1 Mission Critical Power Review Understanding concepts of mission critical power designs Chris Loeffler, Ed Spears, Power Quality Global HQ, Raleigh, NC
2 Did you know? Eaton is the #2 UPS manufacturer worldwide for single phase systems. Eaton is the #1 UPS manufacturer worldwide for UPS systems > 5kVA. Eaton is the leading IT Sector OEM UPS Manufacturer 2 2
3 Three-Phase Product Lineup Covering kva with single systems - Providing paralleled capacity up to 8.8 MVA 3 3
4 Eaton Solutions Are Different, They Are Designed To Deliver Efficient Uptime Eaton Backup Power solutions solve many of the challenges seen in other backups. Eaton solutions are designed to deliver: 4 4
5 Today's agenda UPS designs Reliability and Availability Types of redundancy Improving redundancy Options for power distribution flexibility Energy efficient designs Additional considerations Closing 5 5
6 Do you find yourself asking: What makes the best sense for me? How much redundancy do I need? What is the best approach to save money? How much is this going to cost? 6 6
7 Standby UPS Designs Eaton 3105 Line Interactive Eaton 5130 Eaton 5PX Double Conversion Eaton 9130 Eaton 9355 Multi-mode Eaton BladeUPS Eaton
8 Reliability vs. Availability Reliability is many times expressed as the products expected operational time before it quits operating properly MTBF Mean Time Before Failure MIL-HDBK-217F Telcordia (Bellcore) SR-332 MTBF is NOT a good measure of performance Availability is a better measure MTBF Availability = MTBF + MTTR MTTR = Mean time to repair Availability is usually expressed by the number of 9 s 8 8
9 Types of redundancy - improving availability No redundancy Subsystem redundancy Parallel redundancy (N+1) redundancy (2N) redundancy (2N+1) redundancy 9 9
10 No Redundancy Power System INPUT Subsystem A λ 1 Subsystem B λ 2 Subsystem C λ 3 Subsystem D λ 4 OUTPUT All devices are serially connected A fault in any device causes downtime 10 10
11 Power Architectures Tier I Tier level definitions per the Uptime Institute 11 11
12 How to increase availability Batteries are typically a UPS systems weakest point UPS System Parallel connected Series connected Battery Battery Battery Battery Battery Battery Battery Battery Battery Battery For additional reliability add an external battery monitor 12 12
13 How to increase availability Add a maintenance bypass in case of a system fault, or you need to work on the UPS/battery. Utility AC Maintenance Bypass (Manual) 13 13
14 Eaton 9390 Parallel Battery Cabinet Battery Cabinet UPS Maintenance Bypass/Distribution 14 14
15 Eaton 5130 Maintenance Bypass UPS with internal battery Second Parallel Battery Module 15 15
16 Power Architectures Tier II Tier level definitions per the Uptime Institute 16 16
17 Subsystem redundancy Redundancy in electronics Some designs may include some redundant internal components, but still contain a number of sub systems that are common. Subsystem B λ 2 INPUT Subsystem A λ 1 Subsystem B λ 2 Subsystem C λ 3 Subsystem D λ 4 OUTPUT Subsystem B λ
18 Parallel redundancy Parallel Redundant systems. The highest level of redundancy, because there are no, or very simple redundant components, which have a minimal impact to overall reliability. These systems should also have peer to peer control capability, as then a control issue in one system will not impact another. Subsystem A λ 1 INPUT Subsystem A λ 1 Subsystem A OUTPUT λ
19 Increasing power infrastructure availability N+1 systems 30 kva 30 kva 30 kva 30 kva Any single UPS can be taken off line for maintenance or repair Load 90 kva total 19 19
20 Which is more reliable? System A None Redundancy Scale Maximum System B None Redundancy Scale Maximum 20 20
21 Product examples of subsystem vs. parallel redundancy System A Competitors products System B Eaton products E BladeUPS
22 Redundant components in a BladeUPS 60 kw (N+1) system Battery system Battery breaker Static Bypass Switch Logic Control Maintenance Bypass Switch Rectifier and Inverter UPS 1 UPS 2 UPS 3 UPS 4 UPS 5 UPS 6 Maint Bypass Static Bypass 22 22
