XVD Driver for bipolar electronic expansion stepper valves

Size: px
Start display at page:

Download "XVD Driver for bipolar electronic expansion stepper valves"

Transcription

1 Driver for bipolar electronic expansion stepper valves EN User and Installation manual

2 CONTENTS 1 Introduction USING THE MANUAL General Description Main functions: Models and Features Models and Accessories Remote terminal List of compatible valves Accessories Mechanical installation assembly Access to DipSwitches and connector for MFK / SKP SKP 10 remote terminal assembly Mechanical dimensions Electrical connections General warnings Power supply - high voltage outputs (relay) Analogue inputs-probes Serial connections Wiring diagrams Connection of compatible valves SKP 10 connection Example of / Energy Flex connection Technical Data General Specifications I/O features Serials Mechanical specifications Transformer Permitted use Improper Use Responsibility and residual risks Disclaimer User Interface (folder PAr/UI) LED SKP 10 keys LED SKP Access to folders - menu structure Set main display "States" menu Programming the Set Point Inputs/Outputs display Alarm Display (AL) Programming menu Parameters (folder PAr) Multi Function Key (folder Par/FnC) Entering a password (Par/PASS folder) Configuration physical I/O (folder PAr/dL...) Preliminary notes Analogue inputs Digital Inputs Digital outputs DipSwitch table Operating mode Applications Single actuator /60

3 9.2 Stand-Alone Command from digital input or serial Regulating digital inputs* ** Regulation serial RS485** Energy Flex application Example of heat pump 1 circuit application Example of heat pump 2 circuits Parameters (PAr) Parameters / visibility table, folder visibility table and client table Parameters / visibility table Valve configuration parameters Valve configuration parameters table de01..de09, de80 con de Folder visibility table Client Table Alarms Alarms Table Multi Function Key (folder FnC) Upload/Download via DipSwitch DipSwitch LED Upload/Download via SKP Download from reset Monitoring Configuration with Modbus RTU Data format (RTU) Modbus commands available and data areas Configuration of device address Configuration of parameter addresses Configuration of variable / state addresses /60

4 1 INTRODUCTION 1.1 USING THE MANUAL To allow quick, easy reference, the manual has been designed with the following features: References Cross references Highlighting icons: References column: The reference symbols on the left of text indicate the different topics; this helps you find the information you need quickly. Cross references: All words in italics are listed in the analytical index with the number of the page where they are dealt with in more detail; In the "online" (computer) manual, words in italics are "hyperlinks" (i.e. mouse-clickable links), connecting up the different parts of the manual and making it "navigable". Some text passages are marked by icons in the references column, which have the following meanings: Important: Information that the user must be aware of, to prevent any damage to the system or hazards for people, devices, data, etc; users must read this information. Note / highlight: Further information on the topic in question that the user should be aware of. Tip: A suggestion that could help the user to understand and make better use of the information provided. 1.2 General Description is the compact solution in the Eliwell platform of drivers to manage bipolar motorized electronic expansion stepper valves, suitable for a variety of HVAC/R market requirements and many others. The option of selecting the type of refrigerant and compatibility with the most popular valves on the market make a particularly versatile module. also allows you to configure a refrigerant not included in the default factory list. Valve control with current-powered motor and separate cold and heat function via double regulator mapping improves performance. allows the high-precision, stable and reliable regulation of refrigerant flow making the system more efficient and saving energy by regulating overheating and valve opening to meet demand in real time. Reliability is guaranteed by isolated serial connections and backup sensors. Various models of are available, i.e. as a single actuator, standalone mode (via digital inputs or RS485 serial) or in combination with the Energy-Flex range of compact controllers regulating chillers and heat pumps with up to 2 circuits/4 compressors per circuit. The models are available in the DIN rail-mounted version which cuts cabling times. To configure parameters and command the controller, there is a remote SKP 10 controller to be connected to the LAN serial inside the door. interfaces with the Modbus RTU serial communication standard and can download parameter maps and applications using the Multi Function Key. It is also possible to connect ratiometric pressure sensors and a 32x74 remote SKP 10 terminal with no additional serial interfaces. All digital inputs and outputs are independent and can be configured individually, meaning they can be adapted to fit any system. The power supply is 24V~/24Vc 4/60

5 <IMG INFO> 42,9 29, Main functions: Refrigerant selection using dipswitches under the door. Backup probes to control saturation and evaporator output (overheating). LED display of valve state. Parameter settings via keyboard or PC Multi Function Key (MFK) to download and upload parameter maps and firmware. DeviceManager software for rapid parameter programming. Remote keyboard (up to 100m cable) that connects directly without a serial interface. NTC configurable inputs, Pt1000, mA, V, 0...5V ratiometric. 2 digital inputs to command valves and/or alarms. 1.3 Models and Features -->See Models and Specifications chapters. 5/60

6 2 MODELS AND ACCESSORIES Model 420 LAN 420 RS DIGITAL Code Analogue Inputs Voltage Low voltage (SELV) Voltage Free Digital Inputs High voltage Digital Outputs Digital Output Open Collector Integrated RS-485 serial 420BLAN NO YES 420B YES NO 420B NO NO B NO NO LAN Power supply 24V~/c Imax 0.8A/ph 24V~/c Imax 0.8A/ph 24V~/c Imax 0.8A/ph 24V~/c Imax 0.8A/ph Remote terminal Model Code Assembly Dimensions Display Power supply SKP panel 74x32x30mm LED / 4 digit From driver List of compatible valves The is compatible with the valves listed below. Contact the Eliwell Support Service for information on how to use the valve. Eliwell is not responsible for information provided by the valve manufacturer, including technical modifications or updates. Always refer to the valve manufacturer's technical manual, especially to check ratings and proper function. Model POWER SUPPLY Note Danfoss ETS50 12V Bipolar Danfoss ETS100 12V Bipolar ALCO EX5 24 V Bipolar ALCO EX6 24 V Bipolar ALCO EX7 24 V Bipolar ALCO EX8 24 V Bipolar Carel E2V 12V Bipolar Sporlan SER 12V Bipolar Sporlan SEI-30 12V Bipolar Sporlan SEI-50 12V Bipolar Sporlan SEH 12V Bipolar model only. 2.2 Accessories N.B.: The photos are intended to show the accessories and are for indication purposes only. The dimensions shown in the figures are not to scale. Documentation / Name Code Description Notes Remote terminal x74 terminal Instruction sheet 8FI20016 Energy Flex GB-I Transformer TF V~/24V 35VA transformer Please Note. Use a cable with length <10m Fitted to DIN rail 6/60

7 IMG INFO IMG INFO Name Code Description Documentation / Notes Multi Function key MFK100T Programming Copy Card to upload/download parameters and firmware / Temperature probes FAST temperature probes Ratiometric transducers Pressure transducers SN SN8T6H1502 SN8T6A1502 SN8T6N1502 SN8DNB11502A0 SN8DEC11502A0 SN8DEB21502C0 TD TD TD TD TD TD TD NTC 103AT 1.5m probe, (plastic cap, 2-wire cable); NTC 5X20 1.5m TPE IP68 temperature probe NTC 6X40 1.5m TPE STEEL IP68 temperature probe NTC 6X50 1.5m TPE STEEL IP68 temperature probe NTC 1.5m 4x16 TPE O-RING IP67 temperature probe NTC 4X40 1.5m TPE STEEL IP67 temperature probe NTC 1.5m 6x20 TPE O-RING IP68 temperature probe. EWPA 010 R 0/5V 0/10BAR ratiometric transducer with female connector EWPA 030 R 0/5V 0/30BAR ratiometric transducer Female connector EWPA 050 R 0/5V 0/50BAR ratiometric transducer with female connector. EWPA mA -0.5/8bar pressure transducer with male connector. EWPA mA -0.5/8bar pressure transducer with female connector. EWPA mA 0/30bar pressure transducer with male connector. EWPA mA 0/30bar pressure transducer with female connector. instruction sheet SN GB-I instruction sheet SN8T6H1502 GB-I instruction sheet SN8T6A1502 GB-I instruction sheet SN8T6N1502 GB-I instruction sheet SN8DNB11502A0 GB-I instruction sheet SN8DEC11502A0 GB-I instruction sheet SN8DEB21502C0 GB-I instruction sheet 9IS41070 EWPA GB-I- E-D-F-RUS Power EWPA GB- I-E-D-F TD EWPA mA 0/50bar pressure transducer with male connector. Interface modules Contact Eliwell Sales Department DeviceManager Interface (DMI) instruction sheet DMI 9IS42020 GB-I 7/60

