1 UPS Topologies - Project Performance Comparisons Rowan Peck, NDY r.peck@ndy.com

2 Overview Let s explore UPS solutions: Plant cost Quantity of redundant plant Building cost TCO energy, water, maintenance Which UPS topology best suits your project? Why?

3 Typical UPS topologies: N+1 parallel UPS 500kW UPS 500kW UPS 500kW UPS 1000 kw IT Load

4 Typical UPS topologies: 1+1 or N+N UPS 1000 kw IT Load

5 Typical UPS topologies: Group-redundant system n out of n+1 Static Switch selection from non-parallel UPS

6 Typical UPS topologies: Block Redundant system one redundant unit backs up n non-parallel others

7 Dependability: = Availability + Reliability.. + Maintainability + Safety What does this mean to your UPS topology choices?

8 Availability & Reliability: Technology selection lifetime performance Failure time - history & theory (MTBF) Repair time - history & theory (MTTR) Reduce / eliminate single points of failure Reduce common failure modes (esp. controls)

9 Availability & Reliability: Coverage what needs to be supported by UPS?

10 Maintainability & Safety: What are the risks and complexity in: Day to day operations? Upgrade of plant for load growth?

11 Maintainability & Safety: What are the risks and complexity in: Failure mode operations? Replacement of plant? Planned After major failure

12 About Parallel vs. Non-parallel UPS : Non-parallel preferred: For systems that are to be upgraded later Not locked in to any model or manufacturer Original kit can remain to its end of useful life Reduce common-mode failure points = higher dependability

13 Lifecycle costs: What makes up the CAPEX cost of the UPS system? UPS plant, energy storage, switchgear Downstream distribution to load

14 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? The building indoor and outdoor fire services lighting security etc

15 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? Upstream power and switchgear normal and standby HV, LV transformers generators

16 Lifecycle costs: What ELSE makes up the CAPEX cost of the UPS system? Cooling plant Chillers pumps piping fans controls

17 Lifecycle costs: What makes up the OPEX cost of the UPS system?

18 Lifecycle costs: What makes up the OPEX cost of the UPS system?

19 Lifecycle costs: What makes up the OPEX cost of the UPS system?

20 Lifecycle costs: What makes up the OPEX cost of the UPS system?

21 Lifecycle costs: What makes up the OPEX cost of the UPS system?

22 Lifecycle costs: What makes up the OPEX cost of the UPS system?

23 Lifecycle costs: What ELSE makes up the OPEX cost of the UPS system?

24 Lifecycle costs: What ELSE makes up the OPEX cost of the UPS system?

25 Some Available UPS Technologies: Static Double Conversion Rotary (Hybrid) UPS Static Delta Conversion Dynamic Diesel UPS Offline UPS CAPEX differs OPEX differs

26 Energy Storage solutions: VRLA or Lead Acid (wet) Batteries Minutes or hours of backup time selected based on standby power scheme Limited life in service high refresh cost

27 Energy Storage solutions: Flywheel Seconds of backup time Requires standby power quick-start Extended life in service Not well suited to parallel generators

28 Energy Storage solutions: What about cooling? Ride through on cooling a requirement with high density loads Seconds available to restart and cool if conditions are to be maintained

29 Project Comparison Sample project requirements: 1000kW IT Load per module Critical cooling to operate during mains failure New Build

30 N+1 Static UPS

31 N+1 Static UPS - Space

32 N+N Static UPS

33 N+N Static UPS - Space

34 N+1 Rotary UPS k W U P S 1000 kw IT Load

35 N+1 Rotary UPS - Space

36 N+1 DRUPS All Load Schematic:

37 N+1 DRUPS All Load External BYPASS (Emergency / Maintenance) Mains G G G M ALL Load Normal Power Path: Coupling Choke Isolation Uniblock-machine supplies the load Long-Term Backup Power Source: Active redundancy Coupled Standby Generator via 2 * rectifier, 2 * inverter Dynamic Energy storage Short-Term Backup Power Source: M/G + min. 10 sec Flywheel Base Diagram courtesy of Piller

38 N+1 DRUPS All Load Schematic IT Load Power: From Primary UPS From Redundant UPS IT Load in two halves Capacity to each half is 550kW (800A Static Switch)

