Technology Standards
|
|
- Malcolm Poole
- 5 years ago
- Views:
Transcription
1 June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the attached Technology Standards. Technology Standards Revision - 9 April 211
2 Table of Contents INTRODUCTION... 5 CONTRACTOR REQUIREMENTS... 5 DEFINITIONS... 5 A. Terms... 5 B. Abbreviations and Acronyms... 5 STANDARDS... 5 DESIGN REQUIREMENTS... 6 TOPOLOGY... 6 A. Inter-Building Fiber Optic Cable... 6 B. Intra-Building Fiber Optic Cable... 7 Table 1 Fiber Transmission Performance... 7 C. Inter-Building Multipair UTP... 7 D. Intra-Building Multipair UTP... 7 HORIZONTAL/STATION CABLE... 7 Figure 1- Network Topology (VoIP)... 8 TELECOMMUNICATION ROOM OVERVIEW... 8 A. TELECOMMUNICATIONS ROOMS... 8 B. MDF... 9 C. BDF... 9 D. IDF... 9 E. Environmental Control...1 F. Telecommunication Racks...1 G. Power Distribution...1 H. Plywood Backboard...11 I. Through Wall Penetrations...11 J. Conduits...11 K. Ladder Tray and cable support systems...11 L. Service Entrance...11 M. Grounding...12 N. Work space...12 O. Four Post Racks...12 P. Lighting...12 Q. Access doors...12 R. Clearance and Ceiling height...12 S. Flooring...12 TELECOMMUNICATIONS OUTLETS...13 A. Standard Telecommunications Outlet...13 B. Classroom and Office Outlets...13 D. Wall Phone Outlet...13 E. Labeling...14 Figure 2- Sample Telecommunications Outlet Faceplate...14 Label Criteria for outlet coming from BDF, Rack 1, Patch Panel 1, and ports ADMINISTRATION...14 A. Voice Connections...14 B. Data Connections...14 C. Fiber Optic Jumpers...15 LABELING AND DOCUMENTATION...15 ii
3 A. Inter-Building Backbone Cabling...15 B. Intra-Building Backbone Cabling...15 C. Faceplates...15 D. Horizontal Cabling...16 TESTING...16 A. Fiber Optic Backbone...16 B. UTP Backbone...16 C. Horizontal/Station Cabling...16 LOW VOLTAGE AS-BUILT DOCUMENTATION...17 A. General...17 CABLING PATHWAYS...17 A. Open Cabling...17 B. Conduits...17 C. Cable Tray...18 D. Fire Stopping...18 Figure 3 Label for Firewall Penetrations...19 E. Surface Mounted Raceway...19 WIRELESS ACCESS POINT...2 A. General...2 B. Power...2 C. Wireless Access Point Locations...2 DIGITAL SIGNAGE...2 A. Power Requirements...21 B. Conduit and Data Outlet...21 C. Wall Support Backing...21 CLASSROOM MEDIA STANDARDS...21 A. Media Equipped Classroom...21 B. Pathway Standards...21 C. Classroom Lighting Zone Diagram...22 AV Classroom Elevation Figures 1A and 1B...23 AV Conference Room Elevation Figures 2A and 2B...24 AV Classroom Layout Figure AV Classroom Reflected Ceiling Plan Figure AV Technology Podium Elevation Figures 5A and 5B...27 AV Technology Desk Style Podium Elevation Figure AV Wide Classroom View with Technology Podium Figure AV Classroom View with Technology Podium Figure AV Video Conference Room Figures 9A and 9B...31 APPENDIX A INSIDE CONDUIT AND PATHWAY REQUIREMENTS...32 A. Conduit...32 B. Wireways...32 C. Pathway...32 APPENDIX B OUTSIDE PLANT CONDUIT AND VAULT DETAIL...33 A. Outside Plant Conduit...33 B. Installation...33 C. Design Elements...33 D. Vaults...34 E. Loading Requirements:...34 APPENDIX C OUTSIDE CONDUIT SYSTEM AND VAULT INSTALLATION...35 GUIDELINES...35 A. Vault Placement and Security...35 iii
4 B. Drainage...35 C. Vault Racking and Space Allocations...35 D. Conduit Allocation and Fill Procedures...35 APPENDIX D PRE-APPROVED PRODUCT SET...36 A. Approved Part Numbers APPENDIX E MAIN DISTRIBUTION FRAME (TYPICAL)...41 APPENDIX F BUILDING DISTRIBUTION FRAME (TYPICAL)...42 APPENDIX G INTERMEDIATE DISTRIBUTION FRAME (TYPICAL)...43 APPENDIX H MDF/BDF BAYFACE (TYPICAL)...44 APPENDIX I IDF BAYFACE (TYPICAL)...45 APPENDIX J BONDING AND GROUNDING DETAIL...46 A. Bonding...46 Table 2 Bonding Conductor Sizing...46 B. Grounding...47 C. Labeling, Color-Coding, and Marking...47 Figure 4: Label for Grounding and Bonding Conductors...47 D. Telecommunications Main Grounding Busbar (TMGB)...47 E. Bonding to a Panel Board...48 F. Connections to the Telecommunications Main Grounding Busbar...48 G. Installation Requirements...48 H. Bonding Conductor for Telecommunications...48 I. Telecommunications Bonding Backbone ( TBB )...49 J. Bonding and Sizing the TBB...49 K. Telecommunications Grounding Busbar...49 L. Bonding to the TGB...5 M. Bonding to the Metal Building Frame...5 APPENDIX K - GLOSSARY...51 iv
5 INTRODUCTION This document addresses telecommunications infrastructure standards. The requirements specified are based on current (PCC) and industry standards. This document will be used by PCC staff and consulting Architects, Engineers, and Designers working for the College on projects in new or existing facilities requiring the design and installation of telecommunications distribution systems. This guide and accompanying specifications serve as the basis for the construction documents to ensure uniformity and consistency of the telecommunication systems installed. Any exceptions to these standards must be reviewed and approved by the Technical Services Division Manager on a per project basis. CONTRACTOR REQUIREMENTS Workmanship shall be of the best quality and competent and experienced low voltage electricians shall be employed and shall be under the direct supervision of a competent and experienced foreman. Cabling vendor must be a certified Panduit installer with a current Panduit license to install. At least 5% of the Cabling contractor's personnel working on the project must be certified installers. Panduit certification and warranty testing results will be provided to Architect, Owner or Authorized Representative. DEFINITIONS A. Terms The terms College and Owner as used in this document represent Portland Community College. B. Abbreviations and Acronyms The college will utilize the following terminology when referencing telecommunications rooms and facilities, specifically: Main Distribution Frame or MDF An entrance to a campus for both public and private network service cables (including wireless) including the entrance point of the building and continuing to the entrance room or space. The MDF also serves as a BDF. Building Distribution Frame (BDF) An environmentally controlled centralized space for telecommunications equipment that usually houses a point of entry from the main building crossconnect. Intermediate Distribution Frame (IDF) An environmentally controlled enclosed architectural space designed to contain telecommunications equipment, cable terminations, or cross-connect cabling. Telecommunications Room as used in this document refers to the MDF, BDF, or IDF in generic terms, as a point for termination of telecommunications cables. STANDARDS All telecommunication distribution designs shall be based on and shall comply with the following industry standards. ANSI/TIA/EIA A Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant-OFSTP-14A. ANSI/TIA/-568-C: Generic Telecommunications Cabling for Customer Premises April 211 Page 5
6 ANSI/TIA/-568-C: Commercial Building Telecommunications Cabling Standard ANSI/TIA/EIA-568-C: Commercial Building Telecommunications Cabling Standard, Part 2: Balanced Twisted Pair Cabling ANSI/TIA/ -568-C: Optical Fiber Cabling Components Standard, June 28 TIA -569-B: Commercial Building Standard for Telecommunications Pathways and Spaces ANSI/TIA/EIA-598-Color Coding of Fiber optic Cables. ANSI/TIA/EIA-66-A. The Administration Standard for the Telecommunications infrastructure of Commercial Building ANSI-J-STD-67-A-22. Commercial Building Grounding and Bonding Requirements for Telecommunications ANSI/TIA/EIA-758. Customer Owned Outside Plant Telecommunications Cabling Standard NFPA-7, National Electric Code (NEC) All above referenced documents are to be latest version, including addendum, in publication at time work is requested. In addition to the above telecommunications standards, all design documents shall comply with codes and requirements of the local Authority Having Jurisdiction (AHJ). DESIGN REQUIREMENTS The telecommunication distribution system design shall provide a cost effective standards based structured cabling system that is capable of supporting current and future voice, video and data applications over a common cabling plant. The system shall support at a minimum IEEE 82.3 Ethernet applications including 1Base-T, 1Base-TX, 1Base-T, and 1Base-TX in the horizontal link and 1GBase-x in the backbone connections. TOPOLOGY The telecommunication distribution system shall be a hierarchical star topology consisting of backbone cables connecting the Main Distribution Frame ( MDF ) to Building Distribution Frame ( BDF ) or Intermediate Distribution Frame ( IDF ). Horizontal cables shall be installed from each Telecommunication Outlet ( TO ) to the nearest telecommunications room serving that area of the building. A. Inter-Building Fiber Optic Cable The inter-building fiber optic cable will be a composite construction with 48 strands of 5/125μm laser optimized multimode and 12 strands of single mode combined under a common jacket. Fiber shall be tight buffer and jacket ratings shall be suitable for indoor-outdoor placement without need for fan-out assemblies prior to termination within a building. The fiber will meet the specifications listed in ANSI/TIA/EIA 568-C and the transmission performance parameters listed in Table 1. Inter-building fiber cables shall be installed within 1" orange inner duct. Coordinate with TSS Department for exact fiber requirements. The fiber optic strands shall be terminated with LC type connectors. The LC will have a ceramic ferule and will be attached to each fiber strand with either a heat cure or anaerobic type epoxy. In large buildings with more than 4 stories, containing a BDF and three (3) IDFs, an additional 12 strands of 5/125μm multimode will be required for each additional IDF in the building if such may be accomplished within the 55 meter limitation noted below. April 211 Page 6
