INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

Size: px
Start display at page:

Download "INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION"

Transcription

1 INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Factory Name: ACS TEXTILES (BANGLADESH) LTD. Tetlabo, Barpa Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 26 Sep 2018 The Alliance for Bangladesh Worker Safety Page 1/14

2 Factory Name: ACS TEXTILES (BANGLADESH) LTD. 26 Sep 2018 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/14

3 26 Sep 2018 GENERAL INFORMATION General Information Factory Name: Country: Province: City: ACS TEXTILES (BANGLADESH) LTD. Bangladesh Dhaka Rupgonj Zip Code: 1464 Audit Duration: Re-Audit: 1 Days Re-Audit After 0 Months Draft Report Date : 02 October 2018 Final Report Date : 31 October 2018 Are all action items from previous assessment complete? : Buildings in Complex : No There are 30 buildings/sheds and 1 communication tower within this complex used by 2 factories either combinedly or separately with different FFC ID. Factories are named as: 1. ACS Textiles (Bangladesh ) Ltd. FFC ID-9329 and 2. ACS Towel Ltd. FFC ID Out of 30 buildings/sheds, 8 are production buildings/sheds and 22 are ancillary buildings/sheds. Production buildings/sheds are named as: 1) 2 storied pre-fabricated weaving shed unit-1. 2) 2 storied pre-fabricated warping shed. 3) 1 storied pre-fabricated processing shed. 4) 2 storied pre-fabricated weaving shed unit-2. 5) 3 storied (B+2) pre fabricated Towel shed (used by ACS Towel Ltd). 6) 3 storied RC weaving -4 building. 7) 3 storied RC digital printing shed. 8) 2 storied RC warping (sizing-3)- building. Ancillary buildings/sheds are named as: 1) 3 storied RC office building. 2) 3 storied RC Accessories building. 3) 2 storied RC utility building unit-1 4) 3 storied RC chemical godown building. 5) 3 storied RC staff quarter. 6) 1 storied pre fabricated grey and yearn shed (Demolition has been found in progress) 7) 2 storied RC utility building unit-2 8) 2 storied Medical center. Child care and pump room shed. 9) 3 storied RC new Security Barrack (audited by us). 10) Partially 3 leveled RC ETP complex (audited by us). 11) 1 storied RC security office attached with main gate (audited by us). 12) 1 storied RC security posts (6 Nos) (audited by us). 13) 1 storied RC smoking room (6 Nos) (audited by us). 14) 1 storied Empty drum store shed (audited by us). 15) 1 storied Wastage shed (audited by us). 16) 1 storied RC RMS room (audited by us). 17) 1 storied Carpentry workshop and Wastage room shed (audited by us). 18) 1 storied Salt store and ETP office shed (audited by us). 19) 1 storied Mechanical maintenance and oil heater shed (audited by us). 20) 1 storied Automobile workshop shed (audited by us). 21) 1 storied RC ATM Booth (audited by us). 22) 1 storied Parking shed (audited by us). Other Structure: 1) One 4 legged Self supported steel Communication Tower (audited by us). All production buildings/sheds and 8 ancillary buildings/sheds (SL No 1-8) out of 22 ancillary buildings/sheds were previously audited by another QAF. Demolition of one of the previously audited ancillary sheds named as prefabricated grey & yarn shed has been found in progress. Presently our audit scope is limited to 14 ancillary buildings/sheds (SL No 9-22) out of 22 ancillary buildings/sheds and one 4 legged Self supported steel Communication Tower. Out of 8 production buildings/sheds, 7 buildings/sheds are used by ACS Textiles (Bangladesh) Ltd and only one production shed is used by ACS Towel Ltd. 22 Ancillary buildings/sheds and communication tower are combinedly used by The Alliance for Bangladesh Worker Safety Page 3/14