23 Maintaining a parallel rack system design In a BladeUPS system, all parts can be replaced by end user or any other service provider. Failure of chassis Power out Power in Failure of power module Battery end of life 23 23
24 Power system integrated into the IT space Modular power and power distribution Using the Eaton RPM (rack power module) a small initial UPS deployment can be easily expanded over time. RPM epdu Total load +12kW 24kW 12kW +24kW 48kW Po we r E d g e All power distribution in the racks Extra battery capacity can go in any cabinet Reduced need for electrical contractors Po we r E d g e Powe rvault 2 10S Po we r E d g e P o we r E d g e Powe rvault 2 10S 0 48k 12kW power distribution building blocks Po we r E d g e P o we r E d g e PowerVault 530F Powe rvault 2 10S Po werva ult 210 S PowerVault 530F Powe rvault 2 10S 12kW N+1 24k 12kW power building blocks Redundant UPS Power Po werva ult 210 S PowerVault 530F PowerVault 530F PowerVaul t 530F Increase power and distribution on the fly Customers can change out power distribution 24 24
25 Standalone horizontal parallel system 25 25
26 4 x 80kVA (320) or 240kVA N+1 parallel system If total system is redundant (N+1), failure of any one system does not effect critical bus Protected AC from inverters 26 26
27 Power Architectures Tier III Tier level definitions per the Uptime Institute 27 27
28 Increasing power infrastructure availability Adding power supply redundancy at the server UPS 1 Power panel 1 Tier III deployment, one power source can be off-line for service or repair A side power B side power 28 Power panel 2 28
29 Increasing power infrastructure availability 2N systems UPS 1 UPS 2 Power panel 1 2N deployment, one power source can be off-line for service or repair A side power B side power Power panel
30 Power Architectures Tier IV Tier level definitions per the Uptime Institute 30 30
31 Maximum power infrastructure availability 2N+1 systems Rack Transfer switch (ATS) UPS 1C UPS 1B UPS 1A UPS 2A UPS 2B UPS 2C Power panel 1 Power panel
32 Today - Modular approach to IT UPS RPP UPS RPP AC Unit 32 AC Unit 32
33 Modular building block concepts High density small footprint: PowerVault 530F Po we r Ed g e Po we r Ed g e Po we r Ed g e Build a 12 to 60 kw N+1 system in 1 cabinet with up to 6 modules connected in one 42U cabinet. 60kW 34 Power Vault 210S Each 6U system can be a single system in a standard IT cabinet, supporting up to 12 kw 37 Power Vault 210S IT load equipment Each 12 kw BladeUPS system is 6U and includes battery with automated maintenance bypass. 60kW N kW 36kW kW kW Compute expansion needed kW Single BladeUPS Scalable BladeUPS 33 33
34 Flexible, Scalable, Upgradeable On-site upgrade On-site 275 kva Redundant! upgrade 550 kva Redundant! Add another 275 kva in the field for redundancy, or for capacity Simply choose an ISBM sized for future growth Leave space on the left side Enables flexibility for future changes in load demands, and new requirements for higher reliability 34 34
35 Project BlueGrass sites (Louisville, KY) Blue Site 20.7 acres Expandable to support 6 data 10K sq. ft. Max power density of 180 w/sq. ft. 14 miles from Red Site Red Site 30 acres Expandable to support 6 data 10K sq. ft. Max power density of 180 w/sq. ft. 14 miles from Blue Site 35 35
36 Blue Grass Design Blue and Red Facilities are identical Overall facility 102,000 sq. ft. Office space 10,000 sq. ft. Gray space: White space: Electrical infrastructure 35,000 sq. ft. Mechanical infrastructure 14,000 sq. ft. Two data 10,000 sq. ft. each Power density 90 w/sq. ft. (day one) Upgrade steps at 120 and 180 w/sq. ft. All electrical and mechanical infrastructure components are redundant (n+1) 36 36
37 Out of UPS power (1500 sq ft floor) 150kVA PDU 150kVA PDU 300 kva UPS 300kVA UPS room AC Unit AC Unit AC Unit Existing UPS will not support additional equipment Need to add 10 racks of Blade Servers, replacing two full rows of ~4kW per rack equipment Would like 2(N+1) UPS protection for Blades 37 37
