STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016

Size: px
Start display at page:

Download "STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016"

Transcription

1 STATE DATA CENTER DRAFT PROPOSAL 1

2 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles

3 MEETING GOALS INFORMATION AND OUTCOMES 3 Review Existing Conditions Present New Equipment Basis of Design (B.O.D.) Examine Potential for Cost Savings Discuss Alternates/Options

4 EXISTING CONDITIONS MECHANICAL EQUIPMENT 4 Open draft cooling towers reject heat from water cooled chillers Pumps distribute chilled water to rooftop air handlers

5 EXISTING CONDITIONS MECHANICAL EQUIPMENT 5 Cooling Towers 2x 300 / 1x 100 Ton Pumps 3x 10 HP Chillers 2x 300 / 1x 100 Ton Primary 2x 5 HP Secondary 2x 10 HP Air Handlers Data Hall 7x 24K CFM Data Hall & Office 1x 25.9K CFM UPS & Switch Board Boiler 2x 10K CFM 1x 1084 MB

6 EXISTING CONDITIONS ELECTRICAL EQUIPMENT 6 Utility Transformer 2000 kva Existing MV Switch Generators 2x 1285kW Diesel N+1 Redundancy Paralleling Switchgear 5000A Rated N+1 Redundancy Normal Distribution 3000A - 480V Service UPS Data Hall (IT) 2x 675kW, 2N Redundancy House Loads PDU 1x 60kW 8x 150kVA (A+B) 2x 225kVA (A+B)

7 EXISTING CONDITIONS DATA HALL 7 Tier III Reliability Concurrent Maintainability No single points of failure (2) 675kW UPSs (10) PDUs Underfloor air distribution No hot/cold Aisle Containment

8 NEW WORK BACK OF HOUSE & YARD 8 Fuel Polisher (Alt) Transformer Cooling tower (10) PDUs Generator Switchgear 300 Ton Chiller Primary & Secondary Pumps (2) 675kw UPS + 60kw House UPS

9 NEW WORK CHILLER AND PUMPS 9

10 BASIS OF DESIGN CHILLERS 10 YORK YMC2-S1055AA 300 TON CAPACITY OPERATING WEIGHT 13,000 LBS

11 NEW WORK COOLING TOWER 11

12 BASIS OF DESIGN COOLING TOWER 12 EVAPCO 300 TON

13 NEW WORK GENERATOR 13

14 BASIS OF DESIGN GENERATOR 14 CATERPILLAR 3512C DIESEL GENERATOR PRIME RATED, CONTINUOUS DUTY, 1250kW

15 NEW WORK UPS & SWITCHGEAR 15

16 BASIS OF DESIGN DATA HALL UPS 16 Schneider Electric 750kW Internal & External Bypass, (+3) Storage Cabinets VRLA Batteries (7 Min) or Flywheel (10 Full Load

17 BASIS OF DESIGN HOUSE UPS 17 Schneider Electric 72kW Internal & External Bypass

18 BASIS OF DESIGN EXPLORING FLYWHEEL UPS TECHNOLOGY 18 Mag-Lev Bearings, no maintenance required Lower runtime vs Batteries Lower total cost of ownership

19 BASIS OF DESIGN NORMAL SWITCHGEAR A Main-Tie-Main, 480V/3P, 100kAIC

20 NEW WORK PDUs 20

21 BASIS OF DESIGN PDU 21 MGE PMM 150kVA Rated 480V Input, 208V Output 168 Output Branch Circuits (10) Total PDUs, 5 per UPS

22 NEW WORK TRANSFORMER 22

23 BASIS OF DESIGN TRANSFORMER 23 GE PROLEC 2500 KVA

24 NEW WORK ROOFTOP EQUIPMENT 24 (6) 24,000 CFM AHUs (1) 10,000 CFM AHU

25 BASIS OF DESIGN AIR HANDLER UNITS 25 Energy Labs Inc. - 24,000 CFM Serves Data Hall N + 1 Provided for each side (North & South) of the Data Center