4 26 Sep 2018 both factories. Names of 8 production buildings/sheds used by ACS Textiles (Bangladesh) Ltd are - 1) 2 storied pre-fabricated weaving shed unit-1. 2) 2 storied pre-fabricated warping shed. 3) 1 storied prefabricated processing shed. 4) 2 storied pre-fabricated weaving shed unit-2. 5) 3 storied RC weaving -4 building. 6) 3 storied RC digital printing shed. 7) 2 storied RC warping (sizing-3)- building. Names of production shed used by ACS Towel Ltd is: 1) 3 storied (B+2) pre fabricated Towel shed (used by ACS Towel Ltd). Names of Ancillary buildings/sheds excluding 1 storied pre-fabricated grey & yarn shed (which is in process of demolition) and communication tower combinedly used by both factories are given below: 1) 3 storied RC office building. 2) 3 storied RC Accessories building. 3) 2 storied RC utility building unit-1 4) 3 storied RC chemical godown building. 5) 3 storied RC staff quarter. 6) 2 storied RC utility building unit-2 7) 2 storied Medical center. Child care and pump room shed. 8) 3 storied RC new Security Barrack (audited by us). 9) 3 leveled RC ETP complex (audited by us). 10) 1 storied RC security office attached with main gate (audited by us). 11) 1 storied RC security posts (6 Nos) (audited by us). 12) 1 storied RC smoking room (6 Nos) (audited by us). 13) 1 storied Empty drum store shed (audited by us). 14) 1 storied Wastage shed (audited by us). 15) 1 storied RC RMS room (audited by us). 16) 1 storied Carpentry workshop and Wastage room shed (audited by us). 17) 1 storied Salt store and ETP office shed (audited by us). 18) 1 storied Mechanical maintenance and oil heater shed (audited by us). 19) 1 storied Automobile workshop shed (audited by us). 20) 1 storied RC ATM Booth (audited by us). 21) 1 storied Parking shed (audited by us). 22) One 4 legged Self supported steel Communication Tower (audited by us) Is the building(s) owned or rented by the Factory?: Number of Building Levels (Stories) : Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Ancillary Structures in Complex : Owned 1) 3 storied RC new Security Barrack: 3-story above grade. All floors are use as security barrack. 2) Partially 3 leveled RC ETP complex: Partially 3 story with underground tank. 3) 1 storied RC security office attached with main gate: 1-story above grade. 4) 1 storied RC security posts (6 Nos): 1-story above grade. 5) 1 storied RC smoking room (6 Nos): 1-story above grade. 6) 1 storied Empty drum store shed: 1-story above grade. 7) 1 storied Wastage shed: 1-story above grade. 8) 1 storied RC RMS room: 1-story above grade. 9) 1 storied Carpentry workshop and Wastage room shed: 1-story above grade. 10) 1 storied Salt store and ETP office shed: 1-story above grade. 11) 1 storied Mechanical maintenance and oil heater shed: 1-story above grade. 12) 1 storied Automobile workshop shed: 1-story above grade. 13) 1 storied RC ATM Booth: 1-story above grade. 14) 1 storied Parking shed: 1-story above grade. Other Structure: 1) One 4 legged Self supported steel Communication Tower: Height about 70 ft. 1) 3 storied RC new Security Barrack: Ground floor 5,573 sft, 1st floor 5,573 sft and 2nd floor 5,573 sft (Total 5,573 x3 floor = 16,719 sft). 2) Partially 3 leveled RC ETP complex: 3) 1 storied RC security office attached with main gate: about 463 sft. 4) 1 storied RC security posts (6 Nos): 56 sft x 6 nos = 336 sft. 5) 1 storied RC smoking room (6 Nos): 49 sft x 6 nos = 297 sft. 6) 1 storied Empty drum store shed: about 1,276 sft. 7) 1 storied Wastage shed: about 1,632 sft. 8) 1 storied RC RMS room: about 333 sft. 9) 1 storied Carpentry workshop and Wastage room shed: about 390 sft. 10) 1 storied Salt store and ETP office shed: about 210 sft. 11) 1 storied Mechanical maintenance and oil heater shed: about 1,190 sft. 12) 1 storied Automobile workshop shed: about 574 sft. 13) 1 storied RC ATM Booth: about 171 sft. 14) 1 storied Parking shed: about 1,800 sft. Other Structure: 1) One 4 legged Self supported steel Communication Tower: about 220 sft. 1) 3 storied RC new Security Barrack: ) Partially 3 leveled RC ETP complex: ) 1 storied RC security office attached with main gate: ) 1 storied RC security posts (6 Nos): ) 1 storied RC smoking room (6 Nos): ) 1 storied Empty drum store shed: ) 1 storied Wastage shed: ) 1 storied RC RMS room: ) 1 storied Carpentry workshop and Wastage room shed: ) 1 storied Salt store and ETP office shed: ) 1 storied Mechanical maintenance and oil heater shed: ) 1 storied Automobile workshop shed: ) 1 storied RC ATM Booth: ) 1 storied Parking shed: Other Structure: 1) One 4 legged Self supported steel Communication Tower: Ancillary buildings/sheds are named as: 1) 3 storied RC office building. 2) 3 storied RC Accessories building. 3) 2 storied RC utility building unit-1 4) 3 storied RC chemical godown building. 5) 3 storied RC staff quarter. The Alliance for Bangladesh Worker Safety Page 4/14