38 Modular concept in existing space 150kVA PDU 150kVA PDU Modular UPS Modular UPS 6U Rack PDU 6U Rack PDU 6U Rack PDU 6U Rack PDU 6U Rack PDU 6U Rack PDU 6U Rack PDU 6U Rack PDU 300 kva UPS 300kVA 6U Rack PDU Modular UPS 6U Rack PDU Modular UPS 150 kva XFMR AC Unit AC Unit AC Unit 150 kva XFMR Standard density standard availability N only power level Area that could have density increased to 15 kw per rack High density high availability compute 2(N+1) power 38 38
39 What are other considerations: What size module is the right size? What is the price I will pay for additional reliability? 39 39
40 The Value of Eaton Eaton Three-Phase UPSs provide the greatest combination of benefits, delivering tangible benefits for specifying engineers, consultants and end users» Lowest Total Cost of Ownership industry-wide» Superior Performance and efficiency» Real-time Information and Control» World-class Support and Service 40 Eaton
41 Low TCO Low TCO Improving the bottom line Eaton UPSs deliver low TCO from advances in several product facets» 400V Site Design» High Power Density small system footprints» Reduced weight and transportation costs» Low installation and Leading Efficiency Quantifiable Benefits» Maintenance» Scalability 41 41
42 UPS Efficiency over time 42 42
43 Low TCO Leading Efficiency Two complementary Eaton-proprietary technologies, maximizing UPS efficiency under any condition! Variable Module Management System (VMMS)» Maximized efficiency in double conversion mode» Both in single- and multi-ups systems applications Energy Saver Systems (ESS)» The ultimate savings: 99% efficiency» Automatic fast transfer to double conversion mode when needed (in less than 2 ms) Energy Advantage Architecture Higher System Efficiency No Compromise On Reliability 43 43
44 Low TCO Leading Efficiency Energy costs are overwhelming equipment costs in data centers.» UPS electrical losses account for 5-10% of the overall electrical expenditure.* Eaton s Energy Saver System drives these losses down to nearly zero. The energy savings recovers the cost of the UPS in less than 5 years. * Underlying figures from The Invisible Crisis in the Data Center: The Economic Meltdown of Moore s Law, Uptime Institute,
45 Low TCO Leading Efficiency ESS Efficiency 99% across the complete operating range 45 45
46 Low TCO Leading Efficiency The energy savings from ESS typically recovers 100% of the UPS cost over a 3-5 year period» At 250kW of critical load, the savings is equivalent to $4000 per year per point of efficiency gain. Backing up your 250kW load with an ESS UPS is equivalent to pulling 29 cars off the road
47 Low TCO Leading Efficiency How to maximize efficiency with lighter loads in double conversion mode, especially in multi-ups and redundant system configurations? Solution #1: Concentrate load on certain UPS s to maximize UPS load level and overall system efficiency» Some energy savings Limited to multiple-ups systems (with several UPS in parallel) Still not optimal Solution #2: Eaton 9395 and its Variable Module Management System» Automatically optimize efficiency at UPM level Concentrate the load on certain UPM s to maximize overall system efficiency» Only possible thanks to modularity of Eaton 9395 UPS Not limited to multiple-ups systems Achieve even higher optimization thanks to UPM s modularity 47 47
48 Low TCO Leading Efficiency Example with same load applied to different multi-ups configurations 48 48
49 Low TCO Leading Efficiency UPS Efficiency Eaton kVA UPS Efficiency % Eaton kVA UPS Eaton 1100kVA 825kVA kVA 550kVA with with UPS VMMS VMMS and and N+0 N+0 configuration* configuration* Eaton kVA UPS VMMS allows to shift to higher efficiency curves (according to to system s redundancy requirements) up to N+0 VMMS efficiency curve kVA kVA kVA kVA 9395 VMMS N+0 Typical Operations Range Load kva Notes: - Scaled drawing - VMMS and N+0 curves using VMMS default max UPM % load 80% (*)
50 Low TCO 400V Site Design 480V AC» Losses through the UPS, isolation transformer/pdu, and server equipment» End-to-end efficiency of approximately 76% 50 50
51 Low TCO 400V Site Design 600V AC» Used primarily in Canada» Can provide small savings in equipment costs, and utilizes lower currents» Requires multiple isolation transformer-based PDUs» End-to-end efficiency of approximately 76% 51 51