39 N+1 DRUPS All Load

40 N+1 DRUPS All Load - Space

41 Summary Comparison Option Capex Opex (pa) NPV (1) MTBF N+1 Static UPS $5.4M $550k $33M 1.3M hrs N+N Static UPS $6.3M $690k $29M 1.4M hrs N+N Delta UPS $5.9M $550k $29M 1.4M hrs N+1 Rotary UPS $5.9M $460k $30M 6.7M hrs N+1 DRUPS All Load $7M $410k $30M 23M hrs Note 1: NPV against an assumed revenue stream for the IT space supported

42 Conclusions What counts is the BIG picture UPS technology is a PART of the picture TCO includes all the parts Which UPS topology best suits your project? Why?

43 Discussion For more information and a slide pack incl. reference UPS schematics: Rowan Peck

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

The Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power. Alex Emms Operations Director

The Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power. Alex Emms Operations Director The Modular UPS and Lithium-Ion Battery Combo - Raising the bar for Datacentre Critical Power Alex Emms Operations Director Less UPS Drivers More UPS Drivers UPS Datacentre Drivers/Trends Datacentres =

More information

Modularity in UPS Design What does it Mean, What are the Pro s and Con s?

Modularity in UPS Design What does it Mean, What are the Pro s and Con s? Modularity in UPS Design What does it Mean, What are the Pro s and Con s? Mike Elms Technical Manager Uninterruptible Power Supplies Ltd www.upspower.co.uk Modularity in UPS Design What does it Mean, What

More information

Mid-Sized Data Center UPS Solutions Overview

Mid-Sized Data Center UPS Solutions Overview Mid-Sized Data Center UPS Solutions Overview 2008 2008 Eaton Eaton Corporation. Corporation. All All rights rights reserved. reserved. Mid-Range System Concerns IT / ENGINEERS / BUYERS Cooling Designs

More information

Modular and Scalable Power Converters in the UPS Industry

Modular and Scalable Power Converters in the UPS Industry A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric

More information

Compute Engineering Workshop March 9, 2015 San Jose

Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud

More information

Newave s approach for protecting mission critical application

Newave s approach for protecting mission critical application ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment

More information

Zero downtime for mission critical applications? Absolutely.

Zero downtime for mission critical applications? Absolutely. Pierre-Alain Gubelmann, ABB Power Protection, Giornadas Tecnicas, Santiago de Chile, 11-12 Abril 2017 Zero downtime for mission critical applications? Absolutely. 2017-04-18 Slide 1 The Benefits of Modular

More information

Keor HPE UPS THREE-PHASE UPS. from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Keor HPE UPS THREE-PHASE UPS. from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Keor HPE UPS THREE-PHASE UPS from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES LEGRAND UPS SERVICE continuity ENERGY efficiency SUPERIOR PERFORMANCES Legrand, world

More information

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016 STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS

More information

ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/BICSI Data Center Design and Implementation Best Practices ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Vice Chair BICSI Mainland Europe

More information

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary.

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary. How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter Summary Diesel Rotary UPS (DRUPS) systems are best in class regarding energy

More information

Distributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Distributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Distributed by Keor T UPS THREE-PHASE UPS from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES T THREE-PHASE UPS T has been designed with advanced technologies and the

More information

ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/BICSI Data Center Design and Implementation Best Practices ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Secretary BICSI Mainland Europe

More information

CPS VS UPS FOR POWERING DATA CENTERS

CPS VS UPS FOR POWERING DATA CENTERS CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Rotabloc Diesel Rotary UPS Systems

Rotabloc Diesel Rotary UPS Systems Rotabloc Diesel Rotary UPS Systems Simply Reliable Solutions for Continuous Data Center Power IEM Power Systems Rotary UPS is a fully integrated system comprising the RBT UPS Module, Engine Genset, Switchgear,

More information

Current Trends in UPS Technology. Voltages

Current Trends in UPS Technology. Voltages Voltages 1 Voltages 3-ph, 4 W, 120/208V classification for small and mid range sizes 3-ph, 480V classification is typical in larger capacity UPS Systems 3-ph, 4 W, 230/400V becoming more widely used in

