys Previous and Next Tab. For TX Pack Controllers (WTPK) Name the pack controller using the correct protocol. Set Hussman Yes/No. This is for the type of configuration in which the packs have been wired. Hussman No, would select the Space Cooling wiring configuration. Set the pack controller pressure engineering units for either PSI or BAR. Use the connected function YES/NO to switch the pack controller on or off within the software. The default is set to off (Connected - No). While the controller is set to off no alarms will be created if the physical controller is not present on the network. This facility enables the total addition of all controllers which can then be switched on individually when they are physically present on the network. Under Grp1 Num Comps, input the number of compressors on the pack. Under Grp1 Usage, input whether the pack is LT or HT. To do this, highlight, press & Look up, select LT or HT, then press n. Under Cond Num Fans input the number of condenser fans on the pack. If it is a dual temperature pack then input the number of compressors in Grp1 and Grp2 and input whether that group is LT or HT. ( Grp2 Usage does not appear until you insert a number into Grp 2 Num Comps ) Press s+$ Set logging on the Suction and Discharge pressure. 31 of 75

32 Highlight the sensor to be logged then press *7 Logging Setup. The box Logging Group Cell is automatically highlighted press & select Base Log and press n. Base Log should then appear in the Logging Group Cell box. Press ). The suffix L indicates whether this sensor is now logging but you will have to refresh the sensor page before it shows. Complete setting up the logs on each of the sensors by repeating this paragraph then press ) *B s+$ to check whether the suffixes appear to prove they are logging. Press ( Home For Woodley Pack Controllers (WPK) These are Microm pack controllers. CPC refer to these as Woodley Pack Controllers because they sit on a Woodley third party highway. Name the pack controller using the correct protocol. Set the pack controller pressure engineering units for either PSI or BAR. Input the number of condenser fans as 0 (Zero) under Num Condensers. Press s+# Set logging on the suction and discharge pressure (See TX pack controllers). Press ( Home Note: The Microm pack controllers must be set to sys of 75

33 Section Five Setting Up an IRLDS This section shows how to setup the Einstein to connect to an infrared leak detection unit (IRLDS). Add an IRLDS under Connected I/O Boards & Controllers in Network Status Setup. Add a logging group under Add Control Application Logging Group. Under Edit Existing Application Name it Leak Detection and give it 1500 samples. Set the Log Interval to (number of channels x 30 seconds). Please refer to previous sections of the manual. E.g. seven channel site (7 x 30 = 210 seconds = 3 ½ minutes 0:3:30) Press %L Leak Detection. If there is only 1 leak detection unit it will take you directly into it. If there are multiple leak detection units the Einstein will bring up a list of the units from which you need to select the one you require. Press *B Setup At the top of the screen you will see the titles of each of the pages in IR Leak Detection. You can navigate these pages by using the! Keys Previous and Next Tab. General [Shortcut: %L*B] Leave the unit name as default unit Leak DetectXXX. Enter the number of channels (Zones) that are installed onsite. E.g. If 2 unit s onsite Designation would be Leak Detect001 & Leak Detect002 Outputs [Shortcut: %L*B@] These outputs are set at default logging. Change this to the Leak Detection Logging that has been setup. Highlight each output and follow the following procedure. Press *7. Base log will be highlighted. Press & and scroll to Leak Detection and press n. The Logging Group Cell has now changed to Leak Detection. Press ) Back. Zone Names [Shortcut: %L*Bs+#] Enter the names of the zones according to Tesco terminology (At the rear of this manual) 33 of 75

34 Press ( Home Setting Up an Analogue Sensor Control as part of the IRLDS Setup Each of the zones on the IRLDS have to be tied to an Analog Sensor Control Control application for alarming purposes. Create a number of Analog Sensor Control equal to the amount of zones on the unit under Control Applications. Press $ Sensors Select the Analogue Sensor that you want to setup from the list and press n. Press *B Setup At the top of the screen you will see the titles of each of the pages in Sensor Control AV. You can navigate these pages by using the! Keys Previous and Next Tab. General [Shortcut: $ Select the Analog Sensor n*b] Name the Sensor using the correct terminology e.g. LT1 REF.LEAK. Full terminology is found at the rear of this manual. Change the engineering units to PPM (Parts per million) using & Look up. Inputs [Shortcut: $ Select the Analog Sensor n*b@] The default input page is looking for a Board and Point number. Change this to Controller: Application: Property by pressing #12. Under Controller press & and select the IRLDS unit. Scroll to Application and press & n to select. Scroll to Output and type in the OUTPUTX X being the zone number that this input is looking at. Setpoints [Shortcut: $ Select the Analog Sensor n*b s+$] Set Cutin at 200 and Cutout at 195. Outputs [Shortcut: $ Select the Analog Sensor n*b s+%] This Section only applies to the Zones which have Strobes/Sirens i.e. coldrooms 34 of 75

35 CPC Strobe Panel Activated Strobes/Sirens If the coldroom strobes/sirens are being set off via a CPC Strobe panel then an 8RO must be added to the Einstein (Use Connected I/O Boards & Controllers in Network Status Setup ) Input the relevant 8 RO Board Address and Point number in Command Out that the strobe/siren is wired into. I.e. The output board inside the strobe panel has 8 relays. Each of the coldroom strobes/sirens will be wired into one of these relays. Input the relevant relay by putting in a number 1-8 under Point. If the DFMC s are activating the strobes/sirens then leave the Board and Point blank. From the Home Screen DFMC Activated Strobes/Sirens [Shortcut: Select DFMC n*bs+#] Inputs Under Leak Alarm Controller press F7 and select RX300 (The Einstein) press n. Scroll to Application press F7 and select the Analog sensor that corresponds to this DFMC press n. I.e. Link the Produce Coldroom DFMC to the Analogue sensor that you have created for this room. Under Output press & and select Command Out press n. Press ( Note: The physical DFMC has to be changed to Gas for the Strobe/siren to activate via the Einstein. Do this using the Danfoss Handheld Unit. Alarms [Shortcut: $ Select the Analog Sensor n *Bs+^] Set Alarm HI Limit at 200 Notices [Shortcut: $ Select the Analog Sensor n *B s+&] Set Notice Hi Limit at 50 Set Notice Delay to (number of channels x 30 seconds x 3) E.g. seven channel site (7 x 30 x 3 = 630 seconds = 10 ½ minutes 0:10:30) Press ( Home 35 of 75