52 Low TCO 400V Site Design 400V AC» Commonly used throughout the world» PDU isolation transformers eliminated» End-to-end efficiency of approximately 80% 52 52
53 Options to increase flexibility Maintenance bypass, PDUs, RPPs, paralleling cabinets, ATS switches, 9155 & 9355 BladeUPS & 9355 rack Rack ATS switches paralleling cabinets 9155 & 9355 bypass power distribution w/receptacle options Data Center Bus Way DC Systems Static Switch Remote Power Panel PDU 53 Power Distribution Rack 53
54 Real-time Information and Control Real-time Information and Control Keeping data centers and facilities online requires real-time information and control capabilities. Eaton UPSs offer flexible options to interface with multiple systems and give customers the best control
55 Power Xpert and IPM Software Power Management Cooling IT and Networks Business Processes Utility Substation and Metering Parallel or Transfer Equipment Generator CHP Fuel Cell or MicroTurbine IT Monitoring Medium Voltage >600VAC Eqpt Power Facility Monitoring Utility Monitoring Low Voltage 600VAC Eqpt Compute H2O Storage, Network Ice In-row Power & Cooling DC Power Pumps Chiller Static Auto-Tie Central UPS Tower Precision Cooling Power Distribution Units Raised Floor Compute Main Frames Volume Servers Blade Servers Storage SATA Disk Tape Blended Eaton Software IPM, IPP, vcenter Power Xpert Software, Reporting 55 & Foreseer Network Corporate Networks VoIP Integrated Blade/Switch In-Row Power and Cooling Modular UPS Rack Mount PDUs In Row Cooling Rear Door Heat Exchanger Liquid Cooling Racks 55
56 Software Offerings IPM Intelligent Power Manager PX Power Xpert 56 56
57 Power Xpert Built in User View Templates - Geographical Layout Example Data Center LIVE Webcam video stream embedded into PXS Local Weather LIVE webpage embedded Events bubble up and change City-label colors accordingly
58 Layout Manager - Design the GUI to your liking Custom layouts can be created for any supported devices Indicators can appear animated and change color on status changes Review and acknowledge critical and cautionary alarms at-a-glance Custom bitmaps and graphical elements can be easily imported 3 rd rd party devices can be integrated into custom layouts easily. The user can choose from a variety of available gauges Links to other custom layout web pages can be easily embedded for drilling up or down for more information Custom mathematical formulas are supported to to create calculations based on multiple variables e.g. PUE, DCiE The Power Xpert Layout Manager provides the user a library of powerful design tools for the creation of custom Human-Machine Interface (HMI) graphical layouts. Objects can be easily animated, various gauges can be selected and custom bitmaps can be imported with little effort. The Layout Manager software module is included with Power Xpert Software as standard! 58 58
59 Trend Viewer - Understand where things are heading High performance, easy to use, Web based trending Three ways to interact Select attributes for a device from the Grid View Select attributes from multiple devices from Trend Viewer page Can save Trend Groups for easy future access Check attribute boxes on a User View Trend Display Chart or Data option Mix and match Multiple trends at one time Multiple axis supported Fixed or custom time frames Export results to Excel 59 59
60 Monitoring points to understand efficiency 60 60
61 Summary Energy efficiency is peaking in interest Use this opportunity to push high efficiency platforms IT Virtualization is hot Requires highly reliable power infrastructure Eaton s software integration into VM s is leading edge IT budgets are still recovering Customers are looking for modular build as you grow, and some level of increasing availability without a lot of extra cost Complete solutions are preferred Reductions in staff require simpler to purchase, deploy and manage solutions, and delivering flexible options means additional $ 61 61
62 62 62
Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?
