S&C System VI Switchgear Indoor and Outdoor Distribution (15 kv through 38 kv)

Size: px
Start display at page:

Download "S&C System VI Switchgear Indoor and Outdoor Distribution (15 kv through 38 kv)"

Transcription

1 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) I. General 1.01 The witchgear hall be in accordance with the one-line diagram, and hall conform to the following pecification The witchgear hall conit of a ga-tight tank containing SF 6 ga, load-interrupter witche and reettable vacuum fault interrupter with viible open gap and integral viible ground, and a microproceor-baed overcurrent control. Load-interrupter witch terminal hall be equipped with buhing rated ampere continuou, and fault-interrupter terminal hall be equipped with buhing well rated 200 ampere continuou or buhing rated ampere continuou (a pecified) to provide for elbow connection. Manual operating mechanim and viewing window hall be located on the oppoite ide of the tank from the buhing and buhing well o that operating peronnel hall not be required to perform any routine operation in cloe proximity to high-voltage elbow and cable. Metering bay hall be connected to witching cubicle via buhing connecting the bu of the witching cubicle to the bu of the metering bay Rating The rating for the integrated witchgear hall be a deignated below. (Select value from one of the column hown in the table on page 2.) Frequency, Hz kv, Maximum kv, BIL Main Bu Continuou, Ampere Three-Pole Load-Interrupter Switche Continuou, Ampere Load Dropping, Ampere Ten-Time Duty-Cycle Fault-Cloing, Ampere RMS Symmetrical Ampere, Peak Fault Interrupter Continuou, Ampere Load Dropping, Ampere Ten-Time Duty-Cycle Fault Interrupting, Ampere RMS Symmetrical Ten-Time Duty-Cycle Fault-Cloing, Ampere RMS Symmetrical Ampere, Peak Short-Circuit Rating Ampere, RMS Symmetrical New Publication c2000 Page 1 of 10

2 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) SELECTION OF RATINGS1 IEC ANSI Frequency, Hz or or 60 kv Voltage Cla Max BIL Main Bu Continuou, Ampere Three-Pole Load- Interrupter Switche Fault Interrupter Short- Circuit Rating Continuou, Ampere Load Dropping, Ampere Ten-Time Duty-Cycle Fault Cloing, Ampere RMS Symmetrical Ampere, Peak Continuou, Ampere Load Dropping, Ampere Ten-Time Duty-Cycle Fault Interrupting, Ampere RMS Symmetrical Ten-Time Duty-Cycle Fault Cloing, Ampere RMS Symmetrical Ampere, Peak Ampere, RMS Symmetrical Actual capabilitie may be limited to lower value by the buhing inert, elbow, and cable ued on thee unit. a Rating are ampere ( ampere for IEC) continuou and load dropping when the fault interrupter are furnihed with - ampere buhing Certification of Rating The manufacturer of the witchgear hall be completely and olely reponible for the performance of the load-interrupter witch and fault interrupter a well a the complete integrated aembly a rated. The manufacturer hall furnih, upon requet, certification of rating of the load-interrupter witch, fault interrupter, and the integrated witchgear aembly coniting of witche and fault interrupter in combination with the ga-tight tank Compliance with Standard and Code The witchgear hall conform to or exceed the applicable requirement of the following tandard and code: The applicable portion of ANSI C , covering encloure integrity for padmounted equipment. The applicable portion of ANSI C37.71, ANSI C37.72, ANSI C37.73, IEC 56, and IEC (Cla A), which pecify tet procedure and equence for the load-interrupter witche, fault interrupter, and the complete witchgear aembly. The following optional feature hould be pecified a required: The applicable portion of IEC 298, Appendix AA covering arc reitance, through 12.5 ka for 15 cycle. Page 2 of 10

3 II. Contruction (Switching and Interrupting Cubicle) 2.01 SF 6 -Ga Inulation The SF 6 ga hall conform to ASTM D2472. The witchgear hall be filled with SF 6 ga to a preure of 7 pig at 68º F. The ga-tight tank hall be evacuated prior to filling with SF 6 ga to minimize moiture in the tank. The witchgear hall withtand ytem voltage at a ga preure of 0 pig at 68º F. (f) 2.02 Ga-Tight Tank A ga-fill valve hall be provided. A temperature-compenated preure gauge hall be provided that i color coded to how the operating range. The gauge hall be mounted inide the ga-tight tank (viible through a large viewing window) to provide conitent preure reading regardle of the temperature or altitude at the intallation ite. The tank hall be ubmerible and able to withtand up to 10 feet of water over the bae. The tank hall be of welded contruction and hall be made of 7-gauge mild teel or Type 304 tainle teel, a pecified in Section IV. A mean of lifting the tank hall be provided Ga-Tight Tank Finih (for mild teel only) To remove oil and dirt, to form a chemically and anodically neutral converion coating to improve the finih-to-metal bond, and to retard underfilm propagation of corroion, mild-teel urface hall undergo a thorough pretreatment proce compried of a fully automated ytem of cleaning, rining, phophatizing, ealing, drying, and cooling, before any protective coating are applied. By utilizing an automated pretreatment proce, the mild-teel urface of the ga-tight tank hall receive a highly conitent thorough treatment, eliminating fluctuation in reaction time, reaction temperature, and chemical concentration. After pretreatment, protective coating hall be applied that hall help reit corroion and protect the mild-teel urface of the ga-tight tank. To etablih the capability to reit corroion and protect the mild teel, repreentative tet pecimen coated by the manufacturer finihing ytem hall atifactorily pa the following tet: (1) 1500 hour of expoure to alt-pray teting per ASTM B 117 with: (i) Underfilm corroion not to extend more than ¹ ₃₂ from the cribe a evaluated per ASTM D 1645, Procedure A, Method 2 (craping); and (ii) Lo of adheion from bare metal not to extend more than ¹ ₈ from the cribe. Page 3 of 10