36 Output 8 on the strobe panel is for the enunciator siren on the enclosure. This is to activate at the same time as any one of the coldroom zone strobes. To do this setup a digital combiner. Setting up a Digital Combiner Add a digital combiner using Add Control Application [Shortcut: *Z1] and Edit using Edit Existing Application [Shortcut: *Z2] found in Section 3 of this manual. General [Shortcut: *Z2] Name the Digital Combiner Strobe Annun enter the number of inputs. I.e. number of coldrooms. Change the Combination method to OR. Comb Ins [Shortcut: *Z2@] Assign a coldroom to each of these inputs. First change their designation from Board & Point to Controller, Application and Property. Press # Edit. Press 1 Alternate I/O Formats. Press 2 Controller, Application and Property. Do this for each of the Inputs. When changed to Controller, Application and Property highlight Input 1 Controller box Press & and select the RX300 Press n. Press Press ' to highlight the Application box Press & and select the first coldroom Press n. Press ' to highlight the Output box Press & and select Command Out, Press n. Repeat this sequence for each of the coldrooms. Outputs [Shortcut: *Z2s+$] Highlight the Output box and put in the Board & Point number which the Strobe enclosure Siren is attached (normally BD:1 PT:8) Press ( Home 36 of 75

37 Section Six Setting up Power Monitoring The power monitoring is a Control Application. Add the power monitoring by referring to the Add Control Application section in this manual. Edit the power monitoring by referring to the Edit Existing Application section in this manual. When you have selected the power monitoring for editing there is a list of all the power monitoring points that have been created. Highlight the point to setup and press enter. General [Shortcut: *Z2&Highlight Pow Mon nnhighlight Mon Point n] Name the monitoring point e.g. Main, Bakery, Hot Chicken. Next Tab Twice Inputs [Shortcut: *Z2&Highlight Pow Mon nnhighlight Mon Point n@@] Enter the board and point number of the input which you have wired it into. E.g. if it is the first 16AI and terminal 12 then the board is 1 and the point number is 12. It will now ask you to select the type of sensor for this input press any key. Highlight the sensor type and press F7 Lookup Scroll down, highlight Pulse Accum. Press Enter. Press ) Back. Other factors are needed to complete the setup of power monitoring which are site specific. Please contact CPC for further information. 37 of 75

38 Section Seven Hardware Setup Gateway Setup The Gateway Should be situated at the end of the Danbuss/Microm (Woodley 3 rd Party) Network. Jumpers J1, J2, J3 are for setting End of Line (EOL) on the Danbuss/Microm network. The jumpers should be set closest to the J2 plug for termination/eol. Inboard signifies middle of line. Jumpers J4, J5, J6 are for setting EOL on the Einstein network. The jumpers should be set closest to the J3 plug for termination/eol. Inboard signifies middle of line. The Dip switches should have No. 6 up (ON) All others should be down (OFF). The Gateway needs to be programmed with the number and range of cases that it will be looking for on the network it will be connected to. You will need a CPC handheld for the next procedure. The gateway should be programmed with all the networks disconnected. Plug in the CPC handheld to its socket on the gateway. The first screen that shows is the gateway type and revision number. There are two distinct gateway types the first is the DFMC gateway and the second is the Woodley gateway. 38 of 75

39 DFMC Gateway Only DFMC controllers can operate on this gateway and network. Press / to scroll to the second screen. Press the right arrow to input the first DFMC address number on the particular network you are programming for. Press the right arrow again and input the number of units which are on the network. E.g. Network 1 Starts with First Unit 01 and has 28 DFMC s. Offset 0 Network 2 Starts with First Unit 29 and has 28 DFMC s. Offset 0 Network 3 Starts with First Unit 57 and has 28 DFMC s. Offset 0 Network 4 Starts with First Unit 85 and has 28 DFMC s. Offset 0 It is normal practice to set a couple of spares up on the gateway for adding in DFMC s at a later date without the need for reprogramming the gateway. Just add 2 to the number of DFMC s when calculating. E.g. Network 1 Starts with First Unit 01 and has 28 DFMC s and 2 Spare. Offset 0 Network 2 Starts with First Unit 31 and has 28 DFMC s and 2 Spare. Offset 0 Network 3 Starts with First Unit 61 and has 28 DFMC s and 2 Spare. Offset 0 Network 4 Starts with First Unit 91 and has 28 DFMC s and 2 Spare. Offset 0 If the number of addresses exceeds 120 an offset has to be put in the gateway and the bit switches on the DFMC s should start back at 1. E.g. Network 5 Starts with First Unit 121 and has 28 DFMC s and 2 Spare. Offset 120 In most cases the DFMC 120 will fall mid network. The offset has to be put in for the whole of that network. E.g. Network 5 starts at DFMC 110 and finishes at DFMC 135 the gateway should be set with an offset of 109 and the relevant DFMC s need to be addressed starting with 1 again. Woodley Gateway (Combo) Known as a Woodley Combo Gateway because this gateway will accept Microm & TX case controllers, Microm pack controllers and TX pack controllers. These can all operate on the same network. The second screen on this gateway is for inputting Microm & TX case controllers. Press the right arrow to input information on this page. Follow the same procedure as for DFMC gateway programming starting with First Unit 1. Even if these Microm/TX controllers are on the same site as DFMC s, the addressing is separate. Press the Down Arrow to scroll to the third screen. This page is for inputting TX pack controllers. Press the right arrow to input information on this page. Press the Down Arrow to scroll to the fourth screen. This page is for inputting Microm pack controllers. Press the right arrow to input information on this page. There is no distinction between Microm and TX controllers within the gateway. Microm and TX controllers can have the same controller address numbers as DFMC s as they are on different networks and Gateways. 39 of 75

40 Combo Gateway Protocol Suggested Protocol. Einstein User Guide Rev 1.12 April 2006 The following protocol is recommended. It has been listed to show what should be input into the gateway with the CPC handset Controller Addresses Handset Input Information Address WCC Handset Offset 2 Address WTPK Handset 1 20 Offset 119 (Limited high address) Address WPK Handset 1 20 Offset 221 WCC should start with 1 and X range. (Even if there are pack controllers in the middle of them) No two addresses can be the same between the WCC, WTPK, WPK if they are using the same combo gateway. Guardian Pack Controllers (eg RCC X) SET the Comms mode to SYS6 (the controller will only answer on one Third party address) the address it will answer on is 2 higher than the address set in the unit menu. 16 AI Setup 40 of 75

