1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: Members of the NEC-Code Making Panel 13 FROM: Jean O Connor DATE: March 9, 2012 SUBJECT: NFPA 70 ROP Final Ballot Results (A2013 Cycle) The March 8, 2012 date for circulation changes and final receipt of letter ballots has passed. In accordance with the NFPA Regulations Governing Committee Projects, the attached report contains the number of members eligible to vote, the names of principals whose ballots were not returned, and the reasons for negative, affirmative and abstaining comments. Attachment: Final Ballot Results Report

2 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: 0 Entire Document (Log # 1170l ) 13-2 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: 0 Entire Document (Log # 921l ) 13-3 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Battery System (New) and (Log # 1606 ) 13-4 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Emergency Systems (New) and (Log # 1613 ) 13-5 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Nominal Battery Voltage (New) and (Log # 1605 ) 13-6 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Phase Converter (New) and (Log # 1604 ) 13-7 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Sealed Cell or Battery (New) and (Log # 1608 ) 13-9 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Storage Battery (New) and (Log # 1607 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 2682 ) Degnan, J. Field marking of generators for permanent installations is not necessary, but does no harm. Field marking of rental units or portable generators that are used in multiple applications may or may not be accurate. If the NEC is going to require field marking it should also require verification of the indicated marking prior to application. Little, L. We agree with the affirmative comments by Mr. Degnan and Mr. Ode. Ode, M. The last sentence in the Panel Action text should be moved to the last sentence of the Panel Statement as follows: "CMP-13 does not accept the proposed requirement for marking the location of the generator bonding which may be inaccessbile in some cases." since it is not part of the actual text to be inserted as text into the NEC Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 2932 )

3 Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (Log # 2643 ) Brown, J. The panel's action does not meet the submitter's intent and this proposal should have been rejected. The inclusion of overload in the section title does not address his concerns for short-circuit protection. The term Overload does not need to be included in the title since the present title Overcurrent Protection already encompasses overload protection, as the submitter of this proposal has stated. Little, L. This action is not necessary and is confusing a well defined term. The term "overcurrent" is defined in Article 100 and clearly includes "overload." Adding the term "overload" to the section title does not add clarity since the existing title is "overcurrent." Combining these two terms for a new section title "Overcurrent and Overload Protection" infers that overcurrent protection is not overload protection. The submitters proposed revision was directed at adding "short circuit" into (A). How does adding the term "overload" into the section title meet the intent of the submitter? Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 1158 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 425 ) Little, L. For correlation with the actions taken on proposals throughout the NEC, the reference to "600 volts" should be revised to "1000 volts." Ode, M. While I agree with the Panel Action, the existing text has an errata that should be fixed as part of the revision in the proposal. In the last sentence, the word "and" should be changed to "through" read as follows: The higher horsepower rating of Table through Table shall be used whenever the generator selection is between two ratings Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Exception (New) (Log # 502 ) Little, L. For correlation with the actions taken on proposals throughout the NEC, the reference to "600 volts" should be revised to "1000 volts." Ode, M. See my comment on Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 480 )

4 3 Little, L. The action to accept in principle should be modified as follows: Disconnecting Means Required for Generators. Generators shall be equipped with disconnect(s), lockable in the open position, by means of which the generator and all protective devices and control apparatus are able to be disconnected entirely from the circuits supplied by the generator except where all of the following conditions apply: (1) The generator is listed. (2) The driving means for the generator can be readily shut down, rendered incapable of restarting and is lockable in the OFF position in accordance with (3) The generator is not arranged to operate in parallel with another generator or other source of voltage. Informational Note: See UL 2200 Standard for Safety of Stationary Engine Generator Assemblies. The action to accept in principle proposal will permit the installation of a standby generator without a disconnecting means installed at any point from the generator terminals to the equipment supplied. A means to simply shut down the driving means for the generator, such as a diesel engine, is all that will be required. The panel action to accept proposal is based partially on UL 2200 which mandates a means to stop the driving means, prevent restarting and requires this means to be lockable in the OFF position. Not all generators are listed. The above modifications are needed for the safety of all installer/maintainers. It should be noted that OSHA does not permit an emergency stop button to be used to lockout electrical equipment. See CFR (b)(2)(ii)(B). If a Nationally Recognized Testing Laboratory (NRTL) has listed such a device for lockout/tagout, it may be considered by OSHA as an acceptable means of lockout/tagout. The reference to correlates with the action on proposal a Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # CP1304 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (Log # 501 ) Ode, M. This proposal should have been a reject instead of an accept in principle since Proposal 13-16a deleted Section Little, L. We agree with the affirmative comment by Mr. Ode Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (New) (Log # 2461 )

5 4 Caron, D. The panel statement does not address the submitter's substantiation. Large generators, arranged to operate in parallel to serve loads in hospitals and other occupancies, are very common. The conductors, controls and equipment required to parallel the generators, including the electrically operated circuit breakers and the common bus in the paralleling switchgear, should be defined or recognized in some way in Article 445 as a system. Rules for applying ground fault protection (700.6(D)) and selective coordination (700.27) are often misapplied, or as the submitter has indicated, cannot be applied Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (New) (Log # 3364 ) Czarnecki, N. This proposal seeks to add GFCI protection to all 125V generator outlets without any substantiation that an issue exists at all levels. In order to establish a functional GFCI configuration on the generator, the generator is forced to be of the bonded neutral variety. Therefore, this proposal would have the effect of eliminating floating neutral generators used to power structures, non-separately derived standby systems, and transfer switches for non-separately derived systems. Eliminating such equipment will not enhance safety, but obsolete safe infrastructure already in place. Enhanced safety has not been accomplished and potentially compromised with users defeating the system by removing grounding connections to find a means to get power on in their home. Note: Supporting Material is available for review at NFPA Headquarters. Degnan, J. The submitter did not present any new information regarding the different safety issues associated with portable generator grounding that wasn't available in 2008, when this same proposal failed to gain the required acceptance of the panel.

