Improved power supply after Fukushima and OPC in Japanese BWRs

Size: px
Start display at page:

Download "Improved power supply after Fukushima and OPC in Japanese BWRs"

Transcription

1 BWR-club workshop on Robust Power in Uppsala Improved power supply after Fukushima and OPC in Japanese BWRs May 3 rd, 2017 Hitachi-GE Nuclear Energy, Ltd Masashi Sugiyama Hitachi-GE Nuclear Energy, Ltd All rights reserved.

2 Improved power supply after Fukushima and OPC in Japanese BWRs Contents 1.Current Situation of Japanese BWRs 2.Fukushima trouble experience 3.Improvements 4.Open phase Condition Hitachi-GE Nuclear Energy, Ltd All rights reserved.

3 1-1. Current Situation of Japanese BWRs Unfortunately, None of BWR power plants resume operation after Fukushima accident. We had twenty-eight (28) operating BWRs including Fukushima Daiichi, four (4) units were under construction and four (4) were planning stage power plants before the accident. Eight (8) units including six (6) units of Fukushima Daiichi were decided to be decommissioning. The other units, especially Kashiwazaki-Kariwa unit 7 (ABWR), Shimane unit 2 (BWR5), Onagawa unit 3 (BWR5), and Tokai unit 2 (BWR6) are under assessment to restart. On the other hands, nine (9) units out of twenty-six (26) PWRs have already got the permission to restart. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 2

4 2. Fukushima Trouble Experience On March 11 th All of off-site power was lost due to the earthquake. As for Fukushima Unit 1-4, there were 4 lines of 275kV and 1 line of 66kV, 2 lines of 275kV were lost due to the ACB failures in the switchyard. As for the rest of 2 lines, one line was under construction to replace ACB with GCB and another line was flood affected by Tsunami. The ACBs in the off-site substation were broken caused by earthquake. The cables from 66kV switchyard to unit 1 switchgear were lost due to the earthquake. (The 66kV line itself was available.) 2. All of medium voltage switchgears was flood by Tsunami. Due to the old design, separation between redundant systems was insufficient. 3. All of DGs successfully started as designed after LOPA but they were lost due to Tsunami. 4. DC power supplies except unit 3 was lost due to Tsunami. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 3

5 3-1. Off-site power LOPA by CCF In case of Fukushima, all of off-site power except 66kV line came from only one Substation. The 66kV line was not considered as back-up off-site power for safety systems. The ACBs in the Substation were broken due to earthquake. To confirm at least two independent substations and the independent transmission lines shall be able to feed off-site power to the NPP. To confirm GIS application which has stronger seismic resistance. To confirm separation. Some modification have been done at the cable space under the main control room floor. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 4

6 3-2. On-site power source Improvement against SBO Additional power sources 1) Additional switchgears on the hill. 2) Additional on-site power supply ( GTG etc.) 3) Mobile power sources ( Trucks) with the connection panels for them. 4) Additional batteries for RCIC on the higher floor. Load shedding on the other div. batteries. Extended the design base DC power supplies' coping time from 8hrs to 12hrs. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 5

7 3-3. Improvement against Tsunami Improvement against Tsunami Physical protections 1) Embankment 2) Sea wall 3) Waterproof doors 4) Stagnant at the penetrations ( pipes and trays) Hitachi-GE Nuclear Energy, Ltd All rights reserved. 6

8 3-4. Improvement against the other hazards The other hazards have been estimated. Earthquake Tornado 1)Fixing outside facilities such as DG oil pumps. 2)Enhanced or underground DG fuel tanks Neighborhood fire 1)Fire belt surrounding the buildings. The inner overflow 1) Water proof ( cable and pipe penetrations, Hatch's, HVAC ducts and doors.) 2) Prevention of the counter flow of the floor drains. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 7

9 3-5. Improvement against the other hazards Fire 1) Separation 2) Fire wall Snow Low temperature Eruption of Volcano Lightning Hitachi-GE Nuclear Energy, Ltd All rights reserved. 8