This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationMid-Sized Data Center UPS Solutions Overview
Mid-Sized Data Center UPS Solutions Overview 2008 2008 Eaton Eaton Corporation. Corporation. All All rights rights reserved. reserved. Mid-Range System Concerns IT / ENGINEERS / BUYERS Cooling Designs
More informationIncreasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density
More informationEaton 93PM: Value, Benefits, and Features Eaton. All Rights Reserved..
Eaton 93PM: Value, Benefits, and Features 93PM value proposition The Eaton 93PM UPS combines unprecedented efficiency, reliability and vertical or horizontal scalability with eyecatching design. A space-saving,
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationLiebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology
Liebert APM from 30 to 300 kw The Compact Row Based UPS With FlexPower Technology LIEBERT APM from 30 to 300 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the
More informationNewave s approach for protecting mission critical application
ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationEaton Open Data Centre Solutions. Kari Koli
Eaton Open Data Centre Solutions Presenter: Stefan Coote Kari Koli 2008 Eaton Corporation. All rights reserved. Eaton Worldwide Founded in 1911 by J.O. Eaton World Headquarters in Cleveland, Ohio USA Customers
More informationProduct Brochure Eaton 93PR UPS kw
Product Brochure Eaton 93PR UPS 25-200 kw For more than 50 years, Eaton has been safeguarding the critical systems of businesses across the globe. Whether protecting a single desktop or the largest data
More informationEaton 93PR UPS kw
Eaton 93PR UPS 25 200 kw The most advanced UPS for data centers and mission critical applications 93PR 25-200 kw Contents Why the 93PR Product range Maximum Availability Lowest TCO Product Detail 2 2 3
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationAPMTM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology
APM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology T M LIEBERT APM UPS Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationPower+ Family Products. P+ Family Products: Seth Davis- Global Marketing Manager
Power+ Family Products 1 P+ Family Products: Seth Davis- Global Marketing Manager Power+ Family Product line Power+ 10-20KVA 19 2 Mega Power+ 3 Power+ Family Product line Have you ever asked yourself what
More informationEaton BladeUPS 12 60kW
Power Quality Solution for Data Centres Eaton BladeUPS 12 60kW The power quality solution that simply grows with your needs Delivering power reducing costs Two key trends have emerged in the data centre:
More informationProduct brochure. Eaton 9PXM UPS. A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage
Product brochure Eaton 9PXM UPS A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage Highest level of reliability. Lowest cost of ownership. The Eaton 9PXM UPS
More informationModular and Scalable Power Converters in the UPS Industry
A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationTel: AC Power for Business-Critical Continuity TM
Tel: +852-2690-4118 AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across your enterprise
More informationConverged Power Solutions. Data center power reinvented
Converged Power Solutions Data center power reinvented always on anywhere anytime With Eltek s Converged Power Solutions, the next generation power solution for data centers is here. It offers unmatched
More informationEaton 93PM UPS Efficient. Scalable. Innovative.
