ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE

Size: px
Start display at page:

Download "ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE"

Transcription

1 Network(s): Summary: ENGINEERING CONSTRUCTION PROCEDURE ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE LPN This document details the installation procedure for the Remsdaq Callisto 1 control unit and RTU used with ground-mounted switchgear in LPN. It includes the physical installation of the control unit and cabling together with installation of the mains supply, earthing, flood alarm, current transformers and fuse carriers. Author: James Ford Approver: Paul Williams Date: 29/11/2018 This document forms part of the Company's Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current version. Circulation UK Power Networks External Asset Management UK Power Networks Services Capital Programme Contractors Connections ICPs/IDNOs Health & Safety Meter Operators Legal G81 Website Network Operations Procurement Strategy & Regulation Technical Training THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE

2 Revision Record Version 5.0 Review Date 29/11/2023 Date 27/11/2018 Author James Ford Reason for update: Periodic review What has changed: No content changes to document and associated documents. Review dates extended Version 4.1 Review Date 02/09/2018 Date 08/06/2015 Author Lee Strachan Reason for update: Minor version update What has changed: Reference to EDS (withdrawn document) removed Version 4.0 Review Date 02/09/2018 Date 08/06/2015 Author James Ford Reason for update: Periodic review What has changed: Update: correction to wrong terminal number in section 13.7 (Pin No 8 Violet) Version 3.0 Review Date 22/06/2015 Date 03/09/2014 Author James Ford Update: Section 9 - RTU positioning amended to ensure safe egress by operator Version 2.0 Review Date Date 25/02/2011 Author Mariann Grigg Update: Rebranded only No changes Version 1.0 Review Date Date 26/05/2010 Author Stephen Tucker Original based on ex LPN document UK Power Networks 2018 All rights reserved 2 of 27

3 Contents 1 Introduction Scope References Abbreviations and Definitions Callisto 1 RTU Functionality Callisto 1 Description Equipment General Location Multi-core Cables Flood Alarm Current Transformers and Fuse Carriers RMU Plugs Mains Supply Battery Installation and Functional Check Appendix A Parts List Appendix B Fixing Details Figures Figure 6-1 Protocol Converter Front View... 8 Figure 6-2 Protocol Converter Rear View... 8 UK Power Networks 2018 All rights reserved 3 of 27

4 1 Introduction This document details the installation procedure for the Remsdaq Callisto 1 control unit and remote terminal unit (RTU) used with ground-mounted switchgear in LPN. It includes the physical installation of the control unit and cabling together with installation of the mains supply, earthing, flood alarm, current transformers and fuse carriers. Note: The installation of the communications equipment is covered in the commissioning procedure. This procedure shall be carried out in accordance with the requirements of the UK Power Networks Distribution Safety Rules. This procedure shall be carried out having regard to the requirements and recommendations of the manufacturer. If conflict exists between the requirements of the manufacturer and those of UK Power Networks the matter shall be referred to Asset Management (or your UK Power Networks nominated contact). 2 Scope This procedure applies to the Remsdaq Callisto 1 control unit and RTU used in LPN. Refer to ECP for the installation details for other control units. 3 References This procedure should be read in conjunction with the following references: Remsdaq Callisto 1 RTU cabinet drawing 4969/A1/0008. Remsdaq Callisto 1 RTU wiring diagram 4929/A1/0002. This procedure should be used with the following forms: ECP a Remsdaq Callisto RTU Installation Check Form. ECP b Remsdaq Callisto RTU Functional Check Form. ECP c Remsdaq Callisto RTU Defect Report Form. UK Power Networks 2018 All rights reserved 4 of 27

5 4 Abbreviations and Definitions Term ACB CT EFPI GPRS GSM IP PMR RMU RTU Definition Air Circuit Breaker Current Transformer Earth Fault Passage Indicator General Packet Radio Service Global System for Mobile Internet Protocol Private Mobile Radio Ring Main Unit Remote Terminal Unit 5 Callisto 1 RTU Functionality 5.1 The Callisto 1 control unit and RTU is used to provide remote control of high-voltage switchgear on the LPN network. The Callisto 1 contains a micro-processor which controls the ring switches of the ring main units (RMU) enabling rapid supply restoration by either automation or by remote commands issued by the Control Engineer. 5.2 All Callisto 1 RTUs are loaded with the same configuration software. The current software is Callisto Base The Callisto 1 provides the following basic functionality: Remote control and indication of three switches or circuit breakers. The most common use is control and indication of the two switches on a ring main unit (SW1 and SW2). Together with the indication of the circuit breaker used to feed the local transformer (SW3/CB3). Indication for three earth fault passage indicators (EFPI). The EFPIs are referenced to the circuit to which they are fitted, i.e. EFPI 1 is associated with SW1 and EFPI 2 with SW2 etc. The Callisto 1 has a common EFPI reset control. Monitoring other status inputs including a flood alarm and a substation alarm. Monitoring three-phase voltage and current on the cable between the transformer and LV board. Monitoring the percentage harmonic distortion for both current and voltage. UK Power Networks 2018 All rights reserved 5 of 27

6 6 Callisto 1 Description 6.1 A photo of the Callisto 1 cabinet with the main parts identified is shown below. Main processor boards (IoA and IoB) Connection boards (up to 8) Power supply board Terminal rail Power supply toroid Protocol converter 12V lead-acid batteries 6.2 Processing boards boards IoB and IoA are located under the blue cover on the left hand side of the Callisto 1. IoB is the main processing board and has up to 16 digital inputs and 16 control outputs (arranged in control pairs). IoA is the analogue input board and can monitor up to 32 analogue inputs. The sampling rate of the voltage and current inputs is 1.6 khz. IoA is used to monitor the 3 EFPI states. 6.3 Power board is located under the blue cover on the left hand side of the Callisto 1 and contains the battery charger module. It also provides a 12V supply to the backplane. 6.4 Power supply the Callisto 1 is powered by a 230V AC mains supply and two 12V lead-acid sealed batteries. The battery supply provides the high current required to operate the actuator and a backup during mains failure. A power supply toroid converts the mains supply and provides a 32V DC supply to the battery charger board. 6.5 Connection boards there are up eight connection boards (two control, two digital input and four analogue input). The connection boards are used for connecting cables between the Callisto 1 and the switchgear. The Callisto 1 is supplied with the following: Card slot 1 Control board IoCT8 special. Card slot 2 Control board IoCT8 not fitted. Card slot 3 Status input board IoDT8. Card slot 4 Status input board IoDT8. Card slot 5 Analogue input board IoAT9. Card slot 6 Analogue input board IoAT9. Card slot 7 Analogue input board IoAT9 not fitted. Card slot 8 Analogue input board IoAT5 not fitted. UK Power Networks 2018 All rights reserved 6 of 27