10 4. Open Phase Condition Current Situation Lower risk, compare with the U.S. plants 1) CV cable connections between Switchyard to start-up transformers. No overhead transmission lines nor air insulation points. 2) Multiple overhead transmission lines. The risk of open phase condition of the switchyard bus is low. Protection relay for OPC is now under development. 1) Transformer excitation current, 3 phase currents and 3 phase voltages both magnitudes and angles are detected. 2) Proper logic to detect OPC in any case is under consideration. Hitachi-GE Nuclear Energy, Ltd All rights reserved. 9

11 Thank you for your attention Hitachi-GE Nuclear Energy, Ltd All rights reserved. 10

Hitachi-GE Nuclear Energy, Ltd.(HGNE) Junichi Kawahata. Ref. CNJ-OG-G056Rev.7.3 All Rights Reserved Copyright 2009, Hitachi-GE Nuclear Energy, Ltd.

Hitachi-GE Nuclear Energy, Ltd.(HGNE) Junichi Kawahata. Ref. CNJ-OG-G056Rev.7.3 All Rights Reserved Copyright 2009, Hitachi-GE Nuclear Energy, Ltd. Advanced Technologies and Further Evolution Towards New Build NPP Projects International Conference on Opportunities and Challenges for Water Cooled Reactors in the 21st Century Hitachi-GE Nuclear Energy,

More information

nuclearsafety.gc.ca Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada

nuclearsafety.gc.ca Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada R.P. Rulko () IAEA Technical Meeting on Evaluation of Nuclear Power Plant Design Safety in the Aftermath

More information

Situation and response of JAEA to the Earthquake in Northeastern Japan (Outline of activities on March 11-15)

Situation and response of JAEA to the Earthquake in Northeastern Japan (Outline of activities on March 11-15) As of 20:00, March 15, 2011 Japan Atomic Energy Agency Situation and response of JAEA to the Earthquake in Northeastern Japan (Outline of activities on March 11-15) Summary Situation of each site Commercial

More information

The failings of the Advanced Boiling Water Reactor (ABWR) proposed for Wylfa Nuclear Power Station

The failings of the Advanced Boiling Water Reactor (ABWR) proposed for Wylfa Nuclear Power Station The failings of the Advanced Boiling Water Reactor (ABWR) proposed for Wylfa Nuclear Power Station Professor Steve Thomas, Emeritus Professor of Energy Policy University of Greenwich May 2018 Construction

More information

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS Presentation by: RANA NASIR ALI General Manager, Power Plants Projects, at PITCO November 02, 2017 ELECTRICAL PLANT CONCEPT The electrical equipment, depending

More information

TVA Response to the Fukushima Event and Lessons Learned from Recent Natural Disasters

TVA Response to the Fukushima Event and Lessons Learned from Recent Natural Disasters TVA Response to the Fukushima Event and Lessons Learned from Recent Natural Disasters SOUTHERN LEGISLATIVE CONFERENCE July 17, 2011 Agenda Centralized Response Center What We Have Done Key Initiatives

More information

United States Nuclear Regulatory Commission Post 2011 Fukushima Daiichi Event Actions

United States Nuclear Regulatory Commission Post 2011 Fukushima Daiichi Event Actions United States Nuclear Regulatory Commission Post 2011 Fukushima Daiichi Event Actions Presenter Jerome Bettle 1 NRC Response included offering technical assistance to the Japanese government and monitoring

More information

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast!

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast! PREFABRICATED SUBSTATIONS AND E-HOUSES tgood.com Energy, Fast! Global leader in prefabricated substations and E-House systems PRODUCT OVERVIEW Fully integrated prefabricated substations and E-House systems.

More information

Step 4 Assessment of Electrical Engineering for the UK Advanced Boiling Water Reactor

Step 4 Assessment of Electrical Engineering for the UK Advanced Boiling Water Reactor Title of document New Reactors Division Step 4 Assessment of Electrical Engineering for the UK Advanced Boiling Water Reactor Assessment Report: ONR-NR-AR-17-018 Revision 0 December 2017 Template Ref:

More information

ABWR Reactor Technology

ABWR Reactor Technology 9 th International School on Nuclear Power Hitachi-GE Nuclear Energy, Ltd. Property ABWR Reactor Technology Polish benefits from a U.K deployment Kazue Okumura HGNE Nuclear Engineering David Hinds GEH