4 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) (2) 1000 hour of humidity teting per ASTM D 4585 uing the Cleveland Condening Type Humidity Cabinet with no blitering a evaluated per ASTM D 714. (3) Crohatch adheion teting per ASTM D 3359 Method B with no lo of finih. Certified tet abtract ubtantiating the above capabilitie hall be furnihed upon requet. The finih hall be inpected for cuff and cratche. Blemihe hall be touched up by hand to retore the protective integrity of the finih. The finih hall be indoor light gray, atifying the requirement of ANSI Standard Z55.1 for No Viewing Window 2.05 High-Voltage Bu Each load-interrupter witch hall be provided with a large viewing window at leat 6 inche by 12 inche to allow viual verification of the witch-blade poition (open, cloed, and grounded) while hining a flahlight on the blade. Each fault interrupter hall be provided with a large viewing window at leat 6 inche by 12 inche to allow viual verification of the diconnect-blade poition (open, cloed, and grounded) while hining a flahlight on the blade. Viewing window hall be located on the oppoite ide of the gear from the buhing and buhing well o that operating peronnel hall not be required to perform any routine operation in cloe proximity to high-voltage elbow and cable. A cover hall be provided for each viewing window to prevent operating peronnel from viewing the flah which may occur during witching operation. Bu and interconnection hall withtand the tree aociated with hort-circuit current up through the maximum rating of the witchgear. Before intallation of aluminum bu, all electrical contact urface hall firt be prepared by machine abrading to remove any oxide film. Immediately after thi operation, the electrical contact urface hall be coated with a uniform coating of an oxide inhibitor and ealant Proviion for Grounding 2.07 Termination One ground-connection pad hall be provided on the ga-tight tank of the witchgear. The ground-connection pad hall be contructed of tainle teel and welded to the ga-tight tank, and hall have a hort-circuit rating equal to that of the witchgear. Terminal for load-interrupter witche hall have -ampere buhing, and terminal for fault interrupter hall have 200-ampere buhing well to permit connection of elbow. Page 4 of 10

5 Buhing and buhing well hall be located on one ide of the gear to reduce the required operating clearance. The following optional feature hould be pecified a required: Terminal for fault interrupter hall be equipped with -ampere buhing. Buhing rated ampere continuou hall be provided without a threaded tud. Terminal for load-interrupter witche hall be equipped with 200-ampere buhing well Buhing and Buhing Well Buhing and buhing well hall conform to ANSI/IEEE Standard 386 (ANSI Standard C119.2). Buhing and buhing well hall include a emiconductive coating. Buhing and buhing well hall be mounted in uch a way that the emiconductive coating i olidly grounded to the ga-tight tank. III. Baic Component 3.01 Load-Interrupter Switche 3.02 Fault Interrupter The three-phae, gang-operated load-interrupter witche hall have a ten-time dutycycle fault-cloing rating equal to or exceeding the hort-circuit rating of the witchgear. Thi rating define the ability to cloe the witch ten time againt a three-phae fault with aymmetrical (peak) current in at leat one phae equal to the rated value, with the witch remaining operable and able to carry and interrupt rated current. Certified tet abtract etablihing uch rating hall be furnihed upon requet. The witch hall be provided with an integral ground poition that i readily viible through the viewing window to eliminate the need for cable handling and expoure to high voltage to ground the equipment. The ground poition hall have a ten-time duty-cycle fault-cloing rating. The witch hall be provided with an open poition that i readily viible through the viewing window to eliminate the need for cable handling and expoure to high voltage to etablih a viible gap. The open gap of the witch hall be ized to allow cable teting through a feedthru buhing or the back of the elbow. Fault interrupter hall have a ten-time duty-cycle fault-cloing and fault interrupting rating equal to or exceeding the hort-circuit rating of the witchgear. Thi rating define the fault interrupter ability to cloe ten time againt a three-phae fault with aymmetrical (peak) current in at leat one phae equal to the rated value and clear the reulting fault current, with the interrupter remaining operable and able to carry and interrupt rated current. Certified tet abtract etablihing uch rating hall be furnihed upon requet. Page 5 of 10

6 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) (f) 3.03 Operating Mechanim (f) 3.04 Overcurrent Control The fault interrupter hall be provided with a diconnect with an integral ground poition that i readily viible through the viewing window to eliminate the need for cable handling and expoure to high voltage to ground the equipment. The ground poition hall have a ten-time duty-cycle fault-cloing rating. The diconnect hall be provided with an open poition that i readily viible through the viewing window to eliminate the need for cable handling and expoure to high voltage to etablih a viible gap. The open gap of the diconnect hall be ized to allow cable teting through a feedthru buhing or the back of the elbow. An internal indicator hall be provided for each fault interrupter to how when it i in the tripped condition. The indicator hall be clearly viible through the viewing window. Load-interrupter witche and fault interrupter hall be operated by mean of a quickmake, quick-break mechanim. The manual handle hall charge the operating mechanim for opening, cloing, and grounding of the witche and fault interrupter. Operating mechanim hall be equipped with an operation elector to prevent inadvertent operation from the cloed poition directly to the grounded poition, or from the grounded poition directly to the cloed poition. The operation elector hall require phyical movement to the proper poition to permit the next operation. Operating haft hall be padlockable in any poition to prevent operation. The operation elector hall be padlockable to prevent operation to the grounded poition. The operating mechanim hall indicate witch poition which hall be clearly viible from the normal operating poition. A microproceor-baed overcurrent control hall be provided to initiate fault interruption. The control hall be capable of ingle-pole or three-pole tripping of each fault interrupter. The control hall be mounted in a watertight encloure and hall be removable in the field without taking the gear out of ervice. Control etting hall be field programmable uing a peronal computer connected via a data port to the control. The data port hall be acceible from the exterior of the encloure. Power and ening for the control hall be upplied by integral current tranformer. Page 6 of 10