5 26 Sep ) 1 storied pre fabricated grey and yearn shed (Demolition has been found in progress) 7) 2 storied RC utility building unit-2 8) 2 storied Medical center. Child care and pump room shed. 9) 3 storied RC new Security Barrack (audited by us). 10) Partially 3 leveled RC ETP complex (audited by us). 11) 1 storied RC security office attached with main gate (audited by us). 12) 1 storied RC security posts (6 Nos) (audited by us). 13) 1 storied RC smoking room (6 Nos) (audited by us). 14) 1 storied Empty drum store shed (audited by us). 15) 1 storied Wastage shed (audited by us). 16) 1 storied RC RMS room (audited by us). 17) 1 storied Carpentry workshop and Wastage room shed (audited by us). 18) 1 storied Salt store and ETP office shed (audited by us). 19) 1 storied Mechanical maintenance and oil heater shed (audited by us). 20) 1 storied Automobile workshop shed (audited by us). 21) 1 storied RC ATM Booth (audited by us). 22) 1 storied Parking shed (audited by us). Other Structure: 1) One 4 legged Self supported steel Communication Tower. Approximate Ancillary Structures Area (SF) : Number of Occupants : Provide brief description of the electrical system for each building.: Physical location of Substation? : What equipment/loads does the UPS serve? : 1) 3 storied RC new Security Barrack: Ground floor 5,573 sft, 1st floor 5,573 sft and 2nd floor 5,573 sft (Total 5,573 x3 floor = 16,719 sft). 2) Partially 3 leveled RC ETP complex: 3) 1 storied RC security office attached with main gate: about 463 sft. 4) 1 storied RC security posts (6 Nos): 56 sft x 6 nos = 336 sft. 5) 1 storied RC smoking room (6 Nos): 49 sft x 6 nos = 297 sft. 6) 1 storied Empty drum store shed: about 1,276 sft. 7) 1 storied Wastage shed: about 1,632 sft. 8) 1 storied RC RMS room: about 333 sft. 9) 1 storied Carpentry workshop and Wastage room shed: about 390 sft. 10) 1 storied Salt store and ETP office shed: about 210 sft. 11) 1 storied Mechanical maintenance and oil heater shed: about 1,190 sft. 12) 1 storied Automobile workshop shed: about 574 sft. 13) 1 storied RC ATM Booth: about 171 sft. 14) 1 storied Parking shed: about 1,800 sft. Other Structure: 1) One 4 legged Self supported steel Communication Tower: about 220 sft. In a total the numbers of occupants in the factory complex are 4,940 persons, ACS Textiles (Banglaesh) Ltd , and ACS Towels Ltd Out of 4,940 persons, there is a capacity of 196 persons in the ancillary structures assessed and the per floor data are given as under: storied RC new Security Barrack: Capacity-Level 1: (32 sleeping + dining 26=) 58 persons, Level 2: 44 persons, and Level 3: 48 persons. 2. Partially, 3- leveled RC ETP complex: Level-1: 22 and Level-2: storied RC security office attached to main gate: 5 persons, per shift is storied RC security posts (6 Nos): 6 persons, one in one post per shift storied RC smoking room (6 Nos): 18 persons, 3 in one room at a time storied Empty drum storage shed: 02 persons storied Wastage shed: 02 persons storied RC RMS room:01 person storied Carpentry workshop and Wastage room shed: 3 persons storied Salt store and ETP office shed: 01 person storied Mechanical maintenance and oil heater shed: 3 persons, per shift is storied Automobile workshop, shed: 02 persons storied RC ATM Booth: 3 persons in 3 shifts, per shift storied Parking shed: 04 person. Other Structure: 1. One 4-legged Self supported steel Communication Tower: Nil. Service Line : REB. LT Panel : 04nos. MDB : Nil. FDB : Nil. DB : 01nos. SDB : 03nos. Transformer : 1X1500KVA, 1X1250KVA, 2X1000KVA. Generator : 10X900KW, 3X1064KW. UPS/IPS : Nil. COS/Interlocking : 02nos. PFI : 5X1000KVAR. BBT Riser : Nil. Lift : Nil. Fuel Tank Capacity : Nil. Transformer, LT Panel, Generator, COS, PFI already audited in previous assessment. Outside of production building. IPS/UPS not required for audited structures. Because life safety loads are used by built in battery. The Alliance for Bangladesh Worker Safety Page 5/14