7 6.6 Terminal rail is used to terminate connections not taken as direct inputs into the Callisto 1 connection boards second relay is used to switch the 24V positive supply to the actuator following a control command this is to avoid damage to plant/actuators in case of a limit switch failure. 6.8 Protocol converter is used to provide GPRS communication between the control system and the Callisto 1. The protocol converter will be used at all new sites and will be retrofitted at existing sites to upgrade the communication from PMR/GSM to IP (Internet Protocol) over the GPRS (General Packet Radio Service) mobile network. Where no GPRS signal is available PSTN will be used. Existing Configuration New Configuration RS 232 Serial Link Callisto 1 RTU RS 232 Serial Link Callisto 1 RTU Existing Modem (GSM or PMR) Protocol Converter with integrated GPRS Module (IP over GPRS) The protocol converter includes the following interfaces (refer to Figure 6-1and Figure 6-2): Serial communications port, with integral TX and RX communication LED indications for communications connection to the existing Callisto 1. Serial communications port, with integral TX and RX communication LED indications for connection to the existing Callisto 1 configuration/diagnostics port. Ethernet port for direct connection of a PC for configuration or alternatively it may be used for Network Control communications via broadband or other IP network where GPRS coverage is inadequate. GPRS antenna connection. SIM card slot. Power connection suitable for nominal 24V DC input (range 18V to 30V). Health LED indication, Signal strength LED indications, GPRS service LED indications, TX and RX communication LED indications. UK Power Networks 2018 All rights reserved 7 of 27

8 Serial port (Comms) Ethernet port Serial port LEDs LEDs Earth stud LED Earth stud Figure 6-1 Protocol Converter Front View DC power supply and protective earth block SIM card holder Connector for the GSM/GPRS network antenna Figure 6-2 Protocol Converter Rear View UK Power Networks 2018 All rights reserved 8 of 27

9 6.9 Other equipment (current transformer clamps and voltage carriers containing fuses/links as shown below) enable the Callisto 1 to monitor the three-phase current and voltage at the substation. The current transformer clamps and the voltage fuses/links are attached directly to the LV cables between the transformer and the LV board. Note: the current transformer clamps are designed to be removed and replaced safely without the need to short the output. Clip-on CTs Fuse carriers UK Power Networks 2018 All rights reserved 9 of 27

10 7 Equipment 7.1 The following test equipment is required to carry out the work in this procedure: Multi-meter. Insulation resistance tester (e.g. Megger). RMU simulator. 8 General 8.1 The sections that follow cover the installation of the items below in further detail. Cabinet. Multi-core cables. Flood alarm. Current transformers. Fuse links. RMU plugs. Modem. Mains supply. Battery. 8.2 The installation shall be carried out with in accordance with the following: Remsdaq Callisto 1 cabinet drawing 4969/A1/0008 attached to this procedure. Remsdaq Callisto 1 wiring diagram 4929/A1/0002 attached to this procedure. Parts list Appendix A. Fixing details Appendix B. A multi-meter shall be used for continuity checks do not use bell testers, buzzers or Meggers as they may damage the Callisto 1. Cable insulation tests shall be carried out with the wires disconnected from the Callisto 1. UK Power Networks 2018 All rights reserved 10 of 27

11 9 Location 9.1 The positioning of the Callisto 1 cabinet will be determined by the layout of the secondary substation and the space available. The position should be such that an operator has safe egress from the substation after operation which would usually mean a location near the main door of the substation (diagrams below). ACB Transformer Transformer ACB Ring Main Unit RTU LV Board Ring Main Unit Entrance Entrance R T U LV Board RTU Standard Secondary Substation Package Secondary Substation 9.2 Mount the cabinet onto the wall with the top two fixings at a height of 1750mm above floor level and a distance between them of 570mm. Refer to Remsdaq drawing 4969/A1/0008 for details of cabinet and fixings. UK Power Networks 2018 All rights reserved 11 of 27

12 10 Multi-core Cables 10.1 The four multi-core cables used to connect the Callisto 1 to the RMU, CTs and voltage fuses and are all screened cables. These cables have been selected to prevent interference and therefore the correct installation and termination of these cables is essential to ensure correct operation. UK Power Networks 2018 All rights reserved 12 of 27

13 1 M 10.2 To prevent the induction of currents from the earth ring the screened cables should not be run in parallel with the earthing conductor. If it is run in parallel there should be a minimum gap of 1m between them. In some positions where the 1m gap cannot be achieved the parallel run should be kept as short as possible. The screened cable may cross the earthing at right angles as shown below. Screened cable Earthing 10.3 Install a cable tray between the Callisto 1 and the RMU to support the multi-core cables. The cable trays should be constructed on-site to suit the substation arrangement and secured to the wall using 2 HPS 6/5 Hammascrews and to the RMU using cable ties. A basic arrangement is shown below. Dimension to be determined on site approx 800mm Approx 150mm Notes: 100mm Cable Tray Fixing Hole for Earth Strap Fixing Holes This part of rollover to be hammered flat to avoid cable bend 1. Tray work to be earthed via substation earth bar. 2. All cut edges are to be de-burred Run the two mutli-core cables (18c 16/02 and 7c 2.5mm2) from the Callisto 1 and the RMU. Run two further multi-core cables (8c 16/02 and 4c 16/02) from the Callisto 1 and to the CTs and voltage fuses respectively. UK Power Networks 2018 All rights reserved 13 of 27

14 10.5 The cables should be positioned at the Callisto 1 as shown below. All empty holes should be filled using 20mm plastic blanking grommets. RTU base plate viewed from below Front Rear A - 18c 16/02 to 16 Way plug/socket RMU B - 7c 2.5 mm to 6 Way plug/socket RMU C - 2c 1.5 mm2 mains supply D - Spare E - 8c 16/02 to Current sensors F - 4c 16/02 to Voltage sensors G - 4c 7/02 to PIR H-R - Spare S - Aerial or BT line 10.6 Enter the cables into the cabinet using a cable gland the cable gland components and correct position of the screening is shown below. Locking nut Flat washer Rubber 'o' ring Body RTU cabinet Brass top hat Screening Rubber sleeve grip Metal collar Compression ring Multi core cable 10.7 If any of the cores are damaged the cable shall be replaced before continuing. Any spare cores should be tied up and left in the trunking inside the Callisto 1 cabinet and should not be cut off. UK Power Networks 2018 All rights reserved 14 of 27

15 10.8 The sheath of the screened cable shall be removed using an approved knife. Care should be taken to avoid damage to the screening of the cable. If damage to the screening does occur it should be reported to the supervisor who will decide if the cable needs to be replaced All cable terminations shall be stripped using the approved stripping tool (Wire Stripper HB1-U) and no other tool should be used The cable terminations in the Callisto 1, at the CTs and fuse links shall use crimped lugs. The correct size/type of crimp lug or termination method for each cable is shown in the table below and shall be crimped using an approved crimping tool (Crimpstar HP 3 and Crimpstar HP 4). Equipment Cable Crimp Type Callisto 1 18 core 16/02 Insulated End Sleeves P/N PKE 7508 (A) RMU plug box Blue shoe lace crimp Insulated End Sleeves P/N PKE 7508 (A) Blue shoe lace crimp Callisto 1 7 core 2.5mm 2 * Insulated End Sleeves P/N PKE 2508 (A) RMU plug box Grey shoe lace crimp * Insulated End Sleeves P/N PKE 2508 (A) Grey shoe lace crimp Callisto 1 8 core 16/02 Insulated End Sleeves P/N PKE 7508 (A) CTs Blue shoe lace crimp Straight connectors Red Callisto 1 4 core 16/02 Insulated End Sleeves P/N PKE 7508 (A) Fuse Links Blue shoe lace crimp Insulated End Sleeves P/N PKE 7508 (A) Blue shoe lace crimp Callisto 1 2 core 1.5mm 2 flex Insulated End Sleeves P/N PKE 1508 (A) Fused spur Earth cable 70mm 2 earth cable Black shoe lace crimp Screw termination (no crimp) *Note: Cores 1 and 3 from the 7 core 2.5mm 2 cable terminated in terminal 20 shall be terminated using a grey double crimp lug. UK Power Networks 2018 All rights reserved 15 of 27