More information

Rotabloc Diesel Rotary UPS Systems

Rotabloc Diesel Rotary UPS Systems Rotabloc Diesel Rotary UPS Systems Simply Reliable Solutions for Continuous Data Center Power IEM Power Systems Rotary UPS is a fully integrated system comprising the RBT UPS Module, Engine Genset, Switchgear,

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Tel: Mobile: Tel: Fax:

Tel: Mobile: Tel: Fax: Tel: Mobile: Tel: Fax: Introduction Diesel Generating Solutions 6kVA - 3.3MVA Turnkey Power Generation Solutions IPE offers complete power generation solutions alongside JCB broadcrown s world class range

More information

High Performance Computing (HPC) Data Center Proposal

High Performance Computing (HPC) Data Center Proposal High Performance Computing (HPC) Data Center Proposal Imran Latif, Facility Project Manager Scientific & Enterprise Computing Data Centers at BNL 10/14/2015 Quick Facts!! Located on 1 st floor in Building

More information

Keor HPE UPS. THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Keor HPE UPS. THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Keor HPE UPS THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES LEGRAND UPS SERVICE continuity ENERGY efficiency SUPERIOR PERFORMANCES Legrand, world

More information

200 kw, Tier 3, Chilled Water, 5250 ft 2

200 kw, Tier 3, Chilled Water, 5250 ft 2 [eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,

More information

PRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 100kW 3MW

PRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 100kW 3MW PRODUCT BROCHURE Conceptpower DPA 500 480V UL Modular UPS 100kW 3MW 2 C O N C E P T P O W E R D PA 5 0 0 4 8 0 V M O D U L A R U P S Today s data centers require continuous uptime. That target is why ABB

More information

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft. [Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL

More information

PowerWAVE 9250DPA. ( N+1 kva/kw) Parallelable up to 1.5 MVA/MW

PowerWAVE 9250DPA. ( N+1 kva/kw) Parallelable up to 1.5 MVA/MW PowerWAVE 9250DPA (50 250 N+1 kva/kw) Parallelable up to 1.5 MVA/MW True modular UPS for medium power applications in critical, high-density computing environments such as small to medium-sized data centres,

More information

Avoiding the effect of severe component failures on UPS availability for business continuity and security

Avoiding the effect of severe component failures on UPS availability for business continuity and security Avoiding the effect of severe component failures on UPS availability for business continuity and security Enrico Simoni, Borri Chief Technical Officer DCW London, 13-03-2019 Summary Doing all the work:

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

Hitec QPS product range

Hitec QPS product range Hitec QPS product range Continuous Power Uninterrupted Power Quality Power Highest No-Break UPS Ratings Exceptional Power Density Modular Design Approach Best End-to-End Efficiency Optimized Availability

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Est FlexiPower Ultra UPS FPX Ultra kVA

Est FlexiPower Ultra UPS FPX Ultra kVA Est.1968 FlexiPower Ultra UPS FPX Ultra 500 1000kVA Prepared by Thycon Industrial Pty Ltd. The Thycon FlexiPower Ultra boasts the lowest cost of ownership of any UPS system by offering energy efficiency,

More information

Eaton 93PM: Value, Benefits, and Features Eaton. All Rights Reserved..

Eaton 93PM: Value, Benefits, and Features Eaton. All Rights Reserved.. Eaton 93PM: Value, Benefits, and Features 93PM value proposition The Eaton 93PM UPS combines unprecedented efficiency, reliability and vertical or horizontal scalability with eyecatching design. A space-saving,

More information

Tel: AC Power for Business-Critical Continuity TM

Tel: AC Power for Business-Critical Continuity TM Tel: +852-2690-4118 AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across your enterprise

More information

Est FlexiPower Maxi UPS FPX Maxi kVA

Est FlexiPower Maxi UPS FPX Maxi kVA Est.1968 FlexiPower Maxi UPS FPX Maxi 50 250kVA True modular UPS system for critical applications Designed and Published by Thycon. A UPS DESIGNED TO MEET THE NEEDS OF TODAY AND TOMORROW The FlexiPower

More information

Syska Criticality Levels

Syska Criticality Levels Appendix C Syska Criticality Levels SYSKA CRITICALITY LEVEL TM DEFINITIONS Syska Hennessy Group Critical Facilities are designed and constructed on a scale of 1 10, 10 being the ultimate in criticality.