8 IMG INFO Name Code Description BA11250N3700 BA10000R3700 Bus Adapter 130 TTL RS485 communication interface TTL/RS V aux. output for power supply to device. TTL cable, L = 1 m ( 2) Bus Adapter 150 TTL RS485 communication interface TTL/RS- 485 TTL cable, L = 1 m ( 2) Documentation / Notes instruction sheet 9IS43084 BusAdapter GB-I-E-D-F Connectivity BARF0TS00NH00 ( 1 ) RadioAdapter TTL/WIRELESS instruction sheet 8FI40023 RadioAdapter GB-I-E-D-F manual 9MAX0010 RadioAdapter GB-I-E-D-F instruction sheet 9IS44065 WebAdapter GB-I-E-D-F- RUS WA0ET00X700 WebAdapter manual 8MAx0202 WebAdapter X = 0 IT; 1 EN; 2 FR; 3 ES; 5 DE; A RU WA0WF00X700 WebAdapter Wi-Fi Software Tools Contact Eliwell Sales Department DeviceManager manual 8MAx0219 X = 0 IT; 1 EN; 2 FR; 3 ES; 5 DE; A RU Demo Case Contact Eliwell Sales Department Demo case / ( 1 ) Various items available. Contact the Sales Department ( 2 ) Various lengths available on request. GENERAL NOTES: Connection of remote keyboard via 3-way cables with no optional modules. Eliwell can also supply a variety of different NTC probes depending on the cable type (PVC or silicon) and length. 8/60

9 <IMG INFO> 3 MECHANICAL INSTALLATION 3.1 assembly The device is designed for DIN rail mounting. The ambient temperature range for correct operation is from -5 to +55 C with 90% non-condensing RH. Also avoid fitting the device in places where there is high humidity and/or dirt; it is suitable for use in environments with an ordinary or normal level of pollution. Keep the area around the instrument cooling slots adequately ventilated. The TTL serial is on the top of the cover and inserts vertically Access to DipSwitches and connector for MFK / SKP 10. Remove the door (see picture on right) using a flat-tip screwdriver or nail of your index finger. Configure dipswitches appropriately and/or connect the MFK or SKP 10. On completion of configuration, replace the front panel of the keyboard by lightly pressing it into position. driver mechanical dimensions 61.6mm 70.2mm Access to DipSwitches 87mm 43.6mm 5.2mm 56.4mm MFK connector TTL MFK OFF A B C Keyb 9/60

10 <IMG INFO> <IMG INFO> 3.2 SKP 10 remote terminal assembly The remote SKP 10 terminal is designed for panel mounting. Drill a 29x71mm hole and insert the instrument; secure it with the special brackets provided. Do not install the instrument in damp and/or dirty places; in fact, it is suitable for use in places with ordinary or normal levels of pollution. Keep the area around the instrument cooling slots adequately ventilated SKP 10 assembly Remote SKP 10 terminal mechanical dimensions 70mm 30mm 29mm 71mm 74mm 30mm 32mm 28mm 3.3 Mechanical dimensions Length (L) mm Depth (d) Height (H) mm Note mm SKP 10 front panel 76.4 // 35 (+0.2 mm) front panel (cover) 70 // 45 (+0.2 mm) SKP 10 dimensions dimensions DIN Hole for panel wall-mounting of SKP from Din bar to cover 71 // 29 (+0.2 mm / -0.1 mm) 10/60

11 <IMG INFO> 30,9 43, ,35-1 <IMG INFO> 30,9 43, ,35-1 <IMG INFO> 30,9 43, ,35-1 <IMG INFO> 42,9 29, <IMG INFO> 23,95 27, <IMG INFO> 23,95 27, ELECTRICAL CONNECTIONS 4.1 General warnings Before doing anything, make sure the device is connected to a suitable external transformer. The following rules must be followed when connecting cards to each other and to the application: Check ratings for valve stated in the manufacturer's manual. Loads that exceed the maximum limits set forth herein must not be applied to outputs; When connecting loads, follow connection diagrams carefully; To avoid electric pairings, wire all low SELV utilities separately from high voltage ones. Before connecting the valve, configure driver appropriately by selecting the type of valve from the compatible ones. IMPORTANT! Make sure the machine is switched off before working on the electrical connections. The operations must be carried out by qualified personnel. To ensure proper connections, comply with the following: Power supplies other than those specified can seriously damage the system. Use cables of suitable section for the terminals used. Separate the cables of probes and digital inputs from inductive loads and high voltage connections to prevent any electromagnetic interference. Do not place the probe cables near other electrical equipment (switches, meters, etc.) Make connections as short as possible and do not wind them around electrically connected parts. To avoid causing static discharges, do not touch the electronic components on the boards. The device must be connected to a suitable transformer that complies with the specifications provided in the Specifications chapter Power supply - high voltage outputs (relay) Do not exceed the maximum permissible current; in case of higher loads, use a contactor of adequate capacity. Temperature probes Attention! Make sure the power supply voltage complies with that required by the instrument Analogue inputs-probes The temperature probes have no characteristic insertion polarity and can be extended using standard bipolar cable (note that extending cables can affect the performance of the device in terms of electromagnetic compatibility: take great care with the wiring). Pressure probes Attention! Pressure probes have a specific insertion polarity which must be observed. Signal cables (temperature/pressure probes, digital inputs, TTL serial) must be wired separately from high voltage cables. Eliwell-supplied probes are recommended. Contact Eliwell sales department for item availability. TTL MFK KEYB Serial connections Use a 5-wire TTL cable up to 30 cm in length. An Eliwell-supplied TTL cable is recommended. Contact Eliwell sales department for item availability. TTL serial inside the door for connection to MFK. Live 3-wire LAN serial SKP 10 inside the door for connection to remote SKP 10 terminal. Max. distance 100m To be used to configure the device and view resources. We recommend using this connection to work temporarily on the driver. LAN Model 420 LAN Live 3-wire LAN serial available on the terminal board for connection to the LAN network (see Applications chapter). Max. distance 100m This connection is to permanently connect Flex/Free Smart modules (including the remote SKP 10 terminal). N.B.: If the driver is part of a LAN network with Energy Flex or Free Smart devices, will act as an expansion: the remote SKP 10 terminal will act on Flex/Free Smart modules (in which parameters are replicated) and not on. Use the serial Key to modify parameters directly or view resources. N.B.: If the driver is part of a LAN network with Energy Flex or Free Smart devices, the remote SKP 10 terminal doesn't require a power supply. See wiring diagrams. 11/60

12 OFF OFF S S 4.2 Wiring diagrams 420 LAN Open Collector 2 3 D02 12Vc Televis/ Modbus (via BusAdapter) Valve Output DO2 12Vc W2- W2+ W1- W1+ + ~ ~ Solenoid Alarm valve 11 NO 12 C GND AI1 AI2 AI3 AI4 NTC/ Pt GND AI1 AI2 - SIG SIG V 0-10V LOAD max 100mA 420 LAN MFK A B C Keyb DO1 + 12Vc AI1 AI2 SIG SIG + DO2 12Vc GND AI1 AI2 - SIG SIG Signal WHITE BROWN GND Signal DI1 DI2 GND GND LAN DI1 DI2 GND 5Vc AI1 AI2 AI3 AI4 WHITE BROWN GND Transucer Power Supply LAN EWPA mA Transducer mA GND 5Vc AI1 AI2 BLACK RED BLUE BLUE EWPA R 0/5V Open Collector 2 3 D02 12Vc Televis/ Modbus (via BusAdapter) Valve Output DO2 12Vc W2- W2+ W1- W1+ + ~ ~ Solenoid Alarm valve 11 NO 12 C GND AI1 AI2 AI3 AI4 NTC/ Pt GND AI1 AI2 - SIG SIG V 0-10V LOAD max 100mA 420 RS485 MFK A B C Keyb DO1 + 12Vc AI1 AI2 SIG SIG + 12Vc GND AI1 AI2 - SIG SIG Signal RS WHITE BROWN GND Signal DI1 DI2 GND - + G DI1 DI2 GND 5Vc AI1 AI2 AI3 AI4 WHITE BROWN GND Transducer Power Supply Televis/ Modbus (direct connection) EWPA mA Transducer mA GND 5Vc AI1 AI2 BLACK RED BLUE BLUE EWPA R 0/5V 12/60