26 BASIS OF DESIGN AIR HANDLER UNITS 26 Energy Labs Inc. - 10,000 CFM Serves UPS & Switch board rooms N + 1 for total Room Loads

27 NEW WORK MODIFICATIONS PIPING MODIFICATIONS (Alt) 27

28 NEW WORK MODIFICATIONS FUEL POLISHING (ALTERNATE) 28 Maintain Fuel Oil Quality Remove Water from System Remove microbes and other contaminants

29 NEW WORK MODIFICATIONS EPO SWITCH 29 Verify EPO functionality (NEC 645) EPO shall shutdown All power to IT Equipment in Data Hall (Cord & Plug) All power to HVAC serving Data Hall New equipment must tie into EPO Alternative is NEC Chapter 3 Wiring

30 POWER MONITORING 30 New equipment monitoring system and controls will communicate with BMS Generators Switchboards UPSs PDUs Fire Alarm Evaluate DAS concerns with existing monitoring system and upgrade as necessary

31 NEW WORK DATA HALL OPTIONS 31 Option 1: No improvements (Baseline) Option 2: Vented Chimneys (Alternate) Option 3: Containment (Alternate)

32 DATA HALL OPTION #1 NO IMPROVEMENTS 32 Keep existing distribution Inefficient ventilation & conditioning Cost rise with increased utilization

33 DATA Hall EXISTING PHOTO 33

34 DATA HALL OPTION #2 VENTED CHIMNEYS 34 Install chimneys on all servers Install insulated ducting to vent the chimneys Reduction in conditioning loads cost to overall space

35 DATA HALL OPTION #3 HOT/COLD AISLE CONTAINMENT 35 Create Hot/Cold aisles with new walls and ceiling Reconfigure ducting Significant reduction in operating cost and energy usage Increased energy efficiency and PUI CONTAINMENT

36 Energy Usage (kwh) STEWARDSHIP ENERGY USAGE DAS Energy Usage 36 14,000,000 12,000,000 Servers 10,000,000 Lighting Power Equipment 8,000,000 UPS Make Up Air 6,000,000 Exhaust Fans Chiller Plant 4,000,000 Cooling Towers AHU 2,000,000 - Current Day Baseline (Option 1) Containment (Option 2 and 3)

37 STEWARDSHIP ENERGY COST 37 Annual Cost of Energy $900,000 $800,000 $700,000 $600,000 $500,000 $400,000 $300,000 $200,000 $100,000 $0 Current Day Baseline (Option 1) Containment (Option 2 and 3)

38 STEWARDSHIP ROI 38 System First Cost Annual Energy Consumption Annual Energy Cost (1) First Cost Difference Annual Energy Savings Simple Payback Dollars KWH Dollars Years Annual Average PUE Baseline $0 13,868,510 $762, EEM 1 - Provide Containment and 70 F Economizer $521,000 11,419,716 $628,084 $521,000 $134, Utility rate based an average of 5.5 cents a KWH

39 COST ESTIMATE PROBABLE COST OF CONSTRUCTION 39 TOTAL PROBABLE CONSTRUCTION COST $8,593,000 (Baseline) Includes: Direct Costs (Labor and Materials, Contingencies, Permits, Insurance, Markup, Escalation) Excludes: Soft Costs (i.e. design fees, AHJ requirements, 1% for Art, SEED Analysis)

40 COST ESTIMATE W/ ALTERNATES PROBABLE COST OF CONSTRUCTION 40 Alt #1: Containment Alt #2: Water Tower Alt #3: Chilled Water Distribution Alt #4: Fuel Polishing Alt #5: Failure/Maintainability Analysis Alt #6: Relocate EPO Alt #7: Flywheel UPS ILO Battery System Alt #8: Replace (E) UPS w/ Flywheel 521, ,000 65, , ,000 7,000* 578,000 1,667,000 TOTAL PROBABLE CONSTRUCTION COST (Baseline + All Alternates) $11,785,000

