4 SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Additional Agenda for the 80 th Meeting of Protection Coordination Sub-Committee of SRPC to be held on December, Grid Occurrences Additional Grid Additional Tripping Events that occurred during the period November, 2018 given at Annexure-I would be discussed in the PCSC meeting. Constituents are requested to furnish the following information in respect of the above grid occurrences to have fruitful discussions. (a) (b) (c) Single line diagram of the station with switching devices, CT, PT and relay details. Cause of the tripping & Remedial Action taken Relay setting details Constituents are requested to bring/ furnish full particulars of the tripping events pertaining to their system. 2. Conduction of Protection Audit of various Stations (Substations as well as Generation Switchyards) at Transmission & Distribution level and Model Protection Audit Formats You are kindly aware that at regional level protection audit of various 220 kv & above Stations (Substations as well as Generation Switchyards) are being conducted by different SRPC Teams (comprising members from different SR-Constituents) in line with CERC Order dated in respect of APTRANSCO Petition no: 95/MP/2015 and CERC Order dated in respect of TSTRANSCO's Petition no: 83/MP/2015. These audits are being conducted using the model protection audit formats given by the Consultant, M/s Tractebel Engineering, with some modifications (copy enclosed at ). However, since ensuring healthiness of protection systems at all stations (generation/ transmission/ distribution) is important for integrated grid operation, conducting protection audit of these stations assumes significance. While the issue is under discussion at national level bodies like NPC/ CEA, Hon ble CERC also vide their Order dated in Petition No. 09/ SM/ 2015 has directed RPC s to take up the issue of protection audit and relay setting in transmission system / distribution system within States with all concerned. In this regard, it is proposed to discuss the practices being followed by various SR-Constituents in conducting protection audit of their own stations and the help they are rendering to respective DISCOMs in this regard. Accordingly, APGENCO, APTRANSCO, TSGENCO, TSTRANSCO, KPCL, KPTCL, KSEBL, TANGEDCO, TANTRANSCO, KSEBL, PGCIL (SR-I) are requested to kindly submit & present the action being taken by them ***** Additional Agenda for the 80 th Meeting of PCSC scheduled to be held on December, 2018 Page 1

5 Grid Occurrences - 80 Annexure-I For all tripping events involving failure of substation equipment, Constituents are requested to kindly furnish the SLD or equivalent pictorial representation showing (i) Location of the fault, and (ii) Bus-bar arrangement/ Configuration of feeders and other connected equipment with proper CB positions (OPEN/ CLOSE) at the time of occurrence of the fault. I. Details of Grid Incidents: Sl. No. Details of Event Date &Time Reason Category Tripping of 400kV Kalpakka-Gazuwaka Ckt- 1 &2 Tripping of 400/220kV ICT-1 at Kaiga Tripping of 400kV Kaiga- Guttur Ckt-1 and 400/220kV ICT-1 at Kaiga. Tripping of 400kV Nellore PS SGPL Ckt-1 Tripping of 400kV Uravakonda-Veltoor Ckt at 16:47 Hrs at 09:14 Hrs at 16:00 Hrs at 20:20 hrs at 12:00 Hrs 400kV Kalpakka-Gazuwaka Ckt-1&2 tripped due to relay maloperation during through fault. SOTF protection maloperated due to problem with the settings and DT was sent to Kalpakka end. As reported, while opening od 400kV Kaiga-Guttur Ckt-1 at Guttur end for maintenance, LBB protection operated on pole discrepancy resulting in tripping of ICT-1 at Kaiga. As reported 400kV Kaiga-Guttur-Ckt-1 tripped on B-phase to ground fault. At the same time 400/220kV ICT-1 at Kaiga tripped on operation of LBB protection due to pole discrepancy. Y- phase to earth fault occurred in line due to snapping of GIS to Air bushing conductor at NCC switchyard. The conductor got grounded such that fault was being fed by NPS bus and there was earth fault and broken conductor start at SGPL end. NPS end got tripped in zone-2 due to non-receipt of carrier resulting in a 3 phase trip at NPS. After 500ms, earth fault occurred at SGPL end resulting in zone-1 operation and 3 phase trip. A/r was not attempted at SGPL end As per FIR, 400kV Uravakonda - Veltoor Ckt-2 tripped on operation of overvoltage Stage-1 at Uravakonda end and DT received at veltoor end. From the DR furnished, voltages at Uravakonda end are: Vr- 243kV, Vy-245kV and Vb-242kV. From the DR operation of Overvoltage Stage-1 protection could not be established. Over voltage grading of the line at Uravakonda end is 109%, 6secs, tripping is not as per grading. GI-2 GI-2 GI-2 GI-2 GI-2 Grid Occurrences to be discussed in the 80 th Meeting of PCSC scheduled to be held on December, /2