6 Little, L. The following comment is written to address the negative comment by Mr. Czarnecki: We agree that acceptance of this proposal will require all portable generators to be of the bonded neutral type. There are many presently in production. The sketch provided by Mr. Czarnecki with the negative ballot comment clearly reveals his concern, which is the viability of 15/20 ampere, 125-volt, single pole transfer switches. They will not work through a GFCI. A two pole transfer switch would be required because a portion of the neutral current would flow over the equipment grounding conductor where a single pole transfer switch is used causing the GFCI to open. We strongly disagree that the elimination of the floating neutral type generator will remove safe infrastructure already in place. The infrastructure already in place represents serious safety concerns along with clear and indisputable NEC violations. The issue at the core of this proposal is the use of portable generators to supply power to a dwelling unit when there is a loss of power. This occurs regularly across the country when there is a weather related event that causes a loss of power. Homeowners use portable generators to supply power to sump pumps, heaters, lighting, wet vacuums, refrigerators, freezers and other appliances during weather related events. There are 15/20 ampere, 125-volt, single pole transfer switches on the market and their use allows the homeowner to supply power to the selected branch circuit by plugging the male end of an extension cord into a receptacle outlet on the generator and by plugging the female end of the extension cord into a flanged outlet on the 15/20 ampere, 125-volt, single pole transfer switch. Once this connection is made, we no longer have a floating neutral generator. We now have a grounded system through the solid connection to the service supplied neutral conductor. This means that all other receptacle outlets on the generator now have potential to ground without GFCI protection. The homeowner will utilize every receptacle outlet in these weather related events, and without GFCI protection, serious safety concerns exist. Where a generator is used in this manner it is covered by the NEC, it is part of the premises wiring as defined below: Premises Wiring (System). Interior and exterior wiring, including power, lighting, control, and signal circuit wiring together with all their associated hardware, fittings, and wiring devices, both permanently and temporarily installed. This includes (a) wiring from the service point or power source to the outlets or (b) wiring from and including the power source to the outlets where there is no service point. Such wiring does not include wiring internal to appliances, luminaires, motors, controllers, motor control centers, and similar equipment. A portable generator supplying a dwelling unit through a transfer switch is indisputably part of the premises wiring and is covered by the NEC. The requirements in and (B) apply. We understand and are sympathetic to the concerns of Mr. Czarnecki. However, we must take action to prevent exposure to shock hazards. We cannot look the other way because of the impact on a particular product when it comes to safety. The claim that this revision will drive homeowners/users to defeat the system by removing grounding connections is without merit because we presently have both types of generators readily available. When a homeowner/ user decides to buy a new portable generator, they will go online or to a local home improvement 5

7 6 store. A simple trip to Lowes or Home Depot reveals that many of the portable generators available already have GFCI type receptacles. The Purpose of the NEC is the practical safeguarding of persons and property from hazards arising from the use of electricity. That is the intent of this proposal. We need to get it right. Paulsen, S. While I agree with the intent to provide additional personal protection I also feel that this now a product standards issue. The standard for generators should be updated to include this requirement. When I read the proposed Rule it could imply to add ground-fault circuit interrupter protection to existing generators as well. This could result in certified generators being modified in the field and thus voiding the existing certification Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (Log # 3302a ) Rodriguez, A. The primary function of the conductor presently defined as an "equipment grounding conductor" is actually a bonding function. The grounding electrode conductor grounds systems and equipment. Accepting this change will help increase usability and understanding of the associated requirements. The existing term and the associated terms grounded and bonded are frequently misunderstood and misused by both new and experienced NEC users. Spina, M. Similar proposals have been presented in the past and have been rejected. Reasons given often relate to cost, significant changes in documentation required, or the fact that knowledgeable people know what this conductor is used for. Cost and documentation changes should never be an argument where safety is concerned. Further, not all electrical practitioners are knowledgeable in the main intent of this conductor. There is no justification for retaining an incorrect and potentially hazardous electrical installation just because we have used this definition for many years. The intent of the proposed change is to provide a descriptive name to a construction element that has resulted in much misunderstanding with possible hazardous operating conditions in electrical installations. The use of the term grounding implies that grounding is its principal function. Although grounding may be desirable, providing an effective fault current path (i.e. bonding) is and should be the emphasis. There are many who feel that a connection to a water pipe (which may or may not be a good ground) meets the needs of equipment grounding. There are two conductors described in the Code performing the same function but named differently. The bonding jumper is a short conductor that insures the electrical integrity of enclosure to raceway. The longer conductor, intended to provide a low impedance path to the source, is named a grounding conductor instead of its real function as a bonding conductor. Technically, the definition in Article 100 may be adequate for Panel members and those that teach. Practically, the definition is confusing if the terminology does not fit the function performed. The equipment bonding conductor, as it should be called, provides its primary function whether or not it is grounded. For a grounded system, it is grounded because the system is grounded. For an ungrounded system, it is grounded to limit the voltage due to a lightning strike or contact with a higher voltage system. Changing the name will assist in educating electricians into the why they are installing a conductor that needs to be continuous all of the way back to the source Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: xx (New) (Log # 2996 )