More information

Status of Full-fledged Recovery following the Great East Japan Earthquake and Future Measures

Status of Full-fledged Recovery following the Great East Japan Earthquake and Future Measures Status of Full-fledged Recovery following the Great East Japan Earthquake and Future Measures March 1, 2012 Nippon Telegraph and Telephone East Corporation ( NTT EAST ) Efforts following the Great East

More information

The contribution of ETSON to improved emergency preparedness in the light of the Fukushima NPS accident

The contribution of ETSON to improved emergency preparedness in the light of the Fukushima NPS accident The contribution of ETSON to improved emergency preparedness in the light of the Fukushima NPS accident F.-P. Weiss (GRS) A. Kerner (GRS), E. Scott-de-Martinville (IRSN), et al. Introduction ETSON members

More information

Local Supply Chain Development

Local Supply Chain Development GE Hitachi Nuclear Energy International Local Supply Chain Development Douglas McDonald Vice President, Africa and Middle East NPP Sales GE Hitachi Nuclear Alliance Wilmington, NC Tokyo, Japan Nuclear

More information

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October FLEX Implementation Roy Harter RLH Global Services rlharter@aol.com SAMG-D course, IAEA, Vienna, Austria 19-23 October 2015 What is FLEX? US Nuclear Industry Response to NRC Mitigating Strategies Order

More information

Open Access. Definitions

Open Access. Definitions Open-IX Data Center Technical Standards Version 2.0, January 1, 2018 Questions: dc-group@open-ix.org The purpose of the Open- IX Data Center Technical Standards document is to establish a recommended standard

More information

UK ABWR Generic Design Assessment Generic PCSR Chapter 4 : Safety Management throughout Plant Lifecycle

UK ABWR Generic Design Assessment Generic PCSR Chapter 4 : Safety Management throughout Plant Lifecycle Form10/00 Document ID Document Number Revision Number : : GA91-9101-0101-04000 QGI-GD-0008 C Generic Design Assessment Generic PCSR Chapter 4 : Safety Management throughout Plant Lifecycle Hitachi-GE Nuclear

More information

Fukushima Daiichi Nuclear Power Station Unit 2 Primary Containment Vessel Internal Investigation Results (Bulletin)

Fukushima Daiichi Nuclear Power Station Unit 2 Primary Containment Vessel Internal Investigation Results (Bulletin) Fukushima Daiichi Nuclear Power Station Unit 2 Primary Containment Vessel Internal Investigation Results (Bulletin) January 19, 2018 Tokyo Electric Power Company Holdings, Inc. 1. Primary containment

More information

SCADA Training - T&D Automation

SCADA Training - T&D Automation SCADA Training - T&D Automation Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This course covers all the

More information

Electrical Equipment and Comprehensive Power Grid Solutions

Electrical Equipment and Comprehensive Power Grid Solutions Integration into the future Electrical Equipment and Comprehensive Power Grid Solutions About us Joint-Stock Company Rusatom Automated Control Systems (JSC RASU) is a subsidiary of State Atomic Energy

More information

Nuclear Generation Event Response: Strengthening Safety After Fukushima. Jim Scarola Executive Director US Industry Fukushima Response

Nuclear Generation Event Response: Strengthening Safety After Fukushima. Jim Scarola Executive Director US Industry Fukushima Response Nuclear Generation Event Response: Strengthening Safety After Fukushima Jim Scarola Executive Director US Industry Fukushima Response 1 Industry Response Coordination The Way Forward Fukushima Response

More information

IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA. Aram Hakobyan and Craig Nierode Dominion Energy

IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA. Aram Hakobyan and Craig Nierode Dominion Energy IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA Aram Hakobyan and Craig Nierode Dominion Energy PSA-2017 Pittsburgh, PA FLEX strategies OVERVIEW Surry plant features and risk contributors Flooding SBO FLEX

More information

Emergency Support Function (ESF) #14a: UTILITIES: Central Electric & Steam. ESF Activation Contact: Cornell IPP Customer Service (607)

Emergency Support Function (ESF) #14a: UTILITIES: Central Electric & Steam. ESF Activation Contact: Cornell IPP Customer Service (607) Emergency Support Function (ESF) #14a: UTILITIES: Central Electric & Steam ESF Activation Contact: Cornell IPP Customer Service (607)255-5322 Primary Department I. Purpose: Cornell IPP: Utilities and Energy

More information

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages.