13 <IMG INFO> 423, <IMG INFO> 423,3 249,9 0 OFF OFF S 420 Open Collector 2 3 D02 12Vc Televis/ Modbus (via BusAdapter) Valve Output DO2 12Vc W2- W2+ W1- W1+ + ~ ~ Solenoid Alarm valve 11 NO 12 C GND AI1 AI2 AI3 AI4 NTC/ Pt GND AI1 AI2 - SIG SIG V 0-10V LOAD max 100mA 420 MFK A B C Keyb DO1 + 12Vc AI1 AI2 SIG SIG + 12Vc GND AI1 AI2 - SIG SIG Signal DI1 DI2 GND DI1 DI2 GND 5Vc AI1 AI2 AI3 AI4 WHITE BROWN WHITE BROWN GND Signal GND Transducer Power Supply EWPA mA Transducer mA GND 5Vc AI1 AI2 BLACK RED BLUE BLUE EWPA R 0/5V 100 Solenoid / Alarm Televis/ Modbus (via BusAdapter) 2 W2- W2+ W1- W Valve Output 6 L N Solenoid Alarm valve S 11 NO 12 C GND AI1 NTC/ Pt GND AI1 - SIG V 0-10V 100 MFK A B C Keyb DO1 + 12Vc AI1 SIG + 12Vc GND AI1 - SIG Signal GND 5Vc AI1 WHITE BROWN GND Transducer Power Supply EWPA mA Transducer mA GND 5Vc AI1 BLACK RED BLUE EWPA R 0/5V 13/60

14 KEY Terminal Label Description Note Parameters 2-3 LOAD max 100mA Open Open Collector Output LOAD max 100mA Collector 2=DO; 3= 12Vc dl Vc Probe power supply For 4..20mA current input Valve Valve output 4= W2-; 5=W2+; 6=W1-; 8-9 Output POWER SUPPLY Power supply 10 Ground Solenoid / Alarm DO1 7=W1+ Check polarity in the case of direct current Connect earth when possible Relay output Solenoid valve / Alarm dl90 Model LAN Live serial 420 LAN Televis/Modbus serial Model Direct connection DI1 Digital Input 1 The digital input must dl40 never be connected to a 18 DI2 Digital Input 2 dl41 power output 19 GND Ground 20 5 Vc Probe power supply For ratiometric probe 21 AI1 Analogue input 1 Saturation Probe dl10 / dl11 / dl20 22 AI2 Analogue Input 2 Backup saturation probe dl12 / dl13 / dl21 23 AI3 Analogue Input 3 24 AI4 Analogue input 4 KEYB Connection to SKP 10 remote terminal Evaporator output temperature probe (overheating) Evaporator output temperature backup probe (overheating) Present inside the door View resources and configure driver Present inside the door MFK Connection to Upload/download MultiFunctionKey parameters application TTL Televis/Modbus connection Via BusAdapter and/or dl22 dl23 Probe and transducer colours Black Blue Brown Red White Yellow Signal Transducer Transducer Power Supply 14/60

15 <IMG INFO> Connection of compatible valves CAREL Green Brown White Yellow DANFOSS ETS Green Red Black White SPORLAN SEI SPORLAN SEH SPORLAN SER Green Red White Black ALCO EX5 ALCO EX6 White Black Blue Brown ALCO EX7 ALCO EX8 Green Brown White Yellow Check valve s manufacturer datasheet W2- W2+ W1- W Valve Output Colour Black Blue Brown Red White Yellow Note Check valve manufacturer datasheet 15/60

16 <IMG INFO> 42,9 29, <IMG INFO> 23,95 27, ,35 <IMG INFO> 424,1 228,2 0 OFF S OFF S SKP 10 connection Solenoid valve Alarm Valve Output DO2 2 12Vc W2- W2+ W1- W ~ ~ NO 12 C 420 LAN MFK A B C Keyb DO1 SKP 10 BLACK GND BLUE SIGNAL RED 12Vdc GND LAN DI1 DI2 GND 5Vc AI1 AI2 AI3 AI4 Model 420 LAN Live 3-wire LAN serial available on the terminal board for connection to the remote SKP 10 terminal. Max. distance 100m. We recommend using this connection to connect the remote SKP 10 terminal temporarily to the driver. The - SKP 10 connection for other models is the same. N.B.: If the driver is part of a LAN network with Energy Flex or Free Smart devices, the remote SKP 10 terminal doesn't require a power supply. In this case, the remote SKP 10 terminal is part of a LAN network also with 420 LAN See wiring diagram: Example of / Energy Flex connection Model 420 LAN only Televis/ Modbus (via BusAdapter) Valve Output Solenoid Alarm valve G LAN DO2 12Vc W2- W2+ W1- W1+ + ~ ~ MFK A B C Keyb NO DO1 C RS-485 /S Models only SC46xx(/C/S) SC64(/C/S) SE646 SKP 10 R E D B B L L U A E C K GND LAN DI1 DI2 GND 5Vc AI1 AI2 AI3 AI4 4 G 3 5 AO DI1 DI2 DI3 DI4 DI5 DI6 AO2 AI1 AI2 AI3 AI4 AI5 GND GND Supply Supply 4 G 3 5 AO DI1 DI2 DI3 DI4 DI5 DI6 AO2 AI1 AI2 AI3 AI4 AI5 GND GND Supply Supply BLACK GND BLACK GND BLACK GND BLACK GND BLUE SIGNAL BLUE SIGNAL BLUE SIGNAL BLUE SIGNAL RED 12Vdc RED 12Vdc RED 12Vdc SKW22L ONLY! DO NOT CONNECT +12Vdc to 3 LAN NO! SKW22/22L black / GND blue / signal red /+12Vdc Probe red /+12Vdc blue / signal black / GND LAN Colours of wires GND / black Signal / Blue 12Vdc / Red Probe SKW22L only DO NOT CONNECT +12Vdc to terminal 3 16/60

17 5 TECHNICAL DATA 5.1 General Specifications Standard Min. Max. Supply voltage 24V~/c Power supply frequency 50Hz/60Hz Power consumption 30VA / 25W Insulation class Operating temperature 25 C -5 C 55 C Ambient operating humidity (non-condensing) 30% 10% 90% Ambient storage temperature 25 C -20 C 85 C Ambient storage humidity (non-condensing) 30% 10% 90% Classification The product complies with the following European Community Directives.. and complies with the following harmonised regulations Use Assembly Directive 2006/95/EC Directive 89/108/EC EN / EN / EN operating (not safety) device to be incorporated On DIN omega bar. Type of action 1.B Pollution class 2 (normal) Overvoltage category II Rated impulse voltage 2500V Digital outputs See label on device. Fire resistance category D Software class and structure A For each circuit, type of disconnection or interruption disconnection microswitch PTI of materials used for insulation PTI 250V Period of electrical stress on the insulating parts long period 5.2 I/O features Type and Label Description 420 LAN 420 RS DIGITAL 100 Digital inputs DI1 DI2 2 no-voltage digital inputs Closing current for ground: 0.5mA x x x // High voltage digital outputs DO1 1 x 5A 250V~ relay; x x x x Analogue inputs AI1 AI2 AI3 AI4 AI1 AI2 2 configurable inputs: a) temperature NTC 103AT 10kO, Pt1000 measurement range -50 C 99.9 C; b) ma current input / 0-5V ratiometric measurement range ; c) 0-10V voltage input, measurement range %; AI3 AI4 a) temperature NTC 103AT 10kO, Pt1000 measurement range -50 C 99.9 C; x x x Only AI1 Open Collector low voltage (SELV) digital output DO2 accuracy: 1% full scale Resolution: (a) 0.1 C (b) 0.1 bar (c) 0.1% Input impedance (b): 0-10V and 0-5V: 21Kohm 4 20mA: 100Ohm 1 Open Collector output Max. current x x x // 17/60

