1 Power and Cooling in the Data Center: Hyper-density Trends and Solutions Ken Baker Infrastructure Technologist 2004 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice
2 Modern Datacenter Design Raised floor, forced air cooling through perforated panels Power and network wiring may be under floor or overheard Designed for 5-10 year lifecycles Not designed for additional growth in power and cooling capacity Cooling efficiencies average between 40-50% 2
3 Average Datacenter Density Lawrence Berkley National Labs study found no datacenters in their study that exceeded 1950W /sq meter Historical trends have shown loading in the W /sq meter Customers have not seen a need to invest in support for density until now. 3
4 Energy Density of Datacenters Datacenter capacity is not rising at the same rate as power density in servers Indicates there is a resistance to dense deployments in volume 4
5 Customer Landscape 3000 Sanger Institute Customer Facility Examples Watts per square meter Dreamworks Palo Alto Nacio Cutten Road 365 Main Site6.2 PNNL Los Alamos Verizon Raytheon Oracle Watts Site Site4.2 Site4.1 Site3 Site8.1 Morgan Stanley Goldman Deutsche Bank Wells Fargo BofA Site8.2 Site2 Site1 State Farm Citigroup Site9 Site7 Size of Datacenter
6 Datacenter Trends Four years ago Average servers per rack = 4 6 Average U size was 5 7U Average watts per rack = Today Average servers per rack = 8-24 Average U size is moving down to 2U Average watts per rack = Future Power densities of watts per U are imminent 6
7 Server Trends Generation over generation density growth rates DL360 G2 DL360 G3 246 W 389 W 58% 2p, 4gb, 2hdd, 1pci 1U DL380G2 362 W DL380 G3 581 W 60 % 2p, 4gb, 6hdd, 2pci 2U DL580 G1 456 W DL580 G2 754 W 65% 4p, 8gb, 4hdd, 3pci 4U 7
8 Intel Processor Roadmap 8+ Way Common Platform CSI based 4 Way Gallatin 2M/130nm 2.0GHz Gallatin 4M 4M/130nm 3GHz T case 71 ºC TDP 85 W Potomac 8M/90nm 3.6GHz T case 65 ºC TDP 115 W 667 MHz Tulsa Dual core 8M/90nm 3.4GHz T case 69 ºC TDP 175 W 32bit Whitefield 16M/90nm TDP W DP Prestonia 512K/130nm 2.8GHz Prestonia 2ML3 130nm 3.2 GHz T case 71 ºC TDP 94 W Nocona 1M/90nm 3.6GHz T case 71 ºC TDP 103 W Dempsey DP DC 65nm T case? ºC TDP 150 W Woodcrest 4M (mobile dual) 65nm TDP 70 W 400 MHz 533 MHz 800 MHz 8
9 Impact of Future Dense Server Designs Dense designs drive up the Watts/ square meter requirement A typical rack requires 1.3 square meters of space At bl30p watt densities of watts per cabinet (max theoretical), the watt density for a facility of bl30p s could exceed >26,000 watts per square meter! 9
10 Understanding the Limits of Data Center Designs HP commissioned study Impact of increasing power density What can a facility successfully support? How can we improve the efficiency of a datacenter? Initial data indicates supporting room level power densities above 2000 to 2500 watts per square meter is not practical using classic raised floor designs 10
11 CM750-FL BC Y-Plot at 78 from the raised floor 11 R1C13-C14 max = 78.5 o F
12 CM750 - FL Solved One extra tile Layout PDU 1 PDU 2 PDU 4 PDU 3 Legend: = deactivated tiles = 56% tiles = 25% tiles = 30KW cabinets 12
13 R1C12 - C13 max = 68.3 o F CM750-FL Solved Y-Plot at 78 from the raised floor Note: Maximum allowable rack inlet temperature is 77 o F 13
14 PDU 3 PDU 4 CM1500 FL - BC Layout Top View 14 Extra AHU All floor tiles 25% open AHU1 AHU2 AHU9 AHU3 AHU4 Hot Aisle Hot Aisle Hot Aisle Hot Aisle Hot Aisle Hot Aisle AHU8 R3C1 AHU7 AHU10 AHU6 AHU5 Extra AHU PDU 2 PDU 1
15 CM1500 FL - BC Y-Plot at 78 from the raised floor Max. inlet temperature occurs at R9C1: 84.1 o F R9C1 R10C1 15
16 R1C14 CM1500 FL Solved HE Layout Top View Extra AHU AHU1 R1T14 AHU2 AHU9 AHU3 R9T14 AHU4 R1C1 R2T1 R2C1 PDU1 PDU2 R3T1 PDU4 PDU3 R10C14 AHU8 AHU7 AHU10 AHU6 R9C1 AHU5 Extra AHU 16