16 11 Flood Alarm 11.1 If the substation is not equipped with a flood alarm the input needs to be shorted. The flood alarm input is on IoDT8 Card Slot 4, input 3, terminals 5 and 6 as shown below. Flood alarm input short UK Power Networks 2018 All rights reserved 16 of 27

17 12 Current Transformers and Fuse Carriers 12.1 The current transformers (CT) and fuse carriers are fitted to the LV cables between the transformer and the LV board or air circuit breaker (ACB), as shown below, to enable the three-phase current and voltage to be monitored The CTs and fuse links should be fitted as close to the LV board/acb as possible Check the LV cables are dead before carrying out this work Attach three clip-on CTs to the LV phase cables as shown above, with P1 towards the transformer (supply) and P2 towards the LV board/acb (load). Fit a DO NOT REMOVE label on each clip-on CT. Note: The correct CTs are of a voltage output type, designated by the label..xx V output, and may safely be unclipped without shorting the outputs Attach four fuse carriers directly to the LV phase and neutral cables, as shown above, using a self tapping screw (drill size 3mm). Note: Do not install the fuses/links at this stage they should be left locked in the Callisto 1 cabinet for installation during commissioning. A solid link is fitted to the neutral Terminate the cables from the CTs and fuse carriers in the Callisto 1 as shown below Carry out an insulation test of the fuse carry cabling using an appropriate tester. UK Power Networks 2018 All rights reserved 17 of 27

18 UK Power Networks 2018 All rights reserved 18 of 27

19 13 RMU Plugs 13.1 The connection between the cables from the Callisto 1 and the RMU use two plugs and sockets. The RMU is delivered with the sockets installed by the manufacturer the 16-way plug/socket is used for the indications/control initiation pulses and the 6- way way plug/socket is used for 24V supplies/indication common On completion of the plug connections DO NOT CONNECT the Callisto 1 to the RMU this is part of the commissioning process The plugs and sockets use a stuffing gland to secure the sheath of the screened cable and the screening should be cut back and insulated using PVC tape as shown below. Rubber Socket to RMU Screening Washers Roll screening back over sheath and insulate Cut off and insulate spare cores Cable PVC tape 13.4 The 16-way plug uses an 18 core 16/02 cable which has colour coded cores and 6- way plug uses a 7 core 2.5mm cable cores are numbered 1 to 6, the seventh core is an earth cable. The two spare cores should be cut back and insulated The earth cable should be cut back in the plug and insulated. UK Power Networks 2018 All rights reserved 19 of 27

20 13.6 Terminate the 7c 2.5mm 2 cable into the 6-way plug and the Callisto 1 as shown below. 6-way Plug Pin No Cable Core No Description Callisto 1 Connection Volt DC supply Terminal rail Volt DC supply switched Terminal rail EFPI reset common Terminal rail volt DC supply Terminal rail Switch indication common Terminal rail 23 (Via 12 Card slot 3) 6 6 EFPI indication common Terminal rail 10 7 Cut back & insulate both ends Terminal rail Terminate the 18c 16/0.2mm 2 cable into the 16-way plug and the Callisto 1 as shown below. 16-way Plug Pin No Cable Core Colour Description Callisto 1 Connection 1 Red Switch 1 open indication Card Slot 3 Terminal 1 2 Blue Switch 2 open indication Card Slot 3 Terminal 5 3 Green CB 3 open indication Card Slot 3 Terminal 9 4 Yellow EFPI 1 indication Card Slot 5 Terminal 21 5 White EFPI 3 indication Card Slot 6 Terminal 23 6 Black Open switch 1 command Card Slot 1 Terminal 8 7 Brown Open switch 2 command Card Slot 1 Terminal 10 8 Violet Open CB3 command Card Slot 1 Terminal 12 9 Orange Switch 1 close indication Card Slot 3 Terminal 3 10 Pink Switch 2 close indication Card Slot 3 Terminal 7 11 Turquoise CB 3 close indication Card Slot 3 Terminal Grey EFPI 2 indication Card Slot 5 Terminal Red/Blue Reset EFPIs command Card Slot 1 Terminal Green/Red Close switch 1 command Card Slot 1 Terminal 9 15 Yellow/Red Close switch 2 command Card Slot 1 Terminal White/Red Close CB3 command Card Slot 1 Terminal 13 Red/Black Cut back & insulate both ends Red/Brown Cut back & insulate both ends UK Power Networks 2018 All rights reserved 20 of 27

21 14 Mains Supply 14.1 The Callisto 1 power supply is provided from an un-switched fused spur connected to a double socket outlet in the substation Check the double socket outlet is dead before carrying out this work Fix the fused spur to the wall below the Callisto 1 as shown below Connect the fused spur to the double socket outlet using 2.5mm 2 single-core stranded cables run in 20mm plastic conduit. These should fixed using standard wood screws, raw plugs, conduit saddles and various other fixings available from stores. The conduit saddles should be fixed using No 10 1½" wood screws or Hilti fixings EDB 8-28mm and the distance between saddles should be 1500mm horizontal and 1750mm vertical Connect the fused spur box to the Callisto 1 using two-core 1.5mm 2 flex via a 20mm plastic gland. The mains supply should be connect to terminals I and 2 on the terminal rail as shown below.. Terminal Block Live Neutral 14.6 Connect a minimum 35mm 2 stranded aluminium or stranded 16mm 2 copper earth cable between the Callisto 1 cabinet and the substation earth. UK Power Networks 2018 All rights reserved 21 of 27

22 15 Battery 15.1 Care should be taken to avoid shorting the battery terminals or shorting the terminals to the Callisto 1 cabinet during installation Early battery types will have horizontal bolts and nuts it is essential that the direction is as shown in the drawing below. Later battery types will have fixings in the vertical plane, avoiding the possibility of the incorrect fixing of bolts potentially resulting in making contact with the cabinet Connect the short leads shown in the diagram below to each battery, whilst the battery is outside the Callisto 1 (e.g. on the floor). BLACK/RED RED BLACK/RED RED Plastic insulator 15.4 Install the batteries into the left-hand side of Callisto 1 cabinet, ensuring that the terminals are clear of the cabinet and any other metal object Connect the two numbered leads together 1 to 1, 2 to 2. Note: The batteries are usually supplied fully charged and will receive additional charge when installed in the Callisto 1 do not attempt to fast charge them by using car battery chargers or paralleling with other batteries. 16 Installation and Functional Check 16.1 Carry out a full installation check using test form ECP a On completion of a successful installation check carry out a functional check as detailed below to ensure that any potential wiring faults are identified and corrected before the Callisto 1 is connected to the RMU for final commissioning Check the communications device, if installed, is disconnected before starting Insert a 5A fuse into the fused spur. UK Power Networks 2018 All rights reserved 22 of 27