Product Brochure 20-200 kw Eaton UPS Efficient. Scalable. nnovative. features and benefits The Eaton UPS combines unprecedented and reliability with an eye-catching design. A space-saving, scalable and
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 100kW 3MW
PRODUCT BROCHURE Conceptpower DPA 500 480V UL Modular UPS 100kW 3MW 2 C O N C E P T P O W E R D PA 5 0 0 4 8 0 V M O D U L A R U P S Today s data centers require continuous uptime. That target is why ABB
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW
PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120
More informationLiebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity
Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW AC Power For Business-Critical Continuity Emerson Network Power, a division of Emerson, is a global company that combines
More informationPowering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM
Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and
More informationProduct brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW
Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS
More informationModular, scalable, high-efficiency power protection for data centers
Scalable to 20 kw Modular, scalable, high-efficiency power protection for data centers The Symmetra TM PX 20 kw is a world-class, high-efficiency, ENERGY STAR qualified power protection system designed
More informationThe Evolving Data Center
The Evolving Data Center Dominic Loh Product Manager, Power Quality, APAC Data Centers are enabling global growth Proliferation of mobile computing Digitalization of everything Big Data 2 Evolution of
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationAPMTM UPS 18kW - 90kW The Flexpower Technology for mission critical applications
APM UPS 18kW - 90kW The Flexpower Technology for mission critical applications WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationEst FlexiPower Ultra UPS FPX Ultra kVA
Est.1968 FlexiPower Ultra UPS FPX Ultra 500 1000kVA Prepared by Thycon Industrial Pty Ltd. The Thycon FlexiPower Ultra boasts the lowest cost of ownership of any UPS system by offering energy efficiency,
More informationRepeatable IT Hub Rooms
Repeatable IT Hub Rooms Repeatable IT Hub Rooms Catalogue Reducing the cost of NCPI through standardisation Data Centre Solutions Expertly Engineered Reducing the costs of NCPI through standardisation
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationLiebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM
Liebert NXr Series 30kVA to 160kVA AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across
More informationLiebert APM from kw. The Compact Row-Based UPS With FlexPower Technology TM
Liebert APM from 30-300 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
More informationLiebert APM UPS The Industry s Highest Energy Efficiency In A Row-Based, On-line UPS. AC Power For Business-Critical Continuity
Liebert APM UPS The Industry s Highest Energy Efficiency In A Row-Based, On-line UPS AC Power For Business-Critical Continuity Liebert APM with FlexPower Technology: An Adaptable UPS That Meets Increasing
More informationSymmetra PX 48kW. Scalable from 16 to 48kW. Make the most of your energy TM. Modular, Scalable, High-Efficiency Power Protection for Data Centers
Symmetra PX 48kW Scalable from 16 to 48kW Modular, Scalable, High-Efficiency Power Protection for Data Centers High performance, right-sized, modular, scalable, 3-phase power protection with high efficiency
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationUPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications
INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationModular, scalable, high-efficiency power protection for data centers
Scalable from 16 kw to 160 kw Modular, scalable, high-efficiency power protection for data centers The right-sized UPS for demanding business-critical applications The Schneider Electric Symmetra PX 96/160
More informationSmartRow Solution Intelligent, Integrated Infrastructure for the Data Center
SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them
More informationLiebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity
Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW AC Power For Business-Critical Continuity Emerson Network Power, a division of Emerson, is a global company that combines
More informationThe Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power. Alex Emms Operations Director
The Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power Alex Emms Operations Director Less UPS Drivers More UPS Drivers UPS Datacentre Drivers/Trends Datacentres =
More informationEaton 93PM UPS kw
Eaton 93PM UPS 30 200 kw Class-leading energy efficiency with minimal operating cost August 2013 2013 Eaton. All rights reserved. Eaton 93PM UPS Content Introduction to Eaton 93PM Overview Lowest Total
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationHelp your Cisco customers defend against downtime and reduce costs
Help your Cisco customers defend against downtime and reduce costs Why and when to sell Eaton Power Management solutions Incorporating power management with Cisco solutions boosts your sales revenue, while
More informationSmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity
SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.