6 II. Details of Trippings due to Failure or Non-operation of Auto-Reclose: Annexure-I Sl. No. Element Date & Time Reason 1 Tripping of 400kV Gooty Nelamangala at 00:43 Hrs B-phase to earth fault occurred in line. Autoreclose was successful at Nelamangala end. At gooty end auto-reclose did not operate. Pole discrepancy operation was observed form EL of gooty end. After 8 sec, over voltage operation got operated at Gooty end resulting in DT send to Nelamangala and tripping of line III. Details of Trippings due to PLCC mal-operation: Sl. No. Element Date & Time Reason 1 Tripping of 400kV Ghani- Narnoor Ckt at 16:46Hrs 400kV Ghani - Narnoor ckt-2 tripped at Narnoor end on DT receipt due to mal operation of PLCC signal. Line did not trip at Ghani end. ***** Grid Occurrences to be discussed in the 80 th Meeting of PCSC scheduled to be held on December, /2

7 General Information: Substation Name: SS Voltage level: PROTECTION AUDIT REPORT Fault level of all Equipment (for both 3-ph & 1-ph faults at all voltage levels) Audit Team: Date of commissioning of the substation: Region: Audit Date: Name of the Utility which owns the Substation Name Southern Region Organization Name Auditee Team: Name Organization Name Attached Documents: 1 Detailed Single Line Diagram of the Substation 2 Protection Philosophy being followed 3 Adopted Relay Settings (given by Head Quarters/ Corporate Office) 4 Extracted Relay Settings (in PDF format) 5 Calculation Sheet(s) showing protection settings calculation for all feeders and transformers 6 AC Supply Changeover Scheme 7 Details on Periodicity of Relay Testing and latest Relay Test Reports Southern Region - (Station Name) 1/58 Page 1 of 58

8 Details of Measurement of Dependability & Security of PLCC Channels CT Characteristics at all Taps in case of multi-ratio CTs Details of Measurement of Station Earth-Mat & Earth-Pits Details & Settings of df/dt and UF Relays, if applicable Details of Special Protection Schemes details, if applicable (including implemented schematic diagram for SPS, test results, last operation records) Record of previous Trippings for last six months and associated Fault Analysis. Southern Region - (Station Name) 2/58 Page 2 of 58

9 (Capacity) MW Generator Unit-1 Protection Audit - check list No Relay configuration - Generator protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for Gen. Unit protection? 3 Are Group A and Group B protections connected to separate DC sources for Gen. Unit? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection 100% Stator Earth Fault protection 95% Stator Earth Fault protection 5 Inter-turn Fault protection Loss of Excitation protection Negative Phase Sequence Current protection Low Forward Power/ Reverse Power protection Out-of-step/ Pole slipping protection Over-Voltage protection Under-frequency protection Back-up Impedance protection Accidental back-energisation/ Dead machine protection Rotor Earth-Fault protection Thermal Over-load protection Breaker failure active Disturbance Report active 6 Connected to Trip Coil 1/Trip Coil2/Both 7 Feed from DC supply 1/DC supply2 Connected to dedicated CT core? 8 Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Southern Region - (Station Name) 3/58 Page 3 of 58

10 (Capacity) MW Generator Unit-1 Protection Audit - check list No Relay configuration - Generator protections Relay 1 Functional Relay 2 make and model 11 Functions available in Relay 1 Relay 2 Functional Relay 3 make and model Functions available in Relay 1 Relay 3 Functional 12 Are all the Lock out relays (86) considered for Gen. Unit protection provided with supervision relays (74/86)? 13 Do the Gen. Unit protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 4/58 Page 4 of 58