7 (f) (g) (h) (i) The minimum total clearing time (from initiation of the fault to total clearing) for fault interruption hall be 40 milliecond (2.4 cycle) at 60 hertz or 44 milliecond (2.2 cycle) at 50 hertz. The control hall feature time-current characteritic (TCC) curve including tandard E-peed, coordinating-peed tap, and coordinating-peed main curve. Coordinatingpeed tap curve hall optimize coordination with load-ide weak-link/backup currentlimiting fue combination, and coordinating-peed main curve hall optimize coordination with tap-interrupter curve. The tandard E-peed curve hall have phae-overcurrent etting ranging from 25E through 200E. The coordinating-peed tap curve hall have phae-overcurrent and independent ground-overcurrent etting ranging from 50 ampere through 400 ampere. The coordinating-peed main curve hall have phae-overcurrent and independent ground-overcurrent etting ranging from 100 ampere through 800 ampere. The control hall have intantaneou-trip (1 ka through 8 ka) and definite-time delay (32 m through 96 m) etting to allow tailoring of the coordinating-peed tap and coordinating-peed main curve to the application Optional Voltage Indication (Select voltage indication or voltage indication with proviion for low-voltage phaing.) Voltage indication (1) Voltage indication for each load-interrupter witch and fault interrupter by mean of capacitive tap on the buhing hall be provided to eliminate the need for cable handling and expoure to high voltage to tet the cable for voltage. Thi feature hall include a flahing LCD diplay to indicate the preence of voltage for each phae, and a olar panel to upply power for teting of the complete voltage-indication circuit. (2) The voltage-indication feature hall be mounted on the cover for the viewing window on the oppoite ide of the gear from the buhing and buhing well o that operating peronnel hall not be required to perform any routine operation in cloe proximity to high-voltage elbow and cable. Voltage indication with proviion for low-voltage phaing (1) Voltage indication with proviion for low-voltage phaing for each load-interrupter witch and fault interrupter by mean of capacitive tap on the buhing hall be provided to eliminate the need for cable handling and expoure to high voltage to tet the cable for voltage and phaing. Thi feature hall include a flahing LCD diplay to indicate the preence of voltage for each phae, and a olar panel to upply power for teting of the complete voltage-indication circuit and phaing circuit. (2) The voltage-indication feature hall be mounted on the cover for the viewing window on the oppoite ide of the gear from the buhing and buhing well o that operating peronnel hall not be required to perform any routine operation in cloe proximity to high-voltage elbow and cable. Page 7 of 10

8 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) IV. Switchgear Encloure 4.01 Tank contruction (for witching and interrupting cubicle) The ga-tight tank hall be made of 7-gauge mild teel. The following optional feature hould be pecified a required: To guard againt corroion due to extremely harh environmental condition, the gatight tank hall be made of Type 304 tainle teel Encloure (for witching and interrupting cubicle) (f) (g) (h) (i) (j) (k) The witchgear hall be provided with a pad-mounted encloure uitable for intallation of the gear on a concrete pad. The pad-mounted encloure hall be eparable from the witchgear to allow clear acce to the buhing and buhing well for cable termination. The baic material hall be 14-gauge hot-rolled, pickled, and oiled teel heet. The encloure hall be provided with removable front and back panel, and hinged liftup roof ection for acce to the operating and termination compartment. Each roof ection hall have a retainer to hold it in the open poition. Lift-up roof ection hall overlap the panel and hall have proviion for padlocking that incorporate a mean to protect the padlock hackle from tampering. The bae hall conit of continuou 90-degree flange, turned inward and welded at the corner, for bolting to the concrete pad. Panel opening hall have 90-degree flange, facing outward, that hall provide trength and rigidity a well a deep overlapping between panel and panel opening to guard againt water entry. For buhing rated ampere continuou, the termination compartment hall be of an adequate depth to accommodate encapulated urge arreter mounted on -ampere elbow having 200-ampere interface. For buhing well rated 200 ampere continuou, the termination compartment hall be of an adequate depth to accommodate 200-ampere elbow mounted on feedthru inert. An intruction manual holder hall be provided. Non-removable lifting tab hall be provided Encloure Contruction (metering cubicle) In etablihing the requirement for the encloure deign, conideration hall be given to all relevant factor uch a controlled acce; tamper reitance; corroion reitance; protection from ingre of rodent, inect, and weed; and the poibility of arcing fault within the encloure. The material for all external ide of the encloure and the roof hall be 11-gauge hotrolled, pickled, and oiled teel heet. Page 8 of 10

