SCP Hardware Quick Reference

Size: px
Start display at page:

Download "SCP Hardware Quick Reference"

Transcription

1 SP Hardware Quick Reference RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: /08

2 Table Of ontents MODEL PAGE MODEL PAGE MINI-SP MINI-SPE 5 SP-MB 7 SP-E 9 SP-MEM SP-MEM7 EP-50 5 EP-50 PLUS 7 EP-50 9 EP-500 EP-50 LP-50 5 LP-50 PLUS 7 LP-50 9 LP-500 MR-50 Series 5 MR-50 Series 7 MR-50 Series 9 MR-5E MR-5 Series MR-5 Series 5 MR-5 Series 7 MR-6E 9 MR-6IN Series 5 MR-6IN Series 5 MR-6IN Series 55 MR-6OUT Series 57 MR-6OUT Series 59 MR-6OUT Series 6 MUX-8 6 LP RS Technologies, LL. - All rights reserved.

3 (Always set to ) J (Always set to W) J7 85 W W TO MINI-SP Quick Reference MINI-SP not evaluated by UL Detail + Volts D (50mA) - Tamper Input (N/ - Jumper if not used) Power Fault (N/ - Jumper if not used) AD A { { IN IN (Always closed) J J (Not used) U 85 J J5 J6 J9 (Always set to ) J8 J0 (Always closed) (hannel Termination) J (hannel Termination) J TXD TR+ RXD TR- RTS R+ TR+ TS R- TR- TR+ TR- Host hannel (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) Memory Backup Battery (Exp. ) Battery Bypass Sleeve (Exp. ) REMOVE FOR SERVIE U S LED A LED B LED Address Dip Switch (Fig. ) Normal LED Function LED A = Power (~ pulse/second) LED B = Host ommunication (~ pulse/second) LED = SIO ommunication (Rapid pulse) RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

4 TO Figure : Host hannel and Address Dip Switch onfiguration Oview S - RS- Hardwired Address Dip Switch Address Off Off Off Off Off On On Off S - Dialup Address Dip Switch Address On Off Off Off On On On Off DB-9 Wiring DB-5 Wiring USR Sportster,600 External Modem DB-5 Wiring TXD TR+ RXD TR- Pin Pin 5 9 TXD TR+ RXD TR- Pin Pin TXD TR+ RXD TR- Pin Pin Pin Pin 6 Jump, 6 & 0 together RTS R+ TS R- Pin 5 6 RTS R+ TS R- Pin 7 RTS R+ TS R- Pin 5 Pin 7 Pin Figure : RS-85 Sub-Panel Bus Termination TR+ (hannel Termination) J (hannel Termination) J TR- TR+ TR- The MINI-SP has two distinct RS-85 sub-panel buses. Each bus needs to be terminated at both the beginning and ending points. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. (see Two Wire RS-85 Wiring diagram for sub-panel wiring information) Explanation : Memory Backup Battery If the MINI-SP should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The MINI-SP will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR5 lithium battery or equivalent. TE: When setting up or servicing the MINI-SP, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. 08 RS Technologies, LL. - All rights reserved.

5 (Always set to ) J (Always set to W) J7 85 W W TO MINI-SPE Quick Reference MINI-SPE not evaluated by UL Detail + Volts D (50mA with NI) - Tamper Input (N/ - Jumper if not used) Power Fault (N/ - Jumper if not used) { { AD A IN IN (Always open) J J (Exp. ) U 85 J J5 J6 J9 (Always set to ) J8 J0 (Always closed) (hannel Termination) J (hannel Termination) J TXD TR+ RXD TR- RTS R+ TR+ TS R- TR- TR+ TR- Host hannel (Not used) hannel RS-85 Sub-Panel Bus (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) Address Dip Switch Memory Backup Battery (Exp. ) Battery Bypass Sleeve (Exp. ) REMOVE FOR SERVIE U S LED A LED B LED Always set to address 0. Always turn on switches 5, 6 & 7. Set switches prior to powering up. Normal LED Function LED A = Power (~ pulse/second) LED B = Host ommunication (~ pulse/second) LED = SIO ommunication (Rapid pulse) RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

6 TO Explanation : Network Interface ard Oview Network Interface ard Setup The 0Base-T Network Interface ard (NI) has been installed on the MINI-SPE by the factory and acts as the interface between the software and the MINI-SPE. The NI will require an IP Address, Subnet Mask and Gateway in order for the software to communicate with it. To program this information into the NI, a MA Address is required. Every NI has a unique MA Address which can be found on the white tag that is attached to it. A sample of a MA Address would be 00-0-A-7-OF-7F and can be found under the model number of the NI (O-E-AA). Programming the NI can be performed through one of three methods. Method One: RS Programmer (P/N: RS-PROG-TOOL) The RS Programmer comes with a cross-over cable which is used to connect the programmer to the MINI-SPEs NI. After connecting the programmer to the NI, power up the MINI-SPE and the RS Programmer. The programming software will automatically launch. Enter the NIs MA Address into the MA Address fields. Enter the desired IP Address, Gateway and Subnet Mask into their respective fields. Select the appropriate SP type and software application from their respective drop lists and then click the 'Set onfiguration' button. One of two messages will appear, 'onfiguration set!' if the programming was successful or 'Panel timeout' if the programming failed. Method Two: Access It! Ultra SPe IP Programmer Access It! Ultra installs a utilities folder which contains the SPe IP Programmer. If the computer resides on the same subnet as the NI being programmed, you may program it while connected to the network. From the start menu, click Start Programs Access It! Ultra Utilities SPe IP Programmer to run the SP-E/MINI SP-E Programmer utility. Enter the NIs MA Address into the MA Address fields. Enter the desired IP Address, Gateway and Subnet Mask into their respective fields. Select the appropriate SP type and software application from their respective drop lists and then click the 'Set onfiguration' button. One of two messages will appear, 'onfiguration set!' if the programming was successful or 'Panel timeout' if the programming failed. Method Three: Manually The manual ARP command is a tedious, but effective method in programming the NI. This method should be used only as a last resort. If the computer resides on the same subnet as the NI being programmed, you may program it while connected to the network. From the start menu, click Start Run followed by typing 'cmd' for NT.0, 000 and XP or 'command' for 98 and Me. This will open a ommand Prompt window from which the following commands will be run from. Power Recycle Switch Status LEDs RJ-5 Jack LED Description LED Functions (Green) Serial Port hannel Status Lights solid green to indicate hannel is idle. Blinks green to indicate hannel is connected to the network and active. (Yellow) Serial Port hannel Status Lights solid yellow to indicate hannel is idle. Blinks yellow to indicate hannel is connected to the network and active. Blinks or lights solid red in combination with the green (hannel ) LED to indicate diagnostics and error detection. (Red) Diagnostics (Green) Network Link Status *non-fatal error Red solid, green (hannel ) blinking: x: EPROM checksum error x: RAM error x: Network controller error x: EEPROM checksum error 5x: Duplicated IP address on the network* 6x: Software does not match hardware* Red blinking, green (hannel ) blinking: x: Faulty network connection* 5x: No DHP response received* Lights solid green to indicate network port is connected to the network ommand Prompt Window Portion ommand Variable Reference General ommand Information arp -s xxx.xxx.xxx.xxx yy-yy-yy-yy-yy-yy<enter> xxx.xxx.xxx.xxx = IP Address Temporarily sets the IP Address. yy-yy-yy-yy-yy-yy = MA Address telnet xxx.xxx.xxx.xxx <Enter> xxx.xxx.xxx.xxx = IP Address The telnet connection will fail, but the NI will change its IP Address. telnet xxx.xxx.xxx.xxx 9999 xxx.xxx.xxx.xxx = IP Address Opens a telnet session for further programming. Telnet Session Window Portion ommand Variable Reference General ommand Information <Enter> Enters the NIs Setup Mode. 0<Enter> Selects option 0 Server configuration. xxx<enter> xxx = First IP octet Programs the NIs first IP octet. xxx<enter> xxx = Second IP octet Programs the NIs second IP octet. xxx<enter> xxx = Third IP octet Programs the NIs third IP octet. xxx<enter> xxx = Fourth IP octet Programs the NIs fourth IP octet. Y Y = Yes Enables Gateway to be programmed. xxx<enter> xxx = First Gateway octet Programs the NIs first Gateway octet. xxx<enter> xxx = Second Gateway octet Programs the NIs second Gateway octet. xxx<enter> xxx = Third Gateway octet Programs the NIs third Gateway octet. xxx<enter> xxx = Fourth Gateway octet Programs the NIs fourth Gateway octet. xx<enter> xx = Number of bits to mask Programs the NIs Subnet Mask (08) class /8 bits ( ) (6) class B 6/6 bits ( ) () class A 8/ bits ( ) <Enter> Bypasses the hange telnet config password option. <Enter> Selects option hannel configuration. 800<Enter> Programs the Baudrate to 8,00. <Enter> Programs the I/F Mode to. 0<Enter> Programs the Flow to 0. xxxxx<enter> xxxxx = Network TP port (000) Default Access It! setting (00) If running Access It! Lite or Access It! UltraLite. Programs the Port No to 000 or 00 IMPORTANT TE: Only set the Port No to 00, when running Access It! Lite or Access It! UltraLite which require the Lantronix Redirector Software! 0<Enter> Programs the onnectmode to 0. <Enter> Bypasses the first Remote IP Address octet option. <Enter> Bypasses the second Remote IP Address octet option. <Enter> Bypasses the third Remote IP Address octet option. <Enter> Bypasses the fourth Remote IP Address octet option. <Enter> Bypasses the Remote Port option. <Enter> Bypasses the DisonnMode option. <Enter> Bypasses the FlushMode option. <Enter> Bypasses the hours DisonnTime option. <Enter> Bypasses the minutes DisonnTime option. <Enter> Bypasses the Sendhar option. <Enter> Bypasses the Sendhar option. 5<Enter> Selects option 5 Expert settings. 5<Enter> Programs the TP Keepalive time to 5 seconds. 9<Enter> Selects option 9 Save and exit. Explanation : Memory Backup Battery If the MINI-SPE should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The MINI-SPE will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR5 lithium battery or equivalent. TE: When setting up or servicing the MINI-SPE, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. (hannel Termination) J (hannel Termination) J Figure : RS-85 Sub-Panel Bus Termination TR+ TR+ TR- TR- The MINI-SPE has two distinct RS-85 sub-panel buses. Each bus needs to be terminated at both the beginning and ending points. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. (see Two Wire RS-85 Wiring diagram for sub-panel wiring information) 08 RS Technologies, LL. - All rights reserved.

