ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE
|
|
- Rhoda Lane
- 5 years ago
- Views:
Transcription
1 Document Number: ECS Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE EPN, LPN, SPN This document details the configuration procedure for the Lucy Gemini 3, Type E RTU. Author: James Ford Approver: Paul Williams Date: 05/11/2018 This document forms part of the Company s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Applicable To UK Power Networks External Asset Management G81 Website Capital Programme UK Power Networks Services Connections Contractors Health & Safety ICPs/IDNOs Legal Meter Operators Network Operations Procurement Strategy & Regulation Technical Training THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
2 Revision Record Version 2.0 Review Date 05/11/2023 Date 21/09/2018 Author James Ford Reason for update: Periodic review What has changed: Reference to PAKNET removed and to include details of the use of the Type E RTU with multi panel switchgear and as a retrofit RTU. Updates of screenshots. Version 1.0 Review Date 19/05/2018 Date 27/04/2017 Author James Ford New document detailing the configuration process for the Lucy Gemini 3 Type E RTU. UK Power Networks 2018 All rights reserved 2 of 28
3 Contents 1 Introduction Scope Glossary and Abbreviations Description Comms Device Installation Gemini 3 Configuration References Dependent Documents Appendix A RTU Software Update Appendix B Status Information Screens Appendix C Communications Monitor Figures Figure 1 Gemini 3 RTU Cabinet Layout... 6 Figure 2 Switch 1 and Switch 2 FPI CT Connections... 7 Figure 3 Sockets on Underside of RTU... 8 Figure 4 Comms Device DIN Rail Installation... 8 Figure 5 Comms Device Installed... 9 Figure 6 RTU configuration tool log in Figure 7 Config and Software version number Figure 8 RTU Configuration Page Figure 9 Starting Commissioning Wizard Figure 10 Commissioning Wizard start page Figure 11 Commissioning Wizard switch setup page Figure 12 FPI Figure 13 FPI Settings Page Figure 14 Comms Type/Area Selection Figure 15 Modbus Connected Devices Figure 16 PLTU and Voltage Mismatch UK Power Networks 2018 All rights reserved 3 of 28
4 1 Introduction 1.1 This procedure details the configuration procedures to set up a Lucy Gemini 3 RTU for use in secondary substations. 1.2 This procedure shall be carried out by the Commissioning Engineer or their appointed representative, who shall be an Authorised Person having appropriate training and experience. 1.3 This procedure shall be carried out in accordance with the requirements of the Distribution Safety Rules. 1.4 This procedure shall be carried out having regard to the requirements and recommendations of the manufacturer. If conflict exists between the requirements of the manufacturer and those of UK Power Networks the matter shall be referred to Asset Management. 1.5 This procedure assumes that the unit has been installed in accordance with the appropriate procedures. 2 Scope 2.1 This procedure applies to the configuration of the Lucy Gemini 3 RTU. The Gemini 3 is used is used to provide remote control of all UK Power Networks approved secondary RMUs. 2.2 The Type E RTU can be used to monitor and control secondary substation multi panel switchgear. Specific details regarding the connection to and use of the Type E RTU with the multi panel switchgear is contained within a separate document, see references section. 2.3 The Type E RTUs can be used as a retrofit RTU with old specification RMUs. Specific details regarding the connection to and use of the Type E RTU as a retrofit is detailed within a separate document, see references section. 2.4 The commissioning procedure for the secondary substation is contained in the relevant substation commissioning document, see references section. UK Power Networks 2018 All rights reserved 4 of 28
5 3 Glossary and Abbreviations Term Definition ADSL Asynchronous Digital Subscriber Line APN Access Point Name (secure access to mobile comms networks) CT Current Transformer DNP3 Distributed Network Protocol PowerOn Electricity Network Management and Control ESN Electronic Serial Number EFPI Earth Fault Passage Indicator FPI Fault Passage Indicator GPRS/3G/4G Mobile Comms Networks (Vodafone and O2) HMI Human Machine Interface RMU Ring Main Unit RTU Remote Terminal Unit SHDSL Symmetrical High-Speed Digital Subscriber Line UK Power Networks 2018 All rights reserved 5 of 28
6 4 Description 4.1 An overview of the main components of the Gemini 3 is shown Figure 1. Figure 1 Gemini 3 RTU Cabinet Layout 4.2 For use with RMUs, the Gemini 3 has remote control and monitoring facilities for up to four switches or circuit-breakers (or a mixture of both) using the DSM modules and is shown in Figure 1. Each switch/circuit breaker to be controlled and / or monitored needs an umbilical cable connection between the equipment and the Gemini For use with multi panel switchgear, the Type E RTU has control facilities for up to four switches or circuit-breakers and monitoring (open/close) of up to eight switches or circuit-breakers (including the four controlled). 4.4 Local control and monitoring is provided using the HMI. 4.5 The Gemini 3 is mains powered with a battery back-up and is self-monitoring. UK Power Networks 2018 All rights reserved 6 of 28