9 4.04 Encloure Finih To guard againt unauthorized or inadvertent entry, there hall be no acce to high voltage through ide or rear heet of the metal-encloed witchgear aembly; and no acce to high voltage by mean of externally removable panel. To guard againt corroion, all hardware (including door fitting, fatener, etc.), all operating-mechanim part, and other part ubject to abraive action from mechanical motion hall be of either nonferrou material, or galvanized or zinc-nickel-plated material. Cadmium-plated ferrou part hall not be ued. All exterior welded eam hall be filled and anded mooth for neat appearance. To remove oil and dirt, to form a chemically and anodically neutral converion coating to improve the finih-to-metal bond, and to retard underfilm propagation of corroion, all urface hall undergo a thorough pretreatment proce compried of a fully automated ytem of cleaning, rining, phophatizing, ealing, drying, and cooling, before any protective coating are applied. By utilizing an automated pretreatment proce, the encloure hall receive a highly conitent thorough treatment, eliminating fluctuation in reaction time, reaction temperature, and chemical concentration. After pretreatment, protective coating hall be applied that hall help reit corroion and protect the teel encloure. To etablih the capability to reit corroion and protect the encloure, repreentative tet pecimen coated by the manufacturer finihing ytem hall atifactorily pa the following tet: (1) 4000 hour of expoure to alt-pray teting per ASTM B 117 with: (i) Underfilm corroion not to extend more than ¹ ₃₂ from the cribe a evaluated per ASTM D 1645, Procedure A, Method 2 (craping); and (ii) Lo of adheion from bare metal not to extend more than ¹ ₈ from the cribe. (2) 1000 hour of humidity teting per ASTM D 4585 uing the Cleveland Condening Type Humidity Cabinet with no blitering a evaluated per ASTM D 714. (3) 500 hour of accelerated weathering teting per ASTM G 53 uing lamp UVB-313 with no chalking a evaluated per ASTM D 659, and no more than 10% reduction of glo a evaluated per ASTM D 523. (4) Crohatch adheion teting per ASTM D 3359 Method B with no lo of finih. (5) 60-inch-pound impact adheion teting per ASTM D 2794 with no chipping or cracking. (6) Oil reitance teting coniting of a 72-hour immerion bath in mineral oil with no hift in color, no treaking, no blitering, and no lo of hardne. (7) 3000 cycle of abraion teting per ASTM 4060 with no penetration to the ubtrate. Certified tet abtract ubtantiating the above capabilitie hall be furnihed upon requet. Page 9 of 10

10 S&C Sytem VI Switchgear Indoor and Outdoor Ditribution (15 kv through 38 kv) The finih hall be inpected for cuff and cratche. Blemihe hall be touched up by hand to retore the protective integrity of the finih. The finih hall be olive green, Munell 7GY3.29/1.5. The following optional feature() hould be pecified a required: (1) To guard againt corroion due to extremely harh environmental condition, the entire exterior of the encloure hall be fabricated from Type 304 tainle teel. The following optional feature hould be pecified a required: (2) The finih hall be outdoor light gray, atifying the requirement of ANSI Standard Z55.1 for No. 70. V. Labeling 5.01 Hazard-Alerting Sign The exterior of the pad-mounted encloure (if furnihed) hall be provided with Warning Keep Out Hazardou Voltage Inide Can Shock, Burn, or Caue Death ign. Each unit of witchgear hall be provided with a Danger Hazardou Voltage Failure to Follow Thee Intruction Will Likely Caue Shock, Burn, or Death ign. The text hall further indicate that operating peronnel mut know and obey the employer work rule, know the hazard involved, and ue proper protective equipment and tool to work on thi equipment. Each unit of witchgear hall be provided with a Danger Keep Away Hazardou Voltage Will Shock, Burn, or Caue Death ign Nameplate, Rating Label, and Connection Diagram Each unit of witchgear hall be provided with a nameplate indicating the manufacturer name, catalog number, model number, date of manufacture, and erial number. Each unit of witchgear hall be provided with a rating label indicating the following: voltage rating; main bu continuou rating; hort-circuit rating; fault-interrupter rating including interrupting and duty-cycle fault-cloing; and load-interrupter witch rating including duty-cycle fault-cloing and hort-time. VI. Acceorie (Specify a required.) 6.01 A hotgun clamp tick (6-5¹ ₂, 8-5¹ ₂ ) in length hall be provided complete with a canva torage bag An adapter cable for connecting an overcurrent control to a uer-furnihed peronal computer (having a 25-pin or 9-pin erial communication port) in the field hall be provided An adapter cable for connecting an overcurrent control removed from it encloure to a uerfurnihed peronal computer (having a 25-pin or 9-pin erial communication port) in the hop hall be provided. Page 10 of 10

AHSC MEDIUM VOLTAGE ELECTRICAL SEPARATION

AHSC MEDIUM VOLTAGE ELECTRICAL SEPARATION AHSC MEDIUM VOLTAGE ELECTRICAL SEPARATION UA Project No. 1126135 GLHN JOB No. 1587.92 VOLUME 1 of 1 August 28, 2018 GLHN Architects & Engineers, Inc. 2939 E Broadway Blvd, Tucson, AZ 85716 T 520.881.4546

More information

1.01 The switchgear shall be in accordance with the single-line diagram and shall conform to the following

1.01 The switchgear shall be in accordance with the single-line diagram and shall conform to the following Outdoor Distribution (15.5 kv through 38 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The switchgear shall be in accordance with the single-line diagram and shall conform to the following

More information

S&C Scada-Mate Switching Systems. Specifications for S&C Current Sensors

S&C Scada-Mate Switching Systems. Specifications for S&C Current Sensors Thi data heet provide pecification for S&C Current Senor particularly when the Scada-Mate Switch i ued in application where the RTU i upplied by other. S&C Scada-Mate Switche include integral enor for

More information

The new. Available exclusively from Richards Manufacturing

The new. Available exclusively from Richards Manufacturing The new 800 Available excluively from Richard Manufacturing RATINGS We do more teting than indutry tandard require. IEEE 386 require either Impule or AC Withtand. We run both on all of our product. Richard

More information

S&C Vista SD Underground Distribution Switchgear Outdoor Distribution (17.5 kv and 29 kv) Detailed Functional Specification Guide

S&C Vista SD Underground Distribution Switchgear Outdoor Distribution (17.5 kv and 29 kv) Detailed Functional Specification Guide Outdoor Distribution (17.5 kv and 29 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.1 The switchgear shall be in accordance with the single-line diagram and shall conform to the following specification.