11 (Capacity) MW Generator Unit-2 Protection Audit - check list No Relay configuration - Generator protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for Gen. Unit protection? 3 Are Group A and Group B protections connected to separate DC sources for Gen. Unit? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection 100% Stator Earth Fault protection 95% Stator Earth Fault protection 5 Inter-turn Fault protection Loss of Excitation protection Negative Phase Sequence Current protection Low Forward Power/ Reverse Power protection Out-of-step/ Pole slipping protection Over-Voltage protection Under-frequency protection Back-up Impedance protection Accidental back-energisation/ Dead machine protection Rotor Earth-Fault protection Thermal Over-load protection Breaker failure active Disturbance Report active 6 Connected to Trip Coil 1/Trip Coil2/Both 7 Feed from DC supply 1/DC supply2 Connected to dedicated CT core? 8 Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Southern Region - (Station Name) 5/58 Page 5 of 58

12 (Capacity) MW Generator Unit-2 Protection Audit - check list No Relay configuration - Generator protections Relay 1 Functional Relay 2 make and model 11 Functions available in Relay 1 Relay 2 Functional Relay 3 make and model Functions available in Relay 1 Relay 3 Functional 12 Are all the Lock out relays (86) considered for Gen. Unit protection provided with supervision relays (74/86)? 13 Do the Gen. Unit protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 6/58 Page 6 of 58

13 (Capacity) MVA, HV/ LV kv GT-1 Generator Transformer Protection Audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for Gen. Transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for Gen. Transformer? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections 5 Overall differential Differential protection REF protection Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Gen. Transformer differential protection? 6 Are all the Lock out relays (86) considered for Gen. Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI working 9 OTI working 10 Buchholtz working 11 PRD/ PRV working 12 LA rating HV side 13 LA rating IV side Southern Region - (Station Name) 7/58 Page 7 of 58

14 (Capacity) MVA, HV/ LV kv GT-2 Generator Transformer Protection Audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for Gen. Transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for Gen. Transformer? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections 5 Overall differential Differential protection REF protection Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Gen. Transformer differential protection? 6 Are all the Lock out relays (86) considered for Gen. Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI working 9 OTI working 10 Buchholtz working 11 PRD/ PRV working 12 LA rating HV side 13 LA rating IV side Southern Region - (Station Name) 8/58 Page 8 of 58

15 765 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 9/58 Page 9 of 58

16 765 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 10/58 Page 10 of 58

17 765 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 11/58 Page 11 of 58

18 765 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 12/58 Page 12 of 58

19 765 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 13/58 Page 13 of 58

20 765 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 14/58 Page 14 of 58

21 765 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 15/58 Page 15 of 58

22 765 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 16/58 Page 16 of 58

23 400 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 17/58 Page 17 of 58

24 400 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 18/58 Page 18 of 58

25 400 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 19/58 Page 19 of 58

26 400 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 20/58 Page 20 of 58

27 400 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 21/58 Page 21 of 58

28 400 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 22/58 Page 22 of 58

29 400 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 23/58 Page 23 of 58

30 400 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 24/58 Page 24 of 58

31 220 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 25/58 Page 25 of 58

32 220 kv (Line Name) Line-1 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 26/58 Page 26 of 58

33 220 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 27/58 Page 27 of 58

34 220 kv (Line Name) Line-2 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 28/58 Page 28 of 58

35 220 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 29/58 Page 29 of 58

36 220 kv (Line Name) Line-3 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 30/58 Page 30 of 58

37 220 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection 1 Name and length of line 2 Series compensated? Y/N 3 Is this a cable feeder / line feeder/ composite feeder (line+cable)? 4 Which mode of communication is used (PLCC/ OPGW) 5 Details of composite type numerical relays Relay make and model Whether the relay is functional?? Date of testing Mention all the active protections Details of type relays Main-1 Relay Main-2 Relay Mode of Carrier aided scheme for 21 ( If POR scheme is used whether Current Reversal Guard Logic implemented?) Carrier aided scheme active for 67/67N Mode of Carrier aided scheme for 67/67N For 87L which scheme is used? (Pilot wire communication/ digital communication) Power swing/out of step active? SOTF active? Auto Reclose (79) active? Breaker failure active Load Encroachment active Stub Protection active Fault locator active? Disturbance Recorder active? 6 Relay Connected to Trip Coil-1/ Trip Coil-2 or both? 7 Feed from DC supply 1 / DC Supply 2 8 Connected to Dedicated CT core? Define CT core no. to which the relay is connected 9 CT ratio selected 10 VT ratio selected for ex: Siemens 7SA522 21/87L/ Accelerated Under reach/ Permissive Under reach/intertripping Under reach/ Permissive Overreach/ Blocking Over reach/ Phase Comparison Protection (for PLCC) Directional Comparison Protection (Permissive)/ Directional Comparison Protection (Blocking) Other Relays (Back-up relays, DR, FL etc.) Southern Region - (Station Name) 31/58 Page 31 of 58