18 5.3 Serials Label Description Models TTL 1 serial TTL to connect to Personal Computer or via interface module All models MFK 1 serial TTL for connection to MFK to upload/download parameters e/o application All models LAN 3-way JST connector inside the door to connect to remote SKP 10 terminal. All models Disconnectable terminals for Energy Flex network integration. 420 LAN RS-485 Integrated opto-isolated RS-485 serial Mechanical specifications Description Terminals and connectors 1 x 3-way JST connector remote SKP 10 terminal To be used with COLV cable. Container PC+ABS plastic resin with V0 flammability rating. Models All models All models 5.5 Transformer The device must be connected to a suitable current transformer with the following features: Primary voltage: depending on requirements of individual device and/or country of installation. Secondary voltage: 24V~/c Power supply frequency: 50/60Hz Rating: 35VA Please Note. Use a cable with length <10m 5.6 Permitted use This product is used to control bipolar stepper electronic expansion valves. For safety reasons, the instrument must be installed and used according to the instructions supplied and, in particular, parts with dangerous voltages must not be accessible in normal conditions. The device must be adequately protected from water and dust in the relative application, and must only be accessible using tools (except for the front panel). The device is suitable for use in household refrigeration appliances and/or similar equipment and has been tested for safety aspects in accordance with harmonised European reference standards Improper Use Any use other than that expressly permitted is prohibited. The relay contacts supplied are of the functional type and subject to fault (since they are electronically controlled they are prone to short-circuiting or remaining open). Any protection devices specified in product standards or suggested by common sense for obvious safety requirements must be installed externally to the device. 5.7 Responsibility and residual risks Eliwell is not liable for damage resulting from: Unspecified installation/use and, in particular, in contravention of the safety requirements of established legislation or specified in this document. Use on equipment which does not provide adequate protection against electrocution, water and dust in the actual installation conditions. Use on equipment which allows tool-free access to dangerous components. Installation/use on equipment which does not comply with established legislation and standards. 5.8 Disclaimer This document is the exclusive property of Eliwell Controls srl and may not be reproduced or divulged without the express authorisation of Eliwell Controls srl. All possible care has been taken to ensure the accuracy of this document; nevertheless, Eliwell Controls srl cannot accept liability for any damage resulting from its use. 18/60

19 IMG INFO 6 USER INTERFACE (FOLDER PAR/UI) The front panel of the device functions as the user interface and is used to perform all operations relating to the device. SKP LED There are 3 LEDs on the front panel of the driver showing the status of the valve. There are a further 3 LEDs inside the door for uploading/downloading parameters and/or applications (see Multi Function Key chapter). LEDs Colour On Blinking Off EEV Green Valve regulation Valve closed (No regulation in progress) Setpoint satisfied NA* Defrost in progress Defrost Yellow Valve closed (No regulation in progress) // No defrost No serial connection Alarm Red NA Alarm present No alarm * EEV LED off means no power is reaching driver. 19/60

20 <IMG INFO> 6.2 SKP 10 keys The driver does not have a display. Use the remote SKP 10 terminal to command the device. The values displayed on the remote SKP 10 terminal can have up to 4 digits or 3 digits plus a sign. The remote SKP 10 terminal can be used with the Energy Flex or Free Smart range in association with the driver. Refer to relative manuals for a full description of resources. SKP 10 D C B A 1 2 esc set 3 4 No. Key Single press (press and release) [press and hold] 1 UP Quick modification of overheating setpoint* Increases a value / Goes to next label // 2 DOWN Quick modification of overheating setpoint* Decreases a value / Goes to previous label // 3 ESC Exit without saving new settings Go back to previous level // 4 set Confirms value / exit and save new settings Go to next level (access to folder,sub-folder, parameter, value) Access to State Menu 3+4 esc+set Prg Esc+set keys pressed at the same time. Opens Programming Menu * Can also be modified from parameter de32 disp [Main display] See paragraph on Main display LED SKP 10 The display shows the value/resource set for the "main display". In the event of an alarm, it will alternate with the alarm code Exx. (when more than one alarm occurs, the one with the lowest number will be shown first). LEDs No. Colour Description Note A Red Menu (ABC) B Red Pressure Display (Bar) Red Temperature C Display (degrees centigrade) D Red Alarm Values are in relative bars. If the value is Psi, the symbol is not shown. If the value is F the symbol is not shown. 6.3 Access to folders - menu structure Access to folders is organised into menus. Access is determined by the keys on the front panel (see relative sections). Access to each individual menu is explained below (or in the sections indicated). There are 2 menus: "States" menu See "States Menu' section "Programming" Menu See 'Programming Menu' section There are 3 folders/submenus in the Programming Menu: Parameters Menu (PAr folder) See Parameters chapter MFK menu (folder FnC) See Multi Function Key chapter PASS Password See Parameters chapter 20/60

21 6.3.1 Set main display Main Display refers to the contents of the default display, i.e. when keys are not used. allows you to modify the main display to your own requirements. The various contents can be selected from the "disp" menu which is opened by pressing and holding the [set] key for more than 3 seconds. The main display can be selected from: Label Description Value on display dre1 dre2 Overheating temperature Refrigerant saturation temperature AI3 Overheating probe AI1 Saturation probe Value on display in the event of a probe error (backup) AI4 Backup overheating probe AI2 Backup saturation probe dre3 Backup probe overheating temperature AI dre4 Backup probe refrigerant saturation temperature AI dre5* Overheating Difference dre1-dre2 NA dre6 dre7 * default Refrigerant pressure Percentage valve opening AI1 When configuring probe as saturation probe 4..20mA or ratiometric AI2 When configuring probe as backup saturation probe 4..20mA or ratiometric Otherwise, it shows N.B. Analogue inputs are preconfigured during manufacture. The probe display always shows temperatures (to see pressure values, see Input/Output Display). Step by step instructions are provided below. Set main display To open the [disp] menu and modify the main display setup, press and hold the set key for at least 3 seconds. This opens the blinking menu for the previous display (in this case dre3). To modify the display, use the "up" and "down" keys to scroll through the menu and press the set key to confirm. When you have selected the type of display (e.g. dre1), press the set key to confirm. You will be automatically returned to the main display set "States" menu From the states menu you can view values for each resource. Setpoints can be viewed and modified. The resources may be present / not present depending on the model (e.g. do2 is not present in 100). Label Description Change Main display re dre1 dre2 dre7 NO This is a view only menu; see the relative paragraph for information on configuration. Ai dai1 dai2 dai3 dai4 Analogue inputs NO di ddi1 ddi2 Digital inputs NO do ddo1 ddo2 Digital outputs NO AL Er01 Er02 Er15 Alarms NO SP SP1 SP2 SP3 SP4 Setpoint YES (SP4 excluded) 21/60

22 Programming the Set Point Setpoint Description Settable from Parameter SP1 minimum overheating setpoint de32 Note If de32 = 0 is intended as the only overheating setpoint If de30 = 1 is intended as overheating target Quick modification with UP and DOWN keys. SP2 Maximum overheating setpoint de31 Valid if de30=1 SP3 MOP setpoint. de52 expressed in units of temperature View only, not SP4 dynamically Dynamic overheating modifiable. temperature. Calculated If de30 = 0 then the set is defined in de32 Programming the setpoint Example of SP1 configuration To access the State Menu, press and release the set key. Label re will appear on the display. (Use the UP and DOWN keys to scroll the other labels until you find the SP label required) esc set Press the set key to view the label for the first setpoint SP1. Rapid Setpoint SP1 programming esc set Press the set key again to view the value of SP1 (use the up and down keys to view other setpoints). To modify the display, press the up and down keys and then the set key to confirm. Press the set key to confirm. You will be automatically returned to the main display set. Press the up and down keys to quickly modify the setpoint. The current setpoint value appears on the display To modify the value, press the up and down keys and then the set key to confirm. Press the set key to confirm. You will be automatically returned to the main display set. 22/60