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

SERIES SD3800 / SD3810 SPECIFICATION

SERIES SD3800 / SD3810 SPECIFICATION SERIES SD3800 / SD3810 SPECIFICATION SOLID DIELECTRIC SINGLE SIDED 15 KV & 25 KV PADMOUNTED VACUUM LOAD INTERRUPTERS AND VACUUM FAULT INTERRUPTERS WITH VISIBLE DISCONNECTS MANUALLY OPERATED / REMOTELY

More information

Specif ications. S&C Remote Supervisory Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)

Specif ications. S&C Remote Supervisory Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv) Outdoor Distribution (15.5 kv through 38 kv) Specif ications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under "SPECIAL

More information

SITRANS F flowmeters SITRANS F US

SITRANS F flowmeters SITRANS F US SITRANS F flowmeter Siemen AG 2008 Overview Application Energy calculation in: Ditrict heating application Chilled water application Combined cooling/heating application Application SITRANS FUE950 i able

More information

EMU-1. User Manual. Engine Monitoring Unit Analogue to NMEA For variant: EMU-1-BAS. Issue 1.06

EMU-1. User Manual. Engine Monitoring Unit Analogue to NMEA For variant: EMU-1-BAS. Issue 1.06 EMU1 Analogue to Uer Manual For variant: EMU1BAS Iue 1.06 2000 EMU1 Content Company information 4 Important Notice 5 Trademark and Regitered Trademark 5 Fair ue Statement 5 Technical Accuracy 5 Product

More information

Installation Instructions & Users Manual

Installation Instructions & Users Manual TATU CENTRAL BATTERY YTEM AUTOMATIC DIAGNOTIC NORMAL FULL CHARGE NORMAL FAT RECHARGE FAILED BATTERY FAILED TRANFER FAILED CHARGER PAED ANNUAL TET LED DIPLAY ORANGE RED RED PAUE ORANGE FLAH RED FLAH RED/

More information

CoreLine Waterproof the clear choice for LED

CoreLine Waterproof the clear choice for LED Lighting CoreLine Waterproof the clear choice for LED CoreLine Waterproof Whether for a new building or renovation of an exiting pace, cutomer want lighting olution that provide quality of light and ubtantial

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

ML85C. Data Sheet. Press fit monitoring module. Special features. Block. diagram PLC. B en

ML85C. Data Sheet. Press fit monitoring module. Special features. Block. diagram PLC. B en ML85C Pre fit monitoring module Special feature Data Sheet Meaurement and evaluation ytem for force/diplacement coure in fitting procee Graphical repreentation of the procee with zoom function Immediate

More information

Professional Baby Scale INSTRUCTION MANUAL BD-815MA

Professional Baby Scale INSTRUCTION MANUAL BD-815MA Profeional Baby Scale INSTRUCTION MANUAL BD-85MA Thank you for purchaing the TANITA digital baby cale. For optimum performance and afety, pleae read thi manual carefully, and keep it handy for future reference.

More information

Multi-Target Tracking In Clutter

Multi-Target Tracking In Clutter Multi-Target Tracking In Clutter John N. Sander-Reed, Mary Jo Duncan, W.B. Boucher, W. Michael Dimmler, Shawn O Keefe ABSTRACT A high frame rate (0 Hz), multi-target, video tracker ha been developed and

More information

1Introduction CHAPTER ONE IN THIS CHAPTER. APEX Drive Description and Block Diagram. ➀ Introduction 1

1Introduction CHAPTER ONE IN THIS CHAPTER. APEX Drive Description and Block Diagram. ➀ Introduction 1 CHAPTER ONE Introduction IN THIS CHAPTER Introduction APE Drive Decription and Block Diagram ➀ Introduction INTRODUCTION Thi uer guide decribe three product. APE0 Servo Drive 6A peak, 8A continuou; phae

More information

E5ZE-8 Multipoint Temperature Controller Communications Manual

E5ZE-8 Multipoint Temperature Controller Communications Manual E5ZE-8 Multipoint Temperature Controller Communication Manual Produced December 2000 Notice: OMRON product are manufactured for ue according to proper procedure by a qualified operator and only for the

More information

Model 2657A-LIM-3 LO Interconnect Module

Model 2657A-LIM-3 LO Interconnect Module Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect

More information

Edits in Xylia Validity Preserving Editing of XML Documents

Edits in Xylia Validity Preserving Editing of XML Documents dit in Xylia Validity Preerving diting of XML Document Pouria Shaker, Theodore S. Norvell, and Denni K. Peter Faculty of ngineering and Applied Science, Memorial Univerity of Newfoundland, St. John, NFLD,

More information

SCHEDULE DOCUMENT CONNECT MPLS SERVICES PUBLIC NODE4 LIMITED 17/07/2017

SCHEDULE DOCUMENT CONNECT MPLS SERVICES PUBLIC NODE4 LIMITED 17/07/2017 SCHEDULE DOCUMENT CONNECT MPLS SERVICES PUBLIC NODE4 LIMITED 17/07/017 SCHEDULE DOCUMENT CONNECT MPLS SERVICES Additional term, Service Decription & Service Level Agreement for ConnectMPLS Service 1. SERVICE

More information

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Laboratory Exercise 6

Laboratory Exercise 6 Laboratory Exercie 6 Adder, Subtractor, and Multiplier The purpoe of thi exercie i to examine arithmetic circuit that add, ubtract, and multiply number. Each circuit will be decribed in VHL and implemented

More information

(12) Patent Application Publication (10) Pub. No.: US 2011/ A1

(12) Patent Application Publication (10) Pub. No.: US 2011/ A1 (19) United State US 2011 0316690A1 (12) Patent Application Publication (10) Pub. No.: US 2011/0316690 A1 Siegman (43) Pub. Date: Dec. 29, 2011 (54) SYSTEMAND METHOD FOR IDENTIFYING ELECTRICAL EQUIPMENT

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

(12) Patent Application Publication (10) Pub. No.: US 2013/ A1. Dhar et al. (43) Pub. Date: Jun. 6, 2013 NY (US) (57) ABSTRACT

(12) Patent Application Publication (10) Pub. No.: US 2013/ A1. Dhar et al. (43) Pub. Date: Jun. 6, 2013 NY (US) (57) ABSTRACT (19) United State US 2013 0145314A1 (12) Patent Application Publication (10) Pub. No.: US 2013/0145314 A1 Dhar et al. (43) Pub. Date: Jun. 6, 2013 (54) SYSTEMAND METHOD FORCHANGEABLE (52) U.S. Cl. FOCUS

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-STC Kelvin Standard Triaxial Connector Card Description The Model 8020-STC Kelvin Standard

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation.