23 16.5 Connect the Callisto 1 to RMU simulator (shown below) Check Common Supplies Healthy (shown below) the 24 Volt Supply, EFPI Indication and EFPI Reset Common should be illuminated and the Switchgear Indication Common shouldn't be illuminated. If these are not illuminated check fuses 9 to 12, 20 and 21 in the Callisto Carry out a functional check using test form ECP b. Any faults found during the functional check should be rectified and the functional check repeated. This process should be repeated until functional check is completed successfully If there are defects that cannot be rectified complete a defect report using test form ECP c If instructed, on completion of checks remove 5A mains supply fuse from fused spur and disconnect the batteries Provided there are no outstanding faults the Callisto 1 is now installed ready to commission with the RMU onto the network. UK Power Networks 2018 All rights reserved 23 of 27

24 Appendix A Parts List Deliver To: Work Location: Materials Required By Date Required Instructions for use: Complete ALL of details in the above fields. Job Number Contact Phone No Indicate the quantity of materials required from the Accessories list. Fax the completed form to Bury St Edmunds All of the materials on this sheet will be delivered as indicated above. Standard RTU/RMU change SHEET L8 Description Materials Code 1 Qty RTU Standard Materials Kit Spur fused Un-switched ASHLEY 11181S Plastic back box (single) 05388S Fuse link 5AMP 5PTC 11116F 20mm plastic conduit 05342Y 20mm male adaptor 05369K Washer steel FLAT M O * 6mm yellow crimp lug 14451C Nut hexagon full M8 zinc plated 13091C Washer steel flat M8 zinc plated 13276Y * Nuts brass full 6mm nickel plated 13072U * Screw hexagon M6 x 25mm W * Washer steel FLAT M6 zinc plated 13247H * Gland plastic LK TYPE H Carrier fuse mounted "RTU" Kit 11200V Clamp Amp 0.34 Volt AC C/W 14150U Padlock D101 1 ¼ to pass X L Kit for RTU SET 14460B 16-way cable plug hood (ACB) 01694S 16-way plug female (ACB) 01685T Tube heat shrink MWTM 10/ G Tube heat shrink ATUM 19/ W 1 UK Power Networks materials code for internal use only. UK Power Networks 2018 All rights reserved 24 of 27

25 Description Materials Code 1 Qty Bag site tidy H/D 24X36 C/W A 36115W Remote terminal unit standard A 14465A Flex 1.5mm 2 core white 05306D * Tray cable swift SS TYPE 01522E Batteries YUASA NPL24-12-VRLA A 19085J RMU Standard Jointing Materials Joint transitional vertical 04126B SMOE termination kit 04151D SMOE termination kit (unit) 04150T SMOE termination kit (trans) 04154H SFK right angle boot 04155S Label self-adhesive SF L Label SF6/no smoking rigid 21085B Cantilever arms 01468Q Cleat trefoil 70mm 01495M Cleats trefoil 240mm 01496W Rambolt loose lb S * Cable 120mm 1c PVC Gr/Yellow A 05867D 120mm crimp lugs M10 hole 01373S Set of Lucy lugs 3 per packet 01234K Nuts channel 10mm 13280Y Screw set hex head 10x 25mm 13155P * Accessories Green/Yellow PVC Covered Stranded Copper Cable 16mm 2 A 05847L PVC Covered Aluminium Cable 35mm E Large cable ties (1 bag) 01667V * Medium cable ties (100 per pack) 02232U Small cable ties (1 bag ) 03552P * Split dowel 3/13mm (100 perbox) 01523P Dble dowel 4/12mm (100 perbox) 01477P * Dble dowel 12/25mm (100 per box) 01478Y * Hammerscrew stud (50 per box) 13240P * Hammerscrew (100 per box) 13239T * Dble b/lace ferr 2.5mm grey (500) 34250G * B/lace ferr 1.5mm black (500) 34251R B/lace ferr 2.5mm grey (500) 34252B UK Power Networks 2018 All rights reserved 25 of 27

26 Description Materials Code 1 Qty B/lace ferr 0.02mm blue (500) 34253L In-line connector red (100) 01250N Split dowel 8/28mm (100/ box) 01479J * RTU Cables Cable 2.5mm PVC red (100M) 05853F * Cable 2.5mm PVC black (100M) 05852V * Cable tele 7C 2.5mm PVC (50M) 05188C Cable tele 8c 16/02 DEF (25M) 05187S Cable tele 4c 16/02 DEF (25M) 05186H Cable screened 18C 16/02 (25M) 05189M Cable 2.5mm Y/G Earth (100M) 05843W * HV Cable 300mm XLPE ( x M) A 06006K 95mm XLPE ( x M) A 06004Q Large surgical vinyl treated 34568R Medium surgical vinyl treated 34960T P.F impregnated wipes (tub) A 23104N UK Power Networks 2018 All rights reserved 26 of 27

27 Appendix B Fixing Details The table below details the fixings to be used when installing the equipment. Note: They should only be used in concrete or masonry and not in mortar. Equipment Manufacture Description Drill Size RTU Hilti HPS 18/10 hammascrew with threaded stud 2 cable tray Hilti HPS 6/5 hammascrews 7 core 2.5mm 2 screened cable Hilti EDD 12/25 dowel double clamp Thread length M8x16 Maximum thickness fixed 5mm Cable range 12-25mm 8mm 6mm 6mm 16 core 16/02 screened cable 4 core 16/02 screened cable 8 core 16/02 screened cable Hilti Hilti Hilti EDD 12/25 dowel double clamp EDD 4/12 dowel double clamp EDD 4/12 dowel double clamp Cable range 12-5mm Cable range 4-12mm Cable range 4-12mm 6mm 6mm 6mm 6mm 2 earth cable Hilti EDB 3/13 split dowel Cable range 3-13mm 6mm 20mm conduit Hilti EDB 8-28 split dowel Cable range 8-28mm 6mm The distance between Hilti fixings listed above should be no more than 400mm and 100mm either side of a bend. The Hilti fixings used to support the screened cables should be spaced as shown below. Max 100 mm Max 350 mm Max 350 mm UK Power Networks 2018 All rights reserved 27 of 27

ECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE

ECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE Document Number: ECS 05-9540 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9540 TYPE E AND ANCILLARY ITEMS INSTALLATION PROCEDURE EPN, LPN, SPN This procedure details the installation,

More information

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE Document Number: ECP 11-0501 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0501 SECONDARY SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the end-to-end process

More information

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0521 NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing

More information

EOS REMSDAQ CALLISTO NX TYPE E RTU

EOS REMSDAQ CALLISTO NX TYPE E RTU Document Number: EOS 05-9306 Network(s): Summary: ENGINEERING OPERATING STANDARD EOS 05-9306 REMSDAQ CALLISTO NX TYPE E RTU EPN, LPN, SPN This standard details the application, installation and operation

