1 Towards the Green Data Centre Lex Coors Vice President Data Center Technology & Engineering Group

2 DC Emissions: We Have Lift-Off! Data Centre Greenhouse Gas Emissions are projected to quadruple by 2020 We will overtake the airline industry in emissions in the next 5-10 years Brace yourselves for impact! Data centres Airlines Shipyards Steel plants Carbon dioxide emissions as percentage of world total industries, 2008 [Source:IDC U.S. and Worldwide Server Installed Base Forecast; McKinsey analysis]

3 1. Moving Parts

4 Power v Energy Power Overhead (fixed) Total Energy Usage (variable)

5 Calculating PUE A. Total Energy Usage B. IT Energy Usage A B = PUE

6 How to Recognise a Green Data Centre? Inefficient DC PUE > 2 Legacy equipment No measurement Inefficient components Overspecified by builders Generally in-house Energy-conscious DC PUE Lean design Established measurement data Demonstrable year-onyear improvements Dedicated provider Typical Interxion DC Ideal DC PUE 1 1 = IT load only Not physically possible as any part of infrastructure will involve some loss

7 2. Green Steps

8 Role of the Green Data Centre Provider Interxion approach: active focus in 3 areas: 1. External efficiency focus: industry efficiency standards 3. Customer efficiency focus: proactive support and advice to improve IT efficiency 2. Internal efficiency focus: A.Design B.Operations

9 Customer Focus: Support & Advice 1. Hands-on expert support in energy efficiency implementation efforts 2. Best practice customer installation checklist (efficiency gain 3-5%) 3. Customised hot/cold aisle designs 4. Senior advice and tools in the following areas: Measurement and analysis Implementing the latest efficiency ratings Developing and implementing first phase action plans Integrating figures and ratings with customer CSR

10 Customer Focus: Recommended Steps Step 1. Eliminate Comatose servers 2. Virtualize 3. Upgrade older equipment 4. Reduce demand for new servers 5. Introduce greener and more powerefficient servers and enable power savings features Efficiency Gain 10 25% 25-30% 10 20% 10 20% 10 20% Total 65% + Source: McKinsey and Up Time Insitute 2008

11 3. Internal DC Focus: Design & Operations

12 Good Design = Less Capex For example: On 800 m 2 kva/m 2 Capex saving Tier IV Uptime vs Tier X N+N UPS s, N+1 Generator and N+1 Cooling system : 2 UPS systems of k each = 500 k/ 800 m2 = 625/m 2 2 generators of 3, k = 1.5 MIO/ 800 m2 = 1,875/m 2 1 generator 150 k = 150k/ 800 m2 = 188/ m 2 Saving on cooling: 2 UPS * 4% loss = 64 kw ( 25K for DX system) or 31/m 2 Taken together this amounts to a saving vs. Tier IV as per Uptime doc of 31+ 2, % = 3,535/ m 2 OR 3,535 * 800 m 2 = 2,828,000 less CAPEX

13 Day 1 load: 0.7 kva/m2 * 800 m2 = 560 kva UPS load * 1.8 power ratio = 1,008 kva transformer load. In this case we could: Cash Flow Management: Modular Tier X Design a) Use for the final design 4 smaller generators (3 + 1 redundant) from 1,000 kva but we would start with 2, thus saving: 2 * 750 k (3,150 kva generators) 2 * 150 k (1,000 kva generators) = 1,200,000 saving b) Use the APC-MGE Symmetra MW 1,600 kva/kw system (instead of the smaller 800 kva/kw system) starting with the final 2 frames with only 3 power modules of 200 kw per UPS system installed, thus saving: 4 * 250 k - 2 * 350 k including 600 kva/kw of UPS modules = 300,000 saving c) Start with 2 chillers of 750 kw instead of 8 chillers of 750 kw Saving at Day 1 of: 8 * 125 k 2 * 125 k = 750,000 saving d) Assuming 100 kw/ CRAC, start with 8 CRAC units instead of 16 CRAC units Saving here at day 1 will be 16 * 20 k - 8 * 20 K = 160,000 saving Total CAPEX savings day 1: 2,460,000/ 800 m 2 = 3,075/ m 2 With substantial OPEX savings for year 1

14 The Key to Efficient Operations You have to know the Power Ratio (DCi-PO) to improve the Energy ratio (PUE)

15 Internal Focus: Operational Measures Interxion 6 year PUE Gains Industry Norm Acceptable Exceptional 1 5

16 4. Industry Focus: Measure it to Manage it

17 Industry Standards for Tomorrow Getting around the table to agree efficiency metrics and a workable rating system

18 Industry Focus: The Role of Vendors The Vendor industry should provide standard meters on all equipment to measure Energy Usage v Productivity. Transformers: Energy in v Energy out UPS: Energy in v Energy out (this will allow us to measure efficiencies as a % of load) Switchgear and cables: Getting a better understanding of properties of materials and impact of impurities on efficiency CRAC units energy in v kw and kwh cold out (CRAC unit capacity should be shown at chilled water supply 9 C, 12 C, 15 C) Chillers: Energy in Energy out (Capacity shown at above temps) So finally an open invitation to Vendors: don t drive the data centre industry, let the data centre industry drive you. Let s work together to improve the available systems.