7 B. Intra-Building Fiber Optic Cable The intra-building fiber optic cable will be 12 strands 5/125μm multimode fiber. Fiber shall be tight buffer and jacket ratings shall be suitable for application. The fiber will meet the specifications listed in ANSI/TIA/EIA 568-C and the transmission performance parameters listed in Table 1. In new construction or substantial remodel of an existing facility, intra-building shall be 12 strands 5/125µm Laser Enhanced multimode utilizing factory assembled pre-terminated MTP connectors. Rating shall be OFNP. All intra-building fiber cables shall be installed within 1" orange inner duct. between the BDF and the IDF shall not exceed 55 m (164 ft). The distance The fiber optic strands shall be terminated with LC type connectors. The LC will have a ceramic ferule and will be attached to each fiber strand with either a heat cure or anaerobic type epoxy. Optical fiber cable type Wavelength (nm) Maximum attenuation (db/km) 5/125µm multimode /125µm multimode Single mode Single mode C. Inter-Building Multipair UTP Table 1 Fiber Transmission Performance The Inter-Building backbone copper cables shall be a multipair, Category 3 cable from the campus MDF to the building BDF. The cable shall consist of an ASP sheath with 24 AWG solidcopper conductors encapsulated with water blocking gel filling compound for moisture protection. The multipair UTP will meet or exceed the mechanical and transmission specifications of ANSI/TIA/EIA-568-C. A minimum 25 pair UTP shall be installed per Telecommunications Room. In large buildings with more than 4 stories, containing a BDF and three (3) IDFs, an additional 25 pair of category 3 backbone cable will be required for each additional IDF in the building. Coordinate with TSS Department for exact backbone copper requirements. D. Intra-Building Multipair UTP Intra-building copper backbone shall be 25 pair 24 AWG. Jacket shall be suitably rated for application but in no case less than CMR. The cable will meet or exceed the performance and transmission specifications of ANSI/TIA/EIA-568-C requirements for Category 3. In large buildings with more than 4 stories, containing a BDF and three (3) IDFs, an additional 25 pair of category 3 backbone cable will be required for each additional IDF in the building. Coordinate with TSS Department for exact backbone copper requirements. HORIZONTAL/STATION CABLE The horizontal station cables shall be 1 ohm, 4-pair; Blue category 6 plenum rated UTP cables. The length of each horizontal cable shall not exceed 9 meters (295 feet) regardless of medium. One end of a horizontal cable shall terminate at the Telecommunications Outlet. The other end of a horizontal cable shall terminate on a rack mounted modular patch panel located April 211 Page 7
8 in the nearest Telecommunication Room. Copper based patch panels shall typically be 48 ports with 24 ports as specified by PCC project team. All horizontal station cables will have a 1' service loop coiled at the workstation end of the cable to support future cable relocations. Utility Copper Modular Patch Panels Horizontal (Station) Cable Main Distribution Frame (MDF) Building Distribution Frame (BDF) Network Hardware w/poe 11 Wiring Blocks 11 Wiring Blocks Fiber Patch Panel Inbound Services Telecommunications Room (IDF) Network Core Fiber Patch Panel Fiber Patch Panel VoIP Platform Network Hardware w/poe Utility Copper Utility Copper Modular Patch Panels Horizontal (Station) Cable Modular Patch Panels Network Hardware w/poe Fiber Patch Panel Telecommunications Room (IDF) Horizontal (Station) Cable Figure 1- Network Topology (VoIP) TELECOMMUNICATION ROOM OVERVIEW The term Telecommunications Room is defined spaces where telecommunications cables are terminated and cross connected to appropriate resources. A finer definition and exacting operation criteria are provided below for spaces used to terminate cable, cross connect telecommunications circuits and install various active electronic components. A. TELECOMMUNICATIONS ROOMS A Telecommunication Room (TR) is a dedicated, secure, and environmentally controlled space used to terminate telecommunications cabling and house connecting hardware and networking equipment. There are several types of Telecommunications Rooms, specifically: April 211 Page 8
9 Main Distribution Frame (MDF) - There will be one (1) MDF at each PCC campus or center. The MDF serves as the demarcation point for service providers and PCC. All external telecommunications service providers (voice, video and data) will hand off their services to PCC at the demarcation point established in the MDF. The MDF also serves as the central point that connects inter-building cables. The MDF houses the core telephone and network equipment used to communicate between buildings, campuses or centers, and the public switched network. The MDF will serve as an IDF for all voice, data, and video connections with-in 9 meters of the MDF. Building Distribution Frame (BDF) - There will be one (1) BDF for each building at a campus or center. The BDF serves at the point of entry for inter-building cables. The BDF will have intra-building connections of fiber, copper, between itself and all IDF(s) in a building. The BDF will serve as an IDF for all voice, data, and video connections within 9 meters of the BDF. The BDF houses the network and video equipment used to support voice, data and video in the building. Intermediate Distribution Frame (IDF) - A building will have one or more IDF s if the building has more than one floor or if the distance between the BDF and longest horizontal (station) cable run from the BDF exceeds 9 meters. An IDF provides the voice connection and the data and video connection(s) to an office, classroom, lab, common area, or work space in a building. The IDF houses the equipment used to support voice, data and video in a section of a building. B. MDF At a minimum every College educational or administrative facility shall have a MDF. Where the size of the facility dictates, IDFs shall be provided. The MDF will serve as the connection point to the College s Wide Area Network ( WAN ) and the service entrance facility and demarcation point for Telco and alternate service providers. The MDF will also house the voice system, security, access control and video distribution head ends. It is imperative that the MDF be sized adequately to accommodate each of these systems. The minimum recommended MDF size in new construction projects shall never be smaller than 2' x 3' (6 square feet). The MDF will be located on the first floor. C. BDF The BDF shall be centrally located within a building to minimize horizontal cable lengths and the number of IDFs required. The BDF shall be located on the first floor, and shall be dedicated to the telecommunications function and related support facilities. BDF size in new construction projects shall never be smaller than 15' x 2' (3 square feet) with two horizontal wall dimensions being no less than 15 feet. The BDF will be larger in buildings over 6, square feet. The TR should not be shared with electrical installations other than those for telecommunications. Equipment not related to the support of the telecommunications room (e.g., piping, ductwork, pneumatic tubing, etc.) shall not be installed in, pass through, or enter the Telecommunications Rooms. D. IDF In cases where horizontal cabling lengths exceed 9 meters, an Intermediate Distribution Frame (IDF) is required. The IDF shall meet all of the environmental conditions specified for a BDF in regard to HVAC and power. The IDF shall provide cross connect and interconnect facilities between horizontal cabling serving a portion of the facility and the backbone cabling to the BDF. April 211 Page 9
10 The IDF shall be a dedicated space. The minimum size of an IDF shall be 1 x 15 (15 square feet). If additional racks are required in an IDF to provide mounting space for the required hardware and equipment then the IDF shall be sized to accommodate the racks necessary and provide 3 of clearance in front of, behind and on one end of the racks. E. Environmental Control Environmental control systems shall be provided to the TR on a 24 hours-per-day, 365 daysper-year basis to monitor and maintain acceptable temperature and humidity levels. The systems shall provide cooling to maintain a temperature range of 64 F to 75 F with 3% to 5% relative humidity. A neutral pressure shall be maintained with a minimum of one air exchange per hour. At a minimum, the HVAC system must be capable of removing 7, BTU per hour from the telecom room. If a standalone air conditioning unit is used within the TR, it may be wall mounted or hung from the ceiling. If hung from the ceiling the bottom of the unit must be a minimum of 8 6 above the finished floor. The air conditioning unit shall not be located over the telecommunication equipment. The air conditioning unit shall serve only the TR and a thermostat to control the unit shall be located in the TR. The mechanical condensate piping shall be located away from racks and equipment and shall drain outside the TR. The air conditioning unit shall be capable of and configured for automatic restart following a power failure. F. Telecommunication Racks The BDF shall contain two or more 19 x 7 freestanding telecommunications equipment racks and a least one 4 post rack for mounting patch panels, cable management and networking equipment such as routers and switches. Racks shall be arranged side by side in a row to facilitate routing of cabling between patch panels and the networking equipment. The quantity of racks shall be determined by quantity and type of patch panels and networking equipment required. The racks shall be ganged with 1 wide double sided vertical management hardware placed between the racks and 6 vertical wire management at the outside ends of the row of racks. Racks shall be placed in a manner that will allow a minimum of 3 feet of clearance from the front, plus 42 inches for the rack and equipment with 3 feet clearance in rear and on one side. If one mounting rail of the rack is placed against a wall, the mounting rail shall be no closer than 6 to the wall to allow room for vertical management. G. Power Distribution Minimum standard is below. Specifications will call out power distribution as required on a project basis. Each TR shall be equipped with a rack mounted Uninterruptible Power Supply (UPS) provided and installed by the Contractor. UPS shall be sized to accommodate projected equipment load with a thirty percent (3%) expansion factor. UPS input power will be a 28 volt, 3/4/6/1 amps or as specified mounted at the bottom of the equipment rack the vertical wire manager. Additional duplex convenience outlets shall be placed at 6-foot intervals around the perimeter of the room at 18 inches above the finished floor. Provide two horizontal power strips for each freestanding rack. The power strips shall have a minimum of nine (9) outlets, rated at 2 amps. See Appendix D for Approved Product Manufacturer.. April 211 Page 1