7 (Always set to 5K) J (Always set to 5K) J (Always set to 5K) J LED A LED B LED (Always set to ) J9 (Always set to W) J 85 W W TO SP-MB Quick Reference SP-MB not evaluated by UL Detail + Volts D (50mA) - Tamper Input (N/ - Jumper if not used) Power Fault (N/ - Jumper if not used) { { AD A IN IN 85 J0 J J (Always closed) J8 (Always closed) J7 J (Always set to ) J5 (hannel Termination) J6 (hannel Termination) TXD TR+ RXD TR- RTS R+ TS R- TR+ TR+ TR- TR- TR+ Host hannel (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) J7 (hannel Termination) TR- TR5+ hannel RS-85 Sub-Panel Bus (Fig. ) U J8 (hannel 5 Termination) TR5- hannel 5 RS-85 Sub-Panel Bus (Fig. ) S Address Dip Switch (Fig. ) Normal LED Function LED A = Power (~ pulse/second) LED B = Host ommunication (~ pulse/second) LED = SIO ommunication (Rapid pulse) U8 J5 8K 5K Memory Expansion Bus (Exp. ) U7 U6 Memory Backup Battery (Exp. ) REMOVE FOR SERVIE Battery Bypass Sleeve (Exp. ) RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

8 TO Figure : Host hannel and Address Dip Switch onfiguration Oview S - RS- Hardwired Address Dip Switch Address Off Off Off Off Off On On Off S - Dialup Address Dip Switch Address On Off Off Off On On On Off DB-9 Wiring DB-5 Wiring USR Sportster,600 External Modem DB-5 Wiring TXD TR+ RXD TR- Pin Pin 5 9 TXD TR+ RXD TR- Pin Pin TXD TR+ RXD TR- Pin Pin Pin Pin 6 Jump, 6 & 0 together RTS R+ TS R- Pin 5 6 RTS R+ TS R- Pin 7 RTS R+ TS R- Pin 5 Pin 7 Pin Figure : RS-85 Sub-Panel Bus Termination TR+ J5 (hannel Termination) J6 (hannel Termination) J7 (hannel Termination) J8 (hannel 5 Termination) TR- TR+ TR- TR+ TR- TR5+ TR5- The SP-MB has four distinct RS-85 sub-panel buses. Each bus needs to be terminated at both the beginning and ending points. J5 is the termination jumper for the hannel RS-85 Sub-Panel Bus. J6 is the termination jumper for the hannel RS-85 Sub-Panel Bus. J7 is the termination jumper for the hannel RS-85 Sub-Panel Bus. J8 is the termination jumper for the hannel 5 RS-85 Sub-Panel Bus. (see Two Wire RS-85 Wiring diagram for sub-panel wiring information) Explanation : Memory Backup Battery Explanation : Memory Expansion If the SP-MB should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The SP-MB will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR5 lithium battery or equivalent. TE: When setting up or servicing the SP-MB, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. The SP-MB is equipped with MB of upgradeable RAM. A maximum of MB may be achieved by adding the SP-MEM. Please refer to the SP-MEM Quick Reference for detailed installation instructions. 08 RS Technologies, LL. - All rights reserved.

9 LED A LED B LED TO SP-E Quick Reference SP-E not evaluated by UL Detail + Volts D (600mA with NI) - Tamper Input (N/ - Jumper if not used) Power Fault (N/ - Jumper if not used) Secondary Host (Not used) Memory Backup Battery (Exp. ) { { AD A IN IN (Always set to ) J6 (Always set to ) J9 (Always set to ) J (Always set to ) J5 TXD6 TR6+ RXD6 TR6- RTS6 R6+ TS6 R6- REMOVE FOR SERVIE 85 W W 85 J0 (Always closed) J8 (Always closed) J7 (Always set to W) J (Always set to ) W W 85 J8 (Always set to W) J5 (Always set to ) U J7 (Exp. ) 85 J J6 J7 J0 (Always set to ) J9 J (Always closed) (hannel Termination) J (hannel Termination) J (hannel Termination) J6 (Always open) J 5K 57K J (Not used) J5 (Always set to 5K) J (hannel 5 Termination) TXD TR+ RXD TR- RTS R+ TR+ TR+ TR+ TR5+ TS R- TR- TR- TR- TR5- S Host hannel (Not used) hannel RS-85 Sub-Panel Bus (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) hannel RS-85 Sub-Panel Bus (Fig. ) hannel 5 RS-85 Sub-Panel Bus (Fig. ) Address Dip Switch Always set to address 0. Always turn on switch 5. Set switches prior to powering up. Battery Bypass Sleeve (Exp. ) Normal LED Function LED A = Power (~ pulse/second) LED B = Host ommunication (~ pulse/second) LED = SIO ommunication (Rapid pulse) Memory Expansion Bus (Exp. ) U J RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

10 TO Explanation : Network Interface ard Oview Network Interface ard Setup The 0Base-T Network Interface ard (NI) has been installed on the SP-E by the factory and acts as the interface between the software and the SP-E. The NI will require an IP Address, Subnet Mask and Gateway in order for the software to communicate with it. To program this information into the NI, a MA Address is required. Every NI has a unique MA Address which can be found on the white tag that is attached to it. A sample of a MA Address would be 00-0-A-7-OF-7F and can be found under the model number of the NI (O-E-AA). Programming the NI can be performed through one of three methods. Method One: RS Programmer (P/N: RS-PROG-TOOL) The RS Programmer comes with a cross-over cable which is used to connect the programmer to the SP-Es NI. After connecting the programmer to the NI, power up the SP-E and the RS Programmer. The programming software will automatically launch. Enter the NIs MA Address into the MA Address fields. Enter the desired IP Address, Gateway and Subnet Mask into their respective fields. Select the appropriate SP type and software application from their respective drop lists and then click the 'Set onfiguration' button. One of two messages will appear, 'onfiguration set!' if the programming was successful or 'Panel timeout' if the programming failed. Method Two: Access It! Ultra SPe IP Programmer Access It! Ultra installs a utilities folder which contains the SPe IP Programmer. If the computer resides on the same subnet as the NI being programmed, you may program it while connected to the network. From the start menu, click Start Programs Access It! Ultra Utilities SPe IP Programmer to run the SP-E/MINI SP-E Programmer utility. Enter the NIs MA Address into the MA Address fields. Enter the desired IP Address, Gateway and Subnet Mask into their respective fields. Select the appropriate SP type and software application from their respective drop lists and then click the 'Set onfiguration' button. One of two messages will appear, 'onfiguration set!' if the programming was successful or 'Panel timeout' if the programming failed. Method Three: Manually The manual ARP command is a tedious, but effective method in programming the NI. This method should be used only as a last resort. If the computer resides on the same subnet as the NI being programmed, you may program it while connected to the network. From the start menu, click Start Run followed by typing 'cmd' for NT.0, 000 and XP or 'command' for 98 and Me. This will open a ommand Prompt window from which the following commands will be run from. ommand Prompt Window Portion ommand Variable Reference General ommand Information arp -s xxx.xxx.xxx.xxx yy-yy-yy-yy-yy-yy<enter> xxx.xxx.xxx.xxx = IP Address Temporarily sets the IP Address. yy-yy-yy-yy-yy-yy = MA Address telnet xxx.xxx.xxx.xxx <Enter> xxx.xxx.xxx.xxx = IP Address The telnet connection will fail, but the NI will change its IP Address. telnet xxx.xxx.xxx.xxx 9999 xxx.xxx.xxx.xxx = IP Address Opens a telnet session for further programming. Telnet Session Window Portion ommand Variable Reference General ommand Information <Enter> Enters the NIs Setup Mode. 0<Enter> Selects option 0 Server configuration. xxx<enter> xxx = First IP octet Programs the NIs first IP octet. xxx<enter> xxx = Second IP octet Programs the NIs second IP octet. xxx<enter> xxx = Third IP octet Programs the NIs third IP octet. xxx<enter> xxx = Fourth IP octet Programs the NIs fourth IP octet. Y Y = Yes Enables Gateway to be programmed. xxx<enter> xxx = First Gateway octet Programs the NIs first Gateway octet. xxx<enter> xxx = Second Gateway octet Programs the NIs second Gateway octet. xxx<enter> xxx = Third Gateway octet Programs the NIs third Gateway octet. xxx<enter> xxx = Fourth Gateway octet Programs the NIs fourth Gateway octet. xx<enter> xx = Number of bits to mask Programs the NIs Subnet Mask (08) class /8 bits ( ) (6) class B 6/6 bits ( ) () class A 8/ bits ( ) <Enter> Bypasses the hange telnet config password option. <Enter> Selects option hannel configuration. 500<Enter> Programs the Baudrate to 5,00. <Enter> Programs the I/F Mode to. 0<Enter> Programs the Flow to <Enter> Programs the Port No to <Enter> Programs the onnectmode to 0. <Enter> Bypasses the first Remote IP Address octet option. <Enter> Bypasses the second Remote IP Address octet option. <Enter> Bypasses the third Remote IP Address octet option. <Enter> Bypasses the fourth Remote IP Address octet option. <Enter> Bypasses the Remote Port option. <Enter> Bypasses the DisonnMode option. <Enter> Bypasses the FlushMode option. <Enter> Bypasses the hours DisonnTime option. <Enter> Bypasses the minutes DisonnTime option. <Enter> Bypasses the Sendhar option. <Enter> Bypasses the Sendhar option. 5<Enter> Selects option 5 Expert settings. 5<Enter> Programs the TP Keepalive time to 5 seconds. 9<Enter> Selects option 9 Save and exit. Power Recycle Switch Status LEDs RJ-5 Jack LED Description LED Functions (Green) Serial Port hannel Status Lights solid green to indicate hannel is idle. Blinks green to indicate hannel is connected to the network and active. (Yellow) Serial Port hannel Status Lights solid yellow to indicate hannel is idle. Blinks yellow to indicate hannel is connected to the network and active. Blinks or lights solid red in combination with the green (hannel ) LED to indicate diagnostics and error detection. (Red) Diagnostics (Green) Network Link Status *non-fatal error Explanation : Memory Backup Battery If the SP-E should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The SP-E will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR5 lithium battery or equivalent. TE: When setting up or servicing the SP-E, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. Explanation : Memory Expansion Red solid, green (hannel ) blinking: x: EPROM checksum error x: RAM error x: Network controller error x: EEPROM checksum error 5x: Duplicated IP address on the network* 6x: Software does not match hardware* Red blinking, green (hannel ) blinking: x: Faulty network connection* 5x: No DHP response received* Lights solid green to indicate network port is connected to the network The SP-E is equipped with MB of upgradeable RAM. A maximum of 8MB may be achieved by adding the SP-MEM7 or MB by adding the SP-MEM. Please refer to the SP-MEM7 Quick Reference and the SP-MEM Quick Reference for detailed installation instructions. (hannel Termination) J (hannel Termination) J (hannel Termination) J 08 RS Technologies, LL. - All rights reserved. Figure : RS-85 Sub-Panel Bus Termination J (hannel 5 Termination) TR+ TR+ TR5- TR- TR- TR+ TR5+ TR- The SP-E has four distinct RS-85 sub-panel buses. Each bus needs to be terminated at both the beginning and ending points. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J is the termination jumper for the hannel 5 RS-85 Sub-Panel Bus. (see Two Wire RS-85 Wiring diagram for sub-panel wiring information)