8 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: xx (New) (Log # 3007 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: xx (New) (Log # 3008 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: , Informational Note (New) (Log # 3009 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 2241 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Cell (New) (Log # 2989 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Container (New) (Log # 2990 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Electrolyte (New) (Log # 2991 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Intercell Connector (New) (Log # 2992 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Intertier Connector (Log # 2993 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Nominal Battery Voltage (Log # 2994 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Terminal (New) (Log # 2995 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: and (Log # 2997 )

9 8 Little, L. Further modifications to this section should be considered. The following proposed revisions were in a proposal not received by NFPA staff that was developed by a joint effort of the NEC Task Force of the Technical Correlating Committee and the IEEE Stationary Battery Committee. The section is retitled and subdivided as follows: DC Disconnect Methods (A) Disconnecting Means. A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system with a nominal voltage over 50 volts. A disconnecting means shall be readily accessible and located within sight of the battery system. (B) Remote Actuation. Where controls to activate the disconnecting means of a battery are not located within sight of a stationary battery system, the disconnecting means shall be capable of being locked in the open position in accordance with Section (C) Busway. Where a DC Busway system is installed, the disconnecting means shall be permitted to be incorporated into the busway. (D) Notification. A label shall be installed on or adjacent to the disconnect containing the maximum available short circuit current. The label shall be placed in a conspicuous location near the battery if a disconnect is not provided. Informational Note: Battery equipment suppliers can provide information about short circuit current on any particular battery model (A) requires remote activation for disconnects serving ITE rooms. The disconnect serving the ITE room must be capable of being locked open to prevent the remote actuation from occurring when it will jeopardize safety of personnel. DC busway is common in large UPS installations in which there are multiple strings of batteries. Each string is connected in series to create the necessary dc voltage and each string has a disconnecting means &/or overcurrent protective device. The strings are connected in parallel to a common dc bus which may also have a disconnecting means. The individual string disconnects allow manual disconnecting so that maintenance can be performed on a redundant battery string while the remaining battery strings support the load. It also functions as an OCPD to prevent the energy from other strings from feeding into a faulted cell in one string. The disconnect on a DC busway system allows for a single point of shutdown for the entire dc supply. The stored energy in a battery system is a potential hazard to personnel maintaining the system. The labeling requirement attests this hazard and aids in determining the arc-flash protection boundary and required PPE Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 52 ) Ode, M. In the last sentence in the Panel Statement, change the word "in" to "with" for clarity Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 620 ) Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (A) and (B) (New) (Log # 1076 )

10 9 Little, L. The proposed revision to require that the disconnecting means be installed "as close as practicable" is enforceable. The term "practicable" with reference to distance is used throughout the NEC and has been enforced by AHJs for decades. This proposed revision mirrors the present requirement in (H), which requires overcurrent protection to be installed as "close as practicable" to the battery terminals. Spina, M. A) (H) permits overcurrent protection for battery conductors to be installed as close as practicable. Inclusion of a similar statement here would harmonize the requirements. B) NFPA 70E-2012 Table 130.7(C)(15)(b) Hazard/Risk Category Classifications and Use of Rubber Insulating Gloves and Insulated and Insulating Hand Tools Direct Current Equipment requires determining the available arcing current to select PPE necessary for protection of employees. he arcing current depends on the maximum short circuit from battery system. Without knowing what the available short current is, employees have no way of selecting required PPE for protection from the arc flash hazard. The only way to determine the maximum short circuit available from the battery is from the manufacturer. The optimum time to obtain this value is during the initial installation. Without this information, proper sizing of disconnect switch may not be feasible. This requirement for posting of short circuit current for batteries is similar to the requirements in for service equipment to comply with and Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 2998 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (C) (Log # 2999 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (A), Informational Note (New) (Log # 53 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (C) (Log # 119 ) Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (C), Informational Note (New) (Log # 3001 ) Degnan, J. The note provides valuable information and should be left in. While the panel statement is true, applying it universally to the NEC would result in the removal of many informational notes. Little, L. The panel statement is incorrect. The proposed informational note is designed to inform the code user that additional space may be required. Where adequate space is not provided to permit the hoisting, removal or replacement of batteries, serious safety concerns exist Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (C)(1) and (2) (New) (Log # 3000 )

11 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (New) (Log # 3002 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 3003 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (E) (Log # 3004 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) (New) (Log # 3005 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (X) (New) (Log # 3006 ) Little, L. This proposal should have been accepted. The panel statement to reject agrees with the proposed text. The panel states that a requirement for illumination of batteries belongs in Article 480. The panel also agrees that luminaires should not be located directly above batteries Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 2242 ) 13-48a Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B) (Log # CP1300 ) Caron, D. See my comment on Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (C) (New) (Log # 3366 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 1660 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Fire Pump - Sprinkler Pumps for Residential Homes (New) (Log # 401 ) Ode, M. The submitter did not provide the proposed text or wording in the recommendation in this proposal in accordance with 4.3.3(c) of the NFPA Regulations Governing Committee Projects. NFPA rules require the wording to be added or revised and how the text in the NEC should be revised. Residential fire pumps are already covered by Article 695 in the NEC.