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company LVM Versicherung Kolde-Ring 21 48126 Münster, Germany to confirm that its security area Data Center

More information

IEEE 2014 T&D Conference Paper 14TD Storm & Flood Hardening of Electrical Substations

IEEE 2014 T&D Conference Paper 14TD Storm & Flood Hardening of Electrical Substations 1 IEEE 2014 T&D Conference Paper 14TD0564 - Storm & Flood Hardening of Electrical Substations FORUM 2 Transformers, Substations and Switchgear Forum Room: W185BC, Paper: 14TD0564 Tuesday, April 15, 2014

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

Substation SCADA Monitoring

Substation SCADA Monitoring Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component

More information

Microprocessor protection and automation devices

Microprocessor protection and automation devices Microprocessor protection and automation devices THE ТЭМП 2501 MICROPROCESSOR PROTECTION TERMINALS It is well known that microprocessor protection devices have indisputable advantages over electromechanical

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Factory Name: ACS TEXTILES (BANGLADESH) LTD. Tetlabo, Barpa Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 26 Sep 2018 The Alliance for Bangladesh Worker

More information

FLOOD VULNERABILITY ASSESSMENT FOR CRITICAL FACILITIES

FLOOD VULNERABILITY ASSESSMENT FOR CRITICAL FACILITIES FLOOD VULNERABILITY ASSESSMENT FOR CRITICAL FACILITIES Lisa Graff GIS Team Manager Prairie Research Institute Illinois State Water Survey University of Illinois OUTLINE Motivation Project details Partners

More information

Technical Report REVISION SHEET. STUDSVIK UK LIMITED ENSREG Stress Tests : Final Report NO PROTECTIVE MARKING NO PROTECTIVE MARKING.

Technical Report REVISION SHEET. STUDSVIK UK LIMITED ENSREG Stress Tests : Final Report NO PROTECTIVE MARKING NO PROTECTIVE MARKING. STUDSVIK UK LIMITED ENSREG Stress Tests : Final Report REVISION SHEET Rev. Description Revised By Checked By Approved By A Original copy ER DS MM Studsvik Report Reference: TR_MRF021 Revision: Rev A Date:

More information

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS May 1, 2016 Reviewers should - Be aware that these checklists are not allinclusive but only provide important review items. Reviewers should - Use Checklists

More information

EFASOLAR PVStation Solutions

EFASOLAR PVStation Solutions www.efacec.com EFASOLAR PVStation Solutions EFASOLAR PVStation EFASOLAR PVStation Solutions 0,5 MW 1 x EFASOLAR 50 0,50 MW 1 x EFASOLAR 500M 1 MW 1,46 MW Efacec is a century-long experienced company in

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 6 pages.

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 6 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Bayer Business Services GmbH Düsseldorfer Straße 600 51061 Leverkusen, Germany to confirm that its security

More information

PPC (Plant Process Computer) Replacement Project for TEPCO Summary and Lessons Learned

PPC (Plant Process Computer) Replacement Project for TEPCO Summary and Lessons Learned PPC (Plant Process Computer) Replacement Project for TEPCO Summary and Lessons Learned Masaichi Kitajima Hidefumi Naito Tokyo Electric Power Services Co.,ltd Object of this Presentation TEPSCO recently

More information

IAEA Activities under the Nuclear Safety Action Plan

IAEA Activities under the Nuclear Safety Action Plan International Experts Meeting on Strengthening the Effectiveness of Research and Development in the Light of the Fukushima Daiichi Power Plant Accident February 16 20, 2015 IAEA Activities under the Nuclear

More information

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC ::

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC :: Module Title Duration : Course CTDC : Certified TIA-942 Design Consultant : 3 days Course Description Data centres are at the core of many organisations. Downtime of the data centre could lead to major

More information

Tier IV Standards as Specified in the TIA 942 Document

Tier IV Standards as Specified in the TIA 942 Document S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction

More information

Delaware s Premier Suburban Office Park

Delaware s Premier Suburban Office Park IRON IRON HILL HILL CORPORATE CORPORATE CENTER CENTER Delaware s Premier Suburban Office Park WHITE WING 700 RED WING 750 BLUE WING 800 www.cbre.us/ironhill PROJECT SUMMARY White Wing Red Wing Blue Wing

More information

Delaware s Premier Suburban Office Park

Delaware s Premier Suburban Office Park IRON IRON HILL HILL CORPORATE CORPORATE CENTER CENTER Delaware s Premier Suburban Office Park WHITE WING 700 RED WING 750 www.cbre.us/ironhill PROJECT SUMMARY White Wing Red Wing Blue Wing Parking Garage

More information

GE Enterprise Solutions. Digital Energy

GE Enterprise Solutions. Digital Energy GE Enterprise Solutions Digital Energy g Digital Energy we protect and connect the world s critical equipment to ensure safe, reliable power Our strength lies in the innovative people who deliver solutions

More information

MXPLC. Compact PLC process station. Summary. Application HVAC control systems, data acquisition, interfacing 3 rd party systems.

MXPLC. Compact PLC process station. Summary. Application HVAC control systems, data acquisition, interfacing 3 rd party systems. MXPLC Compact PLC process station Summary The MXPLC is a programmable process station with integrated I/O module with the I/O mix optimized for larger HVAC control applications. The multi-interface process

More information

Seismic-Initiated events risk mitigation in LEad cooled Reactors SILER How to isolate an NPP interface components: Metal Bellows Expansion joints

Seismic-Initiated events risk mitigation in LEad cooled Reactors SILER How to isolate an NPP interface components: Metal Bellows Expansion joints Seismic-Initiated events risk mitigation in LEad cooled Reactors SILER How to isolate an NPP interface components: Metal Bellows Expansion joints What are Metal Bellows Expansion Joints Metal Bellows Expansion

More information

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM Data Center Facility Analysis Project Final Presentation Wednesday, July 22, 2009 1:30 3:30 PM 1 Commonwealth Technology Center Conference Rooms 1 & 2 Enterprise Server Farm (ESF) Facility Data: 1 Technology

More information

Hitachi s Latest Supervisory, Operation and Control System for Thermal Power Station

Hitachi s Latest Supervisory, Operation and Control System for Thermal Power Station Hitachi Review Vol. 52 (2003), No. 2 111 Hitachi s Latest Supervisory, Operation and Control System for Thermal Power Station Isao Kume Shigeki Adachi Kazuo Furudate OVERVIEW: Hitachi supplied Jiangxi

More information

Call for Papers GCC POWER 2011 GCC Cigre s Leading Electric Power Conference & Exhibition In the Gulf Region

Call for Papers GCC POWER 2011 GCC Cigre s Leading Electric Power Conference & Exhibition In the Gulf Region Call for Papers GCC POWER 2011 GCC Cigre s Leading Electric Power Conference & Exhibition In the Gulf Region Kuwait - November 2011 GCC Cigre, is pleased to announce its 7 th International Conference GCC

More information

Benefits, offering and references

Benefits, offering and references DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals

Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals Per Nyström a, Carl Sunde a, and Cilla Andersson b a Risk Pilot, Gothenburg, Sweden b Ringhals AB, Varberg, Sweden

More information

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC February 17, 2010 Revised SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BACKGROUND INFORMATION Syracuse University

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at rotection Speeds Karl Iliev San Diego Gas & Electric Company Eric Udren Quanta Technology, LLC Copyright

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information

DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書

DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書 DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書 Read and save these insturctions 2008 Antari Lighting & Effects Ltd. User Manual Antari DNG-200 Low fog Generator Congratulations on the purchase

More information

FACILITY COMPONENTS - MIDDLE SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL SITE AREAS Parking and Access - Buses 4.0 2.0 0.59 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 4.0 3.0 0.89 Parking and Access

More information

The Fukushima accident Consequences for Japan and France

The Fukushima accident Consequences for Japan and France The Fukushima accident Consequences for Japan and France André-Claude Lacoste Chairman of the French Nuclear Safety Authority (ASN) 16 March 2012 16 March 2012 - The Georges Washington University ASN s

More information

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities UTILITIES ELEMENT NOTE: Unless otherwise noted, the goals, objectives and policies contained in this element shall guide development of the Main Campus and Southwest Campus in Tallahassee as well as the