11 H. Plywood Backboard TELECOMMUNICATION INFRASTRUCTURE STANDARDS Backboards; Fire-retardant treated plywood, 3/4 by 48 by 96 inches (19 by 122 by 244 mm). Comply with requirements for plywood backing panels specified in Division 6 Section "Rough Carpentry." Covering all walls. Backboards are to start 6" above finished floor ( AFF ) and extend to a height of 8.6'. Install backboards with 96-inch (244-mm) dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints. Painted with two (2) coats of paint. Painted finish in the room will be light colored to enhance room lighting. One (1) fire-retardant stamp is to be left unpainted on the bottom of each individual piece of fire-retardant plywood. I. Through Wall Penetrations All horizontal penetrations into the TR shall be accomplished using EZ Path System Series 44+ manufactured by Specified Technologies, Inc. This is a re-enterable product that provides code compliant fire barrier protection without the use of caulk or putty. Quantities shall be determined by number of cables required and systems supported. Provide separate pathway for each system. J. Conduits Conduit will typically enter the BDF under slab and shall be either 2 or 4 in diameter. Conduits entering the BDF through the floor shall extend 3 to 6 above the finished floor. Conduits may only enter the BDF from overhead if such is part of an assembly required to bridge inaccessible space directly adjacent to the BDF. Such conduits shall be routed to the cable tray. Conduits shall be bonded to the Telecommunication Main Grounding Bus Bar (TMGB), with a minimum of a #6 THHN green wire or as indicated in Table 2 of Appendix J. K. Ladder Tray and cable support systems A ladder tray shall be installed around the perimeter of all TRs at 86 above finished floor ( AFF ). The ladder tray shall support cables routed from the EZ Path Series 44+ and conduits to connecting hardware located in racks and wall mounted equipment and 11 fields. The ladder tray shall be sized to accommodate the quantity of cables required and shall comply with the current NEC and ANSI/TIA/EIA fill ratios. The ladder tray shall be a minimum of 12 wide. Ladder tray shall include a cable drop out accessory where cables exit tray. Ladder tray shall be extended to and firmly affixed upon the telecommunication racks and secured to the top of the racks using mounting plates and J-bolts in accordance with manufacturer s instructions. D-ring pathways shall be provided on backboards for routing cabling to wall mounted 11 crossconnect fields and wall mounted equipment. D-rings shall also be mounted between adjacent 11 columns to provide a vertical cable management channel for cross-connect wires. L. Service Entrance For new construction projects, a utility vault shall be placed at the property line and a minimum of (2) 4 schedule 4 PVC conduits shall be provided from the vault to the MDF. For the design process conduits should be installed on an N + 1 basis, see design documents for validation. One (1) 2 schedule 4 PVC conduit shall be provided for the Cable TV service provider. The College shall verify with service providers their requirements for routing the service entrance conduits and communications vaults on the site. April 211 Page 11
12 Innerduct shall be installed in all four inch entrance conduits. Size and quantity of innerduct will be specified when initial service is requested. A minimum of 4 x 4 space shall be provided on the backboard for each service provider. M. Grounding In new construction, or substantial remodel, it is the responsibility of the Electrical Engineer to specify a Telecommunications Bonding Backbone ( TBB ) that complies with the above referenced Standard. It is typically a 1/ (or larger) bare stranded copper cable that is bonded to the Telecommunications Main Grounding Buss bar ( TMGB ) at the BDF and to a Telecommunications Grounding Buss bar (TBB) at each of the IDFs. The initial component of this work is accomplished by the electrical contractor as part of the rough-in package with the actual grounding bars being installed as a part of the final trim-out. All racks, ladder tray and conduit shall be grounded with #6 AWG copper conductor to the TMGB. Refer to Appendix J for further detail. N. Work space The MDF shall have a dedicated work space that allows a 3" X 6" work surface. The work space shall have a minimum of one dedicated 12 volt 2 amps, double duplex receptacle. The work space shall have a Telecommunications Outlet configured with a minimum of four jacks. All TRs shall be equipped with a wall phone. O. Four Post Racks Space shall be allocated in the MDF for four post racks. The four post racks shall be floormounted and shall require a 24 x 48 floor space and 48 front and 36 rear clearance for servicing the equipment. PCC staff shall be consulted as the number of spaces to be reserved in the MDF on a building-by-building basis. P. Lighting Lighting shall be a minimum of 5 foot candles, (5 lumens) measured 3 feet above the finished floor. Placement of lighting shall be coordinated to avoid obstacles such as cable trays that obstruct light. Q. Access doors Doors shall open out from Telecommunications Rooms (MDF, BDF, and IDF) wherever possible and shall be a minimum of 36" wide and 8" high. Room access will be controlled by card readers. Door will be fitted with a lock that can override the card reader, which is keyed as specified by TSS for Telecommunications Rooms. Doors shall be located in hallways or other common areas. In no case shall the door be located in another building occupants designated space. R. Clearance and Ceiling height Minimum clearance height within a Telecommunications Room shall be 8, 6. False ceilings (tbar ceilings, ceiling grids, etc.) shall not be installed in Telecommunications Rooms. S. Flooring The floors for new construction will be sealed concrete. On remodel projects the floors, walls, and ceilings shall be sealed to reduce dust. Flooring materials with anti-static properties - carpet is not acceptable for Telecommunications Rooms. April 211 Page 12
13 TELECOMMUNICATIONS OUTLETS The term Telecommunications Outlet (TO) encompass a broad set of jacks and plugs locations where physical connectivity is provided for a network device. Exacting criteria by type is provided below. A. Standard Telecommunications Outlet A standard wall telecommunications outlet shall be a flush mount faceplate containing three 3 telecommunication jacks. Classroom podium outlets require four (4) telecommunication jacks. Each telecommunications device shall be a Category 6, 8-pin modular jack wired in a T568A pinout. Coordinate with TSS Department for exact outlet requirements. The standard Telecommunications Outlet shall be housed in a recessed 2-1/8 deep x 4 square outlet box flush to the wall with 5/8 single gang mud ring. A one inch conduit and pull string shall be installed from the outlet box to an accessible ceiling space. Appropriately rated bushings shall be installed on the end of the conduit stubbing into the accessible ceiling space. The standard faceplate shall be a vertical single gang frame manufactured from high-impact thermoplastic material. The faceplate shall be available in 4 and 6 port configurations. Faceplates shall be mounted to recessed outlet boxes in the wall. Faceplates must be of a design that allows permanent labeling that remains intact while allowing removal and reinstallation of the plate. B. Classroom and Office Outlets Standard classrooms require one (1) standard floor box outlet and one (1) standard ceiling box outlet. Refer to Figure 2. Offices require two (2) standard wall outlets on opposite walls in the room. Outlet locations are to be coordinated with furniture layout on drawings. Surface Mounted Outlet In retrofit and remodel projects where cabling cannot be routed within the wall, the outlet shall be surface mounted. Where the outlet is surface mounted, the cabling to the outlet shall be installed within a surface raceway. The size of the raceway shall be specified on a case by case basis, but at a minimum, the raceway shall have a one inch cross sectional area. Telecommunication Outlets shall be surface mount outlet boxes compatible with the raceway specified. The surface mount outlet boxes shall be deep versions with a divider wall to maintain separation of power and data cables and allow for termination of both services in one outlet box. For larger raceways a device bracket shall be available for mounting of devices within the raceway. Where surface raceway is used, the faceplate shall be mounted on a single gang surface mount boxes. Faceplates must be of a design that allows permanent labeling that remains intact while allowing removal and reinstallation of the plate. D. Wall Phone Outlet Wall phone outlets shall be a flush or surface mounted to a single gang outlet box. The outlet shall be mounted so the highest operable mechanism is in compliance with ADA requirements. The faceplate shall be stainless steel with keystone opening capable of accepting an 8-pin modular insert. Faceplate shall be equipped with studs for mounting a wall phone. April 211 Page 13
14 E. Labeling TELECOMMUNICATION INFRASTRUCTURE STANDARDS All telecommunication outlets shall be labeled in accordance with TIA/EIA-66-A and conform to Section 13 below. The labels shall be typed or machine-engraved. The label shall identify the Telecommunication Room, patch panel and port on the patch panel that the horizontal cable terminates. Telecommunication outlet labels shall be installed in a manner that does not cover the faceplate attachment screws. Figure 2- Sample Telecommunications Outlet Faceplate Label Criteria for outlet coming from BDF, Rack 1, Patch Panel 1, and ports 5-8. ADMINISTRATION A. Voice Connections The voice ports will be connected to the active equipment using RJ45 to RJ45 modular patch cords. All patch cables will be red factory terminated category 6 and installed to length (maximum 1 of slack). B. Data Connections The data ports will be connected to the backbone termination field using RJ45 to RJ45 modular patch cords. All patch cords will be [white] factory terminated category 6 and installed to length (maximum 1 of slack). Patch cords and station cable will be equal in Category to the installed cable and be stranded unshielded twisted pair (UTP). Patch cords will be used between patch panels and active electronics. Lengths will be kept to a minimum while remaining with standard, manufactured lengths. Likewise, station cords will be stranded unshielded twisted pair in lengths that allow proper routing and minimize coils or slack cable length. In no case will station cords be run across open spaces or taped to the floor. April 211 Page 14