7 4.6 The Gemini 3 uses the DNP3 IP protocol to provide communication with PowerOn network management system for remote control and monitoring. Any appropriate IP compliant comms system can be used, such as: O2 or Vodafone GPRS/3G networks via the dedicated UK Power Networks APNs. Rented ADSL circuits. UKPN SHDSL circuits. UKPN Geostationary Satellite. Fibre. 4.7 The IP comms networks will also provide remote configuration and monitoring capability from UKPN offices. 4.8 The Gemini 3 is capable of providing two internal fault passage indicators (FPI) on the FPM module, driven via the 3 phase RMU FPI CT inputs (where available). These are directly wired to RTU switch 1 and RTU switch Where RMU CT inputs cannot be provided to the RTU (old LPN spec RMUs for instance), or where additional FPIs are required, these can be facilitated using external FPI units connected to the RTU via the RMU marshalling box. Figure 2 Switch 1 and Switch 2 FPI CT Connections UK Power Networks 2018 All rights reserved 7 of 28
8 4.10 Connections to plant and equipment are made using the sockets provided on the bottom of the RTU, see Figure 3. Figure 3 Sockets on Underside of RTU 4.11 The Firmware/Software version for use with both RMUs and multi panel switchgear. However, different configuration files (available on Alfresco) are required. 5 Comms Device Installation 5.1 Ensure the Comms Device mounting DIN rail is installed in the appropriate position for the Comms Device to be installed as shown in Figure 4. Note, the DIN rail may need to be repositioned depending on the Comms Device being fitted. Figure 4 Comms Device DIN Rail Installation UK Power Networks 2018 All rights reserved 8 of 28
9 5.2 Mount the Comms Device on the DIN rail as shown in Figure 5. Figure 5 Comms Device Installed 5.3 Connect the Comms Device power lead into the PSM DC outputs connector on terminals DC 1+ and DC Connect the Comms Device power lead to the Comms Device. 5.5 If using GPRS/3G/4G Comms: Connect the ethernet patch lead to ETH0 of the MCM and to the comms device Ethernet port. 5.6 If a risk assessment of the location allows, the aerial should be mounted outdoors, however if not the aerial should be mounted as high as possible within the substation. 5.7 If the substation is underground, every effort should be made to place the aerial at street level, or as close as reasonably practicable. 5.8 If using GPRS/3G/4G Comms: The Aerial feeder should be passed through one of the stuffing glands already installed on the RTU. The aerial feeder cable may need to be packed out (with insulating tape or something suitable) to ensure the stuffing gland can be tightened to form a good seal around the feeder cable. UK Power Networks 2018 All rights reserved 9 of 28
10 6 Gemini 3 Configuration 6.1 Please note, the process and screenshots may vary slightly from the actual screens shown during configuration, but the principles and process is the same. This is because new functions and features may be added to the RTU between document updates. 6.2 The Gemini 3 RTU is pre-configured for the hardwired I/O points and only requires configuration for the additional options that may be installed on a site by site basis, and the site specific RTU address. 6.3 The Gemini 3 Gemini 3 Configuration Tool software is used to configure the RTU, set up the DNP3 address and IP addresses, etc, and to check the status of the RTU. 6.4 Ensure the Laptop is to set to obtain an IP address automatically (DHCP Client). This should be the standard setting for UK Power Networks Laptops. 6.5 Connect a laptop PC to the ETH-1 Ethernet port on the MCM module using a suitable Ethernet Patch. If the Laptop supports auto-crossover a standard Ethernet Patch Cable may be used to connect a laptop PC to the Gemini 3 for configuration, if not a crossover Ethernet cable is required. 6.6 Start the Gemini 3 Configuration Tool program. 6.7 Input the User Name ukpn Password <deliberately not shown in this document>, and IP Address and select Login. See Figure 6. Figure 6 RTU configuration tool log in 6.8 The configuration program may give a message stating You are trying to read the configuration from the RTU. Any changes that have been made locally will be lost. Are you sure? Select Yes. 6.9 Maximize the page on the screen. UK Power Networks 2018 All rights reserved 10 of 28
11 6.10 Check the RTU has the correct latest software version installed (as available on Alfresco) in the Software Information section, see Figure 7. You may need to scroll down the page using scroll the bar on the right. The same software version is used for both RMUs and multi panel switchgear. Figure 7 Config and Software version number 6.11 If the software version or config version is incorrect, upgrade the software and/or config If the software needs upgrading, follow the procedure detailed in Appendix A If the Config needs to be updated, follow 6.14 to 6.17 (different configs are used for RMUs and multi panel switchgear) If both Config and Software are up to date skip to All Software/Firmware, Configs and PC Config Software can be downloaded for Alfresco at the following location: Home Page > Policies, Procedures & Forms > Engineering > Reference Library > Link to: Reference Library > Relay and RTU Software > Lucy > Gemini 3 UK Power Networks 2018 All rights reserved 11 of 28