19 Conclusions Green Data Centres are real; just ask us! But emissions (and power costs) are rising fast, so we need to do more now We must work together, particularly in measurement Data Centre providers should give leadership. In three areas: Industry standards and ratings that work Data Centre design and operational efficiency steps Support for all customer IT efficiency improvements

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

DC Energy, Efficiency Challenges

DC Energy, Efficiency Challenges DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC) How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity

More information

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm

More information

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015)

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015) 30 th September 2015 Glenn Conlon Always Right Size Modular Data Centres Traditional DC Build: Image courtesy of ENP Traditional DC: IRO 20 million + @ T2/3 Image courtesy of ENP DC Halls x 2, 500 Cabinets

More information

Meeting the Energy Efficiency and Financial Challenges in IT. Liam Newcombe BCS Data Centre Specialist Group Secretary

Meeting the Energy Efficiency and Financial Challenges in IT. Liam Newcombe BCS Data Centre Specialist Group Secretary Meeting the Energy Efficiency and Financial Challenges in IT Liam Newcombe BCS Data Centre Specialist Group Secretary Meeting the Energy and Financial Challenges in IT Recognising the Problem Recognising

More information

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.

Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009 The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

Prefabricated Data Center Solutions: Coming of Age

Prefabricated Data Center Solutions: Coming of Age Prefabricated Data Center Solutions: Coming of Age Steven Carlini - Global Data Center Marketing Director April 2014 Schneider Electric 1 Schneider Electric 2 Your ability to compete relies on the design,

More information

Newave s approach for protecting mission critical application

Newave s approach for protecting mission critical application ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment

More information

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016 STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. COVER FEATURE Cloud control Such is the growth in data centres globally

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Sustainable Data Centre

Sustainable Data Centre white paper Sustainable Data Centre Tackling the Ever-rising Data Centre Energy Costs Why Only Do Half the Job? By Kari Baden Managing Director, Dimension Data Advanced Infrastructure A whitepaper on tackling

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by: Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

Integralna rešenja Infrastrukture Data Centra

Integralna rešenja Infrastrukture Data Centra 1 2 Integralna rešenja Infrastrukture Data Centra Jason Dodier, Solutions Business Development Manager - Global Sales (Schneider Electric) Overview of Prefabricated DC's market Prefab - needs to be satisfied

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Making the impossible data center a reality.

Making the impossible data center a reality. United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental

More information

Nominee: Riello UPS with The Rosebery Group

Nominee: Riello UPS with The Rosebery Group Nominee: Riello UPS with The Rosebery Group Nomination title: Cutting Costs & Carbon Emissions With Modular UPS What was the driving force behind the project? Riello UPS is one of the world s leading manufacturers

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Investor day. November 17, IT business Laurent Vernerey Executive Vice President

Investor day. November 17, IT business Laurent Vernerey Executive Vice President Investor day November 17, 2010 IT business Laurent Vernerey Executive Vice President IT business strategic domain Centralized generation Residential Residential Industries Non Residential Transmission

More information

STATE OF THE ART DATA CENTRES

STATE OF THE ART DATA CENTRES DATA CENTRES STATE OF THE ART DATA CENTRES In recent years, Data Centres have become increasingly important to businesses of all sizes as a higher volume of customers choose to host their servers with

More information

Datacenter Cooling. DC Cooling Efficiency and Project experience. Osman Uzuner. Vakıfbank Central Systems Management Datacenter Operations

Datacenter Cooling. DC Cooling Efficiency and Project experience. Osman Uzuner. Vakıfbank Central Systems Management Datacenter Operations Datacenter Cooling DC Cooling Efficiency and Project experience Osman Uzuner Vakıfbank Central Systems Management Datacenter Operations Agenda Agenda and Intro About Vakıfbank DC Energy Consumption breakdown

More information

Customizable Colocation: Building for the Future

Customizable Colocation: Building for the Future Customizable Colocation: Building for the Future IronGate Data Centers meets the exact needs of customers with flexible Data Center Infrastructure solutions from Schneider Electric IronGate Data Centers

More information

Case Study Leicester City Council

Case Study Leicester City Council Data Centre Solutions...energy efficient by design Case Study Leicester City Council Leicester City Council Deploys New Sub 1.1 PUE3 Data Centre Infrastructure. Designed & Installed by Workspace Technology

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Data Center. Tai Po Data Center

Data Center. Tai Po Data Center Data Center Tai Po Data Center TAI PO DATA CENTER Nexcenter The Global Data Center Vision NTT Communications offers data center services at hundreds of locations worldwide under the brand name Nexcenter.