23 <IMG INFO> <IMG INFO> Inputs/Outputs display Inputs/Outputs display esc esc set set Example of view for Analogue Inputs. The same procedure applies to all other I/Os*** To access the State Menu, press and release the set key. Label re will appear on the display. (Use the UP and DOWN keys to scroll the other labels until you find the Ai label required) Press the set key to view the label for the first analogue input (dai1 in this case). Press the set key again to view the value of dai1. Note that the C icon lights up to indicate that the value shown is in degrees centigrade Press the esc key to go back to the main display. ***For digital inputs, the value will be: - 0 = input not active (this is equivalent to input open) - 1 = input active ( this is equivalent to input shortcircuited to ground) Alarm Display (AL) Alarm display esc set esc set To access the State Menu, press and release the set key. Label re will appear on the display. (Use the UP and DOWN keys to scroll the other labels until you find the AL label required) Press the set key to view the label of the first active alarm (if it exists) In this case, the first alarm is Er01. Use the UP and DOWN keys to scroll any other alarms NOTE: the menu is not cyclical. For example, if the active alarms are Er01 and Er02, the display will show: Er01 ->Er02<Er01 NOTE: -> UP, <-DOWN Press the esc key to go back to the main display. 23/60

24 <IMG INFO> <IMG INFO> <IMG INFO> <IMG INFO> Programming menu Parameters Parameter dl df de Ui parameters Functions FnC MFK Password PASS password Parameters (folder PAr) Modifying a parameter Instructions are provided below on how to change a machine parameter. By way of example, we will look at dl parameter configuration folder, parameter dl01 (folder PAr/dL/dL01). Modifying a parameter esc Press the esc and set keys together to open the parameters menu. This will open the PAr menu. set The PAr parameters menu contains all device parameter folders. Press the set key to view all folders. esc set The first folder the controller shows is the dl configuration folder. Simply press the set key again to modify individual dl parameters. esc set esc set esc set esc set The controller will show parameter dl00 (default factory settings). Press the "up" key to scroll the various parameters or move to the next parameter (dl01 in this case) or the down key to go back to the previous parameter (dl91 in this case). dl00->dl01->dl02-> ->dl91->dl00 dl91<-dl00<-dl01<- <-dl90<-dl91 NOTE: -> UP, <-DOWN Press the set key to view the value of the parameter (dl01 in this case). _ For parameter dl01, the value shown will be 2. Press the "up" and "down" keys to modify the value of the parameter. Press the set key once you have entered the required value. ** Press the esc key to exit this display and go back to the previous level. **N.B. pressing the set key will confirm the value entered. Pressing the esc key will take you back to the previous level without saving the value entered Multi Function Key (folder Par/FnC) See Multi Function Key chapter (folder FnC) 24/60

25 6.3.5 Entering a password (Par/PASS folder) To view parameters visible for the given password, open folder PASS (press esc and set together [esc+set] from the main display and search the folder using the up/down keys) and set the PASS value. Setting password esc set esc set Press the esc and set keys together from the main display to enter the PASS folder. [esc+set] You will enter the menu with a list of folders. Use the "up" and "down" keys to scroll the list until you find the PASS folder. Press the set key to open the PASS folder. Enter the password (installation or manufacturer) from here, press the set key and exit. Now open and view parameters to change a value (see parameters chapter). 25/60

26 7 CONFIGURATION PHYSICAL I/O (FOLDER PAR/DL...) 7.1 Preliminary notes Before doing anything, make sure: The correct refrigerant type has been selected, via dipswitch or from parameter. The correct valve type has been selected, and the configuration and positioning of the latter checked. Inputs and outputs have been configured correctly. The driver and valve have been wired properly - see Electrical Connections chapter. 7.2 Analogue inputs Analogue inputs The analogue inputs referred to below as da1 dai4 total 4 in number. Using the parameters, a physical resource (probe, digital input, voltage/current signal) can be "physically" configured for each type of input: Inputs can be "physically" configured as specified in the table below. Analogue inputs: table Parameter Description dl00 Type of analogue Probe not Ratiometric 0-10 NTC sensor Pt ma input dai1 configured 0-5V V dl01 Type of analogue Probe not Ratiometric 0-10 NTC sensor Pt ma input dai2 configured 0-5V V dl02 Type of analogue Probe not input dai3 configured NTC sensor // // // // dl03 Type of analogue Probe not input dai4 configured NTC sensor // // // // Analogue input dai Parameter range Description dai1 dl10 dl Analogue input dai1 full scale value dai1 dl dl10 Analogue input dai1 start of scale value dai2 dl12 dl Analogue input dai2 full scale value dai2 dl dl12 Analogue input dai2 start of scale value The values read by analogue inputs can be configured in parameters dl20 dl23 Parameter Description Measurement Unit range dl20 Analogue input dai1 differential C/ F dl21 Analogue input dai2 differential C/ F dl22 Analogue input dai3 differential C/ F dl23 Analogue input dai4 differential C/ F Table A analogue input configuration Analogue inputs are preconfigured during manufacture as indicated in the table. Description Configuration of analogue input AiL1 Configuration of analogue input AiL2 Configuration of analogue input AiL3 Configuration of analogue input AiL4 Probe Saturation probe Backup saturation probe Evaporator output probe (overheating) Evaporator output temperature backup probe (overheating) 26/60

27 Digital Inputs 7.3 Digital Inputs There are two no voltage digital inputs, referred to below as ddi1 ddi2. Table B parameter - digital input configuration association Parameter. Description value Description 0= digital input not configured ±1= driver ON/OFF driver (regulation) dl40 Configuration of digital input ddi1-4 +4* ±2= defrost ±3= alarm ±4= system operating mode (modes 0 and 1 only) dl41 Configuration of digital input ddi2-4 +4* NB: If the digital inputs are configured (for values 0), they always have priority over commands from serial dl40=dl41 digital input ddl1 has priority Digital outputs 7.4 Digital outputs See the chapter on Electric Connections for the number and capacity of relays/open collectors and for information on the symbols used on labels supplied with the device. The high voltage output (relays) is identified as DO1 The open collector low voltage (SELV) output is called DO2. Table A parameter association - configuration of outputs Parameter. Description PEn parameter Description Note Present in all models CL90 Configuration of digital output ddo1-2 2* Digital output on relay 0= digital output not configured ±1= solenoid valve ±2= alarm CL91 Configuration of digital output ddo2-2 2* Open Collector (OC) digital output Not available for 100 I/O Polarity *Polarity is defined below: Value Description + Positive Active when contact closed - Negative Active when contact open 27/60

28 <IMG INFO> 42,7 29, DipSwitch table There are six selectors (dipswitches) behind the door, to be used for the rapid selection of refrigerant, to select the protocol and use MFK. Operations can also be performed from the remote SKP 10 terminal by configuring parameters in folder df appropriately. When selecting refrigerant, set dipswitches to 7 and configure parameter de20 accordingly. Upload/Download parameters from Dip Upload ON OFF // // // // MFK Download OFF ON // // // // Refrigerant Dip R404A // // // OFF OFF OFF Select refrigerant Select address LAN network 1 R22 // // // ON OFF OFF 2 R410A // // // OFF ON OFF 3 R134A // // // ON ON OFF 4 R744 (CO2) // // // OFF OFF ON 5 R407C // // // ON OFF ON 6 R427A // // // OFF ON ON Set from 7 parameter de20 // // // ON ON ON Default R404A address Dip // // OFF // // // 1 // // ON // // // 28/60

29 <IMG INFO> 208,45 204, , OPERATING MODE is a controller for electronic expansion stepper valves which regulate the minimum overheating value at the exit point from the evaporator. The regulation value is the percentage opening of the valve, which is converted into a valve output percentage value based on the following parameters: de10 - Maximum valve opening percentage is the maximum opening of the valve. de14 - Minimum valve opening percentage is the minimum opening of the valve. de15 - Maximum valve useful opening percentage is the maximum useful opening of the valve. If the regulator commands an output greater than or equal to de15, the real output will equal de10. N.B.: If de15 <de10 the function is ignored. If the regulator commands an output less than or equal to de14, the real output will be equal to 0. If the regulator commands an output greater than or equal to de10 for a longer time than de13, the maximum valve opening alarm Er08 is generated to signal a critical system condition such as insufficient load, undersized etc... N.B.: to disable the signal, set de13=0. % real output 100% de10 % request de14 de15 100% Set saturation calculates the real overheating value using the two analogue dai3 overheating and dai1 saturation inputs. Via a PID type controller, it modulates valve opening so that overheating reaches the de32 setpoint. The algorithm is dynamic: the actual value of the overheating may not reach the setpoint or drop below it temporarily. It this causes liquid to escape from the evaporator, the value of Setpoint de32 will have to be raised. N.B.: valid for de30=1 de21 system type PID configuration parameters will be loaded automatically from the device by selecting the type of system defined in parameter de21. MOP (Maximum Operating Pressure) For MOP regulation, a threshold can be defined in pressure setpoint de52. If this threshold is exceeded for a time greater than de53, a MOP alarm will be generated (see Er07). MOP regulation can be enabled in parameter de50. MOP regulation can be disabled at switch-on or on resetting after a defrost condition for the time set in de51. 29/60