11 TO SP-MEM Quick Reference SP-MEM not evaluated by UL Detail U U U5 J U U U6 5KB Memory Module (6) Memory Expansion Bus (Fig. ) Top View Bottom View RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

12 TO Figure : Proper Mounting Oview U U U5 J REMOVE FOR SERVIE U U U U5 J U U U6 U U U6 SP-MEM Standoff Position REMOVE FOR SERVIE SP-MB Top View SP-E Top View Place the edge of the SP-MEM board into the standoff prior to seating the memory expansion bus. SP-MB Side View 08 RS Technologies, LL. - All rights reserved. SP-E Side View

13 TO SP-MEM7 Quick Reference SP-MEM7 not evaluated by UL Detail U U U9 J U U U0 U7 U5 U U 5KB Memory Module () U8 U6 U U Memory Expansion Bus (Fig. ) Top View Bottom View RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 0/0

14 TO Figure : Proper Mounting Oview The SP-MEM7 LY works on the SP-E and is only supported with Access It! Ultra, Access It! Ultra Titanium Edition and Access It! Enterprise Edition. REMOVE FOR SERVIE U U U9 U J U U U0 U7 U5 U U SP-MEM7 Standoff Position U8 U6 U U SP-E Top View Place the edge of the SP-MEM7 board into the standoff prior to seating the memory expansion bus. SP-E Side View 08 RS Technologies, LL. - All rights reserved.

15 J7 S IN IN VO LED BZR LK DAT LED BZR LK DAT VO VIN S V PoE J - - Amber LED Green LED TO EP-50 Quick Reference EP-50 not evaluated by UL Detail Top View Bottom View 0/00 Ethernet Host hannel (Explanation ) Relay Relay TB5 Auxiliary Output (A@8Vdc - Figure ) D9 D0 RLY Door Strike (A@8Vdc - Figure ) RLY Volts D ±0% LY! (Vdc - 900mA max.) Optional Door Strike Power - VO / (Vdc - 00mA max.) J - EP-50 Power Source Selector J Setting Power Source PoE Power Over Ethernet V* External Power Source *Vdc power connected to TB. Positive lead to pin (VIN) and negative lead to pin (). Status LED Mostly On Mostly Off Toggle - EP-50 Status Online Offline - Host ommunication Flashes while communicating with host. - Reader & Activity - Door ontact Battery Low (Double Flashes) Flashes when data is received from either reader port. Open losed Fault 5 - Door REX Active Inactive Fault Reader Port Wiegand Reader (Figure ) 6 abinet Tamper 7 - Not Used Alarm Secure N/A N/A N/A N/A D9 - Relay Energized De-Energized N/A Reader Port Wiegand Reader (Figure ) MR-DT Keypad (Figure ) RS-85 Reader Interface D0 - Relay Amber - Ethernet Speed Green Link/Activity Energized De-Energized N/A 00 Mb/S 0 Mb/S N/A Link No Link Ethernet Activity Exit Request (N/O - Figure ) Door ontact (N/ - Jumper if not used - Figure ) J7 - Tamper Input (N/ - Jumper if not used) TB BT S - onfiguration Dip Switch (Explanation ) S - Reset Switch (Does T erase system config./databases) BT - SRAM Backup Battery (Retains system config./databases about weeks) Mechanical Specifications Dimensions 5.5" (0mm) W x.75" (70mm) L Temperature -55º to +85º, storage 0º to +70º, operating Humidity 0% to 95% RH RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 5/0

16 LED BZR LK DAT VO VIN VO LED BZR LK DAT VO LED BZR LK DAT Open Open IN x IN x IN x IN x V PoE losed losed J TO Explanation : S onfiguration DIP Switch & Primary 0/00 Ethernet Host hannel Oview. Set all S - onfiguration DIP Switch DIPs. Apply power to the EP-50 Bulk Erasing The System onfiguration And ardholder Databases. Set S - onfiguration DIP Switch DIPs &. Set S - onfiguration DIP Switch DIPs &. Apply power to the EP-50 onfiguring Primary 0/00 Ethernet Host hannel For DHP Enabled Networks. Make note of the MA address located on the side of the RJ5 jack. Run Access It! Universal 5. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server 6. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 omm Tab hannel: <Set to the newly created channel> TP/IP Settings IP Address: <MAxxxxxxxxxxxx> If the MA address from step was 00-0F-E B then the IP Address field must be entered as the Host Name of MA000FE5000B. Port Number: 00 Encryption Settings: None TE: If unable to resolve the Host Name to an IP Address, contact your local network administrator. LEDs & and LEDs & flash alternately at a.5 second rate. Within 0 seconds, switch S - onfiguration DIP Switch DIP LED flashes at a second rate as memory is being erased WARNING! DO T YLE POWER Erasing memory takes approximately 60 seconds to complete. LEDs & flash for 0 seconds after the memory has been erased, then the EP-50 reboots 5. The EP-50 is now ready to be configured as needed Figure : Reader Port. Set S - onfiguration DIP Switch DIP. Set S - onfiguration DIP Switch DIPs, &. Apply power to the EP-50. Manually configure a computer to Using a crossover cable, connect computer to EP Open a web browser and go to Set S - onfiguration DIP Switch DIP 8. lick on lick Here to Login 9. lick on ontinue to this website (not recommended). 0. Enter a Username of admin. Enter a Password of password. lick Network from the left hand menu. Select Use Static IP configuration:. lick OK IP Address: <Set accordingly> Subnet Mask: <Set accordingly> Default Gateway: <Set accordingly> 5. lick Apply Setting from the left hand menu 6. lick Apply, Reboot button 7. Wait 60 seconds for EP-50 to reboot 8. Remove power from the EP-50 onfiguring Primary 0/00 Ethernet Host hannel For A Static IP Address 9. Set all S - onfiguration DIP Switch DIPs 0. Remove crossover cable and connect to network. Apply power to the EP-50. Run Access It! Universal. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 omm Tab hannel: <Set to the newly created channel> TP/IP Settings IP Address: <Set accordingly> Port Number: 00 Encryption Settings: None Figure : Output Wiring Options Depending on your power source, use one of the two methods of transient clamping shown below to protect the relay contacts and to reduce electromagnetic interference (EMI emissions). Always protect against accidental overloads by wiring in an inline fuse to the (common) side of the relay as shown below. D Fuse D Source Diode* Load *Diode Selection Inductive Load Diode urrent Rating > x Strike urrent Diode Break Down Voltage: x Strike Voltage Vdc or Vdc Strike, Diode N00 (00V / A) Typical A Fuse A Source MOV* Load *MOV Selection Inductive Load lamp Voltage >.5x Vac RMS Vac Strike, Panasonic ERZ-07DK70 Typical Figure : Reader Port Figure : Input Wiring Options Wiegand Reader Black Red Green White Yellow Brown Wiegand Reader Black Green White Yellow Brown Red TB MR-DT R AB 5 M 9 YZ Black Gray Blue (Not used) (Not used) Red TB Non-Supervised Supervised 08 RS Technologies, LL. - All rights reserved.