41 8RO Board Setup Network Configuration Einstein I/O Net DanBuss devices 3-30 Gateway Start: 1 Num: 31 Offset: 0 MC 1 MC 2 MC 31 AKC 114 K1 K3 K4 24 V AC J2 RS485- RS485+ DanBuss J3 J4 (HH) I/O Net 41 of 75

42 TESCO TERMINOLOGY Einstein User Guide Rev 1.12 April 2006 Section Eight The following set of guidelines will be used in future for Einstein whether it is using Microcools, Microms, or IRLDS. SYSTEM NAMES The pack number will be first followed by the system number and then the description. Examples, HT1 S106 DAI ( HT1 Pack, system 106, Dairy ) HT3 S084 RIM ( HT3 Pack, system 84, roll in milk ) LT1 S023 FFF ( LT1 Pack, system 23, Frozen food freezer ) There must be a space between the pack and system number. All systems will be named in this way, if you have a system for example ( HT8 S122.2HTMD ) you will not be able to have a space between the system number and the description as we can only use fourteen characters, the longest description has four characters so this is the worst case scenario. BAF Bakery Freezer BFC Butter & Fats Chiller BKD Back Deli Storage BUF Butchery Freezer BUC Butchery Chiller CAFC Staff Restbite Chiller CAFF Staff Restbite Freezer CCC Customer Collection Chiller COFC Customer Coffee Shop Chiller COFF Customer Coffee Shop Freezer DAC Dairy Chiller DAI Dairy DEL Delicatessen FFF Frozen Food Freezer FFM Frozen Food Multideck FFT Frozen Food Top ( Glass Door ) FFW Frozen Food Well FFGD Frozen Food Glass Door FFZ Fish Frozen FIC Fish Chiller FIF Fish Freezer FIM Fish Multideck FMSO Fresh Meat Serveover FVC Fruit & Veg Chiller F&V Fruit & Veg Case HGD Half Glass Door and Well HSC Home Shopping Chiller HSF Home Shopping Freezer HTMD Multi Purpose Case ICE Ice Cream ICF Ice Cream Freezer MBD Meat Based Dairy MFM Meat Fresh Multideck MFW Meat Fresh Well MLC Milk Coldroom NZM Meat Multideck ( LT) NZW Meat Well ( LT ) PAT Patisserie PDC Produce Chiller PRC Provisions Chiller RIM Roll In Milk SAND Sandwiches SLD Salad IRLDS The naming of the IRLDS channels on the Einstein will use the same descriptions as above, here are some examples, LT1 REF.LEAK HT6 REF.LEAK BFC REF.LEAK 42 of 75

43 Appendices 43 of 75

44 Using The Einstein Short Form When not in use the backlight to the LCD screen switches off, to view information press any key to illuminate display. The default screen is a summary of all the systems with temperature monitoring. Use j and k keys to view additional systems. The Alarm air temperature displayed on the summary screen is the same as the value on the case temperature display. To view more detailed information regarding individual cases/coldrooms Log on to the Einstein. Logging On Press ENTER key and enter your user name, press / key and enter password followed by Enter key. Navigation Between Menu`s The home page of the Einstein will be set to show a summary of the majority of equipment in the store, to navigate to other listings use the following directions from the home page. To go to Microm / TX Woodley controllers press % (more) and then press 5 (WCC). To go to Microcool controllers press % (more) and then press D ( DFMC ). To go to pack controllers press % (more) and then press 7 (Woodley packs). To go to older systems with hard wired probes (old MK3 / 4 Woodley systems) press % ( more ) and then press 4 ( circuits ) these are not present on all sites. To go to hard wired plant fault information press % (more) and then press 6(sensor control). Viewing Individual Case/Coldroom Controllers, Microcool / Microm / TX Woodley Move cursor using / and [ keys and highlight the relevant system name. Press n key and the detailed status information is displayed. To graph any temperature move cursor using /& [ keys to highlight value. Press & key and the graph will be plotted. Use keys to zoom in and out. After Zooming into a graph use the ; and ' keys to move graph window forwards and backwards in time. Press ) key to return to status screen. Press )again to return to summary screen. Case Cleaning for Microcool controllers To switch cases into Fans only mode use the key-switch on the individual case. To initiate a manual defrost use the Danfoss Hand Held terminal. Case Cleaning for Microm controllers To switch cases into Fans only mode use the key-switch on the individual case. To initiate a manual defrost use the Microm setup unit (cabinet/coldroom display). Viewing Individual Pack Controllers Press enter to see a summary of all the pack controllers or use /& [keys to highlight the individual pack you require and press enter for the detailed pack status screen. Pack controller type dictates the amount of information available with regards to compressor / condenser and pack alarm status. To view graphs of suction and discharge pressures follow the graphing instructions for case/coldroom controllers. Viewing Individual Case/Coldroom Temperatures using hard wired probes Move cursor using / and [ keys and highlight the relevant system name. Press n key and the detailed status information is displayed. To graph any temperature move cursor using /& [ keys to highlight value. 44 of 75

45 Press &key and the graph will be plotted. Use # keys to zoom in and out. After Zooming into a graph use the ; and ' keys to move graph window forwards and backwards in time. Press )key to return to status screen. Press )again to return to summary screen. Case Cleaning To inhibit temperature alarms whilst cases are in fans only mode or switched off for cleaning the following procedure should be followed. From summary screen highlight the name of the system to be inhibited Press &key Press n if screen with Access Denied is displayed Press &, and move cursor to select clean. Press enter to select. Press )to return to home screen. The selected case will now show wash. It will stay in wash (clean) mode until it is manually ended (see next paragraph) or for a period of 12 hours. When case cleaning is completed and the system is returned to refrigeration the above procedure should be repeated however End Manual mode should be selected in place of clean. Hard wired Plant Faults To view the status of hard wired plant faults press enter to view the summary or scroll to the individual fault using /& [ and highlight the fault required and now press enter for more information. Alarms Press ^ key to view alarm advisory log. Use j and k keys to view additional alarms To view expanded information regarding an alarm move cursor over entry in alarm log using / and [ keys and press &key. Each line in the advisory log details the time/date of the record entry, type (i.e. Alarm, Notice or Fail) and details of the condition. If the Alarm or Fail condition returns to normal an N prefixes the status (i.e. N-Alm, N-Fail). The time the condition returned to normal can be viewed on the expanded information page. Press Any key to return to alarm advisory log. Press ( to return to home screen. Log Out To log out return to the home screen using either (Home or )Back. From here press * Actions and a menu screen will appear and in that list will be an option to log out. The X button must be pressed but as this button has two functions the s button must be pressed at the same time as the X button, this will log you out of the panel. The Einstein panel will automatically log out any user after 30 minutes of inactivity 45 of 75