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

2016 IEEE / MCPG meetings cycle,

2016 IEEE / MCPG meetings cycle, 2016 IEEE / MCPG meetings cycle, Kameel Andrawos Director, Power Systems Schneider Electric Nashville, TN UPS Topologies UPS Construction Modular construction Traditional with plug-in assemblies UPS Configuration

More information

Pros and Cons of Various DC Distribution Architectures

Pros and Cons of Various DC Distribution Architectures Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification

More information

ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012

ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012 ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012 Robert (RJ) Meyers Data Center Products Lead ENERGY STAR Program US Environmental Protection Agency 1 Overview Main

More information

Modular three-phase UPS system. Conceptpower DPA kva True modular UPS system for critical applications

Modular three-phase UPS system. Conceptpower DPA kva True modular UPS system for critical applications Modular three-phase UPS system Conceptpower DPA 10 250 kva True modular UPS system for critical applications A UPS designed to meet the needs of today and tomorrow The Conceptpower DPA is a high-power,

More information

Optimized MV Generator Power Plant Architectures for Large Data Centers

Optimized MV Generator Power Plant Architectures for Large Data Centers Optimized MV Generator Power Plant Architectures for Large Data Centers White Paper 262 Revision 0 by Julien Moreau Malik Megdiche Daniel Radu Executive summary For large (>5 MW) data center applications,

More information

Galaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups

Galaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups Galaxy VX Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 to 1500

More information

Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.

Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment

More information

The Power of Modularity

The Power of Modularity Protectplus M600 The Power of Modularity to protect critical applications Protectplus M600 Flexible, scalable and smart It s our business to make your power security easy UPS systems from AEG Power Solutions

More information

Data Center Facility Project. Robert Bunger Schneider Electric

Data Center Facility Project. Robert Bunger Schneider Electric Data Center Facility Project Analysis of Data Center Electrical Architectures Supporting OCP Robert Bunger Schneider Electric Critical questions arise about what is upstream of the rack If I adopt Open

More information

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015)

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015) 30 th September 2015 Glenn Conlon Always Right Size Modular Data Centres Traditional DC Build: Image courtesy of ENP Traditional DC: IRO 20 million + @ T2/3 Image courtesy of ENP DC Halls x 2, 500 Cabinets

More information

Eaton 93PM UPS kw

Eaton 93PM UPS kw Eaton 93PM UPS 30 200 kw Class-leading energy efficiency with minimal operating cost August 2013 2013 Eaton. All rights reserved. Eaton 93PM UPS Content Introduction to Eaton 93PM Overview Lowest Total

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

the Centric 300 An advanced modular UPS up to 1800kVA/kW

the Centric 300 An advanced modular UPS up to 1800kVA/kW the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has

More information

Continuous power. Digital static transfer switches for increased data center reliability

Continuous power. Digital static transfer switches for increased data center reliability Digital static transfer switches for increased data center reliability CHRISTOPHER BELCASTRO, HANS PFITZER The information flowing through data centers is, in many cases, essential to the smooth running

More information

Liebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM

Liebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM Liebert NXr Series 30kVA to 160kVA AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across

More information

Galaxy VX. From 500 kw to1500 kw N+1 Parallel solutions up to 4000 kw 480 V. schneider-electric.com

Galaxy VX. From 500 kw to1500 kw N+1 Parallel solutions up to 4000 kw 480 V. schneider-electric.com Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 kw to1500 kw N+1

More information

OTC 2010 X-pert Center

OTC 2010 X-pert Center OTC 2010 X-pert Center Retrofit Solutions Stig Olav Settemsdal Product Manger Drilling Segment What can Siemens offer of retrofit? AC / DC Drilling systems Jacking Systems New Ex-D Water-cooled AC Drilling

More information

Data Center Design: Power, Cooling & Management

Data Center Design: Power, Cooling & Management Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches

More information

Mission Critical Power Review

Mission Critical Power Review Mission Critical Power Review Understanding concepts of mission critical power designs Chris Loeffler, ChrisALoeffler@Eaton.com Ed Spears, EdSpears@Eaton.com Power Quality Global HQ, Raleigh, NC Did you