41 PROJECT TIMELINE 41

42 DISCUSSION Q&A 42

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM Data Center Facility Analysis Project Final Presentation Wednesday, July 22, 2009 1:30 3:30 PM 1 Commonwealth Technology Center Conference Rooms 1 & 2 Enterprise Server Farm (ESF) Facility Data: 1 Technology

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO 6 CASE STUDIES Brevard Community College: Florida Power & Light City of Miami Beach: Johnson Controls, Inc. Cape Canaveral Air Force Station: NORESCO Arbor Shoreline Office Park: Progress Energy Solutions

More information

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation Engineered Energy Solutions An Overview Controls, Automation and Energy Conservation Engineered Energy Solutions Independent Control System Integration and Engineering Firm specializing in the energy efficient

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

University of Florida Data Center at Eastside Campus: Key Facts

University of Florida Data Center at Eastside Campus: Key Facts University of Florida Data Center at Eastside Campus: Key Facts Design: KlingStubbins Architectural Engineering, Philadelphia, PA Construction: Whiting-Turner; Baltimore, MD Commissioning: Hanson Professional

More information

Reliable, Energy Efficient, and Cost-Effective On-site Cogeneration and Back-up Power System for a Mission Critical Data Center

Reliable, Energy Efficient, and Cost-Effective On-site Cogeneration and Back-up Power System for a Mission Critical Data Center Reliable, Energy Efficient, and Cost-Effective On-site Cogeneration and Back-up Power System for a Mission Critical Data Center Critical Facilities Roundtable Dan Hoffman Director of Facilities May 19,

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

1008 kw, Tier 2, Chilled Water, ft 2

1008 kw, Tier 2, Chilled Water, ft 2 [eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

Driving Proactive Facility Operations with Automated HVAC Diagnostics

Driving Proactive Facility Operations with Automated HVAC Diagnostics Driving Proactive Facility Operations with Automated HVAC Diagnostics Turn HVAC Data into Actionable Information AKA Monitoring Based Commissioning Ongoing Commissioning Automated Fault Detection & Diagnostics

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

SCHENDT ENGINEERING PRIOR EXPERIENCE

SCHENDT ENGINEERING PRIOR EXPERIENCE Mitchell Hall Renovation US Air Force Academy, Colorado Corp. was the prime consultant for this project. The project generally consisted of replacing all of the air handling units, exhaust fans, air curtains,

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Increasing Data Center Efficiency through Metering and Monitoring Power Usage

Increasing Data Center Efficiency through Metering and Monitoring Power Usage White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency

More information

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization 2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization Presented by: Steve Keppler, Senior Director Critical Systems Design Build Practice CLEAResult Deep Optimization Standard

More information

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: 15000 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 10-26-11 - Minor revisions to Data Sheets 04-08-10 - Allowed use

More information

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities UTILITIES ELEMENT NOTE: Unless otherwise noted, the goals, objectives and policies contained in this element shall guide development of the Main Campus and Southwest Campus in Tallahassee as well as the

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

Silicon Valley Power Data Center Program Rebate Application

Silicon Valley Power Data Center Program Rebate Application Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account

More information

Achieving Operational Excellence

Achieving Operational Excellence Achieving Operational Excellence Energy Efficient Operations in a Shrinking Budget Environment 2010 Energy/Facilities Connections Conference Innovative Approaches for a New Decade DID YOU KNOW? Nine out

More information

Performance Comparisons

Performance Comparisons UPS Topologies - Project Performance Comparisons Rowan Peck, NDY r.peck@ndy.com Overview Let s explore UPS solutions: Plant cost Quantity of redundant plant Building cost TCO energy, water, maintenance

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

HVAC System Energy Savings Opportunities

HVAC System Energy Savings Opportunities HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered

More information

Cisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project

Cisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE 90.1-2016 Revisions to Waterside Economizer March 15, 2017 Stefan Gracik 510-663-2070 sgracik@integralgroup.com Agenda 1. Background

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

Case Study: Energy Systems Integration Facility (ESIF)

Case Study: Energy Systems Integration Facility (ESIF) Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case

More information

Water cooled chiller plant (all-variable)

Water cooled chiller plant (all-variable) Data Center Water cooled chiller plant (all-variable) Design Envelope File No: 9.572 Date: november 14, 2014 Supersedes: 9.572 Date: september 22, 2014 design envelope s performance improvements are among

More information

Syska Criticality Levels

Syska Criticality Levels Appendix C Syska Criticality Levels SYSKA CRITICALITY LEVEL TM DEFINITIONS Syska Hennessy Group Critical Facilities are designed and constructed on a scale of 1 10, 10 being the ultimate in criticality.

More information

Green IT Project: The Business Case

Green IT Project: The Business Case Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Energy Engineering: Tools and Trends

Energy Engineering: Tools and Trends Energy Engineering: Tools and Trends AEE Northeast Ohio Chapter Meeting March 27, 2008 1 Introduction Background and Experience Energy Engineer for Trane 20 years in HVAC Industry Equipment design and

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm

More information

Datacenter Cooling. DC Cooling Efficiency and Project experience. Osman Uzuner. Vakıfbank Central Systems Management Datacenter Operations

Datacenter Cooling. DC Cooling Efficiency and Project experience. Osman Uzuner. Vakıfbank Central Systems Management Datacenter Operations Datacenter Cooling DC Cooling Efficiency and Project experience Osman Uzuner Vakıfbank Central Systems Management Datacenter Operations Agenda Agenda and Intro About Vakıfbank DC Energy Consumption breakdown

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. 22 ECOLIBRIUM OCTOBER 2018 The hunter and the prey A clever modernisation

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Committed to Energy Efficiency

Committed to Energy Efficiency RESOLUTE Resolute Helps PNC Arena Reduce Energy Consumption and Costs While Improving Fan Comfort Lacking the visibility, real-time data and analytics needed to optimize facility performance and reduce

More information

Precision Cooling Mission Critical Air Handling Units

Precision Cooling Mission Critical Air Handling Units M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly

More information

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group Towards the Green Data Centre Lex Coors Vice President Data Center Technology & Engineering Group DC Emissions: We Have Lift-Off! Data Centre Greenhouse Gas Emissions are projected to quadruple by 2020

More information

QuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired

QuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired Overview The HP Performance-Optimized Data Center (HP POD) is a containerized datacenter equipped with power infrastructure, cooling and IT power distribution. The HP POD can be deployed within weeks instead

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Phil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical

Phil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion

More information

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft. [Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL

More information

DCIM Data Center Infrastructure Management Measurement is the first step

DCIM Data Center Infrastructure Management Measurement is the first step DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by

More information

High Performance Computing (HPC) Data Center Proposal

High Performance Computing (HPC) Data Center Proposal High Performance Computing (HPC) Data Center Proposal Imran Latif, Facility Project Manager Scientific & Enterprise Computing Data Centers at BNL 10/14/2015 Quick Facts!! Located on 1 st floor in Building

More information

ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/BICSI Data Center Design and Implementation Best Practices ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Vice Chair BICSI Mainland Europe

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS 1 25 95 00 Integrated Automation Control Sequences for HVAC GENERAL The HVAC operational sequences in this guideline are commonly used by Duke University. They are being provided as a preferred design

More information

DESIGN-BUILD FOR MISSION CRITICAL FACILITIES

DESIGN-BUILD FOR MISSION CRITICAL FACILITIES DESIGN-BUILD FOR MISSION CRITICAL FACILITIES Case Study: California ISO Iron Point Facility Folsom, CA MISSION POSSIBLE Mission Critical Headquarters Design-Build Delivery Delivered Early Delivered Under