38 220 kv (Line Name) Line-4 Distance Protection Audit - check list No. Relay configuration - Line distance protection Details of separate relays if applicable Relay 1 make and model Functions available in Relay 1 Relay 1 Functional Relay 2 make and model Functions available in Relay 2 Relay 2 Functional 11 Relay 3 make and model Functions available in Relay 3 Relay 3 Functional Relay 4 make and model Functions available in Relay 4 Relay 4 Functional 12 VT Fuse failure protection present & used to block distance function operation? 13 Overvoltage protection available Functional with two stage protection 14 Are all the auxiliary relays (94) considered for Line protection (Main-1/ Main-2/ Backup) provided with supervision relays (74/ 94)? 15 Do the Line Protection protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? Southern Region - (Station Name) 32/58 Page 32 of 58

39 HV/ LV kv ICT-1 Transformer Protection Audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for power transformers? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection REF protection 5 Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Transformer differential protection? 6 Are all the Lock out relays (86) considered for Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI working 9 WTI working 10 Buchholtz working 11 PRD/ PRV working 12 LA rating HV side 13 LA rating IV side Southern Region - (Station Name) 33/58 Page 33 of 58

40 HV/ LV kv ICT-2 Transformer Protection Audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for power transformers? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection REF protection 5 Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Transformer differential protection? 6 Are all the Lock out relays (86) considered for Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI working 9 WTI working 10 Buchholtz working 11 PRD/ PRV working 12 LA rating HV side 13 LA rating IV side Southern Region - (Station Name) 34/58 Page 34 of 58

41 765 kv Bus Reactor Protection Audit - check list No 1 Name,Voltage,Power Relay configuration - Shunt reactor protections 2 Are used 2 groups of protections (Group A and Group B) for shunt reactors protection? 3 Are Group A and Group B protections connected to separate DC sources for shunt reactors? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection REF protection 5 Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil1 / Trip Coil2 / Both Feed from DC supply 1/DC supply2 Breaker failure active 6 7 Disturbance Recorder active Connected to dedicated CT core? Define CT core no.to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Reactor differential protection? Are all the Lock out relays (86) considered for Reactor protection provided with supervision relays (74/ 86)? Do the Reactor protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI indications working 9 WTI indications working 10 Bucholtz working 11 PRD/ PRV working 12 LA rating HV side Southern Region - (Station Name) 35/58 Page 35 of 58

42 400 kv Bus Reactor Protection Audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for power transformers? 4 Do the Group A and Group B protections have separate lockout relays? Details of type relays Details of composite type numerical relays Relay make and model Main Back up A B C D Other Protections Whether the relay is functional? Date of testing Mention all the active protections Differential protection REF protection 5 Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Is CT supervision enabled or not in case of Transformer differential protection? 6 Are all the Lock out relays (86) considered for Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI working 9 WTI working 10 Buchholtz working 11 PRD/ PRV working 12 LA rating HV side Southern Region - (Station Name) 36/58 Page 36 of 58

43 765 kv Line Reactor (Line Name) Protection audit - check list No Relay configuration - Power Transformers protections 1 Name, voltage, power 2 Are used 2 groups of protections (Group A and Group B) for transformer protection? 3 Are Group A and Group B protections connected to separate DC sources for power transformers? 4 Do the Group A and Group B protections have separate lockout relays? 5 Details of composite type numerical relays Relay make and model Whether the relay is functional? Date of testing Mention all the active protections Differential protection REF protection Back-up directional O/C +E/F protection Overfluxing protection Connected to Trip Coil 1/Trip Coil2/Both Feed from DC supply 1/DC supply2 Breaker failure active Disturbance Report active Connected to dedicated CT core? Define CT core no. to which the relay is connected CT ratio selected Details of type relays Main Back up A B C D Other Protections Is CT supervision enabled or not in case of Transformer differential protection? 6 Are all the Lock out relays (86) considered for Transformer protection provided with supervision relays (74/86)? 7 Do the Transformer protection panels have supervision relays for DC supply-1 & DC supply-2 (74/DC-1 & 74/DC-2)? 8 OTI indications working 9 WTI indications working 10 Bucholtz working 11 PRD/ PRV working 12 LA rating HV side Southern Region - (Station Name) 37/58 Page 37 of 58