12 6.16 Load the appropriate RTU configuration file into the RTU. Select Commissioning from the left hand menu. Select Configuration from the following menu. Select the down arrow next to New, then select Load from a File, you may get a message You are trying to open a configuration. Any changes that have been made locally will be lost. Are you sure? Select Yes. See Figure 8. NB, RMUs and Multi Panel switchgear use different configuration files. Browse to locate the RTU Config file on your Laptop. Select the file and click Open. From the RTU Configuration section, select Write. When prompted, click Activate Now and Restart Now. 1) Select Commissioning from the left hand menu 2) Select Configuration 3) Select the Down Arrow next to New 4) Select Load from a File Figure 8 RTU Configuration Page 6.17 Check the RTU now has the correct latest config and software version installed (as available on Alfresco). Select Realtime Monitor from the left hand menu. Check the Config and Software Version is now correct (see Figure 7). UK Power Networks 2018 All rights reserved 12 of 28
13 6.18 Select Commissioning from the left hand menu, then select Wizard, then select Start Commissioning see Figure 9. 1) Select Commissioning from the left hand menu 2) Select Wizard 3) Select the Start Commissioning Figure 9 Starting Commissioning Wizard UK Power Networks 2018 All rights reserved 13 of 28
14 6.19 Step 1: Input the RTU Site Name into the appropriate box (site name specified by PowerOn commissioning engineer). The IP address, Submask and Gateway should be pre-configured to , and respectively. Enter the RTU DNP3 Address (as specified by the PowerOn commissioning engineer) into the DNP3 RTU Address box. See Figure If more than one RTU is being connected to a single Comms Device: The second RTU IP Address should be changed to The third RTU IP Address should be changed to The forth RTU IP Address should be changed to Select Next. Figure 10 Commissioning Wizard start page UK Power Networks 2018 All rights reserved 14 of 28
15 6.21 Step 2: Select which RTU switch is connected to which RMU manufacturer switch/circuit breaker (for instance RTU Sw1, Lucy Electric RMU (switch)). If no switch is connected select Disabled. See Figure If using the Gemini 3 with Mutli Panel Switchgear, additional switches may also be shown on this page (RTU Switches 5, 6, 7 and 8). However, the I/O for these switches are fixed and no selections are required Select Next. Figure 11 Commissioning Wizard switch setup page UK Power Networks 2018 All rights reserved 15 of 28
16 6.24 Step 3: Select whether the Internal FPI functionality needs to be Enabled or Disabled. See Figure 12. If an internal FPI is to be used select Internal FPI Enabled, if an external FPI is used, or no FPI is required select Internal FPI Disabled Wherever the RTU is connecting to an old EPN/SPN/LPN Spec RMU, this will need to be set to Internal FPI Disabled as the old Spec RMUs do not have the required CTs installed Please note, the internal FPIs are only connected to RTU Switch 1 and RTU Switch 2 of the UKPN Spec RMUs, therefore any RMU switch/circuit breaker that needs to use the internal FPI functionality must be connected to either RTU Switch 1 or RTU Switch 2. Figure 12 FPI UK Power Networks 2018 All rights reserved 16 of 28
17 6.25 If the Internal FPI is used, the standard FPI settings are automatically set. If required, they can be altered if required by changing the drop down menu for FPI Profile from Default to Custom. Please be aware, you may need to scroll down the screen to see the settings for the second internal FPI. Figure 13 FPI Settings Page Please note, the standard FPI settings for use with the Type E RTU internal FPIs for EPN, LPN and SPN are: Phase Fault 600A 50ms and Earth Fault 90A 50ms. These values can be overwritten if site specific values have been calculated Select Next. UK Power Networks 2018 All rights reserved 17 of 28
18 6.27 Step 4: Select the region the RTU is to be installed within (which PowerOn system the RTU will communicate to) and the comms type it will use. See Figure 14. DO NOT select any of the comms options under [Test RTUs Only] Select Next. Figure 14 Comms Type/Area Selection UK Power Networks 2018 All rights reserved 18 of 28
19 6.29 Step 5: Select the appropriate Modbus connected device (such as a Power Meters or Protection relays). If no Modbus device is connected select Disabled. See Figure 15. Figure 15 Modbus Connected Devices Please note, the Modbus address of the devices installed on the comms bus must match the Modbus address detailed in the configuration tool Select Next. UK Power Networks 2018 All rights reserved 19 of 28