17 J7 S IN IN VO LED BZR LK DAT LED BZR LK DAT VO VIN S V PoE J - - Amber LED Green LED TO EP-50 Plus Quick Reference EP-50 Plus not evaluated by UL Detail Top View Bottom View 0/00 Ethernet Host hannel (Explanation ) Relay Relay TB5 Auxiliary Output (A@8Vdc - Figure ) D9 D0 RLY N Door Strike (A@8Vdc - Figure ) Status LED Mostly On Mostly Off Toggle Volts D ±0% LY! (Vdc - 900mA max.) Optional Door Strike Power - VO / (Vdc - 00mA max.) - EP-50 Status Online Offline - Host ommunication Flashes while communicating with host. - Reader & Activity Battery Low (Double Flashes) Flashes when data is received from either reader port. - Door ontact Open losed Fault J - EP-50 Power Source Selector J Setting Power Source PoE Power Over Ethernet V* External Power Source *Vdc power connected to TB. Positive lead to pin (VIN) and negative lead to pin (). 5 - Door REX 6 abinet Tamper 7 - Not Used D9 - Relay Active Alarm N/A N/A N/A Energized Inactive Secure De-Energized Fault N/A N/A Reader Port Wiegand Reader (Figure ) *Vdc power connected to TB. Positive lead to pin (VO) and negative lead to pin (). D0 - Relay Amber - Ethernet Speed Green Link/Activity Energized De-Energized N/A 00 Mb/S 0 Mb/S N/A Link No Link Ethernet Activity Sub-Panel Bus (Figure ) EP-50 SIO Wiring LK DAT VO Not Used LED Not Used BZR Not Used Exit Request (N/O - Figure ) Door ontact (N/ - Jumper if not used - Figure ) J7 - Tamper Input (N/ - Jumper if not used) TB BT S - onfiguration Dip Switch (Explanation ) S - Reset Switch (Does T erase system config./databases) BT - SRAM Backup Battery (Retains system config./databases about weeks) Mechanical Specifications Dimensions 5.5" (0mm) W x.75" (70mm) L Temperature -55º to +85º, storage 0º to +70º, operating Humidity 0% to 95% RH RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: /08

18 LED BZRLKDAT VO VIN Open Open V PoE IN x IN x IN x IN x J losed losed TO Explanation : S onfiguration DIP Switch & Primary 0/00 Ethernet Host hannel Oview. Set all S - onfiguration DIP Switch DIPs. Apply power to the EP-50 Bulk Erasing The System onfiguration And ardholder Databases. Set S - onfiguration DIP Switch DIPs &. Set S - onfiguration DIP Switch DIPs &. Apply power to the EP-50 onfiguring Primary 0/00 Ethernet Host hannel For DHP Enabled Networks. Make note of the MA address located on the side of the RJ5 jack. Run Access It! Universal 5. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server 6. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 omm Tab hannel: <Set to the newly created channel> TP/IP Settings IP Address: <MAxxxxxxxxxxxx> If the MA address from step was 00-0F-E B then the IP Address field must be entered as the Host Name of MA000FE5000B. Port Number: 00 Encryption Settings: None TE: If unable to resolve the Host Name to an IP Address, contact your local network administrator. LEDs & and LEDs & flash alternately at a.5 second rate. Within 0 seconds, switch S - onfiguration DIP Switch DIP LED flashes at a second rate as memory is being erased WARNING! DO T YLE POWER Erasing memory takes approximately 60 seconds to complete. LEDs & flash for 0 seconds after the memory has been erased, then the EP-50 reboots 5. The EP-50 is now ready to be configured as needed Figure : Sub-Panel ommunication MR-5 () MR-5 () EP-50 PLUS apacities Any combination of up to 8 wired SIO's up to,000' and / or 8 MR-5E s supporting a maximum of 7 total readers Supported SIO s: MR-5e MR-50 MR-6IN MR-5 MR-6OUT MR-5e MR-5e. Set S - onfiguration DIP Switch DIP. Set S - onfiguration DIP Switch DIPs, &. Apply power to the EP-50. Manually configure a computer to Using a crossover cable, connect computer to EP Open a web browser and go to Set S - onfiguration DIP Switch DIP 8. lick on lick Here to Login 9. lick on ontinue to this website (not recommended). 0. Enter a Username of admin. Enter a Password of password. lick Network from the left hand menu. Select Use Static IP configuration:. lick OK D IP Address: <Set accordingly> Subnet Mask: <Set accordingly> Default Gateway: <Set accordingly> 5. lick Apply Setting from the left hand menu 6. lick Apply, Reboot button 7. Wait 60 seconds for EP-50 to reboot 8. Remove power from the EP-50 Fuse D Source Diode* Load *Diode Selection Inductive Load Diode urrent Rating > x Strike urrent Diode Break Down Voltage: x Strike Voltage Vdc or Vdc Strike, Diode N00 (00V / A) Typical onfiguring Primary 0/00 Ethernet Host hannel For A Static IP Address 9. Set all S - onfiguration DIP Switch DIPs 0. Remove crossover cable and connect to network. Apply power to the EP-50. Run Access It! Universal. reate a new hannel A hannel Enabled: X Protocol Type: SP hannel Type: IP Server. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 omm Tab hannel: <Set to the newly created channel> TP/IP Settings Fuse Figure : Input Wiring Options Non-Supervised IP Address: <Set accordingly> Port Number: 00 Encryption Settings: None Figure : Output Wiring Options Depending on your power source, use one of the two methods of transient clamping shown below to protect the relay contacts and to reduce electromagnetic interference (EMI emissions). Always protect against accidental overloads by wiring in an inline fuse to the (common) side of the relay as shown below. Figure : Reader Port Wiegand Reader Black Red Green White Yellow Brown A Source MOV* Load *MOV Selection Inductive Load lamp Voltage >.5x Vac RMS Vac Strike, Panasonic ERZ-07DK70 Typical Supervised 08 RS Technologies, LL. - All rights reserved.

19 TB TB0 RS-85 Sub-Panel Bus Termination (Figure 5) - J5 TB RESET TO EP-50 Quick Reference *Not evaluated by UL Detail LED LED LED LED TMP LED FLT LED R LED R Wiegand Reader MR-DT Battery Bypass Sleeve (Exp. ) Memory Backup Battery (Exp. ) Normal LED Function Off-Line / On-Line & Battery Status Off-Line if 0% on On-Line if 80% on Battery low if double flashing Serial Host hannel Activity hannel Internal Sub-Panel Activity hannel RS-85 Sub-Panel Activity Unassigned Reader Port Activity Reader Port Activity S - Reset Switch (Explanation ) Figure (Wiegand Reader Example) 5 9 R AB M YZ Black Green White Yellow Brown Red Black Gray Blue Red (See J7 - Reader Power) Door Strike (Form-, 5A@8Vdc, resistive - Figure ) Auxiliary Output (Form-, 5A@8Vdc, resistive - Figure ) Door Strike (Form-, 5A@8Vdc, resistive - Figure ) Auxiliary Output (Form-, 5A@8Vdc, resistive - Figure ) (Not used) (Not used) (See J7 - Reader Power) Figure (MR-DT* Keypad Example) TB9 OUT OUT OUT OUT TMP FLT R R (Remote display of LED ) (Remote display of LED ) (Remote display of LED ) (Remote display of LED ) READER READER DAT D0 LK D BZR LED VO DAT D0 LK D BZR LED VO TB8 S REMOVE FOR SERVIE PASS J7 + - Reader Ports & Wiegand Readers (Figure ) MR-DT Keypad (Figure ) RS-85 Reader Interface V Relay Relay S LED D7 (red) LED SPD (amber) LED AT (green) Normal Primary 0/00 Ethernet Host hannel LED Function Relay Relay Primary 0/00 Ethernet Host hannel Activity Ethernet Speed 0Mb/S if off 00Mb/S if on Link & Activity No link if off Good link if on Activity if flashing Mechanical Specifications Dimensions 8.0" (0.mm) W x 6.0" (5.mm) L Temperature -55º to +85º, storage 0º to +9º, operating Humidity 0% to 85% RH J7 Setting V PT J7 - Reader Power Reader Port VO Output (50mA max.) VO = Vdc regulated VO = VIN Use V setting LY when VIN power is >6Vdc. Readers requiring a different rating than listed above should be powered separately. The reader ground must reference the panel ground. Relay LEDs = Energized K K K K Relay LED Relay LED Relay LED Relay LEd Input LEDs = Inactive = Active Flashing = Trouble IN Door ontact LED IN Exit Request LED IN Door ontact LED IN Exit Request LED IN5 Auxiliary Input 5 LED IN6 Auxiliary Input 5 LED IN7 Auxiliary Input 7 LED IN8 Auxiliary Input 8 LED TB TB D7 VIN TMP FLT TXD RXD RTS TS TB IN IN TB5 TB6 TB7 SPD AT to Volts D (500mA max.) Tamper Input (N/ - Jumper if not used) Power Fault (N/ - Jumper if not used) 0/00 Ethernet Host hannel (Explanation ) Remote LED Status (Observe polarity connection to LED) S - onfiguration Dip Switch (Explanation ) Serial Host hannel* hannel RS-85 Sub-Panel Bus ( wire LY! - Figure 5) Door ontact (N/ - Jumper if not used - Figure ) Exit Request (N/O - Figure ) Door ontact (N/ - Jumper if not used - Figure ) Exit Request (N/O - Figure ) Auxiliary Input 5 (N/ - Jumper if not used - Figure ) Auxiliary Input 6 (N/ - Jumper if not used - Figure ) Auxiliary Input 7 (N/ - Jumper if not used - Figure ) Auxiliary Input 8 (N/ - Jumper if not used - Figure ) RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 8/08