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

Cannon T4 Modular Data Center (MDC)

Cannon T4 Modular Data Center (MDC) SOLUTIONS Cannon T4 Modular Data Center (MDC) Cannon T4 Modular Data Centers are part of Cannon T4 Data Center Solutions Cannon T4 Data Center Solutions Overview T4 Data Centers T4 Mini Data Centers T4

More information

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary.

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary. How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter Summary Diesel Rotary UPS (DRUPS) systems are best in class regarding energy

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

Rack Colocation Hosting. Data Centre Solutions Expertly Engineered

Rack Colocation Hosting.   Data Centre Solutions Expertly Engineered Rack Colocation Hosting www.workspace-technology.com Data Centre Solutions Expertly Engineered We are committed to ensuring the very best data centre environment for your business Rack Colocation Hosting

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

APC by Schneider Electric Elite Data Centre Partner

APC by Schneider Electric Elite Data Centre Partner Data Centre Solutions...energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

Data Centre Design and Operational Best Practices

Data Centre Design and Operational Best Practices Data Centre Design and Operational Best Practices Ed Ansett Managing Partner i 3 Solutions Group ABB 5 th July 2013 Causes of Failure in Data Centres FAILURE WHO? WHAT? System Design Consulting Engineer

More information

DATA CENTRE & COLOCATION

DATA CENTRE & COLOCATION DATA CENTRE & COLOCATION RISING DEMAND FOR HOSTED SERVICES When it comes to hosted IT infrastructure, organisations are looking for highly resilient, highly available and highly scalable facilities at

More information

1200 West 7th Street, Los Angeles, CA Smart.

1200 West 7th Street, Los Angeles, CA Smart. Overview 1200 West 7th Street, Los Angeles, CA 90017 West 7 Center is conveniently located at 1200 West 7th Street in downtown Los Angeles near the 10 and 110 freeway. This tier III datacenter facility

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. 22 ECOLIBRIUM OCTOBER 2018 The hunter and the prey A clever modernisation

More information

Reference Design Quicktour Design Summary

Reference Design Quicktour Design Summary Quicktour Design Summary Outdoor Heat Rejection Mixed Use or Purpose Built Data Center Facility Indoor/Outdoor Power Generation Mechanical Room Electrical Room Data Center Whitespace Reclaimed Whitespace

More information

Data Centre Solutions. Data Centre Solutions Expertly Engineered

Data Centre Solutions.   Data Centre Solutions Expertly Engineered Data Centre Solutions www.workspace-technology.com Data Centre Solutions Expertly Engineered We will expertly deliver your data centre using our world-class skills and capabilities. Data Centre Solutions

More information

Cloud environment. dr inż. Piotr Boryło , Kraków

Cloud environment. dr inż. Piotr Boryło , Kraków Cloud environment dr inż. Piotr Boryło 7.03.2018, Kraków Agenda Cloud fundamentals Greening the cloud Intercloud Fog/Edge Computing Network Function Virtualization SDN for clouds Testing the cloud vs cloud

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

White Paper - Infrastructure in an energy-efficient data centre

White Paper - Infrastructure in an energy-efficient data centre White Paper - Infrastructure in an energy-efficient data centre Verena Schwalfenberg Dipl.-Ing. Markus Schmidt Copyright 2008 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn

More information

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

Data center redundancy. Air traffic High-speed pipes. Training Design. Costs. Guy with a wrench. Terrorism

Data center redundancy. Air traffic High-speed pipes. Training Design. Costs. Guy with a wrench. Terrorism Data center redundancy Costs Training Design Air traffic High-speed High speed pipes Guy with a wrench Terrorism Fire Communications Backup and Network power Power di t ib ti distribution Security Governance

More information

Liebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology

Liebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology Liebert APM from 30 to 300 kw The Compact Row Based UPS With FlexPower Technology LIEBERT APM from 30 to 300 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala Data Centre Energy & Cost Efficiency Simulation Software Zahl Limbuwala BCS Data Centre Simulator Overview of Tools Structure of the BCS Simulator Input Data Sample Output Development Path Overview of