12 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: On-Site Standby Generator (Log # 1271 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (A)(1) (Log # 497 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (A)(1) (Log # 611 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (C)(1) (Log # 549 ) Caron, D. The panel action, the new text in 13-48a (695.1(B)) and new text in 13-55a, partially meets the intent of Proposal Transfer equipment in the main electric room of a building that is part of a multibuilding campus-style complex, can manually or automatically switch from a feeder supplying the building, to a back-up feeder within the main electric room. A single feeder to the pump room would be considered a reliable source because of the back-up feeder by NFPA (4). The panel statement is not consistent with NFPA 20 language in that NFPA 20 would not require an additional alternate source to the pump room, as required by 695.3(C)(2). Ode, M. The last sentence in the Panel Statement (The Panel Action on 13-48a meets the intent of the submitter) is incorrect. Proposal 13-48a deals with a clarification of Article 695 coverage of the installation of pressure maintenance pumps and transfer equipment upstream of the fire pump transfer switch. Proposal deals with feeder sources for multi-building campus-style complexes a Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) and 695.3(G) (Log # 3532 ) Caron, D. See my comment on Proposal

13 12 Czarnecki, N. Add the following to 695.3(F): Overcurrent Device Selection. An instantaneous trip circuit breaker shall be permitted in lieu of the overcurrent devices specified in 695.4(B)(2) provided it is part of a transfer switch assembly listed for fire pump service. Currently, the NEC only permits the use of an instantaneous trip circuit breaker if provided as part of a listed combination motor controller as specified in (C)(3). The operating characteristics of an instantaneous trip circuit breaker lend themselves very well to the overcurrent protection permitted between the fire pump power source and the fire pump controller or the fire pump transfer switch. Such overcurrent protection is sized to provide only ground fault and short circuit protection for the fire pump motor circuit. It does not provide motor overload protection. Overload protection for the fire pump motor is provided by the circuit breaker in the fire pump controller. This arrangement prevents opening of the overcurrent protective device permitted between the fire pump power source and the fire pump controller or the fire pump transfer switch in the event of a motor overload. If this overcurrent protective device were to open, it may not accessible for immediate resetting and thus, render the fire pump motor inoperable. If the fire pump motor experiences an overload condition causing breaker tripping, it is desirable to have the fire pump breaker trip because it is easily located and reclosed to allow attempts to restart the fire pump motor during a fire event. Fire pumps can be temporarily distressed and one or more attempts at restarting can result in continuous running of the pump motor if the overload condition no longer exists. Instantaneous trip circuit breakers do not provide overload protection which is the required performance for the overcurrent protection permitted between the fire pump power source and the fire pump controller or the fire pump transfer switch. The magnetic trip setting of an instantaneous trip circuit breaker can easily be adjusted to provide the operating characteristics for overcurrent devices as specified in 695.4(B)(2). More importantly, an instantaneous trip circuit breaker does not need to be sized as large in amperes as other protective devices already permitted. Such oversizing is necessary to prevent their overload tripping characteristics from overlapping those of the fire pump circuit breaker. It is recognized that an instantaneous trip circuit breaker is intended to be a factory installed product. This is ensured by including the requirement that it shall be provided as part of a transfer switch assembly listed for fire pump service Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(2)(a) (Log # 1530 ) Ode, M. The Panel Statement should be revised as follows: CMP-13 notes that Proposal does not strike the original text in (1) but provides new text based on the NFPA 20 document as an alternative to the existing text in the NEC Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(2) (Log # 2639 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(2) (Log # 2640 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(2)(a) (Log # 2738 ) Ode, M. See the affirmative statement in Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(3)(a) (Log # 321 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(3)(b) (Log # 326 )

14 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(3) (Log # 844 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 1496 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (B) (Log # 1531 ) Czarnecki, N. The assertion that NFPA20 does not allow for the alternate method of overcurrent protection for transformers, simply because it does not specifically address the issue, is unsupportable Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (C)(2) (Log # 1532 ) Czarnecki, N. The assertion that NFPA20 does not allow for the alternate method of overcurrent protection for transformers, simply because it does not specifically address the issue, is unsupportable Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (C)(2) (Log # 1673 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (A)(2)(d)(1) (Log # 1118 ) Ode, M. The Proposal did not provide any technical substantiation for the change from 2 inches of concrete in the existing NEC text to 4 inches of concrete. UL does not list concrete by itself for a fire rating so any UL fire rated assembly would involve a complete assembly of building materials, often including concrete and other materials. There are many different factors that can affect heat transfer, other than the thickness of concrete. Pre-stressed concrete has a different heat transfer ratio than lightweight concrete, steel reinforcement within concrete will affect heat transfer, and the type of aggregate used within the concrete will also affect heat transfer. The NFPA Fire Protection Handbook states the following: Reinforcing steel can also affect the amount of heat transfer that can occur within the concrete floor or wall." Concrete has a low thermal conductivity and a low thermal capacity. One of the more significant factors in determining the thermal characteristics of reinforced concrete is the type of aggregate used in the concrete and can vary throughout the United States. Concrete in direct contact with earth will have a different heat transfer than concrete installed as a wall or floor ceiling installation for multiple floor locations. Moisture content of the concrete will affect heat transfer. Furthermore, lightweight concrete has much different heat transfer rates than regular, reinforced, or prestressed concrete. The submitter could have provided a Fact Finding Study on the different types of concrete that could be used, the recommended thickness, and addressed the variables with the amount of heat transfer for each application so the Panel could act on the technical merits for this change, rather than just guessing at a depth of concrete. The 2-inch concrete thickness has been used for many NEC cycles to provide physical protection with some limited protection from heat transfer and should not be changed without proper technical substantiation for this change.