6 26 Sep 2018 ASSESSMENT FINDINGS Expansion Details Are as-built drawings available for new electrical safety features of the building? High Non-Compliance Level: Reviewed as built drawing available on site. Document Review: Reviewed single line diagram available. Alliance Standard reference 8.20 Electrical System Maintenance Is the electrical switchgear and panel boards inspected on an annual basis to ensure that the equipment is installed in accordance with the listed ratings? Non-Compliance Level: 3 The electrical switchgear and panel boards is not inspected on an annual basis to ensure that the equipment is installed in accordance with the listed ratings. Document Review: No documentation provided. Establish a periodic inspection program to ensure the electrical systems are free from damage, debris, dirt, lint, and installed in accordance with their listed ratings. Maintain records concerning inspections and follow up actions. Alliance Standards Part 10 Section Electrical Inspections The Alliance for Bangladesh Worker Safety Page 6/14

7 26 Sep 2018 Is a periodical Insulation Resistance Measurement Program established and recorded? Insulation Resistance Test Report was provided. But no pictorial evidence found. Document Review: No proper IR test program was recorded. Develop an Insulation Resistance Measurement Program that ensures deterioration of insulation resistance will be identified quickly. Testing should be in compliance with InterNational Electrical Testing Association (NETA). All transformers, switchgears etc. shall be subject to an insulation resistance measurement test to ground after installation but before any wiring is connected. Insulation tests shall be made between open contacts of circuit breakers, switches etc. and between each phase and earth. Alliance Standard Part 10 Section Insulation Tests and Electrical Inspections Electrical System Conditions Is a readily accessible single point of disconnect provided for each main electrical service feed? High Readily accessible single point of disconnect is not provided for each main electrical service feed. Location: SB/Security post. Photograph: No readily accessible single point of disconnect. Provide readily accessible single point of disconnect for each main electrical service feed. BNBC Main Switch and Switchboards The Alliance for Bangladesh Worker Safety Page 7/14

8 26 Sep 2018 Are switchboards and/or distribution boards installed in compliant locations? High Distribution boards are not installed in compliant locations. Location: SB/Security post. Photograph: DB is not in a compliant locations. Relocate distribution boards to suitable locations for operation and maintenance. Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear All metal in the building is connected to the building earthing/grounding system such as metal rebar in concrete, metal frame of building, or metal water pipe. High All metal in the building is not connected to the building earthing/grounding system. Location: ETP. Photograph: All metal has not proper grounding system. Survey the entire building to identify all locations of non-compliance. Connect all metal in the building to the building earthing system such as metal rebar in concrete, metal frame of building, or metal water pipe. Alliance Standard Part 10 Section Earthing Do switchboards and/or distribution boards have capacity information labels? Non-Compliance Level: 3 Distribution boards have no proper capacity information labels. Location: All panel boards. Photograph: No proper capacity information labels in DBs. Provide capacity information labels (Maximum current rating, number of circuit breakers, rated capacity of circuit breaker, etc.) for Switchboards and/or distribution boards. Display panel schedule on panel door (inner side) printed on a sheet made of non-combustible material. The Alliance for Bangladesh Worker Safety Page 8/14

9 26 Sep 2018 Alliance Standard Part 10 Section 10.7 Main Switch, Switchboards And Metal Clad Switchgear and Inspection of the Installation Are lighting and receptacle (socket) circuits segregated? Non-Compliance Level: 3 Lighting and receptacle (socket) are not circuits segregated. Location: Every floor of New security barrack Photograph: Lighting and receptacle (socket) has not been circuits segregated. Lighting and socket circuits must be separated at the noted locations. Have a qualified electrician separate the lighting and sockets into separate circuits. Alliance Standard Part 10 Section Do switchboards and/or distribution boards have clear identification markings? Distribution boards have no clear identification markings. Location: SB/Security post. Photograph: No marking in SB/Security post. Provide clear and permanent identification marks on all distribution boards, switchboards, sub main boards and switches and post proper caution/danger signage in all electrical panel boards. Alliance Standard Part 10 Section 10.7 BNBC Part 8 Section Are switchboards and/or distribution boards provided with physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed. Distribution boards are not provided with a physical means to prevent the The Alliance for Bangladesh Worker Safety Page 9/14

10 26 Sep 2018 installation of more over current devices than that number for which the panel board was designed, rated and listed. Location: SB/Security post. Photograph: No physical means for DBs. Verify the existing load does not exceed the panel rating. For switch boards and/or distribution boards, provide the physical means to prevent the installation of more over current devices than that number for which the panel board was designed, rated, and listed following NFPA 70 section Alliance Standards Part 10 Section 10.7 Main Switch, Switchboards and Metal Clad Switchgear Electrical wiring and conduit is properly supported. Electrical wiring and conduit is not properly supported. Location: ETP. Photograph: No proper support for electrical wiring. Survey all wiring and conduit to identify all locations where it is not properly supported and protected from physical damage. Provide adequate supports for electrical wiring and conduit. Consult a qualified electrical engineer for required remediation work and selection of appropriate materials. 15 Nov 2018 Alliance Standard Part 10 Section , , and Cable joints are through porcelain/pvc connectors with PIB tape wound around joint. Improper cable joints were found. Location: 1st floor of New security barrack. Photograph: Improper cable joints. Provide cable joints through porcelain/pvc connectors with PIB tape wound around joint before placing the cable in the box in accordance with Alliance Standard Section Alliance Standards Part 10 Section Cable Joints The Alliance for Bangladesh Worker Safety Page 10/14