15 C. Fiber Optic Jumpers Install factory terminated fiber optic duplex jumpers between equipment and fiber panels. A PCC representative shall determine the actual size and configuration of the jumpers based on the network design (SC to SC, SC to ST, ST to ST, LC to LC etc.). LABELING AND DOCUMENTATION Labels shall be affixed in permanent manner using sleeve or wrap around methods. All labels shall be machine printed with a minimum font size of 12 with black lettering on white background. Refer to Figure 2. A. Inter-Building Backbone Cabling Backbone cables shall be labeled within 24 of the cable termination. Labels will contain information clearly identifying both ends of the run using the following nomenclature: MDF to BBB,RRR,TT,CCC, where: MDF = Main Distribution Frame (Only one per campus or center.) BBB = Three (3) letter building designation RRR = Destination Room in the Building (BDF, IDF1, IDF2, IDF3, etc) TT = Type of Cable (MM for Multimode, SM for Single Mode, CP for Copper, CX for Coaxial) CCC = Pair or Strand Count (12 pair, 24 pair, 48 pair, 3 pair, etc.) Example 1 - A 48 pair of Multimode fiber between the Main Distribution Frame and Health Technology (HT) Building Telecommunications Room would have the following label: MDF to HT,BDF,MM,48 Example 2 - A12 pair single mode fiber between the Main Distribution Frame and Health Technology (HT) Building BDF would have the following label: MDF to HT,BDF,SM,12 B. Intra-Building Backbone Cabling Intra-building cables shall be labeled within 24 of the cable termination. Labels will contain information clearly identifying both ends of the run using the following nomenclature: From xx to RRR where: xx= Main Telecommunications Room or Telecommunications Room RRR = Destination Room in the Building (IDF1, IDF2, IDF3, etc) For example, a 12 pair Multimode fiber between the BDF and IDF2 in a building From BDF to IDF2 C. Faceplates Faceplates labels shall be provided to clearly identify each location with the following information: IDF.RN.PP.NN where, IDF = Telecommunications Room servicing the outlet RN = Rack number within the IDF PP = Patch panel within the rack NN = port number (1-48) within the patch panel For example, a faceplate housing four jacks supported from Telecommunications Room 1, third rack, second patch panel, first four ports would be labeled: April 211 Page 15
16 D. Horizontal Cabling All horizontal/station cables will be labeled 4 from the termination at each end. The labels will conform to the following format: IDF.RN.PP.NN where, IDF = Telecommunications Room servicing the outlet RN = Rack number within the IDF PP = Patch panel within the rack NN = port number (1-48) within the patch panel For example IDF 1, Rack 3, Patch Panel 2, Cable 4: TESTING Cabling vendor must be a certified Panduit installer with a current Panduit license to install. At least 5% of the Cabling contractor's personal working on the project must be certified installers. See division 27 requirements for providing license. A. Fiber Optic Backbone Test all fibers of each installed fiber optic segment for end-to-end attenuation in both directions through the fiber patch panels using a power meter and stabilized light source. Test each fiber segment for end-to-end, splice and attenuation using a recording OTDR. The contractor shall provide PCC with a paper copy and an electronic copy of the test results. B. UTP Backbone Test each multipair backbone cable for continuity, capacitance, resistance, opens, grounds, shorts, and rolled pairs. C. Horizontal/Station Cabling Panduit certification and warranty test results must be provided for all locations. Testing documentation will be included with all new projects. Hard copy output indicating successful testing of every location is not required, rather a CD or DVD containing the test data and the appropriate application to display such in a Windows based environment, i.e., Fluke viewer programs. All Category 6 cable paths shall be tested at each jack for the following parameters and meet the requirements imposed by the ANSI/TIA/EIA 568-C building wiring and the manufacture s written specification, specifically: Wire Map Cable Length Pair-to-pair NEXT Power Sum NEXT Attenuation Pair-to-Pair ELFEXT Power Sum ELFEXT Return Loss Propagation Delay Delay Skew April 211 Page 16
17 LOW VOLTAGE AS-BUILT DOCUMENTATION A. General As-built documentation for telecommunications infrastructure is required upon completion of a project. For all projects, the following are the minimum documentation requirements: Complete plans of the new facility showing locations for Telecommunications Room(s) and Telecommunications Outlets. All Telecommunications Outlet locations will be annotated with the above detailed label criteria. This document will be provided electronically in PDF format as well as hard copy. Cable routing showing the pathway(s) in the facility and the point of connection to the outside plant conduit system. This will include information on the number and sizes of each conduit. This document will be provided electronically in PDF format as well as hard copy and may be combined with the above as a separate layer. CABLING PATHWAYS Installation of Raceways/Pathways for telecommunication distribution systems shall be in accordance with applicable portions of TIA-569-B. Horizontal cabling shall be routed from each Telecommunication Outlet to an IDF using a combination of boxes, conduit, open cabling supports and cable tray. In new construction, cabling pathways shall be concealed in walls, casework, concrete slabs and above ceilings whenever possible. In renovations to existing spaces, the horizontal and backbone cabling may be routed in surface raceway when no other cost effective options exist. Spare conduits shall be included as a part of any construction that entails hard ceiling to allow future placement of cables without disturbing the ceiling. A minimum of two, 4 conduits shall be placed in areas where hard ceilings extend beyond four feet from accessible spaces. Conduits are to be labeled as Telecommunications Spare and fire stopped as per requirements of the Authority Having Jurisdiction (AHJ). A. Open Cabling Horizontal cabling may be routed using open cabling supports above accessible ceilings, crawl spaces, mechanical attics and similar spaces when cable tray is not available. Open cabling supports shall be installed parallel or at right angles to the building structure and shall be permanently anchored to building structure or substrates using beam clamps, drop wire or threaded rod hanger brackets. Open cabling supports shall be J-hook type cable supports with an open-top and wide base designed for supporting telecommunications cabling. J-hook supports shall be spaced no further than 48 apart and shall be sized in accordance with manufacturer s recommendations for quantity of cables supported. Fiber optic backbone cabling shall be installed with inner duct when routed using open cabling methods. B. Conduits A conduit pathway shall be provided for horizontal and backbone cabling routed in inaccessible spaces including walls, floors, and ceilings. They shall route to accessible ceiling space. Conduits to Telecommunication Outlets shall be a minimum of 1 diameter. Conduit pathways and sleeves shall be EMT conduit. All conduits shall have appropriate bushings installed on the April 211 Page 17
18 ends prior to cabling being pulled. In case EMT conduit cannot be used 1-1/4 flexible metallic conduit may be used. Nylon pull strings shall be provided in all conduit sleeves and pathways. Telecommunications Outlet conduit runs shall be less than 1 in length and contain no more than two 9-degree bends. Conduit shall be sized to accommodate initial cable requirements plus a fifty percent (5%) expansion without exceeding then-current NEC fill ratio requirements. All conduits shall be supported independently of the ceiling support system. Provide EZ Path System Series 44+ (as See Telecommunication Overview Section I) for wall penetrations. EZ Path Series 44+ shall be provided where cabling passes through a fire-rated assembly of 18 or less. Conduit sleeves that protrude through a floor shall terminate 3" to 6" above the surface of the floor. Backbone cabling shall be routed in separate conduits from horizontal cabling. Under slab conduits shall be home run to the telecom rooms as shown on the drawings. Cables installed in under slab conduits shall be manufactured with jackets rated for damp or wet locations and employ proper moisture blocking techniques in construction. C. Cable Tray Large bundles of horizontal and backbone cabling installed outside of a IDF shall be routed within a cable tray located in accessible ceilings above corridors and other spaces. Cable tray for distribution of cabling shall be wire basket cable management system constructed of a continuous welded steel wire mesh with an electroplated zinc galvanized finish. A divider strip may be installed in the cable tray to provide separation between each of the telecommunication systems in the project. The cable tray and partitions created by the divider strips shall be sized to maintain a 4% fill ratio for each of the cabling systems. Maximum depth of cabling shall be 6. Cable tray shall have minimum dimensions of 12 wide x 4 deep. Cable tray shall not be installed through a rated wall, rather stopped on both sides and used in conjunction with EZ Path System Series 44+ to provide approved barrier and ease of re-entry. Cable trays shall be properly grounded in accordance with NEC and ANSI-J-STD-67-A-22 requirements. Cable trays shall be supported with cantilever wall brackets, trapeze hangers, and center support hangers or other support systems approved by the manufacturer. D. Fire Stopping All penetrations through fire-rated building structures (walls and floors) shall be sealed with an appropriate fire stop system. This requirement applies to through penetrations (complete penetration) and membrane penetrations (through one side of a hollow fire rated structure). Label all firewall penetrations as indicated on Figure 3. April 211 Page 18