15 Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (B) (Log # 10 ) Degnan, J. While test data shows that 2" of concrete fails to protect when subjected to a fire for 2 hours, fire isn't the only consideration. In some egress scenarios, concrete encasement may offer physical protection that would prove more valuable than a system only designed for 2 hours fire. Ode, M. See the Statement in Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 141 ) Little, L. Electrical metallic tubing (EMT) has been proven as an effective ground fault path. See the GEMI research study or the data in the Soares grounding book Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 702 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 1529 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 1828 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) and (E) (Log # 2419 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) and (E) (Log # 2445 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (D) (Log # 2641 ) Savage, Sr., M. The submitter s substantiation states that EMT with set screw connectors would not be an acceptable method of providing a GF return path and would require a separate EGC. However, under EMT is judged to be an acceptable (FMC is required to have listed fittings per this section, no mention of EMT) EGC and no material was presented to show the inadequacy of EMT as a GF return path.

16 15 Czarnecki, N. The substantiation contains an incorrect reference to electrical metallic tubing (EMT) with set-screw fittings as an example of a raceway that is not capable of conducting sufficient ground-fault to open the overcurrent protective device. The Georgia Tech research study on grounding referred to in the Soares Book on Grounding validates that EMT with set-screw fittings and installed in accordance with the NEC is a proven equipment grounding conductor in accordance with the requirements of Article 250. Effective February 1996, UL 514B, the Standard for Safety for Conduit, Tubing and Cable Fittings required that all EMT fittings be subjected to a current test to determine if the EMT and the interface between the EMT and the fitting can effectively carry fault current, in order to permit operation of the overcurrent device and terminate fault current flow. In order to carry a UL listing, EMT fittings must pass this test. Article 358 (Electrical Metallic Tubing) requires the use of listed fittings. Degnan, J. If vibration from the pump compromises the ground path offered by the raceway, and a subsequent pump motor ground fault occurs, its possible to energize the motor frame. Other than this limited scenario, the entire ground return path would need to be examined, not just the portion between the controller and the motor. Little, L. Electrical metallic tubing (EMT) has been proven as an effective ground fault path. See the GEMI research study or the data in the Soares grounding book Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) and (E) (Log # 2843 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 2913 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (E) (Log # 2669 ) Little, L. Electrical metallic tubing (EMT) has been proven as an effective ground fault path. See the GEMI research study or the data in the Soares grounding book Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (I) (Log # 142 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (J)(5) (New) (Log # 1350 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (A) (Log # 3020 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B) (Log # 703 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (G) (Log # 143 )

17 13-84 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (E) (Log # 2808 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (F) (Log # 11 ) Ode, M. See the Statement in Proposal Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (F)(1) (Log # 1119 ) Ode, M. See the Statement in Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (G) (Log # 144 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 1469 ) 13-88a Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 3533 ) Degnan, J. It would be helpful to clarify in the Informational Note that NFPA 99 no longer uses the term "emergency for the life safety and critical branches of the essential electrical system Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Luminaire, Directly Controlled (New) (Log # 1395 ) Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: and (B) (Log # 3312 ) Degnan, J. Reasoning for the negative vote is in the text of the proposal Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: Emergency Systems (Log # 747 ) Degnan, J. The figure is not clear where the delineation is betwen normal and emergency. 16

18 17 Caron, D. The figure for this Proposal (13-91) should be modified per figure (13-91 Attachment 1 Figure 700-2) and the figures for Proposal , and should be similar for consistency. In addition, the figure (13-91 Attachment 2 Figure 695-3(D)) should be added to 695.3(D) for fire pumps when an on-site standby generator is used for the alternate source. ****Insert Two Figures Here*** Czarnecki, N. The changes the Panel suggested could create some level of confusion. Perhaps some additional detail in the comment stage could explain the intent of the figures, the meaning of the symbology, and any requirements the figures were not intended to define Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: Emergency Systems (Log # 1272 ) 13-92a Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: , 700.3(E), , Informational Note (Log # CP1302 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) (Log # 2526 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (A) and (B) (Log # 1448 ) Ode, M. Revise the last sentence in the Panel Statement to read as follows: The entire system, based on Section 700.3(A), may be done yearly or every other year, as determined by the AHJ Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (C) (Log # 1011 ) Brown, J. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (E), 701.5(D), and (E) (Log # 2263 ) Ode, M. Listed and identified emergency automatic transfer switches, as required by 700.5(A) and (C), are already required by UL 1008 to be marked with the types of overcurrent protective devices that are required for protecting the transfer switches and with the short circuit current rating of the transfer switch. The term withstand rating is not used in the requirements in UL 1008 but the rating in available rms symmetrical short circuit current is used in the Standard.