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

The Evolving Data Center

The Evolving Data Center The Evolving Data Center Dominic Loh Product Manager, Power Quality, APAC Data Centers are enabling global growth Proliferation of mobile computing Digitalization of everything Big Data 2 Evolution of

More information

Highly Efficient Power Protection for High Density Computing Applications

Highly Efficient Power Protection for High Density Computing Applications Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density

More information

CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES

CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES DATA CENTER NEEDS A MINUTE IN THE LIFE OF INTERNET Evolving technology has created the necessity for ever greater exchange of data, increasing

More information

How High-Density Colocation and Enhanced Visibility Improve Business Performance

How High-Density Colocation and Enhanced Visibility Improve Business Performance How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications

More information

SIX Trends in our World

SIX Trends in our World Data Center Infrastructure for Cloud and Energy Efficiency SIX Trends in our World Connectivity Simplicity StruxureWare TM for data centers TuanAnh Nguyen, Solution Engineer Manager, Vietnam Schneider

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

The Green Advantage of 10G Optical Fiber

The Green Advantage of 10G Optical Fiber The Green Advantage of 10G Optical Fiber What is the definition of Green? Green. The word invokes natural images of deep forests, sprawling oak trees and financial images of dollar bills. The topic of

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Datacentre Milton Keynes Hall C Data sheet

Datacentre Milton Keynes Hall C Data sheet Datacentre Milton Keynes Hall C Data sheet Data sheet Datacentre Milton Keynes Hall C Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant

More information

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design Data Centers & The Environment The State of Global Environmental Sustainability in Data Center Design December 2018 Today s Data Centers Data centers have a huge impact on the world we live in. Today they

More information

EXTENDING THE LIFECYCLE OF AGEING DATA CENTRES:

EXTENDING THE LIFECYCLE OF AGEING DATA CENTRES: EXTENDING THE LIFECYCLE OF AGEING DATA CENTRES: HOW AND WHAT SHOULD DC s DO FOR RETROFITS Jonathan Price 4 th August 2015 KEY DRIVERS FOR UPGRADING A DATA CENTRE Capacity Resilience Efficiency Lifecycle

More information

CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS

CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical

More information

Rack Centric - High Voltage Distribution

Rack Centric - High Voltage Distribution Rack Centric - High Voltage Distribution Randy Malik Senior Technical Staff Member Research Triangle Park Raleigh, North Carolina Email: Rmalik@us.ibm.com Data Center Application Typical Data Center Energy

More information

Increasing Data Center Efficiency through Metering and Monitoring Power Usage

Increasing Data Center Efficiency through Metering and Monitoring Power Usage White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

NON ISO Modular Datacenter

NON ISO Modular Datacenter NON ISO Modular Datacenter NON ISO MODULAR DATACENTER Benefits NON ISO Modular Data Center is a purpose-engineered and fully > Differed Capex. integrated datacenter system designed to offer organizations

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Rolf Brink Founder/CEO

Rolf Brink Founder/CEO Rolf Brink Founder/CEO +31 88 96 000 00 www.asperitas.com COPYRIGHT 2017 BY ASPERITAS Asperitas, Robertus Nurksweg 5, 2033AA Haarlem, The Netherlands Information in this document can be freely used and

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Topics Covered in this Presentation

Topics Covered in this Presentation DATA CENTER DESIGN CONSIDERATIONS AND TRENDS MUSIC CITY POWER QUALITY GROUP May 5, 2009 Daniel L. Ellis - Eaton 2008 Eaton Corporation. All rights reserved. Topics Covered in this Presentation Economic

More information

ims - Modular DCIM Solution

ims - Modular DCIM Solution ims - Modular DCIM Solution Data Centre Infrastructure Management System Get in touch! Andy Banks Power Management Director m. +44 (0) 7920 136987 t. +44 (0) 1539 720161 e. a.banks@mardix.co.uk Scott Findlater

More information

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct The European Programme for Energy Efficiency in Data Centres: The Code of Conduct Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 Why Data Centres? Continuing demand for

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

HVAC system design to operational efficiency: Strategies and Metrics for improved Total Cost of Ownership

HVAC system design to operational efficiency: Strategies and Metrics for improved Total Cost of Ownership HVA system design to operational efficiency: Strategies and Metrics for improved otal ost of Ownership Michel van Roozendaal Vice President Services and ontracting limate Solutions, urope, Middle ast Africa

More information

Green IT Project: The Business Case

Green IT Project: The Business Case Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information