More information

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE Document Number: ECS 05-9541 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9541 LUCY GEMINI 3 CONFIGURATION PROCEDURE EPN, LPN, SPN This document details the configuration procedure for

More information

EOS LUCY GEMINI 3 TYPE E RTU

EOS LUCY GEMINI 3 TYPE E RTU Document Number: EOS 05-9305 Network(s): Summary: ENGINEERING OPERATION STANDARD EPN, LPN, SPN EOS 05-9305 LUCY GEMINI 3 TYPE E RTU This standard details the application, installation and operation of

More information

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR Document Number: EOS 03-0018 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0018 SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning

More information

EOS LUCY SABRE 'A' RANGE SWITCHGEAR

EOS LUCY SABRE 'A' RANGE SWITCHGEAR Document Number: EOS 03-0027 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0027 LUCY SABRE 'A' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning and operation

More information

EDS SCADA NUMBERING SYSTEM

EDS SCADA NUMBERING SYSTEM Document Number: EDS 05-9007 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 05-9007 SCADA NUMBERING SYSTEM This standard describes the system for numbering SCADA wiring within switchgear

More information

ECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE

ECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0601 GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN Configuration and commissioning procedure for the GPRS/3G/4G

More information

National Light Sources Pty Ltd Electrical Accessories - Date 8th April, Coombes Drive, Penrith, NSW, 2750 Australia

National Light Sources Pty Ltd Electrical Accessories - Date 8th April, Coombes Drive, Penrith, NSW, 2750 Australia National Light Sources Pty Ltd 15 Coombes Drive, Penrith, NSW, 2750 Australia 15 Coombes Drive Penrith NSW 2750 Tel: 02-4732 5444 Fax: 02-4732 6600 Email: sales@nlslight.com.au Product list for Electrical

More information

nls Product List 1st February, 2014 Tel: Fax: Coombes Drive, Penrith, NSW, 2750 Australia

nls Product List 1st February, 2014 Tel: Fax: Coombes Drive, Penrith, NSW, 2750 Australia 15 Coombes Drive, Penrith, NSW, 2750 Australia 15 Coombes Drive Penrith NSW 2750 Tel: 02-4732 5444 Fax: 02-4732 6600 Email: sales@nlslight.com.au Product list for Electrical Accessories Code Item Inner

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

Single-Core PVC 6491X

Single-Core PVC 6491X Single-Core PVC X 0/0 V Application PVC insulated only cable for fixed wiring purposes. Used in trunking or conduit, or may be surface mounted when used for earthing. Specifications In accordance with

More information

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM 1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL

More information

CONSOLE CONNECTOR KIT 9501 INSTALLATION INSTRUCTIONS

CONSOLE CONNECTOR KIT 9501 INSTALLATION INSTRUCTIONS CONSOLE CONNECTOR KIT 9501 INSTALLATION INSTRUCTIONS FOR USE WITH: HAMMOND Organ Models L-100, M-100 Series, M-l, M-2, M-3 LESLIE Speaker Models 760, 770, 825 KIT CONTENT Console Connector Assembly 043075

More information

EDS MW AND MVAR TRANSDUCER CONNECTION

EDS MW AND MVAR TRANSDUCER CONNECTION Document Number: EDS 05-5001 Network(s): Summary: ENINEERIN DESIN STANDARD EDS 05-5001 MW AND MVAR TRANSDUCER CONNECTION EPN, LPN, SPN This standard details the convention to be used when wiring MW and

More information

1. Carefully unpack the um260 s shipping carton and check the contents for damage.

1. Carefully unpack the um260 s shipping carton and check the contents for damage. um260 Installation Manual um260 Installation Chapter 4 um260 MICRO MONITOR INSTALLATION This section of the um260 Micro Monitor Installation Manual describes the requirements and procedures for installing

More information

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions RCD Fused Connection Unit Model: RCD10WPV RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV Installation & Operating Instructions General The Timeguard range of RCDs provides protection

More information

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Peripheral Relay The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Up to 16 Cards can be connected to a multi-loop panel

More information

Electrical Accessories 1st June, 2016

Electrical Accessories 1st June, 2016 15 Coombes Drive, Penrith, NSW, 2750 Australia 15 Coombes Drive Penrith NSW 2750 Tel: 02-4732 5444 Fax: 02-4732 6600 Email: sales@nlslight.com.au Product list for Electrical Accessories Code Item Inner

More information

Transparent Covers for Rail-Mounted Terminal Blocks, Usable with Lead Seals Description and Handling

Transparent Covers for Rail-Mounted Terminal Blocks, Usable with Lead Seals Description and Handling Transparent Covers for Rail-Mounted Terminal Blocks, Usable with Lead Seals Description and Handling 572 Assembly Application Snapping a cover carrier onto the carrier rail. Application examples: cover

More information

EDS LV CUSTOMER UNMETERED SUPPLIES

EDS LV CUSTOMER UNMETERED SUPPLIES Document Number: EDS 08-2102 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-2102 LV CUSTOMER UNMETERED SUPPLIES EPN, LPN, SPN This standard details the requirements for unmetered single-phase

More information

IF-80x Outdoor Terminal

IF-80x Outdoor Terminal 95-10330_IF-800 V2016-10-20 Outdoor Terminal IF-80x Outdoor Terminal 1 IF-800 Outdoor / IF-801 We are pleased that you have decided to use a terminal of the IF-80x series for recording access data. Scope

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

COMPLETE S YSTEM SHELTER

COMPLETE S YSTEM SHELTER COMPLETE S YSTEM SHELTER The weather-resistant Complete System Shelter (CSS) provides protection from the elements for system components such as the console, Solar Power Kit components, sensor interface

More information

ACCESSORIES. Accessories for distance and position sensors Magnets for HLT 1000, HLT 2000, HNT Electrical accessories HLT

ACCESSORIES. Accessories for distance and position sensors Magnets for HLT 1000, HLT 2000, HNT Electrical accessories HLT Accessories ACCESSORIES Accessories to suit every sensor! Whether it's electrical connectors, mechanical adapters or the instrument mounting clamps, the wide range of products from HYDAC offers solutions

More information

Installing the Cisco AS5400XM Universal Gateway

Installing the Cisco AS5400XM Universal Gateway CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,

More information

sonnen Installation Practical

sonnen Installation Practical sonnen Installation Practical sonnen Components sonnenbatterie eco 8.0 Single Phase System Components 4 sonnenbatterie eco 8.0 Single Phase System Components 5 sonnenbatterie eco 8.0 Single Phase System

More information

Product Manual ASL Document Ref.: U doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23

Product Manual ASL Document Ref.: U doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23 Product Manual ASL Document Ref.: U-0618-0103.doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23 RCS01 RPA Transmitter Charging Station This equipment is designed and manufactured

More information

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions

More information

Installation Manual. Table of Contents

Installation Manual. Table of Contents Table of Contents Table of Contents... 4-1 4.1 Confirming the Installation Preparations... 4-1 4.2 Installation Flowchart... 4-1 4.3 Mounting the Switch to the Designated Position... 4-2 4.3.1 Mounting

More information

M12 connector D-coding M12 connector X-coding RJ45 IP20 connector PushPull RJ45 IP65 / IP67 connector