46 Pack Wiring Information 46 of 75

47 Linde TX Pack Controller Format Einstein User Guide Rev 1.11 September 2004 Controller 1 Pack 1 (HT/LT) Controller 2 Pack 2 (HT/LT) For Dual Temperature Packs Transducer 1 Transducer 2 Digital Inputs 4 Channel Relay 4 Channel Relay 4 Channel Relay Output 4 Channel Relay 4 Channel Relay 4 Channel Relay Output Board Output Board Board Output Board Output Board Output Board 8 Channel Input Board 8 Channel Input Board 8 Channel Input Board Address 0 Address 1 Address 2 Address 3 Address 4 Address 5 Address 0 Address 1 Address 2 K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 IP1 Condenser Compressor 1 IP1 Fan Fault Fault IP2 IP2 Compressor 2 Fault K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 IP3 IP3 Compressor 3 Fault IP4 IP4 Compressor 4 Fault K3 Compressor 3 K3 Compressor 7 K3 K3 Compressor 3 K3 Compressor 7 K3 IP5 Low Level Compressor 5 IP5 Liquid Alarm Fault IP6 Main LP Fault Compressor 6 IP6 (Suction) Fault K4 Compressor 4 K4 Compressor 8 K4 K4 Compressor 4 K4 Compressor 8 K4 IP7 Main HP Fault Compressor 7 IP7 (Discharge) Fault IP8 IP8 Compressor 8 Fault IP1 IP2 IP3 IP4 IP5 IP6 IP7 IP8 Compressor 9 Fault Compressor 10 Fault The Linde configuration does not use any output boards for controlling the fans. They are controlled by a separate variable fan speed controller. Addresses are kept consecutive. For smaller configuration packs the number of output boards required would decrease but the addresses would still stay in consecutive order. i.e. if the format shown above only had 8 compressors on controller1, only 2 relay boards would be required. Controller 2 would then start with address 2 and continue consequetively. Hussmann TX Pack Controller Format Controller 1 Condenser Controller 2 Pack 1 (HT/LT) Controller 3 Pack 2 (HT/LT) For Dual Temperature Packs Transducer 1 Transducer 2 Transducer 3 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board Digital Inputs 8 Channel Input Board 8 Channel Input Board 8 Channel Input Board Address 0 Address 1 Address 5 Address 6 Address 7 Address A Address B Address C Address 0 Address 1 Address F K1 Fan Stage 1 K1 Fan Stage 5 K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 IP1 Fan Fault 1 IP1 Compressor 3 Fault IP1 Condenser Overide IP2 Fan Fault 2 IP2 Compressor 4 Fault IP2 Suction 1 Overide K2 Fan Stage 2 K2 Fan Stage 6 K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 IP3 Fan Fault 3 IP3 Compressor 5 Fault IP3 Suction 2 Overide 47 of 75 IP4 Fan Fault 4 IP4 Compressor 6 Fault IP4 Low Liquid Level K3 Fan Stage 3 K3 K3 Compressor 3 K3 Compressor 7 K3 K3 Compressor 3 K3 Compressor 7 K3 IP5 Fan Fault 5 IP5 Compressor 7 Fault IP5 Pack Shutdown K4 Fan Stage 4 K4 K4 Compressor 4 K4 Compressor 8 K4 K4 Compressor 4 K4 Compressor 8 K4 IP7 IP6 Fan Fault 6 IP6 Compressor 8 Fault IP6 IP8 Compressor 1 Fault Compressor 2 Fault IP7 Compressor 9 Fault IP7 IP8 Compressor 10 Fault IP8

48 Einstein User Guide Rev 1.11 September 2004 Space TX Pack Controller Format Controller 1 Pack 1 (HT/LT) Controller2 Pack 2 (HT/LT) For Dual Temperature Packs Controller 3 Condenser Transducer 1 Transducer 2 Transducer 3 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board 4 Channel Relay Output Board Digital Inputs 8 Channel Input Board 8 Channel Input Board 8 Channel Input Board Address 0 Address 1 Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 0 Address 1 Address F K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 K1 Compressor 1 K1 Compressor 5 K1 Compressor 9 K1 Fan Stage 1 K1 Fan Stage 5 IP1 K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 K2 Compressor 2 K2 Compressor 6 K2 Compressor 10 K2 Fan Stage 2 K2 Fan Stage 6 IP3 K3 Compressor 3 K3 Compressor 7 K3 K3 Compressor 3 K3 Compressor 7 K3 K3 Fan Stage 3 K3 IP5 K4 Compressor 4 K4 Compressor 8 K4 K4 Compressor 4 K4 Compressor 8 K4 K4 Fan Stage 4 K4 IP7 IP2 IP4 IP6 Condenser Fan 1 Fault Condenser Fan 2 Fault Condenser Fan 3 Fault Condenser Fan 4 Fault Low Level Liquid Alarm Main LP Fault (Suction) Main HP Fault (Discharge) IP8 Oil Fault IP8 IP1 Compressor 1 Fault IP2 Compressor 2 Fault IP3 Compressor 3 Fault IP4 Compressor 4 Fault IP5 Compressor 5 Fault IP6 Compressor 6 Fault IP7 Compressor 7 Fault Compressor 8 Fault IP1 IP2 IP3 IP4 IP5 IP6 IP7 IP8 TX Controller Alarm Common Pack Alarm Common Pack Alarm 8 Channel Input 8 Channel Input 8 Channel Input 8 Channel Input Board Board Board Board Address 0 Address 1 Address 2 Address F 6/8 Fan Configuratio n IP1 IP2 IP3 IP4 IP5 IP6 IP7 Condenser Fan 1 Fault Condenser Fan 2 Fault Condenser Fan 3 Fault Condenser Fan 4 Fault Low Level Liquid Alarm Main LP Fault (Suction) Main HP Fault (Discharge) IP1 IP2 IP3 IP4 IP5 IP6 IP7 IP8 Oil Fault IP8 Condenser Fan 5 (Or 5+6) Fault Condenser Fan 6 (Or 7+8) Fault Compressor 1 Fault Compressor 2 Fault Compressor 3 Fault Compressor 4 Fault Compressor 5 Fault Compressor 6 Fault IP1 IP2 IP3 IP4 IP5 IP6 IP7 IP8 Compressor 7 Fault Compressor 8 Fault Compressor 9 Fault Compressor 10 Fault IP1 IP2 IP3 IP4 IP5 IP6 IP7 IP8 TX Controller Alarm Common Pack Alarm Common Pack Alarm Addresses are kept consecutive. For smaller configuration packs the number of output boards required would decrease but the addresses would still stay in consecutive order. i.e. if the format shown above only had 8 compressors on controller1, only 2 relay boards would be required. Controller 2 would then start with address 2 and continue consecutively. 48 of 75