11 26 Sep 2018 Lighting fixtures are supported from the structure and seismic bracing is installed as required. Lighting fixtures are not supported from the structure and seismic bracing is not installed as required. Location: ETP. Photograph: Lighting fixtures are not properly supported. Lighting fixtures need to be supported from the structure and seismic bracing will installed as required. Alliance Standards Part 10 Section Lighting Fittings Electrical connections at equipment, fixtures, etc are properly secured. Electrical connections at equipment, fixtures, etc are properly secured. Location: ETP. Photograph: Socket is not properly fixed. Socket shall be fixed with structure properly. Alliance Standards Part 10 Section Electrical Connections Are junction boxes and other electrical devices provided with covers? Junction boxes are not provided with covers. Location: 1st floor of New security barrack. Photograph: No cover for the Junction boxes. Provide adequate covers for junction boxes and other electrical devices according to Alliance Standard. The Alliance for Bangladesh Worker Safety Page 11/14

12 26 Sep 2018 Alliance Standard Part 10 Section and Mechanical guards are provided for electrical equipment and wiring where necessary. Mechanical guards are not provided for electrical equipment and wiring where necessary. Location: ETP. Photograph: No Mechanical guards. Survey all locations to identify missing mechanical guards. Provide mechanical guards for electrical equipment where necessary. 15 Nov 2018 Alliance Standard Part 10 Section 10.3 Electrical Wiring and Cabling, Cables, and 10.7 Main Switch, Switchboards And Metal Clad Switchgear Signage indicating the prohibition of light fixtures without protective covers is installed at required locations. Low Non-Compliance Level: 3 Signage indicating the prohibition of light fixtures without protective covers is not installed at required locations. Location: Wastage shed. Photograph: Signage indicating the prohibition of light fixtures without protective covers is not installed at required locations. "Light fixtures without protective covers (otherwise known as naked lights) shall not be allowed in storage areas or in any area where the Inspector of the Factories Rules ( ) Part 53 disallows these fixtures. Install signs posted in Bengali and English, indicating this prohibition at all entrances to these areas." Alliance Standards Part 10 Section Naked Lights Lightning Protection System The Alliance for Bangladesh Worker Safety Page 12/14

13 26 Sep 2018 Is a lightning protection system installed on the building? High Non-Compliance Level: 2 Lightning Protection System is not installed. Location: Except New security barrack. Photograph: Absence of Lightning Protection System. Lightning Protection System should be installed following NFPA Dec 2018 Alliance Standards Part 10 Section Lightning Protection. Calculate Risk Index to determine if required. The air termination network vertical and horizontal conductors are appropriately spaced. Non-Compliance Level: 2 Lightning Protection System is not installed. Location: Except New security barrack. Photograph: Absence of Lightning Protection System. Lightning Protection System should be installed following NFPA 780. Alliance Standards Part 10 Section Lightning Protection The appropriate number of down conductors are installed based on the building size. Non-Compliance Level: 2 Lightning Protection System is not installed. Location: Except New security barrack. Photograph: Absence of Lightning Protection System. Lightning Protection System should be installed following NFPA 780. The Alliance for Bangladesh Worker Safety Page 13/14

14 26 Sep 2018 Alliance Standards Part 10 Section Lightning Protection The lightning protection ground terminals are bonded to the building or structure grounding. Non-Compliance Level: 2 Lightning Protection System is not installed. Location: Except New security barrack. Photograph: Absence of Lightning Protection System. Lightning Protection System should be installed following NFPA 780. Alliance Standards Part 10 Section Lightning Protection The Alliance for Bangladesh Worker Safety Page 14/14

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT CHITTAGONG FASHION WEAR LTD. SOUTH HALISHAHAR, CHITTAGONG, BANGLADESH Factory List: 1. Chittagong Fashion Wear Ltd. 2. H & W Apparels Inspected on May 5, 2014 SUMMARY

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT Al Islam Textile Industries Ltd. Ramjannessa Super Market (2 nd Floor), 142, Senanibash Road, Pallabi, Mirpur12, Dhaka 1221, Bangladesh. Factory List: 1. Al Islam Textile