20 Open Open IN x IN x IN x IN x losed losed J5 TB TO Explanation : S onfiguration DIP Switch & Primary 0/00 Ethernet Host hannel Oview. Set all S - onfiguration DIP Switch DIPs. Apply power to the EP-50 Bulk Erasing The System onfiguration And ardholder Databases. Set S - onfiguration DIP Switch DIPs &. Set S - onfiguration DIP Switch DIPs &. Apply power to the EP-50 onfiguring Primary 0/00 Ethernet Host hannel For DHP Enabled Networks. Make note of the MA address located on the side of the RJ5 jack. Run Access It! Universal 5. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server 6. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 SIO Port Speed omm Tab Port : 800 Port : 800 hannel: <Set to the newly created channel> TP/IP Settings IP Address: <MAxxxxxxxxxxxx> If the MA address from step was 00-0F-E B then the IP Address field must be entered as the Host Name of MA000FE5000B. Port Number: 00 Encryption Settings: None TE: If unable to resolve the Host Name to an IP Address, contact your local network administrator. LEDs & and LEDs & flash alternately at a.5 second rate. Within 0 seconds, switch S - onfiguration DIP Switch DIP LED flashes at a second rate as memory is being erased WARNING! DO T YLE POWER Erasing memory takes approximately 60 seconds to complete. LEDs & flash for 0 seconds after the memory has been erased, then the EP-50 reboots 5. The EP-50 is now ready to be configured as needed Explanation : S - Reset Switch Pressing the S - Reset Switch will cause the EP-50 to reboot. This process will T erase the system configuration and cardholder databases. Explanation : Memory Backup Battery If the EP-50 should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The EP-50 will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR 5, BR0, or R0 lithium battery or equivalent. For UL installations, refer to L-UL Hardware Installation Manual DOLUL-R0 for replacement procedures.. Set S - onfiguration DIP Switch DIP. Set S - onfiguration DIP Switch DIPs, &. Apply power to the EP-50. Manually configure a computer to Using a crossover cable, connect computer to EP Open a web browser and go to Set S - onfiguration DIP Switch DIP 8. lick on lick Here to Login 9. lick on ontinue to this website (not recommended). 0. Enter a Username of admin. Enter a Password of password. lick Network from the left hand menu. Select Use Static IP configuration:. lick OK IP Address: <Set accordingly> Subnet Mask: <Set accordingly> Default Gateway: <Set accordingly> 5. lick Apply Setting from the left hand menu 6. lick Apply, Reboot button 7. Wait 60 seconds for EP-50 to reboot 8. Remove power from the EP Set all S - onfiguration DIP Switch DIPs 0. Remove crossover cable and connect to network TE: When setting up or servicing the EP-50, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. Only Stand-Alone system was evaluated by UL 08 RS Technologies, LL. - All rights reserved. onfiguring Primary 0/00 Ethernet Host hannel For A Static IP Address. Apply power to the EP-50. Run Access It! Universal. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server. reate a new SP General Tab Model: EP-50 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 SIO Port Speed omm Tab Port : 800 Port : 800 hannel: <Set to the newly created channel> TP/IP Settings IP Address: <Set accordingly> Port Number: 00 Encryption Settings: None Figure : Output Wiring Options Depending on your power source, use one of the two methods of transient clamping shown below to protect the relay contacts and to reduce electromagnetic interference (EMI emissions). Always protect against accidental overloads by wiring in an inline fuse to the (common) side of the relay as shown below. D Fuse D Source Diode* Load *Diode Selection Inductive Load Diode urrent Rating > x Strike urrent Diode Break Down Voltage: x Strike Voltage Vdc or Vdc Strike, Diode N00 (00V / A) Typical Figure : Input Wiring Options Non-Supervised Supervised A Fuse A Source MOV* Load *MOV Selection Inductive Load lamp Voltage >.5x Vac RMS Vac Strike, Panasonic ERZ-07DK70 Typical Figure 5: RS-85 Sub-Panel Bus Termination The EP-50 has one RS-85 subpanel bus and must be terminated at the beginning and ending point. J5 is the termination jumper for the hannel RS-85 Sub-Panel Bus. (see Two Wire RS-85 Wiring diagram for sub-panel wiring information) Refer to L-UL Hardware Installation Manual DOLUL-R

21 TB J5 PORT J PORT TB J0 J8 J9 J7 PORT TB TO EP-500 Quick Reference *Not evaluated by UL Detail Battery Bypass Sleeve (Explanation ) Memory Backup Battery (Explanation ) REMOVE FOR SERVIE S Mechanical Specifications Dimensions 5.0" (7mm) W x 6.0" (5.mm) L Temperature -55º to +85º, storage 0º to +9º, operating Humidity 0% to 85% RH TB VIN TMP to Volts D (0mA or 5mA* with Micro-5) Tamper Input (N/ - Jumper if not used) S - Reset Switch (Explanation ) S - onfiguration Dip Switch (Explanation ) S LED D7 (red) LED SPD (amber) LED AT (green) Normal Primary 0/00 Ethernet Host hannel LED Function Primary 0/00 Ethernet Host hannel Activity Ethernet Speed 0Mb/S if off 00Mb/S if on Link & Activity No link if off Good link if on Activity if flashing D7 FLT SPD AT Power Fault (N/ - Jumper if not used) Primary 0/00 Ethernet Host hannel (Explanation ) 5 6 LED LED LED LED LED 5 LED 6 Normal LED Function Off-Line / On-Line & Battery Status Off-Line if 0% on On-Line if 80% on Battery low if double flashing Serial Host hannel Activity hannel RS-85 Sub-Panel Activity hannel RS-85 Sub-Panel Activity Not used Not used J6 (Always closed) (hannel Termination) (Always set to ) 85 TXD RXD RTS TS Backup Micro-5 Ethernet Host hannel* Serial Host hannel* hannel RS-85 Sub-Panel Bus ( wire LY! - Figure ) Remote LED Status (Observe polarity connection to LED) J J5 J6 J7 - + (Remote display of LED ) (Remote display of LED ) (Remote display of LED ) (Remote display of LED ) (hannel Termination) hannel RS-85 Sub-Panel Bus ( wire LY! - Figure ) RS Technologies, LL - 00 Fisher Street, Suite G - Munster, IN 6 - (877) Fax (9) Revised: 8/08

22 TB J5 J TB TO Explanation : S onfiguration DIP Switch & Primary 0/00 Ethernet Host hannel Oview onfiguring Primary 0/00 Ethernet Host hannel For DHP Enabled Networks onfiguring Primary 0/00 Ethernet Host hannel For A Static IP Address. Set all S - onfiguration DIP Switch DIPs. Apply power to the EP-500. Make note of the MA address located on the side of the RJ5 jack. Run Access It! Universal 5. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server 6. reate a new SP General Tab Model: EP-500 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 SIO Port Speed omm Tab Port : 800 Port : 800 hannel: <Set to the newly created channel> TP/IP Settings IP Address: <MAxxxxxxxxxxxx> If the MA address from step was 00-0F-E B then the IP Address field must be entered as the Host Name of MA000FE5000B. Port Number: 00 Encryption Settings: None TE: If unable to resolve the Host Name to an IP Address, contact your local network administrator.. Set S - onfiguration DIP Switch DIP. Set S - onfiguration DIP Switch DIPs, &. Apply power to the EP-500. Manually configure a computer to Using a crossover cable, connect computer to EP Open a web browser and go to Set S - onfiguration DIP Switch DIP 8. lick on lick Here to Login 9. lick on ontinue to this website (not recommended). 0. Enter a Username of admin. Enter a Password of password. lick Network from the left hand menu. Select Use Static IP configuration: IP Address: <Set accordingly> Subnet Mask: <Set accordingly> Default Gateway: <Set accordingly>. lick OK 5. lick Apply Setting from the left hand menu 6. lick Apply, Reboot button 7. Wait 60 seconds for EP-500 to reboot 8. Remove power from the EP Set all S - onfiguration DIP Switch DIPs 0. Remove crossover cable and connect to network. Apply power to the EP-500. Run Access It! Universal. reate a new hannel hannel Enabled: X Protocol Type: SP hannel Type: IP Server. reate a new SP General Tab Model: EP-500 Device Installed: X SP Time Zone: <Set accordingly> Initialization String: <Leave blank> Address: 0 SIO Port Speed Port : 800 Port : 800 omm Tab hannel: <Set to the newly created channel> TP/IP Settings IP Address: <Set accordingly> Port Number: 00 Encryption Settings: None Bulk Erasing The System onfiguration And ardholder Databases. Set S - onfiguration DIP Switch DIPs &. Set S - onfiguration DIP Switch DIPs &. Apply power to the EP-500 LEDs & and LEDs & flash alternately at a.5 second rate. Within 0 seconds, switch S - onfiguration DIP Switch DIP LED flashes at a second rate as memory is being erased WARNING! DO T YLE POWER Erasing memory takes approximately 60 seconds to complete. LEDs & flash for 0 seconds after the memory has been erased, then the EP-500 reboots 5. The EP-500 is now ready to be configured as needed Explanation : Memory Backup Battery If the EP-500 should experience a complete power loss, the volt lithium memory backup battery provides power to the onboard memory which contains the card file, activity transactions and system configuration data. The EP-500 will retain all database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR5, BR0, or R0 lithium battery or equivalent. For UL installations, refer to L-UL Hardware Installation Manual DOLUL-R0 for replacement procedures. TE: When setting up or servicing the EP-500, it is recommended to leave the battery bypass sleeve in place until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use. Explanation : S - Reset Switch Figure : RS-85 Sub-Panel Bus Termination Pressing the S - Reset Switch will cause the EP-500 to reboot. This process will T erase the system configuration and cardholder databases. (hannel Termination) The EP-500 has two distinct wire RS-85 sub-panel buses. Each bus needs to be terminated at both the beginning and ending points. J is the termination jumper for the hannel RS-85 Sub-Panel Bus. J5 is the termination jumper for the hannel RS-85 Sub-Panel Bus. (hannel Termination) (see Two Wire RS-85 Wiring diagram for sub-panel wiring information) Only Stand-Alone system was evaluated by UL 08 RS Technologies, LL. - All rights reserved. Refer to L-UL Hardware Installation Manual DOLUL-R

AX200. Installation Guide

AX200. Installation Guide Axxess Identification Ltd 27-28 Shrivenham Hundred Business Park, Watchfield, Swindon, Wiltshire SN6 8TZ United Kingdom Tel: +44 (0)1793 784002 Fax: +44 (0)1793 784005 Email: info@axxessid.com May 2008