More informationEst FlexiPower Maxi. Modular UPS kw
Est.1968 FlexiPower Maxi Modular UPS 8 200 kw Modular Parallel Architecture for missioncritical applications The rapid growth of data centers with mission critical applications that are fundamentally immune
More informationPowerWave 9000DPA Designed to meet the requirements of today and tomorrow
PowerWave 9000DPA Designed to meet the requirements of today and tomorrow PowerWAVE 9000DPA: Delivers class-leading Six Nines (99.9999%) power availability. PowerWAVE 9000DPA Up to 250 kva (200 kva N+1)
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationSymmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers
Modular, Scalable, High-Efficiency Power Protection for Data Centers Symmetra PX 48kW Scalable from 16kW to 48kW > High Performance, Right-Sized 3-Phase Power Protection with Industry-Leading Efficiency,
More informationPowerWAVE 8000DPA. (10 20 kva/kw) Parallelable up to 400 kva/kw
PowerWAVE 8000DPA (10 20 kva/kw) Parallelable up to 400 kva/kw Modular UPS designed for low and medium power applications. Key benefits Individual static switches per module Each module has its own display
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationModular three-phase UPS system. Conceptpower DPA kva True modular UPS system for critical applications
Modular three-phase UPS system Conceptpower DPA 10 250 kva True modular UPS system for critical applications A UPS designed to meet the needs of today and tomorrow The Conceptpower DPA is a high-power,
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationLiebert APM. The Compact, Row-Based UPS with Flexpower Technology 30kW - 300kW
Liebert APM The Compact, Row-Based UPS with Flexpower Technology 30kW - 300kW Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
More informationSmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity
SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks Solutions For Business-Critical Continuity Deploy An Efficient and Flexible Row-Based Infrastructure Efficiency. Capacity.
More informationPowerWAVE 8000DPA Modular UPS designed for low and medium power applications
PowerWAVE 8000DPA Modular UPS designed for low and medium power applications PowerWAVE 8000DPA is ideal for low to medium, high density critical power protection applications. For more information call
More informationPowerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)
Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationSMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER
SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online
More informationPowerWAVE 9000DPA Designed to meet the requirements of today and tomorrow
PowerWAVE 9000DPA Designed to meet the requirements of today and tomorrow PowerWAVE 9000DPA: Delivers class-leading Six Nines (99.9999%) power availability. PowerWAVE 9000DPA Up to 250 kva (200 kva N+1)
More informationZero downtime for mission critical applications? Absolutely.
Pierre-Alain Gubelmann, ABB Power Protection, Giornadas Tecnicas, Santiago de Chile, 11-12 Abril 2017 Zero downtime for mission critical applications? Absolutely. 2017-04-18 Slide 1 The Benefits of Modular
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationPower Quality Solutions Eaton 93PR UPS
Power Quality Solutions Eaton 93PR UPS Taking energy efficiency and scalability to the next level Eaton s heritage in industry-leading UPS design and production For more than 50 years, Eaton has been safeguarding
More informationEst FlexiPower Maxi UPS FPX Maxi kVA
Est.1968 FlexiPower Maxi UPS FPX Maxi 50 250kVA True modular UPS system for critical applications Designed and Published by Thycon. A UPS DESIGNED TO MEET THE NEEDS OF TODAY AND TOMORROW The FlexiPower
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationIBM Site Enablement Services
IBM Site Enablement Services Resilience for Your Data Centre 13/05/2005 Why Site Enablement Services? Hardware and Software are becoming increasingly dependable, but the environment in which they operate
More informationRepeatable IT Hub Rooms
Repeatable IT Hub Rooms Repeatable IT Hub Rooms Catalogue Reducing the cost of NCPI through standardisation Reducing the costs of NCPI through standardisation The UK Government s plan for growth, published
More informationCurrent Trends in UPS Technology. Voltages
Voltages 1 Voltages 3-ph, 4 W, 120/208V classification for small and mid range sizes 3-ph, 480V classification is typical in larger capacity UPS Systems 3-ph, 4 W, 230/400V becoming more widely used in
More informationPowerWAVE 9000DPA. (30-50 kva) Parallelable up to 1.5 MVA
PowerWAVE 9000DPA (30-50 kva) Parallelable up to 1.5 MVA Designed to meet the requirements of today and tomorrow. Key benefits Individual static switches per module Each module has its own display and
More informationthe Centric 300 An advanced modular UPS up to 1800kVA/kW
the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has
More information02 Why Does My IT Infrastructure Need a UPS?
