1 UPS Topologies - Project Performance Comparisons Rowan Peck, NDY r.peck@ndy.com
2 Overview Let s explore UPS solutions: Plant cost Quantity of redundant plant Building cost TCO energy, water, maintenance Which UPS topology best suits your project? Why?
3 Typical UPS topologies: N+1 parallel UPS 500kW UPS 500kW UPS 500kW UPS 1000 kw IT Load
4 Typical UPS topologies: 1+1 or N+N UPS 1000 kw IT Load
5 Typical UPS topologies: Group-redundant system n out of n+1 Static Switch selection from non-parallel UPS
6 Typical UPS topologies: Block Redundant system one redundant unit backs up n non-parallel others
7 Dependability: = Availability + Reliability.. + Maintainability + Safety What does this mean to your UPS topology choices?
8 Availability & Reliability: Technology selection lifetime performance Failure time - history & theory (MTBF) Repair time - history & theory (MTTR) Reduce / eliminate single points of failure Reduce common failure modes (esp. controls)
9 Availability & Reliability: Coverage what needs to be supported by UPS?
10 Maintainability & Safety: What are the risks and complexity in: Day to day operations? Upgrade of plant for load growth?
11 Maintainability & Safety: What are the risks and complexity in: Failure mode operations? Replacement of plant? Planned After major failure
12 About Parallel vs. Non-parallel UPS : Non-parallel preferred: For systems that are to be upgraded later Not locked in to any model or manufacturer Original kit can remain to its end of useful life Reduce common-mode failure points = higher dependability
13 Lifecycle costs: What makes up the CAPEX cost of the UPS system? UPS plant, energy storage, switchgear Downstream distribution to load
14 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? The building indoor and outdoor fire services lighting security etc
15 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? Upstream power and switchgear normal and standby HV, LV transformers generators
16 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? Cooling plant Chillers pumps piping fans controls
17 Lifecycle costs: What makes up the OPEX cost of the UPS system?
18 Lifecycle costs: What makes up the OPEX cost of the UPS system?
19 Lifecycle costs: What makes up the OPEX cost of the UPS system?
20 Lifecycle costs: What makes up the OPEX cost of the UPS system?
21 Lifecycle costs: What makes up the OPEX cost of the UPS system?
22 Lifecycle costs: What makes up the OPEX cost of the UPS system?
23 Lifecycle costs: What ELSE makes up the OPEX cost of the UPS system?
24 Lifecycle costs: What ELSE makes up the OPEX cost of the UPS system?
25 Some Available UPS Technologies: Static Double Conversion Rotary (Hybrid) UPS Static Delta Conversion Dynamic Diesel UPS Offline UPS CAPEX differs OPEX differs
26 Energy Storage solutions: VRLA or Lead Acid (wet) Batteries Minutes or hours of backup time selected based on standby power scheme Limited life in service high refresh cost
27 Energy Storage solutions: Flywheel Seconds of backup time Requires standby power quick-start Extended life in service Not well suited to parallel generators
28 Energy Storage solutions: What about cooling? Ride through on cooling a requirement with high density loads Seconds available to restart and cool if conditions are to be maintained
29 Project Comparison Sample project requirements: 1000kW IT Load per module Critical cooling to operate during mains failure New Build
30 N+1 Static UPS
31 N+1 Static UPS - Space
32 N+N Static UPS
33 N+N Static UPS - Space
34 N+1 Rotary UPS k W U P S 1000 kw IT Load
35 N+1 Rotary UPS - Space
36 N+1 DRUPS All Load Schematic:
37 N+1 DRUPS All Load External BYPASS (Emergency / Maintenance) Mains G G G M ALL Load Normal Power Path: Coupling Choke Isolation Uniblock-machine supplies the load Long-Term Backup Power Source: Active redundancy Coupled Standby Generator via 2 * rectifier, 2 * inverter Dynamic Energy storage Short-Term Backup Power Source: M/G + min. 10 sec Flywheel Base Diagram courtesy of Piller
38 N+1 DRUPS All Load Schematic IT Load Power: From Primary UPS From Redundant UPS IT Load in two halves Capacity to each half is 550kW (800A Static Switch)
39 N+1 DRUPS All Load
40 N+1 DRUPS All Load - Space
41 Summary Comparison Option Capex Opex (pa) NPV (1) MTBF N+1 Static UPS $5.4M $550k $33M 1.3M hrs N+N Static UPS $6.3M $690k $29M 1.4M hrs N+N Delta UPS $5.9M $550k $29M 1.4M hrs N+1 Rotary UPS $5.9M $460k $30M 6.7M hrs N+1 DRUPS All Load $7M $410k $30M 23M hrs Note 1: NPV against an assumed revenue stream for the IT space supported
42 Conclusions What counts is the BIG picture UPS technology is a PART of the picture TCO includes all the parts Which UPS topology best suits your project? Why?