More information

02 Why Does My IT Infrastructure Need a UPS?

02 Why Does My IT Infrastructure Need a UPS? UPS Buyer s Guide TABLE OF CONTENTS 01 What is a UPS? 02 Why Does My IT Infrastructure Need a UPS? 03 Common Features of UPS Systems ENERGY STORAGE SYSTEMS BATTERIES POWER PROTECTION MONITORING SOLUTIONS

More information

QuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired

QuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired Overview The HP Performance-Optimized Data Center (HP POD) is a containerized datacenter equipped with power infrastructure, cooling and IT power distribution. The HP POD can be deployed within weeks instead

More information

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance

More information

UPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications

UPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,

More information

Flexible & Scalable 48V Solutions Powering Tomorrow s Data Centers. Sean Gold Maxim Integrated 3/9/2017

Flexible & Scalable 48V Solutions Powering Tomorrow s Data Centers. Sean Gold Maxim Integrated 3/9/2017 Flexible & Scalable 48V Solutions Powering Tomorrow s Data Centers Sean Gold Maxim Integrated 3/9/2017 Rack Architectures are Changing from 12V to 48V Why a New Rack Power Architecture is Needed Data Centers

More information

PRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW

PRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120

More information

Critical Facilities Round Table. How to Effectively Update your Data Center Facilities. Peter Gross, PE EYP Mission Critical Facilities, Inc.

Critical Facilities Round Table. How to Effectively Update your Data Center Facilities. Peter Gross, PE EYP Mission Critical Facilities, Inc. Critical Facilities Round Table How to Effectively Update your Data Center Facilities Peter Gross, PE EYP Mission Critical Facilities, Inc. 10-16-03 2003 EYP Mission Critical Facilities, Inc. Why upgrade?

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information

Zenith Series STS-3 Static Transfer Switches

Zenith Series STS-3 Static Transfer Switches GE Energy Connections Zenith Series STS-3 Static Transfer Switches 60Hz UL Version, 150-1600AMP Seamless Input Source Transfers for Sensitive Critical Loads. Touching all Areas of the Energy Industry GE

More information

Comprehensive Energy Management & Utility Master Plan

Comprehensive Energy Management & Utility Master Plan Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach

More information

Product brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW

Product brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS

More information

Highly Efficient Power Protection for High Density Computing Applications

Highly Efficient Power Protection for High Density Computing Applications Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density

More information

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc. Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

PRODUCT FEATURES AND ADVANTAGES

PRODUCT FEATURES AND ADVANTAGES Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been

More information

Integralna rešenja Infrastrukture Data Centra

Integralna rešenja Infrastrukture Data Centra 1 2 Integralna rešenja Infrastrukture Data Centra Jason Dodier, Solutions Business Development Manager - Global Sales (Schneider Electric) Overview of Prefabricated DC's market Prefab - needs to be satisfied

More information

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS

More information

LIBRA pro. UPS kva three-phase / single-phase kva three-phase / three-phase. online

LIBRA pro. UPS kva three-phase / single-phase kva three-phase / three-phase. online LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL DEVICES SERVERS INDUSTRIAL PLCS

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

GAMATRONIC, A SolarEdge Division.

GAMATRONIC, A SolarEdge Division. GAMATRONIC, A SolarEdge Division. 17 Hartum Street, POB 45029, Jerusalem 9777517,Israel Tel: +972-2-5888222 Fax: +972-2-5828875 e-mail: info@gamatronic.com www.gamatronic.com The Power+ Premium 60 is

More information

Protected Power Supply for your Applications. Telecom Industrial Data Center

Protected Power Supply for your Applications. Telecom Industrial Data Center Protected Power Supply for your Applications Telecom Industrial Data Center The future is here. ELTEK Deutschland- Your partner for highly efficient power systems and services When it comes to power conversion

More information

SMMS i Selection Tool

SMMS i Selection Tool Presentation Reference TP10-Vi04-01 1 Technical Training For... SMMS i Selection Tool EMEA Training 2010 2 SMMS-i Selection Tool Overview Two methods of System Design Wizard Based Selection Drag-&-Drop

More information

Make the most of your Energy from Power Plant to Plug. Chris Simard, Regional Director Field Sales Group

Make the most of your Energy from Power Plant to Plug. Chris Simard, Regional Director Field Sales Group Make the most of your Energy from Power Plant to Plug Chris Simard, Regional Director Field Sales Group We see six key challenges facing our world Connectivity Simplicity Globalization Demand For Energy