19 Any penetrations created by or for the contractor and left unused shall also be sealed as part of the contractor s scope of work. EZ Path System Series 44+ shall be used in conjunction with cable trays to provide a reenterable system allowing telecommunication cables to be easily removed or added in the future. Fire stop systems shall be UL Classified to ASTM E814 (UL 1479). All fire stop systems shall be installed in accordance with the current NEC, NFPA 5 and the manufacturer s recommendations and shall be accomplished in a manner acceptable to the local fire and building authorities having jurisdiction over this work. E. Surface Mounted Raceway WARNING FIRESTOPPING DO NOT DISTURB NOTIFY BUILDING MANAGEMENT OF ANY DAMAGE INSTALLED ON CONTRACTOR WALL RATING 1hr 2hr 4hr (Circle one) Figure 3 Label for Firewall Penetrations Surface mounted raceway ( SMR ) refers to a surface mounted raceway system used for routing telecommunication cabling to outlets on existing solid walls or walls with fire-blocking. Surface raceways may be omitted where access into existing walls is available. See Appendix D for approved products. Horizontal SMR in lab environment shall be installed below the work surface height of computer tables. SMR shall be UL listed and approved for the intended applications by the AHJ. SMR shall be sized to accommodate initial cable requirements plus a fifty percent (5%) expansion without exceeding then-current NEC fill ratio requirements. SMR shall be provided with all fittings including but not limited to mounting clips and straps, couplings, flat, bend limiting internal and external elbows, cover clips, bushings, device boxes and other incidental and miscellaneous hardware required for a complete SMR system. Fittings/bends shall be sized to accommodate Category 6 and fiber optic bend radii as specified in TIA/EIA 568-C. SMR finish shall match as close as possible the finish of the wall it is to be mounted on. SMR shall not be installed through walls. SMR shall be securely supported using mechanical fasteners at intervals not exceeding 5 feet and in accordance with manufacturer s installation instructions. The path of the raceway shall be selected to minimize impact on existing molding, tack boards and other architectural elements. Vertical runs of raceway from the ceiling to outlets shall be installed on walls near corners wherever possible. Raceway may be installed horizontally at the same height as the outlets or near to the ceiling. Entrance end fittings will be supplied at the ends of raceway runs to transition to conduit sleeves through walls, ceilings or floors. SMR shall be installed parallel and perpendicular to surfaces or exposed structural members, and follow surface contours where possible. Metal raceway, bases, covers and dividers shall be bonded and grounded in accordance with applicable code and ANSI-J-STD-67-A-22 April 211 Page 19
20 WIRELESS ACCESS POINT A. General TELECOMMUNICATION INFRASTRUCTURE STANDARDS All new construction and renovation projects should include provisions for a wireless access point ( WAP ). The low voltage contractor will install cabling and WAPs. The provisions shall provide pathways, Category 6 cable, and outlets to support placement of WAPs. Design shall be in compliance with guidelines of TSB-162, Telecommunications Guidelines for Wireless Access Points. The placement of the Wireless Access Points should provide coverage in all classrooms, offices, corridors and public meeting spaces and will be specified or approved by PCC TSS staff. B. Power Power to Wireless Access Points shall be provided by Power over Ethernet ( PoE ) switches located in the nearest Telecommunication Room. C. Wireless Access Point Locations Outside Locations o The design should be based on the coverage range for IEEE 82.11b/g and IEEE 82.11n WAPs. The Wireless Access Points shall be located so that each Access Point covers an area with a radius of no more than 1. o One Category 6 UTP horizontal cable will be installed from the serving IDF to the Wireless Access Point location to provide for interconnection to the wired infrastructure. o Minimum height for the ground is 12 and no more than 2. Inside Locations o The design should be based on the coverage range for IEEE 82.11b/g and IEEE 82.11n WAPs. The Wireless Access Points shall be located so that each Access Point covers an area with a radius of no more than 6. o Two (2) Category 6 UTP horizontal cable will be installed from the serving IDF to the Wireless Access Point location to provide for interconnection to the wired infrastructure. o The horizontal cable shall be terminated on a Category 6, 8-pin modular connector. The connector shall be mounted in a surface mount outlet box mounted adjacent to the Wireless Access Point location. o A 4-foot service loop shall be coiled in the ceiling space above the WAP without exceeding the manufacturer s bend radius. o Minimum height from the ground is 12 and no more than 2'. o WAP should be located at least 2 from EMI sources DIGITAL SIGNAGE The size and location of Digital Signage screens will be determined by the design team, TSS Media Services, and PCC marketing teams. The Digital Signs may be interactive and associated with the building management system, way finding, college information, and public safety. April 211 Page 2
21 A. Power Requirements TELECOMMUNICATION INFRASTRUCTURE STANDARDS A single duplex outlet is required to support electronic equipment. See Architectural Drawings for elevations. B. Conduit and Data Outlet One Category 6 UTP horizontal cable will be installed from the serving IDF to 6" from power outlet. See Architectural Drawings for elevations. C. Wall Support Backing Wall support backing should be rated for a minimum of 75 lbs to support monitor and mounting bracket. Note Backing may need to be increased for 5" or larger monitors. The locations of the power an data outlets need to be coordinated with TSS Media Services to insure that the screen mount does not conflict with the outlet locations. See Architectural Drawings for elevations. CLASSROOM MEDIA STANDARDS A. Media Equipped Classroom In all classrooms the contractor will provide a floor box, conduit pathway, power, data and a ceiling box to support media presentation technologies. See Appendix D for Approved Product Manufacturers. An owner installed media equipped lectern will be placed over the floor box in the classroom. See Media Classroom Technology Figures 1-9 below. B. Pathway Standards Minimum pathway and connectivity requirements for all classroom media construction are as follows. The media conduit pathways will be local to the classroom. Floor Box: One floor box will be installed in the front corner of the room beneath the teaching station location. The placement will be a minimum of 5'-6" from each wall to allow for ADA requirements. See Appendix D for Approved Product Manufacturers. The floor box will require: o One (1) 1¼ conduit for low voltage video cable o One (1) 1 conduit for low voltage audio cable o One (1) ¾ conduit for dedicated 2 amp 11v electrical cable o One (1) 1 conduit for four (4) network data cables o See Media Figure 7 below Ceiling Box: One ceiling box will be installed in the ceiling grid at the projector location. The ceiling box acts as a junction box for wiring for power, data, and media wiring in the ceiling. The architect must confirm the throw distance, aspect ratio, and location for the ceiling box being installed during the design phase for each building with TSS Media Services o The ceiling box will be mounted 14 feet from the center of an 8 or 9 foot screen. o The ceiling box will be centered with the screen. o See Media Figure 7 below. o See Appendix D for Approved Product Manufacturers. Connectivity between the Floor Box and the Ceiling Box will require two (2) conduits: o One (1) 1¼ conduit for low voltage video cable April 211 Page 21
22 o One (1) 1 conduit for low voltage audio cable o Conduits will utilize the shortest path within the classroom walls o No hard 9 degree bends will be accepted. o See Media Figures 7 and 8 below. Power: A dedicated 11v 2 amp breaker servicing both the ceiling and floor boxes will be required. o One (1) duplex 11v connection will be installed in the ceiling box enclosure. o One (1) duplex 11v connection will be installed in the floor box at the designated teaching station location. VoIP Phone/Data: Four (4) data cables will be routed and terminated in the covered floor box and two (2) data cables will be routed and terminated in the ceiling box. Projector Cabling: Media cable connecting the teaching station to the projector and speakers will be provided by TSS Media Services and installed by the contractor. Speakers: Two (2) ceiling speakers will be utilized in all rooms with suspended ceilings. Speakers will be mounted 5 feet 6 inches from either side of projector. A ¾ inch conduit will be installed to connect the speakers. Screens: will be provided by the contractor, be a minimum of 8 feet wide and wall mounted. The aspect ratio of the screen will be determined by the design team with input from the TSS Media Services. Media Storage Closet: Each new building should have a media storage closet centrally located with a minimum dimension of 1 feet x 1 feet. There should be at least one 11v duplex outlet for equipment testing located near the door. C. Classroom Lighting Media Figure 4 below illustrates lighting zone requirements in a technology equipped classroom. A minimum of two (2) independently switched zones are represented. Low voltage lighting interface is desirable. Otherwise the main lighting control should be mounted near the teaching station with an entry switch near the door. Lighting fixtures should not be low hanging reflective instruments. These types of fixtures place limits on location and sight lines of ceiling mounted projectors. April 211 Page 22
23 -- RETRACTABLE '--' -- PROJECTION SCREEN "\.._ (") ON N Q) _Dl.:::: ro o._o... (f) n:: z f- (f) w n:: ::J f- ::J n:: f- (f) Ill T"" n:: lz L "C - c: z ItS T"" f- Cl) z c.. ụ. ::I ::J C) WHilE BOARD DATA _.POWER OU1l T TYPICAL CLASS RM ELEVATION (HEAD OF 1 PROJECTOR CEILING BOX - TIED INTO - u:: DISTANCE TO SCREEN PER ANUF. INSTRUCTON c: (I w :.;: UGHT & VOLUME IJ # (I _j ItS CONTROL w > 4 o l f-.9:! w E... Cl) Cl) ItS (.) D D I I.Ml 1 I, , (I (I t- 5'-6" MIN -----, V"ODIUM CLASS) I r1b\ TYPICAL CLASS RM EL VATION (RIGHT OF HEAD C. --, ) > c "(j) m.> DlQ) md:: (/) >."E :t= ro cu ::J c Ell EW >. ODl u_q c - ro..c c t () Q) O...f-
24 T"""...;:t T"""N OQ.) > c ro o..o... (/) ::: z I- (/) w ::: ::J I- Ill N ::J ' ::: r:::::: I- cu (/) ::: N z zll tn s... :::l C') i= L1. r:::::: z :,i:i ::J cu > Q) w w _J E w I- ::: Q) r:::::: Q) r1 r1 I > CEILING MOUNTED PROJECTOR, DIST. FROM SCREEN WALL PER MANUF , CONFERENCE TABLE WHITt CONFERENCE ROOM I r 1 I WALL PLATE COMPUTER & VIDEA CENTER W/ SEPARATE CONTROL PANEL o l o -qnr I!I FINISHED - -- WALL PLATE COMPUTER/VIDEO CONTROL FA WALL FLOOR I I I ;., "(j) WHITE BOARD I I -r---r I Q.) ::;: O>Q.) a.>o::: I OCJ) >."E r:::::: () c-o :::J c C ' L I CLOSE VIEW OF E$ E(f) COMPUTER/VIDEO >. INTERFACE(S) > ""O_Q c ro c - t::u..c CONFERENCE ROOM (J) c
25 AV Classroom Layout Figure 3 TELECOMMUNICATION INFRASTRUCTURE STANDARDS " p 'TJ t..l -u - )> I I )> (f) (f) :;o c ITI Ul " -u I )> z + N ITI "' I z ITI "' Technology Standards- Revision 9 April211 Page 25