More information

Communications Site Installation R56 Installer and Communications Site Inspector/Auditor version COMPETENCY REQUIREMENTS

Communications Site Installation R56 Installer and Communications Site Inspector/Auditor version COMPETENCY REQUIREMENTS Communications Site Installation R56 Installer and Communications Site Inspector/Auditor version COMPETENCY REQUIREMENTS The following is a listing of each topic considered necessary to be included in

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 00 01 10 Table of Contents DIVISION 00: PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 06.17.2014 00 21 13 Instructions to Bidders 11.08.2013 00 22 13 Supplementary Instructions

More information

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast!

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast! PREFABRICATED SUBSTATIONS AND E-HOUSES tgood.com Energy, Fast! Global leader in prefabricated substations and E-House systems PRODUCT OVERVIEW Fully integrated prefabricated substations and E-House systems.

More information

Tier IV Standards as Specified in the TIA 942 Document

Tier IV Standards as Specified in the TIA 942 Document S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction

More information

Improved power supply after Fukushima and OPC in Japanese BWRs

Improved power supply after Fukushima and OPC in Japanese BWRs BWR-club workshop on Robust Power in Uppsala Improved power supply after Fukushima and OPC in Japanese BWRs May 3 rd, 2017 Hitachi-GE Nuclear Energy, Ltd Masashi Sugiyama Hitachi-GE Nuclear Energy, Ltd.

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

hp uninterruptible power system r12000 xr models installation instructions

hp uninterruptible power system r12000 xr models installation instructions hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Underground Warning Tape. 6. Lockout

More information

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment Installation Service Statement of Work Start-up Service for Cooling Start-up - 1 - Service for Cooling Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

GROUND FAULT CIRCUIT INTERUPTERS

GROUND FAULT CIRCUIT INTERUPTERS Title: GFCI Effective Date: 11/14/2014 Control Number: THG_0031 Revision Number: 1 Date: 10/21/2015 Annual Review Completed: 5/13/2015 GROUND FAULT CIRCUIT INTERUPTERS CONTENTS I. PURPOSE II. GENERAL REQUIREMENTS

More information

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS May 1, 2016 Reviewers should - Be aware that these checklists are not allinclusive but only provide important review items. Reviewers should - Use Checklists

More information

Preparing to Install the VG248

Preparing to Install the VG248 CHAPTER 2 To ensure normal system operation, plan your site configuration and prepare your site before installation. Before installing the VG248, review these sections: Preparing the Installation Site,

More information

POCKET MULTIMETER Model No: MM18

POCKET MULTIMETER Model No: MM18 INSTRUCTIONS FOR: POCKET MULTIMETER Model No: MM18 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions and properly maintained,

More information

PV Module Installation Instructions

PV Module Installation Instructions Name 1601A Page 1 / 8 Name 1601A Page 2 / 8 1 Introduction Thanks for purchasing PV modules of HT SOLAR ENERGY JOINT STOCK COMPANY This manual refers to PV modules manufactured and sold by HT Turkey. This

More information

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016 Safegard V4 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

ICS Entrance Management Sign Installation Guide. Version 1.0

ICS Entrance Management Sign Installation Guide. Version 1.0 ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document

More information

CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS

CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS Throughout this manual, look for this symbol. It means BE ALERT YOUR SAFETY IS INVOLVED. If you do not follow these safety instructions, personal

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

ELECTRICIANS REGULATIONS EXAMINATION 21 November 2015 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 21 November 2015 QUESTION AND ANSWER BOOKLET ER70 Candidate Code No. For Board Use Only Result Date Int Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 21 November 2015 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2 dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Original operating instructions Fail-safe inductive sensor GF711S / / 2013 Original operating instructions Fail-safe inductive sensor GF7S 8528 / 5 / 23 Contents Preliminary note...3. Explanation of symbols...3 2 Safety instructions...4 2. Safety-related requirements regarding

More information

Top 25 standards violated Oregon OSHA inspections, all industries, 2004

Top 25 standards violated Oregon OSHA inspections, all industries, 2004 Oregon OSHA inspections, all industries, 2004 1 1910.1200(e)(1) Written hazard-communication program 395 30 4 0 361 $7,735 $6,635 $1,100 $0 $0 2 437-3-1501 General fall-protection requirements 373 315

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

User Manual. Item no.: Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel.: +49(0) Kunststofferzeugnisse D Teningen Fax: +49(0)

User Manual. Item no.: Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel.: +49(0) Kunststofferzeugnisse D Teningen Fax: +49(0) User Manual AquaControl + Rainwater System Controller Item no.: 351027 Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel.: +49(0)7641-5890 Kunststofferzeugnisse D-79 331 Teningen Fax: +49(0)7641-58950 Page 1 Figure

More information

Open Access. Definitions

Open Access. Definitions Open-IX Data Center Technical Standards Version 2.0, January 1, 2018 Questions: dc-group@open-ix.org The purpose of the Open- IX Data Center Technical Standards document is to establish a recommended standard

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.