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Comprehensive Energy Management & Utility Master Plan

Comprehensive Energy Management & Utility Master Plan Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach

More information

200 kw, Tier 3, Chilled Water, 5250 ft 2

200 kw, Tier 3, Chilled Water, 5250 ft 2 [eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,

More information

10 TECHNIQUES FOR IMPROVING DATA CENTER POWER EFFICIENCY

10 TECHNIQUES FOR IMPROVING DATA CENTER POWER EFFICIENCY NETAPP VISION PAPER 10 TECHNIQUES FOR IMPROVING DATA CENTER POWER EFFICIENCY Dan Hoffman November 2007 WP-7030-1107 IMPROVE POWER EFFICIENCY IN YOUR DATA CENTER USING TODAY S TECHNOLOGIES NetApp is completely

More information

New Wisconsin Energy Code: What it Means for Me?

New Wisconsin Energy Code: What it Means for Me? 2018 Wisconsin Energy Efficiency Expo Hosted by the Wisconsin Association of Energy Engineers New Wisconsin Energy Code: What it Means for Me? May 17, 2018 Shana Scheiber, PE, LEED AP ID+C, WELL AP Building

More information

Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building

Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Dhayanandh Murugan 1, Gabrielle Viola McMorrow 1, Dr.Liping Wang 1, Greenberg Steve 2 1 University of Wyoming,

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

BASELAYER CORE PA20 Power Module

BASELAYER CORE PA20 Power Module TM TM PA20 Power Module The CORE PC20 Power Module is a state of the art switchboard and UPS featuring modularized, critical components and delivers a configurable conditioned power supply. HIGHLIGHTS

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

Advanced RTU Campaign Taking Action Toward Efficient RTUs Michael Deru February 25, 2014

Advanced RTU Campaign Taking Action Toward Efficient RTUs Michael Deru February 25, 2014 Advanced RTU Campaign Taking Action Toward Efficient RTUs Michael Deru February 25, 2014 RTUs cool over 60% of U.S. commercial building floor area Lots of 10 to 20 year old RTUs installed Why RTU s Are

More information

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Trends in Data Center Energy Efficiency

Trends in Data Center Energy Efficiency Trends in Data Center Energy Efficiency Presented by: Todd Boucher Better Building by Design 2012 1 Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education

More information

Data Center NJ1. Piscataway, NJ

Data Center NJ1. Piscataway, NJ Data Center NJ1 Piscataway, NJ powerful/ efficient /reliable solutions > Data Center NJ1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale data centers.

More information

DATA CENTER COLOCATION BUILD VS. BUY

DATA CENTER COLOCATION BUILD VS. BUY DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

Reference Design Quicktour Design Summary

Reference Design Quicktour Design Summary Quicktour Design Summary Outdoor Heat Rejection Mixed Use or Purpose Built Data Center Facility Indoor/Outdoor Power Generation Mechanical Room Electrical Room Data Center Whitespace Reclaimed Whitespace

More information

DEDICATED HEAT RECOVERY UNIT (DHRC)

DEDICATED HEAT RECOVERY UNIT (DHRC) DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

The challenge is that BAS are often very complex with 1000s of data points to review. EMS Optimization Software

The challenge is that BAS are often very complex with 1000s of data points to review. EMS Optimization Software EMS Optimization Software Often immediate energy savings can be achieved with proper set points, sequencing, scheduling and fault detection of the Building Automation System (BAS). The challenge is that

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling CHILLER PLANT CONTROLS The challenges of producing chilled water are not the same as those a decade

More information

Delaware s Premier Suburban Office Park

Delaware s Premier Suburban Office Park IRON IRON HILL HILL CORPORATE CORPORATE CENTER CENTER Delaware s Premier Suburban Office Park WHITE WING 700 RED WING 750 BLUE WING 800 www.cbre.us/ironhill PROJECT SUMMARY White Wing Red Wing Blue Wing

More information