26 ...--(()...-N Q.) _> c ro a..o... Cf) ::: z ZONE 1 I- Cf) w ::: ::::> I- () ::::> ::: -.::1' e t I- CL Cf) :::l ::: C) LL z i.l z c:.!!! i= a.. () C) z c: ::::> Q) (..) '..., () Q) w (.) _J Q) w I- ;;::: E a.. tn tn.!!! (..) ENTRY LIGHT- CONTROL PATH OF CONDUIT(S) ABOVE I HUNG CEILING L t J I II II I II BELOW 11 APPROX. 5'-6" IU APPROX. 5'-6" --m-+ +::t:--j I I I 1 i I io CLASS ROOM AREA UGH I " CLASS ROOM AREA LIGH ZONE 2 II ll II II CEILING BOX IN DROP] II CEILING, PROJECTOR CLASS ROOM AREA LIGHi ZONE 1 CEILIQ OUNTED SPEAKII:RS CLASS ROOM AREA UGH I ZONE 2 TECHNOLOGY PODIUM BELOW,- l I MAIN LIGHT CONTROL -- 5'-6" f'4'\ TYPICAL CLASS RM REFLECTED CEILING PLAN \!V a> c "(j) Q.) ::;: O>Q.) Q.)::: ol ()CJ) >."E ro C"O :::J c E2 Ecn >. ()O> "O.Q c ro c -..c t::u Q.)...1--
27 DISPLAY SCRFFN (' N Q.) _> c ro a..o... I- () ' u :. :. : z co ::::> > Q) w () E w :::l _J w ' I- a.. > PLACARD Ht--- 1 DRAWER W/ KEYBOARD I (V CONTROL SYSTE Cf) DVD/VCR COM jljl.f I Ill ::: HINGED ACC AV RECEIVE - u Tlr PANEL COMPUTER -!!. z TOWER I- Cf) w FRONT TOWARDS I L.. J I II " I Ei$ II, I FLOOR BOX ::: m CLASS INTERIOR I ICJfi I+' ::::> It') ::::> c: co ::: I- Cf) It') tn Q) a.. :::l z z.2> u. i= c: () :.;; C) c: J: (.) Q) I- (5A\ CRESTRON CONTROL PANEL W/ TOUCH SCREEN TELEPHONE EQUIPMENT ACCESS REAR LOGY PODIUM FLOOR BOX (58\ TECHN 1 LOGY PODIUM ELEVATION ro 1" ---, I a> I I c L _j Co '<I- "(j) Q.) ::;: O>Q.) Q.)::: ol ()CJ) >."E ro C""O :::J c E2 Ecn >. ()O> ""O.Q c ro c -..c t::u Q.)...1--
28 DISPLAY SCREEN N OQ.) > c ro a..o... Cf) ::: z I- Cf) w (. ::: Q) REAR ::::> a.. I- :::l () C) ::::> ::: u. I- c: Cf) :.;; ::: LL co z > Q) z w i= E :::l () ' z ::::> a.. Q)..., () en w _J w tn c I- Q) C) c: J: (.) Q) I- > -:.r... I"') '<I- I "N L--- FRONT TOWARDS CLASS ;--- FLOOR BOX./. HINGED ACCESS PANEL(S) DVD/VCR COM AV RECEIVER I I --U---- COMPUTER 11---L TOWER - 1 ' 1 I l / SIDE (6\ALTERNATE DESK STYLE PODIUM I"')..., a> c "(j) Q.) ::;: O>Q.) Q.)::: ol ()CJ) >."E ro C"'O :::J c E2 Ecn >. ()O> "'O.Q c ro c -..c t::u Q.)...1--
29 r- (]) ON N Q) _Dl.:::: ro o..o... (f) n:: z r-.. C... 1> f- ::::s (f) w n:: ::J C) LL E f- ::::s - 3/J,." CONDUIT - ::J "C n:: FOR POWER f- CONNECll\'llY - (f) c.. Win-liN WALL >. n:: C) lz L 1" CONDUIT - FOR LOW VOLTAGE CABUNG - WITHIN WALL z I:.I: 1 1/J,." CONDUIT - f- u FOR AUDIOVISUAL C1> CABUNC - WITHIN -I- WALL z.i: ::J C1> w _j > E w f-... Cl) Cl) ra (.) C1> "C 3:._- - i-+ 1" CONDUIT- FOR NETWORK DATA_. - WllHIN WALL _ "TECHNOLOGY PODIU ----== ---= =::;;;;;; ==== ---= RETRACTABLE PROJEC ON SCREEN _j ======== === WHITE BOARD (7\ TYPICAL VIEW OF CLASS ROOM W/TECHNOLOGY PODIUM - (]) c "(j) m.> DlQ) md:: ol (/) >."E :t= ro cu ::J c Ell EW >. ODl ""D_Q c ro c -..c t () Q) O...f-
30 AV Classroom View with Technology Podium Figure 8 ---j -u < - )> r < 1'1 '1 I )> (}) (}) ::;o ---j 1'1 ::r:: z r G) --< -o c Ul r;:l!: lie ::til:(') g ritjzo wo;:;j!; --j 56c:i! :!i o iz ;c o :: :i!sllll :z,o r-x 8 ::tl \ \ Technology Standards- Revision 9 April 211 Page 3
31 CEILING BOX - ned INTO DROP CEILING STRUCT.,l.ND SECURED TO STRUCT. CEILING RETR,l.CT,l.BLIE SCREEN r- r- ( J Q) _Dl.:::: ro o..o... (f) n:: z f- (f) w n:: ::J f- ::J n:: Ill ') f- (f) "C n:: l c: "' z L ') z (I) QJ f-... ::: w QJ _j (J w c: QJ "C CEILING MOUNTEID PRo.JECTOR, DIST. FROM SCREEN W.A.LL PER M.A.NUF ,..., r I I CONFERENCE T,l.BLE II I I II II II WHITt BO.A.RD I C l L VIDEO CONFERENCE ROOM :::::J N z u:: ::J E f- Q... J..!! c: (.) ALTERNATE "PROFESSION STYLE POOIU -} FLIP UP.A.DDinON.A.L VIDEO CONFERENCE ROOM :; I l j-1 I I II II II II I FLOOR BOX 2'-1" WALL PLATE COf.lPUTER/VIDEO CONTROL WHITE BOAAD. I II I I o l <D o l o C 1 L COMPUTER DEO > CONNECnON c (j) ". Q) s;: >1 I < - II DlQ) I md:: I -;... CLOL VIE W OF PODIUM FLOOR BOX (/) >.'E :t= ro cu ::J c Ell EW >. ODl u..q c ro c -..c () t Q) O...f-
32 APPENDIX A INSIDE CONDUIT AND PATHWAY REQUIREMENTS A. Conduit The following types of conduit are approved for interior uses: Rigid galvanized conduit, zinc coated and manufactured in accordance with UL-6, ANSI and Federal Specification WW-C-54 standards Intermediate Metal Conduit (IMC), zinc coated galvanized steel to comply with UL-1242, Type J and ANSI Standards Electrical Metallic Tubing (EMT), zinc-coated steel to comply with UL-797 and ANSI Standards Liquid tight flexible metal conduit, zinc steel core with smooth gray abrasion resistant, liquid tight, polyvinyl chloride covering (with integral ground wire wound in steel core), to comply with UL36 and ANSI Standards. Anaconda Sealtite type U.A or similar Flexible metal conduit, to comply with UL36, ANSI Standards and Federal Specification WW B. Wireways The following are approved: Non-exposed, all steel in construction with screw covers. All surfaces shall be coated with a rust preventing coating with final finish being gray. Surface raceway, may be steel or UL listed non-metallic product. Where power and signal (low voltage) cables share a common pathway, an approved divider must be present. All fittings and transitions pieces are to be of the same manufacturer, however, power and low voltage receptacles may be from a different manufacturer so long as the product is designed to be an integral part of the completed system. In addition, where a metallic system is specified, the following requirements apply: o Material is to be grounded to known source of building ground o All cut edges that will be exposed to cable shall be finished with a grommet or dielectric bushing material to protect cable from chaffing. o All visible cuts shall be painted to match overall color of product. C. Pathway Pathway shall conform to the requirements of TIA 569-B specifically: o The scope of this Standard is limited to the telecommunications aspect of commercial building design and construction, encompassing telecommunications considerations both within and between buildings. o Telecommunications aspects are generally the pathways into which telecommunications media are placed and the rooms and areas associated with the building used to terminate media and install telecommunications equipment. o The scope is limited only to the telecommunications aspect of building design, this Standard significantly influences the design of other building services, such as electrical power and HVAC. This Standard also impacts space allocation within the building. April 211 Page 32
33 APPENDIX B OUTSIDE PLANT CONDUIT AND VAULT DETAIL A. Outside Plant Conduit All conduits installed outside are considered subsurface pathways. Approved conduit types are: EB-2 for encasement in concrete; EB-35 for encasement in concrete; DB-6 for direct burial or encasement in concrete; DB-1 for direct burial or encasement in concrete; DB-12 for direct burial or encasement in concrete; Rigid Nonmetallic Conduit Schedule 4 for direct burial or encasement in concrete; Rigid Nonmetallic Conduit Schedule 8 for direct burial or encasement in concrete; Multiple Plastic Duct (MPD) for direct burial or installation in conduit; Rigid Metallic Conduit for direct burial or encasement in concrete; Intermediate Metallic Conduit for direct burial or encasement in concrete; Fiberglass Duct for direct burial or encasement in concrete; Innerduct Polyethylene (PE) for direct burial or installation in conduit; Innerduct Polyvinyl Chloride (PVC) for direct burial or installation in conduit. B. Installation Installation shall conform to the following: Encased buried (EB-2) and direct-buried (DB-6) conduit shall meet NEMA standard TC-6. Encased buried (EB-35) and direct-buried (DB-12) conduit shall meet NEMA standard TC-8. Schedule 4 and Schedule 8 Rigid Nonmetallic conduit shall meet NEMA standard TC-2. Nonmetallic conduits shall be encased in concrete of minimum 17,225 kpa (25 lb/in 2) compressive strength where vehicular traffic (i.e., automotive, railway) is above the pathway, or where a bend or sweep is placed. All bends shall be sweeps with a minimum radius of six times the internal diameter (ID) for conduits up to 2 inch and ten times the ID for all conduits larger than 2 inch. C. Design Elements The following is a list of construction elements that need to be considered in the design and installation of subsurface pathways. Excavation; Clearances and separations from other utilities; Depth of burial; Buried street crossings; Casing; Trenching; Boring (pipe pushing); Plowing; Backfill; and, Restore landscape. April 211 Page 33
34 D. Vaults All vaults shall meet the following criteria; Corrosion resistance of metal components. ASTM B 117 salt spray test for (3) days; Chemical resistance of nonmetallic components (gasoline, kerosene, acid/base etc.) ASTM D543; UV degradation of nonmetallic components. ASTM G 53 for (9 days - UVB-313 lamps); Resistance to flame or fire RUS Specification PE-35 or ASTM D 635. E. Loading Requirements: Light duty (pedestrian traffic only), designed for protected areas only. (Test load 1361 kg [3 lb] over 254 mm by 254 mm [1 in by 1 in] area with 13 mm [.5 in] maximum deflection); H-5, designed for sidewalk applications and for occasional non-deliberate traffic (test load 5118 kg (11284 lb) over 254 mm by 254 mm [1 in by 1 in] area with 13 mm [.5 in] maximum deflection); H-1, designed for driveways, parking lots and off road application subject to occasional non-deliberate heavy vehicles (test load 22,568 lbs. over 254 mm by 254 mm [1 in by 1 in] area with 13 mm [.5 in] maximum deflection); and H-2, designed for deliberate heavy vehicular traffic. April 211 Page 34