More information

Power System Vulnerabilities : AHCA 2016 Copyright (c) 2016 SSR, Inc. All rights reserved

Power System Vulnerabilities : AHCA 2016 Copyright (c) 2016 SSR, Inc. All rights reserved Training presentation for: AHCA Florida 2016 Annual Conference Finding & Managing Power System Vulnerabilities David Stymiest, CHFM, CHSP, FASHE, (PEin LA MS MA) Copyright 2016, Smith Seckman Reid, Inc.;

More information

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector

More information

UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS TABLE OF CONTENTS

UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS TABLE OF CONTENTS Table of Contents Introduction Changes from September 16, 2013 version to January 16, 2015 version Supplemental General Requirements (asterisk * indicates revised) 00 00 02 Terms * 00 00 03 Modifications

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2600B-PM-1 200 V Protection Module with 1 A Clamp Description The Model 2600B-PM-1 200 V Protection

More information

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions HP UPS R/T3000 ERM Installation Instructions Overview The ERM consists of two battery packs in a 2U chassis. The ERM connects directly to a UPS R/T3000 or to another ERM. Up to two ERM units can be connected.

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W

More information

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN This Inspection Checklist for Rooftop Photovoltaic (PV) Systems is based on the Model Inspection Checklist

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

ING CITY COUNCIL AGENDA REPORT. Honorable Mayor and City Council Members. Director of Public Works - Utilities. Final Payment Applications

ING CITY COUNCIL AGENDA REPORT. Honorable Mayor and City Council Members. Director of Public Works - Utilities. Final Payment Applications City of RED W1' ING CITY COUNCIL AGENDA REPORT TO: Honorable Mayor and City Council Members FROM: Bob Stark Deputy Director of Public Works - Utilities Agenda Item No.: 8- M Meeting Date: September 25,

More information

StringPin Pinsetter with Electrical Requirements

StringPin Pinsetter with Electrical Requirements Pre-Installation Manual StringPin Pinsetter with Electrical Requirements July 2018 / 10-095400-079 Brunswick StringPin Pinsetter Electrical Requirements Pre-Installation Manual July 2018 by the Brunswick

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

Model 7416LED

Model 7416LED INSTALLATION INSTRUCTIONS FOR Model 7416LED www.sportablescoreboards.com 1 Table of Contents DESCRIPTION... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:... 3 INSTRUCTIONS FOR REPORTING SHIPPING

More information

UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS TABLE OF CONTENTS

UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS TABLE OF CONTENTS Table of Contents Introduction Changes from August 1, 2016 version to April 30, 2018 Supplemental General Requirements (asterisk * indicates revised) 00 00 02 Terms 00 00 03 Modifications to General Requirements

More information

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-STC Kelvin Standard Triaxial Connector Card Description The Model 8020-STC Kelvin Standard

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

4P S. Wireless LAN Connecting Adapter <BRP069A42> Installation Manual

4P S. Wireless LAN Connecting Adapter <BRP069A42> Installation Manual 4P359542-2S Wireless LAN Connecting Adapter Installation Manual Wireless LAN Connecting Adapter Installation Manual Homepage: http://www.onlinecontroller.daikineurope.com For details

More information

Digital Multimeter Safety Tips

Digital Multimeter Safety Tips Digital Multimeter Safety Tips Most engineers perform measurements with a digital multimeter (DMM) as part of their job. Before you grab the nearest handheld DMM next time, make sure you select the right

More information

HPE Energy Efficiency Certification Service

HPE Energy Efficiency Certification Service Data sheet HPE Energy Efficiency Certification Service HPE Technology Consulting As power consumption and heat generation in the data center increase due to information explosion, big data, e-commerce,

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

Model 2657A-LIM-3 LO Interconnect Module

Model 2657A-LIM-3 LO Interconnect Module Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect

More information

The following symbols are used to show dangerous operation or handling. Make sure you understand them before reading the guide.