UPS Buyer s Guide TABLE OF CONTENTS 01 What is a UPS? 02 Why Does My IT Infrastructure Need a UPS? 03 Common Features of UPS Systems ENERGY STORAGE SYSTEMS BATTERIES POWER PROTECTION MONITORING SOLUTIONS
More informationR E C T I F I E R I N V E R T E R C O N V E R T E R MP7
Uninterruptible Power Supply Product Specifications Description The industrial UPS provides your critical equipment with uninterruptible 3 phase AC power. Using high frequency dual conversion technology,
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationNetSure ITM with esure Technology Row-based, Scalable 48V DC UPS. DC Power For Business-Critical Continuity
NetSure ITM with esure Technology Row-based, Scalable 48V UPS Power For Business-Critical Continuity Efficiency Without Compromise provides a path to optimize data center infrastructure around design,
More information1008 kw, Tier 2, Chilled Water, ft 2
[eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationPowerWAVE 9500DPA. ( kva/kw) Parallelable up to 3 MVA/MW
PowerWAVE 9500DPA (100 500 kva/kw) Parallelable up to 3 MVA/MW 500 kva/kw modular UPS, designed with high effciency and maximum flexibility at its core. Total vertical and horizontal scalability using
More informationDC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
More informationLiebert GXT3 5kVA-10kVA UPS Compact UPS Systems For High Power Network Rack Applications. AC Power For Business-Critical Continuity
Liebert GXT3 5kVA-10kVA UPS Compact UPS Systems For High Power Network Rack Applications AC Power For Business-Critical Continuity Liebert GXT3, 5kVA-10kVA UPS Systems: Big Protection, Small Package Today
More informationLiebert APM 30, 60, 90, 120, 150kVA UPS Adaptive Power Quality Solution for Critical Applications
AC Power For Business-Critical Continuity Liebert APM 30, 60, 90, 120, 150kVA UPS Adaptive Power Quality Solution for Critical Applications Tel: +852-2690-4118 Liebert APM Efficiency Without Compromise
More informationPowerWAVE 9250DPA. ( N+1 kva/kw) Parallelable up to 1.5 MVA/MW
PowerWAVE 9250DPA (50 250 N+1 kva/kw) Parallelable up to 1.5 MVA/MW True modular UPS for medium power applications in critical, high-density computing environments such as small to medium-sized data centres,
More informationData Centre Design and Operational Best Practices
Data Centre Design and Operational Best Practices Ed Ansett Managing Partner i 3 Solutions Group ABB 5 th July 2013 Causes of Failure in Data Centres FAILURE WHO? WHAT? System Design Consulting Engineer
More informationSmartMod Intelligent, Integrated Infrastructure for the Data Center
SmartMod Intelligent, Integrated Infrastructure for the Data Center Deploy a High-Capacity, Efficient and Secure Infrastructure in Just Months Building a new data center in a short timeframe is nearly
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationEaton 93PM UPS Efficient. Scalable. Innovative.
Product rochure 20-400kW Eaton UPS Efficient. Scalable. Innovative. The Eaton is an ENERGY STR qualified UPS. ENERGY STR is intended to help consumers save money and protect the environment through energy
More information