17 CM1500 FL Solved HE Y-Plot at 78 from the raised floor Max. inlet temperature occurs at R9C1: 71.8 o F R9C1 R10C1 Note: Maximum allowable rack inlet temperature is 77 o F 17
18 CM3000-FL BC Y-Plot at 78 from the raised floor R4 R5 C13: 95.2 o F R4C13 R5C13 18
19 CM3000-FL - Solved Layout Floor tiles AHU 10 AHU 9 AHU 8 AHU 7 AHU 6 PDU 1 PDU 2 AHU 11 PDU 4 AHU 12 PDU 3 AHU 5 AHU 4 AHU 3 AHU 2 AHU 1 De-activated tiles 25% open tiles All other tiles are 56% open tiles 19
20 CM3000-FL Solved Y-Plot at 78 from the raised floor AHU 10 AHU 9 AHU 8 AHU 7 AHU 6 AHU 11 AHU 12 AHU 5 AHU 4 AHU 3 AHU 2 AHU 1 Highly localized region of 77.3 o F All hot air temperatures observed in the base case have now come down below 68 o F Note: Maximum allowable rack inlet temperature is 77 o F 20
21 CM150 FL - BC Pressure plot at 2 below the raised floor Max of H 2 O observed below the supply of AHU 21
22 Data Center Thermal Modeling Non-intuitive flow patterns (HPL Palo Alto Smart Data Center Project) 5% open vent tile results in cooler inlet temperature Front View 5% open tile 95% open vent tile results in hotter inlet air temperature 95% open tile Front View 22
23 Data Center Thermal Modeling Dreamworks Redwood City (DL360 G3) Solution: This issue was solved by strategically repositioning inlet air vents (the only degree of freedom allowed by the customer) 23
24 Data Center Thermal Modeling Impact of load or cooling changes Modeling has the capability to show the impact of: Turning on new machines AC failure 100 % load Region Size AC shutdown for scheduled maintenance Factoid: For a given data center (at 2250 W /sq meter) with an A /C failure, the reaction time to reduce load is less than ~ 35 seconds to prevent redlining & shutdown 50% load 24
25 Key Findings Use of intuition is counterproductive in managing thermal situations Costs to support datacenter designs above 1000 watts/sq meter can become prohibitive Harvesting of low hanging fruit lies in improving existing efficiencies Thermal modeling can provide significant energy savings and allow for increased densities without spending on new equipment 25
26
27 Co-produced by:
Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More information3331 Quantifying the value proposition of blade systems
3331 Quantifying the value proposition of blade systems Anthony Dina Business Development, ISS Blades HP Houston, TX anthony.dina@hp.com 2004 Hewlett-Packard Development Company, L.P. The information contained
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationCritical Facilities Round Table SUN Microsystems Friday, March 25, Thursday, March 24, 2005 Wright Line LLC,
Critical Facilities Round Table SUN Microsystems Friday, March 25, 2005 Thursday, March 24, 2005 Wright Line LLC, 2003 1 Topic of Discussion Can standardization, non-uniform and high heat densities co-exist
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationWIRELESS ENVIRONMENTAL MONITORS
Packet Powers compact wireless Environmental Monitors makes it easy and affordable to monitor all environmental conditions in your facility. From installation to monitoring in minutes 1 Place wireless
More informationEstimating Data Center Thermal Correlation Indices from Historical Data
Estimating Data Center Thermal Correlation Indices from Historical Data Manish Marwah, Cullen Bash, Rongliang Zhou, Carlos Felix, Rocky Shih, Tom Christian HP Labs Palo Alto, CA 94304 Email: firstname.lastname@hp.com
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationCreating an Energy-Efficient, Automated Monitoring System for Temperature and Humidity at a World-Class Data Center
About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 40 data centers across the U.S., Europe and Asia with a three million-plus square feet of total net rentable space.