The following symbols are used to show dangerous operation or handling. Make sure you understand them before reading the guide. Safety Instructions Before use Thank you very much for purchasing this product. This product is an interface box called "Connection & Control Box" for EPSON short throw projectors. For your safety, read

More information

Model 7705 Control Module

Model 7705 Control Module www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

NZQA unit standard version 2 Page 1 of 5

NZQA unit standard version 2 Page 1 of 5 Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62305-4 Edition 2.0 2010-12 Protection against lightning Part 4: Electrical and electronic systems within structures INTERNATIONAL ELECTROTECHNICAL COMMISSION XC ICS 29.020;

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

DIRECT POWER LIGHTING MANUAL

DIRECT POWER LIGHTING MANUAL SS2 -RGBW RGBW-18L DIRECT POWER LIGHTING MANUAL Coloronix, Inc. 5461 West Jefferson Boulevard Los Angeles, California 90016 (323) 677-4242 http://www.rgbw.com Summary Introduction RGB Color Changing Adjustable

More information

4100/4120-Series Class A / Class B Zone Modules Installation Instructions

4100/4120-Series Class A / Class B Zone Modules Installation Instructions 4100/4120-Series Class A / Class B Zone Modules Installation Instructions Introduction This publication describes the installation procedure for the following modules. Model Description Required Back Box

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND

More information

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

English. Operating Manual. Conductive point level switch MLR120.  Retain for later reference. Companies / brands of GHM English Operating Manual Conductive point level switch MLR120 Companies / brands of GHM www.ghm-group.de Retain for later reference Table of contents Page 1. Proper use (application areas)... 3 Safety

More information

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

How to choose the correct Mount Kelvin central unit

How to choose the correct Mount Kelvin central unit Installation guide Outside world Property Wirepas mesh Mount Kelvin app Internet connection Ethernet DALI 3rd party integrations Mount Kelvin cloud Mount Kelvin central unit Voice control EnOcean wireless

More information

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC ::

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC :: Module Title Duration : Course CTDC : Certified TIA-942 Design Consultant : 3 days Course Description Data centres are at the core of many organisations. Downtime of the data centre could lead to major

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

The right solution for every home

The right solution for every home Domae Household switchboards The right solution for every home Household guide 2002 Building a New Electric World. Household switchboards Domae The right solution for every home Household guide 2002 Building

More information

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-200-KIT 200 V Bias Tee Kit Description The CVU-200-KIT Bias Tee Kit consists of three 2600-RBT-200

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 6 APPR:MDW:JVG:06-08-18

More information

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C*

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C* System Controller SC-201-6M INT Installation Manual Potential dangers from accidents during installation and use are divided into the following two categories. Closely observe these warnings, they are

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

Wa r n i n g-wa r n i n g-wa r n i n g

Wa r n i n g-wa r n i n g-wa r n i n g Installation Instructions of the Power Analyzer Wa r n i n g-wa r n i n g-wa r n i n g Read and understand this manual before connecting device. Death, fire or serious injury can occur from using equipment

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

MEM31215 Certificate III in Engineering - Industrial Electrician

MEM31215 Certificate III in Engineering - Industrial Electrician MEM31215 Certificate III in Engineering - Industrial Electrician Release 2 MEM31215 Certificate III in Engineering - Industrial Electrician Modification History Release 2. MSAENV272B updated to MSMENV272.

More information

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nomination title: Schneider Electric Prefabricated, Pre Assembled Data Centre Modules Schneider Electric has introduced a

More information

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template.

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template. 6. ENGINEERING SYSTEMS REQUIREMENTS G40 SITE ELECTRICAL UTILITIES SYSTEMS REQUIREMENTS SITE ELECTRICAL UTILITIES TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT

More information

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W. HP R/T2200 UPS Installation Instructions Overview The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W. For more information about any of the topics covered in this document, see

More information

Refurbishment of Switchgear and Switchgear Devices

Refurbishment of Switchgear and Switchgear Devices White Paper Refurbishment of Switchgear and Switchgear Devices Low and Medium Voltage Products Introduction There are many suppliers who suggest to users that switchgear assemblies, circuit breakers, and

More information

Panel Installation Datasheet

Panel Installation Datasheet ACTIONPAC LNS5 & SAFEGARD V5 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product

More information

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2 Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

Integration Fully integrated Controls, Power Monitoring, Generator Paralleling, and Switching Schemes as a complete turnkey solution.

Integration Fully integrated Controls, Power Monitoring, Generator Paralleling, and Switching Schemes as a complete turnkey solution. Technical Datasheet Tier Power Systems, Inc. iq Series UL 1558 Switchgear Tier Power Systems iq Series is a leader in switchgear technology. iq Series provides advanced power distribution technology and

More information

Wire Communications Design jfm 07. An Inside Look at Outside Plant

Wire Communications Design jfm 07. An Inside Look at Outside Plant An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information