30 <IMG INFO> 339,95 187, , APPLICATIONS 9.1 Single actuator The driver (EEV Driver ) controls the electronic expansion valve. The driver has a 0-10V / 4 20mA input that translates the control signal from a stepper valve. EEV 0...5V V mA Evaporator / Condenser 9.2 Stand-Alone Regulation can be controlled by Digital inputs - for this type of regulation, 420 Digital* or * ** models are used. Via serial - for this type of configuration only the ** is used. The driver controls the electronic expansion valve and receives commands to defrost and control the EEV from: Digital inputs* (see par. dl40/dl41) or from RS485 serial** Command from digital input or serial Set parameter df02 accordingly * **df02= 0 digital input * **df02 0 serial N.B.: when set to 0 digital inputs always have priority over a serial command, regardless of df02. See Configuration physical I/O chapter (folder PAr/dL ) The Televis/Modbus protocol can be selected in parameter df00 See diagram 30/60

31 IMG INFO Digital inputs or serial RS485 (model RS485) DI1 DI2 Backup Bar C Bar C EEV Evaporator / Condenser Regulating digital inputs* ** Value dl40/dl41 ±1 ±2 ±3 ±4 ON Activation of regulation OFF Disabling of regulation ON Defrost Valve forced open at de11- Percentage valve activation after black-out For the time set in: de35 -valve opening freezing timer after OFF->ON Valve closed (current percentage saved in de11) Valve closed N.B.: the digital input configured as ±1 is ignored until the end of defrost. At the end of defrost, the valve is forced open at the value set in: de12 - percentage actuation of valve after defrost (If 0) Otherwise see de11 OFF No Defrost See regulation ON ON Alarm Valve closed OFF No alarm / Regulation activated with profile defined in ON Regulation de22 - Type of system operating mode 1 preconfigured in Regulation activated with profile defined in OFF factory de21 - Type of system operating mode Regulation serial RS485** If there is a RS485 serial regulation can be controlled from serial in the same way as regulation via digital inputs. N.B.: Operating modes 2 and 3 can also be activated (parameters de23, de24) not available for digital inputs. 9.3 Energy Flex application Model 420 LAN is used for this type of regulation Example of heat pump 1 circuit application The driver controls the electronic expansion valve (EEV). The driver receives commands to defrost and control of EEV from Energy Flex via Eliwell LAN.* When there is no communication, closes the EEV and generates an alarm. *NOTE: if digital inputs DI1, DI2 are configured, i.e. dl40/dl41 0 (not disabled) then they will have priority over commands received from Eliwell LAN. See diagram 31/60

32 <IMG INFO> 339,5 296, ,25 4,85-1 LAN model LAN Eliwell 2nd circuit 1st circuit SD600 DI1 DI2 Backup SE600 EEV Bar C Bar C Evaporator / Condenser Compressor Condenser / Evaporator Example of heat pump 2 circuits Application 2 Driver - 1 Energy Flex range controller The network manages up to 2 drivers + 1 Energy Flex Driver 1 controls the electronic expansion valve 1 (circuit 1 EEV). Driver 2 controls the electronic expansion valve 2 (circuit 2 EEV). Drivers 1&2 receive commands to defrost and control their respective EEVs (1 per circuit) from Energy Flex via Eliwell LAN. Set the network address via Dip Switch for ; 0 = first circuit 1 = second circuit When there is no communication, closes the EEV and generates an alarm. 32/60

33 10 PARAMETERS (PAR) Parameters are used to configure every aspect of ; They can be modified with: The Multi Function key (MFK) Keys on remote SKP 10 terminal Personal computer and Device Manager software The following sections analyse each parameter, divided into categories (folders), in detail. Each folder is designated with 2 figures (example: df, UI, etc). Folder label Acronym meaning (label) Parameters of: dl Driver local configuration I/O configuration df Driver protocol configuration Protocol configuration de Driver valve configuration Valve configuration Ui User interface User interface When not indicated otherwise, the parameter is always visible and modifiable, unless customised settings have been configured via serial. NB: parameters and folder visibility can both be controlled (See Folder table). If folder visibility is modified, the new setting will apply to all parameters in the folder. Levels of visibility Four levels of visibility can be set by assigning suitable values to each parameter and folder, by serial, software (DeviceManager or other communication softwares) or by programming key. The visibility levels are: Value 3 = parameter or folder always visible. Value 2 = manufacturer level; These parameters can only be seen by entering the manufacturer's password (see parameter Ui28) (all parameters specified as always visible, parameters that are visible at the installation level, and manufacturer level parameters will be visible). Value 1 = installation level; These parameters can only be viewed by entering the installation password (see parameter Ui27) (all parameters specified as always visible and parameters that are visible at the installation level will be visible). Value 0 = parameter or folder NOT visible. 1. Parameters and/or folders with visibility level <>3 (i.e. password protected) will only be visible if the correct password is entered (installer or manufacturer) following the procedure outlined below. 2. Parameters and/or folders with visibility level =3 are always visible and no password is required; in this case, the procedure below is not required Parameters / visibility table, folder visibility table and client table The tables below list all information required to read, write and decode all accessible resources in the device. There are three tables: - The parameter table contains all device configuration parameters stored in the non-volatile memory of the instrument, including visibility information - The folders table lists the visibility of all parameter folders - The client table includes all I/O and alarm state resources available in the volatile memory of the instrument. Description of columns: FOLDER LABEL VAL PAR AdDRESS This indicates the label of the folder containing the parameter in question. This indicates the label used to display the parameters in the instrument's menu. The whole part represents the address of the MODBUS register containing the value of the resource to be read or written in the instrument. The value after the point indicates the position of the less significant data bit in the register; if not indicated it is taken to be zero. This information is always provided when the register contains more than one information item, and it is necessary to distinguish which bits actually represent the data (the working size of the data indicated in the column DATA SIZE is also taken into consideration). Given that the modbus registers have the size of one WORD (16 bit), the index number after the point can vary from 0 (least significant bit LSb ) to 15 (most significant bit MSb ). Examples (in binary form the least significant bit is the first on the right): VAL PAR AdDRESS DATA SIZE Value Content of register 8806 WORD ( ) 8806 Byte ( ) 8806,8 Byte ( ) 8806,14 1 bit ( ) 8806,7 4 bits ( )

Electronic controllers for centralised air-conditioning units

Electronic controllers for centralised air-conditioning units Energy Flex Electronic controllers for centralised air-conditioning units General Description Eliwell, a leading manufacturer for over a decade of control equipment for small and medium-size air conditioning

More information

Electronic controllers for small centralised air-conditioning units

Electronic controllers for small centralised air-conditioning units FLEX Electronic controllers for small centralised air-conditioning units General Description Eliwell, a leading manufacturer for over a decade of control equipment for small and medium-size air conditioning

More information

4-step Chiller and Heat Pump Controller

4-step Chiller and Heat Pump Controller 4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW

More information

EMPlus 600. Electronic digital indicator

EMPlus 600. Electronic digital indicator EMPlus 600 EN Electronic digital indicator USER INTERFACE UP Press and release Scroll menu items Increases values DOWN Press and release Scroll menu items Decrease values KEYS EMPlus 600 STAND-BY (ESC)

More information

EWCM Compact controller for compressor plants

EWCM Compact controller for compressor plants EN EWCM 4120-4150-4180 e Compact controller for compressor plants 1 Summary INTRODUCTION - CHaracteristics...4 CONDITIONS OF USE...4 MECHANICAL ASSEMBLY...7 WIRING DIAGRAMS...7 CONNECTION DIFFERENCES BETWEEN