More information

TRENDS IN SWITCHGEAR SPECIFICATIONS

TRENDS IN SWITCHGEAR SPECIFICATIONS TRENDS IN SWITCHGEAR SPECIFICATIONS What changes are we seeing in equipment specifications? What s being discussed in client meetings? What s happening in the market to support these requests? EQUIPMENT

More information

Work on Reconstruction of Electrical Systems at Sendai s Minami-Gamo Sewage Treatment Center Following Great East Japan Earthquake

Work on Reconstruction of Electrical Systems at Sendai s Minami-Gamo Sewage Treatment Center Following Great East Japan Earthquake Hitachi Review Vol. 64 (2015), No. 9 598 Featured Articles Work on Reconstruction of Electrical Systems at Sendai s Minami-Gamo Sewage Treatment Center Following Great East Japan Earthquake Yasuhiro Kato

More information

CenturyLink Data Center Services Omaha, Nebraska

CenturyLink Data Center Services Omaha, Nebraska CenturyLink Data Center Services Omaha, Nebraska HIGH AVAILABILITY ENTERPRISE COMPUTING Designed and equipped to meet the demands of enterprises, wholesale businesses and government agencies, CenturyLink

More information

Retrofitting sewage plants with lightning and surge protection measures

Retrofitting sewage plants with lightning and surge protection measures 904 Retrofitting sewage plants with lightning and surge protection measures A more efficient use of drinking water is growing in significance, especially against a backdrop of increasingly scarce drinking

More information

Horizon Nuclear Power

Horizon Nuclear Power Horizon Nuclear Power Experience of Developing and Building ABWRs in the UK Dr Janet Wilson Director of Licensing and Permissions IAEA Technical Meeting, Vienna 4 February 2014 Horizon Nuclear Power Established

More information

ICON SERIES IDRIVE. Intelligent Constant Pressure. Water Supply Controller User Manual. idrive

ICON SERIES IDRIVE. Intelligent Constant Pressure. Water Supply Controller User Manual. idrive ICON SERIES IDRIVE Intelligent Constant Pressure Water Supply Controller User Manual idrive1150-240 CONTENTS PREFACE 3 1. PRODUCT DESCRIPTION 4 1.1 Functions Description 4 1.2 Model List 4 1.3 Nameplate

More information

Twin Core Data Center Munich

Twin Core Data Center Munich Twin Core Data Center Munich T-Systems Data Center Munich Sister Site, Back Up Location/Twin Core DC ALL (Allach) 1st Route: 13km DWDM System 2nd Route: 27km DC EIP (Euro Industrie Park) Point to Point

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Indirect Adiabatic and Evaporative Data Centre Cooling

Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced

More information

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages.

fulfils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Finanz Informatik GmbH & Co. KG Theodor-Heuss-Allee 90 60486 Frankfurt a. M., Germany to confirm that

More information

Hitachi s Recent Efforts to Cope with Growing Global Nuclear Energy Market

Hitachi s Recent Efforts to Cope with Growing Global Nuclear Energy Market Hitachi Review Vol. 58 (2009), No.2 107 Hitachi s Recent Efforts to Cope with Growing Global Nuclear Energy Market Takashi Masui Masahiko Nakane Masatoshi Takada Noriaki Wada OVERVIEW: The current state

More information

Indirect Adiabatic and Evaporative Data Center Cooling

Indirect Adiabatic and Evaporative Data Center Cooling Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology

More information

Overview. Introduction. Damage Assessment Process Questions objective Data Collection Data Examination Analysis Reporting. Case Study.