19 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B) (Log # 906 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 3330 ) Little, L. Surge protective devices have proven to provide benefits for components and systems against the damages of voltage surges, but the substantiation for this proposal does not document that such protection would specifically benefit emergency systems Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (B)(5) (Log # 63 ) Degnan, J. Reasoning for the negative vote is in the text of proposal 13-90, which was updated for this code cycle Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (B)(5)(b) (Log # 64 ) Degnan, J. Further examination of that paragraph the 2011 NEC (B)(5)(b) reveals that it should be rewritten to clarify its intent. The paragraph states that it shall be permitted to not have overcurrent protection, the exception states that it shall be permitted to have it. I intend to submit a comment suggesting that the proposal be accepted in principle by changing the text to "...multiple feeders with or without overcurrent protection at the source." and eliminating the Exception Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (D)(1) (Log # 12 ) Ode, M. See the Statement in Proposal Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (B) (Log # 3313 ) Degnan, J. The reason for the no vote is in the text of the proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(5) (Log # 496 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(5) (Log # 2131 )

20 19 Degnan, J. If the panel doesn't support removing the paragraph as in proposal 13-90, improving the paragraph's language and clarity is appropriate Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 1116 ) Caron, D. The first level subdivision should be further revised as follows: (D) Fire Protection. Emergency systems shall meet the additional requirements in (D)(1) through (D)(3). in assembly occupancies for not less than 1000 persons or in buildings above 23 m (75 ft) in height Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 1564 ) Caron, D. See my comment on Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 2087 ) Caron, D. See my comment on Proposal Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) Exception (New) (Log # 1143 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D)(1) (Log # 1117 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (B)(6), (B)(5), , , and (Log # 65 ) Ode, M. See the Affirmative Statement in Proposal Eligible To Vote:18 Affirmative: 16 : 2 Abstain: 0 Not Returned: (B)(6), (B)(5) and (Log # 550a )

21 20 Little, L. This action will now permit a generator installation without a disconnecting means. There will only be a control device to stop the generator driving means. Nothing more is required. There is no requirement that the generator be rendered incapable of restarting. There is no requirement that the device used to stop the driving means and to prevent restarting be capable of being locked in the open position must be modified before this action is acceptable in any form. See our proposed solution and statement on Proposal Savage, Sr., M. The submitter's concerns are adequately covered throughout the NEC in various Articles, and this requirement would eliminate the ability to provide Lock Out/Tag Out protection for servicing the system. Caron, D. For clarity, the article should be rewritten as follows: (6) Outdoor Generator Sets. An outdoor housed generator set shall be equipped with a disconnecting means in accordance with (6)(a) or (6)(b): (a) A disconnecting means, in accordance with , mounted on or within the generator enclosure and located within sight of the building or structure supplied. (b) A disconnecting means, in accordance with , mounted on or within the generator enclosure and an additional disconnecting means, in accordance with located where ungrounded conductors serve or pass through the building or structure supplied. Exception: For installations under single management, where conditions of maintenance and supervision ensure that only qualified persons will monitor and service the installation and where documented safe switching procedures are established and maintained for disconnection, the generator set disconnecting means shall not be required to be located within sight of the building or structure served and an additional disconnecting means, in accordance with located where ungrounded conductors serve or pass through the building or structure supplied shall not be required. Ode, M. A new second to last sentence in the revised text should be added as follows: "A listed generator complying with this section and supplied with listed branch circuit or feeder circuit breakers shall not be required to comply with " Adding this text will ensure that circuit breakers supplied as part of the generator does not have to be service rated Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D) (Log # 2153 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (D)(1) (Log # 3125 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) (Log # 428 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) (Log # 1565 )

22 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F) Exception No. 1 (Log # 838 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (F)(4) Exception No. 3 (Log # 2024 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 3367 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 764 ) Caron, D. Revise as follows: Switch Requirements. (A) Arrangement. The switch or switches installed in emergency lighting circuits shall be arranged so that only authorized persons have control of emergency lighting. Exception No. 1: Where two or more single-throw switches are connected in parallel to control a single circuit, at least one of these switches shall be accessible only to authorized persons. Exception No. 2: Additional switches that act only to put emergency lights into operation but not disconnect them shall be permissible. (B) Series Connected or Three Way and Four Way Switches. Switches connected in series or 3- and 4- way switches shall not be used. (C) Motion Sensors. Emergency lighting circuits shall be permitted to be switched by motion sensors, where all of the following conditions are met: (1) Spacing between motion sensors is in accordance with manufacturer's instructions. (2) Manual activation is not required to reenergize emergency lighting when the area is occupied. (3) A non-adjustable time delay of minutes shall be required after the area is vacated prior to extinguishing of lighting for the area. Exception No. (C)(3): Motion sensors with time delays shall be permitted provided it is used in conjunction with an automatic load control relay that will automatically bypass the motion sensor and energize emergency lighting upon loss of normal power. (4) Motion sensors shall not have a manual-off position Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 1398 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (New) (Log # 1397 ) Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 1470 )