M12 connector D-coding M12 connector X-coding RJ45 IP20 connector PushPull RJ45 IP65 / IP67 connector M12 connectors Directory Chapter Page General information....02 M12 connector D-coding....06 M12 connector X-coding....20 RJ45 IP20 connector....27 PushPull RJ45 IP65 / IP67 connector....46 Han 3 A RJ45

More information

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES Network(s): Summary: ENGINEERING BULLETIN EBB 08-0061 PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES EPN, SPN This bulletin provides a framework for the pilot scheme for unmetered

More information

Replacing the Power Supply

Replacing the Power Supply APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools

More information

Digital Keypad Introduction

Digital Keypad  Introduction K2 Digital Keypad Introduction The K02 uses the latest microprocessor technology to operate door strikes and security systems that require a momentary (timed) or latching dry contact closure. All programming

More information

Supplementary instructions. Plug connector Harting HAN 7D. For point level sensors. Document ID: 34456

Supplementary instructions. Plug connector Harting HAN 7D. For point level sensors. Document ID: 34456 Supplementary instructions Plug connector Harting HAN 7D For point level sensors Document ID: 446 Contents Contents For your safety.... Appropriate use.... General safety instructions.... Safety instructions

More information

From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES. Date: 15 August 2007 (Supersedes the 06 March 2007 issue)

From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES. Date: 15 August 2007 (Supersedes the 06 March 2007 issue) Memorandum To: Donna Ward, DEPOT FINANCIAL SERVICES SUPERVISOR From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES cc: Date: 15 August 2007 (Supersedes the 06 March 2007 issue) Re: Purchase Specification

More information

Basketball Shot Clock Set LX2180 Manual

Basketball Shot Clock Set LX2180 Manual Basketball Shot Clock Set LX2180 Manual 72 Industrial Boulevard Wrightsville, GA 31096 Phone: (800) 445-7843 Fax: (800) 864-0212 www.electro-mech.com LX2180 Revision 5 February 8, 2013 Table of Contents

More information

Cardax Prox Plus Mifare Reader

Cardax Prox Plus Mifare Reader Installation Note Cardax Prox Plus Mifare Reader CAUTION This equipment contains components that can be damaged by electrostatic discharge. Ensure both you and the equipment are earthed before beginning

More information

BreezeMAX Wi² and BreezeACCESS Wi² Quick Installation Guide

BreezeMAX Wi² and BreezeACCESS Wi² Quick Installation Guide This Quick Installation Guide is intended for experienced installers. For more information refer to the relevant sections in the BreezeMAX Wi² and BreezeACCESS Wi² System Manual. Wi² Package Content Check

More information

AIR TERMINALS: COPPER

AIR TERMINALS: COPPER AIR TERMINALS: COPPER A ADAPTER TYPE B LESS ADAPTER LA TYPE A B C A B C A B C 3 8 COPPER POINTS (CLASS I ONLY) 1 2 COPPER POINTS (CLASS I OR II) 5 8 COPPER POINTS (CLASS I OR II) THE 3 8 COPPER AND ALUMINUM

More information

Procedure to Install an IO Expansion Cage Assembly in a Maxum II Modular Oven Analyzer

Procedure to Install an IO Expansion Cage Assembly in a Maxum II Modular Oven Analyzer Procedure to Install an IO Expansion Cage Assembly in a Maxum II Modular Oven Analyzer Difficulty Level: Medium Estimated time to execute: 1 Hour Revision History Issue Date Reason 001 5/31/2016 Initial

More information

Modular Terminal Blocks and Terminal Strips with CAGE CLAMP, Series 260 to 262, Side-Entry

Modular Terminal Blocks and Terminal Strips with CAGE CLAMP, Series 260 to 262, Side-Entry 36 Modular Terminal Blocks and Terminal Strips with CAGE CLAMP, Series 260 to 262, Side-Entry Assembly Assembly of modular terminal blocks to terminal strips Mounting of an end plate screw fixing CAGE

More information

for a perfect electrical installation. The range of rail-mounted terminal blocks

for a perfect electrical installation. The range of rail-mounted terminal blocks The range of rail-mounted terminal blocks for a perfect electrical installation. The range of rail-mounted terminal blocks for a perfect electrical installation. The new standard for rail-mounted terminal

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Wired Remote Controller 7 Day Programmable Ductless Systems KSACN0401AAA (High Wall Models) KSACN0501AAA (Ducted/Cassette Models) INSTALLATION INSTRUCTIONS NOTE: Read the entire instruction manual before

More information

Installing Power Modules

Installing Power Modules This chapter contains the procedures for installing cards and modules into the chassis after the chassis has been installed into a rack. This chapter also describes how to connect cables to RSP, RP, alarm,

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

PAR+ & MSC+ Controller. Installation Manual

PAR+ & MSC+ Controller. Installation Manual PAR+ & MSC+ Controller Installation Manual Contents Introduction... 1 System Configuration...1 Parts List and Tools Required for Installation...1 Installation Checklist...1 Mount Controller Pedestal on

More information

E1135C PDU and Pod Upgrade Procedure

E1135C PDU and Pod Upgrade Procedure E4030-90010 Rev. B 12/2003 In this Document... Tools Needed, 2 Contents of the Upgrade Kits, 2 Installation Procedures, 4 Verifying the Power Option of the New PDU, 4 Removing the PDU from the Support

More information

Cord- Mounted Female. Mounted Male. Strain relief clamp # needs to be ordered separately w/cord-mounted connections.

Cord- Mounted Female. Mounted Male. Strain relief clamp # needs to be ordered separately w/cord-mounted connections. -Pin Amp Plastic 0883 Kit (consists of) 080 Receptacle 03 Pins (Qty ) 088 Kit (consists of) 080 Connector 03 Sockets (Qty ) Note: Strain relief clamp 03 needs to be ordered separately with cord-mounted

More information

Accessories for control enclosures. BERNSTEIN attachment solutions. Double coupling head (console version with suspension system attachment)

Accessories for control enclosures. BERNSTEIN attachment solutions. Double coupling head (console version with suspension system attachment) 25 Accessories for control enclosures BERNSTEIN attachment Single coupling head (suspended console version) Double coupling head (console version with suspension system attachment) 322.5 231 232 140 The

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

Terminals, Lugs, and Fasteners

Terminals, Lugs, and Fasteners Terminals, Lugs, and Fasteners East Penn cast terminals are manufactured with 100% recycled lead. Lead is recognized as the premium choice in battery cable terminals because of its maximum current carrying

More information

SERVICE PARTS MANUAL

SERVICE PARTS MANUAL SERVICE PARTS MANUAL 8 SERIES SNOW PLOW FOR SERIAL NUMBERS AFTER 8D100000 00 Sno-Way International 9100G TABLE OF CONTENTS PAGE DEFLECTORS... POWER PACK... HYDRAULIC POWER UNIT... LIFT CYLINDER... ANGLE

More information

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module Han termination Contents Page Han-Fast Lock... 20.11 adapter for Han DD... 20.13 adapter for Han DDD module... 20.16 adapter for Han 40 A Axial module... 20.18 adapter for Han E... 20.20 adapter for Han

More information

CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Receptacle Kit and a Protective Cover Assembly.

CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Receptacle Kit and a Protective Cover Assembly. Revised Sept-28-2009 Sealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System Instructions CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Kit

More information

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2 document Page 1 of 18 TECHKNOW, INC Kiosk Order Confirmation System INSTALLATION MANUAL Revision Date: July 11, 2012 Part # Version 3.2 Techknow, Inc. 393 Mayfield Road Duncan, SC 29334 www.gotechknow.com

More information

(Above 100km Distance) (Streetlight Pole) (Above 100km Distance) (Streetlight Pole)

(Above 100km Distance) (Streetlight Pole) (Above 100km Distance) (Streetlight Pole) Part 9 Miscellaneous Drawing Register Number Description M1-1 SSN Network Device with LV Aerial Supply (ABC) Arrangement M1-2 SSN Network Device with LV Aerial Supply Arrangement M1-3 SSN Network Device

More information

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS (WITH CAPACITOR CHARGER BOARD A3517-02) The process depends on Generator and System configuration. This document applies to installation of Capacitors

More information

Standard Buccaneer BUCCANEER FOR POWER

Standard Buccaneer BUCCANEER FOR POWER IP8 rating tested at 1.05kg/sq cm (15lb/sq in) 10m depth for weeks and.8kg/sq cm (10lb/sq in) 100m depth for hours IPK, Tested in accordance with DIN 0050/Part IPkk Water and dustproof to IP8 when mated,,,,,,

More information

TCNM-ACBB1 Installation Manual

TCNM-ACBB1 Installation Manual The TCNM-ACBB1 is a connection box that can be used as an accessory to facilitate system connections for installation and device replacement of several Banner family reading devices. System cabling is

More information

Quick Start Guide. Preparation. Installation. Operation. Support. Vaisala NOMAD 3 Data Logger. Online manuals

Quick Start Guide. Preparation. Installation. Operation. Support. Vaisala NOMAD 3 Data Logger. Online manuals Quick Start Guide www.vaisala.com Vaisala NOMAD 3 Data Logger Preparation Package Contents Plan Instrumentation Create a SkyServe Account Activating the Nomad 3 Nomad 3 Toolbox Create Setup Files 2 4 5

More information

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution

More information

Codian MSE 8000 Media Services Engine

Codian MSE 8000 Media Services Engine Codian MSE 8000 Media Services Engine Getting started Codian MSE 8000 Media Services Engine Getting started Copyright Codian 2008. All rights reserved. This Getting Started Guide may not be copied, photocopied,

More information

M-Line Series MN Multi-Pin Plugs and Receptacles Vac, Vdc

M-Line Series MN Multi-Pin Plugs and Receptacles Vac, Vdc Applications Designed for the roughest industrial applications, providing reliable, rugged service for power, control and instrumentation. For use in the roughest industrial applications, ranging from:

More information

Switches and Indicators 84

Switches and Indicators 84 Switches and Indicators 84 84 Switches and Indicators Index Series 84 Description Page 177 Product Assembly Page 178 Mounting Instruction Page 179 Product Range - pushbuttons for flush mounting - accessories

More information

Installing a Power over Ethernet injector

Installing a Power over Ethernet injector Installing a Power over Ethernet injector AlphaEclipse StreetSmart and RoadStar signs The instructions in this document explain how to install/replace a Power over Ethernet (PoE) injector in a StreetSmart

More information

Adaptors. Circular Adaptors Polamco design and manufacture the following circular adaptors:

Adaptors. Circular Adaptors Polamco design and manufacture the following circular adaptors: Adaptors Circular Adaptors Polamco design and manufacture the following circular adaptors: Non Screened 37 Series Cable Seal Adaptors 76 Series Low Profile Fixed Adaptors 77 Series Adaptors with Cable

More information

SUN2000-(33KTL, 36KTL, 40KTL)-US Quick Guide (Mounting Bracket Supplied with the SUN2000, Amphenol Helios H4)

SUN2000-(33KTL, 36KTL, 40KTL)-US Quick Guide (Mounting Bracket Supplied with the SUN2000, Amphenol Helios H4) SUN2000-(33KTL, 36KTL, 40KTL)-US Quick Guide (Mounting Bracket Supplied with the SUN2000, Amphenol Helios H4) Issue: 03 Part Number: 31508086 Date: 2017-11-06 HUAWEI TECHNOLOGIES CO., LTD. NOTICE 1. The

More information

POSEIDON SCIENTIFIC INSTRUMENTS PTY LTD 17 QUEEN VICTORIA ST, FREMANTLE WA PHONE (08) FAX (08) MWA-3014

POSEIDON SCIENTIFIC INSTRUMENTS PTY LTD 17 QUEEN VICTORIA ST, FREMANTLE WA PHONE (08) FAX (08) MWA-3014 CABLE DRAWING: DRAWING TITLE: ATIM-T Power Cable POSEIDON SCIENTIFIC INSTRUMENTS PTY LTD 17 QUEEN VICTORIA ST, FREMANTLE WA 6160. PHONE (08) 9430 6639 FAX (08) 9335 4650 MWA-3014 DRAWING NO.: MWACAB-0014

More information

SERVICE PARTS MANUAL

SERVICE PARTS MANUAL SERVICE PARTS MANUAL SERIES SNOW PLOWS WITH EIS PLOW LIGHT HARNESS CONNECTIONS FOR GRAVITY HYDRAULICS WITH SERIAL NUMBERS BEFORE G10000 WITH SERIAL NUMBERS AFTER G00000 FOR DOWN PRESSURE HYDRAULICS WITH

More information

6491X Singles. Size Amps 100m

6491X Singles. Size Amps 100m Cable 6242Y Twin & Earth 6491X Singles Coax Cable 1.0mm 13 17.00 1.5mm 16.5 22.00 2.5mm 23 30.95 4.0mm 29 56.25 6.0mm 38 76.55 10.0mm 52 124.30 16.0mm 69 201.60 1.5mm 17 9.30 2.5mm 24 13.50 4.0mm 32 25.00

More information

Service Managed Gateway TM. Installing and Configuring the GW8600 SMG

Service Managed Gateway TM. Installing and Configuring the GW8600 SMG Service Managed Gateway TM Installing and Configuring the GW8600 SMG Issue 1.1 Date 14 August 2007 Table of Contents 1 About this document...3 1.1 Scope...3 1.2 Readership...3 1.3 More information...3

More information

Posi-Lok Plugs and Panels

Posi-Lok Plugs and Panels THE SAFEST ELECTRICAL SYSTEM FOR HIGH AMPERAGE CONNECTIONS, POSI-LOK IS PART OF THE CAM-LOK FAMILY OF CONNECTORS. THE GROUND ALWAYS MAKES FIRST AND BREAKS LAST ALL POSI-LOK SYSTEMS ARE UL LISTED AND CSA

More information

Standard icontrol Power Supply Kit

Standard icontrol Power Supply Kit Instruction Sheet P/N 07150A Standard icontrol Power Supply Kit This instruction sheet is a guide for upgrading to the Standard icontrol Power Supply. WARNING: Allow only qualified personnel to perform