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationA LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER
A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.
More informationCRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS
CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationHPC Solutions in High Density Data Centers
Executive Report HPC Solutions in High Density Data Centers How CyrusOne s Houston West data center campus delivers the highest density solutions to customers With the ever-increasing demand on IT resources,
More informationAPC InfraStruXure Solution Overview
APC InfraStruXure Solution Overview We re waiting for your call or email. 800--0 uptime@uptimeu.com Wiring Closets ( Racks) Small Server Rooms ( Racks) Small Data Centers ( 0 Racks) Medium Data Centers
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationGreat Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch
Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More information1.0 Executive Summary
Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationHP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems
HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationInnovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation
Innovative Data Center Efficiency Techniques Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation 1 Alternate titles.. Crisis or opportunity? Never build a new data center! Improve
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRemote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products
Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationOptimizing data centers for high-density computing
Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationPower Consumption in the Data Center. Green Concepts
Power Consumption in the Data Center Green Concepts What is your Energy Saving Strategy? Buying Energy Efficient Equipment (EEE) 46% Say Yes to Green Technology Information Week Research Green Data Center
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationEnergy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering
Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationCyrusOne Case Study About CyrusOne
CyrusOne Case Study About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 31 data centers across the U.S., Europe and Asia with a three million-plus square feet of total
More informationTHE ROLE OF INFRARED TESTING AT DATA CENTERS
THE ROLE OF INFRARED TESTING AT DATA CENTERS By: Eric R. Stockton CompuScanIR Division Stockton Infrared Thermographic Services, Inc. www.compuscanir.com 800-248-7226 Introduction Data centers and other
More informationResource Saving: Latest Innovation in Optimized Cloud Infrastructure
Resource Saving: Latest Innovation in Optimized Cloud Infrastructure CloudFest 2018 Presented by Martin Galle, Director FAE We Keep ITSupermicro Green 2018 Cloud Computing Development Technology Evolution
More informationMeasurement and Management Technologies (MMT)
IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationInnovative Data Center Energy Efficiency Solutions
Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal
More informationEnergy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?
This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and
More informationENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD
R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationEnvironmental Data Center Management and Monitoring
1 Environmental Data Center Management and Monitoring A White Paper from aritan 2 Table of Contents Introduction... 3 Sensor Design Considerations... 3 Temperature and Humidity Sensors... 4 Airflow Sensor...5
More information1008 kw, Tier 2, Chilled Water, ft 2
[eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65
More informationQuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired
Overview The HP Performance-Optimized Data Center (HP POD) is a containerized datacenter equipped with power infrastructure, cooling and IT power distribution. The HP POD can be deployed within weeks instead
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationHP ProLiant DL385p Gen8 Server
DATASHEET Gen8 Server Flexibility to future-proof your infrastructure HP Proliant DL385 servers offer low list prices and high rewards The Gen8 server is purpose-built to: Redefine the customer experience
More informationServer Room & Data Centre Energy Efficiency. Technology Paper 003
Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:
More information2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016
2016 COOLING THE EDGE SURVEY Conducted by Vertiv Publication Date: August 30, 2016 TWO STAGE POWER DISTRIBUTION Table of Contents Section I: Methodology Section II: Key Findings 1. Strategic Importance
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationLiebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight
Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationTen Cooling Solutions to Support High- Density Server Deployment
Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,
More informationAssessing and Comparing HP Parallel SCSI and HP Small Form Factor Enterprise Hard Disk Drives in Server Environments
an executive white paper industry standard servers server storage and infrastructure may 23 doc. no. 5981-6439EN - Assessing and Comparing HP Parallel SCSI and HP Small Form Factor Enterprise Hard Disk
More informationDensity in the Data Center
Density in the Data Center INDUSTRY BRIEF Aug 2014 Density in the datacenter refers to the electric power consumed per square foot of floor space (or unit volume of space), number of servers, and the cooling
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationTemperature monitoring and CFD Analysis of Data Centre
Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.
More informationCabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers
Cabinet Level Containment IsoFlo Cabinet Isolated Airfl ow Cabinet for Raised Floor Data Centers IsoFlo Cabinet Cabinet Level Containment Tate s IsoFlo cabinet completely isolates the IT cooling from the
More informationNew Techniques for Energy-Efficient Data Center Cooling
New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,
More informationQuickSpecs. HP Rack Series. Overview. HP Rack Series - 36U
Overview - 42U - 36U - 22U DIM "A" 78.838 [2002.50] DIM "A" 68.338 [1735.78] DIM "A" 43.838 [1113.48] DIM "B" 24.125 [612.77] DIM "B" 24.125 [612.77] DIM "B" 24.125 [612.77] DA - 10995 Worldwide Version
More informationCustomizable Colocation: Building for the Future
Customizable Colocation: Building for the Future IronGate Data Centers meets the exact needs of customers with flexible Data Center Infrastructure solutions from Schneider Electric IronGate Data Centers
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationThe Most Comprehensive DCIM Solution
The Most Comprehensive DCIM Solution NetZoomDC TM is the complete, enterprise Data Center Infrastructure Management (DCIM) software which Models, Manages, Monitors and Maximizes data center assets, space,
More informationsurvey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.
:: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach
More informationSmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity
SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks Solutions For Business-Critical Continuity Deploy An Efficient and Flexible Row-Based Infrastructure Efficiency. Capacity.
More informationSIX Trends in our World
Data Center Infrastructure for Cloud and Energy Efficiency SIX Trends in our World Connectivity Simplicity StruxureWare TM for data centers TuanAnh Nguyen, Solution Engineer Manager, Vietnam Schneider
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationRF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink
INDUSTRIAL INTERNET IN ACTION CASE STUDY RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink CLIENT PROFILE CenturyLink Technology Solutions is the second largest telecommunications
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationData Center Efficiency and Retrofit Best Practices
White Paper August 2014 IT@Intel Data Center Efficiency and Retrofit Best Practices The use of best practices enables us to increase data center efficiency and capacity, optimize the return on invested
More informationIT Level Power Provisioning Business Continuity and Efficiency at NTT
IT Level Power Provisioning Business Continuity and Efficiency at NTT Henry M.L. Wong Intel Eco-Technology Program Office Environment Global CO 2 Emissions ICT 2% 98% Source: The Climate Group Economic
More informationData Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
More informationHP ProLiant BL35p Server Blade
Data sheet The new HP ProLiant BL35p two-way Server Blade delivers uncompromising manageability, maximum compute density and breakthrough power efficiencies to the high-performance data centre. The ProLiant
More informationNewest generation of HP ProLiant DL380 takes #1 position overall on Oracle E-Business Suite Small Model Benchmark
Newest generation of HP ProLiant DL380 takes #1 position overall on Oracle E-Business Suite Small Model Benchmark ProLiant DL380 G6 uses latest Intel Xeon X5570 technology for ultimate performance HP Leadership
More informationServer Technology Inc.
Server Technology Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2011-Sept-22 Headquarters Server Technology, Inc. 1040 Sandhill
More informationAnalysis of Environmental Data in Data Centers
Analysis of Environmental Data in Data Centers Lola Bautista, Ratnesh Sharma Enterprise Systems and Software Laboratory HP Laboratories Palo Alto HPL-2007-98 June 19, 2007* smart-data center, dynamic smart
More informationCase Study Automating Data Centre Infrastructure Diagrams
Case Study Automating Data Centre Infrastructure Diagrams Daniel Nunn, UK Data Centres Manager ICM Business Continuity ICM Overview Phoenix IT Group 2400 employees Acquired ICM in 2007. Other group companies
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More information