43 Discussion For more information and a slide pack incl. reference UPS schematics: Rowan Peck
3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationThe Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power. Alex Emms Operations Director
The Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power Alex Emms Operations Director Less UPS Drivers More UPS Drivers UPS Datacentre Drivers/Trends Datacentres =
More informationModularity in UPS Design What does it Mean, What are the Pro s and Con s?
Modularity in UPS Design What does it Mean, What are the Pro s and Con s? Mike Elms Technical Manager Uninterruptible Power Supplies Ltd www.upspower.co.uk Modularity in UPS Design What does it Mean, What
More informationMid-Sized Data Center UPS Solutions Overview
Mid-Sized Data Center UPS Solutions Overview 2008 2008 Eaton Eaton Corporation. Corporation. All All rights rights reserved. reserved. Mid-Range System Concerns IT / ENGINEERS / BUYERS Cooling Designs
More informationModular and Scalable Power Converters in the UPS Industry
A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationNewave s approach for protecting mission critical application
ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment
More informationZero downtime for mission critical applications? Absolutely.
Pierre-Alain Gubelmann, ABB Power Protection, Giornadas Tecnicas, Santiago de Chile, 11-12 Abril 2017 Zero downtime for mission critical applications? Absolutely. 2017-04-18 Slide 1 The Benefits of Modular
More informationKeor HPE UPS THREE-PHASE UPS. from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
Keor HPE UPS THREE-PHASE UPS from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES LEGRAND UPS SERVICE continuity ENERGY efficiency SUPERIOR PERFORMANCES Legrand, world
More informationSTATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016
STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS
More informationANSI/BICSI Data Center Design and Implementation Best Practices
ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Vice Chair BICSI Mainland Europe
More informationHow green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary.
How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter Summary Diesel Rotary UPS (DRUPS) systems are best in class regarding energy
More informationDistributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
Distributed by Keor T UPS THREE-PHASE UPS from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES T THREE-PHASE UPS T has been designed with advanced technologies and the
More informationANSI/BICSI Data Center Design and Implementation Best Practices
ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Secretary BICSI Mainland Europe
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationRotabloc Diesel Rotary UPS Systems
Rotabloc Diesel Rotary UPS Systems Simply Reliable Solutions for Continuous Data Center Power IEM Power Systems Rotary UPS is a fully integrated system comprising the RBT UPS Module, Engine Genset, Switchgear,
More informationCurrent Trends in UPS Technology. Voltages
Voltages 1 Voltages 3-ph, 4 W, 120/208V classification for small and mid range sizes 3-ph, 480V classification is typical in larger capacity UPS Systems 3-ph, 4 W, 230/400V becoming more widely used in
More informationRotabloc Diesel Rotary UPS Systems
Rotabloc Diesel Rotary UPS Systems Simply Reliable Solutions for Continuous Data Center Power IEM Power Systems Rotary UPS is a fully integrated system comprising the RBT UPS Module, Engine Genset, Switchgear,
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More information5.2 MW, Pod-based build, Chilled Water, ft 2
[Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationTel: Mobile: Tel: Fax:
Tel: Mobile: Tel: Fax: Introduction Diesel Generating Solutions 6kVA - 3.3MVA Turnkey Power Generation Solutions IPE offers complete power generation solutions alongside JCB broadcrown s world class range
More informationHigh Performance Computing (HPC) Data Center Proposal
High Performance Computing (HPC) Data Center Proposal Imran Latif, Facility Project Manager Scientific & Enterprise Computing Data Centers at BNL 10/14/2015 Quick Facts!! Located on 1 st floor in Building
More informationKeor HPE UPS. THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
Keor HPE UPS THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES LEGRAND UPS SERVICE continuity ENERGY efficiency SUPERIOR PERFORMANCES Legrand, world
More information200 kw, Tier 3, Chilled Water, 5250 ft 2
[eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 100kW 3MW
PRODUCT BROCHURE Conceptpower DPA 500 480V UL Modular UPS 100kW 3MW 2 C O N C E P T P O W E R D PA 5 0 0 4 8 0 V M O D U L A R U P S Today s data centers require continuous uptime. That target is why ABB
More information2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.
[Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL
More informationPowerWAVE 9250DPA. ( N+1 kva/kw) Parallelable up to 1.5 MVA/MW
PowerWAVE 9250DPA (50 250 N+1 kva/kw) Parallelable up to 1.5 MVA/MW True modular UPS for medium power applications in critical, high-density computing environments such as small to medium-sized data centres,
More informationAvoiding the effect of severe component failures on UPS availability for business continuity and security
Avoiding the effect of severe component failures on UPS availability for business continuity and security Enrico Simoni, Borri Chief Technical Officer DCW London, 13-03-2019 Summary Doing all the work:
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More information9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2
[Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and
More informationHitec QPS product range
Hitec QPS product range Continuous Power Uninterrupted Power Quality Power Highest No-Break UPS Ratings Exceptional Power Density Modular Design Approach Best End-to-End Efficiency Optimized Availability
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationEst FlexiPower Ultra UPS FPX Ultra kVA
Est.1968 FlexiPower Ultra UPS FPX Ultra 500 1000kVA Prepared by Thycon Industrial Pty Ltd. The Thycon FlexiPower Ultra boasts the lowest cost of ownership of any UPS system by offering energy efficiency,
More informationEaton 93PM: Value, Benefits, and Features Eaton. All Rights Reserved..
Eaton 93PM: Value, Benefits, and Features 93PM value proposition The Eaton 93PM UPS combines unprecedented efficiency, reliability and vertical or horizontal scalability with eyecatching design. A space-saving,
More informationTel: AC Power for Business-Critical Continuity TM
Tel: +852-2690-4118 AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across your enterprise
More informationEst FlexiPower Maxi UPS FPX Maxi kVA
Est.1968 FlexiPower Maxi UPS FPX Maxi 50 250kVA True modular UPS system for critical applications Designed and Published by Thycon. A UPS DESIGNED TO MEET THE NEEDS OF TODAY AND TOMORROW The FlexiPower
More informationSyska Criticality Levels
Appendix C Syska Criticality Levels SYSKA CRITICALITY LEVEL TM DEFINITIONS Syska Hennessy Group Critical Facilities are designed and constructed on a scale of 1 10, 10 being the ultimate in criticality.
More informationIXcellerate Moscow One Datacentre - Phase 1 & 2 Overview
Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering
More information2016 IEEE / MCPG meetings cycle,
2016 IEEE / MCPG meetings cycle, Kameel Andrawos Director, Power Systems Schneider Electric Nashville, TN UPS Topologies UPS Construction Modular construction Traditional with plug-in assemblies UPS Configuration
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012
ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012 Robert (RJ) Meyers Data Center Products Lead ENERGY STAR Program US Environmental Protection Agency 1 Overview Main
More informationModular three-phase UPS system. Conceptpower DPA kva True modular UPS system for critical applications
Modular three-phase UPS system Conceptpower DPA 10 250 kva True modular UPS system for critical applications A UPS designed to meet the needs of today and tomorrow The Conceptpower DPA is a high-power,
More informationOptimized MV Generator Power Plant Architectures for Large Data Centers
Optimized MV Generator Power Plant Architectures for Large Data Centers White Paper 262 Revision 0 by Julien Moreau Malik Megdiche Daniel Radu Executive summary For large (>5 MW) data center applications,
More informationGalaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups
Galaxy VX Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 to 1500
More informationCapacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.
Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment
More informationThe Power of Modularity
Protectplus M600 The Power of Modularity to protect critical applications Protectplus M600 Flexible, scalable and smart It s our business to make your power security easy UPS systems from AEG Power Solutions
More informationData Center Facility Project. Robert Bunger Schneider Electric
Data Center Facility Project Analysis of Data Center Electrical Architectures Supporting OCP Robert Bunger Schneider Electric Critical questions arise about what is upstream of the rack If I adopt Open
More information30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015)
30 th September 2015 Glenn Conlon Always Right Size Modular Data Centres Traditional DC Build: Image courtesy of ENP Traditional DC: IRO 20 million + @ T2/3 Image courtesy of ENP DC Halls x 2, 500 Cabinets
More informationEaton 93PM UPS kw
Eaton 93PM UPS 30 200 kw Class-leading energy efficiency with minimal operating cost August 2013 2013 Eaton. All rights reserved. Eaton 93PM UPS Content Introduction to Eaton 93PM Overview Lowest Total
More informationCalculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationthe Centric 300 An advanced modular UPS up to 1800kVA/kW
the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has
More informationContinuous power. Digital static transfer switches for increased data center reliability
Digital static transfer switches for increased data center reliability CHRISTOPHER BELCASTRO, HANS PFITZER The information flowing through data centers is, in many cases, essential to the smooth running
More informationLiebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM
Liebert NXr Series 30kVA to 160kVA AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across
More informationGalaxy VX. From 500 kw to1500 kw N+1 Parallel solutions up to 4000 kw 480 V. schneider-electric.com
Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 kw to1500 kw N+1
More informationOTC 2010 X-pert Center
OTC 2010 X-pert Center Retrofit Solutions Stig Olav Settemsdal Product Manger Drilling Segment What can Siemens offer of retrofit? AC / DC Drilling systems Jacking Systems New Ex-D Water-cooled AC Drilling
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches
More informationMission Critical Power Review
Mission Critical Power Review Understanding concepts of mission critical power designs Chris Loeffler, ChrisALoeffler@Eaton.com Ed Spears, EdSpears@Eaton.com Power Quality Global HQ, Raleigh, NC Did you
More information02 Why Does My IT Infrastructure Need a UPS?
UPS Buyer s Guide TABLE OF CONTENTS 01 What is a UPS? 02 Why Does My IT Infrastructure Need a UPS? 03 Common Features of UPS Systems ENERGY STORAGE SYSTEMS BATTERIES POWER PROTECTION MONITORING SOLUTIONS
More informationQuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired
Overview The HP Performance-Optimized Data Center (HP POD) is a containerized datacenter equipped with power infrastructure, cooling and IT power distribution. The HP POD can be deployed within weeks instead
More information1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA
The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance
More informationUPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications
INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,
More informationFlexible & Scalable 48V Solutions Powering Tomorrow s Data Centers. Sean Gold Maxim Integrated 3/9/2017
Flexible & Scalable 48V Solutions Powering Tomorrow s Data Centers Sean Gold Maxim Integrated 3/9/2017 Rack Architectures are Changing from 12V to 48V Why a New Rack Power Architecture is Needed Data Centers
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW
PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120
More informationCritical Facilities Round Table. How to Effectively Update your Data Center Facilities. Peter Gross, PE EYP Mission Critical Facilities, Inc.
Critical Facilities Round Table How to Effectively Update your Data Center Facilities Peter Gross, PE EYP Mission Critical Facilities, Inc. 10-16-03 2003 EYP Mission Critical Facilities, Inc. Why upgrade?
More informationT66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management
T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell
More informationZenith Series STS-3 Static Transfer Switches
GE Energy Connections Zenith Series STS-3 Static Transfer Switches 60Hz UL Version, 150-1600AMP Seamless Input Source Transfers for Sensitive Critical Loads. Touching all Areas of the Energy Industry GE
More informationComprehensive Energy Management & Utility Master Plan
Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach
More informationProduct brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW
Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationOptimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.
Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationPRODUCT FEATURES AND ADVANTAGES
Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been
More informationIntegralna rešenja Infrastrukture Data Centra
1 2 Integralna rešenja Infrastrukture Data Centra Jason Dodier, Solutions Business Development Manager - Global Sales (Schneider Electric) Overview of Prefabricated DC's market Prefab - needs to be satisfied
More informationbrightsolid Data Hall 1 Keysource Technical Specifications
brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements
More informationENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER
smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS
More informationLIBRA pro. UPS kva three-phase / single-phase kva three-phase / three-phase. online
LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL DEVICES SERVERS INDUSTRIAL PLCS
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationGAMATRONIC, A SolarEdge Division.