20 6.31 Step 6: Internal PLTU. In EPN and SPN, or in LPN wherever an external PLTU is not required, this will need to be set to Disabled (leave boxes unticked) If PLTU functionality is required, tick the box to enable the PLTU functionality. If the PLTU functionality is enabled, ensure the correct RTU switch is selected, so the correct circuit breaker is tripped If the PLTU functionality is not required, but Voltage Mismatch identification is required, then tick the Voltage Mismatch tick box Select Next. Figure 16 PLTU and Voltage Mismatch UK Power Networks 2018 All rights reserved 20 of 28
21 6.35 Step 7: Select Finish to write the configuration to the RTU. The RTU will restart. Once the RTU has restarted successfully, a message with state The RTU has been configured successfully, click OK Select Exit from the top right corner of the screen. UK Power Networks 2018 All rights reserved 21 of 28
22 7 References EAS Lucy Gemini 3 RTU EOS Lucy Gemini 3 RTU ECS Type E RTU Retrofit Installation Procedure ECS Type E RTU with Multi Panel Switchgear EDS RTU Type E Ground Mounted Switchgear Interface ECP Secondary Ground Mount Substation Commissioning Procedures ECP GPRS/3G/4G Comms Device Commissioning Procedure ECS Type E RTU and Ancillary Items Installation Procedure UK Power Networks Distribution Safety Rules Lucy Gemini 3 Installation, Operation and Maintenance User Manual 8 Dependent Documents The documents below are dependent on the content of this document and may be affected by any changes. EDS ECP EDS ECS ECS ECS Secondary Substation Earthing Design Secondary Commissioning Procedures RTU Type E Ground Mounted Switchgear Interface. Type E RTU and Ancillary Items Installation Procedure Type E RTU Retrofit Installation Procedure Type E RTU with Multi Panel Switchgear UK Power Networks 2018 All rights reserved 22 of 28
23 Appendix A RTU Software Update Download the latest version of the Software from Alfresco: Open Alfresco from the Intranet Home page: Home Page > Policies, Procedures & Forms > Engineering > Reference Library (then select Link to: Reference Library) > Relay and RTU Software > Lucy > Gemini 3 > Lucy G3 Software Download both the SDP and SDP Bootloader zip files to a suitable folder on your laptop. The Gemini 3 software is upgraded using Gemini 3 Configuration Tool as follows: 1. Select Commissioning from the left hand menu. 2. Select Upgrade. 3. Select Load. 1) Select Commissioning from the left hand menu 2) Select Upgrade 3) Select Load UK Power Networks 2018 All rights reserved 23 of 28
24 4. Select the SDP Bootloader file by browsing to the folder you downloaded the files to from Alfresco. This may take a few minutes. UK Power Networks 2018 All rights reserved 24 of 28
25 5. From the 2. Select Software Version for MCM menu, select the version required (this will be the version with the highest number, if they are the same select the MCMBoard.zip version). UK Power Networks 2018 All rights reserved 25 of 28
26 6. Select Start Upgrade at the bottom of the screen. 7. You will see a Confirm Upgrade box appear, select Yes. UK Power Networks 2018 All rights reserved 26 of 28
27 8. You will then see the following boxes appear as the Software goes through the upgrade process. 9. Once the upgrade process has completed you will see the following box, select OK. 10. The process will then need to be repeated to load the SDP file. UK Power Networks 2018 All rights reserved 27 of 28
28 Appendix B Status Information Screens The Gemini 3 Configuration Tool program also provides an HMI to enable the communications, digital alarms/indications, analogues and events to be viewed and the controls to be actioned, to assist with the commissioning and testing of the Gemini 3. The procedure to access the Mimic page is as follows: 1. Follow the procedure detailed in 6.3 to Select Commissioning from the left hand menu. 3. Select Mimic from the left hand menu. Appendix C Communications Monitor Within the Gemini 3 Configuration Tool is the facility to monitor RTU Events and RTU Alarms using two tabs within the configuration tool Realtime Monitor. The RTU Events tab enables the display of historical and real-time time-stamped events (including SCADA protocol events & system events) to be reported to the SCADA. The RTU Alarms tab enables the display of the current alarm state of each module in the system. The procedure to access the Mimic page is as follows: 4. Follow the procedure detailed in 6.3 to Select Realtime Monitor from the left hand menu. 6. Select the desired tab Events or Alarms from the bottom of the screen. UK Power Networks 2018 All rights reserved 28 of 28
EOS LUCY GEMINI 3 TYPE E RTU
Document Number: EOS 05-9305 Network(s): Summary: ENGINEERING OPERATION STANDARD EPN, LPN, SPN EOS 05-9305 LUCY GEMINI 3 TYPE E RTU This standard details the application, installation and operation of
More informationEOS REMSDAQ CALLISTO NX TYPE E RTU
Document Number: EOS 05-9306 Network(s): Summary: ENGINEERING OPERATING STANDARD EOS 05-9306 REMSDAQ CALLISTO NX TYPE E RTU EPN, LPN, SPN This standard details the application, installation and operation
More informationECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE
Document Number: ECP 11-0501 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0501 SECONDARY SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the end-to-end process
More informationECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE
Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0601 GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN Configuration and commissioning procedure for the GPRS/3G/4G
More informationECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE
Document Number: ECS 05-9540 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9540 TYPE E AND ANCILLARY ITEMS INSTALLATION PROCEDURE EPN, LPN, SPN This procedure details the installation,
More informationECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE
Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0521 NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing
More informationEOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR
Document Number: EOS 03-0018 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0018 SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning
More informationEOS LUCY SABRE 'A' RANGE SWITCHGEAR
Document Number: EOS 03-0027 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0027 LUCY SABRE 'A' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning and operation
More informationEDS MW AND MVAR TRANSDUCER CONNECTION
Document Number: EDS 05-5001 Network(s): Summary: ENINEERIN DESIN STANDARD EDS 05-5001 MW AND MVAR TRANSDUCER CONNECTION EPN, LPN, SPN This standard details the convention to be used when wiring MW and
More informationEDS SCADA NUMBERING SYSTEM
Document Number: EDS 05-9007 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 05-9007 SCADA NUMBERING SYSTEM This standard describes the system for numbering SCADA wiring within switchgear
More informationEBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES
Network(s): Summary: ENGINEERING BULLETIN EBB 08-0061 PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES EPN, SPN This bulletin provides a framework for the pilot scheme for unmetered
More informationEDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES
Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-0001 132KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES EPN, LPN, SPN This engineering design standard describes the requirements for
More informationSynchronous switching of distribution sub networks
Synchronous switching of distribution sub networks Paul Stergiou ConEdison USA Manuel P Pimenta, - ConEdison USA Sergio A Rodriguez ConEdison USA Thomas Horan ConEdison USA Andre Smit- Siemens Industry
More informationEDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES
Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution
More informationEDS LV CUSTOMER UNMETERED SUPPLIES
Document Number: EDS 08-2102 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-2102 LV CUSTOMER UNMETERED SUPPLIES EPN, LPN, SPN This standard details the requirements for unmetered single-phase
More informationDesign Guidelines for SCADA & DSA
Design Guidelines for SCADA & 28 th February 2017 28 FEBRUARY 2017 ISSUE 4 PREPARED BY: PRINCIPAL ENGINEER SCADA & MANAGER AUTHORISED BY: MANAGER SECONDARY SYSTEMS DOCUMENT NUMBER: ISSUE 4 This plan is
More informationPOWER GRID AUTOMATION. Pág.. n. RMU Automation
POWER GRID AUTOMATION RMU Automation Distribution Network Non-Controlled Secondary Distribution Systems Distribution Network RMU Automation - Levels RMU Automation - RTU / FRTU SMART CONTROLLER Monitoring
More informationSubstation Workshop. 7 th February 2018
Substation Workshop 7 th February 2018 1 Agenda Welcome and Introductions Antony White Substation Design Overview Andy Moore Question & Answer Session Break 1500kVA Transformers James Devriendt & Andy
More informationSpecification Voltage Limiting Device
Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,
More informationQUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3
QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3 What's in the delivery? Getting started The first steps PC
More informationMESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset
More information7SR21 Non-Directional 7SR22 Directional Overcurrent Relay
7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module
More informationMULTI-LINE 2 APPLICATION NOTES
MULTI-LINE 2 APPLICATION NOTES Converting PPM-2 to PPM 300 Parameter conversion Wiring Options I/O list Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com
More informationISIO 200. Binary Input/Output (I/O) terminal with IEC interface
ISIO 200 Binary Input/Output (I/O) terminal with IEC 61850 interface Compact and easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
More informationTitle System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards
More informationmark150s mark150/485s DDC controllers Summary
mark150s mark150/485s DDC controllers Summary DDC (Direct digital control) controller mark150s and mark150/485s are free programmable process stations with ARM Cortex M4 processor and OS FreeRTOS. They
More informationManual: Distribution Substation Manual (DSM) Section 1: Customer Supply Arrangements
Manual: Distribution Substation Manual (DSM) Section 1: Customer Supply Arrangements Standard Number: HPC-5DA-07-0001-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document
More informationPeter Overgaauw Pascal Stijns 27 Oct 2016 EXPERION PKS CONTROLS ELECTRICAL SYSTEMS TOO!