49 Einstein User Guide Rev 1.11 August 2004 General Drawings 49 of 75

50 Einstein User Guide Rev 1.11 August of 75

51 Einstein User Guide Rev 1.11 August of 75

52 Einstein User Guide Rev 1.11 August of 75

53 Einstein User Guide Rev 1.11 August of 75

54 Einstein User Guide Rev 1.11 August of 75

55 Einstein User Guide Rev 1.11 August of 75

56 Einstein User Guide Rev 1.11 August of 75

57 Einstein User Guide Rev 1.11 August of 75

58 Einstein User Guide Rev 1.11 August of 75

59 Einstein User Guide Rev 1.11 August of 75

60 Einstein User Guide Rev 1.11 August of 75

61 Einstein User Guide Rev 1.11 August of 75

62 Einstein User Guide Rev 1.11 August of 75

63 Einstein User Guide Rev 1.11 August of 75

64 Einstein User Guide Rev 1.11 August of 75

65 Einstein User Guide Rev 1.11 August of 75

66 Einstein User Guide Rev 1.11 August 2004 Multiflex PAK controller Hand Held Terminal operation 66 of 75

67 Einstein User Guide Rev 1.11 August 2004 Table of contents: Overview...68 Communication Settings...69 Scrolling information screens...70 Configuration Screens...72 General Options...72 Compressor Set Points...73 Parameter Listings: of 75

68 Einstein User Guide Rev 1.11 August 2004 Overview The Hand Held terminal provides the user with immediate real time information as to the status of the Multiflex PAK controller, and permits initial configuration and temporary parameter changes to be made. This document describes the features and how to navigate through the screens. Any settings input by the hand held terminal will immediately be overwritten by the Einstein upon disconnection of the hand held terminal. LED Status display area F1 -Configuration F2 - Status Navigation arrow keys Cancel Navigation arrow keys Enter Numeric data entry keys. / - data, or ON/OFF select Multiflex Controller After connecting the hand held terminal into the J1 connector (adjacent to the network connection) of the Multiflex PAK controller, the opening screen will be briefly displayed 68 of 75

69 Einstein User Guide Rev 1.11 August 2004 The Multiflex controller platform is part of a family of CPC refrigeration and plant controllers. This particular application is PAK. This information is displayed on the main screen in conjunction with the software revision. The bottom line of this screen will normally display Press Down Arrow Key, if there are no communications with the system Einstein controller, this message will state FAIL: I/O NET Communication Settings Pressing the down arrow will lead to the communication settings screen. The network address and communication baud rate are defined by positioning the S3 DIP switches on the Multiflex controller. These are set during initial commissioning and should not be modified in normal operation. 69 of 75

70 Einstein User Guide Rev 1.11 August 2004 Scrolling information screens Pressing the down arrow again, leads to a series of scrolling information screens. Pressing the F2 button on the keypad has the same effect. These screens will continually scroll through in sequence. Pressing any key will interrupt this scrolling and the screens can be navigated by using the up / down arrow keys. Suction / Discharge pressures are shown, in conjunction with the Air On 1 temperature (if used). Discharge temperatures for all compressors are displayed on the next screen. Condenser TD This is the actual Delta T between the Condensing temperature, and the Air On condenser temperature averaged across both temperature sensors Condensing temperature & Discharge Pressure. If only one Air On sensor is fitted, a single value is used. Suction Pressure (Actual). Dead Band & Set Points are displayed. The Dead Band setting is applied equally split across the set point. i.e in this instance, the Cut-In will be above 47Psig and Cut-Out will be below 43Psig. The last line indicates the compressors or groups that are currently running. Common Suction temperature, Compressor running current, Condenser fan running current and Liquid receiver refrigerant level are all displayed on this screen. 70 of 75

71 Einstein User Guide Rev 1.11 August 2004 Output Summary: Condenser water spray, LT Pack liquid injection system and alarm output (if available) are shown. The condenser fan configuration is shown on this screen. There are 4 possible stages available. This illustration is showing 4 fans running (2 stages of 2 fans / stage) Compressor stages are depicted in a similar manner. Up to 16 stages of capacity control can be configured; this screen is showing the stages running. Mode Screen: In this screen, this example is illustrating that the all compressors are running, the pack is operating at maximum capacity. Additionally the condenser is showing a failed pressure transducer. 71 of 75

72 Einstein User Guide Rev 1.11 August 2004 Configuration Screens Selecting the F1 button will take you to the main configuration selection screen. This is separated into 6 separate areas which are described below: In order to select each area, first press the Right Arrow key (an arrow will appear after the Select instruction on the bottom line), then the desired area number key (in this instance 1). To accept this choice, press the Down Arrow key (arrow disappears) then press the down arrow again. In order to make initial configuration changes, or temporarily modify these set points first select the desired parameter, this is done by using the Right Arrow key (an arrow will appear after the Select instruction on the bottom line), use the numeric keys to change analogue values. or - keys to toggle between options. General Options The first screen shown the controller name, in this instance it is HT7. Pressing the down arrow will take you through the General screens one at a time. The next screen shows the compressor and condenser fan stages. Here there are 9 stages of compressor used with 8 stages. The pack has been configured to stage up/down in single compressor increments. There are 6 condenser fans configured (but only 3 stages as shown later) The engineering units can be changed from here. Pressure options presently include PSI and KPA. Temperatures can read either Deg F or Deg C. The special code function is not unused. This Compressor / Condenser interlock facility enables the condenser fans to be disabled when the all compressors cycle off. 72 of 75

73 Einstein User Guide Rev 1.11 August 2004 Compressor Set Points Here you can set the compressor suction pressure control parameters. 73 of 75

Rev MultiFlex PAK Compressor/ Condenser Control Board User s Guide

Rev MultiFlex PAK Compressor/ Condenser Control Board User s Guide 026-1712 Rev 2 09-03-04 MultiFlex PAK Compressor/ Condenser Control Board User s Guide 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS RESERVED. The