Overview. Introduction. Damage Assessment Process Questions objective Data Collection Data Examination Analysis Reporting. Case Study. Alexis Kwasinski Field Damage Assessments as a Design Tool for Information and Communications Technology Systems that are Resilient to Natural Disasters Overview Introduction Damage Assessment Process

More information

High-Reliability, Next-Generation Supervisory and Control System for Power Stations

High-Reliability, Next-Generation Supervisory and Control System for Power Stations 214 High-Reliability, Next-Generation Supervisory and Control System for Power Stations High-Reliability, Next-Generation Supervisory and Control System for Power Stations Akio Ito Kazuo Furudate Masayuki

More information

Infrastructure Resilience in Northland. Northland Lifelines Group October 2008

Infrastructure Resilience in Northland. Northland Lifelines Group October 2008 Infrastructure Resilience in Northland Northland Lifelines Group October 2008 NLG what have we achieved so far? Priority utility sites and routes Lifeline utility protocols and debriefs following events

More information

New Nuclear Technology. NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors. Congressional Briefing February 25, 2013

New Nuclear Technology. NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors. Congressional Briefing February 25, 2013 New Nuclear Technology NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors Congressional Briefing February 25, 2013 Michael S. McGough Chief Commercial Officer NuScale Power, LLC 2012 NuScale

More information

Operating and installation instructions Differential pressure monitor

Operating and installation instructions Differential pressure monitor Operating and installation instructions Differential pressure monitor RM-DPC Micro SensorLine Table of contents 1 Safety instructions...3 2 Equipment specification...3 3 Assembly...4 4 Step-by-step installation...4

More information

WELCOME TO A SILVER JACKETS WEBINAR ON:

WELCOME TO A SILVER JACKETS WEBINAR ON: WELCOME TO A SILVER JACKETS WEBINAR ON: Flood Vulnerability Assessment for Critical Facilities For audio, call 877-336-1839 Access code: 8165946 Security Code: 4567 MOLLY WOLOSZYN Extension Climate Specialist

More information

AP1000 European 1. Introduction and General Description of the Plant Design Control Document

AP1000 European 1. Introduction and General Description of the Plant Design Control Document AP1000 European 1. Introduction and General Description of the Plant Design Control Document 1.7 Drawings and Other Detailed Information 1.7.1 Electrical and Instrumentation and Control Drawings Instrument

More information

Circuit Breakers,Reclosers, Switches, and Fuses

Circuit Breakers,Reclosers, Switches, and Fuses Section 17 Circuit Breakers,Reclosers, Switches, and Fuses 170. ARRANGEMENT This rule requires circuit breakers, reclosers, switches, and fuses be accessible only to qualified persons. Section 17 is part

More information

Utility System Infrastructure

Utility System Infrastructure Utility System Infrastructure THE COLLEGE OF 2015 Campus Master Plan WILLIAM & MARY SUPPORTING DOCUMENTATION TABLE OF CONTENTS 3 4 4 4 4 5 Electrical Utility Infrastructure Emergency Power Generators

More information

ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD

ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD 64 Catalyst Drive Canton, North Carolina, 28716 USA +1.828.646.9290 +1.828.646.9527 (Fax) +1.800.203.2658 (Toll Free) www.alltecglobal.com ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD Photovoltaic

More information

Data Center and Colocation RFP Template

Data Center and Colocation RFP Template Data Center and Colocation RFP Template TABLE OF CONTENTS Client Organization Details... 3 Background Information... 3 Existing IT Infrastructure... 3 Business Requirements... 3 Vendor Corporate Profile...

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT CHITTAGONG FASHION WEAR LTD. SOUTH HALISHAHAR, CHITTAGONG, BANGLADESH Factory List: 1. Chittagong Fashion Wear Ltd. 2. H & W Apparels Inspected on May 5, 2014 SUMMARY

More information

Small distributed I/O module

Small distributed I/O module MLIO Summary Application Function Small distributed I/O module Small I/O module MLIO is a microprocessor-controlled, communiccative module for installation outside the control panel. It is used for topologies

More information

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels 10.0 UTILITIES ELEMENT The purpose of this element is to ensure coordinated provision of utility services required to meet the future needs of the University, consistent with current efforts to address

More information

Critical IT Facilities at the Edge

Critical IT Facilities at the Edge Critical IT Facilities at the Edge Mark Howell Global IT Facilities Planning & Engineering Ford Motor Company Critical IT Facilities at the Edge What are critical IT facilities at the Edge? Why are critical

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Alberto Carini, LPLS Italy, June 2013 MNS is The Intelligent MCC. ABB Group June 21, 2013 Slide 1