Peter Overgaauw Pascal Stijns 27 Oct 2016 EXPERION PKS CONTROLS ELECTRICAL SYSTEMS TOO! Abstract Gain a basic understanding of an electrical control management system Exposure to a number of technology
More informationFlexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks
Flexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks (SDRC 9.2) Contents Executive Summary... 5 1. Introduction...
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationQUICK START GUIDE Paralleling and Protection Unit PPU 300
QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107C 1. Introduction
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationNEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS
NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS John DULLER Ahsan HALIM Gordon PATON UK Power Networks UK UK Power Networks UK General Electric - UK john.duller@ukpowernetworks.co.uk
More informationURC Utility Relay Company
communications i-comm modbus / rs-485 AC-PRO Communicating Trip Units instruction manual ZERO-Hertz Communicating Trip Units URC Utility Relay Company Chagrin Falls, OH 44023 Phone: 888.289.2864 www.utilityrelay.com
More informationRapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS
Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS RAPIER GX Gas Enclosed Switch Our new RAPIER GX, pole-mounted
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service.... 2 Disconnect Power Connections, CTs, and Modbus....
More informationOvercurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin
Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection
More informationMV Network Managment Fault tracking, monitoring and control. Easergy Range Merlin Gerin
MV Network Managment Fault tracking, monitoring and control Easergy Range Merlin Gerin References Schneider Electric Industries SAS Postal address MV department F-38050 Grenoble Cedex 9 Tél. : +33 (0)4
More informationAirfield Lighting Control System
Airfield Lighting Control System ALCS Style 2 ALCS Style 3 Reference to Standards ICAO: Annex 14, Volume I, current edition Aerodrome Design Manual, Part 5 FAA: AC 150/5345-56 (current edition) L-890 Airfield
More informationInnovative Electronics for a Changing World INDEX
Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 2713 ELECTRICITY METERING PART 1 - GENERAL 1.1 SUMMARY A. Section includes equipment for metering of the electrical power system. B. Related Sections: 1. Section 26 2300 for metering installed
More informationRelion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation
Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation
More informationIndependent Connections Provider (ICP) Unmetered Connections (UMC) Jointing to Services (UJ2S) Procedure
Independent Connections Provider () Unmetered Connections (UMC) Jointing to Services (UJ2S) Procedure Owner Name Title Neil Clarke Head of Highway Services Signature Date 16 August 2018 Authoriser Name
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E Rev. 2 December 2011 PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service.... 2 Disconnect Power Connections,
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service... 2 Disconnect Power Connections, CTs, and Modbus....
More informationSession Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers
Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are
More informationQUICK START GUIDE Generator Protection Unit GPU 300
QUICK START GUIDE Generator Protection Unit GPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 Info@deif.com www.deif.com Document no.: 4189341035A 1. Introduction 1.1
More informationABB Digital medium-voltage switchgear
NAMIBIA AMEU/AEDU MARCH 2018 ABB Digital medium-voltage switchgear Barry Addinall UniGear Digital Contents 1. Digital switchgear 2. Complexity of Distribution networks 3. New technologies using digital
More informationManual# Installation Manual SDU 410. Safety Shutdown Unit
Manual# 1100641 Installation Manual SDU 410 Safety Shutdown Unit Installation Manual for SDU 410 ~~~ Safety Shutdown Unit Revision 1.0 Revised August 31, 2017 Revision history: Rev. Date Description 1.0
More informationString monitoring with CMS - Circuit monitoring system Increased productivity and improved maintenance of PV systems
S O L A R S T R I N G M O N I TO R I N G String monitoring with CMS - Circuit monitoring system Increased productivity and improved maintenance of PV systems Solar plant operators are constantly facing
More informationDECK All-In-One Enclosure. Quick Installation Guide for Field Installers
DECK All-In-One Enclosure Quick Installation Guide for Field Installers 1 Contents Legal Statement... 2 Preliminary Considerations... 2 Required Installation Tools and Materials... 2 Networking Information...