More information

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2600B-PM-1 200 V Protection Module with 1 A Clamp Description The Model 2600B-PM-1 200 V Protection

More information

Planning of scooping position and approach path for loading operation by wheel loader

Planning of scooping position and approach path for loading operation by wheel loader 22 nd International Sympoium on Automation and Robotic in Contruction ISARC 25 - September 11-14, 25, Ferrara (Italy) 1 Planning of cooping poition and approach path for loading operation by wheel loader

More information

Laboratory Exercise 6

Laboratory Exercise 6 Laboratory Exercie 6 Adder, Subtractor, and Multiplier The purpoe of thi exercie i to examine arithmetic circuit that add, ubtract, and multiply number. Each type of circuit will be implemented in two

More information

ETSI TS V ( )

ETSI TS V ( ) TS 122 153 V14.4.0 (2017-05) TECHNICAL SPECIFICATION Digital cellular telecommunication ytem (Phae 2+) (GSM); Univeral Mobile Telecommunication Sytem (UMTS); LTE; Multimedia priority ervice (3GPP TS 22.153

More information

SIMIT 7. Component Type Editor (CTE) User manual. Siemens Industrial

SIMIT 7. Component Type Editor (CTE) User manual. Siemens Industrial SIMIT 7 Component Type Editor (CTE) Uer manual Siemen Indutrial Edition January 2013 Siemen offer imulation oftware to plan, imulate and optimize plant and machine. The imulation- and optimizationreult

More information

olution nnect S Intercon Speed I November, , HIROSE ELECTRIC CO., LTD. All rights reserved. Rev 3.0 November, 2010 Page 1

olution nnect S Intercon Speed I November, , HIROSE ELECTRIC CO., LTD. All rights reserved. Rev 3.0 November, 2010 Page 1 IT3 erie peed mezzanine Connector Sytem November, 2010 HIROSE ELECTRIC CO., LTD. HIROSE ELECTRIC USA, INC. Page 1 IT3 Serie Deign Overview A New Standard Mezzanine for Flexibility and Performance Flexibility:

More information

vacon nxl the easy and impressive ac drive

vacon nxl the easy and impressive ac drive vacon nxl the eay and impreive ac drive 1 eay to plug, and eaiet to play The Vacon i a powerful and compact AC drive for indutrial and reidential purpoe in the power range from 0.25 to 30 kw. The pace-aving

More information

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only. Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 (440) 248-0400 Fax: (440) 248-6168 www.keithley.com Model 4200-RM Rack Mount Kit Packing List Introduction NOTE This 4200-RM Rack Mount

More information

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module) SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Dimension

More information

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN Padmounted switchgear MN285011EN Effective May 2017 Supersedes November 2004 (S285-10-4) Visible-Break switch accessory operation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Type VFI, Vacuum Fault Interrupter Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear

More information

The Association of System Performance Professionals

The Association of System Performance Professionals The Aociation of Sytem Performance Profeional The Computer Meaurement Group, commonly called CMG, i a not for profit, worldwide organization of data proceing profeional committed to the meaurement and

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

Model 8010 High Power Device Test Fixture Interconnection Reference Guide

Model 8010 High Power Device Test Fixture Interconnection Reference Guide Model 8010 High Power Device Test Fixture Interconnection Reference Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation. Although

More information

Modelling the impact of cyber attacks on the traffic control centre of an urban automobile transport system by means of enhanced cybersecurity

Modelling the impact of cyber attacks on the traffic control centre of an urban automobile transport system by means of enhanced cybersecurity Modelling the impact of cyber attack on the traffic control centre of an urban automobile tranport ytem by mean of enhanced cyberecurity Yoana Ivanova 1,* 1 Bulgarian Academy of Science, Intitute of ICT,

More information

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic

More information

Kinematics Programming for Cooperating Robotic Systems

Kinematics Programming for Cooperating Robotic Systems Kinematic Programming for Cooperating Robotic Sytem Critiane P. Tonetto, Carlo R. Rocha, Henrique Sima, Altamir Dia Federal Univerity of Santa Catarina, Mechanical Engineering Department, P.O. Box 476,

More information

Laboratory Exercise 6

Laboratory Exercise 6 Laboratory Exercie 6 Adder, Subtractor, and Multiplier a a The purpoe of thi exercie i to examine arithmetic circuit that add, ubtract, and multiply number. Each b c circuit will be decribed in Verilog

More information

AUTOMATIC TEST CASE GENERATION USING UML MODELS

AUTOMATIC TEST CASE GENERATION USING UML MODELS Volume-2, Iue-6, June-2014 AUTOMATIC TEST CASE GENERATION USING UML MODELS 1 SAGARKUMAR P. JAIN, 2 KHUSHBOO S. LALWANI, 3 NIKITA K. MAHAJAN, 4 BHAGYASHREE J. GADEKAR 1,2,3,4 Department of Computer Engineering,

More information

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold Tru-Break switchgear module Tru-Break switchgear module agenda Design platform and value Product specifications Operation Configuration examples