More information

Rev MultiFlex I/O Board Installation and Operation Manual

Rev MultiFlex I/O Board Installation and Operation Manual 026-1704 Rev 5 03-10-06 MultiFlex I/O Board Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS RESERVED. The information

More information

Rev Cutler-Hammer Smart Breaker Panel Control Manual

Rev Cutler-Hammer Smart Breaker Panel Control Manual 026-70 Rev 0 6-0-03 Cutler-Hammer Smart Breaker Panel Control Manual 640 Airport Road, Suite 04 Kennesaw, GA 3044 Phone: (770) 425-2724 Fax: (770) 425-939 ALL RIGHTS RESERVED. The information contained

More information

Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher

Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher PR0334 PR0335 PR0332 PR0333 Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management Ltd 80 Johnstone Avenue,

More information

Intuitive and Plant Pack Controller Installation & User Guide

Intuitive and Plant Pack Controller Installation & User Guide Intuitive PR0650-PACK PR0650D-PACK ` Plant PR0600-PACK Intuitive and Plant Pack Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management UK OFFICE Resource

More information

Application Engineering B U L L E T I N. AE R1 November Intelligent Store Discus V1.0 Operators Manual

Application Engineering B U L L E T I N. AE R1 November Intelligent Store Discus V1.0 Operators Manual Application Engineering B U L L E T I N AE8-1337 R1 November 2006 Intelligent Store Discus V1.0 Operators Manual The Intelligent Store Discus product line has recently been introduced on 2D, 3D, and 4D

More information

Rev CH Breaker Gateway Installation and Operation Manual

Rev CH Breaker Gateway Installation and Operation Manual 026-1710 Rev 1 05-15-07 CH Breaker Gateway Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS RESERVED. The information

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

RGX COMMUNICATIONS GATEWAY

RGX COMMUNICATIONS GATEWAY RGX COMMUNICATIONS GATEWAY BTU Ventilation Corporation 47418 US Highway 10 Perham, Mn 56573 USA Phone (218) 346-7482 Fax (218) 346-7485 http:/// Manual ver 2.1 Copyright BTU Ventilation Corp 2008 RGX Communications

More information

Rev Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual

Rev Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual 026-1502 Rev 2 11-20-07 Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 30144 Phone: (770) 425-2724 Fax: (770)

More information

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015 ESC 201 Installation and Operating Instructions Manual SG-0002-03 Jan 2015 Table of Contents 1.0 FUNCTIONS... 5 2.0 FEATURES... 5 3.0 ESC 201 DESCRIPTION... 6 4.0 GENERAL OPERATIONS... 6 4.1 MANUAL MODE

More information

Intuitive Super Plant Pack Controller Installation & User Guide

Intuitive Super Plant Pack Controller Installation & User Guide Intuitive Super Pack PR0650-SUP PR0650-SUP-E1 PR0650-SUP-E2 PR0661 Intuitive Super Plant Pack Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management

More information

CommandCenter Operator Panel

CommandCenter Operator Panel CommandCenter Operator Panel Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start

More information

Dual Digital Module Technical Guide

Dual Digital Module Technical Guide Factory Packaged Controls Coil Products Dual Digital Module Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4

More information

COMPUTER PROCESS CONTROLS

COMPUTER PROCESS CONTROLS TECHNICAL BULLETIN Installation Instructions: ESR8 Valve Regulator (P/N 810-3195) Introduction The ESR8 Valve Regulator board (P/N 810-3195), shown in Figure 1, is a Lon- Works Echelon based electronic

More information

Millennium Simplicity Elite Parameter Points and Quirks

Millennium Simplicity Elite Parameter Points and Quirks Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The

More information

Product Manual SZ2141

Product Manual SZ2141 Product Manual SZ11 Refrigeration Controller Communicating Controls Description The SZ11 is a microprocessor-based refrigeration controller and alarm interface designed to control three coolers or freezers

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

UNIT CONTROLLER 8 (UC8) Modbus RTU communications

UNIT CONTROLLER 8 (UC8) Modbus RTU communications UNIT CONTROLLER 8 (UC8) Modbus RTU communications Date: 2 February 2018 UC8 Software version: 2.0.9 Issue: 5 Page 1 of 34 Contents 1. Introduction... 3 2. Available modbus functions... 4 3. Communications

More information

Product Manual SZ2144

Product Manual SZ2144 Product Manual SZ1 Refrigeration Monitor Communicating Controls Description The SZ1 is a microprocessor-based refrigeration monitor and alarm interface designed to monitor up to six coolers or freezers.

More information

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC.   RATING IS 1 AMP COND. B ENABLE COOL B ENABLE. Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above TECHNICAL BULLETIN Part #: 026-4122 Revision 0 Date: 2/5/2007 Control Techniques Variable-Speed Drive (VSD) Interface to E2 v. 2.40 and Overview Beginning with version 2.40, the E2 RX, BX, and CX series

More information

Rev 3 06-APR Modular Refrigerant Leak Detection Sensor (MRLDS) Installation and Operation Manual

Rev 3 06-APR Modular Refrigerant Leak Detection Sensor (MRLDS) Installation and Operation Manual 026-1307 Rev 3 06-APR-2010 Modular Refrigerant Leak Detection Sensor (MRLDS) Installation and Operation Manual 3240 Town Point Drive NW Suite 100 Kennesaw, GA 30144, USA Phone 770-425-2724 Fax 770-425-9319

More information

E2 RX Refrigeration Controller, E2 BX HVAC Controller, and E2 CX Convenience Store Controller Installation and Operation Manual

E2 RX Refrigeration Controller, E2 BX HVAC Controller, and E2 CX Convenience Store Controller Installation and Operation Manual 026-1610 Rev 3 10-17-05 E2 RX Refrigeration Controller, E2 BX HVAC Controller, and E2 CX Convenience Store Controller Installation and Operation Manual Computer Process Controls, Inc. 1640 Airport Road

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

Mercury T Controller Installation & User Guide

Mercury T Controller Installation & User Guide PR0700 Mercury - TM PR0701 Mercury - TE Mercury T Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management Ltd 80 Johnstone Avenue, Hillington Industrial

More information

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL 641-K31 1 BACVIEW INSTALLATION AND OPERATION IMPORTANT: This manual is for use with controller ZONE I/O 560 FHP part number 641-224