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS S Simplicity Transporter Setup Instructions
525683-UAI-C-0911 ACCESSORY KIT INSTALLATION INSTRUCTIONS S1-33109119000 Simplicity Transporter Setup Instructions A remote Internet connection to a network of Simplicity control(s) allows you the ability
More informationMESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical
More informationMiCOM P111. Three phase and earth fault overcurrent relays
Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features
More informationDesigning a new IEC substation architecture
Designing a new IEC 61850 substation architecture Gerrit Dogger Senior Product and Application Specialist Cooper Power Systems gerrit.dogger@cybectec.com Garry Tennese Station Integration Specialist Manitoba
More informationAmsterdam 27 September 2017 David MacDonald
Operations & Maintenance facilitating condition based and predictive maintenance to support cost-efficient operation and maximum life-cycle of next generation IEC 61850 systems Amsterdam 27 September 2017
More informationService Managed Gateway TM. Installing and Configuring the GW8600 SMG
Service Managed Gateway TM Installing and Configuring the GW8600 SMG Issue 1.1 Date 14 August 2007 Table of Contents 1 About this document...3 1.1 Scope...3 1.2 Readership...3 1.3 More information...3
More informationCompany Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes
Company Directive STANDARD TECHNIQUE: TP18A/1 Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes Summary This document provides guidance on the application of
More informationProcedure to Upgrade from B&W Maintenance Panel to TIB Color Touchscreen Door in a Working Maxum or Maxum II Analyzer Equipped With a SYSCON2
Procedure to Upgrade from B&W Maintenance Panel to TIB Color Touchscreen Door in a Working Maxum or Maxum II Analyzer Equipped With a SYSCON2 Difficulty Level: High Estimated time to execute: 3 Hours Revision
More informationAPPLICATION NOTES. Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG
APPLICATION NOTES Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG CODESYS V3 logic running on AGI 300/400 series product Support of Modbus/TCP and RTU communication Use of remote
More informationLucy Switchgear. SKELEC Automation Project. John Barker Tim Spearing
Lucy Switchgear SKELEC Automation Project John Barker Tim Spearing Contents Lucy Switchgear Automation SKELEC Automation Project Why ABB MicroSCADA / DMS 600 Key facts Group Europe 16% 150m Turnover Americas
More informationCONDUCTOR W4. Installation instruction for W4.1 and W To mount the controller. Controller. Mounting on a DIN rail
CONDUCTOR W Installation instruction for W. and W. 00 Controller To mount the controller. Mounting on a DIN rail Figure. Overview of the Controller. Pos. Product marking. Pos. Termination resistance. =
More informationProtection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW
SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.
More informationNPS/003/017 TECHNICAL SPECIFICATION FOR A GROUND MOUNTED DISTRIBUTION SWITCHGEAR REMOTE CONTROL SYSTEM.
Version:- 2.0 Date of Issue:- July 2015 Page 1 of 70 NPS/003/017 TECHNICAL SPECIFICATION FOR A GROUND MOUNTED DISTRIBUTION SWITCHGEAR REMOTE CONTROL SYSTEM. 1. Purpose This document is the technical specification
More informationIMIO100 IMIO105. DDC controllers. Summary
IMIO100 IMIO105 DDC controllers Summary DDC (Direct digital control) controller IMIO100 and IMIO105 are free programmable process stations with ARM Cortex M4 processor and OS FreeRTOS. They contain one
More informationAdvanced Graphical Interface, AGI 100
APPLICATION NOTES Advanced Graphical Interface, AGI 100 The AGI communication ports Modbus details Specific DEIF driver Example of project creation Document no.: 4189340746A DEIF Screen Designer 1.293
More informationCompany main topic [ Product ] TracFeed DCP2. English. Multifunctional Device for Control and Protection in DC switchgear.
Company main topic [ Product ] TracFeed DCP2 English Multifunctional Device for Control and Protection in DC switchgear Made in Germany 2 TracFeed DCP Our well-known brand name TracFeed DCP is a well-known
More informationI n s t a l l a t i o n M a n u a l. T E D P r o. ( T P C O n l y ) A B C. Rev 1.1
I n s t a l l a t i o n M a n u a l f o r T E D P r o ( T P C O n l y ) A B C Page 2 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * I M P O R T A N T The successful installation
More informationQuick Installation Guide for Field Installers
1 Quick Installation Guide for Field Installers 2 Contents Legal Statement 3 Required Installation Tools and Materials 3 Networking Information 3 Modbus Communication and Wiring 4 Modbus Network and Layout
More informationSPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station
SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal
More informationIEC Test Equipment Requirements
OMICRON K02 03 20060309 IEC 61850 Test Equipment Requirements Dr. Alexander Apostolov K02 03 20060309 Page: 1 Intelligent Substation Automation Systems OMICRON K02 03 20060309 Page: 2 Intelligent Sensor
More informationT48 - Integrating Your Power and Automation Control Systems
T48 - Integrating Your Power and Automation Control Systems PUBLIC Copyright 2018 Rockwell Automation, Inc. All Rights Reserved. 1 Integrated Power & Automation The Evolution of End Client Requirements
More informationOverview and Application
IEC 61850 Overview and Application Who am I? Rich Hunt Market Development Leader GE Grid Solutions Over 25 years in the power systems industry At GE for 10 years (almost) Member of IEEE PSRC, U.S. Representative
More informationDTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A
DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current
More informationGemini 3 Remote Terminal Unit. engineering intelligent solutions
Gemini 3 Remote Terminal Unit engineering intelligent solutions Gemini 3 is a flexible Remote Terminal Unit (RTU) platform for advanced feeder automation on electrical distribution networks. Flexible solutions
More informationCONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM...