More information

Technical Bulletin TB1570. Class: INFO. Subject JVM Software Update Procedure. Series V-Range (501,651,801)

Technical Bulletin TB1570. Class: INFO. Subject JVM Software Update Procedure. Series V-Range (501,651,801) Serie V-Range (501,651,801) Cla: INFO Reviion: E Sheet 1 of 8 Releae Date: 16.12.2015 With the introduction of CAN communication and control on the truck mounted range of Johnton Sweeper, there i now the

More information

An Approach to a Test Oracle for XML Query Testing

An Approach to a Test Oracle for XML Query Testing An Approach to a Tet Oracle for XML Query Teting Dae S. Kim-Park, Claudio de la Riva, Javier Tuya Univerity of Oviedo Computing Department Campu of Vieque, /n, 33204 (SPAIN) kim_park@li.uniovi.e, claudio@uniovi.e,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

(12) Patent Application Publication (10) Pub. No.: US 2017/ A1

(12) Patent Application Publication (10) Pub. No.: US 2017/ A1 (19) United tate (12) Patent Application Publication (10) Pub. No.: U 2017/0049243 A1 Nunn et al. U 2017.0049243A1 (43) Pub. Date: Feb. 23, 2017 (54) (71) (72) (21) (22) (63) (60) NFLATABLE AIR MATTRE

More information

Elektra Installation, Commissioning and Maintenance Manual. Document No. 667/HB/33930/000

Elektra Installation, Commissioning and Maintenance Manual. Document No. 667/HB/33930/000 Siemen Mobility, Traffic Solution Soper Lane, Poole, Doret, BH17 7ER Elektra Intallation, Commiioning and Maintenance Manual Document No. 667/HB/33930/000 THIS DOCUMENT IS ELECTRONICALLY APPROVED AND HELD

More information

Drawing Lines in 2 Dimensions

Drawing Lines in 2 Dimensions Drawing Line in 2 Dimenion Drawing a traight line (or an arc) between two end point when one i limited to dicrete pixel require a bit of thought. Conider the following line uperimpoed on a 2 dimenional

More information

Distributed Packet Processing Architecture with Reconfigurable Hardware Accelerators for 100Gbps Forwarding Performance on Virtualized Edge Router

Distributed Packet Processing Architecture with Reconfigurable Hardware Accelerators for 100Gbps Forwarding Performance on Virtualized Edge Router Ditributed Packet Proceing Architecture with Reconfigurable Hardware Accelerator for 100Gbp Forwarding Performance on Virtualized Edge Router Satohi Nihiyama, Hitohi Kaneko, and Ichiro Kudo Abtract To

More information

(12) Patent Application Publication (10) Pub. No.: US 2003/ A1

(12) Patent Application Publication (10) Pub. No.: US 2003/ A1 US 2003O196031A1 (19) United State (12) Patent Application Publication (10) Pub. No.: US 2003/0196031 A1 Chen (43) Pub. Date: Oct. 16, 2003 (54) STORAGE CONTROLLER WITH THE DISK Related U.S. Application

More information

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria DRT-301 A/D Three phase four wire DIN rail energy meter (Seven modules) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Structure Diagram 1.7 Dimensions

More information

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak SIEREK switchgear Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak SIEREK Metal-Enclosed Interrupter Switchgear Selection and pplication Guide SIEREK medium-voltage metal-enclosed interrupter

More information

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-200-KIT 200 V Bias Tee Kit Description The CVU-200-KIT Bias Tee Kit consists of three 2600-RBT-200

More information

MIRA. A Winning System for gear manufacturing INCORPORATES TYROLIT S TECHNOLOGY AND EXPERIENCE FOR

MIRA. A Winning System for gear manufacturing INCORPORATES TYROLIT S TECHNOLOGY AND EXPERIENCE FOR MIR Winning Sytem for gear manufacturing INCORPORTES TYROLIT S TECHNOLOGY ND EXPERIENCE FOR Gear grinding Bevel gear grinding Gear Honing Dreing tool TYROLIT offer a complete line of tool for the hard

More information

UBC Technical Guidelines Section Edition Primary Unit Substation Page 1 of 14

UBC Technical Guidelines Section Edition Primary Unit Substation Page 1 of 14 Page 1 of 14 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services. Refer to www.energy.ubc.ca. 1.2 Description.1 UBC requirements for Indoor and Outdoor Unit Substations. 2.0 MATERIAL

More information

PRO-1250D CT MID DIN rail three phase four wire energy meter.

PRO-1250D CT MID DIN rail three phase four wire energy meter. PRO-1250D CT MID DIN rail three phase four wire energy meter. 1.1 Safety instructions 1.2 Foreword 1.3 MID certificate 1.4 Performance criteria 1.5 Specifications 1.6 Basic errors 1.7 Description 1.8 Dimensions

More information

Magnetek Dynamic Braking Resistors

Magnetek Dynamic Braking Resistors Magnetek Dynamic Braking Resistors Motor Control Instruction Manual N49 W13650 Campbell Drive Menomonee Falls, WI 53051 Phone: 1-800-288-8178 Fax: 1-800-298-3503 SERVICE: 1-866-MAG-SERV (1-866-624-7378)

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

Analyzing Hydra Historical Statistics Part 2

Analyzing Hydra Historical Statistics Part 2 Analyzing Hydra Hitorical Statitic Part Fabio Maimo Ottaviani EPV Technologie White paper 5 hnode HSM Hitorical Record The hnode i the hierarchical data torage management node and ha to perform all the

More information

Laboratory Exercise 6

Laboratory Exercise 6 Laboratory Exercie 6 Adder, Subtractor, and Multiplier The purpoe of thi exercie i to examine arithmetic circuit that add, ubtract, and multiply number. Each circuit will be decribed in Verilog and implemented