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied: 1) IED Protection and Control Manager PCM 600 Tool (SEP-601) PCM 600 Introduction and Overview Application Configuration Tool (CAP 531) Signal Matrix Tool, SMT Graphical Display Editor, GDE Parameter Setting

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Numerical Protective and Management Relays

Numerical Protective and Management Relays Numerical Protective and Management Relays Presented at: The Institution of Engineers (India) Andaman and Nicobar State Centre Port Blair Dr. H. K. Verma Deputy Director and Professor of Electrical Engineering

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Agenda for the 72 nd Meeting of Protection Coordination Sub-Committee of SRPC to be held on 15 th March, 2018 1. Introduction 2. Confirmation of Minutes of last

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Agenda for the 75 th Meeting of Protection Coordination Sub-Committee of SRPC to be held on 28 th June, 2018 1. Introduction 2. Confirmation of Minutes of last

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4. Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68 The Challenges and Opportunities Faced by Utilities using Modern Protection and Control Systems - Paper Unavailable Trends in Protection and Substation Automation Systems and Feed-backs from CIGRE Activities

More information

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

IMP/ 001 / 014 Policy for the Protection of Distribution Networks Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

GUJARAT TECHNOLOGICAL UNIVERSITY

GUJARAT TECHNOLOGICAL UNIVERSITY GUJARAT TECHNOLOGICAL UNIVERSITY Type of course: Engineering SUBJECT NAME: Switch Gear and Protection SUBJECT CODE: 2170908 Prerequisite: Electrical Power Systems II B.E. 7 th SEMESTER Rationale: This

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

PRC System Protection Coordination Supplementary Reference

PRC System Protection Coordination Supplementary Reference PRC-001-2 System Protection Coordination Supplementary Reference Contents: Disclaimer... 2 Generator Protection Devices or Elements that May Require Coordination with Transmission or Distribution Protective

More information

ICX-CMOS-E-2006 Electrical / I&C Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ICX-CMOS-E-2006 Electrical / I&C Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 102904-ICX-CMOS-E-2006 Electrical / I&C Engineer Holds a B. Sc. in Electronics & Electrical Communications Engineering and has over 9 years hands-on experience working in I&C field. Has extensive experience

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

Application Notes on Generator Protection Schemes

Application Notes on Generator Protection Schemes Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device

More information

Bus Protection Application Challenges

Bus Protection Application Challenges Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Commission Testing Methods for Protection Systems

Commission Testing Methods for Protection Systems Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Use of frame agreement to standardize Protection in Digital Substation Automation Systems, Cooperation between Statnett and ABB

Use of frame agreement to standardize Protection in Digital Substation Automation Systems, Cooperation between Statnett and ABB Use of frame agreement to standardize Protection in Digital Substation Automation Systems, Cooperation between Statnett and ABB R. Loken*, R. Mangelrød*, M.M. Saha, A. Ling *Statnett, Norway, Rannveig.Loken@statnett.no,

More information

Packaged Solutions. Grid Solutions. Value Added Solutions for Protection, Control and Automation Applications. Flexible and Expandable

Packaged Solutions. Grid Solutions. Value Added Solutions for Protection, Control and Automation Applications. Flexible and Expandable Grid Solutions Packaged Solutions Value Added Solutions for Protection, Control and Automation GE s Packaged Solutions provide fully integrated, modular solution sets comprising of engineering, design,

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Agenda for the 56 th Meeting of Protection Coordination Sub- Committee of SRPC to be held on 28 th July, 2016 (Thursday) 1. Introduction 2. Confirmation of Minutes

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Agenda for the 69 th Meeting of Protection Coordination Sub-Committee of SRPC to be held on 23 rd November, 2017 1. Introduction 2. Confirmation of Minutes of

More information

Agenda for the Meeting of Southern Region constituents regarding Connectivity/LTA Applications of IPPs in SR received during November & December, 2016