More information

FX 2 Instruction Manual

FX 2 Instruction Manual FX 2 Instruction Manual Climma Compact Version Annapolis MD USA 301 352 6962 info@veco-na.com Introduction: The FX2-DX digital controller operates onboard air conditioning equipment to provide room temperature

More information

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Service Bulletin SB685 Date: 8/18/2017 Subject: TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Units: All TriPac EVOLUTION Summary: This bulletin updates and

More information

4-step Chiller and Heat Pump Controller

4-step Chiller and Heat Pump Controller 4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW

More information

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units UNIT CONTROLLER 7 (UC7) Operation & Installation Hydronic Units Date: 1 November 2012 Issue: 5 Page 1 of 17 Contents 1. Connections, hydronic unit... 3 2. Functions assigned to SSR1, SSR2 and AUX... 3

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

Installation & Operation and Maintenance

Installation & Operation and Maintenance Gas Safety Products Dual Current Monitor Installation & Operation and Maintenance Read these instructions carefully before operating or servicing Rev: 01 Date: 12-02-18 1 CONTENTS Chapter Content Page

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Intuitive Transcritical CO2 Plant Controller Installation & User Guide

Intuitive Transcritical CO2 Plant Controller Installation & User Guide PR0651-STEP PR0651-STEP OIL ` Intuitive Transcritical CO2 Plant Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721,%&'#(+-./.+0.1.2*1/+3/)++ 45+6&71%/&1+891':+;

More information

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor Innovative Electronics for a Changing World NPM-R10-SNMP Remote Network Power Monitor Optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. SYSTEM BATTERY CONNECTIONS 3. SERIES CONNECTED BATTERIES

More information

SIMREX Corporation Your Trusted Wireless Solution Provider

SIMREX Corporation Your Trusted Wireless Solution Provider SIMSYNC Instruction Manual Traffic Controller Time/Date Synchronization/Coordination System Firmware Release 2.5h SIMREX MAN.SIMSYNC, Rev 13.0 FEBRUARY 2008 Your Trusted Wireless Solution Provider www.simrex.com

More information

Energy Management System. Operation and Installation Manual

Energy Management System. Operation and Installation Manual Energy Management System Operation and Installation Manual AA Portable Power Corp 825 S 19 TH Street, Richmond, CA 94804 www.batteryspace.com Table of Contents 1 Introduction 3 2. Packing List 5 3. Specifications

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review... TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...

More information

Innovative Electronics for a Changing World. Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring

Innovative Electronics for a Changing World. Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring Innovative Electronics for a Changing World Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring INDEX 1. SYSTEM DESCRIPTION 2. SYSTEM WIRING 3. SYSTEM

More information

V0STAT51P-2 Programmable Wired Controller

V0STAT51P-2 Programmable Wired Controller PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF V0STAT51P-2 Programmable Wired Controller Bulletin No. 210766 March 2016 Grouping - Controller can control up to 16 indoor units on the same

More information

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control

More information

FX2-CHILLER. Digital Control. Operations Manual

FX2-CHILLER. Digital Control. Operations Manual FX2-CHILLER Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 www.microair.net Allentown NJ 08501 Fax (609) 259-6601 Introduction: The FX2-CHILLER digital control

More information

INDEX. Network Power Monitor R10 SNMP

INDEX. Network Power Monitor R10 SNMP Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX Amended 21 March 2017: Add user defined Password see page 13 Add wire Connection

More information

Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+

Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+ Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+ The MCS Commitment: Our commitment is to provide practical solutions for the industry s needs and to be both a leader and partner in the

More information

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NETWORK HUMISTAT Compact, self-contained dehumidifier controller. 0.5 degrees C accuracy typical. RH sensor is digitally calibrated for 2% accuracy. Open communication

More information

Instruction Manual CTC-1

Instruction Manual CTC-1 Troubleshooting & Specs CTC-1 Amps / Volts requirements Min / Max operating temperature Min / Max operating Humidity Temperature Measurement range Temperature Accuracy CO2 sensor type CO2 Measurement range

More information

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION

More information

CONTROLS.COM. Bacnet and Modbus Modules. T3-22i. T3000 Building Automation System Overview. T3-8o. Ethernet MAIN NET1 RS485 SUBNET2 RS485.

CONTROLS.COM. Bacnet and Modbus Modules. T3-22i. T3000 Building Automation System Overview. T3-8o. Ethernet MAIN NET1 RS485 SUBNET2 RS485. TEMCO CONTROLS.COM Bacnet and Modbus Modules T3-22i T3000 Building Automation System Overview Building Operator T3-8o Ethernet Internet T3-BB T3-LB T3-TB T3-8o T3-22i Remote User MAIN NET1 RS485 TSTAT8

More information

BD Controller 101N07xx Series 24 V DC with Tool4Cool LabEdition software Operating Instructions

BD Controller 101N07xx Series 24 V DC with Tool4Cool LabEdition software Operating Instructions MAKING MODERN LIVING POSSIBLE with Tool4Cool LabEdition software Operating Instructions 2 DEHC.PS.100.I.02 1.0 Introduction 1.1 Applications... 5 1.2 Capability... 5 1.3 Functions... 5 1.4 Programming

More information

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,

More information

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification General The VT76xxW series is designed for single-stage and multi-stage control of water source heat pumps with dedicated

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel The heart of the Starzone 4000 system is the Starzone Master controller (SZM-4000). Each AHU that is to be zoned will have its own SZM-4000

More information

TPI (Turbine Pump Interface) Guide

TPI (Turbine Pump Interface) Guide (Turbine Pump Interface) Guide Using Franklin Fueling Systems Series Fuel Management System Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838

More information

Quick Start Guide. Variable Speed Drive. Part Number: Issue: 3

Quick Start Guide. Variable Speed Drive. Part Number: Issue: 3 EVC Series Quick Start Guide English Issue 3.book Page 1 Friday, March 11, 2016 1:38 PM Quick Start Guide Variable Speed Drive Part Number: 0478-0335-03 Issue: 3 Original Instructions For the purposes

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51 Dryer M720 Programming and Operation Manual July 15, 2015 Revision 1.51 Contents 1 Important Safety Information 1 1.1 FOR YOUR SAFETY - CAUTION!............................. 1 2 Control Overview 2 2.1

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

M1000 INTELLIGENT ZONE CONTROL SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3

More information

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide Quick Start Guide 560/583 DDC 8733914716(2014/02) Please refer to the included Hardware User s Guide and BACview Installation and Operation Manual for more detailed information on setting up and using

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

Installation & Operation Guide

Installation & Operation Guide Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

Graphical User Interface V1.0.3

Graphical User Interface V1.0.3 Graphical User Interface V1.0.3 Application User Guide 2015 MCI Solutions. All rights reserved. 240815-01 www.mcisolutions.ca Page ii Getting Started Table Of Contents Introduction.................................................