GENERAL INFORMATION Contents CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM... 3 COMMUNICATION... 4 BUILDING-BLOCKS... 5 NETTROLL AND NETDRAW... 5 NETALERT... 6 NETGRAPH... 7 COMTROLL OUTSTATIONS...
More informationMESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS
Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli
More information7SG18 Solkor N Numeric Differential Protection
7SG18 Solkor N Numeric Differential Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release 2010/02 Document reformat due
More informationDate Revision Change(s) 29/07/ First version
Revision overview Revision overview Date Revision Change(s) 29/07/2016 0 First version Copyright 2016 Indu-Sol GmbH We reserve the right to amend this document without notice. We continuously work on further
More informationIS-BX-12 User Manual
IS-BX-12 User Manual Ver 1.0 Sentry360 2014 Table of Contents 1. Overview...3 1.1 Features... 3 1.2 Package Contents... 4 1.3 Dimensions... 4 1.4 Connectors... 5 1.5 Light Sensor... 6 2. Camera Cabling...6
More informationQUICK START GUIDE Paralleling and Protection Unit PPU 300
QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107B 1. Introduction
More informationLecture 5 Substation Automation Systems. Course map
Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part
More informationMESP MODULAR SUBSTATION USER REQUIREMENTS
Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT
More informationISIO 200. Binary Input/Output (I/O) Terminal with IEC GOOSE Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 GOOSE Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal for
More informationRELEASE NOTES. WSOS5 version 5.16.xx. Version Schneider Electric. All Rights Reserved.
RELEASE NOTES WSOS5 version 5.16.xx Version 02 2017 Schneider Electric. All Rights Reserved. Page 1 of 14 The information provided in this documentation contains general descriptions and/or technical characteristics
More informationPower Systems Communications Implementation of IEC61850 in a Substation Environment
Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details
More informationField Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware
Field Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware Introduction Please read this document before upgrading a Powermonitor 3000 to version 4.2x firmware
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationNetwork Asset Design Standard HV SUBSTATION FEEDER EXIT CIRCUITS ISOLATION POLICY
Network Asset Design Standard HV SUBSTATION FEEDER EXIT CIRCUITS ISOLATION POLICY Original Issue: September 2007 Prepared by: Lee Chan & Rob Rogerson This Revision: 0 October 2007 Date For Next Review:
More informationDUCM Hardware. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA
DUCM Hardware Manual DUCM Hardware Installation Manual This manual covers the DUCM hardware features and installation procedures. Effective: May 29, 2015 Niobrara Research & Development Corporation P.O.
More informationSoft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.
Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0
More informationAutomation System Solutions
Automation System Solutions Automation Systems for Power Grid, Power Plant and Industries NR Electric Corporation Automation for Power Grid Substation Automation System Conventional Substation Automation
More informationLM10 to MM200 Retrofit
Grid Solutions LM10 to MM200 Retrofit Replace old LM10 Motor Controller relays with the Multilin TM MM200 Motor Management System The LM10 Motor Controller (discontinued in 2013) has been replaced by new
More informationPlease read these instructions carefully before installing This will ensure an easy start and a great first customer experience with TS4 installation
Please read these instructions carefully before installing This will ensure an easy start and a great first customer experience with TS4 installation INTERACTIVE INSTALLATION AND SAFETY MANUAL FOR TS4:
More informationContent REF615 Technical Presentation
Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide
More informationRelion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation
Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,
More informationMulti-instrument Communication, MIC-2 MKII DIN Quick Start Guide
Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Warnings and legal information Installation and terminals Communication I/O options Alarming Utility software More information Specifications
More informationB. System Design and Performance Requirements
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16950 to 26 27 13, removed references to other section numbers 11/21/14
More informationElectrical Integration with Smart Communication
Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as
More informationENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER
smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS
More information