23 Eligible To Vote:18 Affirmative: 18 : 0 Abstain: 0 Not Returned: (Log # 2255 ) Caron, D. Proponents of selective coordination do not seem to have any concern about coordination of low level ground faults. Ground faults are the most prevalent fault in the field; exponentially more prevalent than high value short circuits. This fact is documented in IEEE literature. Because of the pervasiveness of ground faults, Article and require ground fault protection of equipment for services/feeders over 150 volts and 1,000 amperes. Article requires a second level of ground fault protection as well as selectivity with the upstream ground fault device. There are many requirements in the Code for ground fault circuit interrupters. The majority of the ground fault protection requirements apply to the normal power system. Due to these requirements, over the years, manufacturers have developed the technology to design a complete system that coordinates low level ground faults from service entrance equipment to lighting branch circuits, yet Article 700 explicitly does not require selectivity for these common faults at all, just indication Eligible To Vote:18 Affirmative: 17 : 1 Abstain: 0 Not Returned: (Log # 765 ) Caron, D. The Panel agreed in the 2010 ROP that devices in the normal system are outside the scope of Article 700 and reaffirmed this position in this Panel Statement. The scope of Article 700 is clearly defined in 700.1: The provisions of this article apply to the electrical safety of the installation, operation, and maintenance of emergency systems when the normal electrical supply or system is interrupted. The additional text is accurate and necessary and it provides clarity to help alleviate misinterpretation.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 13 FROM:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 11 FROM:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 3 FROM: Jean

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Code-Making Panel 5 FROM: Kimberly Shea DATE:

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea,

More information

Page 1 of 149 First Revision No. 50-NFPA 79-2012 [ Global Input ] Delete the parenthetical terms used to describe IEC terms that follow terms used in NFPA 79 such as "protective bonding". Add information

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and IEC 60309 H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and amperage to prevent interchangeability of voltages Watertight

More information

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP NEC 2008 Code Changes Top 20 Revisions By: Rafi Wartan, PE, LEED AP #1 Article 210.4 MULTIWIRE BRANCH CIRCUITS The rule on simultaneous disconnecting means requirements for multiwire branch circuits was

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Entry Level Assessment Blueprint Electrical Occupations

Entry Level Assessment Blueprint Electrical Occupations Entry Level Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Safety Apply shop safety rules and ergonomics Explain fire

More information

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Microinverters And The Solar Industry

Microinverters And The Solar Industry Microinverters And The Solar Industry Peter Lum Senior Learning And Development Professional Assistant Professor Skyline College Solar Continues Its Growth 2 Significant Growth Of Microinverters in Solar

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fundamentals

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

Stalking the Elusive and Somewhat Strange PV System

Stalking the Elusive and Somewhat Strange PV System A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles PERSPECTIVES ON PV Stalking the Elusive and Somewhat Strange PV System Photo 1. Framed PV modules

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...

More information

2008 Code Changes for Power Distribution

2008 Code Changes for Power Distribution 2008 Schaedler Yesco Expo 2008 Code Changes for Power Distribution April 17, 2008 / Version 1.0 For internal use only / Copyright Siemens AG 2007. 2008. All rights reserved. Contact Consulting Account

More information

2014 AFCI code compliant safety. Understanding the 2014 NEC. for AFCI protection

2014 AFCI code compliant safety. Understanding the 2014 NEC. for AFCI protection 2014 AFCI code compliant safety Understanding the 2014 NEC for AFCI protection Understanding the code for code compliant safety An arc fault is an unintended arc created by current flowing through an unplanned

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Second Revision No. 1-NFPA [ Global Comment ]

Second Revision No. 1-NFPA [ Global Comment ] Second Revision No. 1-NFPA 79-2017 [ Global Comment ] *************GLOBAL INSTRUCTION - COMP: See Mark's note for clarity*************** Remove all parenthetical terms of (plug/socket) and any variation

More information

UL 508 A standard-compliant design of industrial control panel

UL 508 A standard-compliant design of industrial control panel UL 508 A standard-compliant design of industrial control panel Axel Jöhnke System Architecture Expert 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net Origin and Comprehension Organizations Certificates

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

Why is my AFCI tripping?

Why is my AFCI tripping? www.garyklinka.com Page 1 of 21 Instructions: Fee $25 1. Print these pages. 2. Use the included information located on pages 12-20 to answer the 61 questions below. 3. Circle the correct answers and transfer

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits

Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits Course Details Date: January 28 January 31, 2019 Time: 8:00 A.M. - 4:30 P.M. Capacity: 12 attendees Provider: National Technology

More information

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Means of Egress

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

R-LB R-LX Series Installation, Operation & Maintenance Manual

R-LB R-LX Series Installation, Operation & Maintenance Manual Installation, Operation & Maintenance Manual WARNINGS Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

More Questions from Inspectors Numerous PV Systems Pose Issues

More Questions from Inspectors Numerous PV Systems Pose Issues Perspectives on PV More Questions from Inspectors Numerous PV Systems Pose Issues by John Wiles 76 IAEI NEWS March. April 2012 www.iaei.org Photovoltaic (PV) systems prices continue to drop and inspectors

More information

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL Issue 2011 ASL Intercom BV DESIGNED & MANUFACTURED BY: ASL Intercom B.V. Zonnebaan 42 3542 EG Utrecht The Netherlands Tel: +31 (0)30 2411901 Fax: +31 (0)30

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Spring Test 5 due 4/26/2013

Spring Test 5 due 4/26/2013 Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof

More information

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Means of Egress

More information

Spring Test 13 due 06/14/2013

Spring Test 13 due 06/14/2013 Spring Test 13 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The power supply to the mobile home shall be a feeder assembly consisting

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

Spring Test 17 due 06/14/2013

Spring Test 17 due 06/14/2013 Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered

More information

Fall Test 21 due 12/11/2012

Fall Test 21 due 12/11/2012 Fall Test 21 due 12/11/2012 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Emergency system transfer equipment, including automatic transfer switches,

More information

White Paper Surge Protective Devices in Automatic Transfer Switches

White Paper Surge Protective Devices in Automatic Transfer Switches White Paper Surge Protective Devices in Automatic Transfer Switches Standby power systems provide emergency power, legally required power, or optional standby AC power during utility outages. Standby AC

More information

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C Instruction Manual Electrical Management System (EMS) EMS-HW30C & EMS-HW50C EMS-HW50C EMS-HW30C! CAUTION These instructions are intended to provide assistance with the installation of this product, and

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Testing for safe and efficient branch circuits

Testing for safe and efficient branch circuits Testing for safe and efficient branch circuits Written by Chad Reynolds, Product Manager, IDEAL Test and Measurement Division Branch Circuit Testing Branch circuit wiring and testing practices are primarily

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Emergency Power Supplies

More information

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL August 2016 This product is designed and manufactured by: ASL Intercom B.V. Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax: +31

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

30-Cycle Rated Switchboards - Selectivity Tradeoffs

30-Cycle Rated Switchboards - Selectivity Tradeoffs 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician Certification Exams How to Use the Detailed Content Outlines These Detailed

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options

More information

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS FOR SURGE PROTECTION DEVICES This Tech Note provides an overview of the key standards associated with surge suppressors and AC powerline filters.

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

Spring Test 16 due 06/14/2013

Spring Test 16 due 06/14/2013 Spring Test 16 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. Figure 234.142 1. Refer to the information shown in Figure 234.142. Motor 1

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

ZC Series Zone Monitoring Controllers

ZC Series Zone Monitoring Controllers ZC Series Zone Monitoring Controllers Installation Instructions MANUAL Reset Controllers Model Description Part Number ZC-1 1 Zone Controller 0421 ZC-2 2 Zone Controller 0422 ZC-3 3 Zone Controller 0423

More information

PS 289 DUAL CHANNEL POWER SUPPLY USER MANUAL

PS 289 DUAL CHANNEL POWER SUPPLY USER MANUAL PS 289 DUAL CHANNEL POWER SUPPLY USER MANUAL August 2016 This product is designed and manufactured by: ASL Intercom B.V. Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax: + 31

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual APC 2X Series Hardwire Products PMP2X-A PMF2X-A PMG2X-A PMH2X-A APC hardwired products are designed to provide specification-grade performance at the service entrance,

More information

Rapid Shutdown Requirements for NEC 2017

Rapid Shutdown Requirements for NEC 2017 2017 AEESOLAR DEALER CONF. Rapid Shutdown Requirements for NEC 2017 Presented by: Bill Brooks, CMP 4 2017 NEC Statistics for Article 690 Whole article was reduced from 11,000 words to about 8,000 words.

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

The Leviton Load Center THE FUTURE MADE CURRENT

The Leviton Load Center THE FUTURE MADE CURRENT The Leviton Load Center THE FUTURE MADE CURRENT Raising the Bar Again For over 110 years, Leviton has cultivated a rich tradition of safety and innovation, developing electrical products that set the

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D. Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various

More information

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

OPERATIONS MANUAL. n.form I/O Expander (RACK MOUNT) Document Number: Rev B

OPERATIONS MANUAL. n.form I/O Expander (RACK MOUNT) Document Number: Rev B OPERATIONS MANUAL n.form I/O Expander (RACK MOUNT) Document Number: 200-0009 Rev B table of contents INTRODUCTION FEATURES & CAPABILITIES 1 WIRING General I/O Configuring The System Using The System 4

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN This Inspection Checklist for Rooftop Photovoltaic (PV) Systems is based on the Model Inspection Checklist

More information

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT 26 05 73 POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT Delete the following current section in its entirety (deletions are shown struck through)..01 General A. Short circuit Studies,

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B SURGE PROTECTION PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) USER MANUAL Surge Protection Device B 01 156 9000 This Surge Protection Device is intended for professional use only Read this

More information

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment

More information

hp uninterruptible power system r12000 xr models installation instructions

hp uninterruptible power system r12000 xr models installation instructions hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer

More information

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to

More information

The Leviton Load Center THE FUTURE MADE CURRENT

The Leviton Load Center THE FUTURE MADE CURRENT The Leviton Load Center THE FUTURE MADE CURRENT Raising the Bar Again For over 110 years, Leviton has cultivated a rich tradition of safety and innovation, developing electrical products that set the

More information

GE Digital Energy. Power Quality

GE Digital Energy. Power Quality GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Wall Mounted Medium and High Exposure Surge Protective Devices (SPDs)

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

SureTest Model ST 1D Instructions

SureTest Model ST 1D Instructions #61-152 #61-153 SureTest Model ST 1D Instructions Introduction The SureTest family of circuit analyzers identify problems common to electrical circuits quickly, easily and accurately. They have a patented

More information