Agenda for the Meeting of Southern Region constituents regarding Connectivity/LTA Applications of IPPs in SR received during November & December, 2016 Agenda for the Meeting of Southern Region constituents regarding Connectivity/LTA Applications of IPPs in SR received during November & December, 2016 (To be discussed along with Agenda for Follow up Meeting

More information

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2. -and-a-half solutions SIP5-APN-002, Edition 2 www.siemens.com/protection SIPROTEC 5 Application Note -and-a half solutions SIP5-APN-002, Edition 2 -and-a-half solution Content 1 -and-a-half solutions 3

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems By Eng. Sameh Moustafa Mohamed Abd Elgowad Elbana A thesis submitted to The Faculty

More information

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network. Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

National Load Despatch Centre Power System Operation Corporation

National Load Despatch Centre Power System Operation Corporation Module on Procedure for Data Collection National Load Despatch Centre Power System Operation Corporation Background Algorithms/ Processes AC Load flow and transmission losses Slack bus determination- Average

More information

STCP 04-3 Issue 005 Real Time Data Provision

STCP 04-3 Issue 005 Real Time Data Provision STCP 04-3 Issue 005 Real Time Data Provision STC Procedure Document Authorisation Party Name of Party Representative Signature Date National Grid Electricity Transmission plc SP Transmission plc Scottish

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Distribution List: Southern Region. 2. Chief Engineer (PSP&A II) Central Electricity Authority Sewa Bhawan, R.K.Puram, New Delhi

Distribution List: Southern Region. 2. Chief Engineer (PSP&A II) Central Electricity Authority Sewa Bhawan, R.K.Puram, New Delhi Distribution List: Southern Region. 1. Joint Secretary Ministry of New and Renewable Energy, Block 14, CGO Complex, Lodhi Road, New Delhi-110003 3. Director (Transmission) Transmission Corp. of Andhra

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

RMS Product Presentation

RMS Product Presentation RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company

More information

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

Auxiliary Units for 7SR23 High Impedance Protection Energy Management Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance

More information

We will discuss two types of loss-of-potential (LOP) logic during this presentation:

We will discuss two types of loss-of-potential (LOP) logic during this presentation: 1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which

More information

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating

More information

Recording and Reporting of High Voltage and Low Voltage Switching

Recording and Reporting of High Voltage and Low Voltage Switching 1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

THE INTEGRATED TESTING SOLUTION

THE INTEGRATED TESTING SOLUTION Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters THE INTEGRATED TESTING SOLUTION

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays Control 79 Auto Reclose 86 Lockout CB Control Features Cold Load Settings

More information

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015 Configuration and Interoperability Guide for IEC 60870-5-103 for the SEL-751 Feeder Protection Relay July 10, 2015 Contents 1 Interoperability... 3 1.1 Physical Layer... 3 Electrical Interface... 3 Optical

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

PG&E 500 kv Protection Standard Design and Development

PG&E 500 kv Protection Standard Design and Development PG&E 500 kv Protection Standard Design and Development Davis Erwin, Rafael Pineda, and Monica Anderson Pacific Gas and Electric Company Eric Udren Quanta Technology, LLC Jordan Bell and Neal Jones Schweitzer

More information

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Agenda for the 62 nd Meeting of Protection Coordination Sub-Committee of SRPC to be held on 15 th March, 2017 (Wednesday) 1. Introduction 2. Confirmation of

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

Catalog Edition 6 siemens.com/protection

Catalog Edition 6 siemens.com/protection Selection Guide for and Catalog Edition 6 siemens.com/protection Overview of Siemens Protection Catalogs Documentation Selection guide for and Catalog Catalog Catalog Accessoires Catalog Catalogs Manuals

More information

Central Electricity Authority PSPA-II Division Sewa Bhawan, R.K. Puram, New Delhi

Central Electricity Authority PSPA-II Division Sewa Bhawan, R.K. Puram, New Delhi Central Electricity Authority PSPA-II Division Sewa Bhawan, R.K. Puram, New Delhi 110066 No. 51/4(40 th )/PSPA-II/2016/ Date: 17-Nov-2016 Sub: 40th meeting of the Standing Committee on Power System Planning

More information

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations 2008 Many Changes in IEEE C37.2 IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations Major revisions first since 1995 Substantial additions 1 - New ten more