Alberto Carini, LPLS Italy, June 2013 MNS is The Intelligent MCC. ABB Group June 21, 2013 Slide 1 Alberto Carini, LPLS Italy, June 2013 MNS is The Intelligent MCC June 21, 2013 Slide 1 The MCC evolution Traditional MCC Intelligent relays MCC with integrated intelligence June 21, 2013 Slide 2 The intelligent

More information

DESIGN OF AN INTELLIGENT NITROGEN INJECTION SYSTEM FOR FIRE SAFTEY OF POWER TRANSFORMER

DESIGN OF AN INTELLIGENT NITROGEN INJECTION SYSTEM FOR FIRE SAFTEY OF POWER TRANSFORMER DESIGN OF AN INTELLIGENT NITROGEN INJECTION SYSTEM FOR FIRE SAFTEY OF POWER TRANSFORMER Priya N. Gokhale 1, S.M. Bakre 2 1 Professor, Department of Electrical Engineering, J.S.C.O.E., Maharashtra, India

More information

UNCLASSIFIED Developing the Canadian All-Hazards Symbology For Emergency Management

UNCLASSIFIED Developing the Canadian All-Hazards Symbology For Emergency Management Developing the Canadian All-Hazards Symbology For Emergency Management DATE: June 28, 2016 Outline Role of the GOC and GOC Geomatics Background on our symbology use Development of CAHS the Canadian All-Hazards

More information

OPTIMUM ENERGY PTE LTD

OPTIMUM ENERGY PTE LTD Low Voltage IEC Switchboards A range of modular Form 2, 3 and 4 main and emergency low voltage AC switchboards suitable for a variety of applications in Commercial, Industrial, Marine, Petrochemical, Oil

More information

Demand for sustainable power is growing worldwide. Energy producers are broadening their offerings for a quickly evolving marketplace.

Demand for sustainable power is growing worldwide. Energy producers are broadening their offerings for a quickly evolving marketplace. Power delivery Demand for sustainable power is growing worldwide. Energy producers are broadening their offerings for a quickly evolving marketplace. Forward-thinking power grid design This evolution has

More information

April 6, 2015 Tokyo Electric Power Company. <Reference>

April 6, 2015 Tokyo Electric Power Company. <Reference> Development of a technology to investigate inside the Reactor Primary Containment Vessel (PCV) Site test Investigation B1 on grating around the pedestal inside Unit 1 PCV April 6, 2015 Tokyo

More information

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets www.intellisaw.com The Case for Critical Asset* Monitoring The vast majority of critical assets in the field

More information

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Revised: July 12, 2013 Introduction The following information includes requests for clarification

More information

1200 West 7th Street, Los Angeles, CA Smart.

1200 West 7th Street, Los Angeles, CA Smart. Overview 1200 West 7th Street, Los Angeles, CA 90017 West 7 Center is conveniently located at 1200 West 7th Street in downtown Los Angeles near the 10 and 110 freeway. This tier III datacenter facility

More information

Present Status of Development of the NuScale SMR

Present Status of Development of the NuScale SMR Present Status of Development of the NuScale SMR Innovation for Cool Earth Forum October 10. 2018 Dr. José N. Reyes, Jr. Co-Founder and Chief Technology Officer NuScale Nonproprietary Copyright 2018 NuScale

More information

fulfils all requirements for very high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages.

fulfils all requirements for very high protection of the criteria catalogue The appendix is part of the certificate and consists of 5 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company akquinet AG Paul-Stritter-Weg 5 22297 Hamburg, Germany to confirm that its dual site data center of

More information

Current Control Houses

Current Control Houses Current Control Houses Building Shielding db Type Example 0 Transparent Wood 5 Poor Masonry 10 Moderate Concrete 20 Good Metal Siding 30 Metal All-Metal Current Control Houses Points of Entry Electrical

More information

INVESTIGATIVE REPORT FOR BROWARD COUNTY 911 DISPATCH CENTERS. January 18, 2013

INVESTIGATIVE REPORT FOR BROWARD COUNTY 911 DISPATCH CENTERS. January 18, 2013 INVESTIGATIVE REPORT FOR BROWARD COUNTY 911 DISPATCH CENTERS January 18, 2013 Scope of Work Building Scope 1) Year the facility was built. 2) Hurricane rating. 3) Flood Plain. 4) Future capacity. 5) Square

More information