More information

Touchpad User Guide. National Sales. Product Support. Freecall: Ph:

Touchpad User Guide. National Sales. Product Support. Freecall: Ph: Touchpad User Guide National Sales Ph: 1300 306 125 sales@ias.net.au Product Support Freecall: 1800 354 434 support@ias.net.au Designed and Manufactured in Australia by: Innovative Air Systems Pty Ltd.

More information

PROGRAMMING GUIDE

PROGRAMMING GUIDE www.altroniccontrols.com PROGRAMMING GUIDE DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE/MACHINE OPERATION WHICH COULD WARNING: CAUSE PERSONAL INJURY TO OPERATORS OR OTHER NEARBY PERSONNEL.

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

2-Axis Counter BDD 622

2-Axis Counter BDD 622 2-Axis Counter BDD 622 Technical Description, User's Guide english No. 622-221 D/E. Edition 0701; Subject to modification. www.balluff.com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.f. Germany

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual

Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual 621 Hunt Valley Circle New Kensington, PA 15068 3015-5547 Tel: 724-334-5000 Revision 4 Fax: 724-334-5001 May 17, 2013 Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual

More information

BACnet MS/TP Interface User s Guide

BACnet MS/TP Interface User s Guide PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

AE R6 August CoreSense Protection for Copeland Discus Compressors

AE R6 August CoreSense Protection for Copeland Discus Compressors August 2018 CoreSense Protection for Copeland Discus Compressors TABLE OF CONTENTS SAFETY... 3 Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock,

More information

ADDENDUM WCFX. Vision 2020i Touch Screen Controller. - a1 - Vision 2020i Controller

ADDENDUM WCFX. Vision 2020i Touch Screen Controller. - a1 - Vision 2020i Controller WCFX Vision 2020i Touch Screen Controller - a1 - 1.4 VISION 2020i CONTROLLER AND TERMINAL 1.4.1.1 The fourteen touch keys: Key Description MAIN Display the main screen Vision 2020i controller is equipped

More information

Installing VO2 Analog Output Boards

Installing VO2 Analog Output Boards Chapter 3-6 VO2 Description and Identification Installing VO2 Analog Output Boards The VO2 Variable Output board provides an AKC 55 system with 2 variable outputs for control of loads like variable speed

More information

PduSetup User Manual. Professional Electronics for Automotive and Motorsport

PduSetup User Manual. Professional Electronics for Automotive and Motorsport Professional Electronics for Automotive and Motorsport 6 Repton Close Basildon Essex SS13 1LE United Kingdom +44 (0) 1268 904124 info@liferacing.com www.liferacing.com PduSetup User Manual Document revision:

More information

SP6R Level Controller Operation Manual

SP6R Level Controller Operation Manual SP6R Level Controller Operation Manual www.sjerhombus.com SP6R LEVEL CONTROLLER INTRODUCTION SJE-Rhombus, an industry leader in water and wastewater pump controls, introduces the SP6R Level Controller.

More information

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Section Page Introduction 1 Materials Provided 1 I) Safety Instructions 1 A) Inverter Safety Instructions 1 B) Battery Safety

More information

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new Controller.

More information

Measure & Control Temperature & CO2 levels with analog & digital I/O

Measure & Control Temperature & CO2 levels with analog & digital I/O MADE IN OZ HTC-DIGITAL-LCD PROGRAMMABLE TEMPERATURE CONTROLLER c/w YEARLY PROGRAMMABLE TIME SWITCH COMPATIBLE WITH A WIDE RANGE OF SENSORS ROOM O/A WALL DUCT PIPE Use Features Measure & Control Temperature

More information

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. HTC-DIGITAL-LCD Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. Features Use Australian Made and designed LCD 2 X 16 Character Backlit Display Five Programmable

More information

AE R6 July 2018 Electronic Unit Controller

AE R6 July 2018 Electronic Unit Controller July 2018 Electronic Unit Controller TABLE OF CONTENTS Safety... 3 Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons...

More information

Capacity controller AK-PC 710. Manual

Capacity controller AK-PC 710. Manual Capacity controller AK-PC 710 Manual Contents 1. Introduction...3 Application... 3 Function overview... 3 Principles... 4 2. Design of the controller...7 Module survey... 8 Common data for modules...10

More information

Trailer & Rail Refrigeration Units

Trailer & Rail Refrigeration Units EASY TO RUN X4 7300/7500 Trailer & Rail Refrigeration Units Display Display Screens Starting Unit IntelliSet Pretrip Changing Setpoint Start-Stop or Continuous Operation Data Recorder/Trip Start Manual

More information

PFC-10 Power Factor Controller

PFC-10 Power Factor Controller PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel

More information

ARCTIC AIR DC OLED. Digital Control Operations Manual

ARCTIC AIR DC OLED. Digital Control Operations Manual ARCTIC AIR DC OLED Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Before you start: 1. Applying power:

More information

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018 Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018 Tags: P-8 1800RPM Premium Efficient Motor 460/3/60 Pump and Motor Weight: 183lbs

More information

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging

More information

Model (DRS-54V) Ver. 2.0 August. Dongah Rectifier System Operating Manual

Model (DRS-54V) Ver. 2.0 August. Dongah Rectifier System Operating Manual 2011 Model (DRS-54V) Ver. 2.0 August DRS-54V Dongah Rectifier System AC 240V 1Phase 3WIRE Input -54VDC Output 55A per Shelf 18.5Amps per Module DONGAHELECOMM.LTD _ Proprietary This document contains proprietary

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS www.altroniccontrols.com INSTALLATION INSTRUCTIONS EXACTA 21 MONITORING AND CONTROL SYSTEM CAUTION: The EXACTA 21 CONTROL SYSTEM is CSA CERTIFIED FOR use in Class I, GROUPS C & D, Division 2 hazardous

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

REFRIGERATION AND AIR CONDITIONING. On Site Guide AK2-SC 255

REFRIGERATION AND AIR CONDITIONING. On Site Guide AK2-SC 255 REFRIGERATION AND AIR CONDITIONING On Site Guide AK2-SC 255 How to Use This Guide Read this Guide completely as you install and start up your new AK2-SC 255 controller. The guide will give you thorough

More information