More information

Reyrolle Protection Devices. 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard. Answers for energy

Reyrolle Protection Devices. 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard. Answers for energy Reyrolle Protection Devices 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard Answers for energy 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection

More information

PG&E Transmission Interconnection Handbook

PG&E Transmission Interconnection Handbook Table of Contents TABLE OF CONTENTS... 1 UPDATE HISTORY... UP-1 INTRODUCTION... IN-1 I-1. PURPOSE... IN-1 I-2. INTRODUCTORY DEFINITIONS... IN-1 I-3. HANDBOOK APPLICABILITY... IN-2 I-3.1. New Load, New

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems

IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems Alexandre Oudalov, ABB Switzerland Ltd., Corporate Research, 2014-04-30 Microgrid Protection IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems Microgrid Protection

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

Implementing the protection and control of future DC Grids

Implementing the protection and control of future DC Grids Implementing the protection and control of future DC Grids Hengxu Ha, Sankara Subramanian Innovation and Technology Department, SAS, Alstom Grid 1. The challenge of the DC Grid protection 1 High speed

More information

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-0001 132KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES EPN, LPN, SPN This engineering design standard describes the requirements for

More information

7SA511 V2.2 Numerical Line Protection Relay

7SA511 V2.2 Numerical Line Protection Relay 7SA511 V2.2 Numerical Line Protection Relay Operator Manual Power Blocked 7 8 1 2 3 4 5 6 9 10 11 12 13 14 Manual No. SG-8108-01 Table of Contents Table of Contents User Guide Chapter 1 Introduction...

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA

More information

Advanced Protection and Control for a Power System Serving Industrial Customers

Advanced Protection and Control for a Power System Serving Industrial Customers Advanced Protection and Control for a Power System Serving Industrial Customers Marco F. Jorge Iberdrola Energía Monterrey David Sánchez, Héctor J. Altuve, and Jorge L. Soto Schweitzer Engineering Laboratories,

More information

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations siemens.com/siprotec5 SIPROTEC 5 Table of content Introduction New functions of V7.8 SIPROTEC 5 - the core of Digital Substation

More information

7SR11 and 7SR12 Description of Operation

7SR11 and 7SR12 Description of Operation 7SR11 and 7SR12 Description of Operation Document Release History This document is issue 2012/02. The list of revisions up to and including this issue is: 2012/02 AC auxiliary power supply added 2012/01

More information

Auto-Changeover & Feeder Automation. Reclosers & Sectionalizers

Auto-Changeover & Feeder Automation. Reclosers & Sectionalizers Auto-Changeover & Feeder Automation Reclosers & Sectionalizers WHY AUTOMATE? COMPETITION SERVICE VALUE QUALITY RELIABILITY REGULATION RATES BASED ON RELIABITY & PERFORMANCE PENALTIES REGULATION SAIDI (System

More information

Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power

Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power By S G Patki M V Kini P K Jain G T Jawale Presented at: International Conference on Power System Protection,

More information

SUPPLEMENTARY AGENDA POINTS FOR 496-OCC MEETING

SUPPLEMENTARY AGENDA POINTS FOR 496-OCC MEETING SUPPLEMENTARY AGENDA POINTS FOR 496-OCC MEETING SA-1. GUJARAT ADDITIONAL AGENDA ITEMS: Chief Engineer, SLDC Gujarat vide mail dated 09.06.17 requested to discuss the following additional points in the

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

It is the job of the protection system equipment to recognize and remove the fault.

It is the job of the protection system equipment to recognize and remove the fault. Protection 1 (read section 13.0 of text) 1.0 Introduction Faults do not occur that frequently 1/year/100 miles of transmission is typical. Distribution systems may see more than this. However, when they

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA Deploying Digital Substations: Experience with a Digital Substation Pilot in North America Harsh Vardhan, R Ramlachan GE Grid Solutions, USA Wojciech Szela, Edward Gdowik PECO, USA SUMMARY Though IEC 61850

More information

Protective Relays & SCADA Systems

Protective Relays & SCADA Systems 14 SWITCHGEAR Protective Relays & SCADA Systems SCADA Substation Automation SICAM PAS & PQ Analyzer SICAM PAS (Power Automation System) is a complete substation automation control and protection system

More information