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

SmoothAir Modular Precision Cooling

SmoothAir Modular Precision Cooling TM SmoothAir Modular Precision Cooling ODM/OEM/Customization+ Specialist Support+ Modular Precision Cooling for Smart, Reliable and Green MDC Solution Why Choose Us Products Support Customization Products

More information

1008 kw, Tier 2, Chilled Water, ft 2

1008 kw, Tier 2, Chilled Water, ft 2 [eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65

More information

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL

More information

Wiegand DataCenters * The next Generation of Data Centers

Wiegand DataCenters * The next Generation of Data Centers Wiegand DataCenters * DataCenters * WIEGAND DataCenter * Generation of Green Datacenters! * Power Density * Energy Efficiency * Hardware Flexibility * High Security Standards * Infrastructure Redundancy

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Energy Efficiency : Green Telecom

Energy Efficiency : Green Telecom http://eustandards.in/ Energy Efficiency : Green Telecom Flattening total energy while catering to 1000x more data Amit Marwah, Head of Technology, NSN, India Region 2 Our vision: Mobile networks are able

More information

EFASOLAR PVStation Solutions

EFASOLAR PVStation Solutions www.efacec.com EFASOLAR PVStation Solutions EFASOLAR PVStation EFASOLAR PVStation Solutions 0,5 MW 1 x EFASOLAR 50 0,50 MW 1 x EFASOLAR 500M 1 MW 1,46 MW Efacec is a century-long experienced company in

More information

PowerWAVE 9500DPA. ( kva/kw) Parallelable up to 3 MVA/MW

PowerWAVE 9500DPA. ( kva/kw) Parallelable up to 3 MVA/MW PowerWAVE 9500DPA (100 500 kva/kw) Parallelable up to 3 MVA/MW 500 kva/kw modular UPS, designed with high effciency and maximum flexibility at its core. Total vertical and horizontal scalability using

More information

CenturyLink Data Center Services Omaha, Nebraska

CenturyLink Data Center Services Omaha, Nebraska CenturyLink Data Center Services Omaha, Nebraska HIGH AVAILABILITY ENTERPRISE COMPUTING Designed and equipped to meet the demands of enterprises, wholesale businesses and government agencies, CenturyLink

More information

GSI three-phases series off-grid Inverter User s Manual

GSI three-phases series off-grid Inverter User s Manual GSI three-phases series off-grid Inverter User s Manual CATALOGUE 1. PRODUCT INSTRUCTION...2 2.OPERATION REQUIREMENT. 3 3. ATTENTIONS..3 4. WORKING PRINCIPLE 4 5. FRONT PANEL INSTRUCTION..6 6. INSTALLATION.7

More information

Symmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers

Symmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers Modular, Scalable, High-Efficiency Power Protection for Data Centers Symmetra PX 48kW Scalable from 16kW to 48kW > High Performance, Right-Sized 3-Phase Power Protection with Industry-Leading Efficiency,

More information

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter

More information

Liebert NX - Next Generation UPS for protecting your Business Critical Systems. AC Power Systems for Business-Critical Continuity

Liebert NX - Next Generation UPS for protecting your Business Critical Systems. AC Power Systems for Business-Critical Continuity - Next Generation UPS for protecting your Business Critical Systems AC Power Systems for Business-Critical Continuity Advanced UPS Technology Protects Modern IT Equipment Today s advanced digital computing,

More information

Critical Power from GE. TLE Series UPS. TLE30-40 & TLE kva/kw Scalable three phase 400 Vac

Critical Power from GE. TLE Series UPS. TLE30-40 & TLE kva/kw Scalable three phase 400 Vac Critical Power from GE TLE Series UPS TLE30-40 & TLE40-120 kva/kw Scalable three phase 400 Vac GE provides clean, efficient and reliable power for today s world with the high efficiency TLE Series UPS

More information

Business Case Studies with STEM

Business Case Studies with STEM ITU-D/ ITU-T T Seminar on Standardization and Development of Next Generation Networks for the Arab Region 29 April 2 May 2007, Manama, Barhain with STEM Oscar González Soto ITU Consultant Expert Strategic

More information