More information

MR51e Reader Interface

MR51e Reader Interface J4 J TB6 TB5 TB4 TB3 VIN VO TB2 TB J7 2.75 [69.85] 0.2 [5.08] 2.35 [59.69] J3 MR5e Reader Interface Installation and Specifications. General: www.mercury-security.com 2355 MIRA MAR AVE. LONG BEACH, CA

More information

ACTpro Single Door IP Controller. Operating & Installation Instructions

ACTpro Single Door IP Controller. Operating & Installation Instructions ACTpro 1500 Single Door IP Controller Operating & Installation Instructions 18-00079 Issue 1 This manual refers to the ACTpro 1500 a TCP/IP based control unit supporting up to 32 doors. Access Control

More information

MR52 READER INTERFACE

MR52 READER INTERFACE IN IN2 IN3 IN4 INPUTS IN5 IN6 IN7 IN8 C www.mercury-security.com 2355 MIRA MAR AVE. LONG BEACH, CA 9085-755, (562)986-905 FAX (562) 986-9205 MR52 READER INTERFACE Installation and Specifications: This

More information

installation quick guide integrated access control & environmental monitoring

installation quick guide integrated access control & environmental monitoring installation quick guide integrated access control & environmental monitoring Introduction This Installation Quick Guide is suitable for standard wallmountable AX300 controllers. Illustrative technical

More information

EP1501 Intelligent Controller

EP1501 Intelligent Controller J6 BT K K2 TB5 TB 2.35 [59.69] 2.75 [69.85] EP50 Intelligent Controller with Paired Reader Interface for One Physical Barrier Installation and Specifications: www.mercury-security.com 2355 MIRA MAR AVE.

More information

MR50 READER INTERFACE

MR50 READER INTERFACE 2.75 [69.9] 2.35 [59.7] U1 MR50 READER INTERFAE Installation and Specifications: 1. General: www.mercury-security.com 2355 MIRA MAR AVE. LONG BEAH, A 90815-1755, (562)986-9105 FAX (562) 986-9205 This device

More information

Quick Start Installation Guide

Quick Start Installation Guide apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building

More information

Suprex Ethernet SPX-7200 Ethernet Reader-Extender

Suprex Ethernet SPX-7200 Ethernet Reader-Extender Suprex Ethernet SPX-7200 Ethernet Reader-Extender Product Manual 1 SPX-7200_MAN_181206 Cypress Integration Solutions 35 Years of Access Control Ingenuity CypressIntegration.com 2018 Cypress Computer Systems

More information

ACTpro 1500 Single Door IP Controller

ACTpro 1500 Single Door IP Controller ACTpro 1500 Single Door IP Controller ACTpro 1520 Single Door IP Controller with 12 V DC 2 amp power supply. Operating & Installation Instructions 18-00085 Issue 2 This manual refers to the ACTpro 1500

More information

emerge Essential Access Control System

emerge Essential Access Control System emerge Essential Access ontrol System Document Number: 620-100239, Rev. Installation Guide Linear LL 1950 amino Vida Roble, Suite 150 arlsbad, A 92008-6517 www.linearcorp.com Notices All rights strictly

More information

Quick Start Installation Guide

Quick Start Installation Guide istar Pro Quick Start Installation Guide Version B0 Part Number UM-069 January 2005 OVERVIEW This guide defines all of the commonly used connection methods to the istar Pro. It outlines how to wire readers

More information

SPX-7200 Series SPX-7200 EXP Operations Manual. Suprex Reader Extender - Ethernet SPX-7200_MAN_082112

SPX-7200 Series SPX-7200 EXP Operations Manual. Suprex Reader Extender - Ethernet SPX-7200_MAN_082112 SPX-7200 Series Operations Manual Suprex Reader Extender - Ethernet SPX-7200 EXP-2000 SPX-7200_MAN_082112 Cypress Suprex SPX-7200 Series Overview This manual covers the operation and setup of the Cypress

More information

Startup Guide. NetAXS-123. Version 5.2

Startup Guide. NetAXS-123. Version 5.2 NetAXS-123 Startup Guide Version 5.2 This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2)

More information

SPX-5000 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface. RPT GHz Repeater. SPX GHz

SPX-5000 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface. RPT GHz Repeater. SPX GHz SPX-5000 Series Operations Manual Suprex Reader Extender - RF Wireless Interface SPX-5601 2.4GHz RPT-5651 2.4GHz Repeater SPX-5521 900 Mhz IOX-7621 2.4GHz EXP-2000 SPX-6601 2.4GHz SPX-5000_MAN_082112 This

More information

The following are basic setup instructions for the LAN-520 AESP. Some settings may not apply to every application.

The following are basic setup instructions for the LAN-520 AESP. Some settings may not apply to every application. 1.0 Basic LAN Device Setup The following are basic setup instructions for the LAN-520 AESP. Some settings may not apply to every application. NOTE: The LAN-520 AESP is an updated version of Keri s LAN-520X

More information

UC-2000 Installation Manual Unicorn Computers Technology Limited

UC-2000 Installation Manual Unicorn Computers Technology Limited UC2000 Installation Manual Copyright 2003. All rights reserved. Table of Contents Specifications 2 Enclosure for the UC2000 Controller 3 Unicorn Access Control System Configuration 4 UC2000 Controller

More information

Access control panel U-Prox IC E (Elevator control)

Access control panel U-Prox IC E (Elevator control) 1.003 Access control panel U-Prox IC E (Elevator control) Installation and programming manual About this document http://u-prox.com This manual covers installation, adjustment and use of U-Prox IC E (hereinafter

More information

Suprex RF Series CYPRESS. Operations Manual. Suprex Reader Extender - RF Wireless Interface EXP SPX Mhz SPX-5521_MAN_0316

Suprex RF Series CYPRESS. Operations Manual. Suprex Reader Extender - RF Wireless Interface EXP SPX Mhz SPX-5521_MAN_0316 CYPRESS Suprex RF Series Operations Manual Suprex Reader Extender - RF Wireless Interface EXP-2000 SPX-5521 900 Mhz SPX-5521_MAN_0316 Cypress Suprex SPX-5521 Series Overview This manual covers the operation

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

Mercury Installation Manual

Mercury Installation Manual This document is a guide to successful integration of Mercury panels with Brivo Onair in two steps: a set of pre-installation procedures and associating the panel with Onair. If you have Mercury panels

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

Installation & User Manual

Installation & User Manual Contents Installation Instructions 3 Installation Diagrams 4 System Overview 6 Wiring Diagrams 8 Network Diagrams 9 Operation Instructions Fingerprint Enrollment 12 21 Wi-Enterprise Controller www.transmittersolutionssmart.com

More information

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 18 Input module (selectable polarity) with 3 outputs (selectable polarity) with 1 analog (selectable 0-5V or 4-20mA)

More information

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION

More information

EnerSure Installation Guide

EnerSure Installation Guide EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded

More information

PXL-250 Tiger Controller

PXL-250 Tiger Controller PXL-0 Tiger Controller This quick start guide is made up of specification sheets, a DO/DON T list, basic installation drawings, first time power-on instructions, and short descriptions of key terms and

More information

SPX-7400 Series. Operations Manual. Suprex Reader Extender - Fiber Optic Interface. SPX-7400 shown with EXP-2000 SPX-7400_MAN_082112

SPX-7400 Series. Operations Manual. Suprex Reader Extender - Fiber Optic Interface. SPX-7400 shown with EXP-2000 SPX-7400_MAN_082112 SPX-7400 Series Operations Manual Suprex Reader Extender - Fiber Optic Interface SPX-7400 shown with EXP-2000 SPX-7400_MAN_082112 This manual covers the operation and setup of the Cypress Suprex Fiber

More information

SPX-7400_SPX-7410_MAN_161028

SPX-7400_SPX-7410_MAN_161028 Suprex Fiber Optic SPX-7400 & SPX-7410 Suprex Reader-Extender Data Sheet SPX-7400 Series EXP-2000 SPX-7400_SPX-7410_MAN_161028 1 Cypress Suprex SPX-7400 & SPX-7410 Overview The Suprex Fiber Optic SPX-7400

More information

PRT-RDS2 Standard 2 Reader Expander

PRT-RDS2 Standard 2 Reader Expander PRT-RDS2 Standard 2 Reader Expander Installation Manual CONTENTS Protégé System... Introduction... Reader Expander... Features... Reader Expander Specifications... Protégé System Management Suite... Protégé

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

Technical Manual Nova: Cabinet Security Management System (CSMS)

Technical Manual Nova: Cabinet Security Management System (CSMS) Technical Manual Nova: Cabinet Security Management System (CSMS) KP_nova_TM_160501_EN 1 Publication May, 2016, Keyprocessor BV Paasheuvelweg 20 1105BJ Amsterdam, The Netherlands www.keyprocessor.com/nova

More information

Suprex RS-485 SPX-7500 Wired Reader-Extender

Suprex RS-485 SPX-7500 Wired Reader-Extender Suprex RS-485 SPX-7500 Wired Reader-Extender Product Manual SPX-7500_MAN_181206 Cypress Integration Solutions 35 Years of Access Control Ingenuity CypressIntegration.com 2018 Cypress Computer Systems 1778

More information

INDEX. Network Power Monitor R10 SNMP

INDEX. Network Power Monitor R10 SNMP Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX Amended 21 March 2017: Add user defined Password see page 13 Add wire Connection

More information

Wiring Guide. EP.NMiNi 2. Version 1.04 Last Updated:

Wiring Guide. EP.NMiNi 2. Version 1.04 Last Updated: Wiring Guide EP.NMiNi 2 Version 1.04 Last Updated: 31-01-2013 Before you begin Technical Support If you cannot find the answer to your question in this manual or in the Help files, we recommend you contact

More information

Ethernet Interface Module

Ethernet Interface Module Interface Manual 1 Ethernet Interface Module SignalFire Number: ENET-DIN The SignalFire Ethernet Gateway has the following features: - Wide range DC power input. 6 to 36VDC - Power Over Ethernet (POE)

More information

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor Innovative Electronics for a Changing World NPM-R10-SNMP Remote Network Power Monitor Optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. SYSTEM BATTERY CONNECTIONS 3. SERIES CONNECTED BATTERIES

More information

Installation & User Manual V2.08

Installation & User Manual V2.08 YOUR SECURITY IS OUR PRIORITY Other products from GSD Contents Installation Instructions Installation Diagrams System Overview Wiring Diagrams Network Diagrams Operation Instructions Fingerprint Enrollment

More information

CRC220 and CRC221 INSTALLATION GUIDE. REF No.: DOC0014 ISSUE: 09

CRC220 and CRC221 INSTALLATION GUIDE. REF No.: DOC0014 ISSUE: 09 CRC220 and CRC221 INSTALLATION GUIDE REF No.: DOC0014 ISSUE: 09 30th July 2015 2 Contents CRC220 & CRC221 INSTALLATION GUIDE 1. Scope 1-1 2. Introduction 2-1 2.1 Features 2-1 2.1.1. PCB Features 2-1 2.1.2.