More information

Energy ST 500 Electronic controllers for centralised air-conditioning units

Energy ST 500 Electronic controllers for centralised air-conditioning units Energy ST 500 Electronic controllers for centralised air-conditioning units GB Invensys Controls Europe An Invensys Company UP+DOWN Manual reset ST500 MENU LAYOUT Manual defrost UP DOWN Switch on/off Change

More information

ICPlus 902. Electronic controller with 1 intervention point

ICPlus 902. Electronic controller with 1 intervention point ICPlus 902 EN Electronic controller with 1 intervention point USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Function can be configured by the user (H31)

More information

Programmable controller MCX06C

Programmable controller MCX06C MAKING MODERN LIVING POSSIBLE Technical brochure Programmable controller MCX06C Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best

More information

EWCH 485 Electronic Pulse Counter

EWCH 485 Electronic Pulse Counter Electronic Pulse Counter Technical Data Sheet INSTRUMENT DESCRIPTION GENERAL DESCRIPTION is a programmable microprocessor based counter with 1or 2 outputs. The instrument offers the possibility to program:

More information

XEV EX48 Superheat Controller

XEV EX48 Superheat Controller Instruction Sheet PA-00369 January 2014 XEV EX48 Superheat Controller XEV EX48 Superheat Controller with ModBus Communication Capability XEV EX48 Driver for Emerson EX4,5,6,7,8 Electronic Stepper Expansion

More information

MCX06C Programmable controller

MCX06C Programmable controller Data sheet MCX06C Programmable controller MCX06C is an electronic controller that holds all the typical functionalities of MCX controllers in the 32x74 mm standard size: programmability connection to the

More information

EWPC 901/A rel. 6/96 ing

EWPC 901/A rel. 6/96 ing EWPC 91A rel. 696 ing temperature controller with alarm output WHAT IT IS The EWPC 91A is a temperature controller specifically designed for refrigeration applications. The instrument includes a 1 Vdc

More information

Controllers for compressor racks with advanced energy saving. PN08 September 2016

Controllers for compressor racks with advanced energy saving. PN08 September 2016 page 1 / 16 XC400/600 for small/medium compressor rack management Dixell introduces the new compact parametric controllers for compressor rack with. Dixell presents the XC400/600 series, dedicated to the

More information

Programmable controller Type MCX06C

Programmable controller Type MCX06C Programmable controller Type Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best out of your heating, ventilation, air-conditioning

More information

EWPlus 961 EO Dispenser

EWPlus 961 EO Dispenser EWPlus 961 EO Dispenser Electronic controllers for refrigeration units NOTE: When the controller is powered on it performs a lamp test, during which time the display and LEDs will flash for several seconds

More information

ID 974 DCC electronic controllers for forced air refrigeration units

ID 974 DCC electronic controllers for forced air refrigeration units cod. 9IS42075 rel. 4/06 -GB- *If the conditions for defrosting are not present, or if parameter OdO0, the display will blink three times, to indicate that the operation will not be performed. ID 974

More information

Supplementary operating instructions for your air curtain system Controller TMC 500

Supplementary operating instructions for your air curtain system Controller TMC 500 Supplementary operating instructions for your air curtain system Controller TMC 500 (Translation of the original) Serial number: Year: Please quote this number when contacting customer service! Date 08.04.2016

More information

MCX08M2 Programmable controller

MCX08M2 Programmable controller Data sheet MCX08M2 Programmable controller MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers in the compact size of 8 DIN modules: programmability connection

More information

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS SHORT FORM 2002 SERIES D1000 Intrinsically Safe Galvanic Isolators SERIES D1000, for DIN Rail Mounting, provide the most simple and cost effective

More information

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units UNIT CONTROLLER 7 (UC7) Operation & Installation Hydronic Units Date: 1 November 2012 Issue: 5 Page 1 of 17 Contents 1. Connections, hydronic unit... 3 2. Functions assigned to SSR1, SSR2 and AUX... 3

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

EZ-HT / EZ-MT / EZ-LT. Electronic controllers for refrigeration units

EZ-HT / EZ-MT / EZ-LT. Electronic controllers for refrigeration units EZ-HT / EZ-MT / EZ-LT EN Electronic controllers for refrigeration units EZ-HT / EZ-MT / EZ-LT USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Activates the

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Technical data. Safety notes. Product features

Technical data. Safety notes. Product features Technical data sheet BKN230-MOD 11-00002.F Communication and power supply unit for motorised fire dampers Communication via RTU (RS-48) AC 230 V supply via Euro plug Power is supplied to the actuators

More information

EVDRIVE03 User manual ver. 3.1 Code 144EPDE314 EVDRIVE03. Electronic expansion valves drivers ENGLISH. USER MANUAL ver. 3.

EVDRIVE03 User manual ver. 3.1 Code 144EPDE314 EVDRIVE03. Electronic expansion valves drivers ENGLISH. USER MANUAL ver. 3. EVDRIVE03 Electronic expansion valves drivers ENGLISH USER MANUAL ver. 3.1 CODE 144EPDE314 page 1 of 70 Important Important Read this document carefully before installing and using the device and follow

More information

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

QUICK START GUIDE. vau4/3. Frequency converter.   operating instructions /12 operating instructions QUICK START GUIDE Frequency converter vau4/3 28100241101 12/12 1 Safety information Warning of electrical shock! Danger to life! Electrical shock can cause serious injury or even

More information

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,

More information

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions Evaluation system for flow sensors VS / / 2013 Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...

More information

Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve

Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve FKE003 Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve Features Operation of electronic expansion valves pulsed via integrated electronic

More information

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D D600S - D600D INSTRUCTI MANUAL SIL Switch/Proximity Detector Repeater Relay, DIN Rail, Models D600S, D600D D600 - SIL Switch/Proximity Detector Repeater Relay G.M. International ISM0- Characteristics General

More information

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

Component identification

Component identification IO-ATC8 I/O Expansion Module 8 Analog/Thermocouple Inputs The IO-ATC8 is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 inputs that

More information

XT-9100 Technical Bulletin

XT-9100 Technical Bulletin System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX

More information

RXTH DUAL ROOM SENSOR / SWITCH

RXTH DUAL ROOM SENSOR / SWITCH DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

COMPUTER PROCESS CONTROLS

COMPUTER PROCESS CONTROLS TECHNICAL BULLETIN Installation Instructions: ESR8 Valve Regulator (P/N 810-3195) Introduction The ESR8 Valve Regulator board (P/N 810-3195), shown in Figure 1, is a Lon- Works Echelon based electronic

More information

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1 IO-PT4 I/O Expansion Module 4 PT100 Inputs (-50 to 460 C) The IO-PT4 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 4 PT100 inputs

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

UNIVERSAL CURRENT CONVERTER

UNIVERSAL CURRENT CONVERTER UNIVERSAL CURRENT / VOLTAGE CONVERTER AC/DC Current / Voltage Analyzer The is the first CURRENT / VOLTAGE CONVERTER & ANALYZER ALL IN ONE - of the market. It allow you to connect all isolated current sensors.

More information

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs The IO-DI8-TO8 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 digital inputs,

More information

FCU-MULTI Modbus Fan Coil Unit Controller

FCU-MULTI Modbus Fan Coil Unit Controller Product Sheet CT2.61 Controller Type FCU-MULTI FCU-MULTI Modbus Fan Coil Unit Controller FCU-MULTI is completely stand-alone operating room controller designed for room heating, cooling, ventilation, lighting

More information

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Iso DIN. User Manual. 1 channel Earth Fault Monitoring Page 1 of 5 2017 03 20 User Manual Iso DIN Iso DIN User Manual 1 channel Earth Fault Monitoring Megacon AB Ranhammarsvägen 20 S 168 67 Bromma Sweden Tel: 08 402 42 50 sales@megacon.se www.megacon.se eee

More information

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) TEC (Peltier) Controller PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) Thank you for purchasing the TEC (Peltier) Controller PLC-24V10AL. Read these operating instructions carefully to ensure effective

More information

Strain Gauge Converter

Strain Gauge Converter EN Z-SG General Description Module Z-SG is a strain gauge signal converter. Measurements taken using the 6-wires or 4-wires technique are available through Modbus-RTU serial protocol or the analog output.