More information

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm Long Distance Cylindrical. Extra long for increased protection and sensing performance triple proximity sensors for flush mounting requirements. designed and tested for extra long life. Ordering Information

More information

Parts and Accessories Installation Instructions

Parts and Accessories Installation Instructions Parts and Accessories Installation Instructions F 36 0 M Ericsson handsfree facility retrofit kit BMW 3 Series Saloon (E36/) LHD BMW 3 Series Coupé (E36/) LHD BMW 3 Series touring (E36/3) LHD BMW 3 Series

More information

SERVICE PARTS MANUAL

SERVICE PARTS MANUAL SERVICE PARTS MANUAL DX SERIES SNOW PLOW FOR SERIES SNOW PLOWS SERIAL NUMBERS AFTER DX0000 00 Sno-Way International 0G TABLE OF CONTENTS Page HYDRAULIC SYSTEM (DX)... POWER PACK FRAME... 3 BLADES... LIFT

More information

Supplementary instructions. Plug connector Harting HAN 8D. for continuously measuring sensors. Document ID: 30376

Supplementary instructions. Plug connector Harting HAN 8D. for continuously measuring sensors. Document ID: 30376 Supplementary instructions Plug connector Harting HAN 8D for continuously measuring sensors Document ID: 30376 Contents Contents 1 For your safety 1.1 Appropriate use... 3 1.2 Impermissible use... 3 1.3

More information

Parts and Accessories Installation Instructions

Parts and Accessories Installation Instructions Parts and Accessories Installation Instructions TV function retrofit kit BMW 7 Series (E 65 and E 66) These installation instructions are only valid for cars with SA 69 (navigation system) Important information

More information

Vapor Monitor Interface Module

Vapor Monitor Interface Module Manual No: 577013-951 Revision: A Vapor Monitor Interface Module Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the

More information

TDM To MiniMech conversion ProceDure

TDM To MiniMech conversion ProceDure TDM To MiniMech conversion ProceDure (Model 9100 ATM) TDN 07102-00079 Apr 1 2009 CorporATe HeAdquArTers: 522 E. Railroad Street Long Beach, MS 39560 PHONE: (228) 868-1317 FAX: (228) 868-0437 COPYRIGHT

More information

Network nodes with gateway

Network nodes with gateway 2 878 Siemeca AMR Network nodes with gateway WTX16.GSM WTX16.IP WTX16.MOD The WT 16 network nodes are used to receive and handle the data transmitted by consumption meters of the Siemeca AMR system. They

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

IT power distribution Power distribution units (PDU) Basic. Versions available:

IT power distribution Power distribution units (PDU) Basic. Versions available: IT PDU Basic 1 U With its IT PDU Basic 1 U, BACHMANN provides a huge choice of PDUs in a high-quality aluminium profile. With their extremely compact size of just 1 height unit, mm in depth and 1" in width,

More information

Warning Before Installation

Warning Before Installation Warning Before Installation English Power off the Network Camera as soon as smoke or unusual odors are detected. Refer to your user's manual for the operating temperature. Contact your distributor in the

More information

WINSTA. Full Line Catalog 2008/2009

WINSTA. Full Line Catalog 2008/2009 WINSTA Full Line Catalog 2008/2009 5 Contents FULL LINE CATALOG W4, Volume 1 Rail-Mounted Terminal Block Systems FULL LINE CATALOG W4 Rail-Mounted Terminal Blocks Volume 1 X-COM -SYSTEM Terminal Strips

More information

Weathersafe Vision. Installation & Operating Instructions

Weathersafe Vision. Installation & Operating Instructions Weathersafe Vision Installation & Operating Instructions IP66 Products covered by these instructions 1 TGVL01 TGVL02 TGVL03 TGVL05 TGV101N TGV201N TGV104N Single Gang 2-Way Switch [SP] 10AX (Fluorescent

More information

Navigator II INstallatIoN MaNUal For static and PaN/tIlt configurations

Navigator II INstallatIoN MaNUal For static and PaN/tIlt configurations Navigator II Installation MANUAL For Static and Pan/Tilt Configurations Document Number: 432-0001-00-12, rev 100 FLIR Systems, Inc., 2008. All rights reserved worldwide. No parts of this manual, in whole

More information

CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS

CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS Throughout this manual, look for this symbol. It means BE ALERT YOUR SAFETY IS INVOLVED. If you do not follow these safety instructions, personal

More information

Megatouch FORCE Monitor Chassis Board Replacement

Megatouch FORCE Monitor Chassis Board Replacement Megatouch FORCE Monitor Chassis Board Replacement Visit the Merit Industries, Inc. Web site http://www.meritind.com merit industries, inc. PM0337-01 Rev C Table of Contents FORCE Classic Monitor Chassis

More information

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy Appendix D EMC Installation Guidelines General Product Philosophy The ZETA6xxx was not designed originally for EMC compliance. Therefore, it will require specific measures to be taken during installation.

More information

Upgrade Instructions. P/N Revision A. October Printer Terminal Holder * *

Upgrade Instructions. P/N Revision A. October Printer Terminal Holder * * Upgrade Instructions P/N 96-08-0 Revision A October 000 480 Printer Terminal Holder P/N 96-08-0 Revision A *96080* Instructions This terminal holder connects the INTERMEC R 600 Series and 700 Series Computers

More information

Sensor Accessories Retroreflectors and Retroreflective Tape Sensor Mounting Brackets Sensor Accessories. 52.

Sensor Accessories Retroreflectors and Retroreflective Tape Sensor Mounting Brackets Sensor Accessories. 52. Retroreflectors Sensor Accessory AC Sensor Tester/Demonstrator Pilot Device E65 Control Unit.1 Retroreflectors and Retroreflective Tape Product............................................. 414 Application..........................................

More information

modular enclosure MUREVA, IP65 weatherproof & versatile enclosures aesthetics multi-functional evolutionary ergonomics and time saving security

modular enclosure MUREVA, IP65 weatherproof & versatile enclosures aesthetics multi-functional evolutionary ergonomics and time saving security aesthetics c Elegant and robust design. c Colour easy to integrate in any environment. weatherproof & versatile enclosures multi-functional c Different solutions for: industrial control, electrical distribution,

More information

Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits

Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits Course Details Date: January 28 January 31, 2019 Time: 8:00 A.M. - 4:30 P.M. Capacity: 12 attendees Provider: National Technology

More information

Avanti HP Series Centrifuges Preinstallation

Avanti HP Series Centrifuges Preinstallation J3HP-TB-001AC May 2009 Avanti HP Series Centrifuges Preinstallation INTRODUCTION Purchase of an Avanti HP series high performance centrifuge includes installation and Basic Instrument Training for two

More information

Outdoor PTZ. Mounting on the Ceiling Using Pendant Mount. Installation Guide. For Models: I93, I94, I95, I96, KCM /12/03

Outdoor PTZ. Mounting on the Ceiling Using Pendant Mount. Installation Guide. For Models: I93, I94, I95, I96, KCM /12/03 Outdoor PTZ Mounting on the Ceiling Using Pendant Mount For Models: I93, I94, I95, I96, KCM-8211 2013/12/03 Table of Contents Mounting Solutions... 3 Straight Tube Installation Procedures... 4 Step 1:

More information