GAMATRONIC, A SolarEdge Division. 17 Hartum Street, POB 45029, Jerusalem 9777517,Israel Tel: +972-2-5888222 Fax: +972-2-5828875 e-mail: info@gamatronic.com www.gamatronic.com The Power+ Premium 60 is
More informationProtected Power Supply for your Applications. Telecom Industrial Data Center
Protected Power Supply for your Applications Telecom Industrial Data Center The future is here. ELTEK Deutschland- Your partner for highly efficient power systems and services When it comes to power conversion
More informationSMMS i Selection Tool
Presentation Reference TP10-Vi04-01 1 Technical Training For... SMMS i Selection Tool EMEA Training 2010 2 SMMS-i Selection Tool Overview Two methods of System Design Wizard Based Selection Drag-&-Drop
More informationMake the most of your Energy from Power Plant to Plug. Chris Simard, Regional Director Field Sales Group
Make the most of your Energy from Power Plant to Plug Chris Simard, Regional Director Field Sales Group We see six key challenges facing our world Connectivity Simplicity Globalization Demand For Energy
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationSmoothAir Modular Precision Cooling
TM SmoothAir Modular Precision Cooling ODM/OEM/Customization+ Specialist Support+ Modular Precision Cooling for Smart, Reliable and Green MDC Solution Why Choose Us Products Support Customization Products
More information1008 kw, Tier 2, Chilled Water, ft 2
[eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65
More informationPowerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)
Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL
More informationWiegand DataCenters * The next Generation of Data Centers
Wiegand DataCenters * DataCenters * WIEGAND DataCenter * Generation of Green Datacenters! * Power Density * Energy Efficiency * Hardware Flexibility * High Security Standards * Infrastructure Redundancy
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationEnergy Efficiency : Green Telecom
http://eustandards.in/ Energy Efficiency : Green Telecom Flattening total energy while catering to 1000x more data Amit Marwah, Head of Technology, NSN, India Region 2 Our vision: Mobile networks are able
More informationEFASOLAR PVStation Solutions
www.efacec.com EFASOLAR PVStation Solutions EFASOLAR PVStation EFASOLAR PVStation Solutions 0,5 MW 1 x EFASOLAR 50 0,50 MW 1 x EFASOLAR 500M 1 MW 1,46 MW Efacec is a century-long experienced company in
More informationPowerWAVE 9500DPA. ( kva/kw) Parallelable up to 3 MVA/MW
PowerWAVE 9500DPA (100 500 kva/kw) Parallelable up to 3 MVA/MW 500 kva/kw modular UPS, designed with high effciency and maximum flexibility at its core. Total vertical and horizontal scalability using
More informationCenturyLink Data Center Services Omaha, Nebraska
CenturyLink Data Center Services Omaha, Nebraska HIGH AVAILABILITY ENTERPRISE COMPUTING Designed and equipped to meet the demands of enterprises, wholesale businesses and government agencies, CenturyLink
More informationGSI three-phases series off-grid Inverter User s Manual
GSI three-phases series off-grid Inverter User s Manual CATALOGUE 1. PRODUCT INSTRUCTION...2 2.OPERATION REQUIREMENT. 3 3. ATTENTIONS..3 4. WORKING PRINCIPLE 4 5. FRONT PANEL INSTRUCTION..6 6. INSTALLATION.7
More informationSymmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers
Modular, Scalable, High-Efficiency Power Protection for Data Centers Symmetra PX 48kW Scalable from 16kW to 48kW > High Performance, Right-Sized 3-Phase Power Protection with Industry-Leading Efficiency,
More informationE f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n
E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter
More informationLiebert NX - Next Generation UPS for protecting your Business Critical Systems. AC Power Systems for Business-Critical Continuity
- Next Generation UPS for protecting your Business Critical Systems AC Power Systems for Business-Critical Continuity Advanced UPS Technology Protects Modern IT Equipment Today s advanced digital computing,
More informationCritical Power from GE. TLE Series UPS. TLE30-40 & TLE kva/kw Scalable three phase 400 Vac
Critical Power from GE TLE Series UPS TLE30-40 & TLE40-120 kva/kw Scalable three phase 400 Vac GE provides clean, efficient and reliable power for today s world with the high efficiency TLE Series UPS
More informationBusiness Case Studies with STEM
ITU-D/ ITU-T T Seminar on Standardization and Development of Next Generation Networks for the Arab Region 29 April 2 May 2007, Manama, Barhain with STEM Oscar González Soto ITU Consultant Expert Strategic
More information