More information

Quick Installation Manual

Quick Installation Manual Quick Installation Manual Please Note: Full Technical guide is located on the DVD if this is your first time installing a Hartmann Controls Access Control System. It is strongly recommended you review

More information

INSTALLATION INSTRUCTIONS 920 EntryCheck TM

INSTALLATION INSTRUCTIONS 920 EntryCheck TM 801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS 920 EntryCheck TM The EntryCheck 920 Indoor/Outdoor Keypad is a surface-mount

More information

CR3000 Copy Reader. Installation Guide

CR3000 Copy Reader. Installation Guide CR3000 Copy Reader Installation Guide CONTENTS CONTENTS 1 CR3000 Installation Guide 1 What you get: 2 Installation Overview 3 Install the Reader 4 Mount the Reader 4 Connect the Reader Cables 5 Connect

More information

2000 Series e/em Style Keypad Installation and Programming Manual

2000 Series e/em Style Keypad Installation and Programming Manual 2000 Series e/em Style Keypad Installation and Programming Manual Document Number: 6054022 Revision: 0 Date: 12/21/06 Table of Contents Table of Contents Section 1: Introduction... 6 1 Product Description...6

More information

INSTALLATION INSTRUCTIONS 923P EntryCheck TM

INSTALLATION INSTRUCTIONS 923P EntryCheck TM 801 Avenida Acaso, amarillo, a. 93012 (805) 494-0622 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUTIONS 923P Entryheck TM The Entryheck 923P Indoor/Outdoor Keypad is a surface

More information

Suprex Fiber Optic. Reader-Extender SPX-7400 SPX Product Manual. Reader-Extender. Manual. SPX-7400 Series EXP Suprex_FiberOptic_MAN_170502

Suprex Fiber Optic. Reader-Extender SPX-7400 SPX Product Manual. Reader-Extender. Manual. SPX-7400 Series EXP Suprex_FiberOptic_MAN_170502 Suprex Fiber Optic Reader-Extender SPX-7400 SPX-7410 Product Manual Reader-Extender Manual SPX-7400 Series EXP-2000 Suprex_FiberOptic_MAN_170502 Cypress Integration Solutions 30+ Years of Access Control

More information

GEM80 & ewon Setup Quick Guide

GEM80 & ewon Setup Quick Guide Introduction to the ewon The ewon is an intelligent, programmable Ethernet Gateway, which can be used to bridge GEM 80 PLCs onto an Ethernet network, via the PLC serial port (Port3). This provides network-based

More information

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 16 Output module (selectable polarity) P/N 610-00031 PAGE 1 of 10 1. REVISION LOG... 1 2. MODULE OVERVIEW... 2 2.1. SCOPE...

More information

Access Control System Document Number: , Rev. D. Installation Guide. Essential Essential Plus Elite 36 Elite 64

Access Control System Document Number: , Rev. D. Installation Guide. Essential Essential Plus Elite 36 Elite 64 Essential Essential Plus Elite 36 Elite 64 Access Control System Document Number: 620-100239, Rev. D Installation Guide USA & Canada (800) 421-1587 & (800) 392-0123 (760) 438-7000 - Toll Free FAX (800)

More information

IQ21x Series Controllers

IQ21x Series Controllers IQ1x Series Controllers IQ1x SERIES CONTROLLERS Description Features The IQ1x series of intelligent controllers are designed for use as unitary controllers in building control systems. Full compatibility

More information

F6-Fingerprint. Access Control/Reader. User Manual. F6 - Simplified Instruction. (Master Code) # (Factory default:1234) Enter the Programming Mode

F6-Fingerprint. Access Control/Reader. User Manual. F6 - Simplified Instruction. (Master Code) # (Factory default:1234) Enter the Programming Mode -Fingerprint Access Control/Reader Function Description Enter the Programming Mode - Simplified Instruction Operation (Factory default:1234) Change the Master Code Add Fingerprint User Add Card User Add

More information

6222 Two Door Module Technical Operations Manual

6222 Two Door Module Technical Operations Manual 6222 Two Door Module Technical Operations Manual TABLE OF CONTENTS Specifications...3 Overview...4 Operations...5 Custom Access Mode...5 Standard Access Mode...5 Offline Access Mode...5 Offline Memory...5

More information

QCPort Cover Control Trouble Shooting Guide

QCPort Cover Control Trouble Shooting Guide QCPort Cover Control Trouble Shooting Guide Technical Document Feb. 2006 Page 1 of 14 QCPort Cover Control Description Door Defeater Address/Options Bucket Latch Breaker Actuator Hasp Lock Keypad Overlay

More information

Quick Start Installation Guide

Quick Start Installation Guide RM-DCM-2 Quick Start Installation Guide Version G0 Document Part Number UM-215 May 2010 OVERVIEW The RM-DCM-2 is a UL294 Listed and UL1076 Listed door control module that includes the RM-4E Reader Module

More information

INSTALLATION INSTRUCTIONS 920P EntryCheck TM

INSTALLATION INSTRUCTIONS 920P EntryCheck TM 801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS 920P EntryCheck TM The EntryCheck 920P Indoor/Outdoor Keypad is a surface-mount

More information

PRT-RDE2 Ethernet 2 Reader Expander

PRT-RDE2 Ethernet 2 Reader Expander PRT-RDE2 Ethernet 2 Reader Expander Installation Manual PUBLICATION INFORMATION This manual covers firmware versions 1.44 or higher of the Protégé 2 Reader Ethernet Expander when operating on hardware

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

APSLAN. Communication converter APS mini Plus <-> Ethernet or WIEGAND -> Ethernet. User s Guide

APSLAN. Communication converter APS mini Plus <-> Ethernet or WIEGAND -> Ethernet. User s Guide APSLAN Communication converter APS mini Plus Ethernet or WIEGAND -> Ethernet User s Guide 2004 2014, TECH FASS s.r.o., Věštínská 1611/19, 153 00 Prague, Czech Republic, www.techfass.cz, techfass@techfass.cz

More information

FDW1000(M,S) OPTICAL WIEGAND, MAGSTRIPE & F/2F DATA EXTENDER INSTALLATION AND OPERATION MANUAL

FDW1000(M,S) OPTICAL WIEGAND, MAGSTRIPE & F/2F DATA EXTENDER INSTALLATION AND OPERATION MANUAL OPTICAL WIEGAND, MAGSTRIPE & F/2F DATA EXTENDER This manual serves the following ComNet Model Numbers: FDW00M/C FDW00S/C FDW00M/R FDW00S/R EXP0C EXP0R The ComNet FDW00 data extenders provide optical connectivity

More information

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel Ethernet Module ETHM-2 Firmware version 1.0 ethm2_en 09/08 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.pl SATEL's goal is to continually improve

More information

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT Installation Instructions i-net Access Control Units Part Code: IA-PCB IA-ACB IA-ACU IA-KIT This device is configured for DHCP. Identity Access software will find this device, go to setup and controller,

More information

DATA LOGGER GEOLOGGER G8 PLUS

DATA LOGGER GEOLOGGER G8 PLUS A D V A C E D DATA LOGGER GEOLOGGER G8 PLUS I N S T CONFIGURATION & WIRING OF PERIPHERALS R U C T I O N M A N U A L 1 CONTENTS DESCRIPTION PAGE Main components 3 G8 Module Connections 4 G8 Module Connections

More information

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications 12 Universal Expander Module. Installation Notes. Revision 1.2 August. 2003. 1 Reporting Reporting with most Contact ID maps will treat the Mini Expander, Exp32 and Exp16 as the same. (With the exception

More information

ICPDAS FSM-510G Series Ethernet Management Switch Quick Start

ICPDAS FSM-510G Series Ethernet Management Switch Quick Start ICPDAS FSM-510G Series Ethernet Management Switch Quick Start Version 1.0, Dec 2014 Overview The Management Ethernet Switch solutions are designed for supporting standard industrial applications. Managed

More information

Innovative Electronics for a Changing World. Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring

Innovative Electronics for a Changing World. Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring Innovative Electronics for a Changing World Charge Smart R1 MPPT 12V/24V Auto detect Mains and Solar Battery charger with Remote Network Monitoring INDEX 1. SYSTEM DESCRIPTION 2. SYSTEM WIRING 3. SYSTEM

More information

RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series

RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series RKAT Audit Trail Module RK-LINK TM Software For the Radio Key 600 Series INSTALLATION & OPERATING GUIDE Rev. B P/N 3321515 www.securakeystore.com (800) 878-7829 sales@securakeystore.com COPYRIGHT 2001

More information

IPassan Installation guide

IPassan Installation guide IPassan Installation guide 1 Content 1 Overview... 3 1.1 Features... 3 1.2 Hardware... 3 1.2.1 s... 3 1.2.2 Extra modules... 5 1.3 IPassan manager... 7 2 Installation... 7 2.1... 8 2.1.1 Power supply...