More information

HV-CS kv Edge Mount Triaxial Jack

HV-CS kv Edge Mount Triaxial Jack Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley HV-CS-1589 3 kv Edge Mount Triaxial Jack Installation Information Description The Keithley Instruments

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Stress-Blended Eddy Simulation (SBES) - A new Paradigm in hybrid RANS-LES Modeling

Stress-Blended Eddy Simulation (SBES) - A new Paradigm in hybrid RANS-LES Modeling Stre-Blended Eddy Simulation (SBES) - A new Paradigm in hybrid RANS-LES Modeling Menter F.R. ANSYS Germany GmbH Introduction It i oberved in many CFD imulation that RANS model how inherent technology limitation

More information

Primary Injection Test Procedure

Primary Injection Test Procedure S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Primary Injection Test Procedure Table of Contents Section Page Section Page Introduction Qualified Persons....

More information

VisoVac padmount fault interrupter

VisoVac padmount fault interrupter Network Protector Catalog Data CA024003EN New Issue VisoVac padmount fault interrupter General The medium voltage padmount vacuum fault interrupter from Eaton delivers economical, reliable and flexible

More information

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-3K-KIT 3 kv Bias Tee Kit Description The CVU-3K-KIT Bias Tee Kit consists of three bias tees for

More information

ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK

ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK ES05 Analyi and Deign of Engineering Sytem: Lab : An Introductory Tutorial: Getting Started with SIMULINK What i SIMULINK? SIMULINK i a oftware package for modeling, imulating, and analyzing dynamic ytem.

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP1120 Rev. 1 Page: 1 of 24 CERTIFIED TEST REPORT Cooper Power Systems 15 kv Class 600 Amp CLĒĒR TM LOADBREAK SEPARABLE CONNECTOR SYSTEM REV. 1 DATE September 1, 2011 ORIGINAL REPORT DATE: July

More information

Model 7705 Control Module

Model 7705 Control Module www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

Aspects of Formal and Graphical Design of a Bus System

Aspects of Formal and Graphical Design of a Bus System Apect of Formal and Graphical Deign of a Bu Sytem Tiberiu Seceleanu Univerity of Turku, Dpt. of Information Technology Turku, Finland tiberiu.eceleanu@utu.fi Tomi Weterlund Turku Centre for Computer Science

More information

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN Highlights & Features Full corrosion resistant Aluminium chassis Suitable for 24V system up to 40A Built-in diagnostic monitoring for DC OK, Discharge and Battery Fail by relay contacts LED indicator for

More information

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv) Outdo Distribution (14.4 kv through 34.5 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution switching system shall confm to the following specification. 1.02 The loadbreak

More information

A Basic Prototype for Enterprise Level Project Management

A Basic Prototype for Enterprise Level Project Management A Baic Prototype for Enterprie Level Project Management Saurabh Malgaonkar, Abhay Kolhe Computer Engineering Department, Mukeh Patel School of Technology Management & Engineering, NMIMS Univerity, Mumbai,

More information

Type VR Electrically Operated Ground and Test Device

Type VR Electrically Operated Ground and Test Device Type VR Electrically Operated Ground and Test Device For Use with Masterclad Switchgear 4.76 kv 15 kv, 1200, 2000, 3000, 4000 A Up to 63 ka Short Circuit Rating Class 6055 Instruction Bulletin 6055-37

More information

XTM1250SA DIN rail three phase four wire LCD display energy meter

XTM1250SA DIN rail three phase four wire LCD display energy meter XTM1250SA DIN rail three phase four wire LCD display energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Intrinsic errors 1.6 Description 1.7 Dimensions 1.8

More information

Line Impedance Stabilization Network (LISN)

Line Impedance Stabilization Network (LISN) Model 3816/2 Line Impedance Stabilization Network (LISN) User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

FPGA Implementation of Closed Loop Control of Pan Tilt Mechanism

FPGA Implementation of Closed Loop Control of Pan Tilt Mechanism IJCTA, 9(39), 206, pp. 295-302 International Science Pre Cloed Loop Control of Soft Switched Forward Converter Uing Intelligent Controller 295 FPGA Implementation of Cloed Loop Control of Pan Tilt Mechanim

More information

PCT2000. User Manual. Precision current transducer 2000 A

PCT2000. User Manual. Precision current transducer 2000 A PCT2000 User Manual PCT2000 Precision current transducer 2000 A User Manual Status: November 6, 2018 Copyright 2018 ZES ZIMMER Electronic Systems GmbH Pfeiffstraße 12 61440 Oberursel (Taunus), Germany

More information

Dynamically Reconfigurable Neuron Architecture for the Implementation of Self- Organizing Learning Array

Dynamically Reconfigurable Neuron Architecture for the Implementation of Self- Organizing Learning Array Dynamically Reconfigurable Neuron Architecture for the Implementation of Self- Organizing Learning Array Januz A. Starzyk,Yongtao Guo, and Zhineng Zhu School of Electrical Engineering & Computer Science

More information

Integration of Digital Test Tools to the Internet-Based Environment MOSCITO

Integration of Digital Test Tools to the Internet-Based Environment MOSCITO Integration of Digital Tet Tool to the Internet-Baed Environment MOSCITO Abtract Current paper decribe a new environment MOSCITO for providing acce to tool over the internet. The environment i built according

More information

Laboratory Exercise 2

Laboratory Exercise 2 Laoratory Exercie Numer and Diplay Thi i an exercie in deigning cominational circuit that can perform inary-to-decimal numer converion and inary-coded-decimal (BCD) addition. Part I We wih to diplay on

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5 PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5 1 Safety instructions...3 2 Foreword...4 3 CE certificates...5 4 MID certificate...7 5 Performance criteria...8 6 Specifications...8

More information