35 APPENDIX C OUTSIDE CONDUIT SYSTEM AND VAULT INSTALLATION GUIDELINES Outside plant conduit and vault systems installed at facilities require unique and careful planning prior to placement. In most installations, the conduit duct bank is designed to include electrical, security, pneumatic control systems, video distribution, and telecommunications. The duct bank typically runs parallel to or at right angles from the major structures. Duct banks may be encased at bends or for their entire runs in concrete. As such, it is imperative to allocate pathway for the immediate needs, but to include a one hundred percent growth factor for future systems that will be required over the life span of the institution. A. Vault Placement and Security Vaults are in almost all cases; shared among low voltage applications, i.e., telecommunications, alarm, security, video, HVAC control systems, etc. Sizing and placement of the vaults requires consideration of the likelihood of re-entry and the physical security required for protection against unauthorized access. B. Drainage Installation of vaults should be such that water drainage will continue after the installation. In some instances the soil grading will be sufficient, while in other instances gravel may have to be placed at specified depths. The vault may be located below grade, in which case locator stakes or location devices should be employed. The location of the vault should be away from traffic conditions that could cause injury to personnel, yet it should be easily accessible for maintenance. C. Vault Racking and Space Allocations Approved vaults range in size from 4 x 4 x 6 up to 8 x 8.x 12. Conduits enter and exit these vaults in a variety of sizes and configurations. Allocation of space needs to be coordinated with all systems that will transverse the vault. For telecommunications systems, the following guidelines apply: o Splicing of fiber and copper cabling is not allowed. o Fiber optic cable will be completely encased in innerduct. The innerduct will be labeled as it passes through the vault. o Copper tie and supply cables passing though vaults and be likewise labeled. D. Conduit Allocation and Fill Procedures. All conduits shall be numbered and documented on site plan as-built drawings. All conduits that are not in use shall be plugged with a watertight duct plug designed specifically for such purpose. Separate conduits shall be allocated for fiber and high pair count copper cables. In the case of four-inch conduits allocated for fiber, five (5) oneinch innerducts shall be installed as a part of the initial activation. One, or more, of the innerducts shall be used for the initial fiber allocation with the remaining being allocated as spares. Innerduct shall be labeled at each end and where is passed through a vault as ccc - iii, where ccc = the conduit number from the site as-built drawings and iii = the innerduct number, 1 5, within the conduit. April 211 Page 35
36 APPENDIX D PRE-APPROVED PRODUCT SET The following product sets meet or exceed the requirements set forth by Portland Community College: Manufacturer Panduit Chatsworth Products Incorporated (CPI) APC Optical Cable Corporation (OCC) Cablofil Caddy Wiremold Cooper Notification Components Category 6 product set including patch panels, outlets, faceplates and patch cords Pre-connectorized fiber optic trunk assemblies Fiber optic cassettes used in conjunction with pre-connectorized trunk assemblies Fiber optic patch panels and connector used for field termination Fiber optic patch cord assemblies Surface mount raceway products Cabinets, racks, vertical wire management, overhead ladder tray (to be used in MDF/BDF and IDF locations as part of a seismic assembly) and all associated fastening hardware and components Power distribution and surge suppression Fiber optic cable Single mode outside plant (OSP) fiber Ladder tray and raceway products to be used in areas other than MDF/BDF or IDF, i.e., hallways and corridors where support of large amounts of cable is required Cable support devices Surface mounted metallic raceway SAFEPATH Mass Notification System (MNS) FSR Inc.Brand AMAG Access Control System Floor box Ceiling box AMAG Enterprise Edition Axis Video Surveillance system Axis Cameras EZ-Path EZ Path System Series 44+ April 211 Page 36
37 A. Approved Part Numbers. Note that all part numbers will not be appropriate nor approved for every project. Speciation writer must closely coordinate with Technical Services prior to receiving bids on a project-by-project basis to guarantee correct part numbers are used. Not also that part numbers change and the then current part numbers will be specified on a project-by-project basis to be included in the Bid Specification package. Manufacturer Description Part Number APC 1 to 25 Watts APC 25 to 4 Watts APC 4 to 8 Watts APC 8 to 96 Watts Chatsworth Products Inc (CPI) Smart-UPS XL3VA RM 3U 12V SUA3RMXL3U Batteries RBC 15 Electrical Requirements NEMA L5-12P 2 amp circuit, Smart UPS RT 5VA RM SURTD5RMXLP3U Batteries RBC 44 Electrical Requirements NEMA L14-3P 3 amp circuit, Smart UPS RT 1KVA RM SURT1KRMXL6U 2 w/ (2) 28V to 12V 2U Step-Down Transformer Battery Pack Electrical Requirements Symmetra LX 12KVA scalable to 16 Battery Pack Electrical Requirements SURT192RMXLBP3U 6 amp, hard wire 3 wire (2PH+G) SYA12K16RMP SYARMXR3B3 Rack, two post, 19 x x3 Rack, four post, 19 x 39 x 84 (H) 1 amp, hard wire 4 wire (2PH+N+G) QuadraRack 4 Post frame ExpandaRack QuadraRack Vertical Wire Management, 84 x 1, double sided Vertical Wire management, 84 x 6, double sided Horizontal Management Horizontal Management, 2U Wire Wire Cable Runway, Butt Splices Degree Junction April 211 Page 37
38 Manufacturer Description Part Number Chatsworth Products Inc (CPI) 9 Degree Corners, 12 raceway Wall Angle Support Kit, Triangular Support Bracket, Grounding Strap, 1 each Grounding Strap, 25 each End Cap (for raceway) Telecommunications Main Ground Busbar (TMGB) Telecommunications Ground Busbar (TGB) Panduit Faceplate (four port) CFP4IW Faceplate (six port) Wall Phone Plate Category 6, 8-pin modular jack Category 5e, patch panel, 48 port Patch panel frame, wedge, 28 port Patch panel frame, wedge, 48 port Fiber Trunk Assembly, Female MTP to Female MTP Fiber Interconnect Cable, Female MTP to Female MTP Fiber Cassette Rack Enclosure Fiber Cassette, 6 LC (12 strand), 5/125 m, Laser Optimized Fiber Cassette, 12 LC (24 strand), 5/125 m, Laser Optimized Patch Cord, Category 6 CFP6IW KWP6PY CJ688TGBL DP485E88TGY CPPLA24WBLY CPPLA48WBLY FSPXnn55FxxxA Where nn= strand count, 12 or 24 Where xxx= length, in feet 1 or greater FX12D-5MxxY Where xx= length, in meters, 1M or greater FCE1U FCXO-12-1Y FCXO-24-1Y UTPSPxccc Where x=l ength, in feet ccc= color April 211 Page 38
39 Manufacturer Description Part Number Optical Cable Corporation (OCC) Custom Outside Plant Fiber - Single mode/ OM4 Multimode 5/125 m Laser Optimized Custom Outside Plant Fiber - Single mode/ OM4 Multimode 5/125 m Laser Optimized SLX Singlemode Low water Peak ALE 55 meter 1 GbE SLB Singlemode Bend Tolerant ABE 55 meter 1 GbE Bend Tolerant General Cable Category 6, UTP, Plenum GenSpeed 6 MileStone Control Software Protect Corporate Axis Interior Camera AXIS-216FD Exterior Camera NVR is to be Raid System Server AXIS-225FD N+1 redundancy. 3 days event monitoring. AMAG Access Control System Software AMAG Enterprise Edition Intrusion Module Web Access XML Open Integration Directory Sync Manager Building Control w/bacnet AMAG Intrusion Management Software Module Software Module Software Module Gateway Software Module Access Control Panel AMAG Symmetry M21 or approved equivalent Card Readers HID Multi-class R4 Read Only Gray 34 Bit Badge Printer / Encoder See PCC security for approved product. Request to Exit DS161 PIR exit sensor, Black Door Contact Sentrol 18 G or approved equivalent Raucous Sounder Piezo Electric Sentrol AE912 or approve equivalent 4 door Controller AMAG M21 4DCU option Module Ethernet Module AMAG M21NIC option Module Intrusion System DMP-XR5N Motion Sensor Sentrol AP669 Keypad DMP 793 Battery 12 volt battery backup 7AMP/HR with vented enclosure April 211 Page 39
40 Manufacturer Description Part Number FSR Inc. Floor Box FL-G4 Ceiling Box CB-22SP EZ Path System Cable - Wall Penetration Series 44+ Technology Standards- Revision 9 April 211 Page 4
41 APPENDIX E MAIN DISTRIBUTION FRAME (TYPICAL) Wall mounted ladder rack for riser cable Entrance Conduits Service Providers 2'- " 3'-" 3'-" 6" VM 4'-" Rack 5 4'-" Rack 1 4'-" 1 " VM Rack 6 Rack 2 1 " VM 12 Volt 2 AMP Typical outlet 3'-" TMGB 12 Volt 2 AMP for Telco use Rack 7 Rack 3 1 " VM Rack 8 Mounted at base of vertical wire managers or as directed by Owner 1 " VM 6" VM 3'-" ¾ Fire Treated Plywood April 211 Page 41
42 APPENDIX F BUILDING DISTRIBUTION FRAME (TYPICAL) 15'-" 4" Entrance Conduits Wall mounted ladder rack for riser cable Rack 1 ¾ fire treated plywood 6" VM Rack 2 5'-" 4'-" 1" VM TMGB Rack 3 1" VM 2'-" Rack 4 1" VM Rack 5 6" VM Mount at base of vertical wire management or as directed by Owner 3'-" March 211 Page 42
43 APPENDIX G INTERMEDIATE DISTRIBUTION FRAME (TYPICAL) 1'-" 4 " Entrance Conduits from BDF Wall mounted ladder rack for riser cable Rack 1 ¾ fire treated plywood 6 " VM 5'-" Rack 2 4'-" 1 " VM 15'-" TGB Rack 3 1 " VM Rack 4 6 " VM Mount at base of vertical wire management or as directed by Owner 3' min 3'-" March 211 Page 43
44 APPENDIX H- MDF/BDF BAYFACE (TYPICAL) BDF/MDF Bay Face (Typical) Build out shows max imum configuration, i.e, 12 Panduit wedge panels populated with 48 Category 6 jacks for a total of 576 station ports 1 inch vertica l wire management Maximum Ethernet switches, i.e., 12, 48 port 12Kva UPS to support VoiP and additional ancillary equipment that may be located in this room. Actual bid specifications may call for different configuration to meet specific building requirements Technology Standards- Revision 9 March 211 Page 44
45 APPENDIX I- IDF BAYFACE (TYPICAL) IDF Bay Face (Typical) Build out shows maximum configuration, i.e., 12 Panduit wedge panels populated with 48 Category 6 jacks for a total of 576 station ports. 1 inch vertical wire management Ftber Tte to BDF/MU' Copper Tt e to BDF/ MIT Maximum Ethernet switches, i.e., 12, 48 port 5Kva UPS Actual bid specifications may call for different configuration to meet specific building requirements...!'....!'.... Q Technology Standards- Revision 9 March 211 Page 45
46 APPENDIX J BONDING AND GROUNDING DETAIL A. Bonding Electrical Entrance Facility MDF/BDF/IDF N G TMGB or TGB Grounding Electrode Conductor Bonding conductor for Telecommunications as per table Grounding Electrode System Sizing of the Bonding Conductor Length (in feet) Size (AWG) Less than / / Greater than 66 3/ Table 2 Bonding Conductor Sizing March 211 Page 46
Computer Network Design Guide Existing Systems 1 / 6
COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationOffice of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO
Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note
More informationCopper Riser And Intrabuilding Cabling
Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationNetwork Construction Guide Specification Telecommunications Infrastructure Standards V 2.6
Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12
More informationTarget Interface / Construction Compliance Inspection Checklist
TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data
More informationCOMPUTER NETWORK WIRING SYSTEMS FOR PLCs
SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network
More informationA. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationLos Angeles Community College District Design Standards
LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure
More informationSECTION COMMON WORK RESULTS FOR COMMUNICATIONS
PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationv2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.
Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations
More informationCOMMON WORK RESULTS FOR COMMUNICATIONS
SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationINTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES
INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationSECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations
SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationData Cabling / Low Voltage Technology Specifications
P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall
More informationLACCD IT Design Standards
LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationE. Numbering and Labeling Pathway components. In general, pathway components are not labeled.
27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationANSI/TIA/EIA-568-B Cabling Standard NOTE
95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial
More informationCommunication
27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and
More informationTIA/EIA 568A Sub-system HORIZONTAL CABLING
TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,
More informationMeter Enclosure and Equipment Standards
Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable
More informationDesign Guidelines for Facilities Construction:
Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,
More informationWire Communications Design jfm 07. An Inside Look at Outside Plant
An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure
More informationSYSTIMAX GigaSPEED Xpress Solution Design Guidelines
Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More informationDivision 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationStructured Cabling Guidelines
Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationSECTION TELEPHONE AND COMPUTER CABLING
SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall
More informationSECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION
SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationAnixter Standards Reference Guide
Anixter: The Cabling System Experts Anixter is a leading global supplier of communications and security products, electrical and electronic wire and cable, fasteners and other small components. We help
More informationSECTION COMMUNICATIONS BACKBONE CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED
More informationThis attractive raceway conceals and
5000 Two-Piece Multiple Channel Raceway Access 5000 Nonmetallic Surface Raceway System This attractive raceway conceals and organizes electrical wiring and low-voltage cabling in a sleek, handsome molding.
More informationANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com
A The urpose: stablish a generic telecommunications cabling standard that will support a multivendor environment nable the planning and installation of a structured cabling system for commercial buildings
More informationAT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)
AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T
More informationCommunications Infrastructure Specification
Communications Infrastructure Specification This document defines the communications installation guidelines for the University of Arkansas. Page 1 Revision Information Revision Number: Rev 2.2 Issue Date:
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationInstallation Notes TII Model 341 Protector
Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow
More informationFIBER OPTIC HARDWARE STEVE PAULOV
C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.
More informationUMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management
UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE
More informationOMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE
OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE The Omega MPP enclosure is based on a 19" frame, with 4 empty module slots for MPP modules. Highly flexible : any mix between twisted pair and optical fiber modules.
More informationUniversity of Arkansas at Little Rock
University of Arkansas at Little Rock Policy Name: Infrastructure Cabling and Wiring Standards Policy Number: 702.1 Effective Date: September 24, 2008 Policy: University of Arkansas at Little Rock (UALR)
More informationAT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)
AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide This guide is designed to assist local on-site contacts to understand what you will need to
More informationAT&T Virtual Private Network Service (VPN) and AT&T VPN Express
AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site preparation guide This guide is designed to assist local on-site contacts to understand what you will need to accomplish in preparation
More informationSpecifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC.
Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. 1.01 General Requirements This section details general requirements for plenum sound masking installations. 1.1 Contract
More informationUNDERCARPET CABLING SYSTEM For Power and Communications
UNDERCARPET CABLING SYSTEM For Power and Communications Linking Everything Together Power, Voice, and Data December 5, 2007 Undercarpet Cabling System Overview What is Undercarpet Cabling? Primary Applications
More informationBSD Technical Standard. Division 27: Communications & Technology
Division 27: Communications & Technology I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for telecommunication infrastructure standards.
More informationARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY
ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY Introduction A classroom is measured by its effectiveness in facilitating the exchange of information. The following general guidelines have been developed
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationCabling a Data Center to TIA-942 Standard
Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center
More informationEmery County Senior Center Green River 06/07
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationThis attractive raceway conceals and
Access 5000 Nonmetallic Surface Raceway System 5000 Two-Piece Multiple Channel Raceway This attractive raceway conceals and organizes electrical wiring and low-voltage cabling in a sleek, handsome molding.
More informationCommunications Updated April
27 00 00 Communication 27 05 00 Common Work Results for Communications 1. Purpose a. Coastal Carolina University facilities requiring cabling installation. This document provides the minimum performance
More informationSECTION PANELBOARDS
SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationAtras Network Communications
Atras Network Communications Guide to Information and Communications Technology (ICT) Standards developed and published by the Telecommunications Industry Association (TIA) The Telecommunications Industry
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Date: Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of stations meets DD 9, applicable
More informationPanduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA
Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Figure 1: Industrial Distribution Frame (IDF) Equipment Elevation
More informationThis attractive raceway conceals and
Access 5000 Nonmetallic Surface Raceway System 5000 Two-Piece Multiple Channel Raceway This attractive raceway conceals and organizes electrical wiring and low-voltage cabling in a sleek, handsome molding.
More informationMaster Format Division 27 - Communications
CLEMSON UNIVERSITY Master Format Division 27 - Communications Charlie Breece, RCDD CCIT Network Services and Telecommunications 2012 Master Format Division 27 Communications DIVISION 27 COMMUNICATIONS
More informationAT&T Switched Ethernet Service SM
Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks
More informationU-SERIES SPECIFICATION GUIDE
U-SERIES SPECIFICATION GUIDE Connectivity with flexibility For more product information visit connectrac.com, call us at 877-480 - 5637 or email us at info@connectrac.com ADA COMPLIANT - U.L. TESTED AND
More informationThe 5500 Series from The Wiremold Company
5500 Nonmetallic Raceway Multi-Channel Surface Nonmetallic Raceway Available Factory Prewired. The 5500 Series from The Wiremold Company provides wire and cable management for data, voice, video, and power
More informationElement Z General Design Requirements Owner Standards and Other Requirements
Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases
More informationSpring Test 17 due 06/14/2013
Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered
More informationGround Power Modules. And Accessories For Healthcare Facilities. Technical Bulletin NAE /
2 Ground Power Modules And Accessories For Healthcare Facilities Technical Bulletin NAE2092320 / 10.2011 Ground Power Modules Hospital grade outlet modules Introduction BENDER series GPM ground and power
More informationQualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001
Qualified Partner Programme QPP Installation Practice Felice Guarna Wetzikon, Why installation quality Product performance must be preserved by an accurate installation Long term warranty requires design
More information1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM
1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationBROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS
BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS
More informationAT&T Virtual Private Network Service (VPN) and AT&T VPN Express
AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site Preparation Guide 2017 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered
More informationStructured Cabling Guidelines For The State Of Oregon
Structured Cabling Guidelines For The State Of Oregon Compiled by; TABLE OF CONTENTS 1. INTRODUCTION 2 2. SPECIFICATIONS 4 3. SIX SUBSYSTEMS OF A STRUCTURED CABLING SYSTEM: 5 3.1. Building Entrance/Entrance
More informationXBR V4 INSTALLATION AND USER GUIDE
XBR V4 INSTALLATION AND USER GUIDE xbr V4 Installation and User Guide Page 1 of 18 Revision History Dash#/Rev Date Author Description 0.1 04/03/2013 Eric Anderson Initial draft 0.2 04/08/2013 Eric Anderson
More informationPower/Data Instructions. Genius. Movable Walls. September
Power/Data Genius Movable Walls September 2011 Genius Movable Walls Power and Data in Shell Level 1 Conventional Boxes in Panel (conventional box and conduit) Choose 2x4 box or 4x4 box (shown). Separate
More informationPLC Racks IC697CHS782/783
5 1 PLC Racks IC697CHS782/783 (IC697CHS782/783) datasheet Features Accepts 3rd Party VME modules which require 0.8 spacing. Accepts all IC697 PLC module types. Rear mount rack mounts in a 10 (254 mm) deep
More informationSPECIAL SPECIFICATION 1864 Pole Mounted Cabinet
1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof
More information2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS
NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated
More informationWith the publication. Make the right connection: Bonding a shielded system. installation
Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being
More informationor
Infinite possibilities for your data center The F-Series TeraFrame T M Cabinet System The F-Series TeraFrame Cabinet System from Chatsworth Products, Inc. (CPI) provides configurable thermal management
More informationCabling Infrastructure
Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements
More information