More information

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL Revision 2.1 July. 2014 1 Integriti 8 32 Zone LAN Expander Module Kit P/N: 996005PCB&K For Rev. B PCB. INSTALLATION MANUAL Overview The Integriti 8 Zone Expander Module provides an additional 8 Zone inputs,

More information

DX4020. Installation Guide. Network Interface Module

DX4020. Installation Guide. Network Interface Module DX4020 EN Installation Guide Network Interface Module DX4020 Installation Guide EN 2 Trademarks Microsoft - and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United

More information

Hardware Installation

Hardware Installation LOLM366912 The ipio-8 is a network attached, IP addressed digital input and output device. The ipio-8 can be controlled and monitored with a standard web browser. Multiple ipio-8 devices can communicate

More information

Security Management System by Diebold, Inc. LINX System Hardware Installation Guide

Security Management System by Diebold, Inc. LINX System Hardware Installation Guide Security Management System by Diebold, Inc. LINX System Hardware Installation Guide INSTALLATION GUIDE LINX Integrated Security System WSD 2000 Weatherized Status Display Table of Contents Introduction

More information

IP PUBLIC ADDRESS INTERFACE

IP PUBLIC ADDRESS INTERFACE AUTHOR DATE REFERENCE L. BRARD 01/10/07 Page 2/16 TABLE OF CONTENTS 1. INTRODUCTION... 3 2. DESCRIPTION... 3 2.1 OPERATING DIAGRAM... 3 2.2 CHARACTERISTICS... 4 3. OPERATION... 4 3.1 CONNECTION TO THE

More information

User Manual. cmt-svr Startup Guide

User Manual. cmt-svr Startup Guide User Manual cmt-svr Startup Guide Table of Contents Chapter 1 Overview... 1 1.1 Specification... 1 1.2 Dimensions... 2 1.3 Connector pin designations... 3 1.4 USB host port and SD card slot... 3 1.5 Ethernet

More information

LAN-505 Ethernet Communication

LAN-505 Ethernet Communication Ethernet Communication 1.0 Purpose of this Document This document discusses how to setup, configure, and use the Universal Device Server to provide LAN/WAN Ethernet connectivity between Doors and one or

More information

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM 2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM CONTENTS PAGE Manual Introduction 3 Product Overview 3 Operation and Connection 3 RS232 Connection 3-4 RS485 Connection 3-4 2214 PCB layout 5 RS485 Bus Terminal

More information

Connecting a Cisco Reader Module

Connecting a Cisco Reader Module CHAPTER 3 Overview The optional Cisco Reader Module (Figure 3-1) is similar to the Cisco Physical Access Gateway, providing the same ports for Weigand readers and other input and output devices. The Cisco

More information

Basic Mercury Powered NXT Controller Configuration

Basic Mercury Powered NXT Controller Configuration Doors.NET installation and controller configuration is a three step process. Each of these steps is covered separately in the help file and there are also separate standalone documents available: 1. Doors.NET

More information

Access Easy Controller

Access Easy Controller Access Easy Controller Quick Start Guide en Quick Start Guide Ver..0.0 All rights reserved. No part of this manual may be reproduced, stored in a retrieval system, or transmitted in any form or by any

More information

mark150s mark150/485s DDC controllers Summary

mark150s mark150/485s DDC controllers Summary mark150s mark150/485s DDC controllers Summary DDC (Direct digital control) controller mark150s and mark150/485s are free programmable process stations with ARM Cortex M4 processor and OS FreeRTOS. They

More information

SNAP, CLICK, DONE. Getting Started Guide

SNAP, CLICK, DONE. Getting Started Guide SNAP, CLICK, DONE. Getting Started Guide Introducing Sateon Advance Sateon Advance offers a flexible new approach to access control, with a new range of hardware and software products. The hardware is

More information

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client User Manual V1.0.0 Table of Contents Overview... 1 1.1. Specification... 1 1.2. Dimensions... 2 1.3. Connector pinouts... 3 1.4. Restoring factory default... 3 1.5. LED indicator... 3 1.6. CR1225 battery...

More information

801 Avenida Acaso, Camarillo, Ca (805) Fax: (805)

801 Avenida Acaso, Camarillo, Ca (805) Fax: (805) 801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com IP Pro IP-Based Single Door Controller Operations & Installation Manual P:\INSTALLATION

More information

epad 5.0 Mobile Keypad

epad 5.0 Mobile Keypad Programming Guide epad 5.0 Mobile Keypad Description Providing much-needed flexibility, the epad 5.0 Mobile Keypad allows users to control their DMP security system using an Internet browser. The epad

More information

SINGLE READER EXPANSION MODULE

SINGLE READER EXPANSION MODULE SINGLE READER EXPANSION MODULE INSTALLATION GUIDE A D C - A C X 1 TR- SINGLE READER EXPANSION MODULE The ADC-ACX1 Single Reader Expansion Module provides a solution for interfacing to a one Wiegand reader

More information

1. Features. 2. Installation KNX INTEGRATION MODULE INT-KNX

1. Features. 2. Installation KNX INTEGRATION MODULE INT-KNX KNX INTEGRATION MODULE INT-KNX int-knx_en 09/11 The INT-KNX module integrates the INTEGRA alarm system with the KNX system, so the control panel can control the actuators connected to the KNX bus, and

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2 NET101 RS232 / RS422 / RS485 to Ethernet Converter User s Manual Version 1.2 Copyright Information Copyright 2004-2005, Mega System Technologies, Inc. All rights reserved. Reproduction without permission

More information

PRT-PX16 16 PGM Output Expander

PRT-PX16 16 PGM Output Expander PRT-PX16 16 PGM Output Expander Installation Manual CONTENTS Protégé System Introduction... PGM Expander... Features... PGM Expander Specifications... Protégé System Management Suite... Protégé Modules...

More information

NordField Electronics

NordField Electronics NordField Electronics XS1000 TCP/IP to RS232/422/485 Device Server Overview and quick info sheet 3.0. Hardware Installation & Initial Setup 3.1 RS-232 Configuration:(DB9 Male) (DB9Male) Signal I/O PIN2

More information

Poseidon 4002 MANUAL

Poseidon 4002 MANUAL Poseidon 4002 MANUAL Poseidon 4002 MANUAL POWER input 12VDC supply (jack or terminals) INPUTS Binary inputs 1 6 (for contacts) OUTPUTS Two 50V rated switchover relay contacts ETHERNET 10 or 100/10 Mbps

More information

GV-AS200 Controller. Hardware Installation Guide

GV-AS200 Controller. Hardware Installation Guide GV-AS200 Controller Hardware Installation Guide Before attempting to connect or operate this product, please read these instructions carefully and save this manual for future use. 2008 GeoVision, Inc.

More information

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed Infinity ACX 700 Access Control Unit The Infinity ACX 700 is a programmable, stand-alone access controller that is a basic building block of the Infinity Security Management System. Each ACX 700 controls

More information

User Manual Electronic Systems Protection, Inc. / Technical Support: / espei.com

User Manual Electronic Systems Protection, Inc. / Technical Support: / espei.com RP-IP RP-IP-GNS User Manual 2014 Electronic Systems Protection, Inc. / Technical Support: 1-800-645-9721 / espei.com 2014 Electronic Systems Protection, Inc. / Technical Support: 1-800-645-9721 / espei.com

More information

EQ7000. User Manual. Rev 1.00

EQ7000. User Manual. Rev 1.00 EQ7000 User Manual Rev 1.00 www.equustek.com Revision 1.00 February 27, 2009 Contents INTRODUCTION...4 ABOUT THIS MANUAL...4 INTENDED AUDIENCE...4 HARDWARE SPECIFICATIONS...5 PHYSICAL SPECIFICATIONS...5

More information

MRDT Display Terminal

MRDT Display Terminal www.mercury-security.com 2355 MIRA MAR AVE. LONG BEACH, CA 90815-1755, (562)986-9105 FAX (562) 986-9205 MRDT Display Terminal Installation and Specifications: This device complies with part 15 of the FCC

More information

Conettix ITS-D6682-INTL

Conettix ITS-D6682-INTL Conettix ITS-D6682-INTL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6682-INTL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

Quick Start Guide. 2-Port 10/100 Device Server RS-232/422/485 DB9 M. Access two serial RS-232 or RS-422/485 devices over a 10- or 100-Mbps network.

Quick Start Guide. 2-Port 10/100 Device Server RS-232/422/485 DB9 M. Access two serial RS-232 or RS-422/485 devices over a 10- or 100-Mbps network. LES302A LES302A-KIT LES302AE-KIT 2-Port 10/100 Device Server RS-232/422/485 DB9 M Quick Start Guide Access two serial RS-232 or RS-422/485 devices over a 10- or 100-Mbps network. Customer Support Information

More information

KP2000E/EM Series Style Keypad

KP2000E/EM Series Style Keypad 23852973 KP2000E/EM Series Style Keypad Installation and Programming Instructions Models KP2000EXX and KP2000EMXX Specifications Parameter Voltage Requirements Keypad Current Requirements (Max) Relay Contact

More information

FSM-510G Series Ethernet Management Switch Quick Start Guide

FSM-510G Series Ethernet Management Switch Quick Start Guide FSM-510G Series Ethernet Management Switch Quick Start Guide Overview The Management Ethernet Switch solutions are designed for supporting standard industrial applications. Managed switches are easily

More information

CYPRESS " " EXP SPX Expansion interface! modules EXP-2000_MAN_0314

CYPRESS   EXP SPX Expansion interface! modules EXP-2000_MAN_0314 CYPRESS EXP-2000 SPX Expansion interface! modules The EXP-2000 provides additional Door/Panel interface points to most SPX products. The EXP-2000 uses a local RS-485 network through an SPX gateway device.

More information