More information

Programmable controller MCX06D

Programmable controller MCX06D MAKIG MODER IVIG POSSIBE Technical brochure Programmable controller Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best out of your

More information

Universal Controller

Universal Controller 3 342 Universal Controller For comfort control in HVAC & R-Systems Standalone electronic universal controller with P or PI response Operating voltage in accordance to type AC 24 V Control application selectable

More information

Programmable controller MCX152V

Programmable controller MCX152V MAKIG MODER IVIG POSSIBE Technical brochure Programmable controller MCX152V MCX152V is a standard MCX electronic controller that stands on the top of MCX range thanks to its large number of input and output

More information

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3 INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page

More information

Neon pr. ph/ ORP measurement. Applications. Description

Neon pr. ph/ ORP measurement. Applications. Description Easy handling by graphical menue Fitting for your application by modular setup Simple firmware update and configuration using SD-card Applications Process Water Drinking Water / Beverages Waste Water Treatment

More information

GCI-5K INSTALLATION AND OPERATOR S MANUAL

GCI-5K INSTALLATION AND OPERATOR S MANUAL GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW) Product datasheet Characteristics ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/400...440V(7.5kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020 USER MANUAL MULTI COLOR MODEL : ARC2020 ACCSYS ELECTRONICS 140/6B, GOLDEN INDUSTRIAL ESTATE, JAWAHARLAL NEHRU ROAD, GERUGAMBAKKAM, CHENNAI - 600122 Tel: 044 60505599 / 60505511 E-mail : sales@accsyselectronics.com

More information

SK CU4-EIP-C Part number:

SK CU4-EIP-C Part number: SK CU4-EIP-C Part number: 275 271 519 EtherNet/IP Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter S-14 Compact Digital Multimeter S-14 Compact Digital Multimeter SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation at this meter

More information

XB800D Series (v.1.0)

XB800D Series (v.1.0) XB800D Series (v.1.0) INDEX 1. IMPORTANT RECOMMENDATIONS 3 1.1 PRODUCT DISPOSAL (WEEE) 4 2. INTRODUCTION 5 3. GENERAL SPECIFICATIONS 5 3.1 PROCESSING ENVIRONMENT 5 3.1.1 Fields of application... 5 3.1.2

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

Extruder Controls ExtruVision S

Extruder Controls ExtruVision S Extruder Controls ExtruVision S ExtruVision S - The compact system solution for controlling, visualization, and operating extrusion systems Combination of control panel BA Touch with 5.7'' monitor and

More information

Thermoelectric Cooler Controller TED1000

Thermoelectric Cooler Controller TED1000 Thermoelectric Cooler Controller TED1000 Operating Instructions MANUAL-TED1000-1.0 Aug 2015 Rev.1 2 Contents 1 General... 4 1.1 Warranty and Assistance... 4 1.2 Maintenance... 4 1.3 General Safety Considerations...

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01 ABB Drives User s Manual Analogue I/O Extension Module RAIO-01 Analogue I/O Extension Module RAIO-01 User s Manual 3AFE 64484567 REV A EN EFFECTIVE: 1.2.2002 2002 ABB Oy. All Rights Reserved. Safety

More information

Compact Universal Controllers

Compact Universal Controllers 7 865 ISO9001 RWF40... complete with housing Compact Universal Controllers RWF40... The RWF40... is a universal digital boiler temperature / pressure controller with functions designed specifically for

More information

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER SAFETY INFORMATION The following safety information must be observed to ensure maximum personal safety during the operation of this meter: This meter is

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION OPERATING INSTRUCTION AUTORANGING MULTIMETER MAX Ω F C 10A MAX every 15 min. COM V SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation

More information

EXD-TEVI Economizer Controller for Tandem Compressors

EXD-TEVI Economizer Controller for Tandem Compressors Technical Bulletin EXD-TEVI is a stand-alone controller for enhanced wet vapor injection for Copeland tandem Scroll compressors in heating applications. Features EXD-TEVI Emerson solution for specified

More information

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Control MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions CONTENTS Page

More information

FX05 Controller. FX05 Controller. Features and Benefits Compatible with standard BAS protocols. LON and N2Open plug-in comm.

FX05 Controller. FX05 Controller. Features and Benefits Compatible with standard BAS protocols. LON and N2Open plug-in comm. Platform Catalogue Section 1 Product Bulletin FX05 Issue Date 08 2002 FX05 Controller The FX05 is a high performance controller specifically designed for single compressor chillers and heat pumps. It includes

More information

Mercury 2 & Intuitive Stepper Valve Plate Heat Exchanger Controller Installation & User Guide

Mercury 2 & Intuitive Stepper Valve Plate Heat Exchanger Controller Installation & User Guide Mercury PR0712-PHX PR0722 Intuitive PR0752-PHX-XX Mercury 2 & Intuitive Stepper Valve Plate Heat Exchanger Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data

More information

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW) Characteristics soft starter-ats22-control 220V-power 230V(15kW)/400...440V(30kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

RTD-W Installation Instructions

RTD-W Installation Instructions RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485

More information

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22C17Q Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW) Product data sheet Characteristics ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW) Complementary Assembly style Function available Power supply voltage limits Main Range of

More information

OP10. Pre-programmed, configurable controller for simple applications

OP10. Pre-programmed, configurable controller for simple applications revision 10 2013 OP10 Pre-programmed, configurable controller for simple applications The Optigo OP10 range of controllers can be set to handle everything from temperature or humidity control to control

More information

AIAS. Technical description

AIAS. Technical description Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains AIAS - and Efficient Heating Demand Products Controlled Tunnel Ventilation Fans 1 / 4 AIAS Technical description 2 / 9 AIAS -

More information

Manual Control Unit GFC 32

Manual Control Unit GFC 32 Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control

More information

EXOcompact. Third generation freely programmable controllers

EXOcompact. Third generation freely programmable controllers revision 1 013 EXOcompact Third generation freely programmable controllers Small, compact controller with different types of communication, with or without built-in display. EXOcompact can be used either

More information

SMVector Additional I/O Module Installation and Operation Manual

SMVector Additional I/O Module Installation and Operation Manual SMVector Additional I/O Module Installation and Operation Manual About These Instructions This documentation applies to the optional Additional I/O module for the SMVector inverter and should be used in

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

USER S MANUAL. DAS-G01 The Power of Tomorrow

USER S MANUAL. DAS-G01 The Power of Tomorrow USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 0 USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 Page 1 USER'S MANUAL TABLE OF CONTENTS Page # 1.0 GENERAL INFORMATION...

More information

Temperature Controller (Heat Pumps)

Temperature Controller (Heat Pumps) 3 347 Temperature Controller (Heat Pumps) For comfort control in HVAC & R systems Standalone electronic controller Programmable controller with preconfigured applications Three universal inputs for Ni1000,

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions DIN RAIL ELECTRONIC FAN SPEED Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

AIR CONDITIONING CATALOGUE

AIR CONDITIONING CATALOGUE AIR CONDITIONING CATALOGUE INDEX THE COMPANY APPLICATIONS PLUS PRODUCTS 1 CIRCUIT UP TO 2 COMPRESSOR CONTROLLERS IC100 advanced multifunction controllers 2 CIRCUIT UP TO 6 COMPRESSOR CONTROLLERS IC200

More information

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual

Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual LOGGER S0541 Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual Instruction Manual for use of S0541 logger Instrument is designed for measurement and record of temperature

More information

Compact universal controllers

Compact universal controllers 7 867 Compact universal controllers RWF55... The RWF55 is used mainly for controlling the temperature or pressure in oil- or gas-fired heating plants. If the relevant parameters are set, the RWF55 can

More information

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB T E C H N I C A L M A N U A L TECHNICAL MANUAL C 5300 CV/06-00 GB GB The information contained in this document may be modified without prior notice and is in no way binding, even implicitly, for CLIMAVENETA.

More information

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series TEMPSEN DEVICES Plot No : 2&3, Balaji Nagar, 4 th Street, Mettukuppam, Thoraipakkam, Chennai-600097 Tele fax : +91-44-24581758,Mobil

More information